1. COMPRESSOR
01xCo RG59
1P-CFTV-01
SOBEM CABOS DO 1º
PAVIMENTO PARA O 2º
PAVTO. ATRAVÉS DE
ELETROCALHA LISA COM
TAMPA 150x100mm
DESCEM CABOS DO 2º
PAVIMENTO PARA O 1º
PAVTO. ATRAVÉS DE
ELETROCALHA LISA COM
TAMPA 150x100mm
CIRCULAÇÃO
SOBE CABO DE SONORIZAÇÃO
(2x2,5mm²) DO 1º PAVTO. PARA
O 2º PAVTO. ATRAVÉS DE
ELETRODUTO DE AÇO
GALVANIZADO - Ø1"(25mm)
I. S.
SALA DE REUNIÃO E EDUCAÇÃO
ARMÁRIO METÁLICO DO
TIPO RACK 12 Us COM
PORTA PARA
EQUIPAMENTOS DE ÁUDIO
PADRÃO 19": SUSTENTAÇÃO
DA MATRIZ 8x8 E DO
AMPLIFICADOR
PT-1P-CFTV-05
01xCo RG59
1P-CFTV-05
PAGGING
SON-T1A
SF-2P-01
SF-2P-02
SF-1P-01
SF-1P-02
SF-1P-03
AT-T1A
SF-1P-05
SF-1P-04
PT-2P-CFTV-02
PT-2P-CFTV-01
PT-1P-CFTV-01
PT-1P-CFTV-02
COLETA
PT-1P-CFTV-03
PT-1P-CFTV-04
01xCo RG59
2P-CFTV-02
01xCo RG59
2P-CFTV-01
ESTERILIZAÇÃO
01xCo RG59
2P-CFTV-01
02xCo RG59
02xCo RG59 2P-CFTV-01 a 02
2P-CFTV-01 a 02
02xCo RG59
1P-CFTV-01 a 02
04xCo RG59
1P-CFTV-01 a 02
2P-CFTV-01 a 02
04xCo RG59
1P-CFTV-01 a 02
2P-CFTV-01 a 02
01xCo RG59
1P-CFTV-03
01xCo RG59
1P-CFTV-04
05xCo RG59
1P-CFTV-01 a 03
2P-CFTV-01 a 02
07xCo RG59
1P-CFTV-01 a 05
2P-CFTV-01 a 02
02xCo RG59
1P-CFTV-04 a 05
DESCE CABO DE
SONORIZAÇÃO (2x2,5mm²) DO
2º PAVTO. PARA O 1º PAVTO.
ATRAVÉS DE ELETRODUTO
DE AÇO GALVANIZADO -
Ø1"(25mm)
VACINAÇÃO
SALA DE ESPERA
I.S. MASC.
RECEPÇÃO
TRIAGEM
CIRCULAÇÃO
GINECOLOGIA
DML
ALMOXARIFADO
VARANDA COBERTA
I.S. FEM.
ESCOVÁRIO
RESÍDUOS
RESÍDUOS
CIRCULAÇÃO
GUICHÊ
COPA
TV SUSPENSA
VAGA PARA AMBULÂNCIA
FOSSO
ESCANINHOS
ÁREA PERMEÁVEL
ÁREA PERMEÁVEL
proj. da cobertura
CALÇADA
RUA
PROJEÇÃO CAIXA D'ÁGUA
ALÇAPÃO
LAVAGEM E
DESINFECÇÃO DE MATERIAIS
DML
proj. da
cobertura
SALA DE APOIO
AGENTES
ENDEMIAS
APOIO AGENTES
ENDEMIAS
SALA DE
CURATIVOS
CUIDADOS
BÁSICOS
ATENDIMENTO
MULTIPROFISSIONAL
ATENDIMENTO
MULTIPROFISSIONAL
GUARDA
MEDICAMENTOS
REBAIXO NA CALÇADA P/
ACESSO DE VEÍCULOS
REBAIXO NA CALÇADA P/
ACESSIBILIDADE
CONSULTÓRIO
ODONTOLÓGICO
VESTIÁRIO
MASCULINO
VESTIÁRIO
FEMININO
1-PROIBIDA REPRODUÇÃO OU ALTERAÇÃO DO CONTEÚDO SEM AUTORIZAÇÃO DOS RESPONSÁVEIS TÉCNICOS DO PROJETO.
2-DIREITOS AUTORAIS RESERVADOS - LEI FEDERAL 9.610 DE 19/02/1996.
3-CONFERIR MEDIDAS NO LOCAL.
RESOLUÇÃO 1797/09 DA SES-MG
03 ADEQUAÇÃO DA ARQUITETURA CONFORME VISA 31/01/2013 VIABILE
02 EMISSÃO FINAL 08/11/2012 VIABILE
00 EMISSÃO INICIAL 22/10/2012 VIABILE
VERIFICAÇÃO
Secretaria de Estado de Saúde de Minas Gerais
Cidade Administrativa Presidente Tancredo Neves
Rodovia Pref. Américo Gianetti s/nº - Bairro: Serra Verde - B. Hte -
Minas Gerais - CEP: 31630-900 SES-MG Predio Minas - 12º e 13º andar
FOLHA:
02
02
REVISÃO OBJETO DATA
GERENCIAMENTO E PROJETO:
DESENVOLVIMENTO:
BRENO DE ASSIS OLIVEIRA FEVEREIRO/2013
PROJETO DE SONORIZAÇÃO/CFTV/ALARME
VÁRIAS UNIDADES NO ESTADO DE MINAS GERAIS
ETAPA:
PLANTAS PROJETO EXECUTIVO
Av. Augusto de Lima, nº655
conj. 418 - Centro - BH
Telefax: (31) 3324-2702
http://www.viabile.com.br
viabile@viabile.com.br
DATA:
NOME DO ARQUIVO CAD:
ESCALA: UNIDADE:
INDICADA CENTÍMETROS
CREA-MG: 78.667/D
RESPONSÁVEL TÉCNICO:
BRENO DE ASSIS OLIVEIRA
PROPRIETÁRIO:
SECRETARIA DO ESTADO DE SAÚDE DE MINAS GERAIS
460-UBSSS-R03-ESO-02-PE-T1A.DWG
UBS MINAS - PROJETO MODELO
DISCIPLINA:
PROJETO:
ENDEREÇO:
CONTEÚDO:
NOTAS:
4-COTAS EM CENTÍMETROS.
SUBSECRETARIA DE VIGILÂNCIA E PROTEÇÃO Á SAÚDE
SUPERINTENDÊNCIA DE VIGILÂNCIA SANITÁRIA
DIRETORIA DE INFRAESTRUTURA FÍSICA
PROJETO MODELO UNIDADE BÁSICA DE SAÚDE
PROJETO DE ACORDO COM RDC-50/2002 E
É DE RESPONSABILIDADE DO MUNICIPIO APROVAÇÃO
COM A IMPLANTAÇÃO NO TERRENO ESCOLHIDO.
TIPO T1A - ACLIVE
FORMATO INTERNACIONAL A1 (841 x 594mm)
abrasip-mg
SONORIZAÇÃO - 1° PAVIMENTO
ESCALA: ......................................................................... 1/75
SONORIZAÇÃO - 2° PAVIMENTO
ESCALA: ......................................................................... 1/75
01 MUDANÇA DE ARQUITETURA 26/10/2012 VIABILE
SUBSECRETARIA DE INOVAÇÃO E LOGISTICA
SUPERINTENDENCIA DE GESTÃO
DIRETORIA DE GESTÃO DA REDE FÍSICA
2. SIMBOLOGIA - SONORIZAÇÃO:
SÍMBOLO DESCRIÇÃO
ELETROCALHA METÁLICA LISA COM VIROLA DO TIPO "C" E TAMPA DE PRESSÃO (DIMENSÕES: 150x100mm).
COMPARTILHADA COM CABEAMENTO ESTRUTURADO.
ELETRODUTO DE AÇO GALVANIZADO FIXADO ATRAVÉS DE TIRANTES NA ESTRUTURA - Ø1"(25mm) OU
CONFORME INDICAÇÃO. REF.: ELECON.
