Considerations When Using
Extended Field Wiring Lengths
with Bently Nevada Transducers
[Editor’s Note: This article is an abbreviated version of Bently Nevada Applications Note 178454. Due to space limitations, all available graphs,
tables, and sample calculations have not been reprinted here from that Note. The interested reader is encouraged to download the full Note
from the electronic version of our Reader Service Card for this issue of ORBIT, available at www.orbit-magazine.com.]




T   he standard maximum cable run for Bently Nevada* transducers has been specified for many years
    in our product manuals and datasheets as 1000 feet (305 meters). In some cases, however, users have
found this limitation to be inconvenient and are interested in running field wiring over extended distances
to suit their needs. Longer lengths can be accomplished, provided the user understands the engineering
principles involved and is able to properly quantify the effects of longer cable lengths and assess the impact
on their particular application. This article discusses the key issues with extended field wiring by showing
how wiring length and construction effects capacitance and frequency response, by discussing the types
of applications that are particularly dependent upon high-frequency signal content, and by discussing the
concept of capacitance limits and its relationship to hazardous area installation requirements.


The origin of the 1000 foot limit                                                 Thus, along with our recommendation for 18 AWG
                                                                                  wire came a recommendation to limit the length to
For many years, the field wiring for Bently Nevada trans-                         no more than 1000 feet (305 m) in non-hazardous
ducers has been recommended as 18 AWG. Depending                                  areas. This length was chosen both because it easy
on the transducer type, either 2-conductor or 3-conduc-                           to remember and because it introduces only minimal
tor cable is used. Although lighter gauges can also be                            signal degradation, allowing the full 10 kHz frequency
used (such as 22 AWG), experience has shown that                                  response of our typical transducers to pass with little
lighter gauges have a greater tendency to break when                              attenuation. However, as will be discussed in this article,
connecting to terminals on the monitor and transducer.                            this limit does not hold for all applications. Hazardous
One of the limitations inherent with heavier gauge wire                           area applications and/or those for which the frequency
is that it represents greater capacitance per unit length,                        response requirements differ from 0–10 kHz will require
which in turn affects both the frequency response and                             the designer to carefully consider the field wiring’s
suitability for hazardous areas where strict limits on                            effects on stored energy and signal attenuation. This
total circuit capacitance are in effect.                                          article, and its companion Applications Note, serve
                                                                                  as primers on the subject, familiarizing installation
                                                                                  designers with the engineering considerations and
                                                                                  calculations involved.


Jared Angel
Sustaining Engineer
GE Energy
jared.angel@ge.com

5 2 O R B IT Vo l.27 N o.1 2007
APPLICATIONS




Cable Capacitance                                               When using cable from another supplier, consult their
                                                                datasheet or contact the manufacturer to obtain
The frequency response of cable is affected by                  capacitive values. When this is not possible or practical,
resistance, capacitance, and inductance. However,               it will be necessary to determine these values yourself
capacitance will usually be the first to cause problems.        using the following equations:
In addition, installations into areas with hazardous
classifications usually limit the capacitive load allowed.      •    For two-wire circuits
In either case, the total cable capacitance must be                  Total capacitance = capacitance core to core
calculated and evaluated against the pertinent limits.               + capacitance core to screen.
                                                                     C total = C core-to-core + C core-to-screen
The total cable capacitance is a function of the following
factors:                                                        •    For three-wire circuits
                                                                     Total capacitance = (2 X capacitance core to core)
•     Cable length                                                   + capacitance core to screen.
•     Number of Conductors                                           C total = (2*C core-to-core ) + C core-to-screen
      In most cases, field wiring will have two or three
                                                                The goal is to determine the total capacitive load for
      conductors, depending upon the type of transducer
                                                                a given length of cable. To find this, multiply the cable
      being used. Proximity transducers always use a
                                                                capacitance per unit length by the total cable length.
      three-conductor system (power, signal, common)
                                                                As has previously been noted, this total capacitive
      while other transducers either may not require
                                                                load must be taken into account when considering the
      external power or may share the power/signal wire;
                                                                hazardous area and signal integrity issues.
      consequently, they use a two-conductor system.
                                                                Specific installations often run field wiring cable with
•     Cable Specifications
                                                                lower capacitance than that offered by GE to mitigate
      The relevant values for field wiring analysis are
                                                                long field wire lengths. This is successful when proper
      the cable capacitance per unit length and the
                                                                engineering practices are applied to quantify the
      total capacitive load. The data sheet for cable will
                                                                performance.
      typically lists its capacitance per unit length. If you
      cannot find this value, you can usually calculate it      Applications
      from other datasheet values as explained below.
                                                                Certain applications and measurements are known to
Capacitance values for the field wiring provided by GE          generate high-frequency content and are particularly
for use with Bently Nevada transducers are shown in             dependent upon field wiring that preserves the full
Table 1.                                                        spectral integrity of the signal. This typically occurs
                                                                when the machine itself runs at very high rotational
    Table 1 – Cable Capacitance for field wiring                 speeds and/or when the nature of the vibration tends
    provided by GE for use with Bently Nevada                   to generate a number of harmonics. Some common
    transducers
                                                                applications and their dependence upon high-frequency
 Part Number          Description          Capacitance          signal content are noted below.
 02173006             18 AWG               98 pF/meter          •    Applications more dependent upon high-
                      two-conductor                                  frequency signals
                      cable
                                                                     Gearboxes, turbine blade pass, rolling element
 02120015             18 AWG               289 pF/meter
                                                                     bearing signatures, high-speed machines (e.g.,
                      three-conductor
                                                                     turbo expanders and the high speed stages of
                      cable
                                                                     centrifugal air compressors), speed-sensing appli-
                                                                     cations with the sensor observing a toothed wheel.

                                                                                                          Vo l . 27 N o. 1 2007 ORB I T 53
APPLICATIONS




•     Applications less dependent upon high-                      Signal Quality
      frequency signals
                                                                  Driving a large capacitive load can be problematic as
      Non-vibration measurements (e.g., thrust position,
                                                                  large loads can attenuate higher frequencies. What is
      differential expansion, case expansion), low-speed
                                                                  considered ‘too large’ will depend of the type of trans-
      machines (e.g., hydro turbine/generators, recipro-
                                                                  ducer being used and the frequencies of interest. Table
      cating compressors).
                                                                  2 shows the frequency response of numerous Bently
The above is intended only as a general guideline. Each           Nevada vibration transducers along with notes regarding
application must be evaluated on its own merits by                cable lengths. Obviously, as long as the field wiring
considering the construction of the machine, the fre-             provides a frequency response as good or better than the
quencies it is likely to generate under normal operating          transducer itself, there will be no degradation of high-fre-
conditions (blade pass, gear mesh, ball pass, etc.) and           quency content introduced by the field wiring. However,
the frequencies it is likely to generate under malfunction        the total capacitance may exceed the allowable limits for
conditions (cavitation, structural resonances, rough load         hazardous area applications. Thus, when applicable, the
zone, etc.).                                                      designer must carefully consider both before deciding
                                                                  upon an allowable maximum cable length.


    Table 2 – Field wiring and signal quality considerations for typical Bently Nevada transducers.

