Understanding Power Factor,
Crest Factor, and Surge Factor

White Paper 17
Revision 1


by Neil Rasmussen




                                                               Contents
    > Executive summary                                        Click on a section to jump to it

                                                               Introduction                       2
    This white paper explains the technical terms of power
    factor, crest factor, and surge factor. The use of these   Power factor                       2
    terms in specifying UPS is explained.
                                                               Crest factor                       3

                                                               Surge factor                       4

                                                               Conclusion                         5

                                                               Resources                          6
Understanding Power Factor, Crest Factor, and Surge Factor




Introduction   The terms power factor, crest factor, and surge factor refer to completely different and
               unrelated phenomena. These characteristics are often specified for UPS systems, and
               customers will sometimes place them in specifications.




Power factor   Power factor is a quantity which has important implications when sizing a UPS system and
               power distribution equipment. Power is a measure of the delivery rate of energy and in DC
               (direct current) electrical circuits is expressed as the mathematical product of Volts and Amps
               (Power = Volts x Amps). However, in AC (alternating current) power system, a complication
               is introduced; namely that some AC current (Amps) may flow into and back out of the load
               without delivering energy. This current, called reactive or harmonic current, gives rise to an
               “apparent” power (Volt x Amps) which is larger than the actual power consumed. This
               difference between the apparent power and the actual power gives rise to the power factor.
               The power factor is equal to the ratio of the actual power to the apparent power. The
               apparent power is expressed as the Volt-Amp or VA rating. Therefore, the actual power in
               any AC system is the VA rating multiplied by the power factor.

               For many types of electrical equipment the difference between apparent power (VA) and
               actual power (Watts) is very slight and can be ignored, but for some computers the difference
               is very large and important. Many desktop personal computers present a nonlinear load to
               the AC supply. This is because they have a power supply design known as a "capacitor input
               switch mode power supply". In a study done by PC Magazine, it was found that typical
               personal computer systems exhibit a power factor of .65 which means that the apparent
               power (VA) was 50% larger than the actual power (Watts)!

               Information technology (IT) equipment including servers, routers, hubs, and storage systems
               almost universally use a different power supply design known as "Power Factor Corrected".
               These devices present a very linear load to the AC supply and do not generate harmonic
               currents. In fact they are one of the cleanest loads on the power grid and generate less
               harmonic current than many other devices such as fluorescent lighting or variable speed
               motors. Ten years ago, these devices were nonlinear loads like personal computers, but
               today all of these loads are subject to international regulation IEC 1000-3-2 which require
               them to be made with the "Power Factor Corrected" design.



               Sizing a UPS
               To size a UPS and ensure that the UPS output capacity is sufficient, both the VA rating and
               the Watt rating of the load are important. The watt rating of the UPS relates to the amount of
               power it can deliver, and the VA rating of the UPS relates to the amount of current it can
               deliver. Neither the Watt nor the VA rating of the UPS can be exceeded. In practice, the best
               approach is to size a UPS the Watt rating of the load. This is particularly true for larger IT
               installations where the power factors of the loads are nearly 1. If there is confusion regarding
               power ratings or power factor, and it is desirable to ensure the load can be powered by the
               UPS, then choosing a UPS with a Watt rating greater than or equal to the VA rating of the
               load will always ensure a safety margin.

               Power factor has an important implication in the specification of UPS run time on battery.
               Battery run time is dictated by the watt load on the UPS. However, when many UPS manu-
               facturers specify run time at full load they are referring to full VA load, not the full watt load.
               For example, a UPS rated at 10,000 VA may be rated for 20 minutes of run time at full load.
               In the fine print it notes that this full load is at a .65 power factor. Therefore the load for the
               run time specification is really only 6500 Watts. The same UPS may have a 9000 W rating.