CAIXAS METÁLICAS DE PASSAGEM DO TIPO CONDULETE MÚLTIPLO - TIPOS X, T, LL, E, LR e C
RESPECTIVAMENTE, CONFORME NBR-15.701
SONOFLETOR (ALTO-FALANTE) COAXIAL 6" POTÊNCIA 25Wrms IMPEDÂNCIA 8 OHMS DO TIPO ARANDELA NA
COR BRANCA. REF.: ARANDELA 6CO2R, DA SELENIUM.
CÂMERA COLORIDA PARA SISTEMA DE CFTV INSTALADA EM CAIXA BLINDADA COM FONTE 127V NO INTERIOR
DA CAIXA, INSTALADA EM PAREDE h=2,20m OU CONFORME INDICAÇÃO. DEVERÃO SER INSTALADAS DUAS
CAIXAS 2x4", SENDO UMA PARA A ALIMENTAÇÃO ELÉTRICA E OUTRA PARA A PASSAGEM DO CABO DE VÍDEO.
CABO UTP
RACK
MATRIZ 8x8
AMPLIFICADOR
CAIXAS
SALA DE
ESPERA
CAIXAS
CIRCULAÇÃO
1ºPAVTO.
CAIXAS
CIRCULAÇÃO
2ºPAVTO.
PAGGING/
MICROFONE
CABO UTP CAT 6
DIAGRAMA ESQUEMÁTICO DE
INTERLIGAÇÃO
SONOFLETORES NO FORRO
CHUMBADOR ROSCA
INTERNA Ø1/4"
PORCA SEXTAVADA E
ARRUELA LISA Ø1/4"
ELETRODUTOS (PENDENTE)
RACK METÁLICO FECHADO 19"x12Us PROF.:
670mm COM PORTA DE VIDRO, EQUIPADO COM
RÉGUA DE 10 TOMADAS 2P+T LIGADA AO
NO-BREAK
GAVETA DE VENTILAÇÃO PADRÃO 19" C/
QUATRO VENTILADORES
MATRIZ DE ÁUDIO 8x8 (8 in / 8 out)
NO-BREAK 600VA/127V PADRÃO 19" COM
AUTONOMIA MÍNIMA DE 15 MINUTOS
ELETRODUTO AÇO
GALVANIZADO (Ø CONF.PROJ
PAR DE FIOS POLARIZADOS
BRAÇADEIRA
TIPO "D" BUCHA PLÁSTICA
DETALHE SUGESTIVO DO ARMÁRIO DE SONORIZAÇÃO
1º PAVIMENTO - RECEPÇÃO
SEM ESCALA
AMPLIFICADOR LINHA 70V 150Wts RMS / CANAL -
(110/220V)
DVR 16 CANAIS BNC/1 SAÍDA BNC/1 SAÍDA VGA,
VELOCIDADE MÍNIMA 120fps NTSC E
COMUNICAÇÃO DE REDE RJ-45 EM PROTOCOLO
TCP/IP
ABRAÇADEIRA
CIRCULAR
ELETRODUTO AÇO
GALVANIZADO (Ø
CONF.PROJ.)
TIRANTE ROSCA
TOTAL Ø1/4"
DETALHE TÍPICO DE FIXAÇÃO DOS
FIXAR A CADA 1,50m (NO MÁXIMO)
SEM ESCALA
ELETRODUTO DE
AÇO
GALVANIZADO
S6 E PARAFUSO
DETALHE FIXAÇÃO DO ELETRODUTO
FIXAÇÃO DIRETA EM PAREDES OU LAJE
SEM ESCALA - SUPORTAR A CADA 1,50m
PASSAGEM POR OBSTÁCULOS
LAJE
FORRO
SONOFLETOR (ALTO-FALANTE)
CAIXA DE PASSAGEM
4"x4"
BRAÇADEIRA TIPO "D"
C/ UNHA A CADA 2m
DETALHE TÍPICO DE FIXAÇÃO DOS
SEM ESCALA
ELETRODUTOS PVC/AÇO
e
mm
e
mm
2,3
2,7
2,9
3,0
3,1
3,8
4,0
5,0
DIÂMETRO
NOMINAL-DN
mm POL
EXTERNO-DE
mm
DIÂMETRO
NOMINAL-DN
mm
25
32
40
50
60
75
85
110
POL
3/4
1
1.1/4
1.1/2
2
2.1/2
3
4
EXTERNO-DE
mm
25,9
33,0
42,0
47,4
59,0
74,7
87,6
113,1
ELETRODUTOS DE AÇO CARBONO, TIPO LEVE I, CONF. NBR 5624
ESPESSURA NOMINAL DA PAREDE
ELETRODUTOS DE PVC RÍGIDO ROSQUEÁVEL, CLASSE B, CONF. NBR 6150
ESPESSURA NOMINAL DA PAREDE
1,5
1,5
2,0
2,25
2,25
2,85
2,65
2,65
20
25
32
40
50
65
80
100
3/4
1
1.1/4
1.1/2
2
2.1/2
3
4
25,2
31,5
40,5
46,6
58,4
74,1
86,8
111,6
NOTAS GERAIS:
1 - MEDIDAS EM MILÍMETROS, EXCETO ONDE INDICADO.
2 - CONSIDERAR AS MEDIDAS DAS COTAS PRIORITÁRIAS EM RELAÇÃO À ESCALA.
3 - OS ELETRODUTOS UTILIZADOS DEVERÃO SER DE AÇO GALVANIZADO, COM NO MÍNIMO Ø1" (25mm).
4 - EM TODAS AS DERIVAÇÕES DEVERÃO SER UTILIZADAS CAIXAS DE PASSAGEM DO TIPO CONDULETE METÁLICO.
5 - OS LANCES ENTRE DUAS CAIXAS DE PASSAGEM NÃO DEVERÃO CONTER MAIS DO QUE DUAS CURVAS,
EVITANDO-SE TAMBÉM CURVAS REVERSAS SEMPRE QUE POSSÍVEL.
6 - OS ELETRODUTOS DEVERÃO SER PROVIDOS DE BUCHAS E ARRUELAS EM SUAS EXTREMIDADES, EXCETO
AQUELAS QUE TERMINAM EM CAIXAS DE PASSAGEM.
7 - SONDAR OS ELETRODUTOS COM ARAME OU CABO DE NYLON, DEIXANDO UMA SOBRA DE ± 1,0m EM CADA
CAIXA ANTES DA PASSAGEM DOS CABOS.
8 - AS PONTAS DE TODOS OS CABOS DEVERÃO SER IDENTIFICADAS COM ETIQUETAS TERMOCONTRÁTEIS OU
OUTRO MÉTODO QUE NÃO PERMITA A RETIRADA DA IDENTIFICAÇÃO SEM DANIFICAR O CABO. OS CABOS
DEVERÃO SER IDENTIFICADOS CONFORME DESCRITO NESTE PROJETO.
9 - TODAS AS CONEXÕES ENTRE AMPLIFICADORES, SONOFLETORES, DVR E CÂMERAS DE VÍDEO DEVERÃO
UTILIZAR OS CONECTORES APROPRIADOS EM CADA PONTA.
10 - ATERRAR TODAS AS PARTES METÁLICAS NÃO ENERGIZADAS DA INSTALAÇÃO.
11 - TODOS OS SONOFLETORES (ALTO-FALANTES) DEVERÃO TER SUA POLARIDADE TESTADA NO LOCAL,
EVITANDO-SE O CANCELAMENTO SONORO NA INTERLIGAÇÃO INVERTIDA.
12 - O DVR DEVERÁ SER INTERLIGADO À REDE, E A GRAVAÇÃO DE IMAGENS SERÁ REALIZADA EM COMPUTADOR
DEFINIDO COMO SERVIDOR. O SERVIDOR SERÁ FORNECIDO PELA SES/MG, E NÃO FAZ PARTE DO ESCOPO DA
EMPRESA INSTALADORA.
13 - PREVER UMA TOMADA ELÉTRICA PARA CADA CÂMERA A SER INSTALADA.
1-PROIBIDA REPRODUÇÃO OU ALTERAÇÃO DO CONTEÚDO SEM AUTORIZAÇÃO DOS RESPONSÁVEIS TÉCNICOS DO PROJETO.
2-DIREITOS AUTORAIS RESERVADOS - LEI FEDERAL 9.610 DE 19/02/1996.
3-CONFERIR MEDIDAS NO LOCAL.
