SlideShare une entreprise Scribd logo
1  sur  5
Télécharger pour lire hors ligne
COMPRESSOR 
01xCo RG59 
1P-CFTV-01 
SOBEM CABOS DO 1º 
PAVIMENTO PARA O 2º 
PAVTO. ATRAVÉS DE 
ELETROCALHA LISA COM 
TAMPA 150x100mm 
DESCEM CABOS DO 2º 
PAVIMENTO PARA O 1º 
PAVTO. ATRAVÉS DE 
ELETROCALHA LISA COM 
TAMPA 150x100mm 
CIRCULAÇÃO 
SOBE CABO DE SONORIZAÇÃO 
(2x2,5mm²) DO 1º PAVTO. PARA 
O 2º PAVTO. ATRAVÉS DE 
ELETRODUTO DE AÇO 
GALVANIZADO - Ø1"(25mm) 
I. S. 
SALA DE REUNIÃO E EDUCAÇÃO 
ARMÁRIO METÁLICO DO 
TIPO RACK 12 Us COM 
PORTA PARA 
EQUIPAMENTOS DE ÁUDIO 
PADRÃO 19": SUSTENTAÇÃO 
DA MATRIZ 8x8 E DO 
AMPLIFICADOR 
PT-1P-CFTV-05 
01xCo RG59 
1P-CFTV-05 
PAGGING 
SON-T1A 
SF-2P-01 
SF-2P-02 
SF-1P-01 
SF-1P-02 
SF-1P-03 
AT-T1A 
SF-1P-05 
SF-1P-04 
PT-2P-CFTV-02 
PT-2P-CFTV-01 
PT-1P-CFTV-01 
PT-1P-CFTV-02 
COLETA 
PT-1P-CFTV-03 
PT-1P-CFTV-04 
01xCo RG59 
2P-CFTV-02 
01xCo RG59 
2P-CFTV-01 
ESTERILIZAÇÃO 
01xCo RG59 
2P-CFTV-01 
02xCo RG59 
02xCo RG59 2P-CFTV-01 a 02 
2P-CFTV-01 a 02 
02xCo RG59 
1P-CFTV-01 a 02 
04xCo RG59 
1P-CFTV-01 a 02 
2P-CFTV-01 a 02 
04xCo RG59 
1P-CFTV-01 a 02 
2P-CFTV-01 a 02 
01xCo RG59 
1P-CFTV-03 
01xCo RG59 
1P-CFTV-04 
05xCo RG59 
1P-CFTV-01 a 03 
2P-CFTV-01 a 02 
07xCo RG59 
1P-CFTV-01 a 05 
2P-CFTV-01 a 02 
02xCo RG59 
1P-CFTV-04 a 05 
DESCE CABO DE 
SONORIZAÇÃO (2x2,5mm²) DO 
2º PAVTO. PARA O 1º PAVTO. 
ATRAVÉS DE ELETRODUTO 
DE AÇO GALVANIZADO - 
Ø1"(25mm) 
VACINAÇÃO 
SALA DE ESPERA 
I.S. MASC. 
RECEPÇÃO 
TRIAGEM 
CIRCULAÇÃO 
GINECOLOGIA 
DML 
ALMOXARIFADO 
VARANDA COBERTA 
I.S. FEM. 
ESCOVÁRIO 
RESÍDUOS 
RESÍDUOS 
CIRCULAÇÃO 
GUICHÊ 
COPA 
TV SUSPENSA 
VAGA PARA AMBULÂNCIA 
FOSSO 
ESCANINHOS 
ÁREA PERMEÁVEL 
ÁREA PERMEÁVEL 
proj. da cobertura 
CALÇADA 
RUA 
PROJEÇÃO CAIXA D'ÁGUA 
ALÇAPÃO 
LAVAGEM E 
DESINFECÇÃO DE MATERIAIS 
DML 
proj. da 
cobertura 
SALA DE APOIO 
AGENTES 
ENDEMIAS 
APOIO AGENTES 
ENDEMIAS 
SALA DE 
CURATIVOS 
CUIDADOS 
BÁSICOS 
ATENDIMENTO 
MULTIPROFISSIONAL 
ATENDIMENTO 
MULTIPROFISSIONAL 
GUARDA 
MEDICAMENTOS 
REBAIXO NA CALÇADA P/ 
ACESSO DE VEÍCULOS 
REBAIXO NA CALÇADA P/ 
ACESSIBILIDADE 
CONSULTÓRIO 
ODONTOLÓGICO 
VESTIÁRIO 
MASCULINO 
VESTIÁRIO 
FEMININO 
1-PROIBIDA REPRODUÇÃO OU ALTERAÇÃO DO CONTEÚDO SEM AUTORIZAÇÃO DOS RESPONSÁVEIS TÉCNICOS DO PROJETO. 
2-DIREITOS AUTORAIS RESERVADOS - LEI FEDERAL 9.610 DE 19/02/1996. 
3-CONFERIR MEDIDAS NO LOCAL. 
RESOLUÇÃO 1797/09 DA SES-MG 
03 ADEQUAÇÃO DA ARQUITETURA CONFORME VISA 31/01/2013 VIABILE 
02 EMISSÃO FINAL 08/11/2012 VIABILE 
00 EMISSÃO INICIAL 22/10/2012 VIABILE 
VERIFICAÇÃO 
Secretaria de Estado de Saúde de Minas Gerais 
Cidade Administrativa Presidente Tancredo Neves 
Rodovia Pref. Américo Gianetti s/nº - Bairro: Serra Verde - B. Hte - 
Minas Gerais - CEP: 31630-900 SES-MG Predio Minas - 12º e 13º andar 
FOLHA: 
02 
02 
REVISÃO OBJETO DATA 
GERENCIAMENTO E PROJETO: 
DESENVOLVIMENTO: 
BRENO DE ASSIS OLIVEIRA FEVEREIRO/2013 
PROJETO DE SONORIZAÇÃO/CFTV/ALARME 
VÁRIAS UNIDADES NO ESTADO DE MINAS GERAIS 
ETAPA: 
PLANTAS PROJETO EXECUTIVO 
Av. Augusto de Lima, nº655 
conj. 418 - Centro - BH 
Telefax: (31) 3324-2702 
http://www.viabile.com.br 
viabile@viabile.com.br 
DATA: 
NOME DO ARQUIVO CAD: 
ESCALA: UNIDADE: 
INDICADA CENTÍMETROS 
CREA-MG: 78.667/D 
RESPONSÁVEL TÉCNICO: 
BRENO DE ASSIS OLIVEIRA 
PROPRIETÁRIO: 
SECRETARIA DO ESTADO DE SAÚDE DE MINAS GERAIS 
460-UBSSS-R03-ESO-02-PE-T1A.DWG 
UBS MINAS - PROJETO MODELO 
DISCIPLINA: 
PROJETO: 
ENDEREÇO: 
CONTEÚDO: 
NOTAS: 
4-COTAS EM CENTÍMETROS. 
SUBSECRETARIA DE VIGILÂNCIA E PROTEÇÃO Á SAÚDE 
SUPERINTENDÊNCIA DE VIGILÂNCIA SANITÁRIA 
DIRETORIA DE INFRAESTRUTURA FÍSICA 
PROJETO MODELO UNIDADE BÁSICA DE SAÚDE 
PROJETO DE ACORDO COM RDC-50/2002 E 
É DE RESPONSABILIDADE DO MUNICIPIO APROVAÇÃO 
COM A IMPLANTAÇÃO NO TERRENO ESCOLHIDO. 
TIPO T1A - ACLIVE 
FORMATO INTERNACIONAL A1 (841 x 594mm) 
abrasip-mg 
SONORIZAÇÃO - 1° PAVIMENTO 
ESCALA: ......................................................................... 1/75 
SONORIZAÇÃO - 2° PAVIMENTO 
ESCALA: ......................................................................... 1/75 
01 MUDANÇA DE ARQUITETURA 26/10/2012 VIABILE 
SUBSECRETARIA DE INOVAÇÃO E LOGISTICA 
SUPERINTENDENCIA DE GESTÃO 
DIRETORIA DE GESTÃO DA REDE FÍSICA
SIMBOLOGIA - SONORIZAÇÃO: 
SÍMBOLO DESCRIÇÃO 
ELETROCALHA METÁLICA LISA COM VIROLA DO TIPO "C" E TAMPA DE PRESSÃO (DIMENSÕES: 150x100mm). 
COMPARTILHADA COM CABEAMENTO ESTRUTURADO. 
ELETRODUTO DE AÇO GALVANIZADO FIXADO ATRAVÉS DE TIRANTES NA ESTRUTURA - Ø1"(25mm) OU 
CONFORME INDICAÇÃO. REF.: ELECON. 
CAIXAS METÁLICAS DE PASSAGEM DO TIPO CONDULETE MÚLTIPLO - TIPOS X, T, LL, E, LR e C 
RESPECTIVAMENTE, CONFORME NBR-15.701 
SONOFLETOR (ALTO-FALANTE) COAXIAL 6" POTÊNCIA 25Wrms IMPEDÂNCIA 8 OHMS DO TIPO ARANDELA NA 
COR BRANCA. REF.: ARANDELA 6CO2R, DA SELENIUM. 
CÂMERA COLORIDA PARA SISTEMA DE CFTV INSTALADA EM CAIXA BLINDADA COM FONTE 127V NO INTERIOR 
DA CAIXA, INSTALADA EM PAREDE h=2,20m OU CONFORME INDICAÇÃO. DEVERÃO SER INSTALADAS DUAS 
CAIXAS 2x4", SENDO UMA PARA A ALIMENTAÇÃO ELÉTRICA E OUTRA PARA A PASSAGEM DO CABO DE VÍDEO. 
CABO UTP 
RACK 
MATRIZ 8x8 
AMPLIFICADOR 
CAIXAS 
SALA DE 
ESPERA 
CAIXAS 
CIRCULAÇÃO 
1ºPAVTO. 
CAIXAS 
CIRCULAÇÃO 
2ºPAVTO. 
PAGGING/ 
MICROFONE 
CABO UTP CAT 6 
DIAGRAMA ESQUEMÁTICO DE 
INTERLIGAÇÃO 
SONOFLETORES NO FORRO 
CHUMBADOR ROSCA 
INTERNA Ø1/4" 
PORCA SEXTAVADA E 
ARRUELA LISA Ø1/4" 
ELETRODUTOS (PENDENTE) 
RACK METÁLICO FECHADO 19"x12Us PROF.: 
670mm COM PORTA DE VIDRO, EQUIPADO COM 
RÉGUA DE 10 TOMADAS 2P+T LIGADA AO 
NO-BREAK 
GAVETA DE VENTILAÇÃO PADRÃO 19" C/ 
QUATRO VENTILADORES 
MATRIZ DE ÁUDIO 8x8 (8 in / 8 out) 
NO-BREAK 600VA/127V PADRÃO 19" COM 
AUTONOMIA MÍNIMA DE 15 MINUTOS 
ELETRODUTO AÇO 
GALVANIZADO (Ø CONF.PROJ 
PAR DE FIOS POLARIZADOS 
BRAÇADEIRA 
TIPO "D" BUCHA PLÁSTICA 
DETALHE SUGESTIVO DO ARMÁRIO DE SONORIZAÇÃO 
1º PAVIMENTO - RECEPÇÃO 
SEM ESCALA 
AMPLIFICADOR LINHA 70V 150Wts RMS / CANAL - 
(110/220V) 
DVR 16 CANAIS BNC/1 SAÍDA BNC/1 SAÍDA VGA, 
VELOCIDADE MÍNIMA 120fps NTSC E 
COMUNICAÇÃO DE REDE RJ-45 EM PROTOCOLO 
TCP/IP 
ABRAÇADEIRA 
CIRCULAR 
ELETRODUTO AÇO 
GALVANIZADO (Ø 
CONF.PROJ.) 
TIRANTE ROSCA 
TOTAL Ø1/4" 
DETALHE TÍPICO DE FIXAÇÃO DOS 
FIXAR A CADA 1,50m (NO MÁXIMO) 
SEM ESCALA 
ELETRODUTO DE 
AÇO 
GALVANIZADO 
S6 E PARAFUSO 
DETALHE FIXAÇÃO DO ELETRODUTO 
FIXAÇÃO DIRETA EM PAREDES OU LAJE 
SEM ESCALA - SUPORTAR A CADA 1,50m 
PASSAGEM POR OBSTÁCULOS 
LAJE 
FORRO 
SONOFLETOR (ALTO-FALANTE) 
CAIXA DE PASSAGEM 
4"x4" 
BRAÇADEIRA TIPO "D" 
C/ UNHA A CADA 2m 
DETALHE TÍPICO DE FIXAÇÃO DOS 
SEM ESCALA 
ELETRODUTOS PVC/AÇO 
e 
mm 
e 
mm 
2,3 
2,7 
2,9 
3,0 
3,1 
3,8 
4,0 
5,0 
DIÂMETRO 
NOMINAL-DN 
mm POL 
EXTERNO-DE 
mm 
DIÂMETRO 
NOMINAL-DN 
mm 
25 
32 
40 
50 
60 
75 
85 
110 
POL 
3/4 
1 
1.1/4 
1.1/2 
2 
2.1/2 
3 
4 
EXTERNO-DE 
mm 
25,9 
33,0 
42,0 
47,4 
59,0 
74,7 
87,6 
113,1 
ELETRODUTOS DE AÇO CARBONO, TIPO LEVE I, CONF. NBR 5624 
ESPESSURA NOMINAL DA PAREDE 
ELETRODUTOS DE PVC RÍGIDO ROSQUEÁVEL, CLASSE B, CONF. NBR 6150 
ESPESSURA NOMINAL DA PAREDE 
1,5 
1,5 
2,0 
2,25 
2,25 
2,85 
2,65 
2,65 
20 
25 
32 
40 
50 
65 
80 
100 
3/4 
1 
1.1/4 
1.1/2 
2 
2.1/2 
3 
4 
25,2 
31,5 
40,5 
46,6 
58,4 
74,1 
86,8 
111,6 
NOTAS GERAIS: 
1 - MEDIDAS EM MILÍMETROS, EXCETO ONDE INDICADO. 
2 - CONSIDERAR AS MEDIDAS DAS COTAS PRIORITÁRIAS EM RELAÇÃO À ESCALA. 
3 - OS ELETRODUTOS UTILIZADOS DEVERÃO SER DE AÇO GALVANIZADO, COM NO MÍNIMO Ø1" (25mm). 
4 - EM TODAS AS DERIVAÇÕES DEVERÃO SER UTILIZADAS CAIXAS DE PASSAGEM DO TIPO CONDULETE METÁLICO. 
5 - OS LANCES ENTRE DUAS CAIXAS DE PASSAGEM NÃO DEVERÃO CONTER MAIS DO QUE DUAS CURVAS, 
EVITANDO-SE TAMBÉM CURVAS REVERSAS SEMPRE QUE POSSÍVEL. 
6 - OS ELETRODUTOS DEVERÃO SER PROVIDOS DE BUCHAS E ARRUELAS EM SUAS EXTREMIDADES, EXCETO 
AQUELAS QUE TERMINAM EM CAIXAS DE PASSAGEM. 
7 - SONDAR OS ELETRODUTOS COM ARAME OU CABO DE NYLON, DEIXANDO UMA SOBRA DE ± 1,0m EM CADA 
CAIXA ANTES DA PASSAGEM DOS CABOS. 
8 - AS PONTAS DE TODOS OS CABOS DEVERÃO SER IDENTIFICADAS COM ETIQUETAS TERMOCONTRÁTEIS OU 
OUTRO MÉTODO QUE NÃO PERMITA A RETIRADA DA IDENTIFICAÇÃO SEM DANIFICAR O CABO. OS CABOS 
DEVERÃO SER IDENTIFICADOS CONFORME DESCRITO NESTE PROJETO. 
9 - TODAS AS CONEXÕES ENTRE AMPLIFICADORES, SONOFLETORES, DVR E CÂMERAS DE VÍDEO DEVERÃO 
UTILIZAR OS CONECTORES APROPRIADOS EM CADA PONTA. 
10 - ATERRAR TODAS AS PARTES METÁLICAS NÃO ENERGIZADAS DA INSTALAÇÃO. 
11 - TODOS OS SONOFLETORES (ALTO-FALANTES) DEVERÃO TER SUA POLARIDADE TESTADA NO LOCAL, 
EVITANDO-SE O CANCELAMENTO SONORO NA INTERLIGAÇÃO INVERTIDA. 
12 - O DVR DEVERÁ SER INTERLIGADO À REDE, E A GRAVAÇÃO DE IMAGENS SERÁ REALIZADA EM COMPUTADOR 
DEFINIDO COMO SERVIDOR. O SERVIDOR SERÁ FORNECIDO PELA SES/MG, E NÃO FAZ PARTE DO ESCOPO DA 
EMPRESA INSTALADORA. 
13 - PREVER UMA TOMADA ELÉTRICA PARA CADA CÂMERA A SER INSTALADA. 
1-PROIBIDA REPRODUÇÃO OU ALTERAÇÃO DO CONTEÚDO SEM AUTORIZAÇÃO DOS RESPONSÁVEIS TÉCNICOS DO PROJETO. 
2-DIREITOS AUTORAIS RESERVADOS - LEI FEDERAL 9.610 DE 19/02/1996. 
3-CONFERIR MEDIDAS NO LOCAL. 
RESOLUÇÃO 1797/09 DA SES-MG 
03 ADEQUAÇÃO DA ARQUITETURA CONFORME VISA 01/02/2013 VIABILE 
02 EMISSÃO FINAL 08/11/2012 VIABILE 
00 EMISSÃO INICIAL 22/10/2012 VIABILE 
VERIFICAÇÃO 
Secretaria de Estado de Saúde de Minas Gerais 
Cidade Administrativa Presidente Tancredo Neves 
Rodovia Pref. Américo Gianetti s/nº - Bairro: Serra Verde - B. Hte - 
Minas Gerais - CEP: 31630-900 SES-MG Predio Minas - 12º e 13º andar 
FOLHA: 
01 
02 
REVISÃO OBJETO DATA 
GERENCIAMENTO E PROJETO: 
DESENVOLVIMENTO: 
BRENO DE ASSIS OLIVEIRA FEVEREIRO/2013 
PROJETO DE SONORIZAÇÃO 
VÁRIAS UNIDADES NO ESTADO DE MINAS GERAIS 
ETAPA: 
SIMBOLOGIA, NOTAS GERAIS E DETALHES PROJETO EXECUTIVO 
CONSTRUTIVOS 
Av. Augusto de Lima, nº655 
conj. 418 - Centro - BH 
Telefax: (31) 3324-2702 
http://www.viabile.com.br 
viabile@viabile.com.br 
DATA: 
NOME DO ARQUIVO CAD: 
ESCALA: UNIDADE: 
INDICADA CENTÍMETROS 
CREA-MG: 78.667/D 
RESPONSÁVEL TÉCNICO: 
BRENO DE ASSIS OLIVEIRA 
PROPRIETÁRIO: 
SECRETARIA DO ESTADO DE SAÚDE DE MINAS GERAIS 
460-UBSSS-R03-ESO-01-PE-T1A.DWG 
UBS MINAS - PROJETO MODELO 
DISCIPLINA: 
PROJETO: 
ENDEREÇO: 
CONTEÚDO: 
NOTAS: 
4-COTAS EM CENTÍMETROS. 
SUBSECRETARIA DE VIGILÂNCIA E PROTEÇÃO Á SAÚDE 
SUPERINTENDÊNCIA DE VIGILÂNCIA SANITÁRIA 
DIRETORIA DE INFRAESTRUTURA FÍSICA 
PROJETO MODELO UNIDADE BÁSICA DE SAÚDE 
PROJETO DE ACORDO COM RDC-50/2002 E 
É DE RESPONSABILIDADE DO MUNICIPIO APROVAÇÃO 
COM A IMPLANTAÇÃO NO TERRENO ESCOLHIDO. 
TIPO T1A - ACLIVE 
FORMATO INTERNACIONAL A1 (841 x 594mm) 
abrasip-mg 
01 MUDANÇA DE ARQUITETURA 26/10/2012 VIABILE 
SUBSECRETARIA DE INOVAÇÃO E LOGISTICA 
SUPERINTENDENCIA DE GESTÃO 
DIRETORIA DE GESTÃO DA REDE FÍSICA
4'/)±7'±5(/$d­2'($5*$6(0(0Ï5,$'(È/8/2 
CIRCUITO '(65,d­2 
