Earthquakes LoadsEarthquakes Loads
As per IS 1893 : 2002As per IS 1893 : 2002
BuildingBuilding
Step: 1 Design Horizontal Seismic Coefficient,
Ah = ZISa / 2Rg
where, Z = Zone Factor (Table 2)
I = Importance Factor (Table 6)
R = Response Reduction Factor (Table 7)
Sa/g = Average Response Acceleration Coefficient (Fig. 2)
Step: 2 Calculation of Seismic Weight ,
Step:3 Design Seismic Lateral Force :
Vb = Ah . W
W = Seismic weight of building (clause 7.4.2)
Design Horizontal Seismic CoefficientDesign Horizontal Seismic Coefficient
It is the factor which is multiplied with Seismic wt. to
determine design lateral force.
Ah = ZISa / 2Rg
1) Z = Zone Factor
Seismic Zone Z
II 0.10
III 0.16
IV 0.24
V 0.36
MUSE 11BMUSE 11B
2) I = Importance factor
3) R = Response Reduction Factor
Sr. No. Structure I
I
Important services
and community
buildings
1.5
II All other building 1.0
Sr. No. Structure R
I
Ordinary RC moment
resisting frame
3
II
Special RC moment-
resisting frame
5
4) Sa / g = Spectral Acceleration Coefficient
Step : 2 Seismic Weight
Sr. No. Floor Load %
I Upto 3 25
II Above 3 50
ExampleExample
10m
5m
10m
Consider a single storey reinforced concrete office building which
is located in Ludhiana. The soil conditions are medium stiff . The
lumped weight due to dead loads is 12kN/m2
on roofs and a live
load of 4 kN/m2 . Determine design seismic load on the structure
as per new code.
Data GivenData Given
• Zone factor (Z) = 0.24 ( Ldh in Zone IV)
• Importance factor (I) = 1.0 (Office Building)
• Response reduction factor = 5 (R.C.C. Frame)
• Live Load = 4 KN/m2
• Dead load = 12KN/m2
+
Design Horizontal Seismic CoefficientDesign Horizontal Seismic Coefficient
• Fundamental period = 2 sec
• Soil Condition = medium stiff
• Hence Sa / g = 2.5
Ah = ZISa / 2Rg
= 0.24 x 1.0 x 2.5 / 5x2
= 0.06
G. N. D..E.C.G. N. D..E.C.
Seismic WeightSeismic Weight
Floor area = 10 X 10 m2
Live Load = 4 KN/m2
Only 50% of live load is to be lumped at roofs.
Dead load = 12KN/m2
Seismic Weight = 100 X (4*0.5+ 12) = 1400KN
Seismic Shear forceSeismic Shear force
Vb = Ah . W
= 0.06 x 1400
= 84 KN
• Problem:
A single storey R.C.C. building is situated at Jalandhar. The
soil below foundation is hard strata. Determining seismic
shear force acting on the building. Compare the seismic
shear force with an identical building in Bangalore. take
fundamental time period as unity and seismic weight of
building = 1500 KN.
Case I: Building in JalandharCase I: Building in Jalandhar
• Zone factor (Z) = 0.24 As Jalandhar in Zone IV
• Importance factor (I) = 1.5