RESOLUÇÃO 1797/09 DA SES-MG
03 ADEQUAÇÃO DA ARQUITETURA CONFORME VISA 01/02/2013 VIABILE
02 EMISSÃO FINAL 08/11/2012 VIABILE
00 EMISSÃO INICIAL 22/10/2012 VIABILE
VERIFICAÇÃO
Secretaria de Estado de Saúde de Minas Gerais
Cidade Administrativa Presidente Tancredo Neves
Rodovia Pref. Américo Gianetti s/nº - Bairro: Serra Verde - B. Hte -
Minas Gerais - CEP: 31630-900 SES-MG Predio Minas - 12º e 13º andar
FOLHA:
01
02
REVISÃO OBJETO DATA
GERENCIAMENTO E PROJETO:
DESENVOLVIMENTO:
BRENO DE ASSIS OLIVEIRA FEVEREIRO/2013
PROJETO DE SONORIZAÇÃO
VÁRIAS UNIDADES NO ESTADO DE MINAS GERAIS
ETAPA:
SIMBOLOGIA, NOTAS GERAIS E DETALHES PROJETO EXECUTIVO
CONSTRUTIVOS
Av. Augusto de Lima, nº655
conj. 418 - Centro - BH
Telefax: (31) 3324-2702
http://www.viabile.com.br
viabile@viabile.com.br
DATA:
NOME DO ARQUIVO CAD:
ESCALA: UNIDADE:
INDICADA CENTÍMETROS
CREA-MG: 78.667/D
RESPONSÁVEL TÉCNICO:
BRENO DE ASSIS OLIVEIRA
PROPRIETÁRIO:
SECRETARIA DO ESTADO DE SAÚDE DE MINAS GERAIS
460-UBSSS-R03-ESO-01-PE-T1A.DWG
UBS MINAS - PROJETO MODELO
DISCIPLINA:
PROJETO:
ENDEREÇO:
CONTEÚDO:
NOTAS:
4-COTAS EM CENTÍMETROS.
SUBSECRETARIA DE VIGILÂNCIA E PROTEÇÃO Á SAÚDE
SUPERINTENDÊNCIA DE VIGILÂNCIA SANITÁRIA
DIRETORIA DE INFRAESTRUTURA FÍSICA
PROJETO MODELO UNIDADE BÁSICA DE SAÚDE
PROJETO DE ACORDO COM RDC-50/2002 E
É DE RESPONSABILIDADE DO MUNICIPIO APROVAÇÃO
COM A IMPLANTAÇÃO NO TERRENO ESCOLHIDO.
TIPO T1A - ACLIVE
FORMATO INTERNACIONAL A1 (841 x 594mm)
abrasip-mg
01 MUDANÇA DE ARQUITETURA 26/10/2012 VIABILE
SUBSECRETARIA DE INOVAÇÃO E LOGISTICA
SUPERINTENDENCIA DE GESTÃO
DIRETORIA DE GESTÃO DA REDE FÍSICA
4. 850 1471 (kW) (kVA) (V) R S T (A) (A)
0 0 0,95 1,41 1,48 220 2 RS 0,74 0,74 0,00 6,74 2 x 16 C 1 4,0
0 0 0,95 1,02 1,08 220 2 TR 0,54 0,00 0,54 4,90 2 x 16 C 1 4,0
0 0 0,95 0,41 0,43 220 2 ST 0,00 0,22 0,22 1,97 2 x 16 C 1 2,5
0 0 0,95 0,48 0,51 220 2 RS 0,25 0,25 0,00 2,30 2 x 16 C 1 2,5
0 0 0,95 0,67 0,71 220 2 TR 0,35 0,00 0,35 3,22 2 x 16 C 1 4,0
0 0 0,85 0,68 0,80 127 1 R 0,80 0,00 0,00 6,30 1 x 16 C 1 4,0
0 0 0,85 0,94 1,10 127 1 S 0,00 1,10 0,00 8,66 1 x 16 C 1 4,0
0 0 0,85 0,85 1,00 127 1 T 0,00 0,00 1,00 7,87 1 x 16 C 1 4,0
0 0 0,85 0,94 1,10 127 1 R 1,10 0,00 0,00 8,66 1 x 16 C 1 4,0
0 0 0,85 0,60 0,70 127 1 S 0,00 0,70 0,00 5,51 1 x 16 C 1 4,0
0 0 0,85 0,60 0,70 127 1 T 0,00 0,00 0,70 5,51 1 x 16 C 1 4,0
0 0 0,85 0,68 0,80 127 1 S 0,00 0,80 0,00 6,30 1 x 16 C 1 4,0
0 0 0,85 0,43 0,50 127 1 S 0,00 0,50 0,00 3,94 1 x 16 C 1 4,0
0 0 0,85 0,68 0,80 127 1 R 0,80 0,00 0,00 6,30 1 x 16 C 1 4,0
0 0 0,85 0,51 0,60 127 1 S 0,00 0,60 0,00 4,72 1 x 16 C 1 4,0
0 0 0,85 1,53 1,80 127 1 T 0,00 0,00 1,80 14,17 1 x 16 C 1 6,0
0 0 0,85 0,68 0,80 127 1 T 0,00 0,00 0,80 6,30 1 x 16 C 1 4,0
0 0 0,85 0,77 0,90 127 1 S 0,00 0,90 0,00 7,09 1 x 16 C 1 4,0
0 0 0,85 0,70 0,82 127 1 R 0,82 0,00 0,00 6,44 1 x 16 C 1 4,0
0 0 0,85 1,11 1,31 220 2 RS 0,65 0,65 0,00 5,94 2 x 16 C 1 4,0
0 0 0,85 1,11 1,31 220 2 TR 0,65 0,00 0,65 5,94 2 x 16 C 1 4,0
0 0 0,85 1,11 1,31 220 2 ST 0,00 0,65 0,65 5,94 2 x 16 C 1 4,0
0 0 0,85 1,11 1,31 220 2 RS 0,65 0,65 0,00 5,94 2 x 16 C 1 4,0
0 0 0,85 1,11 1,31 220 2 TR 0,65 0,00 0,65 5,94 2 x 16 C 1 4,0
0 0 0,85 1,11 1,31 220 2 ST 0,00 0,65 0,65 5,94 2 x 16 C 1 4,0
0 0 0,85 1,11 1,31 220 2 RS 0,65 0,65 0,00 5,94 2 x 16 C 1 4,0
0 0 0,85 1,11 1,31 220 2 TR 0,65 0,00 0,65 5,94 2 x 16 C 1 4,0
0 0 0,85 1,11 1,31 220 2 ST 0,00 0,65 0,65 5,94 2 x 16 C 1 4,0
0 0 0,85 1,11 1,31 220 2 RS 0,65 0,65 0,00 5,94 2 x 16 C 1 4,0
0 0 0,85 1,11 1,31 220 2 TR 0,65 0,00 0,65 5,94 2 x 16 C 1 4,0
0 0 0,85 1,11 1,31 220 2 TR 0,65 0,00 0,65 5,94 2 x 16 C 1 4,0
0 0 0,85 1,11 1,31 220 2 ST 0,00 0,65 0,65 5,94 2 x 16 C 1 4,0
0 0 0,85 1,47 1,73 220 3 RST 0,58 0,58 0,58 4,54 3 x 16 C 1 4,0
0 1 0,85 1,47 1,73 220 3 RST 0,58 0,58 0,58 4,54 3 x 16 C 1 4,0
0 0 0,85 0,77 0,90 127 1 T 0,00 0,00 0,90 7,09 1 x 16 C 1 4,0
0 0 0,85 1,02 1,20 127 1 R 1,20 0,00 0,00 9,45 1 x 16 C 1 4,0
0 0 0,85 0,77 0,90 127 1 S 0,00 0,90 0,00 7,09 1 x 16 C 1 4,0
0 0 0,85 0,85 1,00 127 1 T 0,00 0,00 1,00 7,87 1 x 16 C 1 4,0
0 0 0,85 0,85 1,00 127 1 R 1,00 0,00 0,00 7,87 1 x 16 C 1 4,0
0 0 1,00 6,50 6,50 220 2 RS 3,25 3,25 0,00 29,55 2 x 32 C 1 4,0
0 0 1,00 6,50 6,50 220 2 TR 3,25 0,00 3,25 29,55 2 x 32 C 1 4,0