,/80,1$d­2 
(W) 
BLOCO 
AUTONOMO 
(W) 
6,1$/,=$d­2 
(W) 
TOMADAS 
(W) 
CHUVEIROS 
(W) 
AR CONDICIONADO 
(W) 
16 32 60 25 50 85 170 510 850 1530 6500 1110 
,/80,1$d­29$,1$d­26$/$'( 
(63(5$5((3d­275,$*(02/(7$6$/$'(5(81,­2( 
('8$d­2$7(1',0(17208/7,352),66,21$/ 
,/80,1$d­2$7(1',0(17208/7,352),66,21$/*8$5'$ 
0(',$0(1726*,1(2/2*,$8,'$'26%È6,2685*Ç1,$( 
(0(5*Ç1,$6$/$'(85$7,926(629È5,2 
L1 4 42 0 0 0 0 0 0 0 0 0 0 
L2 0 32 0 0 0 0 0 0 0 0 0 0 
L3 ,/80,1$d­2,58/$d­2%$1+(,526(6$'$'0/ 18 2 1 0 0 0 0 0 0 0 0 0 
,/80,1$d­22168/7Ï5,22'2172/Ï*,2$*(17(6'(6$Ò'( 
$/02;$5,)$'25(6Ë'826 
,/80,1$d­223$9(67,È5,20$68/,129(67,È5,2)(0,1,12 
/$9$*(0('(6,1)(d­2'(0$7(5,$,6(67(5,/,=$d­2'0/ 
,58/$d­2 
L4 10 10 0 0 0 0 0 0 0 0 0 0 
L5 2 20 0 0 0 0 0 0 0 0 0 0 
T1 720$'$65((3d­2±ž3$972 0 0 0 0 0 0 4 0 0 0 0 0 
T2 720$'$69$,1$d­26$/$(63(5$±ž3$972 0 0 0 0 0 5 0 1 0 0 0 0 
T3 720$'$69$,1$d­2±ž3$972 0 0 0 0 0 0 2 1 0 0 0 0 
T4 720$'$675,$*(02/(7$±ž3$972 0 0 0 0 0 3 4 0 0 0 0 0 
T5 720$'$6$7(1',0(17208/7,352),66,21$/±ž3$972 0 0 0 0 0 3 2 0 0 0 0 0 
T6 720$'$6$7(1',0(17208/7,352),66,21$/±ž3$972 0 0 0 0 0 3 2 0 0 0 0 0 
T7 720$'$68,'$'26%È6,2685*Ç1,$((0(5*Ç1,$±ž3$972 0 0 0 0 0 4 2 0 0 0 0 0 
T8 720$'$66$/$'(5(81,­2(('8$d­2±ž3$972 0 0 0 0 0 5 0 0 0 0 0 0 
T9 720$'$66$/$'(5(81,­2(('8$d­2±ž3$972 0 0 0 0 0 2 0 1 0 0 0 0 
T10 720$'$66$/$'(5(81,­2(('8$d­2±*(/$'(,5$±ž3$972 0 0 0 0 0 0 0 1 0 0 0 0 
T11 720$'$6$/$'(5(81,­2(('8$d­2±0,5221'$6±ž3$972 0 0 0 0 0 0 0 0 0 1 0 0 
T12 720$'$6*,1(2/2*,$±ž3$972 0 0 0 0 0 4 2 0 0 0 0 0 
T13 720$'$66$/$'(85$7,926*8$5'$0(',$0(1726±ž3$972 0 0 0 0 0 5 2 0 0 0 0 0 
T14 720$'$6,6,58/$d­2±ž3$972 0 0 0 0 2 7 0 0 0 0 0 0 
T15 32172'()25d$±$521'9$,1$d­2±ž3$972 0 0 0 0 0 0 0 0 0 0 0 1 
T16 32172'()25d$±$521'75,$*(0±ž3$972 0 0 0 0 0 0 0 0 0 0 0 1 
T17 32172'()25d$±$521'2/(7$±ž3$972 0 0 0 0 0 0 0 0 0 0 0 1 
T18 32172'()25d$±$521'$7(1',0(17208/7,352),66,21$/±ž 
PAVTO 
0 0 0 0 0 0 0 0 0 0 0 1 
T19 32172'()25d$±$521'$7(1',0(17208/7,352),66,21$/±ž 
PAVTO 
0 0 0 0 0 0 0 0 0 0 0 1 
T20 32172'()25d$±$521'8,'$'26%È6,26±ž3$972 0 0 0 0 0 0 0 0 0 0 0 1 
T21 32172'()25d$±$521'8,'$'26%È6,26±ž3$972 0 0 0 0 0 0 0 0 0 0 0 1 
T22 32172'()25d$±$521'6$/$'(85$7,926±ž3$972 0 0 0 0 0 0 0 0 0 0 0 1 
T23 32172'()25d$±$521'*,1(2/2*,$±ž3$972 0 0 0 0 0 0 0 0 0 0 0 1 
T24 32172'()25d$±$521'*8$5'$0(',$0(1726±ž3$972 0 0 0 0 0 0 0 0 0 0 0 1 
T25 32172'()25d$±$521'6$/$'(5(81,­2(('8$d­2±ž3$972 0 0 0 0 0 0 0 0 0 0 0 1 
T26 32172'()25d$±$521'6$/$'(5(81,­2(('8$d­2±ž3$972 0 0 0 0 0 0 0 0 0 0 0 1 
T27 32172'()25d$±$521'6$/$'((63(5$±ž3$972 0 0 0 0 0 0 0 0 0 0 0 1 
T28 32172'()25d$3$5$3/$7$)250$(/(9$7Ï5,$±75,)È6,29 0 0 0 0 0 0 0 0 0 0 0 0 
T29 32172'()25d$0217$$5*$ 0 0 0 0 0 0 0 0 0 0 0 0 
T30 720$'$62168/7Ï5,22'2172/Ï*,2±68%62/2 0 0 0 0 0 9 0 0 0 0 0 0 
T31 720$'$62168/7Ï5,22'2172/Ï*,2±68%62/2 0 0 0 0 0 0 0 2 0 0 0 0 
T32 720$'$65(6Ë'826'0/$/02;$5,)$'2(67(5,/,=$d­26$/$'( 
$32,2$*(17(6(1'(0,$6±68%62/2 
0 0 0 0 0 9 0 0 0 0 0 0 
T33 720$'$6/$9$*(0('(6,1)(d­2'(0$7(5,$,6,58/$d­2 
9(67,È5,20$6()(0±68%62/2 
0 0 0 0 0 10 0 0 0 0 0 0 
T34 720$'$(67(5(/,=$d­2±$872/$9(±68%62/2 0 0 0 0 0 0 0 0 1 0 0 0 
T35 321726'()25d$+89(,529(67,È5,20$68/,12±9±68%62/2 0 0 0 0 0 0 0 0 0 0 1 0 
T36 321726'()25d$+89(,529(67,È5,2)(0,1,12±9±68%62/2 0 0 0 0 0 0 0 0 0 0 1 0 
T37 720$'$623$±68%62/2 0 0 0 0 0 4 0 1 0 0 0 0 
T38 720$'$23$±0,5221'$6±68%62/2 0 0 0 0 0 0 0 0 0 1 0 0 
T39 720$'$6$*(17(6'(6$Ò'(±68%62/2 0 0 0 0 0 3 4 0 0 0 0 0 
T40 32172'()25d$±$521'2168/7Ï5,22'2172/Ï*,2± 
SUBSOLO 
0 0 0 0 0 0 0 0 0 0 0 1 
T41 32172'()25d$±$521'2168/7Ï5,22'2172/Ï*,2± 
SUBSOLO 
0 0 0 0 0 0 0 0 0 0 0 1 
T42 32172'()25d$±$521'(67(5,/,=$d­2±68%62/2 0 0 0 0 0 0 0 0 0 0 0 1 
T43 32172'()25d$±$521'/$9$*(0('(6,1)(d­2'(0$7(5,$,6± 
SUBSOLO 
0 0 0 0 0 0 0 0 0 0 0 1 
T44 32172'()25d$±$521'$*(17(6'(6$Ò'(±68%62/2 0 0 0 0 0 0 0 0 0 0 0 1 
T45 32172'()25d$2035(6625 0 0 0 0 0 0 0 0 0 0 0 0 
T46 BLOCO AUTONOMO 0 0 0 8 0 0 0 0 0 0 0 0 
T47 720$'$5$.±ž3$972 0 0 0 0 0 0 0 0 1 0 0 0 
T48 720$'$5$.62125,=$d­2±ž3$972 0 0 0 0 0 0 0 0 1 0 0 0 
T49 TOMADAS CFTV 0 0 0 0 0 6 0 0 0 0 0 0 
TOTAL 34,00 106,00 1,00 8,00 2,00 82,00 24,00 7,00 3,00 2,00 2,00 18,00 
F.P. 327Ç1,$727$/ 7(16­2 FASES (48,/Ë%5,2 
3527(d­2 
P In CURVA 
COMPRESSOR 
(W) 
MONTA CARGA 
(W) 1ž'( 
FASES 
CORRENTE 
NOMINAL 
1Ò0(52'( 
CONDUTORES 
POR FASE 
CONDUTOR 
PPð
850 1471 (kW) (kVA) (V) R S T (A) (A) 
0 0 0,95 1,41 1,48 220 2 RS 0,74 0,74 0,00 6,74 2 x 16 C 1 4,0 
0 0 0,95 1,02 1,08 220 2 TR 0,54 0,00 0,54 4,90 2 x 16 C 1 4,0 
0 0 0,95 0,41 0,43 220 2 ST 0,00 0,22 0,22 1,97 2 x 16 C 1 2,5 
0 0 0,95 0,48 0,51 220 2 RS 0,25 0,25 0,00 2,30 2 x 16 C 1 2,5 
0 0 0,95 0,67 0,71 220 2 TR 0,35 0,00 0,35 3,22 2 x 16 C 1 4,0 
0 0 0,85 0,68 0,80 127 1 R 0,80 0,00 0,00 6,30 1 x 16 C 1 4,0 
0 0 0,85 0,94 1,10 127 1 S 0,00 1,10 0,00 8,66 1 x 16 C 1 4,0 
0 0 0,85 0,85 1,00 127 1 T 0,00 0,00 1,00 7,87 1 x 16 C 1 4,0 
0 0 0,85 0,94 1,10 127 1 R 1,10 0,00 0,00 8,66 1 x 16 C 1 4,0 
0 0 0,85 0,60 0,70 127 1 S 0,00 0,70 0,00 5,51 1 x 16 C 1 4,0 
0 0 0,85 0,60 0,70 127 1 T 0,00 0,00 0,70 5,51 1 x 16 C 1 4,0 
0 0 0,85 0,68 0,80 127 1 S 0,00 0,80 0,00 6,30 1 x 16 C 1 4,0 
0 0 0,85 0,43 0,50 127 1 S 0,00 0,50 0,00 3,94 1 x 16 C 1 4,0 
0 0 0,85 0,68 0,80 127 1 R 0,80 0,00 0,00 6,30 1 x 16 C 1 4,0 
0 0 0,85 0,51 0,60 127 1 S 0,00 0,60 0,00 4,72 1 x 16 C 1 4,0 
0 0 0,85 1,53 1,80 127 1 T 0,00 0,00 1,80 14,17 1 x 16 C 1 6,0 
0 0 0,85 0,68 0,80 127 1 T 0,00 0,00 0,80 6,30 1 x 16 C 1 4,0 
0 0 0,85 0,77 0,90 127 1 S 0,00 0,90 0,00 7,09 1 x 16 C 1 4,0 
0 0 0,85 0,70 0,82 127 1 R 0,82 0,00 0,00 6,44 1 x 16 C 1 4,0 
0 0 0,85 1,11 1,31 220 2 RS 0,65 0,65 0,00 5,94 2 x 16 C 1 4,0 
0 0 0,85 1,11 1,31 220 2 TR 0,65 0,00 0,65 5,94 2 x 16 C 1 4,0 
0 0 0,85 1,11 1,31 220 2 ST 0,00 0,65 0,65 5,94 2 x 16 C 1 4,0 
0 0 0,85 1,11 1,31 220 2 RS 0,65 0,65 0,00 5,94 2 x 16 C 1 4,0 
0 0 0,85 1,11 1,31 220 2 TR 0,65 0,00 0,65 5,94 2 x 16 C 1 4,0 
0 0 0,85 1,11 1,31 220 2 ST 0,00 0,65 0,65 5,94 2 x 16 C 1 4,0 
0 0 0,85 1,11 1,31 220 2 RS 0,65 0,65 0,00 5,94 2 x 16 C 1 4,0 
0 0 0,85 1,11 1,31 220 2 TR 0,65 0,00 0,65 5,94 2 x 16 C 1 4,0 
0 0 0,85 1,11 1,31 220 2 ST 0,00 0,65 0,65 5,94 2 x 16 C 1 4,0 
0 0 0,85 1,11 1,31 220 2 RS 0,65 0,65 0,00 5,94 2 x 16 C 1 4,0 
0 0 0,85 1,11 1,31 220 2 TR 0,65 0,00 0,65 5,94 2 x 16 C 1 4,0 
0 0 0,85 1,11 1,31 220 2 TR 0,65 0,00 0,65 5,94 2 x 16 C 1 4,0 
0 0 0,85 1,11 1,31 220 2 ST 0,00 0,65 0,65 5,94 2 x 16 C 1 4,0 
0 0 0,85 1,47 1,73 220 3 RST 0,58 0,58 0,58 4,54 3 x 16 C 1 4,0 
0 1 0,85 1,47 1,73 220 3 RST 0,58 0,58 0,58 4,54 3 x 16 C 1 4,0 
0 0 0,85 0,77 0,90 127 1 T 0,00 0,00 0,90 7,09 1 x 16 C 1 4,0 
0 0 0,85 1,02 1,20 127 1 R 1,20 0,00 0,00 9,45 1 x 16 C 1 4,0 
0 0 0,85 0,77 0,90 127 1 S 0,00 0,90 0,00 7,09 1 x 16 C 1 4,0 
0 0 0,85 0,85 1,00 127 1 T 0,00 0,00 1,00 7,87 1 x 16 C 1 4,0 
0 0 0,85 0,85 1,00 127 1 R 1,00 0,00 0,00 7,87 1 x 16 C 1 4,0 
0 0 1,00 6,50 6,50 220 2 RS 3,25 3,25 0,00 29,55 2 x 32 C 1 4,0 
0 0 1,00 6,50 6,50 220 2 TR 3,25 0,00 3,25 29,55 2 x 32 C 1 4,0 
0 0 0,85 0,85 1,00 127 1 S 0,00 1,00 0,00 7,87 1 x 16 C 1 4,0 
0 0 0,85 1,53 1,80 127 1 T 0,00 0,00 1,80 14,17 1 x 16 C 1 4,0 
0 0 0,85 0,94 1,10 127 1 S 0,00 1,10 0,00 8,66 1 x 16 C 1 4,0 
0 0 0,85 1,11 1,31 220 2 TR 0,65 0,00 0,65 5,94 2 x 16 C 1 4,0 
0 0 0,85 1,11 1,31 220 2 ST 0,00 0,65 0,65 5,94 2 x 16 C 1 4,0 
0 0 0,85 1,11 1,31 220 2 RS 0,65 0,65 0,00 5,94 2 x 16 C 1 4,0 
0 0 0,85 1,11 1,31 220 2 TR 0,65 0,00 0,65 5,94 2 x 16 C 1 4,0 
0 0 0,85 1,11 1,31 220 2 ST 0,00 0,65 0,65 5,94 2 x 16 C 1 4,0 
1 0 0,85 0,85 1,00 220 2 RS 0,50 0,50 0,00 4,55 2 x 16 C 1 4,0 
0 0 0,85 0,20 0,24 127 1 T 0,00 0,00 0,24 1,85 1 x 16 C 1 2,5 
0 0 0,85 0,85 1,00 127 1 R 1,00 0,00 0,00 7,87 1 x 16 C 1 4,0 
0 0 0,85 0,85 1,00 127 1 T 0,00 0,00 1,00 7,87 1 x 16 C 1 4,0 
0 0 0,85 0,51 0,60 127 1 R 0,60 0,00 0,00 4,72 1 x 16 C 1 4,0 
1,00 1,00 0,88 61,30 69,33 380 3 RST 23,31 19,69 22,13 105,46 3 x 125 D 1 50,0 
0(0Ï5,$'(È/8/2 
'5±P$ 
48('$'(7(16­2 
QUEDA DE 
7(16­2()(7,9$ 
LIMITE: 
COMPRIMENTO 
0È;,02'2 
CIRCUITO 
(m) 3,00% '5±$ 
40 1,05% 
30 0,57% 
45 0,55% X 
18 0,26% 
14 0,18% X 
42 1,79% 
44 2,58% 
44 2,35% 
40 2,35% 
37 1,38% 
32 1,19% 
29 1,24% 
40 1,07% 
41 1,75% X 
41 1,31% X 
41 2,62% X 
32 1,36% 
33 1,58% 
43 1,87% X 
43 1,00% 
39 0,90% 
39 0,90% 
32 0,74% 
32 0,74% 
29 0,67% 
24 0,56% 
28 0,65% 
33 0,77% 
34 0,79% 
36 0,84% 
36 0,84% 
36 0,84% 
15 0,23% 
11 0,17% 
15 0,72% 
9 0,58% 
22 1,06% X 
11 0,59% X 
11 0,59% 
13 1,50% X 
14 1,62% X 
16 0,85% X 
15 1,44% X 
17 1,00% 
15 0,35% 
12 0,28% 
14 0,32% 
14 0,32% 
14 0,32% 
18 0,32% 
50 1,00% 
40 2,13% 
40 2,13% 
40 1,28% 
40 0,66% 
NOTAS: 
1-PROIBIDA REPRODUÇÃO OU ALTERAÇÃO DO CONTEÚDO SEM AUTORIZAÇÃO DOS RESPONSÁVEIS TÉCNICOS DO PROJETO. 
2-DIREITOS AUTORAIS RESERVADOS - LEI FEDERAL 9.610 DE 19/02/1996. 
3-CONFERIR MEDIDAS NO LOCAL. 
4-COTAS EM CENTÍMETROS. 
RESOLUÇÃO 1797/09 DA SES-MG 
03 ADEQUAÇÃO DA ARQUITETURA CONFORME VISA 01/02/2013 VIABILE 
02 EMISSÃO FINAL 08/11/2012 VIABILE 
00 EMISSÃO INICIAL 27/09/2012 VIABILE 
VERIFICAÇÃO 
Secretaria de Estado de Saúde de Minas Gerais 
Cidade Administrativa Presidente Tancredo Neves 
Rodovia Pref. Américo Gianetti s/nº - Bairro: Serra Verde - B. Hte - 
Minas Gerais - CEP: 31630-900 SES-MG Predio Minas - 12º e 13º andar 
FOLHA: 
05 
05 
REVISÃO OBJETO DATA 
GERENCIAMENTO E PROJETO: 
DESENVOLVIMENTO: 
BRENO ASSIS DE OLIVEIRA FEVEREIRO/2013 
INSTALAÇÕES ELÉTRICAS 
VÁRIAS UNIDADES NO ESTADO DE MINAS GERAIS 
ETAPA: 
QUADRO DE CARGAS PROJETO EXECUTIVO 
Av. Augusto de Lima, nº655 
conj. 418 - Centro - BH 
Telefax: (31) 3324-2702 
http://www.viabile.com.br 
viabile@viabile.com.br 
DATA: 
NOME DO ARQUIVO CAD: 
ESCALA: UNIDADE: 
INDICADA MILÍMETROS 
CREA: 78.667/D 
RESPONSÁVEL TÉCNICO: 
BRENO ASSIS DE OLIVEIRA 
PROPRIETÁRIO: 
SECRETARIA DO ESTADO DE SAÚDE DE MINAS GERAIS 
460-UBSSS-R03-ELE-05-PE-T1A.DWG 
UBS MINAS - PROJETO MODELO 
DISCIPLINA: 
PROJETO: 
ENDEREÇO: 
CONTEÚDO: 
SUBSECRETARIA DE VIGILÂNCIA E PROTEÇÃO Á SAÚDE 
SUPERINTENDÊNCIA DE VIGILÂNCIA SANITÁRIA 
DIRETORIA DE INFRAESTRUTURA FÍSICA 
PROJETO MODELO UNIDADE BÁSICA DE SAÚDE 
PROJETO DE ACORDO COM RDC-50/2002 E 
É DE RESPONSABILIDADE DO MUNICIPIO APROVAÇÃO 
COM A IMPLANTAÇÃO NO TERRENO ESCOLHIDO. 
TIPO T1A - ACLIVE 
FORMATO INTERNACIONAL A1 ALONGADO (1026 x 594mm) 
abrasip-mg 
01 ALIMENTAÇÃO DOS PONTOS DE CFTV, RACK DE SONORIZAÇÃO E BEBEDOUROS 26/10/2012 VIABILE 
SUBSECRETARIA DE INOVAÇÃO E LOGISTICA 
SUPERINTENDENCIA DE GESTÃO 
DIRETORIA DE GESTÃO DA REDE FÍSICA
#10,0 
FUSÍVEL MODULAR 
#10,0 DPS 
275V 
20kA - 8/20us 
R 
S 
T 
TERRA 
#10,0 
#10,0 
#10,0 
#10,0 
32A 
DE ALIMENTADORES/IMPLANTAÇÃO 
40A (C) 
40A (C) 40A (C) 
125A 
MÍNIMO DE 10kA 
BARRA 1 - IN MÍNIMO: 150A - TRIFÁSICO - Icc MÍNIMO: 10kA 
L1 
16A 
#4,0 
L4 
16A 
