George Hannah,
  Product Development Director

Better by design, exploring containment
 options to optimise every Cooling kW
Why Airedale?


  Global provider of efficient cooling solutions


   Almost 40 years experience in IT industry


Largest UK manufacturer of IT cooling solutions


      A pioneer in free-cooling technology


    An industry leader in rack level cooling
Who Are We?
Who Are We?
What Do We Do?




50,000 applications since 1974   2011   1,200 last year
Business Issues


    Footprint
                               Uptime
   And Density




Operational
                                 Efficiency
  Costs



                     Capital
                      Costs
Types of Containment
The 2nd Law of Thermodynamics

“The second law states that spontaneous natural processes
   increase entropy overall, or in another formulation that
    heat can spontaneously be conducted or radiated only
       from a higher-temperature region to a lower-
     temperature region, but not the other way around.”


             TH                       TC


                         TW
Open Aisle (500kW Facility)

Temperature (oC)
            45

            40

            35

            30

            25
 Return

            20

            15
 Supply
            10
                      Total heat load            5 kW per Rack
            5
                      Total number of cabinets       100
Cold Aisle Containment (500kW Facility)

Temperature (oC)
            45

            40

            35

            30

            25

            20

            15

            10
                      Total heat load             5 kW per Rack
            5
                      Total number of cabinets        100
Hot Aisle Containment (500kW Facility)

Temperature (oC)
            45

            40

            35

            30

            25                                   Additional IT
                                                 opportunity =
            20                                     420kW
            15

            10
                      Total heat load                10 kW per Rack
            5
                      Total number of cabinets              50
InRak Hot Aisle Containment (500kW Facility)

Temperature (oC)
            45

            40

            35

            30

            25
                                               Additional
            20
                                            IT opportunity =
            15                                  420kW
            10
                      Total heat load              9.8 kW per Rack
            5
                      Total number of cabinets           51
OnRak Compact Hot Aisle (500kW Facility)

Temperature (oC)
            45

            40

            35                              Additional
                                          IT opportunity
            30
                                            =1880kW
            25

            20

            15

            10
                      Total heat load              20 kW per Rack
            5
                      Total number of cabinets             25
ECHO - Compact Hot Aisle (500kW Facility)

Temperature (oC)
            45

            40

            35

            30                           Additional IT opportunity =
                                                   894kW
            25

            20

            15

            10
                      Total heat load                 20 kW per Rack
            5
                      Total number of cabinets             25
Supply and Return Temperatures

                             Temperature (oC)
                    Supply                      Return
 OnRak                                   45

                                         40
  ECHO
                                         35

  InRak                                  30

                                         25
Hot Aisle                                20

                                         15
Cold Aisle
                                         10

Open Aisle                               5
Supply and Return Temperatures


Temperature 0C
                                           Return Air
   45
   40
   35
   30
   25
   20                                      Supply Air
   15
   10
    5
    0
                  CRAC
         Open     Cold     Hot
                  Cold             InRak   OnRak    ECHO
         Aisle    Aisle    Aisle
                  Aisle
What is Free Cooling?




Indirect - AIR       Direct - AIR   Indirect - WATER


                            IN

                         OUT
Free Cooling


                                Open Aisle

    Free cooling              Concurrent Mode        Mechanical

Hours per year
  600
                        1%



  300
                        48%       51%


        -6 -2    6     2 10 14 18 22 26         30
                     Ambient Temperature (ºC)
Free Cooling


                                Cold Aisle

    Free cooling             Concurrent Mode         Mechanical

Hours per year
  600




  300


         6%               62%        32%

        -6 -2    6     2 10 14 18 22 26         30
                     Ambient Temperature (ºC)
Free Cooling


                                 Hot Aisle

    Free cooling             Concurrent Mode          Mechanical

Hours per year
  600




  300
          25%                 67%              18%


        -6 -2    6     2 10 14 18 22 26          30
                     Ambient Temperature (ºC)
Free Cooling


                                    InRak

    Free cooling             Concurrent Mode          Mechanical

Hours per year
  600




  300
          25%                 67%              18%


        -6 -2    6     2 10 14 18 22 26          30
                     Ambient Temperature (ºC)
Free Cooling


                                    OnRak

    Free cooling             Concurrent Mode          Mechanical

Hours per year
  600




  300
          20%                 69%              11%


        -6 -2    6     2 10 14 18 22 26          30
                     Ambient Temperature (ºC)
Free Cooling


                                   ECHO

    Free cooling             Concurrent Mode         Mechanical

Hours per year
  600
                                    1%


  300
                             89%          10%


        -6 -2    6     2 10 14 18 22 26         30
                     Ambient Temperature (ºC)
Free Cooling




  Free cooling



                      Open Aisle   Cold Aisle   Hot Aisle
Concurrent Mode




  Mechanical
                         InRak      OnRak        ECHO
Technical Matrix




                               System      Space claim   Space claim
             Free-cooling
                              efficiency    (cooling         (IT
              opportunity   (Annualised    equipment     equipment
                 (%)            PUE)          (m²)          (m²)
Open Aisle      49%             1.45           14            60
Cold Aisle      68%             1.38           14            60
Hot Aisle       92%             1.30           14            30
  InRak         92%             1.29           12            30
 OnRak          89%             1.26           3             15
  ECHO          99%             1.24           14            15
Commercial Matrix