               APC by Schneider Electric                                            White Paper 17    Rev 1    2
Understanding Power Factor, Crest Factor, and Surge Factor


                           This means that the run time was provided at 6500/9000 or 72% of the full load watt rating of
                           the UPS. At 72% of the Watt rating the UPS may run almost 70% longer than at the real full
                           load Watt rating. So this UPS which claimed to have 20 minutes of run time may only provide
                           12 minutes of run time at the true full load Watt rating. To overcome this confusion, always
                           make sure run time specifications are based on Watt loads, and not VA loads.

                           Manufacturers of smaller desktop UPS often only include VA specifications for their UPS
                           products. When the Watt rating of a UPS is not furnished, it can be very difficult to determine
                           if the UPS is capable of supplying a specific load. Lower cost UPS products often have a
                           Watt rating of 50% of the nameplate VA rating. This can cause confusion, for example a
                           1000 VA UPS that will not run a 600 W load (the Watt load rating is either not provided or in
                           the fine print and in reality is only 500 W).
      Link to resource
                           In addition to their contribution to power factor, harmonics have other implications in power
      APC White Paper 26
                           system design. These are discussed in detail in APC White Paper 26, Hazards of Harmonics
Hazards of Harmonics and   and Neutral Overloads.
Neutral Overloads



Crest factor               In addition to a low power factor, some computer loads are also unusual in that they exhibit a
                           very high crest factor. Crest factor is the ratio between the instantaneous peak current
                           required by the load and the RMS current (RMS stands for Root Mean Square, which is a
                           type of average). Most common electrical appliances exhibit a crest factor of 1.4 (1.4 is the
                           ratio of the peak value of a sine wave to its RMS value). Computers and IT equipment with
                           Power Factor Corrected power supplies exhibit a crest factor of 1.4. Personal computers and
                           stackable hubs exhibit a crest factor of 2 to 3.

                           When a load exhibits a crest factor of more than 1.4, the source (UPS) must supply the peak
                           current desired by the load. If the source does not supply the current, then the source
                           voltage will become deformed (distorted) by the excess peak current. Therefore, if a UPS is
                           not sized to supply the crest factor desired by the load, the output voltage waveform of the
                           UPS will be distorted.

                           The crest factor requirement of a computer load will vary depending on the source which it is
                           supplied from. The crest factor may even vary when the computer load is moved from one
                           AC receptacle to another in the same room. It is widely believed that the crest factor is an
                           inherent characteristic of a computer load, when in fact crest factor results from an interaction
                           between the load and the AC source. The crest factor required by a computer load depends
                           on the AC source waveform. For a sine wave source, a non-power factor corrected personal
                           computer will typically exhibit a crest factor of 2 to 3. For a source waveform which is a
                           stepped approximation to a sine wave, as used in most UPS below 1 kW, a computer will
                           exhibit a crest factor of 1.4 to 1.9.

                           It is widely but mistakenly believed that it is desirable to operate a computer at as high a crest
                           factor as possible. In fact, computer manufacturers go to great lengths to reduce the crest
                           factor of the computer because high crest factor causes overheating of power supply
                           components.

                           The reduction in crest factor which occurs when a computer load is operated from a UPS,
                           surge suppressor, or power conditioner is a positive side benefit, except if the reduction is
                           accompanied by excessive distortion of the input voltage waveform to the computer load.
                           Such distortion may result in a significantly reduced peak voltage being supplied to the load,
                           which is equivalent to a brownout condition. The UPS or line conditioner must be designed to
                           maintain the proper peak voltage.

                           Typical sine wave UPS systems such as the APC by Schneider Electric Symmetra or Smart-
                           UPS models have a crest factor capability of approximately 3 when operated at full load, 4


                           APC by Schneider Electric                                          White Paper 17    Rev 1   3
Understanding Power Factor, Crest Factor, and Surge Factor


               when operated at 1/2 load, and 8 when operated at 1/4 load. Typical smaller stepped wave
               models such as the APC Back-UPS have a crest factor capability of 1.6 at full load and 2 at
               1/2 load. UPS systems with this performance will maintain the proper peak voltage into the
               computer load for computers with any input crest factor specification.