BARRA 2 - PENTE TRIFÁSICO MÍNIMO 24 PINOS - 80A 
VER PROJETO ESPECÍFICO 
Pe R S T N 
#6,0 
#10,0 
#10,0 
#10,0 
T19 
16A 
#4,0 
T17 
16A 
#4,0 
16A 
#4,0 
T39 T41 
16A 
T40 
16A 
QDC-T1/A - DIAGRAMA MULTIFILAR (96 POLOS) 
NEUTRO DR 
L2 
16A 
#4,0 
#6,0 
#6,0 
NEUTRO 
#6,0 
#10,0 
#6,0 
BARRA 3 - PENTE TRIFÁSICO MÍNIMO 24 PINOS - 80A 
#2,5 
R 
S 
T 
R 
S 
T 
BARRA 4 - PENTE TRIFÁSICO MÍNIMO 24 PINOS - 80A 
DETALHE SUGESTIVO DO QUADRO 
QUADRO METÁLICO DE SOBREPOR 
INTERRUPTOR 
TETRAPOLAR 
DR3-In 40A 
SENS. 30mA 
TIPO AC 
R 
S 
T 
BARRA 5 - PENTE TRIFÁSICO MÍNIMO 23 PINOS - 80A 
#4,0 
T1 
16A 
#4,0 
T6 
16A 
#4,0 
T13 
16A 
#4,0 
T8 T12 
T25 
16A 
#4,0 
T23 
16A 
#4,0 
T44 
#4,0 #4,0 #2,5 #2,5 #2,5 
16A 
#4,0 
T9 
16A 
#4,0 
T33 
32A 
#6,0 
RES. 
40A (C) 
#6,0 
T2 
16A 
#4,0 
T3 
16A 
#4,0 
T5 T4 
16A 
#4,0 
16A 
#4,0 
16A 
#4,0 
16A 
#4,0 
T16 
16A 
#4,0 
T45 
T18 
16A 
#4,0 
T20 
16A 
#4,0 
T21 
16A 
#4,0 
T22 
16A 
#4,0 
T24 
16A 
#4,0 
T26 
16A 
#4,0 
T27 
16A 
#4,0 
T28 
16A 
#4,0 
T29 
16A 
#4,0 
T30 
16A 
#4,0 
T37 
16A 
#4,0 
T38 
#4,0 
16A 
#4,0 
T42 
16A 
#4,0 
16A 
#4,0 
T46 
16A 
#2,5 
T10 RES. 
16A 
#4,0 
T11 
16A 
#6,0 
T14 
16A 
#4,0 
T31 
16A 
#4,0 
T32 
16A 
#4,0 
T34 
32A 
#6,0 
T35 
16A 
#4,0 
T36 
16A 
#4,0 
RES. RES. 
40A (C) 
#6,0 
T7 
16A 
#4,0 
T43 
16A 
L3 
16A 
#2,5 
L5 
16A 
#4,0 
RES. RES. RES. 
T47 
16A 
#4,0 
T15 
16A 
#4,0 
RES. 
T48 
16A 
#4,0 
T49 
16A 
#4,0 
SIMBOLOGIA P/ QUADRO: 
DISPOSITIVO PROTETOR DE SURTOS (DPS) PARA FASES E 
NEUTRO. CARACTERÍSTICAS TÉCNICAS DOS DPS's CLASSE I E 
CLASSE II, SEGUNDO NBR5410: - OBEDECER A NBR IEC 61.643-1; 
Up (NÍVEL DE PROTEÇÃO): INFERIOR A 1,5kV; - Uc (MÁXIMA 
TENSÃO DE OPERAÇÃO CONTÍNUA): 275V; - Iimp (CORRENTE DE 
IMPULSO): SUPERIOR A 12,5kA (10/350us); - In (CORRENTE 
NOMINAL DE DESCARGA): SUPERIOR A 20kA (8/20us) PARA REDES 
TRIFÁSICAS; 
PARA DPS CLASSE I (Uc 275V/12,5/60KA), UTILIZAR NAS FASES 
COMO PROTEÇÃO BACKUP, FUSÍVEIS MODULARES NH-63A gG/gL. 
PARA DPS CLASSE II (Uc 275V/20kA, 8/20us), UTILIZAR NAS FASES E 
NEUTRO COMO PROTEÇÃO BACKUP, FUSÍVEIS MODULARES 
NH-32A gG/gL. INDICAÇÃO NOS QUADROS. O POSIONAMENTO DOS 
FUSÍVEIS/DPS'S, DEVERÁ ESTAR EM CONFORMIDADE COM A 
FIGURA 14-a DA NBR 5410. 
DISPOSITIVO DIFERENCIAL RESIDUAL (DR). CARACTERÍSTICAS 
TÉCNICAS: - OBEDECER IEC 1008; - NÚMERO DE MÓDULOS: 4; 
- CORRENTE NOMINAL (IN): CONFORME INDICAÇÃO EM PLANTA; 
- SENSIBILIDADE: 30mA; TENSÃO MÁXIMA: 415Vca TETRAPOLAR; 
FREQUÊNCIA: 60Hz; TIPO: AC. 
DISJUNTORES TERMO-MAGNÉTICOS (MINI DISJUNTORES), 
CURVAS B, C OU D CONFORME INDICAÇÃO NOS QUADROS, 
SEGUNDO A NORMA IEC-60947-2 E DIMENSIONADOS PARA 
Icc = 5,0kA/220V( MONOPOLAR, BIPOLAR E TRIPOLAR, 
RESPECTIVAMENTE). 
PARA OS DISJUNTORES GERAIS DEVERÃO SER SEGUIDOS 
TAMBÉM OS CRITÉRIOS DA NORMA IEC-60947-2, PORÉM 
DEVERÃO SER DO TIPO EM CAIXA MOLDADA, TERMOMAGNÉTICO 
E DIMENSIONADOS PARA Icc MÍNIMO = 10,0kA/220V. 
CABO DE COBRE COM ISOLAÇÃO TERMOPLÁSTICO NÃO 
HALOGENADO E COM BAIXA EMISSÃO DE FUMAÇA, 70°C 750V, 
CLASSE 5 DE ENCORDOAMENTO (FASES - COR PRETA). 
CABO DE COBRE COM ISOLAÇÃO TERMOPLÁSTICO NÃO 
HALOGENADO E COM BAIXA EMISSÃO DE FUMAÇA, 70°C 750V, 
CLASSE 5 DE ENCORDOAMENTO (NEUTRO - COR AZUL CLARO). 
CABO DE COBRE COM ISOLAÇÃO TERMOPLÁSTICO NÃO 
HALOGENADO E COM BAIXA EMISSÃO DE FUMAÇA, 70°C 750V, 
CLASSE 5 DE ENCORDOAMENTO (TERRA - COR VERDE). 
NOTAS GERAIS DOS QUADROS: 
01 - TODOS OS DISJUNTORES DOS CIRCUITOS TERMINAIS OBEDECERÃO À NBR IEC-60.947-2 
(MINI-DISJUNTORES PADRÃO EUROPEU CURVAS B, C OU D CONFORME INDICAÇÃO NOS QUADROS DE 
CARGAS) E SERÃO DIMENSIONADOS PARA Icc = 5,0kA/220V. OS DISJUNTORES GERAIS TAMBÉM 
OBEDECERÃO À NBR IEC-60 .947-2, PORÉM, SERÃO DIMENSIONADOS PARA Icc = 10kA/220V E DEVERÃO SER 
DO TIPO TERMOMAGNÉTICO EM CAIXA MOLDADA . 
02 - TODOS OS DISJUNTORES NO INTERIOR DOS QUADROS DEVERÃO SER IDENTIFICADOS ATRAVÉS DE 
ETIQUETAS ACRÍLICAS DE IDENTIFICAÇÃO CONFORME NOMES DOS CIRCUITOS CONSTANTES NOS 
QUADROS DE CARGAS. 
03 - FORAM PREVISTOS ESPAÇOS RESERVAS MÍNIMOS PARA AMPLIAÇÕES FUTURAS, COM BASE NO 
NÚMERO DE CIRCUITOS EFETIVAMENTE INSTALADO NO QDC E DE ACORDO COM A NBR-5410:2004. 
04 - O QUADRO SERÁ METÁLICO, DE EMBUTIR (PREVER ALVENARIA PARA SUSTENTAÇÃO), COM NO MÍNIMO 
IP-30 (EM EXCEÇÃO AOS QUADROS LOCALIZADOS AO TEMPO, QUE DEVERÃO POSSUIR GRAU DE 
PROTEÇÃO MÍNIMO IP-54), PROVIDO DE ALETAS PARA VENTILAÇÃO, PORTA DE TRINCO COM CHAVE, NÃO 
ESTAR INSTALADO EM ÁREAS MOLHADAS OU ÚMIDAS, LONGE DE GÁS, DOTADO DE FÁCIL ACESSO E NÃO 
SER OBSTRUÍDO, DEVENDO POSSUIR SOBRETUDO, CERTIFICAÇÃO DE TESTES SEGUNDO NBR IEC 60.439-1 
EMITIDO POR EMPRESA ESPECIALIZADA NA MONTAGEM DE QUADROS ELÉTRICOS. 
05 - O QUADRO DEVERÁPOSSUIR, ALÉM DOS DISJUNTORES TERMINAIS DESCRITOS NO QUADRO DE 
CARGAS, DISPOSITIVOS DR, DPS DE ENTRADA COM PROTEÇÃO BACKUP, BARRAS DE TERRA E NEUTRO, 
SENDO AS BARRAS DE NEUTRO PARA DR SEGREGADAS DA BARRA DE NEUTRO GERAL DO QUADRO, 
CONFORME LAYOUT SUGESTIVO DO DIAGRAMA MULTIFILAR. 
06 - O QUADRO DEVERÁ POSSUIR PLACA DE MONTAGEM INTERNA NA COR LARANJA, CANALETAS PARA A 
PASSAGEM DE CABOS (RESPEITANDO A TAXA DE OCUPAÇÃO MÁXIMA DOS CABOS NESTAS CANALETAS, 
SEGUNDO ORIENTAÇÕES DA NBR 5410), BASE CONECTORA PARA A DISTRIBUIÇÃO DOS CABOS (ENTRADA E 
SAÍDA) E IDENTIFICAÇÃO DE NOME, TENSÃO E FREQUÊNCIA EM SUA PORTA, EM ETIQUETA ACRÍLICA DE 
FUNDO PRETO E LETRAS BRANCAS. TAMBÉM DEVERÁ POSSUIR UMA PLACA DE ADVERTÊNCIA INTERNA AO 
QUADRO, CONFORME DIZERES NESTA FOLHA. PREVER SOBRETUDO ESPAÇOS PARA DR E DPS CONFORME 
DETALHADO NO DIAGRAMA MULTIFILAR. 
07- NO QUADRO DEVERÃO SER FIXADOS, ATRAVÉS DE DISPOSITIVO PRÓPRIO, OS DIAGRAMAS DOS 
MESMOS, CONTENDO TODAS AS PROTEÇÕES ENVOLVIDAS CONFORME EXECUTADO . 
08- AS TERMINAÇÕES DOS ELETRODUTOS NO QUADROS ELÉTRICO, SEJAM ELES METÁLICOS OU EM 
MATERIAL PLÁSTICO ANTI-CHAMA (PVC RÍGIDO), DEVERÃO SER COM CONECTOR TIPO BOX RETO, COM 
BUCHA E ARRUELA DE ACABAMENTO, ADEQUADAS ÀS BITOLAS DO MESMO. AS ELETROCALHAS DEVERÃO 
SER PROVIDAS DE FLANGES PRÉ-MOLDADOS CONFORME DIMENSÕES DE PROJETO. 
09- AS TERMINAÇÕES DOS CABOS NO QUADRO ELÉTRICO DEVERÃO RECEBER TEMINAL DO TIPO AGULHA 
PARA CONEXÃO COM OS BORNES DOS DISJUNTORES E TERMINAL TIPO OLHAL PARA CONEXÃO NOS 
BARRAMENTOS. TODOS OS TERMINAIS DEVERÃO SER COMPRIMIDOS ATRAVÉS DE FERRAMENTA 
ADEQUADA. 
10- O QUADRO DEVER Á ESTAR LIMPO, LIVRE DE ARGAMASSAS, POEIRA, CAPA DE CABOS, FILAMENTOS DE 
CABOS DE COBRE E OUTROS MATERIAIS ESTRANHOS À INSTALAÇÃO. 
11- OS TERMINAIS DAS BARRAS DE CONEXÃO NÃO UTILIZADOS DEVERÃO SER ISOLADOS POR CAPA 
PROTETORA ADEQUADA, DO MESMO FABRICANTE DAS BARRAS DE CONEXÃO . 
12- TODOS OS CABOS ALIMENTADORES DOS CIRCUITOS INTERNOS AO QUADRO SERÃO DE COBRE COM 
ISOLAÇÃO TERMOPLÁSTICO NÃO HALOGENADO E COM BAIXA EMISSÃO DE FUMAÇA 70 ºC 750V. DEVERÃO 
SOBRETUDO, RECEBER ETIQUETAS DE IDENTIFICAÇÃO (TAG´s), INDELÉVEIS, COM INDICAÇÃO DO CIRCUITO 
A QUE ESTÁ LIGADO, CONFORME DESCRIÇÃO DO CAMPO CIRCUITO DO QUADRO DE CARGAS 
CORRESPONDENTE. 
13 - ATERRAR TODAS AS PORTAS DOS QUADROS ATRAVÉS DE CABO DE COBRE #6,0mm² ISOLAÇÃO VERDE 
EM PVC 70°C 750V. 
14 - CONFORME NBR 5410/2004, DEVIDO A POSSIBILIDADE DE FALHA INTERNA, FAZENDO COM QUE OS 
DPS`s ENTRE EM CURTO CIRCUITO, A NORMA IMPÕE A NECESSIDADE DE DISPOSITIVO DE PROTEÇÃO PARA 
ELIMINAR TAL CURTO CIRCUITO. DESTA FORMA, DEVERÁ SER UTILIZADO, EM TODOS OS QUADROS, ANTES 
E EM SÉRIE COM O DPS, DISPOSITIVO DE BACK UP PARA DEVIDA PROTEÇÃO. PARA DPS`s CLASSE I , 
FUSÍVEIS DO TIPO MODULAR 63A . PARA DPS´s CLASSE II , FUSÍVEIS TIPO MODULAR 32A . 
ADVERTÊNCIA 
1- QUANDO UM DISJUNTOR OU FUSÍVEL ATUA, DESLIGANDO ALGUM CIRCUITO OU A 
INSTALAÇÃO INTEIRA, A CAUSA PODE SER UMA SOBRECARGA OU UM CURTO-CIRCUITO. 
DESLIGAMENTOS FREQUENTES SÃO SINAL DE SOBRECARGA. POR ISSO, NUNCA TROQUE 
SEUS DISJUNTORES OU FUSÍVEIS POR OUTRO DE MAIOR CORRENTE (MAIOR AMPERAGEM) 
SIMPLESMENTE. COMO REGRA, A TROCA DE UM DISJUNTOR OU FUSÍVEL POR OUTRO DE 
MAIOR CORRENTE REQUER, ANTES, A TROCA DOS FIOS E CABOS ELÉTRICOS, POR OUTROS 
DE MAIOR SEÇÃO (BITOLA). 
2- DA MESMA FORMA, NUNCA DESATIVE OU REMOVA A CHAVE AUTOMÁTICA DE PROTEÇÃO 
CONTRA CHOQUES ELÉTRICOS (DISPOSITIVOS DR), MESMO EM CASO DE DESLIGAMENTOS 
SEM CAUSA APARENTE. SE OS DESLIGAMENTOS FOREM FREQUENTES E, PRINCIPALMENTE, 
SE AS TENTATIVAS DE RELIGAR A CHAVE NÃO TIVEREM ÊXITO, ISSO SIGNIFICA, MUITO 
PROVAVELMENTE, QUE A INSTALAÇÃO ELÉTRICA APRESENTA ANOMALIAS INTERNAS, QUE 
SÓ PODEM SER IDENTIFICADAS E CORRIGIDAS POR PROFISSIONAIS QUALIFICADOS. A 
DESATIVAÇÃO OU REMOÇÃO DA CHAVE SIGNIFICA A ELIMINAÇÃO DE MEDIDA PROTETORA 
CONTRA CHOQUES ELÉTRICOS E RISCO DE VIDA PARA OS USUÁRIOS DA INSTALAÇÃO. 
DETALHE DA ADVERTÊNCIA SEGUNDO A NBR 5410 
A SER FIXADA DENTRO DOS QUADROS ELÉTRICOS 
TABELA 1: ESPAÇO RESERVA 
QUANTIDADE DE CIRCUITOS 
EFETIVAMENTE DISPONÍVEL 
N 
ESPAÇO MÍNIMO DESTINADO A 
RESERVA (EM NÚMEROS DE 
CIRCUITOS) 
ATÉ 6 2 
7 A 12 3 
13 A 30 4 
N30 0,15xN 
NOTAS: 
1-PROIBIDA REPRODUÇÃO OU ALTERAÇÃO DO CONTEÚDO SEM AUTORIZAÇÃO DOS RESPONSÁVEIS TÉCNICOS DO PROJETO. 
2-DIREITOS AUTORAIS RESERVADOS - LEI FEDERAL 9.610 DE 19/02/1996. 
3-CONFERIR MEDIDAS NO LOCAL. 
4-COTAS EM CENTÍMETROS. 
SUBSECRETARIA DE VIGILÂNCIA E PROTEÇÃO Á SAÚDE 
SUPERINTENDÊNCIA DE VIGILÂNCIA SANITÁRIA 
DIRETORIA DE INFRAESTRUTURA FÍSICA 
PROJETO MODELO UNIDADE BÁSICA DE SAÚDE 
PROJETO DE ACORDO COM RDC-50/2002 E 
RESOLUÇÃO 1797/09 DA SES-MG 
É DE RESPONSABILIDADE DO MUNICIPIO APROVAÇÃO 
COM A IMPLANTAÇÃO NO TERRENO ESCOLHIDO. 
03 ADEQUAÇÃO DA ARQUITETURA CONFORME VISA 01/02/2013 VIABILE 
02 EMISSÃO FINAL 08/11/2012 VIABILE 
01 ALIMENTAÇÃO DOS PONTOS DE CFTV, RACK DE SONORIZAÇÃO E BEBEDOUROS 26/10/2012 VIABILE 
00 EMISSÃO INICIAL 27/09/2012 VIABILE 
VERIFICAÇÃO 
FOLHA: 
04 
05 
REVISÃO OBJETO DATA 
GERENCIAMENTO E PROJETO: 
DESENVOLVIMENTO: 
BRENO ASSIS DE OLIVEIRA FEVEREIRO/2013 
INSTALAÇÕES ELÉTRICAS 
VÁRIAS UNIDADES NO ESTADO DE MINAS GERAIS 
ETAPA: 
DIAGRAMA MULTIFILAR PROJETO EXECUTIVO 
Av. Augusto de Lima, nº655 
conj. 418 - Centro - BH 
Telefax: (31) 3324-2702 
http://www.viabile.com.br 
viabile@viabile.com.br 
DATA: 
NOME DO ARQUIVO CAD: 
ESCALA: UNIDADE: 
INDICADA MILÍMETROS 
CREA: 78.667/D 
RESPONSÁVEL TÉCNICO: 
BRENO ASSIS DE OLIVEIRA 
PROPRIETÁRIO: 
SECRETARIA DO ESTADO DE SAÚDE DE MINAS GERAIS 
460-UBSSS-R03-ELE-04-PE-T1A.DWG 
UBS MINAS - PROJETO MODELO 
DISCIPLINA: 
PROJETO: 
ENDEREÇO: 
CONTEÚDO: 
SUBSECRETARIA DE INOVAÇÃO E LOGISTICA 
SUPERINTENDENCIA DE GESTÃO 
DIRETORIA DE GESTÃO DA REDE FÍSICA 
TIPO T1A - ACLIVE 
FORMATO INTERNACIONAL A1 (841 x 594mm) 
abrasip-mg 
Secretaria de Estado de Saúde de Minas Gerais 
Cidade Administrativa Presidente Tancredo Neves 
Rodovia Pref. Américo Gianetti s/nº - Bairro: Serra Verde - B. Hte - 
Minas Gerais - CEP: 31630-900 SES-MG Predio Minas - 12º e 13º andar