                                                          Month



                              Operating       Total     Payback
             Capital costs      costs       operating    period
                             (annualised)   £/kW p.a.   (months)

Open Aisle    £139,996        £291,402        £99          13
Cold Aisle    £143,878        £125,869        £84          14
Hot Aisle     £124,383         £95,585        £58          16
  InRak       £190,575         £60,350        £56          14
 OnRak        £186,620         £57,827        £33          15
  ECHO        £192,208         £42,992        £27          15
Case Study: Open Aisle Containment




                               System      Space claim   Space claim
             Free-cooling
                              efficiency    (cooling         (IT
              opportunity   (Annualised    equipment     equipment
                 (%)            PUE)          (m²)          (m²)
Open Aisle      49%             1.45           14            60
Cold Aisle      68% PUE         1.38           14            60
                  2.0
Hot Aisle       92%             1.30           14            30
  InRak         92%             1.29           12            30
                  1.5
 OnRak          89%             1.26           3             15
  ECHO          99%0            1.24           14            15
Case Study: Open Aisle Containment




  The chillers give us 1500kW n + 1 cooling plus a
stunning reduction in electricity consumption i.e.
  2.5 times cooling capacity for 100 – 150kW less
             power consumption per day.




                                  Mark Ford
                        Data Centre Manager
Case Study: Cold Aisle Containment




                               System      Space claim   Space claim
             Free-cooling
                              efficiency    (cooling         (IT
              opportunity   (Annualised    equipment     equipment
                 (%)            PUE)          (m²)          (m²)
Open Aisle      49%             1.45           14            60
Cold Aisle      68%             1.38           14            60
Hot Aisle       92%             1.30           14            30
  InRak         92%             1.29           12            30
 OnRak          89%             1.26           3             15
  ECHO          99%             1.24           14            15
Case Study: Hot Aisle Containment




                               System           Space claim   Space claim
             Free-cooling
                              efficiency         (cooling         (IT
              opportunity   (Annualised         equipment     equipment
                 (%)            PUE)               (m²)          (m²)
Open Aisle      49%             1.45                   14         60
Cold Aisle      68%             1.38                   14         60
Hot Aisle       92%             1.30                   14         30
  InRak         92%             1.29                   12         30
                                           ---------
                                           ---------
 OnRak          89%             1.26       ------      3          15
                                            95%
  ECHO          99%             1.24                   14         15
Case Study: Hot Aisle Containment




Airedale provides us with a fully integrated cooling
  solution designed for maximum efficiency and
critical redundancy…Our carbon neutral status helps
     our clients take huge steps towards their own
      environmental goals and carbon reduction
                      commitments.



                                 Rob Garbutt
                       Chief Executive Officer
Case Study: InRak Hot Aisle Containment




                               System      Space claim   Space claim
             Free-cooling
                              efficiency    (cooling         (IT
              opportunity   (Annualised    equipment     equipment
                 (%)            PUE)          (m²)          (m²)
Open Aisle      49%             1.45           14            60
Cold Aisle      Guaranteed PUE 1.29
                68%        1.38                14            60
Hot Aisle       92%             1.30           14            30
  InRak         92%             1.29           12            30
 OnRak          89%             1.26           3             15
  ECHO          99%             1.24           14            15
Case Study: InRak Hot Aisle Containment




The InRak is perfectly designed…the units are very
clever; they ‘talk’ to each other and maintain pressure
   in the room. ACIS gives us 24/7 control of the
            operation and peace of mind.




                                Mike Marchant
                          Data Centre Manager
Case Study: OnRak Compact Hot Aisle




                               System      Space claim   Space claim
             Free-cooling
                              efficiency    (cooling         (IT
              opportunity   (Annualised    equipment     equipment
                 (%)            PUE)          (m²)          (m²)
Open Aisle      49%             1.45           14            60
Cold Aisle      68%             1.38           14            60
                 35% savings vs. standard DX
Hot Aisle       92%             1.30           14            30
  InRak         92%             1.29           12            30
 OnRak          89%             1.26           3             15
  ECHO          99%             1.24           14            15
Case Study: OnRak Compact Hot Aisle




    Our HPC facility at Leeds is growing …by meeting
    our space constraints and slotting into our existing
    cooling loop, the OnRak units from Airedale have
     saved us space in an already densely packed
                       environment



                                Dr Jon Summers
Senior Lecturer, School of Mechanical Engineering
Increased IT Opportunity

                                  Cooling          Additional
Space   m2      Rack (m2)
                               Equipment (m2)      Space (m2)

100
                            30m²     32m²       56m²    45m²
 80

 60

 40

 20

 0
        Open      Cold      Hot
                                     InRak      OnRak   ECHO
        Aisle     Aisle     Aisle
3 Year Lifecycle Cost

     £               Total Capital       Operating
                                           Costs           PUE
(millions)               Cost          (over 3 years)

  1.2
             1.45        1.38        1.30      1.29      1.26    1.24
  1.0

  0.8

   0.6

   0.4

   0.2

     0
             Open        Cold        Hot
                                              InRak     OnRak    ECHO
             Aisle       Aisle       Aisle
Business Issues