• Response reduction factor = 5 (R.C.C. frame building)
• Spectral acceleration Sa/g = 1 (Hard Strata)
• Seismic weight (W) = 1500 KN
Seismic Base ShearSeismic Base Shear
Vb = Ah . W
= ZISa / 2Rg x W
= 0.24x 1.5x1x15000/2/5
= 540 KN
Case II: Building in BangaloreCase II: Building in Bangalore
• Zone factor (Z) = 0.10 As Bangalore in Zone IV
• Importance factor (I) = 1.5
• Response reduction factor = 5 (R.C.C. frame building)
• Spectral acceleration Sa/g = 1 (Hard Strata)
• Seismic weight (W) = 1500 KN
Seismic Base ShearSeismic Base Shear
Vb = Ah . W
= ZISa / 2Rg x W
= 0.10x 1.5x1x15000/2/5
= 225 KN
Result: Comparison of base shear values in the above two cases
show that seismic design force in Jalandhar is 2.4 times that
of Bangalore for identical type of building $ soil condition.
ExampleExample
• Problem:
Considering a four storey building of R.C.C. is located in Bhuj.
The soil conditions are medium stiff and entire building is
located on raft footing. The lumped weight due to dead load is
12 KN/m2 on floors and 10KN/m2 on roof. The floor are cater
to carry a live load of 4KN/ m2 on floor and 1.5 KN/m2 on
roof. Determine design seismic load on structure.
Data GivenData Given
• Zone factor (Z) = 0.36 As Bhuj in Zone IV
• Importance factor (I) = 1.0
• Response reduction factor = 5 (R.C.C. frame building)
• Spectral acceleration Sa/g = 1 (Hard Strata)
Seismic weightSeismic weight
The floor area is 15×20=300 sq. m. Since the live load class is
4kN/sq.m, only 50% of the live load is lumped at the floors. At roof,
no live load is to be lumped. Hence, the total seismic weight on the
floors and the roof is:
Floors:
W1=W2 =W3 =300×(12+0.5×4)
= 4,200 KN
Roof:
W4 = 300×10
= 3,000 KN
(clause7.3.1, Table 8 of IS: 1893 Part 1)
Total Seismic weight of the structure,
W = ΣWi = 3×4,200 + 3,000
= 15,600 KN
Design Horizontal Seismic CoefficientDesign Horizontal Seismic Coefficient
• Fundamental period = 2 sec
• Soil Condition = medium stiff
• Hence Sa / g = 2.5
Ah = ZISa / 2Rg
= 0.36 x 1.0 x 2.5 / 5x2
= 0.09
Seismic Shear forceSeismic Shear force
Vb = Ah . W
= 0.09 x 15600
= 1440 KN
Distribution of design force to each floor,
Qi = Vb.wi.hi
2
/ ∑ wj.hj
2
Qi = Design lateral force at floor i
wi = Seismic weight of floor i
hi = height of floor i measured from base
n = number of floors
Lateral load distributionLateral load distribution
Storey
Level
Wi hi wi.hi
2
wi.hi
2
/
∑ wj.hj
2
Lateral
Force
4 3000 13.8 571.3 .424 611
3 4200 10.6 471.9 .350 501
2 4200 7.4 230 .171 246
1 4200 4.2 74.1 .055 79
1347.3 1000 1440
i s code 1893:2002

