7. LV Switchgear – Arc Flash Requirements
IEEE1584 & NFPA 70E
Non IAC LV switchgear
IAC LV Switchgear
The US regulations do not require the use of Arc rated PPE
on IAC switchgear when carrying out normal operations.
Refer NFPA 70E-12 Hazard Risk Category 130C)(15)(a)
11. Active Arc Fault Protection Options
1. Short-circuit
protection on the LV switchboard
incoming supply.
AS/NZS 3000:2007 clause 2.5.5.3 looks at limiting the
damage to a switchboard due to an internal arcing.
2. Arc detection Systems
AS/NZS 3000:2007 clause 2.5.5.3 also look at arc fault
protection using arc detectors and warn of the problems of
extraneous light sources and discrimination.
3. Arc Detectors in conjunction with an Ultra Fast
Earthing Switch (UFES)
The NFPA 70E-12 Hazard Risk Category 130C)(15)(a)
says for non IAC LV MCC’s up to 65kA where the arc
duration is 30ms Arc Rated PPE is not required to carry
out normal operations
14. Arc Fault Protection
Safety by Design
Active protection devices, in comparison to passive
protection, are more susceptible to failure owing to the
additional electromechanical and electronic devices
The proven way is to prevent the fault arcs from occurring
in the first place, eliminate the need to work live and then in
the unlikely event of an internal arc contain the arc to that
compartment
Safety by Design
• Withdrawable Design.
• All operations behind closed
doors
• Internal Arc Fault
Containment