               Lower quality UPS systems on the market have limited peak output current capability and
               consequently low crest factor performance and will distort the output voltage under personal
               computer loads. Typically this does not cause a malfunction with smaller PC installations.
               However in large multi-PC installations such as call centers can cause significant degradation
               of the UPS output waveform. In these cases it is not uncommon to see a UPS output
               waveform that is nearly a square-wave. This situation can cause various types of office
               machines to malfunction.

               The fact that virtually all equipment installed in data centers today such as servers, routers,
               and storage devices are power factor corrected has virtually eliminated crest factor as a
               problem in the data center. Crest factor problems today are limited to call center or trading
               floor installations with a high density of personal computers.




Surge factor   This term is often mistakenly related to the surge suppression characteristic of a UPS or
               surge suppressor, which is a different and unrelated characteristic. Surge factor relates to
               the momentary overload capacity of the UPS and is a measure of the ability of the UPS to
               start-up loads which temporarily require extra power when they start-up. Examples of loads
               which have a high surge factor requirement include motors, compressors, and to a lesser
               extent disk drives.

               For typical computer systems with hard disk drives, the surge factor required is approximately
               1.15 times the steady-state power consumption. For large disk arrays, the surge factor
               required can be approximately 1.5 times the steady-state power consumption.




               APC by Schneider Electric                                         White Paper 17    Rev 1    4
Understanding Power Factor, Crest Factor, and Surge Factor




Conclusion   Most UPS systems today have sufficient crest factor and surge factor to meet virtually any
             requirement in a data room or data center. Therefore, their use in bid specifications is
             relatively unimportant.

             Power factor remains a misunderstood subject, and ignoring or misapplying the power factor
             concepts can result in a number of problems, including: overestimation of UPS run time;
             incorrect comparison of run time between competitive products, and under sizing of UPS
             systems. The guidelines and warnings regarding power factor that are summarized in this
             paper can prevent these misunderstandings.




                       About the author
                  Neil Rasmussen is the Senior VP of Innovation for APC, which is the IT Business Unit of
                  Schneider Electric. He establishes the technology direction for the world’s largest R&D budget
                  devoted to power, cooling, and rack infrastructure for critical networks.

                  Neil holds 14 patents related to high efficiency and high density data center power and cooling
                  infrastructure, and has published over 50 white papers related to power and cooling systems,
                  many published in more than 10 languages, most recently with a focus on the improvement of
                  energy efficiency. He is an internationally recognized keynote speaker on the subject of high
                  efficiency data centers. Neil is currently working to advance the science of high-efficiency,
                  high-density, scalable data center infrastructure solutions and is a principal architect of the APC
                  InfraStruXure system.

                  Prior to founding APC in 1981, Neil received his bachelors and masters degrees from MIT in
                  electrical engineering, where he did his thesis on the analysis of a 200MW power supply for a
                  tokamak fusion reactor. From 1979 to 1981 he worked at MIT Lincoln Laboratories on flywheel
                  energy storage systems and solar electric power systems.




             APC by Schneider Electric                                                White Paper 17      Rev 1    5
Understanding Power Factor, Crest Factor, and Surge Factor




Resources
Click on icon to link to resource



                                        Hazards of Harmonics and Neutral Overloads
                                        APC White Paper 26




                                        APC White Paper Library
                                        whitepapers.apc.com




                                        APC TradeOff Tools™
                                        tools.apc.com




                                             Contact us
                                       For feedback and comments about the content of this white paper:

                                           Data Center Science Center, APC by Schneider Electric
                                           DCSC@Schneider-Electric.com

                                       If you are a customer and have questions specific to your data center project:

                                             Contact your APC by Schneider Electric representative




                                    APC by Schneider Electric                                   White Paper 17   Rev 1   6

Contenu connexe

Dernier

Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...
Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...
Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...amitlee9823
 
Dr. Admir Softic_ presentation_Green Club_ENG.pdf
Dr. Admir Softic_ presentation_Green Club_ENG.pdfDr. Admir Softic_ presentation_Green Club_ENG.pdf
Dr. Admir Softic_ presentation_Green Club_ENG.pdfAdmir Softic
 