Contenu connexe

Tendances

Unit iii braced_cuts
Unit iii braced_cutsUnit iii braced_cuts
Unit iii braced_cuts
Gimmick
 

Tendances (20)

Unit iii braced_cuts
Unit iii braced_cutsUnit iii braced_cuts
Unit iii braced_cuts
 
7 losses in prestress
7 losses in prestress7 losses in prestress
7 losses in prestress
 
Pile Foundations
Pile FoundationsPile Foundations
Pile Foundations
 
Part-II: Seismic Analysis/Design of Multi-storied RC Buildings using STAAD.Pr...
Part-II: Seismic Analysis/Design of Multi-storied RC Buildings using STAAD.Pr...Part-II: Seismic Analysis/Design of Multi-storied RC Buildings using STAAD.Pr...
Part-II: Seismic Analysis/Design of Multi-storied RC Buildings using STAAD.Pr...
 
REPAIRS AND REHABILITATION OF STRUCTURES
REPAIRS AND REHABILITATION OF STRUCTURESREPAIRS AND REHABILITATION OF STRUCTURES
REPAIRS AND REHABILITATION OF STRUCTURES
 
Reinforced earth walls
Reinforced earth wallsReinforced earth walls
Reinforced earth walls
 
Seismic Analysis
Seismic AnalysisSeismic Analysis
Seismic Analysis
 
Laterally Loaded Piles
Laterally Loaded PilesLaterally Loaded Piles
Laterally Loaded Piles
 
Unit 1 sheet pile-converted
Unit 1   sheet pile-convertedUnit 1   sheet pile-converted
Unit 1 sheet pile-converted
 
Counterfort Retaining Wall
Counterfort Retaining WallCounterfort Retaining Wall
Counterfort Retaining Wall
 
Chapter 13
Chapter 13Chapter 13
Chapter 13
 
ANALYSIS & DESIGN OF G+3 STORIED REINFORCED CONCRETE BUILDING
ANALYSIS & DESIGN OF G+3 STORIED REINFORCED CONCRETE BUILDING ANALYSIS & DESIGN OF G+3 STORIED REINFORCED CONCRETE BUILDING
ANALYSIS & DESIGN OF G+3 STORIED REINFORCED CONCRETE BUILDING
 
Burmister 2 layer
Burmister 2 layerBurmister 2 layer
Burmister 2 layer
 
Expansive soil
Expansive soilExpansive soil
Expansive soil
 
From force-based to displacement-based seismic design. What comes next?
From force-based to displacement-based seismic design. What comes next?From force-based to displacement-based seismic design. What comes next?
From force-based to displacement-based seismic design. What comes next?
 
Chapter 11
Chapter 11Chapter 11
Chapter 11
 
Geotechnical Aspects of EQ Resistant Design
Geotechnical Aspects of EQ Resistant DesignGeotechnical Aspects of EQ Resistant Design
Geotechnical Aspects of EQ Resistant Design
 
Review of Causes of Foundation Failures and Their Possible Preventive and Rem...
Review of Causes of Foundation Failures and Their Possible Preventive and Rem...Review of Causes of Foundation Failures and Their Possible Preventive and Rem...
Review of Causes of Foundation Failures and Their Possible Preventive and Rem...
 
Bearing capacity of shallow foundations by abhishek sharma
Bearing capacity of shallow foundations by abhishek sharma Bearing capacity of shallow foundations by abhishek sharma
Bearing capacity of shallow foundations by abhishek sharma
 
Earthquake resistant design
Earthquake resistant designEarthquake resistant design
Earthquake resistant design
 

En vedette (6)

Basic concepts in indian standard eq design codes
Basic concepts in indian standard eq design codesBasic concepts in indian standard eq design codes
Basic concepts in indian standard eq design codes
 
1893 1
1893 11893 1
1893 1
 
OER_RC_1225_008
OER_RC_1225_008OER_RC_1225_008
OER_RC_1225_008
 
Is 875 wind load
Is 875   wind loadIs 875   wind load
Is 875 wind load
 
MODAL AND RESPONSE SPECTRUM (IS 18932002) ANALYSIS 0F R.C FRAME BUILDING (IT ...
MODAL AND RESPONSE SPECTRUM (IS 18932002) ANALYSIS 0F R.C FRAME BUILDING (IT ...MODAL AND RESPONSE SPECTRUM (IS 18932002) ANALYSIS 0F R.C FRAME BUILDING (IT ...
MODAL AND RESPONSE SPECTRUM (IS 18932002) ANALYSIS 0F R.C FRAME BUILDING (IT ...
 