0 0 0,85 0,85 1,00 127 1 S 0,00 1,00 0,00 7,87 1 x 16 C 1 4,0
0 0 0,85 1,53 1,80 127 1 T 0,00 0,00 1,80 14,17 1 x 16 C 1 4,0
0 0 0,85 0,94 1,10 127 1 S 0,00 1,10 0,00 8,66 1 x 16 C 1 4,0
0 0 0,85 1,11 1,31 220 2 TR 0,65 0,00 0,65 5,94 2 x 16 C 1 4,0
0 0 0,85 1,11 1,31 220 2 ST 0,00 0,65 0,65 5,94 2 x 16 C 1 4,0
0 0 0,85 1,11 1,31 220 2 RS 0,65 0,65 0,00 5,94 2 x 16 C 1 4,0
0 0 0,85 1,11 1,31 220 2 TR 0,65 0,00 0,65 5,94 2 x 16 C 1 4,0
0 0 0,85 1,11 1,31 220 2 ST 0,00 0,65 0,65 5,94 2 x 16 C 1 4,0
1 0 0,85 0,85 1,00 220 2 RS 0,50 0,50 0,00 4,55 2 x 16 C 1 4,0
0 0 0,85 0,20 0,24 127 1 T 0,00 0,00 0,24 1,85 1 x 16 C 1 2,5
0 0 0,85 0,85 1,00 127 1 R 1,00 0,00 0,00 7,87 1 x 16 C 1 4,0
0 0 0,85 0,85 1,00 127 1 T 0,00 0,00 1,00 7,87 1 x 16 C 1 4,0
0 0 0,85 0,51 0,60 127 1 R 0,60 0,00 0,00 4,72 1 x 16 C 1 4,0
1,00 1,00 0,88 61,30 69,33 380 3 RST 23,31 19,69 22,13 105,46 3 x 125 D 1 50,0
0(0Ï5,$'(È/8/2
'5±P$
48('$'(7(162
QUEDA DE
7(162()(7,9$
LIMITE:
COMPRIMENTO
0È;,02'2
CIRCUITO
(m) 3,00% '5±$
40 1,05%
30 0,57%
45 0,55% X
18 0,26%
14 0,18% X
42 1,79%
44 2,58%
44 2,35%
40 2,35%
37 1,38%
32 1,19%
29 1,24%
40 1,07%
41 1,75% X
41 1,31% X
41 2,62% X
32 1,36%
33 1,58%
43 1,87% X
43 1,00%
39 0,90%
39 0,90%
32 0,74%
32 0,74%
29 0,67%
24 0,56%
28 0,65%
33 0,77%
34 0,79%
36 0,84%
36 0,84%
36 0,84%
15 0,23%
11 0,17%
15 0,72%
9 0,58%
22 1,06% X
11 0,59% X
11 0,59%
13 1,50% X
14 1,62% X
16 0,85% X
15 1,44% X
17 1,00%
15 0,35%
12 0,28%
14 0,32%
14 0,32%
14 0,32%
18 0,32%
50 1,00%
40 2,13%
40 2,13%
40 1,28%
40 0,66%
NOTAS:
1-PROIBIDA REPRODUÇÃO OU ALTERAÇÃO DO CONTEÚDO SEM AUTORIZAÇÃO DOS RESPONSÁVEIS TÉCNICOS DO PROJETO.
2-DIREITOS AUTORAIS RESERVADOS - LEI FEDERAL 9.610 DE 19/02/1996.
3-CONFERIR MEDIDAS NO LOCAL.
4-COTAS EM CENTÍMETROS.
RESOLUÇÃO 1797/09 DA SES-MG
03 ADEQUAÇÃO DA ARQUITETURA CONFORME VISA 01/02/2013 VIABILE
02 EMISSÃO FINAL 08/11/2012 VIABILE
00 EMISSÃO INICIAL 27/09/2012 VIABILE
VERIFICAÇÃO
Secretaria de Estado de Saúde de Minas Gerais
Cidade Administrativa Presidente Tancredo Neves
Rodovia Pref. Américo Gianetti s/nº - Bairro: Serra Verde - B. Hte -
Minas Gerais - CEP: 31630-900 SES-MG Predio Minas - 12º e 13º andar
FOLHA:
05
05
REVISÃO OBJETO DATA
GERENCIAMENTO E PROJETO:
DESENVOLVIMENTO:
BRENO ASSIS DE OLIVEIRA FEVEREIRO/2013
INSTALAÇÕES ELÉTRICAS
VÁRIAS UNIDADES NO ESTADO DE MINAS GERAIS
ETAPA:
QUADRO DE CARGAS PROJETO EXECUTIVO
Av. Augusto de Lima, nº655
conj. 418 - Centro - BH
Telefax: (31) 3324-2702
http://www.viabile.com.br
viabile@viabile.com.br
DATA:
NOME DO ARQUIVO CAD:
ESCALA: UNIDADE:
INDICADA MILÍMETROS
CREA: 78.667/D
RESPONSÁVEL TÉCNICO:
BRENO ASSIS DE OLIVEIRA
PROPRIETÁRIO:
SECRETARIA DO ESTADO DE SAÚDE DE MINAS GERAIS
460-UBSSS-R03-ELE-05-PE-T1A.DWG
UBS MINAS - PROJETO MODELO
DISCIPLINA:
PROJETO:
ENDEREÇO:
CONTEÚDO:
SUBSECRETARIA DE VIGILÂNCIA E PROTEÇÃO Á SAÚDE
SUPERINTENDÊNCIA DE VIGILÂNCIA SANITÁRIA
DIRETORIA DE INFRAESTRUTURA FÍSICA
PROJETO MODELO UNIDADE BÁSICA DE SAÚDE
PROJETO DE ACORDO COM RDC-50/2002 E
É DE RESPONSABILIDADE DO MUNICIPIO APROVAÇÃO
COM A IMPLANTAÇÃO NO TERRENO ESCOLHIDO.
TIPO T1A - ACLIVE
FORMATO INTERNACIONAL A1 ALONGADO (1026 x 594mm)
abrasip-mg
01 ALIMENTAÇÃO DOS PONTOS DE CFTV, RACK DE SONORIZAÇÃO E BEBEDOUROS 26/10/2012 VIABILE
SUBSECRETARIA DE INOVAÇÃO E LOGISTICA
SUPERINTENDENCIA DE GESTÃO
DIRETORIA DE GESTÃO DA REDE FÍSICA
5. #10,0
FUSÍVEL MODULAR
#10,0 DPS
275V
20kA - 8/20us
R
S
T
TERRA
#10,0
#10,0
#10,0
#10,0
32A
DE ALIMENTADORES/IMPLANTAÇÃO
40A (C)
40A (C) 40A (C)
125A
MÍNIMO DE 10kA
BARRA 1 - IN MÍNIMO: 150A - TRIFÁSICO - Icc MÍNIMO: 10kA
L1
16A
#4,0
L4
16A
BARRA 2 - PENTE TRIFÁSICO MÍNIMO 24 PINOS - 80A
VER PROJETO ESPECÍFICO
Pe R S T N
#6,0
#10,0
#10,0
#10,0
T19
16A
#4,0
T17
16A
#4,0
16A
#4,0
T39 T41
16A
T40
16A
QDC-T1/A - DIAGRAMA MULTIFILAR (96 POLOS)
NEUTRO DR
L2
16A
#4,0
#6,0
#6,0
NEUTRO
#6,0
#10,0
#6,0
BARRA 3 - PENTE TRIFÁSICO MÍNIMO 24 PINOS - 80A
#2,5
R
S
T
R
S
T
BARRA 4 - PENTE TRIFÁSICO MÍNIMO 24 PINOS - 80A
DETALHE SUGESTIVO DO QUADRO
QUADRO METÁLICO DE SOBREPOR
INTERRUPTOR
TETRAPOLAR
DR3-In 40A
SENS. 30mA
TIPO AC
R
S
T
BARRA 5 - PENTE TRIFÁSICO MÍNIMO 23 PINOS - 80A
#4,0
T1
16A
#4,0
T6
16A
#4,0
T13
16A
#4,0
T8 T12
T25
16A
#4,0
T23
16A
#4,0
T44
#4,0 #4,0 #2,5 #2,5 #2,5
16A
#4,0
T9
16A
#4,0
T33
32A
#6,0
RES.