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...amitlee9823
 
RSA Conference Exhibitor List 2024 - Exhibitors Data
RSA Conference Exhibitor List 2024 - Exhibitors DataRSA Conference Exhibitor List 2024 - Exhibitors Data
RSA Conference Exhibitor List 2024 - Exhibitors DataExhibitors Data
 
Call Girls In Panjim North Goa 9971646499 Genuine Service
Call Girls In Panjim North Goa 9971646499 Genuine ServiceCall Girls In Panjim North Goa 9971646499 Genuine Service
Call Girls In Panjim North Goa 9971646499 Genuine Serviceritikaroy0888
 
KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...
KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...
KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...Any kyc Account
 
John Halpern sued for sexual assault.pdf
John Halpern sued for sexual assault.pdfJohn Halpern sued for sexual assault.pdf
John Halpern sued for sexual assault.pdfAmzadHosen3
 
Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...
Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...
Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...Dipal Arora
 
👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...
👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...
👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...rajveerescorts2022
 
Value Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and painsValue Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and painsP&CO
 
Pharma Works Profile of Karan Communications
Pharma Works Profile of Karan CommunicationsPharma Works Profile of Karan Communications
Pharma Works Profile of Karan Communicationskarancommunications
 
Cracking the Cultural Competence Code.pptx
Cracking the Cultural Competence Code.pptxCracking the Cultural Competence Code.pptx
Cracking the Cultural Competence Code.pptxWorkforce Group
 
How to Get Started in Social Media for Art League City
How to Get Started in Social Media for Art League CityHow to Get Started in Social Media for Art League City
How to Get Started in Social Media for Art League CityEric T. Tung
 
VIP Call Girls In Saharaganj ( Lucknow ) 🔝 8923113531 🔝 Cash Payment (COD) 👒
VIP Call Girls In Saharaganj ( Lucknow  ) 🔝 8923113531 🔝  Cash Payment (COD) 👒VIP Call Girls In Saharaganj ( Lucknow  ) 🔝 8923113531 🔝  Cash Payment (COD) 👒
VIP Call Girls In Saharaganj ( Lucknow ) 🔝 8923113531 🔝 Cash Payment (COD) 👒anilsa9823
 
Yaroslav Rozhankivskyy: Три складові і три передумови максимальної продуктивн...
Yaroslav Rozhankivskyy: Три складові і три передумови максимальної продуктивн...Yaroslav Rozhankivskyy: Три складові і три передумови максимальної продуктивн...
Yaroslav Rozhankivskyy: Три складові і три передумови максимальної продуктивн...Lviv Startup Club
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756dollysharma2066
 
Mondelez State of Snacking and Future Trends 2023
Mondelez State of Snacking and Future Trends 2023Mondelez State of Snacking and Future Trends 2023
Mondelez State of Snacking and Future Trends 2023Neil Kimberley
 
Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...
Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...
Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...lizamodels9
 
Call Girls in Gomti Nagar - 7388211116 - With room Service
Call Girls in Gomti Nagar - 7388211116  - With room ServiceCall Girls in Gomti Nagar - 7388211116  - With room Service
Call Girls in Gomti Nagar - 7388211116 - With room Servicediscovermytutordmt
 

Dernier (20)

Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...
Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...
Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...
 
Dr. Admir Softic_ presentation_Green Club_ENG.pdf
Dr. Admir Softic_ presentation_Green Club_ENG.pdfDr. Admir Softic_ presentation_Green Club_ENG.pdf
Dr. Admir Softic_ presentation_Green Club_ENG.pdf
 
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
 
RSA Conference Exhibitor List 2024 - Exhibitors Data
RSA Conference Exhibitor List 2024 - Exhibitors DataRSA Conference Exhibitor List 2024 - Exhibitors Data
RSA Conference Exhibitor List 2024 - Exhibitors Data
 
Call Girls In Panjim North Goa 9971646499 Genuine Service
Call Girls In Panjim North Goa 9971646499 Genuine ServiceCall Girls In Panjim North Goa 9971646499 Genuine Service
Call Girls In Panjim North Goa 9971646499 Genuine Service
 
KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...
KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...
KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...
 
