2. 2013 NFPA 72 Changes
Fire Alarm System Documentation
Requirements – Chapter 7
Proper documentation is required to properly install
and maintain the system:
Design layout documentation
Shop Drawings
Record (As-Built) drawings
OM Manuals
Electronic Site Specific Software
02/06/14
2
3. 2013 NFPA 72 Changes
Fire Alarm System Documentation Requirements – Chapter 7
•
•
•
New Systems
Design
Acceptance
Completion
7.1.1 – Documentation of new
systems shall comply with the
minimum requirements of this
chapter.
02/06/14
X
•
•
•
Existing Systems
Alteration
Maintenance
Testing
7.1.2-Documentation of the
alteration of existing systems
shall comply with the minimum
requirements of this chapter.
3
4. 2013 NFPA 72 Changes
Minimum Documentation Required – 7.2.1
•
•
•
•
•
•
02/06/14
Written Narrative
Riser Diagram
Floor Plan
Sequence of Operation
X
Equipment Technical Data Sheets
Manufacturers Published Instructions
4
5. 2013 NFPA 72 Changes
Minimum Documentation Required – 7.2.1
•
•
•
•
•
•
02/06/14
Battery Calculations
Voltage Drop Calculations
Completed Record of Completion
Completed Record of Inspection and Testing
X
Site Specific Software (Electronic Copy)
Record (As-Built) Drawings
5
6. 2013 NFPA 72 Changes
Minimum Documentation Required – 7.2.2
•
The person responsible for the design (layout) shall be identified on the
system design documents.
Minimum Documentation Required – 7.2.3
X
•
02/06/14
All fire alarm drawings shall use symbols described in NFPA 170, Standard
for Fire Safety and Emergency Symbols
6
9. 2013 NFPA 72 Changes
Design Documentation Audible Notification
•
•
•
Design sound pressure levels indicated
Ambient noise indicated
Audible design sound pressure levels
X
Design Documentation Visible Notification
•
•
02/06/14
Designation of rooms that will have visible notification
Performance based design alternatives for strobe design
9
10. 2013 NFPA 72 Changes
Records Retention
•
•
•
•
02/06/14
Keep all test records for 1 year, and all must be available to AHJ
Design documentation must be kept for the life of the system
All new systems require a records cabinet at the FACU or another
approved location, all documentation must be stored there
X
A copy of site specific, non volatile, non-erasable, non-rewritable software
must be provided the Owner
10