40A (C)
#6,0
T2
16A
#4,0
T3
16A
#4,0
T5 T4
16A
#4,0
16A
#4,0
16A
#4,0
16A
#4,0
T16
16A
#4,0
T45
T18
16A
#4,0
T20
16A
#4,0
T21
16A
#4,0
T22
16A
#4,0
T24
16A
#4,0
T26
16A
#4,0
T27
16A
#4,0
T28
16A
#4,0
T29
16A
#4,0
T30
16A
#4,0
T37
16A
#4,0
T38
#4,0
16A
#4,0
T42
16A
#4,0
16A
#4,0
T46
16A
#2,5
T10 RES.
16A
#4,0
T11
16A
#6,0
T14
16A
#4,0
T31
16A
#4,0
T32
16A
#4,0
T34
32A
#6,0
T35
16A
#4,0
T36
16A
#4,0
RES. RES.
40A (C)
#6,0
T7
16A
#4,0
T43
16A
L3
16A
#2,5
L5
16A
#4,0
RES. RES. RES.
T47
16A
#4,0
T15
16A
#4,0
RES.
T48
16A
#4,0
T49
16A
#4,0
SIMBOLOGIA P/ QUADRO:
DISPOSITIVO PROTETOR DE SURTOS (DPS) PARA FASES E
NEUTRO. CARACTERÍSTICAS TÉCNICAS DOS DPS's CLASSE I E
CLASSE II, SEGUNDO NBR5410: - OBEDECER A NBR IEC 61.643-1;
Up (NÍVEL DE PROTEÇÃO): INFERIOR A 1,5kV; - Uc (MÁXIMA
TENSÃO DE OPERAÇÃO CONTÍNUA): 275V; - Iimp (CORRENTE DE
IMPULSO): SUPERIOR A 12,5kA (10/350us); - In (CORRENTE
NOMINAL DE DESCARGA): SUPERIOR A 20kA (8/20us) PARA REDES
TRIFÁSICAS;
PARA DPS CLASSE I (Uc 275V/12,5/60KA), UTILIZAR NAS FASES
COMO PROTEÇÃO BACKUP, FUSÍVEIS MODULARES NH-63A gG/gL.
PARA DPS CLASSE II (Uc 275V/20kA, 8/20us), UTILIZAR NAS FASES E
NEUTRO COMO PROTEÇÃO BACKUP, FUSÍVEIS MODULARES
NH-32A gG/gL. INDICAÇÃO NOS QUADROS. O POSIONAMENTO DOS
FUSÍVEIS/DPS'S, DEVERÁ ESTAR EM CONFORMIDADE COM A
FIGURA 14-a DA NBR 5410.
DISPOSITIVO DIFERENCIAL RESIDUAL (DR). CARACTERÍSTICAS
TÉCNICAS: - OBEDECER IEC 1008; - NÚMERO DE MÓDULOS: 4;
- CORRENTE NOMINAL (IN): CONFORME INDICAÇÃO EM PLANTA;
- SENSIBILIDADE: 30mA; TENSÃO MÁXIMA: 415Vca TETRAPOLAR;
FREQUÊNCIA: 60Hz; TIPO: AC.
DISJUNTORES TERMO-MAGNÉTICOS (MINI DISJUNTORES),
CURVAS B, C OU D CONFORME INDICAÇÃO NOS QUADROS,
SEGUNDO A NORMA IEC-60947-2 E DIMENSIONADOS PARA
Icc = 5,0kA/220V( MONOPOLAR, BIPOLAR E TRIPOLAR,
RESPECTIVAMENTE).
PARA OS DISJUNTORES GERAIS DEVERÃO SER SEGUIDOS
TAMBÉM OS CRITÉRIOS DA NORMA IEC-60947-2, PORÉM
DEVERÃO SER DO TIPO EM CAIXA MOLDADA, TERMOMAGNÉTICO
E DIMENSIONADOS PARA Icc MÍNIMO = 10,0kA/220V.
CABO DE COBRE COM ISOLAÇÃO TERMOPLÁSTICO NÃO
HALOGENADO E COM BAIXA EMISSÃO DE FUMAÇA, 70°C 750V,
CLASSE 5 DE ENCORDOAMENTO (FASES - COR PRETA).
CABO DE COBRE COM ISOLAÇÃO TERMOPLÁSTICO NÃO
HALOGENADO E COM BAIXA EMISSÃO DE FUMAÇA, 70°C 750V,
CLASSE 5 DE ENCORDOAMENTO (NEUTRO - COR AZUL CLARO).
CABO DE COBRE COM ISOLAÇÃO TERMOPLÁSTICO NÃO
HALOGENADO E COM BAIXA EMISSÃO DE FUMAÇA, 70°C 750V,
CLASSE 5 DE ENCORDOAMENTO (TERRA - COR VERDE).
NOTAS GERAIS DOS QUADROS:
01 - TODOS OS DISJUNTORES DOS CIRCUITOS TERMINAIS OBEDECERÃO À NBR IEC-60.947-2
(MINI-DISJUNTORES PADRÃO EUROPEU CURVAS B, C OU D CONFORME INDICAÇÃO NOS QUADROS DE
CARGAS) E SERÃO DIMENSIONADOS PARA Icc = 5,0kA/220V. OS DISJUNTORES GERAIS TAMBÉM
OBEDECERÃO À NBR IEC-60 .947-2, PORÉM, SERÃO DIMENSIONADOS PARA Icc = 10kA/220V E DEVERÃO SER
DO TIPO TERMOMAGNÉTICO EM CAIXA MOLDADA .
02 - TODOS OS DISJUNTORES NO INTERIOR DOS QUADROS DEVERÃO SER IDENTIFICADOS ATRAVÉS DE
ETIQUETAS ACRÍLICAS DE IDENTIFICAÇÃO CONFORME NOMES DOS CIRCUITOS CONSTANTES NOS
QUADROS DE CARGAS.
03 - FORAM PREVISTOS ESPAÇOS RESERVAS MÍNIMOS PARA AMPLIAÇÕES FUTURAS, COM BASE NO
NÚMERO DE CIRCUITOS EFETIVAMENTE INSTALADO NO QDC E DE ACORDO COM A NBR-5410:2004.
04 - O QUADRO SERÁ METÁLICO, DE EMBUTIR (PREVER ALVENARIA PARA SUSTENTAÇÃO), COM NO MÍNIMO
IP-30 (EM EXCEÇÃO AOS QUADROS LOCALIZADOS AO TEMPO, QUE DEVERÃO POSSUIR GRAU DE
PROTEÇÃO MÍNIMO IP-54), PROVIDO DE ALETAS PARA VENTILAÇÃO, PORTA DE TRINCO COM CHAVE, NÃO
ESTAR INSTALADO EM ÁREAS MOLHADAS OU ÚMIDAS, LONGE DE GÁS, DOTADO DE FÁCIL ACESSO E NÃO
SER OBSTRUÍDO, DEVENDO POSSUIR SOBRETUDO, CERTIFICAÇÃO DE TESTES SEGUNDO NBR IEC 60.439-1
EMITIDO POR EMPRESA ESPECIALIZADA NA MONTAGEM DE QUADROS ELÉTRICOS.
05 - O QUADRO DEVERÁPOSSUIR, ALÉM DOS DISJUNTORES TERMINAIS DESCRITOS NO QUADRO DE
CARGAS, DISPOSITIVOS DR, DPS DE ENTRADA COM PROTEÇÃO BACKUP, BARRAS DE TERRA E NEUTRO,
SENDO AS BARRAS DE NEUTRO PARA DR SEGREGADAS DA BARRA DE NEUTRO GERAL DO QUADRO,
CONFORME LAYOUT SUGESTIVO DO DIAGRAMA MULTIFILAR.