    Footprint
   And Density                 Uptime




Operational
                                 Efficiency
  Costs



                     Capital
                      Costs
Contact Us


    For more information on any of our products please visit:


            www.airedale.com
        Or alternatively, call us on + 44 (0)113 239 1000

         Connect with us on YouTube, LinkedIn or Flickr:

               www.youtube.com/airedalecooling

www.linkedin.com/company/airedale-international-air-conditioning-
               ltd?trk=hb_tab_compy_id_110826

         www.flickr.com/photos/airedale-air-conditioning/

More Related Content

What's hot

10 ta data sheet - flypartsguy.com - 8.2018
10 ta   data sheet - flypartsguy.com - 8.201810 ta   data sheet - flypartsguy.com - 8.2018
10 ta data sheet - flypartsguy.com - 8.2018FrankEasel
 
Original Opto TLP185GB TLP185G TLP185 P185 185 SOP-4 New
Original Opto TLP185GB TLP185G TLP185 P185 185 SOP-4 NewOriginal Opto TLP185GB TLP185G TLP185 P185 185 SOP-4 New
Original Opto TLP185GB TLP185G TLP185 P185 185 SOP-4 NewAUTHELECTRONIC
 
Original Transistor NPN BD139 1.5A 80V TO-126 New
Original Transistor NPN BD139 1.5A 80V TO-126 NewOriginal Transistor NPN BD139 1.5A 80V TO-126 New
Original Transistor NPN BD139 1.5A 80V TO-126 NewAUTHELECTRONIC
 
Fairchild semiconductor hgtg30n60a4d 320413
Fairchild semiconductor hgtg30n60a4d 320413Fairchild semiconductor hgtg30n60a4d 320413
Fairchild semiconductor hgtg30n60a4d 320413ask0122
 
Data Sheet LM7805
Data Sheet LM7805Data Sheet LM7805
Data Sheet LM7805arwicaksono
 
Original N-CHANNEL IGBT IRGS4B60KD1TRRP GS4B60KD1 600V 7.6A TO-263-3 New IR
Original N-CHANNEL IGBT IRGS4B60KD1TRRP GS4B60KD1 600V 7.6A TO-263-3 New IROriginal N-CHANNEL IGBT IRGS4B60KD1TRRP GS4B60KD1 600V 7.6A TO-263-3 New IR
Original N-CHANNEL IGBT IRGS4B60KD1TRRP GS4B60KD1 600V 7.6A TO-263-3 New IRAUTHELECTRONIC
 

What's hot (7)

10 ta data sheet - flypartsguy.com - 8.2018
10 ta   data sheet - flypartsguy.com - 8.201810 ta   data sheet - flypartsguy.com - 8.2018
10 ta data sheet - flypartsguy.com - 8.2018
 
CHP Proposal
CHP ProposalCHP Proposal
CHP Proposal
 
Original Opto TLP185GB TLP185G TLP185 P185 185 SOP-4 New
Original Opto TLP185GB TLP185G TLP185 P185 185 SOP-4 NewOriginal Opto TLP185GB TLP185G TLP185 P185 185 SOP-4 New
Original Opto TLP185GB TLP185G TLP185 P185 185 SOP-4 New
 
Original Transistor NPN BD139 1.5A 80V TO-126 New
Original Transistor NPN BD139 1.5A 80V TO-126 NewOriginal Transistor NPN BD139 1.5A 80V TO-126 New
Original Transistor NPN BD139 1.5A 80V TO-126 New
 
Fairchild semiconductor hgtg30n60a4d 320413
Fairchild semiconductor hgtg30n60a4d 320413Fairchild semiconductor hgtg30n60a4d 320413
Fairchild semiconductor hgtg30n60a4d 320413
 
Data Sheet LM7805
Data Sheet LM7805Data Sheet LM7805
Data Sheet LM7805
 
Original N-CHANNEL IGBT IRGS4B60KD1TRRP GS4B60KD1 600V 7.6A TO-263-3 New IR
Original N-CHANNEL IGBT IRGS4B60KD1TRRP GS4B60KD1 600V 7.6A TO-263-3 New IROriginal N-CHANNEL IGBT IRGS4B60KD1TRRP GS4B60KD1 600V 7.6A TO-263-3 New IR
Original N-CHANNEL IGBT IRGS4B60KD1TRRP GS4B60KD1 600V 7.6A TO-263-3 New IR
 

Similar to Better by design exploring containment options to optimise every cooling kW - Airedale International Air Conditioning Ltd

Cold start of a 5.5MVA offshore transformer
Cold start of a 5.5MVA offshore transformerCold start of a 5.5MVA offshore transformer
Cold start of a 5.5MVA offshore transformerPieter Jan Jordaens
 
Modelling of a cooling tower in EES
Modelling of a cooling tower in EESModelling of a cooling tower in EES
Modelling of a cooling tower in EESShiyas Basheer
 
Energy study Fan Coil Units versus active chilled beams
Energy study   Fan Coil Units versus active chilled beamsEnergy study   Fan Coil Units versus active chilled beams
Energy study Fan Coil Units versus active chilled beamsMick Holland
 