SEISMIC_DESIGN
SEISMIC_DESIGNSEISMIC_DESIGN
SEISMIC_DESIGN
 

Similaire à i s code 1893:2002

DESIGN AND ANALYSIS OF EARTH-QUAKE RESISTANT FOR MULTI-STORIED BUILDING ON A ...
DESIGN AND ANALYSIS OF EARTH-QUAKE RESISTANT FOR MULTI-STORIED BUILDING ON A ...DESIGN AND ANALYSIS OF EARTH-QUAKE RESISTANT FOR MULTI-STORIED BUILDING ON A ...
DESIGN AND ANALYSIS OF EARTH-QUAKE RESISTANT FOR MULTI-STORIED BUILDING ON A ...
Ijripublishers Ijri
 

Similaire à i s code 1893:2002 (20)

presentation.pptx
presentation.pptxpresentation.pptx
presentation.pptx
 
Analysis of g+3 rcc storied building
Analysis of g+3 rcc storied buildingAnalysis of g+3 rcc storied building
Analysis of g+3 rcc storied building
 
Assignement 2: Structural Analysis
Assignement 2: Structural AnalysisAssignement 2: Structural Analysis
Assignement 2: Structural Analysis
 
Final structure report
Final structure reportFinal structure report
Final structure report
 
G.p presentation
G.p presentationG.p presentation
G.p presentation
 
EQ21.pdf
EQ21.pdfEQ21.pdf
EQ21.pdf
 
Building Structure calculation
Building Structure calculationBuilding Structure calculation
Building Structure calculation
 
Building Structure Project 2 report
Building Structure Project 2 reportBuilding Structure Project 2 report
Building Structure Project 2 report
 
IRJET- Comparative Analysis of NBC 105:1994 and IS 1893:2016 Seismic Codes wi...
IRJET- Comparative Analysis of NBC 105:1994 and IS 1893:2016 Seismic Codes wi...IRJET- Comparative Analysis of NBC 105:1994 and IS 1893:2016 Seismic Codes wi...
IRJET- Comparative Analysis of NBC 105:1994 and IS 1893:2016 Seismic Codes wi...
 
Example314b taskgroupb-c-120730160543-phpapp01
Example314b taskgroupb-c-120730160543-phpapp01Example314b taskgroupb-c-120730160543-phpapp01
Example314b taskgroupb-c-120730160543-phpapp01
 
Earthquake Resistance Design-Impact On Cost Of Reinforced Concrete Builidings
Earthquake Resistance Design-Impact On Cost Of Reinforced  Concrete BuilidingsEarthquake Resistance Design-Impact On Cost Of Reinforced  Concrete Builidings
Earthquake Resistance Design-Impact On Cost Of Reinforced Concrete Builidings
 
Structural design including disaster (wind & cyclone land slide_eq_ resistan...
Structural design including disaster (wind & cyclone  land slide_eq_ resistan...Structural design including disaster (wind & cyclone  land slide_eq_ resistan...
Structural design including disaster (wind & cyclone land slide_eq_ resistan...
 
Sachpazis pile analysis & design. calculation according to en 1997 1-2004
Sachpazis pile analysis & design. calculation according to en 1997 1-2004Sachpazis pile analysis & design. calculation according to en 1997 1-2004
Sachpazis pile analysis & design. calculation according to en 1997 1-2004
 
DESIGN AND ANALYSIS OF EARTH-QUAKE RESISTANT FOR MULTI-STORIED BUILDING ON A ...
DESIGN AND ANALYSIS OF EARTH-QUAKE RESISTANT FOR MULTI-STORIED BUILDING ON A ...DESIGN AND ANALYSIS OF EARTH-QUAKE RESISTANT FOR MULTI-STORIED BUILDING ON A ...
DESIGN AND ANALYSIS OF EARTH-QUAKE RESISTANT FOR MULTI-STORIED BUILDING ON A ...
 
A Comperative study of Analysis of a G+3 Residential Building by the Equivale...
A Comperative study of Analysis of a G+3 Residential Building by the Equivale...A Comperative study of Analysis of a G+3 Residential Building by the Equivale...
A Comperative study of Analysis of a G+3 Residential Building by the Equivale...
 