06 - O QUADRO DEVERÁ POSSUIR PLACA DE MONTAGEM INTERNA NA COR LARANJA, CANALETAS PARA A
PASSAGEM DE CABOS (RESPEITANDO A TAXA DE OCUPAÇÃO MÁXIMA DOS CABOS NESTAS CANALETAS,
SEGUNDO ORIENTAÇÕES DA NBR 5410), BASE CONECTORA PARA A DISTRIBUIÇÃO DOS CABOS (ENTRADA E
SAÍDA) E IDENTIFICAÇÃO DE NOME, TENSÃO E FREQUÊNCIA EM SUA PORTA, EM ETIQUETA ACRÍLICA DE
FUNDO PRETO E LETRAS BRANCAS. TAMBÉM DEVERÁ POSSUIR UMA PLACA DE ADVERTÊNCIA INTERNA AO
QUADRO, CONFORME DIZERES NESTA FOLHA. PREVER SOBRETUDO ESPAÇOS PARA DR E DPS CONFORME
DETALHADO NO DIAGRAMA MULTIFILAR.
07- NO QUADRO DEVERÃO SER FIXADOS, ATRAVÉS DE DISPOSITIVO PRÓPRIO, OS DIAGRAMAS DOS
MESMOS, CONTENDO TODAS AS PROTEÇÕES ENVOLVIDAS CONFORME EXECUTADO .
08- AS TERMINAÇÕES DOS ELETRODUTOS NO QUADROS ELÉTRICO, SEJAM ELES METÁLICOS OU EM
MATERIAL PLÁSTICO ANTI-CHAMA (PVC RÍGIDO), DEVERÃO SER COM CONECTOR TIPO BOX RETO, COM
BUCHA E ARRUELA DE ACABAMENTO, ADEQUADAS ÀS BITOLAS DO MESMO. AS ELETROCALHAS DEVERÃO
SER PROVIDAS DE FLANGES PRÉ-MOLDADOS CONFORME DIMENSÕES DE PROJETO.
09- AS TERMINAÇÕES DOS CABOS NO QUADRO ELÉTRICO DEVERÃO RECEBER TEMINAL DO TIPO AGULHA
PARA CONEXÃO COM OS BORNES DOS DISJUNTORES E TERMINAL TIPO OLHAL PARA CONEXÃO NOS
BARRAMENTOS. TODOS OS TERMINAIS DEVERÃO SER COMPRIMIDOS ATRAVÉS DE FERRAMENTA
ADEQUADA.
10- O QUADRO DEVER Á ESTAR LIMPO, LIVRE DE ARGAMASSAS, POEIRA, CAPA DE CABOS, FILAMENTOS DE
CABOS DE COBRE E OUTROS MATERIAIS ESTRANHOS À INSTALAÇÃO.
11- OS TERMINAIS DAS BARRAS DE CONEXÃO NÃO UTILIZADOS DEVERÃO SER ISOLADOS POR CAPA
PROTETORA ADEQUADA, DO MESMO FABRICANTE DAS BARRAS DE CONEXÃO .
12- TODOS OS CABOS ALIMENTADORES DOS CIRCUITOS INTERNOS AO QUADRO SERÃO DE COBRE COM
ISOLAÇÃO TERMOPLÁSTICO NÃO HALOGENADO E COM BAIXA EMISSÃO DE FUMAÇA 70 ºC 750V. DEVERÃO
SOBRETUDO, RECEBER ETIQUETAS DE IDENTIFICAÇÃO (TAG´s), INDELÉVEIS, COM INDICAÇÃO DO CIRCUITO
A QUE ESTÁ LIGADO, CONFORME DESCRIÇÃO DO CAMPO CIRCUITO DO QUADRO DE CARGAS
CORRESPONDENTE.
13 - ATERRAR TODAS AS PORTAS DOS QUADROS ATRAVÉS DE CABO DE COBRE #6,0mm² ISOLAÇÃO VERDE
EM PVC 70°C 750V.
14 - CONFORME NBR 5410/2004, DEVIDO A POSSIBILIDADE DE FALHA INTERNA, FAZENDO COM QUE OS
DPS`s ENTRE EM CURTO CIRCUITO, A NORMA IMPÕE A NECESSIDADE DE DISPOSITIVO DE PROTEÇÃO PARA
ELIMINAR TAL CURTO CIRCUITO. DESTA FORMA, DEVERÁ SER UTILIZADO, EM TODOS OS QUADROS, ANTES
E EM SÉRIE COM O DPS, DISPOSITIVO DE BACK UP PARA DEVIDA PROTEÇÃO. PARA DPS`s CLASSE I ,
FUSÍVEIS DO TIPO MODULAR 63A . PARA DPS´s CLASSE II , FUSÍVEIS TIPO MODULAR 32A .
ADVERTÊNCIA
1- QUANDO UM DISJUNTOR OU FUSÍVEL ATUA, DESLIGANDO ALGUM CIRCUITO OU A
INSTALAÇÃO INTEIRA, A CAUSA PODE SER UMA SOBRECARGA OU UM CURTO-CIRCUITO.
DESLIGAMENTOS FREQUENTES SÃO SINAL DE SOBRECARGA. POR ISSO, NUNCA TROQUE
SEUS DISJUNTORES OU FUSÍVEIS POR OUTRO DE MAIOR CORRENTE (MAIOR AMPERAGEM)
SIMPLESMENTE. COMO REGRA, A TROCA DE UM DISJUNTOR OU FUSÍVEL POR OUTRO DE
MAIOR CORRENTE REQUER, ANTES, A TROCA DOS FIOS E CABOS ELÉTRICOS, POR OUTROS
DE MAIOR SEÇÃO (BITOLA).
2- DA MESMA FORMA, NUNCA DESATIVE OU REMOVA A CHAVE AUTOMÁTICA DE PROTEÇÃO
CONTRA CHOQUES ELÉTRICOS (DISPOSITIVOS DR), MESMO EM CASO DE DESLIGAMENTOS
SEM CAUSA APARENTE. SE OS DESLIGAMENTOS FOREM FREQUENTES E, PRINCIPALMENTE,
SE AS TENTATIVAS DE RELIGAR A CHAVE NÃO TIVEREM ÊXITO, ISSO SIGNIFICA, MUITO
PROVAVELMENTE, QUE A INSTALAÇÃO ELÉTRICA APRESENTA ANOMALIAS INTERNAS, QUE
SÓ PODEM SER IDENTIFICADAS E CORRIGIDAS POR PROFISSIONAIS QUALIFICADOS. A
DESATIVAÇÃO OU REMOÇÃO DA CHAVE SIGNIFICA A ELIMINAÇÃO DE MEDIDA PROTETORA
CONTRA CHOQUES ELÉTRICOS E RISCO DE VIDA PARA OS USUÁRIOS DA INSTALAÇÃO.
DETALHE DA ADVERTÊNCIA SEGUNDO A NBR 5410
A SER FIXADA DENTRO DOS QUADROS ELÉTRICOS
TABELA 1: ESPAÇO RESERVA
QUANTIDADE DE CIRCUITOS
EFETIVAMENTE DISPONÍVEL
N
ESPAÇO MÍNIMO DESTINADO A
RESERVA (EM NÚMEROS DE
CIRCUITOS)
ATÉ 6 2
7 A 12 3
13 A 30 4
N30 0,15xN
NOTAS:
1-PROIBIDA REPRODUÇÃO OU ALTERAÇÃO DO CONTEÚDO SEM AUTORIZAÇÃO DOS RESPONSÁVEIS TÉCNICOS DO PROJETO.
2-DIREITOS AUTORAIS RESERVADOS - LEI FEDERAL 9.610 DE 19/02/1996.
3-CONFERIR MEDIDAS NO LOCAL.
4-COTAS EM CENTÍMETROS.
SUBSECRETARIA DE VIGILÂNCIA E PROTEÇÃO Á SAÚDE
SUPERINTENDÊNCIA DE VIGILÂNCIA SANITÁRIA
DIRETORIA DE INFRAESTRUTURA FÍSICA
PROJETO MODELO UNIDADE BÁSICA DE SAÚDE
PROJETO DE ACORDO COM RDC-50/2002 E
RESOLUÇÃO 1797/09 DA SES-MG
É DE RESPONSABILIDADE DO MUNICIPIO APROVAÇÃO
COM A IMPLANTAÇÃO NO TERRENO ESCOLHIDO.