Transducer                        Frequency Response         Notes

3300XL 8mm and                    0 - 10 kHz                 Extended field wire lengths can attenuate relevant
NSv Proximitor* Sensor                                       high-frequency content and affect measurement integrity.
3300XL 11mm                       0 – 8 kHz                  Extended field wire lengths can attenuate relevant
Proximitor Sensor                                            high-frequency content and affect measurement integrity.
3300XL 25mm                       0 – 2.7 kHz                Extended field wire lengths will rarely be an issue for
Proximitor Sensor                                            frequency response considerations.
3300XL 50mm                       0 - 50Hz                   Extended field wire lengths will rarely be an issue for
Proximitor Sensor                                            frequency response considerations.
XL Radiation Resistant            15 ft. system:             Extended field wire lengths can attenuate relevant
Proximitor Sensor                 0 – 10 kHz                 high-frequency content and affect measurement integrity.

                                  40 ft. system:
                                  0 – 9 kHz

                                  110 ft system:
                                  0 – 5 kHz

LVDT                              n/a                        Extended field wiring lengths are not recommended under
                                                             any circumstance due to the LVDT’s sensitivity to resistance.
Velomitors                        Varies depending on        Extended field wire lengths can attenuate relevant
                                  model. See pertinent       high-frequency content and affect measurement integrity,
                                  transducer datasheet.      depending on transducer frequency response.
Accelerometers                    Varies depending on        Extended field wire lengths can attenuate relevant high-
                                  model. See pertinent       frequency content and affect measurement integrity.
                                  transducer datasheet
Thermocouples                     n/a                        Extended field wiring lengths are not recommended under
and RTDs                                                     any circumstances due to the sensor’s sensitivity
                                                             to resistance.


5 4 O R B IT Vo l.27 N o.1 2007
APPLICATIONS




The manual for each transducer will typically provide a graph similar to Figure 1, showing the affect of total cable
capacitance on frequency response.


   Figure 1 – Effect of field wiring total capacitance on frequency response for 3300 XL 8mm Proximity
   Transducer System (5 meter system length, no I.S. barriers)




Frequency Response Calculation Examples

Example 1

Goal
Determine the frequency response attenuation that will           Since this value is very close to the 440 nF curve of
occur for a 3300 XL 8mm proximity transducer system (5           Figure 1, we will use that curve for estimation purposes.
meter system length, no barriers) when 1500 m of GE’s            When computing signal strength, it is customary to use
standard 18 AWG 3-conductor field wiring is used.                the -3db point as the so-called cut-off frequency (–3dB
                                                                 represents a signal that has only one-half of the original
Solution
                                                                 amplitude). The –3dB point for 440nF of total field wiring
Using the value of 289 pF/m from Table 1 for 3-conduc-
                                                                 capacitance is approximately 5 kHz. Thus, by introduc-
tor field wiring, the total cable capacitance for 1500 m
                                                                 ing 1500 meters of field wiring, we have reduced the 10
is found simply as:
                                                                 kHz frequency response of the transducer system to
289 pF/m x 1500 m = 433,500 pF = 433.5 nF
                                                                 approximately 5 kHz.




                                                                                                    Vo l . 27 N o. 1 2007 ORB I T 55
APPLICATIONS




Example 2                                                     Intrinsically Safe (I.S.)
                                                              The apparatus is incapable of releasing sufficient elec-
Goal
                                                              trical or thermal energy under normal and abnormal
Determine whether the transducer installation of
                                                              operating conditions to cause ignition of a specific
example 1 would be acceptable for a speed-indication
                                                              flammable atmosphere.
application using a 60-tooth wheel on a turbine running
at 6200 rpm.                                                  As can be seen, I.S. is a more stringent requirement,
                                                              requiring a design that limits the energy under both nor-
Solution
                                                              mal and abnormal operating conditions. Consequently,
A proximity transducer observing a 60-tooth wheel
                                                              designers will find that the maximum capacitance
turning at 6200 rpm will generated a square-wave
                                                              allowed for I.S. installations is more restrictive than
type pulse with nominal frequency of:
                                                              for N.I. installations. Also, although both inductors and
60 teeth/rev x 1 pulse/tooth x 6200 rev/min = 372,000         capacitors can store energy, the energy stored in the
pulses per min = 6200 pulses/sec = 6.2 kHz.                   capacitance of the field wiring is much larger than that
                                                              stored by the wiring’s inductance for our transducer/
Clearly, the cable length introduces too much attenua-
                                                              monitor applications. Agency approvals work on the
tion at this frequency, particularly since a “clean” square
                                                              basis of “most restrictive.” In other words, the designer
wave signal is necessary for a tachometer to trigger reli-
                                                              looks at the cable lengths that will result in either exces-
ably. At this frequency (6200 Hz), even the fundamental
                                                              sive capacitive energy or excessive inductive energy,
(1X) component of the square wave will be attenuated
                                                              and uses the more restrictive constraint. Invariably, as
by more than 4 dB as noted in Figure 1. The user would
                                                              noted, capacitance turns out to be the limiting factor
either need to shorten the field wiring length or choose
                                                              for our applications. Consequently, the discussion here
field wiring with a lower capacitance-per-meter rating.
                                                              confines itself only to capacitance. However, be aware
Hazardous Area Considerations                                 that with other electrical or electronic apparatus you
                                                              encounter, inductance may be the limiting factor. The
Another extremely important issue with extended               astute designer will know when an installation will need
length field wiring is the need to remain compliant with      to be concerned with capacitive constraints instead of
hazardous area classifications when applicable. Today,        inductive constraints, and vice-versa.
the most common methods of complying with hazard-
ous area classifications are through the use of designs       I.S. installations rely on special current/voltage limiting
that are either intrinsically safe (in the case of Zone 0/1   devices, such as galvanic isolators or so-called I.S. barri-
areas) or nonincendive (in the case of Zone 2 areas). The     ers. Although each uses different principles of operation,
principle behind such designs is to limit the amount of       the idea of an energy-limiting circuit is the same. When
available energy such that a flammable atmosphere             external barriers are used, a small voltage drop occurs
cannot be ignited under the appropriate conditions.           across the resistance of the barrier. Bently Nevada
                                                              monitoring systems designed for use with external bar-
Nonincendive (N.I.)                                           riers allow the user to compensate for this small voltage
The apparatus is incapable of releasing sufficient            drop. Systems that are available with internal barriers,
electrical or thermal energy under normal operating           such as 3300 and 3500, provide this compensation
conditions to cause ignition of a specific flammable          automatically; it is transparent to the user.
atmosphere.




5 6 O R B IT Vo l.27 N o.1 2007
APPLICATIONS




When considering the allowable maximum length of                          C total = C cable + Ci ≤ 0.2μF
field wiring, the designer consults the appropriate tables
                                                                          C total = C cable + Ci ≤ 200nF
and specifications for the particular zone, atmosphere,
and Bently Nevada hardware type, allowing the                             C cable + 6nF ≤ 200nF
maximum capacitance available for field wiring to be
                                                                          C cable ≤ 194nF
determined. One the maximum capacitance has been
determined, the maximum field wiring length can be                        C cable ≤ 194,000pF
readily ascertained. Similar calculations are also per-
                                                                          Now, since we have found the maximum total cable
formed to determine the maximum field wiring length
                                                                          capacitance Ccable, the maximum allowable length is
while retaining the necessary frequency response for
                                                                          simply Ccable divided by the capacitance per unit length
the application. Finally, the designer chooses the more
                                                                          (which is found in Table 1):
restrictive of these two constraints (frequency response
                                                                                    C cable = 194,000pF
or hazardous area) and this becomes the governing                         Lmax =
                                                                                   289pF/m        289pF/m
criteria for the maximum cable length.