Chapter 1-types of structures and loads
Chapter 1-types of structures and loadsChapter 1-types of structures and loads
Chapter 1-types of structures and loads
 
Seismic evaluation of masonry building a case study
Seismic evaluation of masonry building a case studySeismic evaluation of masonry building a case study
Seismic evaluation of masonry building a case study
 
SEISMIC EVALUATION OF MASONRY BUILDING A CASE STUDY
SEISMIC EVALUATION OF MASONRY BUILDING A CASE STUDYSEISMIC EVALUATION OF MASONRY BUILDING A CASE STUDY
SEISMIC EVALUATION OF MASONRY BUILDING A CASE STUDY
 
Analysis and Design of Residential building.pptx
Analysis and Design of Residential building.pptxAnalysis and Design of Residential building.pptx
Analysis and Design of Residential building.pptx
 
Static and Dynamic Behavior of Reinforced Concrete Framed Building: A Compara...
Static and Dynamic Behavior of Reinforced Concrete Framed Building: A Compara...Static and Dynamic Behavior of Reinforced Concrete Framed Building: A Compara...
Static and Dynamic Behavior of Reinforced Concrete Framed Building: A Compara...
 

Dernier

Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoorTop Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
dharasingh5698
 
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Kandungan 087776558899
 
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
amitlee9823
 

Dernier (20)

Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoorTop Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torque
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.ppt
 
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
 
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
 
Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01
 
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 
Design For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the startDesign For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the start
 
Unit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdfUnit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdf
 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdf
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
Work-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxWork-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptx
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
 