03 ADEQUAÇÃO DA ARQUITETURA CONFORME VISA 01/02/2013 VIABILE
02 EMISSÃO FINAL 08/11/2012 VIABILE
01 ALIMENTAÇÃO DOS PONTOS DE CFTV, RACK DE SONORIZAÇÃO E BEBEDOUROS 26/10/2012 VIABILE
00 EMISSÃO INICIAL 27/09/2012 VIABILE
VERIFICAÇÃO
FOLHA:
04
05
REVISÃO OBJETO DATA
GERENCIAMENTO E PROJETO:
DESENVOLVIMENTO:
BRENO ASSIS DE OLIVEIRA FEVEREIRO/2013
INSTALAÇÕES ELÉTRICAS
VÁRIAS UNIDADES NO ESTADO DE MINAS GERAIS
ETAPA:
DIAGRAMA MULTIFILAR PROJETO EXECUTIVO
Av. Augusto de Lima, nº655
conj. 418 - Centro - BH
Telefax: (31) 3324-2702
http://www.viabile.com.br
viabile@viabile.com.br
DATA:
NOME DO ARQUIVO CAD:
ESCALA: UNIDADE:
INDICADA MILÍMETROS
CREA: 78.667/D
RESPONSÁVEL TÉCNICO:
BRENO ASSIS DE OLIVEIRA
PROPRIETÁRIO:
SECRETARIA DO ESTADO DE SAÚDE DE MINAS GERAIS
460-UBSSS-R03-ELE-04-PE-T1A.DWG
UBS MINAS - PROJETO MODELO
DISCIPLINA:
PROJETO:
ENDEREÇO:
CONTEÚDO:
SUBSECRETARIA DE INOVAÇÃO E LOGISTICA
SUPERINTENDENCIA DE GESTÃO
DIRETORIA DE GESTÃO DA REDE FÍSICA
TIPO T1A - ACLIVE
FORMATO INTERNACIONAL A1 (841 x 594mm)
abrasip-mg
Secretaria de Estado de Saúde de Minas Gerais
Cidade Administrativa Presidente Tancredo Neves
Rodovia Pref. Américo Gianetti s/nº - Bairro: Serra Verde - B. Hte -
Minas Gerais - CEP: 31630-900 SES-MG Predio Minas - 12º e 13º andar
6. #4,0
T7 T15
#4,0 #4,0
T20 T7
T21
#4,0
T22-1,11kW-220V
T20-1,11kW-220V T7-2X200VA
T19
#4,0
T6
T4
T27 T28
#4,0
N O
L
T46
J
T14
#4,0
T12
COMPRESSOR
#4,0
T12 T13
G
T46 F
T4
#4,0
T4
#4,0
T17 T18
#4,0 C
T46 T1 T14
T2 T16
#4,0
T1-600VA
COLETA
T18-1,11kW-220V
PLANTA DE TOMADAS DO PRIMEIRO PAVIMENTO
T29
T33-6500W
T33
#4,0
T29
T29
T35 T36
T33
T33
T34
#4,0
#4,0
PLANTA DE TOMADAS DO SEGUNDO PAVIMENTO
I. S.
T12
#4,0
SALA DE REUNIÃO E EDUCAÇÃO
T49
T1
#4,0
T12
T46
T1
T12
T46 T1
T1
#4,0
#4,0
T46 T1
T14
T2-2X200VA
T46 T1
#4,0
T1
T16
#4,0
T46
T46
T46 T1 T2
T1
T1
T1
T46
T1
#4,0
T2
#4,0
T2
#4,0
T1
#4,0
T14b'
T14b'
T14b'
T14b'
T14a'
#4,0
T14a'
T14a'
T14
T14
T14a' T46 T1 T2 T14
#4,0
#4,0
#4,0
T16-1,11kW-220V
T2-600VA
T4-2X200VA
T4
T17-1,11kW-220V
A T3-4X200VA
B
T14
B
T8
D
T4
T4-2X200VA
T10 T11
#6,0
T9
T8
T5 T5 E
T19-1,11kW-220V
F
T8
F
T26
T27 T28
#4,0
T26
T27 T28
#4,0
T28
#4,0
T6-2X200VA
T46
T5
T8
T5
T5
T5 T6
T6
T6
T6 T6
T7
T7
T7
K
T7
T22
#4,0
T7
T21-1,11kW-220V
I
T6 T7
T7
K
M
T9-600VA
T11-1,8kVA
T10-600VA
T11
#6,0
T9
T9
T8
T8
T8
T9 T9
T12
T12
T24 T25
#4,0
T24 T25
#4,0
T12 T12
T12-2X200VA
T14
T24-1,11kW-220V
T25-1,11kW-220V
T14
T14
G
T13
T13
T13-200VA
T13-200VA
T12 T13
T25
#4,0
H
T14
T13
T13 T13
T13
T13 T14
T23
#4,0
O T23-1,11kW-220V
J
T46 T46
T46
T44
#4,0
T7
T7
T14
T14
M
T31
T46
T33
T32 T32 T32 T32
T35 T36
#4,0 T35
T37-2X200VA
T45-1kVA
T40-1,11kW-220V
T40
#4,0
T35 T35
#4,0
T42-1,11kW-220V
T32 T35 T49
T37
T37
#4,0
#4,0 #4,0
T37
T37-200VA
T37-200VA
T37
T37
T37
#4,0
T37
T34-6500W
T34
#4,0
T32
T32
T34
#6,0
T32 T37 T42
#4,0
T32
T32
T37 T42
#4,0
T36-1,8kVA
T49
T35
T35
T35
T35
T35
T32
T35 T36
T36
#4,0
T35-600VA
T35
T35
T34
#6,0
T32 T37 T42
#4,0
T32 T32
T32
T32
T40 T41
#4,0
T40 T41
#4,0
T41
#4,0
T41-1,11kW-220V
T31
T31
R
T31 T45 T31 T45
T31
T31
T31
S
T31
T
V
U
T30-2X600VA
T38-1,11kW-220V
T38
#4,0
T29 T29
T29
T29
T29
T29
T29
T30
T39-1,11kW-220V
T39
#4,0 T29
T29
2XT29
T32
T32
T46
T46
T46
T46
T46
T31 T31
T31
T31
O
P
Q
R
#4,0
T47-1KVA
T47
#4,0
T48
#4,0
T14 T48-1KVA
T49
T7 T49
T49
T49
T49 T49
T49
T3 T49
T49
T49
T49
T49
T49
T49
T49
T14
T14
T32 T32
T14
T14
VACINAÇÃO
SALA DE ESPERA
I.S. MASC.
RECEPÇÃO
TRIAGEM
CIRCULAÇÃO
GINECOLOGIA
DML
ALMOXARIFADO
VARANDA COBERTA
I.S. FEM.