Several examples follow that demonstrate these
                                                                          Lmax = 671m
concepts for typical monitoring system hardware.
[Editor’s Note: Due to space limitations, only selected tables from the   It is worth noting that while up to 671 m of this field
Applications Note have been provided here, allowing the reader to
                                                                          wiring would allow the system to remain within
perform the sample calculations below.]
                                                                          hazardous area constraints, it introduces 194 nF of
Hazardous Area Calculation Examples                                       total capacitance which affects the frequency response
                                                                          adversely. Referring again to Figure 1 (we will use the
Example 3
                                                                          curve for 176 nF since it is close to the actual value of
Goal                                                                      194 nF), it can be seen that the –3dB point is now less
Determine the maximum cable length Lmax allowed in                        than 10 kHz (somewhere between 8 and 8.5 kHz). Thus,
a Zone 2 area with atmosphere type IIC for a channel                      for applications that require the full 10 kHz frequency
using a 3500/42M monitor with Prox/Vel I/O module and                     response of the proximity transducer, the field wiring
a 3300 XL 8mm Proximity Probe (5 meter system length).                    would have to be shortened until the attenuation was
Assume the use of field wiring with Bently Nevada part                    within acceptable limits.
number 02120015.

Solution
Using Table 3, it can be seen that the maximum allow-                         Project Services
able connected capacitance Co for a 3500/42 monitor
                                                                              Although many customers will feel comfort-
with a Prox/Vel I/O module (p/n 140471-XX) is 0.2 μF (200                     able performing these calculations themselves
nF) regardless of atmosphere (gas) type. Next, per the                        and managing the installation of transducers,
published specifications in the 3300XL 8mm proximity                          monitors, and associated field wiring, other
transducer system datasheet, the input capacitance Ci                         customers prefer to use GE’s project services
of the Proximitor module is 5.7 nF, which we round off to                     capabilities. These services can be provided
6 nF. This allows us to determine the maximum allowable                       for selected portions of a project, such as field
total capacitance of the field wiring, Ccable, as follows:                    wiring calculations; or, they can be provided as
                                                                              part of a broader scope, such as preparation
                                                                                                   of drawings, supervision
                                                                                                   of subcontractors, and
                                                                                                   field machining services
                                                                                                   to retrofit or upgrade
                                                                                                   instrumentation on exist-
                                                                                                   ing machinery. 2007 ORB I T 57
                                                                                                          Vo l . 27 N o. 1
APPLICATIONS




    Table 3 – Maximum capacitance for 3500 monitoring system I/O modules in Zone 2 hazardous areas for
    gas group IIA - IIC

 Module Number                                                                          Co by gas group (uF)
                                                                                IIC               IIB                IIA
 146031-01, 3500/22M-01                                                                           1000


 140471-01,-02 3500/25, 3500/4x Prox / Velomitor 3500/64                                          0.2


 169459-01, -02, 350 0/4x Multimode, Prox/Velom (IT and ET)                                       0.2


 169715-01, -02, 3500/4x, Multimode Positive Input (IT and ET)                                    0.1


 125800-01, 3500/25                                                                               0.2


 133819-02, 3500/61, Thermocouple and RTD                                      1.56               10.5               42


 133835-02, 3500/61, Isolated Thermocouple                                     1.56               10.5               42


 136491-01, 3500/62, +/- 10Vdc I/O                                             1.71               1.71               48




Example 4

Goal
Assume the details given in example 3; however,                  Thus, field wiring cable should be chosen with a
installation constraints now require that the transducer         capacitance per unit length less than or equal to 194
system be located a minimum of 1000m from the moni-              pF/m. Since this value is less than the standard 18 AWG
tor system. Find the maximum cable capacitance per               3-conducter field wiring cable of Table 1, GE’s standard
unit length that can be used.                                    cable cannot be used and an alternative cable type
                                                                 meeting the required capacitance per unit length must
Solution
                                                                 be employed.
The maximum total cable capacitance Ccable is the same
as in example 3; namely, 194,000 pF. Here, however, we           As pointed out in example 3, although the length of
are given the length and need to find the capacitance            field wiring used here will allow the system to remain
per unit length CUL.                                             within the constraints imposed by the hazardous area
           Ccable                         194,000pF              criteria, it will result in some roll-off of the frequency
Lmax =                            CUL =
            CUL                            1000m                 response. As such, this length of field wiring may or may
                                                                 not be acceptable depending on whether the full 10
           Ccable                                                kHz frequency response available from the proximity
CUL =                             CUL = 194pF/m
           Lmax                                                  transducer is required or not.




5 8 O R B IT Vo l.27 N o.1 2007
APPLICATIONS




Example 5                                                   Summary

Goal
                                                            Long field wiring lengths are sometimes required
Determine the maximum cable length Lmax for the
channel described in Example 3 except now it must be        due to the nature of the cable runs and plant
suitable for a Zone 0 classified area with gas group IIC.
                                                            layout. This introduces additional capacitance and
Assume that the 3500 monitor uses an I/O module for
Prox/Accel with internal barriers. Assume also the same     can affect the integrity of the monitoring system in
field wiring type as example 3.                             one or both of the following ways:
Solution
Using Table 4, it can be seen that the maximum              •    By attenuating high frequencies in the
allowable connected capacitance Co for a 3500/42                 vibration signal
monitor with an internal barrier Prox/Vel I/O module (p/n
135470-01) is 0.083μF (83 nF). Also, as before, the input
                                                            •    By allowing too much stored electrical energy,
capacitance Ci of the Proximitor module is approxi-
mately 6 nF. This allows us to determine the maximum             violating hazardous area certification limits
allowable total capacitance of the field wiring, Ccable,
as follows.                                                 In order to determine the maximum length of field

                                                            wiring, the designer must therefore understand
    Table 4 – Maximum capacitance for 3500 moni-
    toring system I/O modules in Zone 0/1 hazardous         both the necessary frequency response required
    areas with gas group IIC atmospheres
                                                            by the application and the allowable maximum
 Barrier Module Number              Co by gas group (uF)    capacitance for the particular hazardous area
 135470-01, Proximitor &            0.083
                                                            classification (when applicable). The calculations
 Accelerometer
 135471-01, Velomitor               0.088                   allow the designer to determine either the maxi-

                                                            mum length of standard field wiring cable that can
 137101-01, Process Variable        0.76
                                                            be used, or the maximum capacitance per unit
 135472-01, Temperature             8.8                     length of alternate field wiring, allowing cable with

                                                            appropriate specifications to be procured.
C total = C cable + Ci ≤ 0.083μF
                                                            *Denotes a trademark of the General Electric Company.