Me2202 engineering thermodynamics uq - may june 2014
Me2202 engineering thermodynamics   uq - may june 2014Me2202 engineering thermodynamics   uq - may june 2014
Me2202 engineering thermodynamics uq - may june 2014BIBIN CHIDAMBARANATHAN
 
New ton presentation_c
New ton  presentation_cNew ton  presentation_c
New ton presentation_cEUROPAGES
 
Chillers selection 640 gpm
Chillers selection 640 gpmChillers selection 640 gpm
Chillers selection 640 gpmJoseAlvitrez1
 
Misubishi eti and etw heat pump presentation may 4th, 2011 rev.1
Misubishi eti and etw heat pump presentation may 4th, 2011 rev.1Misubishi eti and etw heat pump presentation may 4th, 2011 rev.1
Misubishi eti and etw heat pump presentation may 4th, 2011 rev.1Thermatec
 
Misubishi eti and etw heat pump presentation may 4th, 2011 rev.1
Misubishi eti and etw heat pump presentation may 4th, 2011 rev.1Misubishi eti and etw heat pump presentation may 4th, 2011 rev.1
Misubishi eti and etw heat pump presentation may 4th, 2011 rev.1Thermatec
 
Me1201 engineering thermodynamics uq - nov dec 2007
Me1201 engineering thermodynamics   uq - nov dec 2007Me1201 engineering thermodynamics   uq - nov dec 2007
Me1201 engineering thermodynamics uq - nov dec 2007BIBIN CHIDAMBARANATHAN
 
Case study: 160 Tooley Street
Case study: 160 Tooley StreetCase study: 160 Tooley Street
Case study: 160 Tooley StreetVikki Jacobs
 
Me2202 engineering thermodynamics uq - april may 2010
Me2202 engineering thermodynamics   uq - april may 2010Me2202 engineering thermodynamics   uq - april may 2010
Me2202 engineering thermodynamics uq - april may 2010BIBIN CHIDAMBARANATHAN
 
54666070 kiln-operation
54666070 kiln-operation54666070 kiln-operation
54666070 kiln-operationDin Sokreach
 
Ice Slurry TES for Turbine Inlet Cooling
Ice Slurry TES for Turbine Inlet CoolingIce Slurry TES for Turbine Inlet Cooling
Ice Slurry TES for Turbine Inlet Coolingss383
 
Crac precision climate_control_units_for_data_centres
Crac precision climate_control_units_for_data_centresCrac precision climate_control_units_for_data_centres
Crac precision climate_control_units_for_data_centresEeu SC
 

Similar to Better by design exploring containment options to optimise every cooling kW - Airedale International Air Conditioning Ltd (20)

Cold start of a 5.5MVA offshore transformer
Cold start of a 5.5MVA offshore transformerCold start of a 5.5MVA offshore transformer
Cold start of a 5.5MVA offshore transformer
 
Modelling of a cooling tower in EES
Modelling of a cooling tower in EESModelling of a cooling tower in EES
Modelling of a cooling tower in EES
 
Thermodynamic, part 5
Thermodynamic, part 5Thermodynamic, part 5
Thermodynamic, part 5
 
Energy study Fan Coil Units versus active chilled beams
Energy study   Fan Coil Units versus active chilled beamsEnergy study   Fan Coil Units versus active chilled beams
Energy study Fan Coil Units versus active chilled beams
 
Cep report
Cep reportCep report
Cep report
 
Me2202 engineering thermodynamics uq - may june 2014
Me2202 engineering thermodynamics   uq - may june 2014Me2202 engineering thermodynamics   uq - may june 2014
Me2202 engineering thermodynamics uq - may june 2014
 
Lecture28
Lecture28Lecture28
Lecture28
 
New ton presentation_c
New ton  presentation_cNew ton  presentation_c
New ton presentation_c
 
Thermodynamic, examples b
Thermodynamic, examples bThermodynamic, examples b
Thermodynamic, examples b
 
Chillers selection 640 gpm
Chillers selection 640 gpmChillers selection 640 gpm
Chillers selection 640 gpm
 
Misubishi eti and etw heat pump presentation may 4th, 2011 rev.1
Misubishi eti and etw heat pump presentation may 4th, 2011 rev.1Misubishi eti and etw heat pump presentation may 4th, 2011 rev.1
Misubishi eti and etw heat pump presentation may 4th, 2011 rev.1
 
Misubishi eti and etw heat pump presentation may 4th, 2011 rev.1
Misubishi eti and etw heat pump presentation may 4th, 2011 rev.1Misubishi eti and etw heat pump presentation may 4th, 2011 rev.1
Misubishi eti and etw heat pump presentation may 4th, 2011 rev.1
 
Me1201 engineering thermodynamics uq - nov dec 2007
Me1201 engineering thermodynamics   uq - nov dec 2007Me1201 engineering thermodynamics   uq - nov dec 2007
Me1201 engineering thermodynamics uq - nov dec 2007
 
Case study: 160 Tooley Street
Case study: 160 Tooley StreetCase study: 160 Tooley Street
Case study: 160 Tooley Street
 
Me2202 engineering thermodynamics uq - april may 2010
Me2202 engineering thermodynamics   uq - april may 2010Me2202 engineering thermodynamics   uq - april may 2010
Me2202 engineering thermodynamics uq - april may 2010
 