John Halpern sued for sexual assault.pdf
John Halpern sued for sexual assault.pdfJohn Halpern sued for sexual assault.pdf
John Halpern sued for sexual assault.pdf
 
Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...
Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...
Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...
 
👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...
👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...
👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...
 
Value Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and painsValue Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and pains
 
Pharma Works Profile of Karan Communications
Pharma Works Profile of Karan CommunicationsPharma Works Profile of Karan Communications
Pharma Works Profile of Karan Communications
 
Cracking the Cultural Competence Code.pptx
Cracking the Cultural Competence Code.pptxCracking the Cultural Competence Code.pptx
Cracking the Cultural Competence Code.pptx
 
How to Get Started in Social Media for Art League City
How to Get Started in Social Media for Art League CityHow to Get Started in Social Media for Art League City
How to Get Started in Social Media for Art League City
 
VIP Call Girls In Saharaganj ( Lucknow ) 🔝 8923113531 🔝 Cash Payment (COD) 👒
VIP Call Girls In Saharaganj ( Lucknow  ) 🔝 8923113531 🔝  Cash Payment (COD) 👒VIP Call Girls In Saharaganj ( Lucknow  ) 🔝 8923113531 🔝  Cash Payment (COD) 👒
VIP Call Girls In Saharaganj ( Lucknow ) 🔝 8923113531 🔝 Cash Payment (COD) 👒
 
Yaroslav Rozhankivskyy: Три складові і три передумови максимальної продуктивн...
Yaroslav Rozhankivskyy: Три складові і три передумови максимальної продуктивн...Yaroslav Rozhankivskyy: Три складові і три передумови максимальної продуктивн...
Yaroslav Rozhankivskyy: Три складові і три передумови максимальної продуктивн...
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
 
VVVIP Call Girls In Greater Kailash ➡️ Delhi ➡️ 9999965857 🚀 No Advance 24HRS...
VVVIP Call Girls In Greater Kailash ➡️ Delhi ➡️ 9999965857 🚀 No Advance 24HRS...VVVIP Call Girls In Greater Kailash ➡️ Delhi ➡️ 9999965857 🚀 No Advance 24HRS...
VVVIP Call Girls In Greater Kailash ➡️ Delhi ➡️ 9999965857 🚀 No Advance 24HRS...
 
Mondelez State of Snacking and Future Trends 2023
Mondelez State of Snacking and Future Trends 2023Mondelez State of Snacking and Future Trends 2023
Mondelez State of Snacking and Future Trends 2023
 
Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...
Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...
Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...
 
Call Girls in Gomti Nagar - 7388211116 - With room Service
Call Girls in Gomti Nagar - 7388211116  - With room ServiceCall Girls in Gomti Nagar - 7388211116  - With room Service
Call Girls in Gomti Nagar - 7388211116 - With room Service
 

En vedette

2024 State of Marketing Report – by Hubspot
2024 State of Marketing Report – by Hubspot2024 State of Marketing Report – by Hubspot
2024 State of Marketing Report – by HubspotMarius Sescu
 
Everything You Need To Know About ChatGPT
Everything You Need To Know About ChatGPTEverything You Need To Know About ChatGPT
Everything You Need To Know About ChatGPTExpeed Software
 
Product Design Trends in 2024 | Teenage Engineerings
Product Design Trends in 2024 | Teenage EngineeringsProduct Design Trends in 2024 | Teenage Engineerings
Product Design Trends in 2024 | Teenage EngineeringsPixeldarts
 
How Race, Age and Gender Shape Attitudes Towards Mental Health
How Race, Age and Gender Shape Attitudes Towards Mental HealthHow Race, Age and Gender Shape Attitudes Towards Mental Health
How Race, Age and Gender Shape Attitudes Towards Mental HealthThinkNow
 
AI Trends in Creative Operations 2024 by Artwork Flow.pdf
AI Trends in Creative Operations 2024 by Artwork Flow.pdfAI Trends in Creative Operations 2024 by Artwork Flow.pdf
AI Trends in Creative Operations 2024 by Artwork Flow.pdfmarketingartwork
 