C total = C cable + Ci ≤ 83nF

C cable + 6nF ≤ 83nF

C cable ≤ 77nF

C cable ≤ 77,000pF

Finally, the maximum allowable length is found using
the same equation as 3.
           C cable = 77,000pF
Lmax =
         289pF/m       289pF/m

Lmax = 266m

                                                                                                    Vo l . 27 N o. 1 2007 ORB I T 59

Contenu connexe

En vedette

Sop for air compressors
Sop for air compressorsSop for air compressors
Sop for air compressorschaosbrigade
 
Cooling fin fan vibration calibration and trip point setting
Cooling fin fan vibration calibration and trip point settingCooling fin fan vibration calibration and trip point setting
Cooling fin fan vibration calibration and trip point settingManorom Chiewpanich
 
R&t 2008 principles and practices of vibrational analysis - keefer
R&t 2008   principles and practices of vibrational analysis - keeferR&t 2008   principles and practices of vibrational analysis - keefer
R&t 2008 principles and practices of vibrational analysis - keefermakarandnikume
 
Where should a keyphasor transducer be mounted?
Where should a keyphasor transducer be mounted?Where should a keyphasor transducer be mounted?
Where should a keyphasor transducer be mounted?GE Measurement & Control
 
Ppt pump house one point basic
Ppt pump house one point  basicPpt pump house one point  basic
Ppt pump house one point basicPRIME ELECTRIC LTD
 
01 beginning vibration analysis
01 beginning vibration analysis01 beginning vibration analysis
01 beginning vibration analysisDương Phúc
 
Beginners guide vibration
Beginners guide vibrationBeginners guide vibration
Beginners guide vibrationnagasqueen
 
Vibration Monitoring
Vibration MonitoringVibration Monitoring
Vibration MonitoringPri Hadi
 
Vibration Monitoring
Vibration Monitoring Vibration Monitoring
Vibration Monitoring IONEL DUTU
 
Gas Turbine Operation
Gas Turbine OperationGas Turbine Operation
Gas Turbine OperationMalik M. N.
 
Industrial Internet: Pushing the Boundaries of Minds and Machines
Industrial Internet: Pushing the Boundaries of Minds and MachinesIndustrial Internet: Pushing the Boundaries of Minds and Machines
Industrial Internet: Pushing the Boundaries of Minds and MachinesGE Measurement & Control
 

En vedette (16)

Solutions for LNG facilities
Solutions for LNG facilitiesSolutions for LNG facilities
Solutions for LNG facilities
 
1 q05 ch_one-shotbalancing
1 q05 ch_one-shotbalancing1 q05 ch_one-shotbalancing
1 q05 ch_one-shotbalancing
 
Sop for air compressors
Sop for air compressorsSop for air compressors
Sop for air compressors
 
Cooling fin fan vibration calibration and trip point setting
Cooling fin fan vibration calibration and trip point settingCooling fin fan vibration calibration and trip point setting
Cooling fin fan vibration calibration and trip point setting
 
R&t 2008 principles and practices of vibrational analysis - keefer
R&t 2008   principles and practices of vibrational analysis - keeferR&t 2008   principles and practices of vibrational analysis - keefer
R&t 2008 principles and practices of vibrational analysis - keefer
 
Where should a keyphasor transducer be mounted?
Where should a keyphasor transducer be mounted?Where should a keyphasor transducer be mounted?
Where should a keyphasor transducer be mounted?
 
Ppt pump house one point basic
Ppt pump house one point  basicPpt pump house one point  basic
Ppt pump house one point basic
 
01 beginning vibration analysis
01 beginning vibration analysis01 beginning vibration analysis
01 beginning vibration analysis
 
Beginners guide vibration
Beginners guide vibrationBeginners guide vibration
Beginners guide vibration
 
Power Generation: Coal-Fired
Power Generation: Coal-FiredPower Generation: Coal-Fired
Power Generation: Coal-Fired
 
Vibration Monitoring
Vibration MonitoringVibration Monitoring
Vibration Monitoring
 
vibration
vibrationvibration
vibration
 
Vibration Monitoring
Vibration Monitoring Vibration Monitoring
Vibration Monitoring
 
Gas Turbine Operation
Gas Turbine OperationGas Turbine Operation
Gas Turbine Operation
 
Mechanical Vibration- An introduction
Mechanical Vibration- An introductionMechanical Vibration- An introduction
Mechanical Vibration- An introduction
 
Industrial Internet: Pushing the Boundaries of Minds and Machines
Industrial Internet: Pushing the Boundaries of Minds and MachinesIndustrial Internet: Pushing the Boundaries of Minds and Machines
Industrial Internet: Pushing the Boundaries of Minds and Machines
 

Plus de GE Measurement & Control

Customer Success Story Bently Nevada* Asset Condition Monitoring
Customer Success Story Bently Nevada* Asset Condition MonitoringCustomer Success Story Bently Nevada* Asset Condition Monitoring
Customer Success Story Bently Nevada* Asset Condition MonitoringGE Measurement & Control
 
Customer Success Story: Bently Nevada Asset Condition Monitoring
Customer Success Story: Bently Nevada Asset Condition MonitoringCustomer Success Story: Bently Nevada Asset Condition Monitoring
Customer Success Story: Bently Nevada Asset Condition MonitoringGE Measurement & Control
 
Wind energy resource assessment and forecasting
Wind energy resource assessment and forecastingWind energy resource assessment and forecasting
Wind energy resource assessment and forecastingGE Measurement & Control
 
Experience with Hydro Generator Expert Systems
Experience with Hydro Generator Expert SystemsExperience with Hydro Generator Expert Systems
Experience with Hydro Generator Expert SystemsGE Measurement & Control
 
Condition Monitoring Solutions for Reciprocating Compressors
Condition Monitoring Solutions for Reciprocating CompressorsCondition Monitoring Solutions for Reciprocating Compressors
Condition Monitoring Solutions for Reciprocating CompressorsGE Measurement & Control
 

Plus de GE Measurement & Control (7)

Performance Monitoring For Gas turbines
Performance Monitoring For Gas turbines Performance Monitoring For Gas turbines
Performance Monitoring For Gas turbines
 
Power Generation: Combined Cycle
Power Generation: Combined CyclePower Generation: Combined Cycle
Power Generation: Combined Cycle
 
Customer Success Story Bently Nevada* Asset Condition Monitoring
Customer Success Story Bently Nevada* Asset Condition MonitoringCustomer Success Story Bently Nevada* Asset Condition Monitoring
Customer Success Story Bently Nevada* Asset Condition Monitoring
 
Customer Success Story: Bently Nevada Asset Condition Monitoring
Customer Success Story: Bently Nevada Asset Condition MonitoringCustomer Success Story: Bently Nevada Asset Condition Monitoring
Customer Success Story: Bently Nevada Asset Condition Monitoring
 
Wind energy resource assessment and forecasting
Wind energy resource assessment and forecastingWind energy resource assessment and forecasting
Wind energy resource assessment and forecasting
 
Experience with Hydro Generator Expert Systems
Experience with Hydro Generator Expert SystemsExperience with Hydro Generator Expert Systems
Experience with Hydro Generator Expert Systems
 
Condition Monitoring Solutions for Reciprocating Compressors
Condition Monitoring Solutions for Reciprocating CompressorsCondition Monitoring Solutions for Reciprocating Compressors
Condition Monitoring Solutions for Reciprocating Compressors
 

Dernier

Onemonitar Android Spy App Features: Explore Advanced Monitoring Capabilities
Onemonitar Android Spy App Features: Explore Advanced Monitoring CapabilitiesOnemonitar Android Spy App Features: Explore Advanced Monitoring Capabilities
Onemonitar Android Spy App Features: Explore Advanced Monitoring CapabilitiesOne Monitar
 
The-Ethical-issues-ghhhhhhhhjof-Byjus.pptx
The-Ethical-issues-ghhhhhhhhjof-Byjus.pptxThe-Ethical-issues-ghhhhhhhhjof-Byjus.pptx
The-Ethical-issues-ghhhhhhhhjof-Byjus.pptxmbikashkanyari
 