Me2202 ENGINEERING THERMODYNAMICS
Me2202 ENGINEERING THERMODYNAMICSMe2202 ENGINEERING THERMODYNAMICS
Me2202 ENGINEERING THERMODYNAMICS
 
54666070 kiln-operation
54666070 kiln-operation54666070 kiln-operation
54666070 kiln-operation
 
HR.pptx
HR.pptxHR.pptx
HR.pptx
 
Ice Slurry TES for Turbine Inlet Cooling
Ice Slurry TES for Turbine Inlet CoolingIce Slurry TES for Turbine Inlet Cooling
Ice Slurry TES for Turbine Inlet Cooling
 
Crac precision climate_control_units_for_data_centres
Crac precision climate_control_units_for_data_centresCrac precision climate_control_units_for_data_centres
Crac precision climate_control_units_for_data_centres
 

Recently uploaded

UiPath Community: Communication Mining from Zero to Hero
UiPath Community: Communication Mining from Zero to HeroUiPath Community: Communication Mining from Zero to Hero
UiPath Community: Communication Mining from Zero to HeroUiPathCommunity
 
The Ultimate Guide to Choosing WordPress Pros and Cons
The Ultimate Guide to Choosing WordPress Pros and ConsThe Ultimate Guide to Choosing WordPress Pros and Cons
The Ultimate Guide to Choosing WordPress Pros and ConsPixlogix Infotech
 
Generative AI for Technical Writer or Information Developers
Generative AI for Technical Writer or Information DevelopersGenerative AI for Technical Writer or Information Developers
Generative AI for Technical Writer or Information DevelopersRaghuram Pandurangan
 
TeamStation AI System Report LATAM IT Salaries 2024
TeamStation AI System Report LATAM IT Salaries 2024TeamStation AI System Report LATAM IT Salaries 2024
TeamStation AI System Report LATAM IT Salaries 2024Lonnie McRorey
 
Emixa Mendix Meetup 11 April 2024 about Mendix Native development
Emixa Mendix Meetup 11 April 2024 about Mendix Native developmentEmixa Mendix Meetup 11 April 2024 about Mendix Native development
Emixa Mendix Meetup 11 April 2024 about Mendix Native developmentPim van der Noll
 
TrustArc Webinar - How to Build Consumer Trust Through Data Privacy
TrustArc Webinar - How to Build Consumer Trust Through Data PrivacyTrustArc Webinar - How to Build Consumer Trust Through Data Privacy
TrustArc Webinar - How to Build Consumer Trust Through Data PrivacyTrustArc
 
Rise of the Machines: Known As Drones...
Rise of the Machines: Known As Drones...Rise of the Machines: Known As Drones...
Rise of the Machines: Known As Drones...Rick Flair
 
Enhancing User Experience - Exploring the Latest Features of Tallyman Axis Lo...
Enhancing User Experience - Exploring the Latest Features of Tallyman Axis Lo...Enhancing User Experience - Exploring the Latest Features of Tallyman Axis Lo...
Enhancing User Experience - Exploring the Latest Features of Tallyman Axis Lo...Scott Andery
 
A Framework for Development in the AI Age
A Framework for Development in the AI AgeA Framework for Development in the AI Age
A Framework for Development in the AI AgeCprime
 
How AI, OpenAI, and ChatGPT impact business and software.
How AI, OpenAI, and ChatGPT impact business and software.How AI, OpenAI, and ChatGPT impact business and software.
How AI, OpenAI, and ChatGPT impact business and software.Curtis Poe
 
(How to Program) Paul Deitel, Harvey Deitel-Java How to Program, Early Object...
(How to Program) Paul Deitel, Harvey Deitel-Java How to Program, Early Object...(How to Program) Paul Deitel, Harvey Deitel-Java How to Program, Early Object...
(How to Program) Paul Deitel, Harvey Deitel-Java How to Program, Early Object...AliaaTarek5
 
Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24
Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24
Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24Mark Goldstein
 
Potential of AI (Generative AI) in Business: Learnings and Insights
Potential of AI (Generative AI) in Business: Learnings and InsightsPotential of AI (Generative AI) in Business: Learnings and Insights
Potential of AI (Generative AI) in Business: Learnings and InsightsRavi Sanghani
 
Merck Moving Beyond Passwords: FIDO Paris Seminar.pptx
Merck Moving Beyond Passwords: FIDO Paris Seminar.pptxMerck Moving Beyond Passwords: FIDO Paris Seminar.pptx
Merck Moving Beyond Passwords: FIDO Paris Seminar.pptxLoriGlavin3
 
Decarbonising Buildings: Making a net-zero built environment a reality
Decarbonising Buildings: Making a net-zero built environment a realityDecarbonising Buildings: Making a net-zero built environment a reality
Decarbonising Buildings: Making a net-zero built environment a realityIES VE
 
Modern Roaming for Notes and Nomad – Cheaper Faster Better Stronger
Modern Roaming for Notes and Nomad – Cheaper Faster Better StrongerModern Roaming for Notes and Nomad – Cheaper Faster Better Stronger
Modern Roaming for Notes and Nomad – Cheaper Faster Better Strongerpanagenda
 