ESCOVÁRIO
RESÍDUOS
RESÍDUOS
COPA
TV SUSPENSA
VAGA PARA AMBULÂNCIA
FOSSO
ESCANINHOS
ÁREA PERMEÁVEL
ÁREA PERMEÁVEL
proj. da cobertura
CALÇADA
RUA
ALÇAPÃO
LAVAGEM E
DESINFECÇÃO DE MATERIAIS
ESTERILIZAÇÃO
GUICHÊ
DML
proj. da
cobertura
SALA DE APOIO
AGENTES
ENDEMIAS
APOIO AGENTES
ENDEMIAS
SALA DE
CURATIVOS
CUIDADOS
BÁSICOS
ATENDIMENTO
MULTIPROFISSIONAL
ATENDIMENTO
MULTIPROFISSIONAL
GUARDA
MEDICAMENTOS
REBAIXO NA CALÇADA P/
ACESSO DE VEÍCULOS
REBAIXO NA CALÇADA P/
ACESSIBILIDADE
CONSULTÓRIO
ODONTOLÓGICO
VESTIÁRIO
FEMININO
ESCALA: ......................................................................................................... 1/75
ESCALA: .......................................................................................................... 1/75
T4
#4,0
T4
#4,0
T5
T26
T27
T28
T14
#4,0
T14
#4,0
#4,0
T46 T1 T2 T14
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
T8
T11
#6,0
T9
T5-2X200VA
T15
T43
T43
T34
#4,0
T34
#4,0
T34
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0 #4,0
#4,0 #4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0 #4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0 #4,0
#4,0
#4,0
#4,0
#4,0 #4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
A
LEGENDA PARA PERCURSO DE CABOS (QDC-QDC-T1/A):
B
T46 T1 T2 T4 T14 T16
C
D
E
F
#4,0
G
H
T3 T1 T2 T4 T14
T48
#4,0
T46
T3 T1 T2 T4
T16 T17
#4,0
T14
T3 T16 T17
T8 T1 T2 T4 T48
#4,0
T14
T5 T8 T9 T10 T3 T1 T2 T4 T16 T17 T18
T11
#4,0
#6,0
T14
T5 T8 T9 T10 T3 T1 T2 T4 T16 T17 T18 T19
T11
#4,0
#6,0
T14
T5 T8 T9 T10 T3 T1 T2 T4 T16 T17 T18 T19 T26 T27 T28
T11
#4,0
#6,0
T14
T5 T6 T8 T9 T10 T12 T13 T3 T1 T2 T4 T16 T17 T18 T19 T26 T27 T28
T11
#4,0
T14
I T3 T1 T2 T4 T28
#6,0
T5 T6 T8 T9 T10 T12 T13 T16 T17 T18 T19 T24 T25 T26 T27 T11
#4,0
T14
J T3 T1 T2 T4 T28
#6,0
T5 T6 T7 T8 T9 T10 T12 T13 T16 T17 T18 T19 T20 T21 T24 T25 T26 T27 T11
#4,0
K T3 T1 T2 T4
#6,0
T14
T43 T6 T7 T8 T9 T10 T12 T13 T16 T17 T18 T19 T20 T21 T24 T25 T26 T27 T28 T11
#4,0
#6,0
T14
T6 T7 T8 T9 T10 T12 T13 T16 T17 T18 T19 T20 T21 T22 T24 T25 T26 T27 T28 T11
L T3 T1 T2 T4
#4,0
M T3 T1 T2 T4
#6,0
T14
T6 T7 T8 T9 T10 T12 T13 T16 T17 T18 T19 T20 T21 T22 T23 T24 T25 T26 T27 T28 T11
#4,0
N T3 T1 T2 T4
#6,0
T14
T6 T7 T8 T9 T10 T12 T13 T16 T17 T18 T19 T20 T21 T22 T23 T24 T25 T26 T27 T28 T44 T11
#4,0
O T3 T1 T2 T4
#6,0
T6 T7 T8 T9 T10 T12 T13 T15 T16 T17 T18 T19 T20 T21 T22 T23 T24 T25 T26 T27 T28 T44 T11
#4,0
P T3 T1 T2 T4
#6,0
T6 T7 T8 T9 T10 T12 T13 T15 T31 T16 T17 T18 T19 T20 T21 T22 T23 T24 T25 T26 T27 T28 T44 T11
#4,0
Q T3 T1 T2 T4
#6,0
T6 T7 T8 T9 T10 T12 T13 T15 T29 T31 T16 T17 T18 T19 T20 T21 T22 T23 T24 T25 T26 T27 T28 T44 T11
#4,0
R T3 T1 T2 T4
#6,0
T6 T7 T8 T9 T10 T12 T13 T15 T29 T31 T32 T16 T17 T18 T19 T20 T21 T22 T23 T24 T25 T26 T27 T28 T38 T44 T11
#4,0
S T3 T1 T2 T4
#6,0
T6 T7 T8 T9 T10 T12 T13 T15 T29 T30 T31 T32 T45 T16 T17 T18 T19 T20 T21 T22 T23 T24 T25 T26 T27 T28 T38 T44 T11
#4,0
T T3 T1 T2 T4
#6,0
T10 T12 T13 T15 T29 T30 T31 T32 T45 T16 T17 T18 T19 T20 T21 T22 T23 T24 T25 T26 T27 T28 T38 T39 T44 T11
#4,0
#6,0
U T36 T40 T41 T42
#4,0
T6 T7 T8 T9
T32 T35 T37
T6 T7 T8 T9 V T35 T37
T1
T3
T2 T4
#4,0
T16 T17
T10
T12 T13
T15 T29 T31 T32
T30 T45
T18 T19 T20 T21 T22 T23 T24 T25 T26 T27 T28 T36 T38
T39
T40 T41 T42
T44
T11
#6,0
T46
T46
T46
T46
T46
T46
T46
T46
T46
T16
T18 T48
T18
T48
T48
T48
T48
T48
T48
T48
T48
T48
T48
T47
T47
T47
T47
T47
T47
T47
T49
T49
T49
T49
T49
T49
T49 T48
T48
T48
T48
T48
T48
T48
T49
T49 T47
T49 T47
T49 T47
T49 T47
T49 T47
T49 T47
T49 T47
T49 T47
T49 T47
T49 T47
T49 T47
T49 T47
T49 T14
T47
T14
T14
T14
T14
T14
T14
T14
T5
T5
T5
T5
T5
T5
T5
T5
T5
T5
T5 T49
T46 T43
T46 T43
T46 T43
T46 T43
T46 T43
T46 T43
T46 T43
T46 T43
T46 T43
T46 T43
#4,0
NOTAS:
1-PROIBIDA REPRODUÇÃO OU ALTERAÇÃO DO CONTEÚDO SEM AUTORIZAÇÃO DOS RESPONSÁVEIS TÉCNICOS DO PROJETO.
2-DIREITOS AUTORAIS RESERVADOS - LEI FEDERAL 9.610 DE 19/02/1996.
3-CONFERIR MEDIDAS NO LOCAL.
4-COTAS EM CENTÍMETROS.
SUBSECRETARIA DE VIGILÂNCIA E PROTEÇÃO Á SAÚDE
SUPERINTENDÊNCIA DE VIGILÂNCIA SANITÁRIA
DIRETORIA DE INFRAESTRUTURA FÍSICA
PROJETO MODELO UNIDADE BÁSICA DE SAÚDE
PROJETO DE ACORDO COM RDC-50/2002 E
RESOLUÇÃO 1797/09 DA SES-MG
É DE RESPONSABILIDADE DO MUNICIPIO APROVAÇÃO
COM A IMPLANTAÇÃO NO TERRENO ESCOLHIDO.
03 ADEQUAÇÃO DA ARQUITETURA CONFORME VISA 31/01/2013 VIABILE
02 EMISSÃO FINAL 08/11/2012 VIABILE
01 ALIMENTAÇÃO DOS PONTOS DE CFTV, RACK DE SONORIZAÇÃO E BEBEDOUROS 26/10/2012 VIABILE
00 EMISSÃO INICIAL 27/09/2012 VIABILE
VERIFICAÇÃO
FOLHA:
03
05
REVISÃO OBJETO DATA
GERENCIAMENTO E PROJETO:
DESENVOLVIMENTO:
BRENO ASSIS DE OLIVEIRA FEVEREIRO/2013
INSTALAÇÕES ELÉTRICAS
VÁRIAS UNIDADES NO ESTADO DE MINAS GERAIS
ETAPA:
PLANTAS DE TOMADAS DO 1º E 2º PROJETO EXECUTIVO
PAVIMENTOS
Av. Augusto de Lima, nº655
conj. 418 - Centro - BH
Telefax: (31) 3324-2702
http://www.viabile.com.br
viabile@viabile.com.br
DATA:
NOME DO ARQUIVO CAD:
ESCALA: UNIDADE:
INDICADA CENTÍMETROS
CREA: 78.667/D
RESPONSÁVEL TÉCNICO:
BRENO ASSIS DE OLIVEIRA
PROPRIETÁRIO:
SECRETARIA DO ESTADO DE SAÚDE DE MINAS GERAIS
460-UBSSS-R03-ELE-03-PE-T1A.DWG
UBS MINAS - PROJETO MODELO
DISCIPLINA:
PROJETO:
ENDEREÇO:
CONTEÚDO:
SUBSECRETARIA DE INOVAÇÃO E LOGISTICA
SUPERINTENDENCIA DE GESTÃO
DIRETORIA DE GESTÃO DA REDE FÍSICA
TIPO T1A - ACLIVE
FORMATO INTERNACIONAL A1 (841 x 594mm)
abrasip-mg
Secretaria de Estado de Saúde de Minas Gerais
Cidade Administrativa Presidente Tancredo Neves
Rodovia Pref. Américo Gianetti s/nº - Bairro: Serra Verde - B. Hte -
Minas Gerais - CEP: 31630-900 SES-MG Predio Minas - 12º e 13º andar