Environmental Impact Of Rotary Screw Compressors
Environmental Impact Of Rotary Screw CompressorsEnvironmental Impact Of Rotary Screw Compressors
Environmental Impact Of Rotary Screw Compressorselgieurope
 
TriStar Gold Corporate Presentation - April 2024
TriStar Gold Corporate Presentation - April 2024TriStar Gold Corporate Presentation - April 2024
TriStar Gold Corporate Presentation - April 2024Adnet Communications
 
Appkodes Tinder Clone Script with Customisable Solutions.pptx
Appkodes Tinder Clone Script with Customisable Solutions.pptxAppkodes Tinder Clone Script with Customisable Solutions.pptx
Appkodes Tinder Clone Script with Customisable Solutions.pptxappkodes
 
EUDR Info Meeting Ethiopian coffee exporters
EUDR Info Meeting Ethiopian coffee exportersEUDR Info Meeting Ethiopian coffee exporters
EUDR Info Meeting Ethiopian coffee exportersPeter Horsten
 
Psychic Reading | Spiritual Guidance – Astro Ganesh Ji
Psychic Reading | Spiritual Guidance – Astro Ganesh JiPsychic Reading | Spiritual Guidance – Astro Ganesh Ji
Psychic Reading | Spiritual Guidance – Astro Ganesh Jiastral oracle
 
Excvation Safety for safety officers reference
Excvation Safety for safety officers referenceExcvation Safety for safety officers reference
Excvation Safety for safety officers referencessuser2c065e
 
Effective Strategies for Maximizing Your Profit When Selling Gold Jewelry
Effective Strategies for Maximizing Your Profit When Selling Gold JewelryEffective Strategies for Maximizing Your Profit When Selling Gold Jewelry
Effective Strategies for Maximizing Your Profit When Selling Gold JewelryWhittensFineJewelry1
 
14680-51-4.pdf Good quality CAS Good quality CAS
14680-51-4.pdf  Good  quality CAS Good  quality CAS14680-51-4.pdf  Good  quality CAS Good  quality CAS
14680-51-4.pdf Good quality CAS Good quality CAScathy664059
 
WSMM Technology February.March Newsletter_vF.pdf
WSMM Technology February.March Newsletter_vF.pdfWSMM Technology February.March Newsletter_vF.pdf
WSMM Technology February.March Newsletter_vF.pdfJamesConcepcion7
 
Horngren’s Financial & Managerial Accounting, 7th edition by Miller-Nobles so...
Horngren’s Financial & Managerial Accounting, 7th edition by Miller-Nobles so...Horngren’s Financial & Managerial Accounting, 7th edition by Miller-Nobles so...
Horngren’s Financial & Managerial Accounting, 7th edition by Miller-Nobles so...ssuserf63bd7
 
Cyber Security Training in Office Environment
Cyber Security Training in Office EnvironmentCyber Security Training in Office Environment
Cyber Security Training in Office Environmentelijahj01012
 
Go for Rakhi Bazaar and Pick the Latest Bhaiya Bhabhi Rakhi.pptx
Go for Rakhi Bazaar and Pick the Latest Bhaiya Bhabhi Rakhi.pptxGo for Rakhi Bazaar and Pick the Latest Bhaiya Bhabhi Rakhi.pptx
Go for Rakhi Bazaar and Pick the Latest Bhaiya Bhabhi Rakhi.pptxRakhi Bazaar
 
trending-flavors-and-ingredients-in-salty-snacks-us-2024_Redacted-V2.pdf
trending-flavors-and-ingredients-in-salty-snacks-us-2024_Redacted-V2.pdftrending-flavors-and-ingredients-in-salty-snacks-us-2024_Redacted-V2.pdf
trending-flavors-and-ingredients-in-salty-snacks-us-2024_Redacted-V2.pdfMintel Group
 
Memorándum de Entendimiento (MoU) entre Codelco y SQM
Memorándum de Entendimiento (MoU) entre Codelco y SQMMemorándum de Entendimiento (MoU) entre Codelco y SQM
Memorándum de Entendimiento (MoU) entre Codelco y SQMVoces Mineras
 
Driving Business Impact for PMs with Jon Harmer
Driving Business Impact for PMs with Jon HarmerDriving Business Impact for PMs with Jon Harmer
Driving Business Impact for PMs with Jon HarmerAggregage
 
The McKinsey 7S Framework: A Holistic Approach to Harmonizing All Parts of th...
The McKinsey 7S Framework: A Holistic Approach to Harmonizing All Parts of th...The McKinsey 7S Framework: A Holistic Approach to Harmonizing All Parts of th...
The McKinsey 7S Framework: A Holistic Approach to Harmonizing All Parts of th...Operational Excellence Consulting
 
Introducing the Analogic framework for business planning applications
Introducing the Analogic framework for business planning applicationsIntroducing the Analogic framework for business planning applications
Introducing the Analogic framework for business planning applicationsKnowledgeSeed
 

Dernier (20)

Onemonitar Android Spy App Features: Explore Advanced Monitoring Capabilities
Onemonitar Android Spy App Features: Explore Advanced Monitoring CapabilitiesOnemonitar Android Spy App Features: Explore Advanced Monitoring Capabilities
Onemonitar Android Spy App Features: Explore Advanced Monitoring Capabilities
 
The-Ethical-issues-ghhhhhhhhjof-Byjus.pptx
The-Ethical-issues-ghhhhhhhhjof-Byjus.pptxThe-Ethical-issues-ghhhhhhhhjof-Byjus.pptx
The-Ethical-issues-ghhhhhhhhjof-Byjus.pptx
 
Environmental Impact Of Rotary Screw Compressors
Environmental Impact Of Rotary Screw CompressorsEnvironmental Impact Of Rotary Screw Compressors
Environmental Impact Of Rotary Screw Compressors
 
TriStar Gold Corporate Presentation - April 2024
TriStar Gold Corporate Presentation - April 2024TriStar Gold Corporate Presentation - April 2024
TriStar Gold Corporate Presentation - April 2024
 
Appkodes Tinder Clone Script with Customisable Solutions.pptx
Appkodes Tinder Clone Script with Customisable Solutions.pptxAppkodes Tinder Clone Script with Customisable Solutions.pptx
Appkodes Tinder Clone Script with Customisable Solutions.pptx
 
EUDR Info Meeting Ethiopian coffee exporters
EUDR Info Meeting Ethiopian coffee exportersEUDR Info Meeting Ethiopian coffee exporters
EUDR Info Meeting Ethiopian coffee exporters
 
Psychic Reading | Spiritual Guidance – Astro Ganesh Ji
Psychic Reading | Spiritual Guidance – Astro Ganesh JiPsychic Reading | Spiritual Guidance – Astro Ganesh Ji
Psychic Reading | Spiritual Guidance – Astro Ganesh Ji
 
Excvation Safety for safety officers reference
Excvation Safety for safety officers referenceExcvation Safety for safety officers reference
Excvation Safety for safety officers reference
 
Effective Strategies for Maximizing Your Profit When Selling Gold Jewelry
Effective Strategies for Maximizing Your Profit When Selling Gold JewelryEffective Strategies for Maximizing Your Profit When Selling Gold Jewelry
Effective Strategies for Maximizing Your Profit When Selling Gold Jewelry
 
14680-51-4.pdf Good quality CAS Good quality CAS
14680-51-4.pdf  Good  quality CAS Good  quality CAS14680-51-4.pdf  Good  quality CAS Good  quality CAS
14680-51-4.pdf Good quality CAS Good quality CAS
 
WSMM Technology February.March Newsletter_vF.pdf
WSMM Technology February.March Newsletter_vF.pdfWSMM Technology February.March Newsletter_vF.pdf
WSMM Technology February.March Newsletter_vF.pdf
 
Horngren’s Financial & Managerial Accounting, 7th edition by Miller-Nobles so...
Horngren’s Financial & Managerial Accounting, 7th edition by Miller-Nobles so...Horngren’s Financial & Managerial Accounting, 7th edition by Miller-Nobles so...
Horngren’s Financial & Managerial Accounting, 7th edition by Miller-Nobles so...
 