Contenu connexe

En vedette

Apresentacao Reformas, Ampliações e Construções
Apresentacao Reformas, Ampliações e ConstruçõesApresentacao Reformas, Ampliações e Construções
Apresentacao Reformas, Ampliações e ConstruçõesAlfredo Martins
 
Projeto de Layout de um Centro de Distribuição - Intralogistica
Projeto de Layout de um Centro de Distribuição - IntralogisticaProjeto de Layout de um Centro de Distribuição - Intralogistica
Projeto de Layout de um Centro de Distribuição - IntralogisticaAlex Felix Nepomuceno
 
Escopo da Construção de uma UBS
Escopo da Construção de uma UBSEscopo da Construção de uma UBS
Escopo da Construção de uma UBSMarco Coghi
 
Upa unidade de pronto atendimento regional sul
Upa   unidade de pronto atendimento regional sulUpa   unidade de pronto atendimento regional sul
Upa unidade de pronto atendimento regional sulPrestone
 
Manual estrutura ubs
Manual estrutura ubsManual estrutura ubs
Manual estrutura ubsrosa07
 
Arquitetura Hospitalar | 1ª Semana de Design de Interiores de Juiz de Fora
Arquitetura Hospitalar | 1ª Semana de Design de Interiores de Juiz de ForaArquitetura Hospitalar | 1ª Semana de Design de Interiores de Juiz de Fora
Arquitetura Hospitalar | 1ª Semana de Design de Interiores de Juiz de ForaArto Arquitetura
 
Plantas Técnicas de Piso, Teto e Demolir-Construir
Plantas Técnicas de Piso, Teto e Demolir-ConstruirPlantas Técnicas de Piso, Teto e Demolir-Construir
Plantas Técnicas de Piso, Teto e Demolir-Construirdanilosaccomori
 
As Unidades de Saúde Familiar (USF) : organização, funcionamento e modelos de...
As Unidades de Saúde Familiar (USF) : organização, funcionamento e modelos de...As Unidades de Saúde Familiar (USF) : organização, funcionamento e modelos de...
As Unidades de Saúde Familiar (USF) : organização, funcionamento e modelos de...COLUFRAS
 
PAC 2 em Pernambuco - balanço de janeiro de 2012
PAC 2 em Pernambuco - balanço de janeiro de 2012PAC 2 em Pernambuco - balanço de janeiro de 2012
PAC 2 em Pernambuco - balanço de janeiro de 2012Giovanni Sandes
 
4 a 20 mili amperes 0 a 10 volts relatorio projeto circuito trabalho
4 a 20 mili amperes 0 a 10 volts relatorio projeto circuito trabalho4 a 20 mili amperes 0 a 10 volts relatorio projeto circuito trabalho
4 a 20 mili amperes 0 a 10 volts relatorio projeto circuito trabalhoZeca Leite
 
UPA - BELO HORIZONTE
UPA - BELO HORIZONTEUPA - BELO HORIZONTE
UPA - BELO HORIZONTEMarco Coghi
 
Mapacirurgico
MapacirurgicoMapacirurgico
Mapacirurgicocrisenf
 
Zanettini - Apresentação
Zanettini - ApresentaçãoZanettini - Apresentação
Zanettini - Apresentaçãofe_17
 
Apoio diagnostico-terapia-anatomia-somasus-vol4
Apoio diagnostico-terapia-anatomia-somasus-vol4Apoio diagnostico-terapia-anatomia-somasus-vol4
Apoio diagnostico-terapia-anatomia-somasus-vol4Joceline Costa
 

En vedette (20)

Projetos arquitetonicos de saude
Projetos arquitetonicos de saudeProjetos arquitetonicos de saude
Projetos arquitetonicos de saude
 
Apresentacao Reformas, Ampliações e Construções
Apresentacao Reformas, Ampliações e ConstruçõesApresentacao Reformas, Ampliações e Construções
Apresentacao Reformas, Ampliações e Construções
 
ARQUITETURA ASSISTENCIAL E SAÚDE: DISCUTINDO CONCEPÇÕES E PROTAGONISTAS
ARQUITETURA ASSISTENCIAL E SAÚDE: DISCUTINDO CONCEPÇÕES E PROTAGONISTASARQUITETURA ASSISTENCIAL E SAÚDE: DISCUTINDO CONCEPÇÕES E PROTAGONISTAS
ARQUITETURA ASSISTENCIAL E SAÚDE: DISCUTINDO CONCEPÇÕES E PROTAGONISTAS
 
Projeto de Layout de um Centro de Distribuição - Intralogistica
Projeto de Layout de um Centro de Distribuição - IntralogisticaProjeto de Layout de um Centro de Distribuição - Intralogistica
Projeto de Layout de um Centro de Distribuição - Intralogistica
 
Escopo da Construção de uma UBS
Escopo da Construção de uma UBSEscopo da Construção de uma UBS
Escopo da Construção de uma UBS
 
Upa unidade de pronto atendimento regional sul
Upa   unidade de pronto atendimento regional sulUpa   unidade de pronto atendimento regional sul
Upa unidade de pronto atendimento regional sul
 
Manual estrutura ubs
Manual estrutura ubsManual estrutura ubs
Manual estrutura ubs
 
Arquitetura Hospitalar | 1ª Semana de Design de Interiores de Juiz de Fora
Arquitetura Hospitalar | 1ª Semana de Design de Interiores de Juiz de ForaArquitetura Hospitalar | 1ª Semana de Design de Interiores de Juiz de Fora
Arquitetura Hospitalar | 1ª Semana de Design de Interiores de Juiz de Fora
 
Plantas Técnicas de Piso, Teto e Demolir-Construir
Plantas Técnicas de Piso, Teto e Demolir-ConstruirPlantas Técnicas de Piso, Teto e Demolir-Construir
Plantas Técnicas de Piso, Teto e Demolir-Construir
 
As Unidades de Saúde Familiar (USF) : organização, funcionamento e modelos de...
As Unidades de Saúde Familiar (USF) : organização, funcionamento e modelos de...As Unidades de Saúde Familiar (USF) : organização, funcionamento e modelos de...
As Unidades de Saúde Familiar (USF) : organização, funcionamento e modelos de...
 
Projeto 2
Projeto 2Projeto 2
Projeto 2
 
PAC 2 em Pernambuco - balanço de janeiro de 2012
PAC 2 em Pernambuco - balanço de janeiro de 2012PAC 2 em Pernambuco - balanço de janeiro de 2012
PAC 2 em Pernambuco - balanço de janeiro de 2012
 
4 a 20 mili amperes 0 a 10 volts relatorio projeto circuito trabalho
4 a 20 mili amperes 0 a 10 volts relatorio projeto circuito trabalho4 a 20 mili amperes 0 a 10 volts relatorio projeto circuito trabalho
4 a 20 mili amperes 0 a 10 volts relatorio projeto circuito trabalho
 
UPA - BELO HORIZONTE
UPA - BELO HORIZONTEUPA - BELO HORIZONTE
UPA - BELO HORIZONTE
 
Mapacirurgico
MapacirurgicoMapacirurgico
Mapacirurgico
 
Somasus 2
Somasus 2Somasus 2
Somasus 2
 
Arquitetura e Memória em Saúde
Arquitetura e Memória em SaúdeArquitetura e Memória em Saúde
Arquitetura e Memória em Saúde
 
Zanettini - Apresentação
Zanettini - ApresentaçãoZanettini - Apresentação
Zanettini - Apresentação
 
Apoio diagnostico-terapia-anatomia-somasus-vol4
Apoio diagnostico-terapia-anatomia-somasus-vol4Apoio diagnostico-terapia-anatomia-somasus-vol4
Apoio diagnostico-terapia-anatomia-somasus-vol4
 
Implantacoes unidades hospitalares
Implantacoes unidades hospitalaresImplantacoes unidades hospitalares
Implantacoes unidades hospitalares
 

Similaire à Ubs t1 a_final_parte4

Construction pdf major project
Construction pdf major projectConstruction pdf major project
Construction pdf major projectYolanda Sewpersad
 
Sommer cable catalogue section 2
Sommer cable catalogue section 2Sommer cable catalogue section 2
Sommer cable catalogue section 2Aryan Subedi
 
Crabtree Weatherseal
Crabtree WeathersealCrabtree Weatherseal
Crabtree WeathersealMark Cheatle
 
NETVIEL-2015.pptx
NETVIEL-2015.pptxNETVIEL-2015.pptx
NETVIEL-2015.pptxsunnysoe1
 
STI 7555AED Instruction Manual
STI 7555AED Instruction ManualSTI 7555AED Instruction Manual
STI 7555AED Instruction ManualJMAC Supply
 
STI 7554 Instruction Manual
STI 7554 Instruction ManualSTI 7554 Instruction Manual
STI 7554 Instruction ManualJMAC Supply
 
Airtherm uPVC damper brochure
Airtherm uPVC damper brochureAirtherm uPVC damper brochure
Airtherm uPVC damper brochureAndy Brown
 
ComNet FVT2001M1 Data Sheet
ComNet FVT2001M1 Data SheetComNet FVT2001M1 Data Sheet
ComNet FVT2001M1 Data SheetJMAC Supply
 
Acoustic components speakers, microphones, audio exciters - seltech 2017
Acoustic components  speakers, microphones, audio exciters - seltech 2017Acoustic components  speakers, microphones, audio exciters - seltech 2017
Acoustic components speakers, microphones, audio exciters - seltech 2017Davin Moorman
 
LDavis_work_examples
LDavis_work_examplesLDavis_work_examples
LDavis_work_examplesLoren Davis
 
Product Preview & Price List - Neptune India
Product Preview & Price List - Neptune IndiaProduct Preview & Price List - Neptune India
Product Preview & Price List - Neptune IndiaNeptune India Limited.
 
Amm brochure
Amm brochureAmm brochure
Amm brochureNICOMATIC
 

Similaire à Ubs t1 a_final_parte4 (20)

Modelo 1
Modelo 1Modelo 1
Modelo 1
 
Construction pdf major project
Construction pdf major projectConstruction pdf major project
Construction pdf major project
 
Sommer cable catalogue section 2
Sommer cable catalogue section 2Sommer cable catalogue section 2
Sommer cable catalogue section 2
 
15-0478_WD_B
15-0478_WD_B15-0478_WD_B
15-0478_WD_B
 
Mil qualified-connectors-pei-genesis
Mil qualified-connectors-pei-genesisMil qualified-connectors-pei-genesis
Mil qualified-connectors-pei-genesis
 
Crabtree Weatherseal
Crabtree WeathersealCrabtree Weatherseal
Crabtree Weatherseal
 
NETVIEL-2015.pptx
NETVIEL-2015.pptxNETVIEL-2015.pptx
NETVIEL-2015.pptx
 
Sony hcd-gtx88
Sony  hcd-gtx88Sony  hcd-gtx88
Sony hcd-gtx88
 
STI 7555AED Instruction Manual
STI 7555AED Instruction ManualSTI 7555AED Instruction Manual
STI 7555AED Instruction Manual
 
STI 7554 Instruction Manual
STI 7554 Instruction ManualSTI 7554 Instruction Manual
STI 7554 Instruction Manual
 
RIVPF_GB_LOCAL
RIVPF_GB_LOCALRIVPF_GB_LOCAL
RIVPF_GB_LOCAL
 
Airtherm uPVC damper brochure
Airtherm uPVC damper brochureAirtherm uPVC damper brochure
Airtherm uPVC damper brochure
 
ComNet FVT2001M1 Data Sheet
ComNet FVT2001M1 Data SheetComNet FVT2001M1 Data Sheet
ComNet FVT2001M1 Data Sheet
 
Acoustic components speakers, microphones, audio exciters - seltech 2017
Acoustic components  speakers, microphones, audio exciters - seltech 2017Acoustic components  speakers, microphones, audio exciters - seltech 2017
Acoustic components speakers, microphones, audio exciters - seltech 2017
 
LDavis_work_examples
LDavis_work_examplesLDavis_work_examples
LDavis_work_examples
 
Alarmline digital manual
Alarmline digital manualAlarmline digital manual
Alarmline digital manual
 
Product Preview & Price List - Neptune India
Product Preview & Price List - Neptune IndiaProduct Preview & Price List - Neptune India
Product Preview & Price List - Neptune India
 
Architecture Portfolio
Architecture PortfolioArchitecture Portfolio
Architecture Portfolio
 
Amm brochure
Amm brochureAmm brochure
Amm brochure
 
Diffuser1
Diffuser1Diffuser1
Diffuser1
 

Dernier

Work Experience-Dalton Park.pptxfvvvvvvv
Work Experience-Dalton Park.pptxfvvvvvvvWork Experience-Dalton Park.pptxfvvvvvvv
Work Experience-Dalton Park.pptxfvvvvvvvLewisJB
 
home automation using Arduino by Aditya Prasad
home automation using Arduino by Aditya Prasadhome automation using Arduino by Aditya Prasad
home automation using Arduino by Aditya Prasadaditya806802
 
Energy Awareness training ppt for manufacturing process.pptx
Energy Awareness training ppt for manufacturing process.pptxEnergy Awareness training ppt for manufacturing process.pptx
Energy Awareness training ppt for manufacturing process.pptxsiddharthjain2303
 
BSNL Internship Training presentation.pptx
BSNL Internship Training presentation.pptxBSNL Internship Training presentation.pptx
BSNL Internship Training presentation.pptxNiranjanYadav41
 
System Simulation and Modelling with types and Event Scheduling
System Simulation and Modelling with types and Event SchedulingSystem Simulation and Modelling with types and Event Scheduling
System Simulation and Modelling with types and Event SchedulingBootNeck1
 
Risk Management in Engineering Construction Project
Risk Management in Engineering Construction ProjectRisk Management in Engineering Construction Project
Risk Management in Engineering Construction ProjectErbil Polytechnic University
 
Crushers to screens in aggregate production
Crushers to screens in aggregate productionCrushers to screens in aggregate production
Crushers to screens in aggregate productionChinnuNinan
 
Class 1 | NFPA 72 | Overview Fire Alarm System
Class 1 | NFPA 72 | Overview Fire Alarm SystemClass 1 | NFPA 72 | Overview Fire Alarm System
Class 1 | NFPA 72 | Overview Fire Alarm Systemirfanmechengr
 
Configuration of IoT devices - Systems managament
Configuration of IoT devices - Systems managamentConfiguration of IoT devices - Systems managament
Configuration of IoT devices - Systems managamentBharaniDharan195623
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionDr.Costas Sachpazis
 