Use of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptx
Use of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptxUse of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptx
Use of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptxLoriGlavin3
 
Manual 508 Accessibility Compliance Audit
Manual 508 Accessibility Compliance AuditManual 508 Accessibility Compliance Audit
Manual 508 Accessibility Compliance AuditSkynet Technologies
 
What is DBT - The Ultimate Data Build Tool.pdf
What is DBT - The Ultimate Data Build Tool.pdfWhat is DBT - The Ultimate Data Build Tool.pdf
What is DBT - The Ultimate Data Build Tool.pdfMounikaPolabathina
 
2024 April Patch Tuesday
2024 April Patch Tuesday2024 April Patch Tuesday
2024 April Patch TuesdayIvanti
 

Recently uploaded (20)

UiPath Community: Communication Mining from Zero to Hero
UiPath Community: Communication Mining from Zero to HeroUiPath Community: Communication Mining from Zero to Hero
UiPath Community: Communication Mining from Zero to Hero
 
The Ultimate Guide to Choosing WordPress Pros and Cons
The Ultimate Guide to Choosing WordPress Pros and ConsThe Ultimate Guide to Choosing WordPress Pros and Cons
The Ultimate Guide to Choosing WordPress Pros and Cons
 
Generative AI for Technical Writer or Information Developers
Generative AI for Technical Writer or Information DevelopersGenerative AI for Technical Writer or Information Developers
Generative AI for Technical Writer or Information Developers
 
TeamStation AI System Report LATAM IT Salaries 2024
TeamStation AI System Report LATAM IT Salaries 2024TeamStation AI System Report LATAM IT Salaries 2024
TeamStation AI System Report LATAM IT Salaries 2024
 
Emixa Mendix Meetup 11 April 2024 about Mendix Native development
Emixa Mendix Meetup 11 April 2024 about Mendix Native developmentEmixa Mendix Meetup 11 April 2024 about Mendix Native development
Emixa Mendix Meetup 11 April 2024 about Mendix Native development
 
TrustArc Webinar - How to Build Consumer Trust Through Data Privacy
TrustArc Webinar - How to Build Consumer Trust Through Data PrivacyTrustArc Webinar - How to Build Consumer Trust Through Data Privacy
TrustArc Webinar - How to Build Consumer Trust Through Data Privacy
 
Rise of the Machines: Known As Drones...
Rise of the Machines: Known As Drones...Rise of the Machines: Known As Drones...
Rise of the Machines: Known As Drones...
 
Enhancing User Experience - Exploring the Latest Features of Tallyman Axis Lo...
Enhancing User Experience - Exploring the Latest Features of Tallyman Axis Lo...Enhancing User Experience - Exploring the Latest Features of Tallyman Axis Lo...
Enhancing User Experience - Exploring the Latest Features of Tallyman Axis Lo...
 
A Framework for Development in the AI Age
A Framework for Development in the AI AgeA Framework for Development in the AI Age
A Framework for Development in the AI Age
 
How AI, OpenAI, and ChatGPT impact business and software.
How AI, OpenAI, and ChatGPT impact business and software.How AI, OpenAI, and ChatGPT impact business and software.
How AI, OpenAI, and ChatGPT impact business and software.
 
(How to Program) Paul Deitel, Harvey Deitel-Java How to Program, Early Object...
(How to Program) Paul Deitel, Harvey Deitel-Java How to Program, Early Object...(How to Program) Paul Deitel, Harvey Deitel-Java How to Program, Early Object...
(How to Program) Paul Deitel, Harvey Deitel-Java How to Program, Early Object...
 
Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24
Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24
Arizona Broadband Policy Past, Present, and Future Presentation 3/25/24
 
Potential of AI (Generative AI) in Business: Learnings and Insights
Potential of AI (Generative AI) in Business: Learnings and InsightsPotential of AI (Generative AI) in Business: Learnings and Insights
Potential of AI (Generative AI) in Business: Learnings and Insights
 
Merck Moving Beyond Passwords: FIDO Paris Seminar.pptx
Merck Moving Beyond Passwords: FIDO Paris Seminar.pptxMerck Moving Beyond Passwords: FIDO Paris Seminar.pptx
Merck Moving Beyond Passwords: FIDO Paris Seminar.pptx
 
Decarbonising Buildings: Making a net-zero built environment a reality
Decarbonising Buildings: Making a net-zero built environment a realityDecarbonising Buildings: Making a net-zero built environment a reality
Decarbonising Buildings: Making a net-zero built environment a reality
 
Modern Roaming for Notes and Nomad – Cheaper Faster Better Stronger
Modern Roaming for Notes and Nomad – Cheaper Faster Better StrongerModern Roaming for Notes and Nomad – Cheaper Faster Better Stronger
Modern Roaming for Notes and Nomad – Cheaper Faster Better Stronger
 
Use of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptx
Use of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptxUse of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptx
Use of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptx
 
Manual 508 Accessibility Compliance Audit
Manual 508 Accessibility Compliance AuditManual 508 Accessibility Compliance Audit
Manual 508 Accessibility Compliance Audit
 