Cyber Security Training in Office Environment
Cyber Security Training in Office EnvironmentCyber Security Training in Office Environment
Cyber Security Training in Office Environment
 
Go for Rakhi Bazaar and Pick the Latest Bhaiya Bhabhi Rakhi.pptx
Go for Rakhi Bazaar and Pick the Latest Bhaiya Bhabhi Rakhi.pptxGo for Rakhi Bazaar and Pick the Latest Bhaiya Bhabhi Rakhi.pptx
Go for Rakhi Bazaar and Pick the Latest Bhaiya Bhabhi Rakhi.pptx
 
The Bizz Quiz-E-Summit-E-Cell-IITPatna.pptx
The Bizz Quiz-E-Summit-E-Cell-IITPatna.pptxThe Bizz Quiz-E-Summit-E-Cell-IITPatna.pptx
The Bizz Quiz-E-Summit-E-Cell-IITPatna.pptx
 
trending-flavors-and-ingredients-in-salty-snacks-us-2024_Redacted-V2.pdf
trending-flavors-and-ingredients-in-salty-snacks-us-2024_Redacted-V2.pdftrending-flavors-and-ingredients-in-salty-snacks-us-2024_Redacted-V2.pdf
trending-flavors-and-ingredients-in-salty-snacks-us-2024_Redacted-V2.pdf
 
Memorándum de Entendimiento (MoU) entre Codelco y SQM
Memorándum de Entendimiento (MoU) entre Codelco y SQMMemorándum de Entendimiento (MoU) entre Codelco y SQM
Memorándum de Entendimiento (MoU) entre Codelco y SQM
 
Driving Business Impact for PMs with Jon Harmer
Driving Business Impact for PMs with Jon HarmerDriving Business Impact for PMs with Jon Harmer
Driving Business Impact for PMs with Jon Harmer
 
The McKinsey 7S Framework: A Holistic Approach to Harmonizing All Parts of th...
The McKinsey 7S Framework: A Holistic Approach to Harmonizing All Parts of th...The McKinsey 7S Framework: A Holistic Approach to Harmonizing All Parts of th...
The McKinsey 7S Framework: A Holistic Approach to Harmonizing All Parts of th...
 
Introducing the Analogic framework for business planning applications
Introducing the Analogic framework for business planning applicationsIntroducing the Analogic framework for business planning applications
Introducing the Analogic framework for business planning applications
 

Considerations When Using Extended Field Wiring Lengths with Bently Nevada Transducers