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdf
 

i s code 1893:2002

  • 1. Earthquakes LoadsEarthquakes Loads As per IS 1893 : 2002As per IS 1893 : 2002
  • 2. BuildingBuilding Step: 1 Design Horizontal Seismic Coefficient, Ah = ZISa / 2Rg where, Z = Zone Factor (Table 2) I = Importance Factor (Table 6) R = Response Reduction Factor (Table 7) Sa/g = Average Response Acceleration Coefficient (Fig. 2) Step: 2 Calculation of Seismic Weight , Step:3 Design Seismic Lateral Force : Vb = Ah . W W = Seismic weight of building (clause 7.4.2)
  • 3. Design Horizontal Seismic CoefficientDesign Horizontal Seismic Coefficient It is the factor which is multiplied with Seismic wt. to determine design lateral force. Ah = ZISa / 2Rg 1) Z = Zone Factor Seismic Zone Z II 0.10 III 0.16 IV 0.24 V 0.36
  • 5. 2) I = Importance factor 3) R = Response Reduction Factor Sr. No. Structure I I Important services and community buildings 1.5 II All other building 1.0 Sr. No. Structure R I Ordinary RC moment resisting frame 3 II Special RC moment- resisting frame 5
  • 6. 4) Sa / g = Spectral Acceleration Coefficient Step : 2 Seismic Weight Sr. No. Floor Load % I Upto 3 25 II Above 3 50
  • 7. ExampleExample 10m 5m 10m Consider a single storey reinforced concrete office building which is located in Ludhiana. The soil conditions are medium stiff . The lumped weight due to dead loads is 12kN/m2 on roofs and a live load of 4 kN/m2 . Determine design seismic load on the structure as per new code.
  • 8. Data GivenData Given • Zone factor (Z) = 0.24 ( Ldh in Zone IV) • Importance factor (I) = 1.0 (Office Building) • Response reduction factor = 5 (R.C.C. Frame) • Live Load = 4 KN/m2 • Dead load = 12KN/m2 +
  • 9. Design Horizontal Seismic CoefficientDesign Horizontal Seismic Coefficient • Fundamental period = 2 sec • Soil Condition = medium stiff • Hence Sa / g = 2.5 Ah = ZISa / 2Rg = 0.24 x 1.0 x 2.5 / 5x2 = 0.06
  • 10. G. N. D..E.C.G. N. D..E.C. Seismic WeightSeismic Weight Floor area = 10 X 10 m2 Live Load = 4 KN/m2 Only 50% of live load is to be lumped at roofs. Dead load = 12KN/m2 Seismic Weight = 100 X (4*0.5+ 12) = 1400KN
  • 11. Seismic Shear forceSeismic Shear force Vb = Ah . W = 0.06 x 1400 = 84 KN
  • 12. • Problem: A single storey R.C.C. building is situated at Jalandhar. The soil below foundation is hard strata. Determining seismic shear force acting on the building. Compare the seismic shear force with an identical building in Bangalore. take fundamental time period as unity and seismic weight of building = 1500 KN.
  • 13. Case I: Building in JalandharCase I: Building in Jalandhar • Zone factor (Z) = 0.24 As Jalandhar in Zone IV • Importance factor (I) = 1.5 • Response reduction factor = 5 (R.C.C. frame building) • Spectral acceleration Sa/g = 1 (Hard Strata) • Seismic weight (W) = 1500 KN
  • 14. Seismic Base ShearSeismic Base Shear Vb = Ah . W = ZISa / 2Rg x W = 0.24x 1.5x1x15000/2/5 = 540 KN
  • 15. Case II: Building in BangaloreCase II: Building in Bangalore • Zone factor (Z) = 0.10 As Bangalore in Zone IV • Importance factor (I) = 1.5 • Response reduction factor = 5 (R.C.C. frame building) • Spectral acceleration Sa/g = 1 (Hard Strata) • Seismic weight (W) = 1500 KN
  • 16. Seismic Base ShearSeismic Base Shear Vb = Ah . W = ZISa / 2Rg x W = 0.10x 1.5x1x15000/2/5 = 225 KN Result: Comparison of base shear values in the above two cases show that seismic design force in Jalandhar is 2.4 times that of Bangalore for identical type of building $ soil condition.
  • 17. ExampleExample • Problem: Considering a four storey building of R.C.C. is located in Bhuj. The soil conditions are medium stiff and entire building is located on raft footing. The lumped weight due to dead load is 12 KN/m2 on floors and 10KN/m2 on roof. The floor are cater to carry a live load of 4KN/ m2 on floor and 1.5 KN/m2 on roof. Determine design seismic load on structure.
  • 18. Data GivenData Given • Zone factor (Z) = 0.36 As Bhuj in Zone IV • Importance factor (I) = 1.0 • Response reduction factor = 5 (R.C.C. frame building) • Spectral acceleration Sa/g = 1 (Hard Strata)
  • 19. Seismic weightSeismic weight The floor area is 15×20=300 sq. m. Since the live load class is 4kN/sq.m, only 50% of the live load is lumped at the floors. At roof, no live load is to be lumped. Hence, the total seismic weight on the floors and the roof is: Floors: W1=W2 =W3 =300×(12+0.5×4) = 4,200 KN Roof: W4 = 300×10 = 3,000 KN (clause7.3.1, Table 8 of IS: 1893 Part 1) Total Seismic weight of the structure, W = ΣWi = 3×4,200 + 3,000 = 15,600 KN
  • 20. Design Horizontal Seismic CoefficientDesign Horizontal Seismic Coefficient • Fundamental period = 2 sec • Soil Condition = medium stiff • Hence Sa / g = 2.5 Ah = ZISa / 2Rg = 0.36 x 1.0 x 2.5 / 5x2 = 0.09
  • 21. Seismic Shear forceSeismic Shear force Vb = Ah . W = 0.09 x 15600 = 1440 KN
  • 22. Distribution of design force to each floor, Qi = Vb.wi.hi 2 / ∑ wj.hj 2 Qi = Design lateral force at floor i wi = Seismic weight of floor i hi = height of floor i measured from base n = number of floors
  • 23. Lateral load distributionLateral load distribution Storey Level Wi hi wi.hi 2 wi.hi 2 / ∑ wj.hj 2 Lateral Force 4 3000 13.8 571.3 .424 611 3 4200 10.6 471.9 .350 501 2 4200 7.4 230 .171 246 1 4200 4.2 74.1 .055 79 1347.3 1000 1440