What is DBT - The Ultimate Data Build Tool.pdf
What is DBT - The Ultimate Data Build Tool.pdfWhat is DBT - The Ultimate Data Build Tool.pdf
What is DBT - The Ultimate Data Build Tool.pdf
 
2024 April Patch Tuesday
2024 April Patch Tuesday2024 April Patch Tuesday
2024 April Patch Tuesday
 

Better by design exploring containment options to optimise every cooling kW - Airedale International Air Conditioning Ltd

  • 1. George Hannah, Product Development Director Better by design, exploring containment options to optimise every Cooling kW
  • 2. Why Airedale? Global provider of efficient cooling solutions Almost 40 years experience in IT industry Largest UK manufacturer of IT cooling solutions A pioneer in free-cooling technology An industry leader in rack level cooling
  • 5. What Do We Do? 50,000 applications since 1974 2011 1,200 last year
  • 6. Business Issues Footprint Uptime And Density Operational Efficiency Costs Capital Costs
  • 8. The 2nd Law of Thermodynamics “The second law states that spontaneous natural processes increase entropy overall, or in another formulation that heat can spontaneously be conducted or radiated only from a higher-temperature region to a lower- temperature region, but not the other way around.” TH TC TW
  • 9. Open Aisle (500kW Facility) Temperature (oC) 45 40 35 30 25 Return 20 15 Supply 10 Total heat load 5 kW per Rack 5 Total number of cabinets 100
  • 10. Cold Aisle Containment (500kW Facility) Temperature (oC) 45 40 35 30 25 20 15 10 Total heat load 5 kW per Rack 5 Total number of cabinets 100
  • 11. Hot Aisle Containment (500kW Facility) Temperature (oC) 45 40 35 30 25 Additional IT opportunity = 20 420kW 15 10 Total heat load 10 kW per Rack 5 Total number of cabinets 50
  • 12. InRak Hot Aisle Containment (500kW Facility) Temperature (oC) 45 40 35 30 25 Additional 20 IT opportunity = 15 420kW 10 Total heat load 9.8 kW per Rack 5 Total number of cabinets 51
  • 13. OnRak Compact Hot Aisle (500kW Facility) Temperature (oC) 45 40 35 Additional IT opportunity 30 =1880kW 25 20 15 10 Total heat load 20 kW per Rack 5 Total number of cabinets 25
  • 14. ECHO - Compact Hot Aisle (500kW Facility) Temperature (oC) 45 40 35 30 Additional IT opportunity = 894kW 25 20 15 10 Total heat load 20 kW per Rack 5 Total number of cabinets 25
  • 15. Supply and Return Temperatures Temperature (oC) Supply Return OnRak 45 40 ECHO 35 InRak 30 25 Hot Aisle 20 15 Cold Aisle 10 Open Aisle 5
  • 16. Supply and Return Temperatures Temperature 0C Return Air 45 40 35 30 25 20 Supply Air 15 10 5 0 CRAC Open Cold Hot Cold InRak OnRak ECHO Aisle Aisle Aisle Aisle
  • 17. What is Free Cooling? Indirect - AIR Direct - AIR Indirect - WATER IN OUT
  • 18. Free Cooling Open Aisle Free cooling Concurrent Mode Mechanical Hours per year 600 1% 300 48% 51% -6 -2 6 2 10 14 18 22 26 30 Ambient Temperature (ºC)
  • 19. Free Cooling Cold Aisle Free cooling Concurrent Mode Mechanical Hours per year 600 300 6% 62% 32% -6 -2 6 2 10 14 18 22 26 30 Ambient Temperature (ºC)
  • 20. Free Cooling Hot Aisle Free cooling Concurrent Mode Mechanical Hours per year 600 300 25% 67% 18% -6 -2 6 2 10 14 18 22 26 30 Ambient Temperature (ºC)
  • 21. Free Cooling InRak Free cooling Concurrent Mode Mechanical Hours per year 600 300 25% 67% 18% -6 -2 6 2 10 14 18 22 26 30 Ambient Temperature (ºC)
  • 22. Free Cooling OnRak Free cooling Concurrent Mode Mechanical Hours per year 600 300 20% 69% 11% -6 -2 6 2 10 14 18 22 26 30 Ambient Temperature (ºC)
  • 23. Free Cooling ECHO Free cooling Concurrent Mode Mechanical Hours per year 600 1% 300 89% 10% -6 -2 6 2 10 14 18 22 26 30 Ambient Temperature (ºC)
  • 24. Free Cooling Free cooling Open Aisle Cold Aisle Hot Aisle Concurrent Mode Mechanical InRak OnRak ECHO
  • 25. Technical Matrix System Space claim Space claim Free-cooling efficiency (cooling (IT opportunity (Annualised equipment equipment (%) PUE) (m²) (m²) Open Aisle 49% 1.45 14 60 Cold Aisle 68% 1.38 14 60 Hot Aisle 92% 1.30 14 30 InRak 92% 1.29 12 30 OnRak 89% 1.26 3 15 ECHO 99% 1.24 14 15
  • 26. Commercial Matrix Month Operating Total Payback Capital costs costs operating period (annualised) £/kW p.a. (months) Open Aisle £139,996 £291,402 £99 13 Cold Aisle £143,878 £125,869 £84 14 Hot Aisle £124,383 £95,585 £58 16 InRak £190,575 £60,350 £56 14 OnRak £186,620 £57,827 £33 15 ECHO £192,208 £42,992 £27 15