11. Properties of Liquid Fuels in Energy Engineering.pdf
11. Properties of Liquid Fuels in Energy Engineering.pdf11. Properties of Liquid Fuels in Energy Engineering.pdf
11. Properties of Liquid Fuels in Energy Engineering.pdfHafizMudaserAhmad
 
Unit7-DC_Motors nkkjnsdkfnfcdfknfdgfggfg
Unit7-DC_Motors nkkjnsdkfnfcdfknfdgfggfgUnit7-DC_Motors nkkjnsdkfnfcdfknfdgfggfg
Unit7-DC_Motors nkkjnsdkfnfcdfknfdgfggfgsaravananr517913
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort servicejennyeacort
 
Internet of things -Arshdeep Bahga .pptx
Internet of things -Arshdeep Bahga .pptxInternet of things -Arshdeep Bahga .pptx
Internet of things -Arshdeep Bahga .pptxVelmuruganTECE
 
Instrumentation, measurement and control of bio process parameters ( Temperat...
Instrumentation, measurement and control of bio process parameters ( Temperat...Instrumentation, measurement and control of bio process parameters ( Temperat...
Instrumentation, measurement and control of bio process parameters ( Temperat...121011101441
 
Virtual memory management in Operating System
Virtual memory management in Operating SystemVirtual memory management in Operating System
Virtual memory management in Operating SystemRashmi Bhat
 
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdfCCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdfAsst.prof M.Gokilavani
 
Main Memory Management in Operating System
Main Memory Management in Operating SystemMain Memory Management in Operating System
Main Memory Management in Operating SystemRashmi Bhat
 

Dernier (20)

Work Experience-Dalton Park.pptxfvvvvvvv
Work Experience-Dalton Park.pptxfvvvvvvvWork Experience-Dalton Park.pptxfvvvvvvv
Work Experience-Dalton Park.pptxfvvvvvvv
 
home automation using Arduino by Aditya Prasad
home automation using Arduino by Aditya Prasadhome automation using Arduino by Aditya Prasad
home automation using Arduino by Aditya Prasad
 
Energy Awareness training ppt for manufacturing process.pptx
Energy Awareness training ppt for manufacturing process.pptxEnergy Awareness training ppt for manufacturing process.pptx
Energy Awareness training ppt for manufacturing process.pptx
 
BSNL Internship Training presentation.pptx
BSNL Internship Training presentation.pptxBSNL Internship Training presentation.pptx
BSNL Internship Training presentation.pptx
 
System Simulation and Modelling with types and Event Scheduling
System Simulation and Modelling with types and Event SchedulingSystem Simulation and Modelling with types and Event Scheduling
System Simulation and Modelling with types and Event Scheduling
 
Risk Management in Engineering Construction Project
Risk Management in Engineering Construction ProjectRisk Management in Engineering Construction Project
Risk Management in Engineering Construction Project
 
Crushers to screens in aggregate production
Crushers to screens in aggregate productionCrushers to screens in aggregate production
Crushers to screens in aggregate production
 
Class 1 | NFPA 72 | Overview Fire Alarm System
Class 1 | NFPA 72 | Overview Fire Alarm SystemClass 1 | NFPA 72 | Overview Fire Alarm System
Class 1 | NFPA 72 | Overview Fire Alarm System
 
Configuration of IoT devices - Systems managament
Configuration of IoT devices - Systems managamentConfiguration of IoT devices - Systems managament
Configuration of IoT devices - Systems managament
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
 
11. Properties of Liquid Fuels in Energy Engineering.pdf
11. Properties of Liquid Fuels in Energy Engineering.pdf11. Properties of Liquid Fuels in Energy Engineering.pdf
11. Properties of Liquid Fuels in Energy Engineering.pdf
 
Unit7-DC_Motors nkkjnsdkfnfcdfknfdgfggfg
Unit7-DC_Motors nkkjnsdkfnfcdfknfdgfggfgUnit7-DC_Motors nkkjnsdkfnfcdfknfdgfggfg
Unit7-DC_Motors nkkjnsdkfnfcdfknfdgfggfg
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
 
Design and analysis of solar grass cutter.pdf
Design and analysis of solar grass cutter.pdfDesign and analysis of solar grass cutter.pdf
Design and analysis of solar grass cutter.pdf
 
Internet of things -Arshdeep Bahga .pptx
Internet of things -Arshdeep Bahga .pptxInternet of things -Arshdeep Bahga .pptx
Internet of things -Arshdeep Bahga .pptx
 
Instrumentation, measurement and control of bio process parameters ( Temperat...
Instrumentation, measurement and control of bio process parameters ( Temperat...Instrumentation, measurement and control of bio process parameters ( Temperat...
Instrumentation, measurement and control of bio process parameters ( Temperat...
 
Virtual memory management in Operating System
Virtual memory management in Operating SystemVirtual memory management in Operating System
Virtual memory management in Operating System
 
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdfCCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
 
Main Memory Management in Operating System
Main Memory Management in Operating SystemMain Memory Management in Operating System
Main Memory Management in Operating System
 
young call girls in Green Park🔝 9953056974 🔝 escort Service
young call girls in Green Park🔝 9953056974 🔝 escort Serviceyoung call girls in Green Park🔝 9953056974 🔝 escort Service
young call girls in Green Park🔝 9953056974 🔝 escort Service
 