  • 1. APPLICATIONS Considerations When Using Extended Field Wiring Lengths with Bently Nevada Transducers [Editor’s Note: This article is an abbreviated version of Bently Nevada Applications Note 178454. Due to space limitations, all available graphs, tables, and sample calculations have not been reprinted here from that Note. The interested reader is encouraged to download the full Note from the electronic version of our Reader Service Card for this issue of ORBIT, available at www.orbit-magazine.com.] T he standard maximum cable run for Bently Nevada* transducers has been specified for many years in our product manuals and datasheets as 1000 feet (305 meters). In some cases, however, users have found this limitation to be inconvenient and are interested in running field wiring over extended distances to suit their needs. Longer lengths can be accomplished, provided the user understands the engineering principles involved and is able to properly quantify the effects of longer cable lengths and assess the impact on their particular application. This article discusses the key issues with extended field wiring by showing how wiring length and construction effects capacitance and frequency response, by discussing the types of applications that are particularly dependent upon high-frequency signal content, and by discussing the concept of capacitance limits and its relationship to hazardous area installation requirements. The origin of the 1000 foot limit Thus, along with our recommendation for 18 AWG wire came a recommendation to limit the length to For many years, the field wiring for Bently Nevada trans- no more than 1000 feet (305 m) in non-hazardous ducers has been recommended as 18 AWG. Depending areas. This length was chosen both because it easy on the transducer type, either 2-conductor or 3-conduc- to remember and because it introduces only minimal tor cable is used. Although lighter gauges can also be signal degradation, allowing the full 10 kHz frequency used (such as 22 AWG), experience has shown that response of our typical transducers to pass with little lighter gauges have a greater tendency to break when attenuation. However, as will be discussed in this article, connecting to terminals on the monitor and transducer. this limit does not hold for all applications. Hazardous One of the limitations inherent with heavier gauge wire area applications and/or those for which the frequency is that it represents greater capacitance per unit length, response requirements differ from 0–10 kHz will require which in turn affects both the frequency response and the designer to carefully consider the field wiring’s suitability for hazardous areas where strict limits on effects on stored energy and signal attenuation. This total circuit capacitance are in effect. article, and its companion Applications Note, serve as primers on the subject, familiarizing installation designers with the engineering considerations and calculations involved. Jared Angel Sustaining Engineer GE Energy jared.angel@ge.com 5 2 O R B IT Vo l.27 N o.1 2007
  • 2. APPLICATIONS Cable Capacitance When using cable from another supplier, consult their datasheet or contact the manufacturer to obtain The frequency response of cable is affected by capacitive values. When this is not possible or practical, resistance, capacitance, and inductance. However, it will be necessary to determine these values yourself capacitance will usually be the first to cause problems. using the following equations: In addition, installations into areas with hazardous classifications usually limit the capacitive load allowed. • For two-wire circuits In either case, the total cable capacitance must be Total capacitance = capacitance core to core calculated and evaluated against the pertinent limits. + capacitance core to screen. C total = C core-to-core + C core-to-screen The total cable capacitance is a function of the following factors: • For three-wire circuits Total capacitance = (2 X capacitance core to core) • Cable length + capacitance core to screen. • Number of Conductors C total = (2*C core-to-core ) + C core-to-screen In most cases, field wiring will have two or three The goal is to determine the total capacitive load for conductors, depending upon the type of transducer a given length of cable. To find this, multiply the cable being used. Proximity transducers always use a capacitance per unit length by the total cable length. three-conductor system (power, signal, common) As has previously been noted, this total capacitive while other transducers either may not require load must be taken into account when considering the external power or may share the power/signal wire; hazardous area and signal integrity issues. consequently, they use a two-conductor system. Specific installations often run field wiring cable with • Cable Specifications lower capacitance than that offered by GE to mitigate The relevant values for field wiring analysis are long field wire lengths. This is successful when proper the cable capacitance per unit length and the engineering practices are applied to quantify the total capacitive load. The data sheet for cable will performance. typically lists its capacitance per unit length. If you cannot find this value, you can usually calculate it Applications from other datasheet values as explained below. Certain applications and measurements are known to Capacitance values for the field wiring provided by GE generate high-frequency content and are particularly for use with Bently Nevada transducers are shown in dependent upon field wiring that preserves the full Table 1. spectral integrity of the signal. This typically occurs when the machine itself runs at very high rotational Table 1 – Cable Capacitance for field wiring speeds and/or when the nature of the vibration tends provided by GE for use with Bently Nevada to generate a number of harmonics. Some common transducers applications and their dependence upon high-frequency Part Number Description Capacitance signal content are noted below. 02173006 18 AWG 98 pF/meter • Applications more dependent upon high- two-conductor frequency signals cable Gearboxes, turbine blade pass, rolling element 02120015 18 AWG 289 pF/meter bearing signatures, high-speed machines (e.g., three-conductor turbo expanders and the high speed stages of cable centrifugal air compressors), speed-sensing appli- cations with the sensor observing a toothed wheel. Vo l . 27 N o. 1 2007 ORB I T 53
  • 3. APPLICATIONS • Applications less dependent upon high- Signal Quality frequency signals Driving a large capacitive load can be problematic as Non-vibration measurements (e.g., thrust position, large loads can attenuate higher frequencies. What is differential expansion, case expansion), low-speed considered ‘too large’ will depend of the type of trans- machines (e.g., hydro turbine/generators, recipro- ducer being used and the frequencies of interest. Table cating compressors). 2 shows the frequency response of numerous Bently The above is intended only as a general guideline. Each Nevada vibration transducers along with notes regarding application must be evaluated on its own merits by cable lengths. Obviously, as long as the field wiring considering the construction of the machine, the fre- provides a frequency response as good or better than the quencies it is likely to generate under normal operating transducer itself, there will be no degradation of high-fre- conditions (blade pass, gear mesh, ball pass, etc.) and quency content introduced by the field wiring. However, the frequencies it is likely to generate under malfunction the total capacitance may exceed the allowable limits for conditions (cavitation, structural resonances, rough load hazardous area applications. Thus, when applicable, the zone, etc.). designer must carefully consider both before deciding upon an allowable maximum cable length. Table 2 – Field wiring and signal quality considerations for typical Bently Nevada transducers. Transducer Frequency Response Notes 3300XL 8mm and 0 - 10 kHz Extended field wire lengths can attenuate relevant NSv Proximitor* Sensor high-frequency content and affect measurement integrity. 3300XL 11mm 0 – 8 kHz Extended field wire lengths can attenuate relevant Proximitor Sensor high-frequency content and affect measurement integrity. 3300XL 25mm 0 – 2.7 kHz Extended field wire lengths will rarely be an issue for Proximitor Sensor frequency response considerations. 3300XL 50mm 0 - 50Hz Extended field wire lengths will rarely be an issue for Proximitor Sensor frequency response considerations. XL Radiation Resistant 15 ft. system: Extended field wire lengths can attenuate relevant Proximitor Sensor 0 – 10 kHz high-frequency content and affect measurement integrity. 40 ft. system: 0 – 9 kHz 110 ft system: 0 – 5 kHz LVDT n/a Extended field wiring lengths are not recommended under any circumstance due to the LVDT’s sensitivity to resistance. Velomitors Varies depending on Extended field wire lengths can attenuate relevant model. See pertinent high-frequency content and affect measurement integrity, transducer datasheet. depending on transducer frequency response. Accelerometers Varies depending on Extended field wire lengths can attenuate relevant high- model. See pertinent frequency content and affect measurement integrity. transducer datasheet Thermocouples n/a Extended field wiring lengths are not recommended under and RTDs any circumstances due to the sensor’s sensitivity to resistance. 5 4 O R B IT Vo l.27 N o.1 2007
  • 4. APPLICATIONS The manual for each transducer will typically provide a graph similar to Figure 1, showing the affect of total cable capacitance on frequency response. Figure 1 – Effect of field wiring total capacitance on frequency response for 3300 XL 8mm Proximity Transducer System (5 meter system length, no I.S. barriers) Frequency Response Calculation Examples Example 1 Goal Determine the frequency response attenuation that will Since this value is very close to the 440 nF curve of occur for a 3300 XL 8mm proximity transducer system (5 Figure 1, we will use that curve for estimation purposes. meter system length, no barriers) when 1500 m of GE’s When computing signal strength, it is customary to use standard 18 AWG 3-conductor field wiring is used. the -3db point as the so-called cut-off frequency (–3dB represents a signal that has only one-half of the original Solution amplitude). The –3dB point for 440nF of total field wiring Using the value of 289 pF/m from Table 1 for 3-conduc- capacitance is approximately 5 kHz. Thus, by introduc- tor field wiring, the total cable capacitance for 1500 m ing 1500 meters of field wiring, we have reduced the 10 is found simply as: kHz frequency response of the transducer system to 289 pF/m x 1500 m = 433,500 pF = 433.5 nF approximately 5 kHz. Vo l . 27 N o. 1 2007 ORB I T 55