  • 27. Case Study: Open Aisle Containment System Space claim Space claim Free-cooling efficiency (cooling (IT opportunity (Annualised equipment equipment (%) PUE) (m²) (m²) Open Aisle 49% 1.45 14 60 Cold Aisle 68% PUE 1.38 14 60 2.0 Hot Aisle 92% 1.30 14 30 InRak 92% 1.29 12 30 1.5 OnRak 89% 1.26 3 15 ECHO 99%0 1.24 14 15
  • 28. Case Study: Open Aisle Containment The chillers give us 1500kW n + 1 cooling plus a stunning reduction in electricity consumption i.e. 2.5 times cooling capacity for 100 – 150kW less power consumption per day. Mark Ford Data Centre Manager
  • 29. Case Study: Cold Aisle Containment System Space claim Space claim Free-cooling efficiency (cooling (IT opportunity (Annualised equipment equipment (%) PUE) (m²) (m²) Open Aisle 49% 1.45 14 60 Cold Aisle 68% 1.38 14 60 Hot Aisle 92% 1.30 14 30 InRak 92% 1.29 12 30 OnRak 89% 1.26 3 15 ECHO 99% 1.24 14 15
  • 30. Case Study: Hot Aisle Containment System Space claim Space claim Free-cooling efficiency (cooling (IT opportunity (Annualised equipment equipment (%) PUE) (m²) (m²) Open Aisle 49% 1.45 14 60 Cold Aisle 68% 1.38 14 60 Hot Aisle 92% 1.30 14 30 InRak 92% 1.29 12 30 --------- --------- OnRak 89% 1.26 ------ 3 15 95% ECHO 99% 1.24 14 15
  • 31. Case Study: Hot Aisle Containment Airedale provides us with a fully integrated cooling solution designed for maximum efficiency and critical redundancy…Our carbon neutral status helps our clients take huge steps towards their own environmental goals and carbon reduction commitments. Rob Garbutt Chief Executive Officer
  • 32. Case Study: InRak Hot Aisle Containment System Space claim Space claim Free-cooling efficiency (cooling (IT opportunity (Annualised equipment equipment (%) PUE) (m²) (m²) Open Aisle 49% 1.45 14 60 Cold Aisle Guaranteed PUE 1.29 68% 1.38 14 60 Hot Aisle 92% 1.30 14 30 InRak 92% 1.29 12 30 OnRak 89% 1.26 3 15 ECHO 99% 1.24 14 15
  • 33. Case Study: InRak Hot Aisle Containment The InRak is perfectly designed…the units are very clever; they ‘talk’ to each other and maintain pressure in the room. ACIS gives us 24/7 control of the operation and peace of mind. Mike Marchant Data Centre Manager
  • 34. Case Study: OnRak Compact Hot Aisle System Space claim Space claim Free-cooling efficiency (cooling (IT opportunity (Annualised equipment equipment (%) PUE) (m²) (m²) Open Aisle 49% 1.45 14 60 Cold Aisle 68% 1.38 14 60 35% savings vs. standard DX Hot Aisle 92% 1.30 14 30 InRak 92% 1.29 12 30 OnRak 89% 1.26 3 15 ECHO 99% 1.24 14 15
  • 35. Case Study: OnRak Compact Hot Aisle Our HPC facility at Leeds is growing …by meeting our space constraints and slotting into our existing cooling loop, the OnRak units from Airedale have saved us space in an already densely packed environment Dr Jon Summers Senior Lecturer, School of Mechanical Engineering
  • 36. Increased IT Opportunity Cooling Additional Space m2 Rack (m2) Equipment (m2) Space (m2) 100 30m² 32m² 56m² 45m² 80 60 40 20 0 Open Cold Hot InRak OnRak ECHO Aisle Aisle Aisle
  • 37. 3 Year Lifecycle Cost £ Total Capital Operating Costs PUE (millions) Cost (over 3 years) 1.2 1.45 1.38 1.30 1.29 1.26 1.24 1.0 0.8 0.6 0.4 0.2 0 Open Cold Hot InRak OnRak ECHO Aisle Aisle Aisle
  • 38. Business Issues Footprint And Density Uptime Operational Efficiency Costs Capital Costs
  • 39. Contact Us For more information on any of our products please visit: www.airedale.com Or alternatively, call us on + 44 (0)113 239 1000 Connect with us on YouTube, LinkedIn or Flickr: www.youtube.com/airedalecooling www.linkedin.com/company/airedale-international-air-conditioning- ltd?trk=hb_tab_compy_id_110826 www.flickr.com/photos/airedale-air-conditioning/

Editor's Notes

  1. Use this slide to set some context for who Airedale are and why they are delivering this pptAiredale is a global provider of efficient cooling solutions, with long-standing experience (nearly 40 years) in precision cooling in the IT industry. It is the largest UK chiller manufacturer, a pioneer in free-cooling technology and an industry leader in the development of rack level cooling. We are working in partnership with Rltec to go a step further and embed a new technology in our products, unique in the cooling industry, which will:- balance energy demand - reduce carbon - generate revenue