Ubs t1 a_final_parte4

  • 1. COMPRESSOR 01xCo RG59 1P-CFTV-01 SOBEM CABOS DO 1º PAVIMENTO PARA O 2º PAVTO. ATRAVÉS DE ELETROCALHA LISA COM TAMPA 150x100mm DESCEM CABOS DO 2º PAVIMENTO PARA O 1º PAVTO. ATRAVÉS DE ELETROCALHA LISA COM TAMPA 150x100mm CIRCULAÇÃO SOBE CABO DE SONORIZAÇÃO (2x2,5mm²) DO 1º PAVTO. PARA O 2º PAVTO. ATRAVÉS DE ELETRODUTO DE AÇO GALVANIZADO - Ø1"(25mm) I. S. SALA DE REUNIÃO E EDUCAÇÃO ARMÁRIO METÁLICO DO TIPO RACK 12 Us COM PORTA PARA EQUIPAMENTOS DE ÁUDIO PADRÃO 19": SUSTENTAÇÃO DA MATRIZ 8x8 E DO AMPLIFICADOR PT-1P-CFTV-05 01xCo RG59 1P-CFTV-05 PAGGING SON-T1A SF-2P-01 SF-2P-02 SF-1P-01 SF-1P-02 SF-1P-03 AT-T1A SF-1P-05 SF-1P-04 PT-2P-CFTV-02 PT-2P-CFTV-01 PT-1P-CFTV-01 PT-1P-CFTV-02 COLETA PT-1P-CFTV-03 PT-1P-CFTV-04 01xCo RG59 2P-CFTV-02 01xCo RG59 2P-CFTV-01 ESTERILIZAÇÃO 01xCo RG59 2P-CFTV-01 02xCo RG59 02xCo RG59 2P-CFTV-01 a 02 2P-CFTV-01 a 02 02xCo RG59 1P-CFTV-01 a 02 04xCo RG59 1P-CFTV-01 a 02 2P-CFTV-01 a 02 04xCo RG59 1P-CFTV-01 a 02 2P-CFTV-01 a 02 01xCo RG59 1P-CFTV-03 01xCo RG59 1P-CFTV-04 05xCo RG59 1P-CFTV-01 a 03 2P-CFTV-01 a 02 07xCo RG59 1P-CFTV-01 a 05 2P-CFTV-01 a 02 02xCo RG59 1P-CFTV-04 a 05 DESCE CABO DE SONORIZAÇÃO (2x2,5mm²) DO 2º PAVTO. PARA O 1º PAVTO. ATRAVÉS DE ELETRODUTO DE AÇO GALVANIZADO - Ø1"(25mm) VACINAÇÃO SALA DE ESPERA I.S. MASC. RECEPÇÃO TRIAGEM CIRCULAÇÃO GINECOLOGIA DML ALMOXARIFADO VARANDA COBERTA I.S. FEM. ESCOVÁRIO RESÍDUOS RESÍDUOS CIRCULAÇÃO GUICHÊ COPA TV SUSPENSA VAGA PARA AMBULÂNCIA FOSSO ESCANINHOS ÁREA PERMEÁVEL ÁREA PERMEÁVEL proj. da cobertura CALÇADA RUA PROJEÇÃO CAIXA D'ÁGUA ALÇAPÃO LAVAGEM E DESINFECÇÃO DE MATERIAIS DML proj. da cobertura SALA DE APOIO AGENTES ENDEMIAS APOIO AGENTES ENDEMIAS SALA DE CURATIVOS CUIDADOS BÁSICOS ATENDIMENTO MULTIPROFISSIONAL ATENDIMENTO MULTIPROFISSIONAL GUARDA MEDICAMENTOS REBAIXO NA CALÇADA P/ ACESSO DE VEÍCULOS REBAIXO NA CALÇADA P/ ACESSIBILIDADE CONSULTÓRIO ODONTOLÓGICO VESTIÁRIO MASCULINO VESTIÁRIO FEMININO 1-PROIBIDA REPRODUÇÃO OU ALTERAÇÃO DO CONTEÚDO SEM AUTORIZAÇÃO DOS RESPONSÁVEIS TÉCNICOS DO PROJETO. 2-DIREITOS AUTORAIS RESERVADOS - LEI FEDERAL 9.610 DE 19/02/1996. 3-CONFERIR MEDIDAS NO LOCAL. RESOLUÇÃO 1797/09 DA SES-MG 03 ADEQUAÇÃO DA ARQUITETURA CONFORME VISA 31/01/2013 VIABILE 02 EMISSÃO FINAL 08/11/2012 VIABILE 00 EMISSÃO INICIAL 22/10/2012 VIABILE VERIFICAÇÃO Secretaria de Estado de Saúde de Minas Gerais Cidade Administrativa Presidente Tancredo Neves Rodovia Pref. Américo Gianetti s/nº - Bairro: Serra Verde - B. Hte - Minas Gerais - CEP: 31630-900 SES-MG Predio Minas - 12º e 13º andar FOLHA: 02 02 REVISÃO OBJETO DATA GERENCIAMENTO E PROJETO: DESENVOLVIMENTO: BRENO DE ASSIS OLIVEIRA FEVEREIRO/2013 PROJETO DE SONORIZAÇÃO/CFTV/ALARME VÁRIAS UNIDADES NO ESTADO DE MINAS GERAIS ETAPA: PLANTAS PROJETO EXECUTIVO Av. Augusto de Lima, nº655 conj. 418 - Centro - BH Telefax: (31) 3324-2702 http://www.viabile.com.br viabile@viabile.com.br DATA: NOME DO ARQUIVO CAD: ESCALA: UNIDADE: INDICADA CENTÍMETROS CREA-MG: 78.667/D RESPONSÁVEL TÉCNICO: BRENO DE ASSIS OLIVEIRA PROPRIETÁRIO: SECRETARIA DO ESTADO DE SAÚDE DE MINAS GERAIS 460-UBSSS-R03-ESO-02-PE-T1A.DWG UBS MINAS - PROJETO MODELO DISCIPLINA: PROJETO: ENDEREÇO: CONTEÚDO: NOTAS: 4-COTAS EM CENTÍMETROS. SUBSECRETARIA DE VIGILÂNCIA E PROTEÇÃO Á SAÚDE SUPERINTENDÊNCIA DE VIGILÂNCIA SANITÁRIA DIRETORIA DE INFRAESTRUTURA FÍSICA PROJETO MODELO UNIDADE BÁSICA DE SAÚDE PROJETO DE ACORDO COM RDC-50/2002 E É DE RESPONSABILIDADE DO MUNICIPIO APROVAÇÃO COM A IMPLANTAÇÃO NO TERRENO ESCOLHIDO. TIPO T1A - ACLIVE FORMATO INTERNACIONAL A1 (841 x 594mm) abrasip-mg SONORIZAÇÃO - 1° PAVIMENTO ESCALA: ......................................................................... 1/75 SONORIZAÇÃO - 2° PAVIMENTO ESCALA: ......................................................................... 1/75 01 MUDANÇA DE ARQUITETURA 26/10/2012 VIABILE SUBSECRETARIA DE INOVAÇÃO E LOGISTICA SUPERINTENDENCIA DE GESTÃO DIRETORIA DE GESTÃO DA REDE FÍSICA
  • 2. SIMBOLOGIA - SONORIZAÇÃO: SÍMBOLO DESCRIÇÃO ELETROCALHA METÁLICA LISA COM VIROLA DO TIPO "C" E TAMPA DE PRESSÃO (DIMENSÕES: 150x100mm). COMPARTILHADA COM CABEAMENTO ESTRUTURADO. ELETRODUTO DE AÇO GALVANIZADO FIXADO ATRAVÉS DE TIRANTES NA ESTRUTURA - Ø1"(25mm) OU CONFORME INDICAÇÃO. REF.: ELECON. CAIXAS METÁLICAS DE PASSAGEM DO TIPO CONDULETE MÚLTIPLO - TIPOS X, T, LL, E, LR e C RESPECTIVAMENTE, CONFORME NBR-15.701 SONOFLETOR (ALTO-FALANTE) COAXIAL 6" POTÊNCIA 25Wrms IMPEDÂNCIA 8 OHMS DO TIPO ARANDELA NA COR BRANCA. REF.: ARANDELA 6CO2R, DA SELENIUM. CÂMERA COLORIDA PARA SISTEMA DE CFTV INSTALADA EM CAIXA BLINDADA COM FONTE 127V NO INTERIOR DA CAIXA, INSTALADA EM PAREDE h=2,20m OU CONFORME INDICAÇÃO. DEVERÃO SER INSTALADAS DUAS CAIXAS 2x4", SENDO UMA PARA A ALIMENTAÇÃO ELÉTRICA E OUTRA PARA A PASSAGEM DO CABO DE VÍDEO. CABO UTP RACK MATRIZ 8x8 AMPLIFICADOR CAIXAS SALA DE ESPERA CAIXAS CIRCULAÇÃO 1ºPAVTO. CAIXAS CIRCULAÇÃO 2ºPAVTO. PAGGING/ MICROFONE CABO UTP CAT 6 DIAGRAMA ESQUEMÁTICO DE INTERLIGAÇÃO SONOFLETORES NO FORRO CHUMBADOR ROSCA INTERNA Ø1/4" PORCA SEXTAVADA E ARRUELA LISA Ø1/4" ELETRODUTOS (PENDENTE) RACK METÁLICO FECHADO 19"x12Us PROF.: 670mm COM PORTA DE VIDRO, EQUIPADO COM RÉGUA DE 10 TOMADAS 2P+T LIGADA AO NO-BREAK GAVETA DE VENTILAÇÃO PADRÃO 19" C/ QUATRO VENTILADORES MATRIZ DE ÁUDIO 8x8 (8 in / 8 out) NO-BREAK 600VA/127V PADRÃO 19" COM AUTONOMIA MÍNIMA DE 15 MINUTOS ELETRODUTO AÇO GALVANIZADO (Ø CONF.PROJ PAR DE FIOS POLARIZADOS BRAÇADEIRA TIPO "D" BUCHA PLÁSTICA DETALHE SUGESTIVO DO ARMÁRIO DE SONORIZAÇÃO 1º PAVIMENTO - RECEPÇÃO SEM ESCALA AMPLIFICADOR LINHA 70V 150Wts RMS / CANAL - (110/220V) DVR 16 CANAIS BNC/1 SAÍDA BNC/1 SAÍDA VGA, VELOCIDADE MÍNIMA 120fps NTSC E COMUNICAÇÃO DE REDE RJ-45 EM PROTOCOLO TCP/IP ABRAÇADEIRA CIRCULAR ELETRODUTO AÇO GALVANIZADO (Ø CONF.PROJ.) TIRANTE ROSCA TOTAL Ø1/4" DETALHE TÍPICO DE FIXAÇÃO DOS FIXAR A CADA 1,50m (NO MÁXIMO) SEM ESCALA ELETRODUTO DE AÇO GALVANIZADO S6 E PARAFUSO DETALHE FIXAÇÃO DO ELETRODUTO FIXAÇÃO DIRETA EM PAREDES OU LAJE SEM ESCALA - SUPORTAR A CADA 1,50m PASSAGEM POR OBSTÁCULOS LAJE FORRO SONOFLETOR (ALTO-FALANTE) CAIXA DE PASSAGEM 4"x4" BRAÇADEIRA TIPO "D" C/ UNHA A CADA 2m DETALHE TÍPICO DE FIXAÇÃO DOS SEM ESCALA ELETRODUTOS PVC/AÇO e mm e mm 2,3 2,7 2,9 3,0 3,1 3,8 4,0 5,0 DIÂMETRO NOMINAL-DN mm POL EXTERNO-DE mm DIÂMETRO NOMINAL-DN mm 25 32 40 50 60 75 85 110 POL 3/4 1 1.1/4 1.1/2 2 2.1/2 3 4 EXTERNO-DE mm 25,9 33,0 42,0 47,4 59,0 74,7 87,6 113,1 ELETRODUTOS DE AÇO CARBONO, TIPO LEVE I, CONF. NBR 5624 ESPESSURA NOMINAL DA PAREDE ELETRODUTOS DE PVC RÍGIDO ROSQUEÁVEL, CLASSE B, CONF. NBR 6150 ESPESSURA NOMINAL DA PAREDE 1,5 1,5 2,0 2,25 2,25 2,85 2,65 2,65 20 25 32 40 50 65 80 100 3/4 1 1.1/4 1.1/2 2 2.1/2 3 4 25,2 31,5 40,5 46,6 58,4 74,1 86,8 111,6 NOTAS GERAIS: 1 - MEDIDAS EM MILÍMETROS, EXCETO ONDE INDICADO. 2 - CONSIDERAR AS MEDIDAS DAS COTAS PRIORITÁRIAS EM RELAÇÃO À ESCALA. 3 - OS ELETRODUTOS UTILIZADOS DEVERÃO SER DE AÇO GALVANIZADO, COM NO MÍNIMO Ø1" (25mm). 4 - EM TODAS AS DERIVAÇÕES DEVERÃO SER UTILIZADAS CAIXAS DE PASSAGEM DO TIPO CONDULETE METÁLICO. 5 - OS LANCES ENTRE DUAS CAIXAS DE PASSAGEM NÃO DEVERÃO CONTER MAIS DO QUE DUAS CURVAS, EVITANDO-SE TAMBÉM CURVAS REVERSAS SEMPRE QUE POSSÍVEL. 6 - OS ELETRODUTOS DEVERÃO SER PROVIDOS DE BUCHAS E ARRUELAS EM SUAS EXTREMIDADES, EXCETO AQUELAS QUE TERMINAM EM CAIXAS DE PASSAGEM. 7 - SONDAR OS ELETRODUTOS COM ARAME OU CABO DE NYLON, DEIXANDO UMA SOBRA DE ± 1,0m EM CADA CAIXA ANTES DA PASSAGEM DOS CABOS. 8 - AS PONTAS DE TODOS OS CABOS DEVERÃO SER IDENTIFICADAS COM ETIQUETAS TERMOCONTRÁTEIS OU OUTRO MÉTODO QUE NÃO PERMITA A RETIRADA DA IDENTIFICAÇÃO SEM DANIFICAR O CABO. OS CABOS DEVERÃO SER IDENTIFICADOS CONFORME DESCRITO NESTE PROJETO. 9 - TODAS AS CONEXÕES ENTRE AMPLIFICADORES, SONOFLETORES, DVR E CÂMERAS DE VÍDEO DEVERÃO UTILIZAR OS CONECTORES APROPRIADOS EM CADA PONTA. 10 - ATERRAR TODAS AS PARTES METÁLICAS NÃO ENERGIZADAS DA INSTALAÇÃO. 11 - TODOS OS SONOFLETORES (ALTO-FALANTES) DEVERÃO TER SUA POLARIDADE TESTADA NO LOCAL, EVITANDO-SE O CANCELAMENTO SONORO NA INTERLIGAÇÃO INVERTIDA. 12 - O DVR DEVERÁ SER INTERLIGADO À REDE, E A GRAVAÇÃO DE IMAGENS SERÁ REALIZADA EM COMPUTADOR DEFINIDO COMO SERVIDOR. O SERVIDOR SERÁ FORNECIDO PELA SES/MG, E NÃO FAZ PARTE DO ESCOPO DA EMPRESA INSTALADORA. 13 - PREVER UMA TOMADA ELÉTRICA PARA CADA CÂMERA A SER INSTALADA. 1-PROIBIDA REPRODUÇÃO OU ALTERAÇÃO DO CONTEÚDO SEM AUTORIZAÇÃO DOS RESPONSÁVEIS TÉCNICOS DO PROJETO. 2-DIREITOS AUTORAIS RESERVADOS - LEI FEDERAL 9.610 DE 19/02/1996. 3-CONFERIR MEDIDAS NO LOCAL. RESOLUÇÃO 1797/09 DA SES-MG 03 ADEQUAÇÃO DA ARQUITETURA CONFORME VISA 01/02/2013 VIABILE 02 EMISSÃO FINAL 08/11/2012 VIABILE 00 EMISSÃO INICIAL 22/10/2012 VIABILE VERIFICAÇÃO Secretaria de Estado de Saúde de Minas Gerais Cidade Administrativa Presidente Tancredo Neves Rodovia Pref. Américo Gianetti s/nº - Bairro: Serra Verde - B. Hte - Minas Gerais - CEP: 31630-900 SES-MG Predio Minas - 12º e 13º andar FOLHA: 01 02 REVISÃO OBJETO DATA GERENCIAMENTO E PROJETO: DESENVOLVIMENTO: BRENO DE ASSIS OLIVEIRA FEVEREIRO/2013 PROJETO DE SONORIZAÇÃO VÁRIAS UNIDADES NO ESTADO DE MINAS GERAIS ETAPA: SIMBOLOGIA, NOTAS GERAIS E DETALHES PROJETO EXECUTIVO CONSTRUTIVOS Av. Augusto de Lima, nº655 conj. 418 - Centro - BH Telefax: (31) 3324-2702 http://www.viabile.com.br viabile@viabile.com.br DATA: NOME DO ARQUIVO CAD: ESCALA: UNIDADE: INDICADA CENTÍMETROS CREA-MG: 78.667/D RESPONSÁVEL TÉCNICO: BRENO DE ASSIS OLIVEIRA PROPRIETÁRIO: SECRETARIA DO ESTADO DE SAÚDE DE MINAS GERAIS 460-UBSSS-R03-ESO-01-PE-T1A.DWG UBS MINAS - PROJETO MODELO DISCIPLINA: PROJETO: ENDEREÇO: CONTEÚDO: NOTAS: 4-COTAS EM CENTÍMETROS. SUBSECRETARIA DE VIGILÂNCIA E PROTEÇÃO Á SAÚDE SUPERINTENDÊNCIA DE VIGILÂNCIA SANITÁRIA DIRETORIA DE INFRAESTRUTURA FÍSICA PROJETO MODELO UNIDADE BÁSICA DE SAÚDE PROJETO DE ACORDO COM RDC-50/2002 E É DE RESPONSABILIDADE DO MUNICIPIO APROVAÇÃO COM A IMPLANTAÇÃO NO TERRENO ESCOLHIDO. TIPO T1A - ACLIVE FORMATO INTERNACIONAL A1 (841 x 594mm) abrasip-mg 01 MUDANÇA DE ARQUITETURA 26/10/2012 VIABILE SUBSECRETARIA DE INOVAÇÃO E LOGISTICA SUPERINTENDENCIA DE GESTÃO DIRETORIA DE GESTÃO DA REDE FÍSICA
  • 3. 4'/)±7'±5(/$d­2'($5*$6(0(0Ï5,$'(È/8/2 CIRCUITO '(65,d­2 ,/80,1$d­2 (W) BLOCO AUTONOMO (W) 6,1$/,=$d­2 (W) TOMADAS (W) CHUVEIROS (W) AR CONDICIONADO (W) 16 32 60 25 50 85 170 510 850 1530 6500 1110 ,/80,1$d­29$,1$d­26$/$'( (63(5$5((3d­275,$*(02/(7$6$/$'(5(81,­2( ('8$d­2$7(1',0(17208/7,352),66,21$/ ,/80,1$d­2$7(1',0(17208/7,352),66,21$/*8$5'$ 0(',$0(1726*,1(2/2*,$8,'$'26%È6,2685*Ç1,$( (0(5*Ç1,$6$/$'(85$7,926(629È5,2 L1 4 42 0 0 0 0 0 0 0 0 0 0 L2 0 32 0 0 0 0 0 0 0 0 0 0 L3 ,/80,1$d­2,58/$d­2%$1+(,526(6$'$'0/ 18 2 1 0 0 0 0 0 0 0 0 0 ,/80,1$d­22168/7Ï5,22'2172/Ï*,2$*(17(6'(6$Ò'( $/02;$5,)$'25(6Ë'826 ,/80,1$d­223$9(67,È5,20$68/,129(67,È5,2)(0,1,12 /$9$*(0('(6,1)(d­2'(0$7(5,$,6(67(5,/,=$d­2'0/ ,58/$d­2 L4 10 10 0 0 0 0 0 0 0 0 0 0 L5 2 20 0 0 0 0 0 0 0 0 0 0 T1 720$'$65((3d­2±ž3$972 0 0 0 0 0 0 4 0 0 0 0 0 T2 720$'$69$,1$d­26$/$(63(5$±ž3$972 0 0 0 0 0 5 0 1 0 0 0 0 T3 720$'$69$,1$d­2±ž3$972 0 0 0 0 0 0 2 1 0 0 0 0 T4 720$'$675,$*(02/(7$±ž3$972 0 0 0 0 0 3 4 0 0 0 0 0 T5 720$'$6$7(1',0(17208/7,352),66,21$/±ž3$972 0 0 0 0 0 3 2 0 0 0 0 0 T6 720$'$6$7(1',0(17208/7,352),66,21$/±ž3$972 0 0 0 0 0 3 2 0 0 0 0 0 T7 720$'$68,'$'26%È6,2685*Ç1,$((0(5*Ç1,$±ž3$972 0 0 0 0 0 4 2 0 0 0 0 0 T8 720$'$66$/$'(5(81,­2(('8$d­2±ž3$972 0 0 0 0 0 5 0 0 0 0 0 0 T9 720$'$66$/$'(5(81,­2(('8$d­2±ž3$972 0 0 0 0 0 2 0 1 0 0 0 0 T10 720$'$66$/$'(5(81,­2(('8$d­2±*(/$'(,5$±ž3$972 0 0 0 0 0 0 0 1 0 0 0 0 T11 720$'$6$/$'(5(81,­2(('8$d­2±0,5221'$6±ž3$972 0 0 0 0 0 0 0 0 0 1 0 0 T12 720$'$6*,1(2/2*,$±ž3$972 0 0 0 0 0 4 2 0 0 0 0 0 T13 720$'$66$/$'(85$7,926*8$5'$0(',$0(1726±ž3$972 0 0 0 0 0 5 2 0 0 0 0 0 T14 720$'$6,6,58/$d­2±ž3$972 0 0 0 0 2 7 0 0 0 0 0 0 T15 32172'()25d$±$521'9$,1$d­2±ž3$972 0 0 0 0 0 0 0 0 0 0 0 1 T16 32172'()25d$±$521'75,$*(0±ž3$972 0 0 0 0 0 0 0 0 0 0 0 1 T17 32172'()25d$±$521'2/(7$±ž3$972 0 0 0 0 0 0 0 0 0 0 0 1 T18 32172'()25d$±$521'$7(1',0(17208/7,352),66,21$/±ž PAVTO 0 0 0 0 0 0 0 0 0 0 0 1 T19 32172'()25d$±$521'$7(1',0(17208/7,352),66,21$/±ž PAVTO 0 0 0 0 0 0 0 0 0 0 0 1 T20 32172'()25d$±$521'8,'$'26%È6,26±ž3$972 0 0 0 0 0 0 0 0 0 0 0 1 T21 32172'()25d$±$521'8,'$'26%È6,26±ž3$972 0 0 0 0 0 0 0 0 0 0 0 1 T22 32172'()25d$±$521'6$/$'(85$7,926±ž3$972 0 0 0 0 0 0 0 0 0 0 0 1 T23 32172'()25d$±$521'*,1(2/2*,$±ž3$972 0 0 0 0 0 0 0 0 0 0 0 1 T24 32172'()25d$±$521'*8$5'$0(',$0(1726±ž3$972 0 0 0 0 0 0 0 0 0 0 0 1 T25 32172'()25d$±$521'6$/$'(5(81,­2(('8$d­2±ž3$972 0 0 0 0 0 0 0 0 0 0 0 1 T26 32172'()25d$±$521'6$/$'(5(81,­2(('8$d­2±ž3$972 0 0 0 0 0 0 0 0 0 0 0 1 T27 32172'()25d$±$521'6$/$'((63(5$±ž3$972 0 0 0 0 0 0 0 0 0 0 0 1 T28 32172'()25d$3$5$3/$7$)250$(/(9$7Ï5,$±75,)È6,29 0 0 0 0 0 0 0 0 0 0 0 0 T29 32172'()25d$0217$$5*$ 0 0 0 0 0 0 0 0 0 0 0 0 T30 720$'$62168/7Ï5,22'2172/Ï*,2±68%62/2 0 0 0 0 0 9 0 0 0 0 0 0 T31 720$'$62168/7Ï5,22'2172/Ï*,2±68%62/2 0 0 0 0 0 0 0 2 0 0 0 0 T32 720$'$65(6Ë'826'0/$/02;$5,)$'2(67(5,/,=$d­26$/$'( $32,2$*(17(6(1'(0,$6±68%62/2 0 0 0 0 0 9 0 0 0 0 0 0 T33 720$'$6/$9$*(0('(6,1)(d­2'(0$7(5,$,6,58/$d­2 9(67,È5,20$6()(0±68%62/2 0 0 0 0 0 10 0 0 0 0 0 0 T34 720$'$(67(5(/,=$d­2±$872/$9(±68%62/2 0 0 0 0 0 0 0 0 1 0 0 0 T35 321726'()25d$+89(,529(67,È5,20$68/,12±9±68%62/2 0 0 0 0 0 0 0 0 0 0 1 0 T36 321726'()25d$+89(,529(67,È5,2)(0,1,12±9±68%62/2 0 0 0 0 0 0 0 0 0 0 1 0 T37 720$'$623$±68%62/2 0 0 0 0 0 4 0 1 0 0 0 0 T38 720$'$23$±0,5221'$6±68%62/2 0 0 0 0 0 0 0 0 0 1 0 0 T39 720$'$6$*(17(6'(6$Ò'(±68%62/2 0 0 0 0 0 3 4 0 0 0 0 0 T40 32172'()25d$±$521'2168/7Ï5,22'2172/Ï*,2± SUBSOLO 0 0 0 0 0 0 0 0 0 0 0 1 T41 32172'()25d$±$521'2168/7Ï5,22'2172/Ï*,2± SUBSOLO 0 0 0 0 0 0 0 0 0 0 0 1 T42 32172'()25d$±$521'(67(5,/,=$d­2±68%62/2 0 0 0 0 0 0 0 0 0 0 0 1 T43 32172'()25d$±$521'/$9$*(0('(6,1)(d­2'(0$7(5,$,6± SUBSOLO 0 0 0 0 0 0 0 0 0 0 0 1 T44 32172'()25d$±$521'$*(17(6'(6$Ò'(±68%62/2 0 0 0 0 0 0 0 0 0 0 0 1 T45 32172'()25d$2035(6625 0 0 0 0 0 0 0 0 0 0 0 0 T46 BLOCO AUTONOMO 0 0 0 8 0 0 0 0 0 0 0 0 T47 720$'$5$.±ž3$972 0 0 0 0 0 0 0 0 1 0 0 0 T48 720$'$5$.62125,=$d­2±ž3$972 0 0 0 0 0 0 0 0 1 0 0 0 T49 TOMADAS CFTV 0 0 0 0 0 6 0 0 0 0 0 0 TOTAL 34,00 106,00 1,00 8,00 2,00 82,00 24,00 7,00 3,00 2,00 2,00 18,00 F.P. 327Ç1,$727$/ 7(16­2 FASES (48,/Ë%5,2 3527(d­2 P In CURVA COMPRESSOR (W) MONTA CARGA (W) 1ž'( FASES CORRENTE NOMINAL 1Ò0(52'( CONDUTORES POR FASE CONDUTOR PPð