  • 5. APPLICATIONS Example 2 Intrinsically Safe (I.S.) The apparatus is incapable of releasing sufficient elec- Goal trical or thermal energy under normal and abnormal Determine whether the transducer installation of operating conditions to cause ignition of a specific example 1 would be acceptable for a speed-indication flammable atmosphere. application using a 60-tooth wheel on a turbine running at 6200 rpm. As can be seen, I.S. is a more stringent requirement, requiring a design that limits the energy under both nor- Solution mal and abnormal operating conditions. Consequently, A proximity transducer observing a 60-tooth wheel designers will find that the maximum capacitance turning at 6200 rpm will generated a square-wave allowed for I.S. installations is more restrictive than type pulse with nominal frequency of: for N.I. installations. Also, although both inductors and 60 teeth/rev x 1 pulse/tooth x 6200 rev/min = 372,000 capacitors can store energy, the energy stored in the pulses per min = 6200 pulses/sec = 6.2 kHz. capacitance of the field wiring is much larger than that stored by the wiring’s inductance for our transducer/ Clearly, the cable length introduces too much attenua- monitor applications. Agency approvals work on the tion at this frequency, particularly since a “clean” square basis of “most restrictive.” In other words, the designer wave signal is necessary for a tachometer to trigger reli- looks at the cable lengths that will result in either exces- ably. At this frequency (6200 Hz), even the fundamental sive capacitive energy or excessive inductive energy, (1X) component of the square wave will be attenuated and uses the more restrictive constraint. Invariably, as by more than 4 dB as noted in Figure 1. The user would noted, capacitance turns out to be the limiting factor either need to shorten the field wiring length or choose for our applications. Consequently, the discussion here field wiring with a lower capacitance-per-meter rating. confines itself only to capacitance. However, be aware Hazardous Area Considerations that with other electrical or electronic apparatus you encounter, inductance may be the limiting factor. The Another extremely important issue with extended astute designer will know when an installation will need length field wiring is the need to remain compliant with to be concerned with capacitive constraints instead of hazardous area classifications when applicable. Today, inductive constraints, and vice-versa. the most common methods of complying with hazard- ous area classifications are through the use of designs I.S. installations rely on special current/voltage limiting that are either intrinsically safe (in the case of Zone 0/1 devices, such as galvanic isolators or so-called I.S. barri- areas) or nonincendive (in the case of Zone 2 areas). The ers. Although each uses different principles of operation, principle behind such designs is to limit the amount of the idea of an energy-limiting circuit is the same. When available energy such that a flammable atmosphere external barriers are used, a small voltage drop occurs cannot be ignited under the appropriate conditions. across the resistance of the barrier. Bently Nevada monitoring systems designed for use with external bar- Nonincendive (N.I.) riers allow the user to compensate for this small voltage The apparatus is incapable of releasing sufficient drop. Systems that are available with internal barriers, electrical or thermal energy under normal operating such as 3300 and 3500, provide this compensation conditions to cause ignition of a specific flammable automatically; it is transparent to the user. atmosphere. 5 6 O R B IT Vo l.27 N o.1 2007
  • 6. APPLICATIONS When considering the allowable maximum length of C total = C cable + Ci ≤ 0.2μF field wiring, the designer consults the appropriate tables C total = C cable + Ci ≤ 200nF and specifications for the particular zone, atmosphere, and Bently Nevada hardware type, allowing the C cable + 6nF ≤ 200nF maximum capacitance available for field wiring to be C cable ≤ 194nF determined. One the maximum capacitance has been determined, the maximum field wiring length can be C cable ≤ 194,000pF readily ascertained. Similar calculations are also per- Now, since we have found the maximum total cable formed to determine the maximum field wiring length capacitance Ccable, the maximum allowable length is while retaining the necessary frequency response for simply Ccable divided by the capacitance per unit length the application. Finally, the designer chooses the more (which is found in Table 1): restrictive of these two constraints (frequency response C cable = 194,000pF or hazardous area) and this becomes the governing Lmax = 289pF/m 289pF/m criteria for the maximum cable length. Several examples follow that demonstrate these Lmax = 671m concepts for typical monitoring system hardware. [Editor’s Note: Due to space limitations, only selected tables from the It is worth noting that while up to 671 m of this field Applications Note have been provided here, allowing the reader to wiring would allow the system to remain within perform the sample calculations below.] hazardous area constraints, it introduces 194 nF of Hazardous Area Calculation Examples total capacitance which affects the frequency response adversely. Referring again to Figure 1 (we will use the Example 3 curve for 176 nF since it is close to the actual value of Goal 194 nF), it can be seen that the –3dB point is now less Determine the maximum cable length Lmax allowed in than 10 kHz (somewhere between 8 and 8.5 kHz). Thus, a Zone 2 area with atmosphere type IIC for a channel for applications that require the full 10 kHz frequency using a 3500/42M monitor with Prox/Vel I/O module and response of the proximity transducer, the field wiring a 3300 XL 8mm Proximity Probe (5 meter system length). would have to be shortened until the attenuation was Assume the use of field wiring with Bently Nevada part within acceptable limits. number 02120015. Solution Using Table 3, it can be seen that the maximum allow- Project Services able connected capacitance Co for a 3500/42 monitor Although many customers will feel comfort- with a Prox/Vel I/O module (p/n 140471-XX) is 0.2 μF (200 able performing these calculations themselves nF) regardless of atmosphere (gas) type. Next, per the and managing the installation of transducers, published specifications in the 3300XL 8mm proximity monitors, and associated field wiring, other transducer system datasheet, the input capacitance Ci customers prefer to use GE’s project services of the Proximitor module is 5.7 nF, which we round off to capabilities. These services can be provided 6 nF. This allows us to determine the maximum allowable for selected portions of a project, such as field total capacitance of the field wiring, Ccable, as follows: wiring calculations; or, they can be provided as part of a broader scope, such as preparation of drawings, supervision of subcontractors, and field machining services to retrofit or upgrade instrumentation on exist- ing machinery. 2007 ORB I T 57 Vo l . 27 N o. 1
  • 7. APPLICATIONS Table 3 – Maximum capacitance for 3500 monitoring system I/O modules in Zone 2 hazardous areas for gas group IIA - IIC Module Number Co by gas group (uF) IIC IIB IIA 146031-01, 3500/22M-01 1000 140471-01,-02 3500/25, 3500/4x Prox / Velomitor 3500/64 0.2 169459-01, -02, 350 0/4x Multimode, Prox/Velom (IT and ET) 0.2 169715-01, -02, 3500/4x, Multimode Positive Input (IT and ET) 0.1 125800-01, 3500/25 0.2 133819-02, 3500/61, Thermocouple and RTD 1.56 10.5 42 133835-02, 3500/61, Isolated Thermocouple 1.56 10.5 42 136491-01, 3500/62, +/- 10Vdc I/O 1.71 1.71 48 Example 4 Goal Assume the details given in example 3; however, Thus, field wiring cable should be chosen with a installation constraints now require that the transducer capacitance per unit length less than or equal to 194 system be located a minimum of 1000m from the moni- pF/m. Since this value is less than the standard 18 AWG tor system. Find the maximum cable capacitance per 3-conducter field wiring cable of Table 1, GE’s standard unit length that can be used. cable cannot be used and an alternative cable type meeting the required capacitance per unit length must Solution be employed. The maximum total cable capacitance Ccable is the same as in example 3; namely, 194,000 pF. Here, however, we As pointed out in example 3, although the length of are given the length and need to find the capacitance field wiring used here will allow the system to remain per unit length CUL. within the constraints imposed by the hazardous area Ccable 194,000pF criteria, it will result in some roll-off of the frequency Lmax = CUL = CUL 1000m response. As such, this length of field wiring may or may not be acceptable depending on whether the full 10 Ccable kHz frequency response available from the proximity CUL = CUL = 194pF/m Lmax transducer is required or not. 5 8 O R B IT Vo l.27 N o.1 2007
  • 8. APPLICATIONS Example 5 Summary Goal Long field wiring lengths are sometimes required Determine the maximum cable length Lmax for the channel described in Example 3 except now it must be due to the nature of the cable runs and plant suitable for a Zone 0 classified area with gas group IIC. layout. This introduces additional capacitance and Assume that the 3500 monitor uses an I/O module for Prox/Accel with internal barriers. Assume also the same can affect the integrity of the monitoring system in field wiring type as example 3. one or both of the following ways: Solution Using Table 4, it can be seen that the maximum • By attenuating high frequencies in the allowable connected capacitance Co for a 3500/42 vibration signal monitor with an internal barrier Prox/Vel I/O module (p/n 135470-01) is 0.083μF (83 nF). Also, as before, the input • By allowing too much stored electrical energy, capacitance Ci of the Proximitor module is approxi- mately 6 nF. This allows us to determine the maximum violating hazardous area certification limits allowable total capacitance of the field wiring, Ccable, as follows. In order to determine the maximum length of field wiring, the designer must therefore understand Table 4 – Maximum capacitance for 3500 moni- toring system I/O modules in Zone 0/1 hazardous both the necessary frequency response required areas with gas group IIC atmospheres by the application and the allowable maximum Barrier Module Number Co by gas group (uF) capacitance for the particular hazardous area 135470-01, Proximitor & 0.083 classification (when applicable). The calculations Accelerometer 135471-01, Velomitor 0.088 allow the designer to determine either the maxi- mum length of standard field wiring cable that can 137101-01, Process Variable 0.76 be used, or the maximum capacitance per unit 135472-01, Temperature 8.8 length of alternate field wiring, allowing cable with appropriate specifications to be procured. C total = C cable + Ci ≤ 0.083μF *Denotes a trademark of the General Electric Company. C total = C cable + Ci ≤ 83nF C cable + 6nF ≤ 83nF C cable ≤ 77nF C cable ≤ 77,000pF Finally, the maximum allowable length is found using the same equation as 3. C cable = 77,000pF Lmax = 289pF/m 289pF/m Lmax = 266m Vo l . 27 N o. 1 2007 ORB I T 59