  • 4. 850 1471 (kW) (kVA) (V) R S T (A) (A) 0 0 0,95 1,41 1,48 220 2 RS 0,74 0,74 0,00 6,74 2 x 16 C 1 4,0 0 0 0,95 1,02 1,08 220 2 TR 0,54 0,00 0,54 4,90 2 x 16 C 1 4,0 0 0 0,95 0,41 0,43 220 2 ST 0,00 0,22 0,22 1,97 2 x 16 C 1 2,5 0 0 0,95 0,48 0,51 220 2 RS 0,25 0,25 0,00 2,30 2 x 16 C 1 2,5 0 0 0,95 0,67 0,71 220 2 TR 0,35 0,00 0,35 3,22 2 x 16 C 1 4,0 0 0 0,85 0,68 0,80 127 1 R 0,80 0,00 0,00 6,30 1 x 16 C 1 4,0 0 0 0,85 0,94 1,10 127 1 S 0,00 1,10 0,00 8,66 1 x 16 C 1 4,0 0 0 0,85 0,85 1,00 127 1 T 0,00 0,00 1,00 7,87 1 x 16 C 1 4,0 0 0 0,85 0,94 1,10 127 1 R 1,10 0,00 0,00 8,66 1 x 16 C 1 4,0 0 0 0,85 0,60 0,70 127 1 S 0,00 0,70 0,00 5,51 1 x 16 C 1 4,0 0 0 0,85 0,60 0,70 127 1 T 0,00 0,00 0,70 5,51 1 x 16 C 1 4,0 0 0 0,85 0,68 0,80 127 1 S 0,00 0,80 0,00 6,30 1 x 16 C 1 4,0 0 0 0,85 0,43 0,50 127 1 S 0,00 0,50 0,00 3,94 1 x 16 C 1 4,0 0 0 0,85 0,68 0,80 127 1 R 0,80 0,00 0,00 6,30 1 x 16 C 1 4,0 0 0 0,85 0,51 0,60 127 1 S 0,00 0,60 0,00 4,72 1 x 16 C 1 4,0 0 0 0,85 1,53 1,80 127 1 T 0,00 0,00 1,80 14,17 1 x 16 C 1 6,0 0 0 0,85 0,68 0,80 127 1 T 0,00 0,00 0,80 6,30 1 x 16 C 1 4,0 0 0 0,85 0,77 0,90 127 1 S 0,00 0,90 0,00 7,09 1 x 16 C 1 4,0 0 0 0,85 0,70 0,82 127 1 R 0,82 0,00 0,00 6,44 1 x 16 C 1 4,0 0 0 0,85 1,11 1,31 220 2 RS 0,65 0,65 0,00 5,94 2 x 16 C 1 4,0 0 0 0,85 1,11 1,31 220 2 TR 0,65 0,00 0,65 5,94 2 x 16 C 1 4,0 0 0 0,85 1,11 1,31 220 2 ST 0,00 0,65 0,65 5,94 2 x 16 C 1 4,0 0 0 0,85 1,11 1,31 220 2 RS 0,65 0,65 0,00 5,94 2 x 16 C 1 4,0 0 0 0,85 1,11 1,31 220 2 TR 0,65 0,00 0,65 5,94 2 x 16 C 1 4,0 0 0 0,85 1,11 1,31 220 2 ST 0,00 0,65 0,65 5,94 2 x 16 C 1 4,0 0 0 0,85 1,11 1,31 220 2 RS 0,65 0,65 0,00 5,94 2 x 16 C 1 4,0 0 0 0,85 1,11 1,31 220 2 TR 0,65 0,00 0,65 5,94 2 x 16 C 1 4,0 0 0 0,85 1,11 1,31 220 2 ST 0,00 0,65 0,65 5,94 2 x 16 C 1 4,0 0 0 0,85 1,11 1,31 220 2 RS 0,65 0,65 0,00 5,94 2 x 16 C 1 4,0 0 0 0,85 1,11 1,31 220 2 TR 0,65 0,00 0,65 5,94 2 x 16 C 1 4,0 0 0 0,85 1,11 1,31 220 2 TR 0,65 0,00 0,65 5,94 2 x 16 C 1 4,0 0 0 0,85 1,11 1,31 220 2 ST 0,00 0,65 0,65 5,94 2 x 16 C 1 4,0 0 0 0,85 1,47 1,73 220 3 RST 0,58 0,58 0,58 4,54 3 x 16 C 1 4,0 0 1 0,85 1,47 1,73 220 3 RST 0,58 0,58 0,58 4,54 3 x 16 C 1 4,0 0 0 0,85 0,77 0,90 127 1 T 0,00 0,00 0,90 7,09 1 x 16 C 1 4,0 0 0 0,85 1,02 1,20 127 1 R 1,20 0,00 0,00 9,45 1 x 16 C 1 4,0 0 0 0,85 0,77 0,90 127 1 S 0,00 0,90 0,00 7,09 1 x 16 C 1 4,0 0 0 0,85 0,85 1,00 127 1 T 0,00 0,00 1,00 7,87 1 x 16 C 1 4,0 0 0 0,85 0,85 1,00 127 1 R 1,00 0,00 0,00 7,87 1 x 16 C 1 4,0 0 0 1,00 6,50 6,50 220 2 RS 3,25 3,25 0,00 29,55 2 x 32 C 1 4,0 0 0 1,00 6,50 6,50 220 2 TR 3,25 0,00 3,25 29,55 2 x 32 C 1 4,0 0 0 0,85 0,85 1,00 127 1 S 0,00 1,00 0,00 7,87 1 x 16 C 1 4,0 0 0 0,85 1,53 1,80 127 1 T 0,00 0,00 1,80 14,17 1 x 16 C 1 4,0 0 0 0,85 0,94 1,10 127 1 S 0,00 1,10 0,00 8,66 1 x 16 C 1 4,0 0 0 0,85 1,11 1,31 220 2 TR 0,65 0,00 0,65 5,94 2 x 16 C 1 4,0 0 0 0,85 1,11 1,31 220 2 ST 0,00 0,65 0,65 5,94 2 x 16 C 1 4,0 0 0 0,85 1,11 1,31 220 2 RS 0,65 0,65 0,00 5,94 2 x 16 C 1 4,0 0 0 0,85 1,11 1,31 220 2 TR 0,65 0,00 0,65 5,94 2 x 16 C 1 4,0 0 0 0,85 1,11 1,31 220 2 ST 0,00 0,65 0,65 5,94 2 x 16 C 1 4,0 1 0 0,85 0,85 1,00 220 2 RS 0,50 0,50 0,00 4,55 2 x 16 C 1 4,0 0 0 0,85 0,20 0,24 127 1 T 0,00 0,00 0,24 1,85 1 x 16 C 1 2,5 0 0 0,85 0,85 1,00 127 1 R 1,00 0,00 0,00 7,87 1 x 16 C 1 4,0 0 0 0,85 0,85 1,00 127 1 T 0,00 0,00 1,00 7,87 1 x 16 C 1 4,0 0 0 0,85 0,51 0,60 127 1 R 0,60 0,00 0,00 4,72 1 x 16 C 1 4,0 1,00 1,00 0,88 61,30 69,33 380 3 RST 23,31 19,69 22,13 105,46 3 x 125 D 1 50,0 0(0Ï5,$'(È/8/2 '5±P$ 48('$'(7(16­2 QUEDA DE 7(16­2()(7,9$ LIMITE: COMPRIMENTO 0È;,02'2 CIRCUITO (m) 3,00% '5±$ 40 1,05% 30 0,57% 45 0,55% X 18 0,26% 14 0,18% X 42 1,79% 44 2,58% 44 2,35% 40 2,35% 37 1,38% 32 1,19% 29 1,24% 40 1,07% 41 1,75% X 41 1,31% X 41 2,62% X 32 1,36% 33 1,58% 43 1,87% X 43 1,00% 39 0,90% 39 0,90% 32 0,74% 32 0,74% 29 0,67% 24 0,56% 28 0,65% 33 0,77% 34 0,79% 36 0,84% 36 0,84% 36 0,84% 15 0,23% 11 0,17% 15 0,72% 9 0,58% 22 1,06% X 11 0,59% X 11 0,59% 13 1,50% X 14 1,62% X 16 0,85% X 15 1,44% X 17 1,00% 15 0,35% 12 0,28% 14 0,32% 14 0,32% 14 0,32% 18 0,32% 50 1,00% 40 2,13% 40 2,13% 40 1,28% 40 0,66% NOTAS: 1-PROIBIDA REPRODUÇÃO OU ALTERAÇÃO DO CONTEÚDO SEM AUTORIZAÇÃO DOS RESPONSÁVEIS TÉCNICOS DO PROJETO. 2-DIREITOS AUTORAIS RESERVADOS - LEI FEDERAL 9.610 DE 19/02/1996. 3-CONFERIR MEDIDAS NO LOCAL. 4-COTAS EM CENTÍMETROS. RESOLUÇÃO 1797/09 DA SES-MG 03 ADEQUAÇÃO DA ARQUITETURA CONFORME VISA 01/02/2013 VIABILE 02 EMISSÃO FINAL 08/11/2012 VIABILE 00 EMISSÃO INICIAL 27/09/2012 VIABILE VERIFICAÇÃO Secretaria de Estado de Saúde de Minas Gerais Cidade Administrativa Presidente Tancredo Neves Rodovia Pref. Américo Gianetti s/nº - Bairro: Serra Verde - B. Hte - Minas Gerais - CEP: 31630-900 SES-MG Predio Minas - 12º e 13º andar FOLHA: 05 05 REVISÃO OBJETO DATA GERENCIAMENTO E PROJETO: DESENVOLVIMENTO: BRENO ASSIS DE OLIVEIRA FEVEREIRO/2013 INSTALAÇÕES ELÉTRICAS VÁRIAS UNIDADES NO ESTADO DE MINAS GERAIS ETAPA: QUADRO DE CARGAS PROJETO EXECUTIVO Av. Augusto de Lima, nº655 conj. 418 - Centro - BH Telefax: (31) 3324-2702 http://www.viabile.com.br viabile@viabile.com.br DATA: NOME DO ARQUIVO CAD: ESCALA: UNIDADE: INDICADA MILÍMETROS CREA: 78.667/D RESPONSÁVEL TÉCNICO: BRENO ASSIS DE OLIVEIRA PROPRIETÁRIO: SECRETARIA DO ESTADO DE SAÚDE DE MINAS GERAIS 460-UBSSS-R03-ELE-05-PE-T1A.DWG UBS MINAS - PROJETO MODELO DISCIPLINA: PROJETO: ENDEREÇO: CONTEÚDO: SUBSECRETARIA DE VIGILÂNCIA E PROTEÇÃO Á SAÚDE SUPERINTENDÊNCIA DE VIGILÂNCIA SANITÁRIA DIRETORIA DE INFRAESTRUTURA FÍSICA PROJETO MODELO UNIDADE BÁSICA DE SAÚDE PROJETO DE ACORDO COM RDC-50/2002 E É DE RESPONSABILIDADE DO MUNICIPIO APROVAÇÃO COM A IMPLANTAÇÃO NO TERRENO ESCOLHIDO. TIPO T1A - ACLIVE FORMATO INTERNACIONAL A1 ALONGADO (1026 x 594mm) abrasip-mg 01 ALIMENTAÇÃO DOS PONTOS DE CFTV, RACK DE SONORIZAÇÃO E BEBEDOUROS 26/10/2012 VIABILE SUBSECRETARIA DE INOVAÇÃO E LOGISTICA SUPERINTENDENCIA DE GESTÃO DIRETORIA DE GESTÃO DA REDE FÍSICA
  • 5. #10,0 FUSÍVEL MODULAR #10,0 DPS 275V 20kA - 8/20us R S T TERRA #10,0 #10,0 #10,0 #10,0 32A DE ALIMENTADORES/IMPLANTAÇÃO 40A (C) 40A (C) 40A (C) 125A MÍNIMO DE 10kA BARRA 1 - IN MÍNIMO: 150A - TRIFÁSICO - Icc MÍNIMO: 10kA L1 16A #4,0 L4 16A BARRA 2 - PENTE TRIFÁSICO MÍNIMO 24 PINOS - 80A VER PROJETO ESPECÍFICO Pe R S T N #6,0 #10,0 #10,0 #10,0 T19 16A #4,0 T17 16A #4,0 16A #4,0 T39 T41 16A T40 16A QDC-T1/A - DIAGRAMA MULTIFILAR (96 POLOS) NEUTRO DR L2 16A #4,0 #6,0 #6,0 NEUTRO #6,0 #10,0 #6,0 BARRA 3 - PENTE TRIFÁSICO MÍNIMO 24 PINOS - 80A #2,5 R S T R S T BARRA 4 - PENTE TRIFÁSICO MÍNIMO 24 PINOS - 80A DETALHE SUGESTIVO DO QUADRO QUADRO METÁLICO DE SOBREPOR INTERRUPTOR TETRAPOLAR DR3-In 40A SENS. 30mA TIPO AC R S T BARRA 5 - PENTE TRIFÁSICO MÍNIMO 23 PINOS - 80A #4,0 T1 16A #4,0 T6 16A #4,0 T13 16A #4,0 T8 T12 T25 16A #4,0 T23 16A #4,0 T44 #4,0 #4,0 #2,5 #2,5 #2,5 16A #4,0 T9 16A #4,0 T33 32A #6,0 RES. 40A (C) #6,0 T2 16A #4,0 T3 16A #4,0 T5 T4 16A #4,0 16A #4,0 16A #4,0 16A #4,0 T16 16A #4,0 T45 T18 16A #4,0 T20 16A #4,0 T21 16A #4,0 T22 16A #4,0 T24 16A #4,0 T26 16A #4,0 T27 16A #4,0 T28 16A #4,0 T29 16A #4,0 T30 16A #4,0 T37 16A #4,0 T38 #4,0 16A #4,0 T42 16A #4,0 16A #4,0 T46 16A #2,5 T10 RES. 16A #4,0 T11 16A #6,0 T14 16A #4,0 T31 16A #4,0 T32 16A #4,0 T34 32A #6,0 T35 16A #4,0 T36 16A #4,0 RES. RES. 40A (C) #6,0 T7 16A #4,0 T43 16A L3 16A #2,5 L5 16A #4,0 RES. RES. RES. T47 16A #4,0 T15 16A #4,0 RES. T48 16A #4,0 T49 16A #4,0 SIMBOLOGIA P/ QUADRO: DISPOSITIVO PROTETOR DE SURTOS (DPS) PARA FASES E NEUTRO. CARACTERÍSTICAS TÉCNICAS DOS DPS's CLASSE I E CLASSE II, SEGUNDO NBR5410: - OBEDECER A NBR IEC 61.643-1; Up (NÍVEL DE PROTEÇÃO): INFERIOR A 1,5kV; - Uc (MÁXIMA TENSÃO DE OPERAÇÃO CONTÍNUA): 275V; - Iimp (CORRENTE DE IMPULSO): SUPERIOR A 12,5kA (10/350us); - In (CORRENTE NOMINAL DE DESCARGA): SUPERIOR A 20kA (8/20us) PARA REDES TRIFÁSICAS; PARA DPS CLASSE I (Uc 275V/12,5/60KA), UTILIZAR NAS FASES COMO PROTEÇÃO BACKUP, FUSÍVEIS MODULARES NH-63A gG/gL. PARA DPS CLASSE II (Uc 275V/20kA, 8/20us), UTILIZAR NAS FASES E NEUTRO COMO PROTEÇÃO BACKUP, FUSÍVEIS MODULARES NH-32A gG/gL. INDICAÇÃO NOS QUADROS. O POSIONAMENTO DOS FUSÍVEIS/DPS'S, DEVERÁ ESTAR EM CONFORMIDADE COM A FIGURA 14-a DA NBR 5410. DISPOSITIVO DIFERENCIAL RESIDUAL (DR). CARACTERÍSTICAS TÉCNICAS: - OBEDECER IEC 1008; - NÚMERO DE MÓDULOS: 4; - CORRENTE NOMINAL (IN): CONFORME INDICAÇÃO EM PLANTA; - SENSIBILIDADE: 30mA; TENSÃO MÁXIMA: 415Vca TETRAPOLAR; FREQUÊNCIA: 60Hz; TIPO: AC. DISJUNTORES TERMO-MAGNÉTICOS (MINI DISJUNTORES), CURVAS B, C OU D CONFORME INDICAÇÃO NOS QUADROS, SEGUNDO A NORMA IEC-60947-2 E DIMENSIONADOS PARA Icc = 5,0kA/220V( MONOPOLAR, BIPOLAR E TRIPOLAR, RESPECTIVAMENTE). PARA OS DISJUNTORES GERAIS DEVERÃO SER SEGUIDOS TAMBÉM OS CRITÉRIOS DA NORMA IEC-60947-2, PORÉM DEVERÃO SER DO TIPO EM CAIXA MOLDADA, TERMOMAGNÉTICO E DIMENSIONADOS PARA Icc MÍNIMO = 10,0kA/220V. CABO DE COBRE COM ISOLAÇÃO TERMOPLÁSTICO NÃO HALOGENADO E COM BAIXA EMISSÃO DE FUMAÇA, 70°C 750V, CLASSE 5 DE ENCORDOAMENTO (FASES - COR PRETA). CABO DE COBRE COM ISOLAÇÃO TERMOPLÁSTICO NÃO HALOGENADO E COM BAIXA EMISSÃO DE FUMAÇA, 70°C 750V, CLASSE 5 DE ENCORDOAMENTO (NEUTRO - COR AZUL CLARO). CABO DE COBRE COM ISOLAÇÃO TERMOPLÁSTICO NÃO HALOGENADO E COM BAIXA EMISSÃO DE FUMAÇA, 70°C 750V, CLASSE 5 DE ENCORDOAMENTO (TERRA - COR VERDE). NOTAS GERAIS DOS QUADROS: 01 - TODOS OS DISJUNTORES DOS CIRCUITOS TERMINAIS OBEDECERÃO À NBR IEC-60.947-2 (MINI-DISJUNTORES PADRÃO EUROPEU CURVAS B, C OU D CONFORME INDICAÇÃO NOS QUADROS DE CARGAS) E SERÃO DIMENSIONADOS PARA Icc = 5,0kA/220V. OS DISJUNTORES GERAIS TAMBÉM OBEDECERÃO À NBR IEC-60 .947-2, PORÉM, SERÃO DIMENSIONADOS PARA Icc = 10kA/220V E DEVERÃO SER DO TIPO TERMOMAGNÉTICO EM CAIXA MOLDADA . 02 - TODOS OS DISJUNTORES NO INTERIOR DOS QUADROS DEVERÃO SER IDENTIFICADOS ATRAVÉS DE ETIQUETAS ACRÍLICAS DE IDENTIFICAÇÃO CONFORME NOMES DOS CIRCUITOS CONSTANTES NOS QUADROS DE CARGAS. 03 - FORAM PREVISTOS ESPAÇOS RESERVAS MÍNIMOS PARA AMPLIAÇÕES FUTURAS, COM BASE NO NÚMERO DE CIRCUITOS EFETIVAMENTE INSTALADO NO QDC E DE ACORDO COM A NBR-5410:2004. 04 - O QUADRO SERÁ METÁLICO, DE EMBUTIR (PREVER ALVENARIA PARA SUSTENTAÇÃO), COM NO MÍNIMO IP-30 (EM EXCEÇÃO AOS QUADROS LOCALIZADOS AO TEMPO, QUE DEVERÃO POSSUIR GRAU DE PROTEÇÃO MÍNIMO IP-54), PROVIDO DE ALETAS PARA VENTILAÇÃO, PORTA DE TRINCO COM CHAVE, NÃO ESTAR INSTALADO EM ÁREAS MOLHADAS OU ÚMIDAS, LONGE DE GÁS, DOTADO DE FÁCIL ACESSO E NÃO SER OBSTRUÍDO, DEVENDO POSSUIR SOBRETUDO, CERTIFICAÇÃO DE TESTES SEGUNDO NBR IEC 60.439-1 EMITIDO POR EMPRESA ESPECIALIZADA NA MONTAGEM DE QUADROS ELÉTRICOS. 05 - O QUADRO DEVERÁPOSSUIR, ALÉM DOS DISJUNTORES TERMINAIS DESCRITOS NO QUADRO DE CARGAS, DISPOSITIVOS DR, DPS DE ENTRADA COM PROTEÇÃO BACKUP, BARRAS DE TERRA E NEUTRO, SENDO AS BARRAS DE NEUTRO PARA DR SEGREGADAS DA BARRA DE NEUTRO GERAL DO QUADRO, CONFORME LAYOUT SUGESTIVO DO DIAGRAMA MULTIFILAR. 06 - O QUADRO DEVERÁ POSSUIR PLACA DE MONTAGEM INTERNA NA COR LARANJA, CANALETAS PARA A PASSAGEM DE CABOS (RESPEITANDO A TAXA DE OCUPAÇÃO MÁXIMA DOS CABOS NESTAS CANALETAS, SEGUNDO ORIENTAÇÕES DA NBR 5410), BASE CONECTORA PARA A DISTRIBUIÇÃO DOS CABOS (ENTRADA E SAÍDA) E IDENTIFICAÇÃO DE NOME, TENSÃO E FREQUÊNCIA EM SUA PORTA, EM ETIQUETA ACRÍLICA DE FUNDO PRETO E LETRAS BRANCAS. TAMBÉM DEVERÁ POSSUIR UMA PLACA DE ADVERTÊNCIA INTERNA AO QUADRO, CONFORME DIZERES NESTA FOLHA. PREVER SOBRETUDO ESPAÇOS PARA DR E DPS CONFORME DETALHADO NO DIAGRAMA MULTIFILAR. 07- NO QUADRO DEVERÃO SER FIXADOS, ATRAVÉS DE DISPOSITIVO PRÓPRIO, OS DIAGRAMAS DOS MESMOS, CONTENDO TODAS AS PROTEÇÕES ENVOLVIDAS CONFORME EXECUTADO . 08- AS TERMINAÇÕES DOS ELETRODUTOS NO QUADROS ELÉTRICO, SEJAM ELES METÁLICOS OU EM MATERIAL PLÁSTICO ANTI-CHAMA (PVC RÍGIDO), DEVERÃO SER COM CONECTOR TIPO BOX RETO, COM BUCHA E ARRUELA DE ACABAMENTO, ADEQUADAS ÀS BITOLAS DO MESMO. AS ELETROCALHAS DEVERÃO SER PROVIDAS DE FLANGES PRÉ-MOLDADOS CONFORME DIMENSÕES DE PROJETO. 09- AS TERMINAÇÕES DOS CABOS NO QUADRO ELÉTRICO DEVERÃO RECEBER TEMINAL DO TIPO AGULHA PARA CONEXÃO COM OS BORNES DOS DISJUNTORES E TERMINAL TIPO OLHAL PARA CONEXÃO NOS BARRAMENTOS. TODOS OS TERMINAIS DEVERÃO SER COMPRIMIDOS ATRAVÉS DE FERRAMENTA ADEQUADA. 10- O QUADRO DEVER Á ESTAR LIMPO, LIVRE DE ARGAMASSAS, POEIRA, CAPA DE CABOS, FILAMENTOS DE CABOS DE COBRE E OUTROS MATERIAIS ESTRANHOS À INSTALAÇÃO. 11- OS TERMINAIS DAS BARRAS DE CONEXÃO NÃO UTILIZADOS DEVERÃO SER ISOLADOS POR CAPA PROTETORA ADEQUADA, DO MESMO FABRICANTE DAS BARRAS DE CONEXÃO . 12- TODOS OS CABOS ALIMENTADORES DOS CIRCUITOS INTERNOS AO QUADRO SERÃO DE COBRE COM ISOLAÇÃO TERMOPLÁSTICO NÃO HALOGENADO E COM BAIXA EMISSÃO DE FUMAÇA 70 ºC 750V. DEVERÃO SOBRETUDO, RECEBER ETIQUETAS DE IDENTIFICAÇÃO (TAG´s), INDELÉVEIS, COM INDICAÇÃO DO CIRCUITO A QUE ESTÁ LIGADO, CONFORME DESCRIÇÃO DO CAMPO CIRCUITO DO QUADRO DE CARGAS CORRESPONDENTE. 13 - ATERRAR TODAS AS PORTAS DOS QUADROS ATRAVÉS DE CABO DE COBRE #6,0mm² ISOLAÇÃO VERDE EM PVC 70°C 750V. 14 - CONFORME NBR 5410/2004, DEVIDO A POSSIBILIDADE DE FALHA INTERNA, FAZENDO COM QUE OS DPS`s ENTRE EM CURTO CIRCUITO, A NORMA IMPÕE A NECESSIDADE DE DISPOSITIVO DE PROTEÇÃO PARA ELIMINAR TAL CURTO CIRCUITO. DESTA FORMA, DEVERÁ SER UTILIZADO, EM TODOS OS QUADROS, ANTES E EM SÉRIE COM O DPS, DISPOSITIVO DE BACK UP PARA DEVIDA PROTEÇÃO. PARA DPS`s CLASSE I , FUSÍVEIS DO TIPO MODULAR 63A . PARA DPS´s CLASSE II , FUSÍVEIS TIPO MODULAR 32A . ADVERTÊNCIA 1- QUANDO UM DISJUNTOR OU FUSÍVEL ATUA, DESLIGANDO ALGUM CIRCUITO OU A INSTALAÇÃO INTEIRA, A CAUSA PODE SER UMA SOBRECARGA OU UM CURTO-CIRCUITO. DESLIGAMENTOS FREQUENTES SÃO SINAL DE SOBRECARGA. POR ISSO, NUNCA TROQUE SEUS DISJUNTORES OU FUSÍVEIS POR OUTRO DE MAIOR CORRENTE (MAIOR AMPERAGEM) SIMPLESMENTE. COMO REGRA, A TROCA DE UM DISJUNTOR OU FUSÍVEL POR OUTRO DE MAIOR CORRENTE REQUER, ANTES, A TROCA DOS FIOS E CABOS ELÉTRICOS, POR OUTROS DE MAIOR SEÇÃO (BITOLA). 2- DA MESMA FORMA, NUNCA DESATIVE OU REMOVA A CHAVE AUTOMÁTICA DE PROTEÇÃO CONTRA CHOQUES ELÉTRICOS (DISPOSITIVOS DR), MESMO EM CASO DE DESLIGAMENTOS SEM CAUSA APARENTE. SE OS DESLIGAMENTOS FOREM FREQUENTES E, PRINCIPALMENTE, SE AS TENTATIVAS DE RELIGAR A CHAVE NÃO TIVEREM ÊXITO, ISSO SIGNIFICA, MUITO PROVAVELMENTE, QUE A INSTALAÇÃO ELÉTRICA APRESENTA ANOMALIAS INTERNAS, QUE SÓ PODEM SER IDENTIFICADAS E CORRIGIDAS POR PROFISSIONAIS QUALIFICADOS. A DESATIVAÇÃO OU REMOÇÃO DA CHAVE SIGNIFICA A ELIMINAÇÃO DE MEDIDA PROTETORA CONTRA CHOQUES ELÉTRICOS E RISCO DE VIDA PARA OS USUÁRIOS DA INSTALAÇÃO. DETALHE DA ADVERTÊNCIA SEGUNDO A NBR 5410 A SER FIXADA DENTRO DOS QUADROS ELÉTRICOS TABELA 1: ESPAÇO RESERVA QUANTIDADE DE CIRCUITOS EFETIVAMENTE DISPONÍVEL N ESPAÇO MÍNIMO DESTINADO A RESERVA (EM NÚMEROS DE CIRCUITOS) ATÉ 6 2 7 A 12 3 13 A 30 4 N30 0,15xN NOTAS: 1-PROIBIDA REPRODUÇÃO OU ALTERAÇÃO DO CONTEÚDO SEM AUTORIZAÇÃO DOS RESPONSÁVEIS TÉCNICOS DO PROJETO. 2-DIREITOS AUTORAIS RESERVADOS - LEI FEDERAL 9.610 DE 19/02/1996. 3-CONFERIR MEDIDAS NO LOCAL. 4-COTAS EM CENTÍMETROS. SUBSECRETARIA DE VIGILÂNCIA E PROTEÇÃO Á SAÚDE SUPERINTENDÊNCIA DE VIGILÂNCIA SANITÁRIA DIRETORIA DE INFRAESTRUTURA FÍSICA PROJETO MODELO UNIDADE BÁSICA DE SAÚDE PROJETO DE ACORDO COM RDC-50/2002 E RESOLUÇÃO 1797/09 DA SES-MG É DE RESPONSABILIDADE DO MUNICIPIO APROVAÇÃO COM A IMPLANTAÇÃO NO TERRENO ESCOLHIDO. 03 ADEQUAÇÃO DA ARQUITETURA CONFORME VISA 01/02/2013 VIABILE 02 EMISSÃO FINAL 08/11/2012 VIABILE 01 ALIMENTAÇÃO DOS PONTOS DE CFTV, RACK DE SONORIZAÇÃO E BEBEDOUROS 26/10/2012 VIABILE 00 EMISSÃO INICIAL 27/09/2012 VIABILE VERIFICAÇÃO FOLHA: 04 05 REVISÃO OBJETO DATA GERENCIAMENTO E PROJETO: DESENVOLVIMENTO: BRENO ASSIS DE OLIVEIRA FEVEREIRO/2013 INSTALAÇÕES ELÉTRICAS VÁRIAS UNIDADES NO ESTADO DE MINAS GERAIS ETAPA: DIAGRAMA MULTIFILAR PROJETO EXECUTIVO Av. Augusto de Lima, nº655 conj. 418 - Centro - BH Telefax: (31) 3324-2702 http://www.viabile.com.br viabile@viabile.com.br DATA: NOME DO ARQUIVO CAD: ESCALA: UNIDADE: INDICADA MILÍMETROS CREA: 78.667/D RESPONSÁVEL TÉCNICO: BRENO ASSIS DE OLIVEIRA PROPRIETÁRIO: SECRETARIA DO ESTADO DE SAÚDE DE MINAS GERAIS 460-UBSSS-R03-ELE-04-PE-T1A.DWG UBS MINAS - PROJETO MODELO DISCIPLINA: PROJETO: ENDEREÇO: CONTEÚDO: SUBSECRETARIA DE INOVAÇÃO E LOGISTICA SUPERINTENDENCIA DE GESTÃO DIRETORIA DE GESTÃO DA REDE FÍSICA TIPO T1A - ACLIVE FORMATO INTERNACIONAL A1 (841 x 594mm) abrasip-mg Secretaria de Estado de Saúde de Minas Gerais Cidade Administrativa Presidente Tancredo Neves Rodovia Pref. Américo Gianetti s/nº - Bairro: Serra Verde - B. Hte - Minas Gerais - CEP: 31630-900 SES-MG Predio Minas - 12º e 13º andar
  • 6. #4,0 T7 T15 #4,0 #4,0 T20 T7 T21 #4,0 T22-1,11kW-220V T20-1,11kW-220V T7-2X200VA T19 #4,0 T6 T4 T27 T28 #4,0 N O L T46 J T14 #4,0 T12 COMPRESSOR #4,0 T12 T13 G T46 F T4 #4,0 T4 #4,0 T17 T18 #4,0 C T46 T1 T14 T2 T16 #4,0 T1-600VA COLETA T18-1,11kW-220V PLANTA DE TOMADAS DO PRIMEIRO PAVIMENTO T29 T33-6500W T33 #4,0 T29 T29 T35 T36 T33 T33 T34 #4,0 #4,0 PLANTA DE TOMADAS DO SEGUNDO PAVIMENTO I. S. T12 #4,0 SALA DE REUNIÃO E EDUCAÇÃO T49 T1 #4,0 T12 T46 T1 T12 T46 T1 T1 #4,0 #4,0 T46 T1 T14 T2-2X200VA T46 T1 #4,0 T1 T16 #4,0 T46 T46 T46 T1 T2 T1 T1 T1 T46 T1 #4,0 T2 #4,0 T2 #4,0 T1 #4,0 T14b' T14b' T14b' T14b' T14a' #4,0 T14a' T14a' T14 T14 T14a' T46 T1 T2 T14 #4,0 #4,0 #4,0 T16-1,11kW-220V T2-600VA T4-2X200VA T4 T17-1,11kW-220V A T3-4X200VA B T14 B T8 D T4 T4-2X200VA T10 T11 #6,0 T9 T8 T5 T5 E T19-1,11kW-220V F T8 F T26 T27 T28 #4,0 T26 T27 T28 #4,0 T28 #4,0 T6-2X200VA T46 T5 T8 T5 T5 T5 T6 T6 T6 T6 T6 T7 T7 T7 K T7 T22 #4,0 T7 T21-1,11kW-220V I T6 T7 T7 K M T9-600VA T11-1,8kVA T10-600VA T11 #6,0 T9 T9 T8 T8 T8 T9 T9 T12 T12 T24 T25 #4,0 T24 T25 #4,0 T12 T12 T12-2X200VA T14 T24-1,11kW-220V T25-1,11kW-220V T14 T14 G T13 T13 T13-200VA T13-200VA T12 T13 T25 #4,0 H T14 T13 T13 T13 T13 T13 T14 T23 #4,0 O T23-1,11kW-220V J T46 T46 T46 T44 #4,0 T7 T7 T14 T14 M T31 T46 T33 T32 T32 T32 T32 T35 T36 #4,0 T35 T37-2X200VA T45-1kVA T40-1,11kW-220V T40 #4,0 T35 T35 #4,0 T42-1,11kW-220V T32 T35 T49 T37 T37 #4,0 #4,0 #4,0 T37 T37-200VA T37-200VA T37 T37 T37 #4,0 T37 T34-6500W T34 #4,0 T32 T32 T34 #6,0 T32 T37 T42 #4,0 T32 T32 T37 T42 #4,0 T36-1,8kVA T49 T35 T35 T35 T35 T35 T32 T35 T36 T36 #4,0 T35-600VA T35 T35 T34 #6,0 T32 T37 T42 #4,0 T32 T32 T32 T32 T40 T41 #4,0 T40 T41 #4,0 T41 #4,0 T41-1,11kW-220V T31 T31 R T31 T45 T31 T45 T31 T31 T31 S T31 T V U T30-2X600VA T38-1,11kW-220V T38 #4,0 T29 T29 T29 T29 T29 T29 T29 T30 T39-1,11kW-220V T39 #4,0 T29 T29 2XT29 T32 T32 T46 T46 T46 T46 T46 T31 T31 T31 T31 O P Q R #4,0 T47-1KVA T47 #4,0 T48 #4,0 T14 T48-1KVA T49 T7 T49 T49 T49 T49 T49 T49 T3 T49 T49 T49 T49 T49 T49 T49 T49 T14 T14 T32 T32 T14 T14 VACINAÇÃO SALA DE ESPERA I.S. MASC. RECEPÇÃO TRIAGEM CIRCULAÇÃO GINECOLOGIA DML ALMOXARIFADO VARANDA COBERTA I.S. FEM. ESCOVÁRIO RESÍDUOS RESÍDUOS COPA TV SUSPENSA VAGA PARA AMBULÂNCIA FOSSO ESCANINHOS ÁREA PERMEÁVEL ÁREA PERMEÁVEL proj. da cobertura CALÇADA RUA ALÇAPÃO LAVAGEM E DESINFECÇÃO DE MATERIAIS ESTERILIZAÇÃO GUICHÊ DML proj. da cobertura SALA DE APOIO AGENTES ENDEMIAS APOIO AGENTES ENDEMIAS SALA DE CURATIVOS CUIDADOS BÁSICOS ATENDIMENTO MULTIPROFISSIONAL ATENDIMENTO MULTIPROFISSIONAL GUARDA MEDICAMENTOS REBAIXO NA CALÇADA P/ ACESSO DE VEÍCULOS REBAIXO NA CALÇADA P/ ACESSIBILIDADE CONSULTÓRIO ODONTOLÓGICO VESTIÁRIO FEMININO ESCALA: ......................................................................................................... 1/75 ESCALA: .......................................................................................................... 1/75 T4 #4,0 T4 #4,0 T5 T26 T27 T28 T14 #4,0 T14 #4,0 #4,0 T46 T1 T2 T14 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 T8 T11 #6,0 T9 T5-2X200VA T15 T43 T43 T34 #4,0 T34 #4,0 T34 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 A LEGENDA PARA PERCURSO DE CABOS (QDC-QDC-T1/A): B T46 T1 T2 T4 T14 T16 C D E F #4,0 G H T3 T1 T2 T4 T14 T48 #4,0 T46 T3 T1 T2 T4 T16 T17 #4,0 T14 T3 T16 T17 T8 T1 T2 T4 T48 #4,0 T14 T5 T8 T9 T10 T3 T1 T2 T4 T16 T17 T18 T11 #4,0 #6,0 T14 T5 T8 T9 T10 T3 T1 T2 T4 T16 T17 T18 T19 T11 #4,0 #6,0 T14 T5 T8 T9 T10 T3 T1 T2 T4 T16 T17 T18 T19 T26 T27 T28 T11 #4,0 #6,0 T14 T5 T6 T8 T9 T10 T12 T13 T3 T1 T2 T4 T16 T17 T18 T19 T26 T27 T28 T11 #4,0 T14 I T3 T1 T2 T4 T28 #6,0 T5 T6 T8 T9 T10 T12 T13 T16 T17 T18 T19 T24 T25 T26 T27 T11 #4,0 T14 J T3 T1 T2 T4 T28 #6,0 T5 T6 T7 T8 T9 T10 T12 T13 T16 T17 T18 T19 T20 T21 T24 T25 T26 T27 T11 #4,0 K T3 T1 T2 T4 #6,0 T14 T43 T6 T7 T8 T9 T10 T12 T13 T16 T17 T18 T19 T20 T21 T24 T25 T26 T27 T28 T11 #4,0 #6,0 T14 T6 T7 T8 T9 T10 T12 T13 T16 T17 T18 T19 T20 T21 T22 T24 T25 T26 T27 T28 T11 L T3 T1 T2 T4 #4,0 M T3 T1 T2 T4 #6,0 T14 T6 T7 T8 T9 T10 T12 T13 T16 T17 T18 T19 T20 T21 T22 T23 T24 T25 T26 T27 T28 T11 #4,0 N T3 T1 T2 T4 #6,0 T14 T6 T7 T8 T9 T10 T12 T13 T16 T17 T18 T19 T20 T21 T22 T23 T24 T25 T26 T27 T28 T44 T11 #4,0 O T3 T1 T2 T4 #6,0 T6 T7 T8 T9 T10 T12 T13 T15 T16 T17 T18 T19 T20 T21 T22 T23 T24 T25 T26 T27 T28 T44 T11 #4,0 P T3 T1 T2 T4 #6,0 T6 T7 T8 T9 T10 T12 T13 T15 T31 T16 T17 T18 T19 T20 T21 T22 T23 T24 T25 T26 T27 T28 T44 T11 #4,0 Q T3 T1 T2 T4 #6,0 T6 T7 T8 T9 T10 T12 T13 T15 T29 T31 T16 T17 T18 T19 T20 T21 T22 T23 T24 T25 T26 T27 T28 T44 T11 #4,0 R T3 T1 T2 T4 #6,0 T6 T7 T8 T9 T10 T12 T13 T15 T29 T31 T32 T16 T17 T18 T19 T20 T21 T22 T23 T24 T25 T26 T27 T28 T38 T44 T11 #4,0 S T3 T1 T2 T4 #6,0 T6 T7 T8 T9 T10 T12 T13 T15 T29 T30 T31 T32 T45 T16 T17 T18 T19 T20 T21 T22 T23 T24 T25 T26 T27 T28 T38 T44 T11 #4,0 T T3 T1 T2 T4 #6,0 T10 T12 T13 T15 T29 T30 T31 T32 T45 T16 T17 T18 T19 T20 T21 T22 T23 T24 T25 T26 T27 T28 T38 T39 T44 T11 #4,0 #6,0 U T36 T40 T41 T42 #4,0 T6 T7 T8 T9 T32 T35 T37 T6 T7 T8 T9 V T35 T37 T1 T3 T2 T4 #4,0 T16 T17 T10 T12 T13 T15 T29 T31 T32 T30 T45 T18 T19 T20 T21 T22 T23 T24 T25 T26 T27 T28 T36 T38 T39 T40 T41 T42 T44 T11 #6,0 T46 T46 T46 T46 T46 T46 T46 T46 T46 T16 T18 T48 T18 T48 T48 T48 T48 T48 T48 T48 T48 T48 T48 T47 T47 T47 T47 T47 T47 T47 T49 T49 T49 T49 T49 T49 T49 T48 T48 T48 T48 T48 T48 T48 T49 T49 T47 T49 T47 T49 T47 T49 T47 T49 T47 T49 T47 T49 T47 T49 T47 T49 T47 T49 T47 T49 T47 T49 T47 T49 T14 T47 T14 T14 T14 T14 T14 T14 T14 T5 T5 T5 T5 T5 T5 T5 T5 T5 T5 T5 T49 T46 T43 T46 T43 T46 T43 T46 T43 T46 T43 T46 T43 T46 T43 T46 T43 T46 T43 T46 T43 #4,0 NOTAS: 1-PROIBIDA REPRODUÇÃO OU ALTERAÇÃO DO CONTEÚDO SEM AUTORIZAÇÃO DOS RESPONSÁVEIS TÉCNICOS DO PROJETO. 2-DIREITOS AUTORAIS RESERVADOS - LEI FEDERAL 9.610 DE 19/02/1996. 3-CONFERIR MEDIDAS NO LOCAL. 4-COTAS EM CENTÍMETROS. SUBSECRETARIA DE VIGILÂNCIA E PROTEÇÃO Á SAÚDE SUPERINTENDÊNCIA DE VIGILÂNCIA SANITÁRIA DIRETORIA DE INFRAESTRUTURA FÍSICA PROJETO MODELO UNIDADE BÁSICA DE SAÚDE PROJETO DE ACORDO COM RDC-50/2002 E RESOLUÇÃO 1797/09 DA SES-MG É DE RESPONSABILIDADE DO MUNICIPIO APROVAÇÃO COM A IMPLANTAÇÃO NO TERRENO ESCOLHIDO. 03 ADEQUAÇÃO DA ARQUITETURA CONFORME VISA 31/01/2013 VIABILE 02 EMISSÃO FINAL 08/11/2012 VIABILE 01 ALIMENTAÇÃO DOS PONTOS DE CFTV, RACK DE SONORIZAÇÃO E BEBEDOUROS 26/10/2012 VIABILE 00 EMISSÃO INICIAL 27/09/2012 VIABILE VERIFICAÇÃO FOLHA: 03 05 REVISÃO OBJETO DATA GERENCIAMENTO E PROJETO: DESENVOLVIMENTO: BRENO ASSIS DE OLIVEIRA FEVEREIRO/2013 INSTALAÇÕES ELÉTRICAS VÁRIAS UNIDADES NO ESTADO DE MINAS GERAIS ETAPA: PLANTAS DE TOMADAS DO 1º E 2º PROJETO EXECUTIVO PAVIMENTOS Av. Augusto de Lima, nº655 conj. 418 - Centro - BH Telefax: (31) 3324-2702 http://www.viabile.com.br viabile@viabile.com.br DATA: NOME DO ARQUIVO CAD: ESCALA: UNIDADE: INDICADA CENTÍMETROS CREA: 78.667/D RESPONSÁVEL TÉCNICO: BRENO ASSIS DE OLIVEIRA PROPRIETÁRIO: SECRETARIA DO ESTADO DE SAÚDE DE MINAS GERAIS 460-UBSSS-R03-ELE-03-PE-T1A.DWG UBS MINAS - PROJETO MODELO DISCIPLINA: PROJETO: ENDEREÇO: CONTEÚDO: SUBSECRETARIA DE INOVAÇÃO E LOGISTICA SUPERINTENDENCIA DE GESTÃO DIRETORIA DE GESTÃO DA REDE FÍSICA TIPO T1A - ACLIVE FORMATO INTERNACIONAL A1 (841 x 594mm) abrasip-mg Secretaria de Estado de Saúde de Minas Gerais Cidade Administrativa Presidente Tancredo Neves Rodovia Pref. Américo Gianetti s/nº - Bairro: Serra Verde - B. Hte - Minas Gerais - CEP: 31630-900 SES-MG Predio Minas - 12º e 13º andar