PEPSICO Presentation to CAGNY Conference Feb 2024
PEPSICO Presentation to CAGNY Conference Feb 2024PEPSICO Presentation to CAGNY Conference Feb 2024
PEPSICO Presentation to CAGNY Conference Feb 2024Neil Kimberley
 
Content Methodology: A Best Practices Report (Webinar)
Content Methodology: A Best Practices Report (Webinar)Content Methodology: A Best Practices Report (Webinar)
Content Methodology: A Best Practices Report (Webinar)contently
 
How to Prepare For a Successful Job Search for 2024
How to Prepare For a Successful Job Search for 2024How to Prepare For a Successful Job Search for 2024
How to Prepare For a Successful Job Search for 2024Albert Qian
 
Social Media Marketing Trends 2024 // The Global Indie Insights
Social Media Marketing Trends 2024 // The Global Indie InsightsSocial Media Marketing Trends 2024 // The Global Indie Insights
Social Media Marketing Trends 2024 // The Global Indie InsightsKurio // The Social Media Age(ncy)
 
Trends In Paid Search: Navigating The Digital Landscape In 2024
Trends In Paid Search: Navigating The Digital Landscape In 2024Trends In Paid Search: Navigating The Digital Landscape In 2024
Trends In Paid Search: Navigating The Digital Landscape In 2024Search Engine Journal
 
5 Public speaking tips from TED - Visualized summary
5 Public speaking tips from TED - Visualized summary5 Public speaking tips from TED - Visualized summary
5 Public speaking tips from TED - Visualized summarySpeakerHub
 
ChatGPT and the Future of Work - Clark Boyd
ChatGPT and the Future of Work - Clark Boyd ChatGPT and the Future of Work - Clark Boyd
ChatGPT and the Future of Work - Clark Boyd Clark Boyd
 
Getting into the tech field. what next
Getting into the tech field. what next Getting into the tech field. what next
Getting into the tech field. what next Tessa Mero
 
Google's Just Not That Into You: Understanding Core Updates & Search Intent
Google's Just Not That Into You: Understanding Core Updates & Search IntentGoogle's Just Not That Into You: Understanding Core Updates & Search Intent
Google's Just Not That Into You: Understanding Core Updates & Search IntentLily Ray
 
Time Management & Productivity - Best Practices
Time Management & Productivity -  Best PracticesTime Management & Productivity -  Best Practices
Time Management & Productivity - Best PracticesVit Horky
 
The six step guide to practical project management
The six step guide to practical project managementThe six step guide to practical project management
The six step guide to practical project managementMindGenius
 
Beginners Guide to TikTok for Search - Rachel Pearson - We are Tilt __ Bright...
Beginners Guide to TikTok for Search - Rachel Pearson - We are Tilt __ Bright...Beginners Guide to TikTok for Search - Rachel Pearson - We are Tilt __ Bright...
Beginners Guide to TikTok for Search - Rachel Pearson - We are Tilt __ Bright...RachelPearson36
 

En vedette (20)

2024 State of Marketing Report – by Hubspot
2024 State of Marketing Report – by Hubspot2024 State of Marketing Report – by Hubspot
2024 State of Marketing Report – by Hubspot
 
Everything You Need To Know About ChatGPT
Everything You Need To Know About ChatGPTEverything You Need To Know About ChatGPT
Everything You Need To Know About ChatGPT
 
Product Design Trends in 2024 | Teenage Engineerings
Product Design Trends in 2024 | Teenage EngineeringsProduct Design Trends in 2024 | Teenage Engineerings
Product Design Trends in 2024 | Teenage Engineerings
 
How Race, Age and Gender Shape Attitudes Towards Mental Health
How Race, Age and Gender Shape Attitudes Towards Mental HealthHow Race, Age and Gender Shape Attitudes Towards Mental Health
How Race, Age and Gender Shape Attitudes Towards Mental Health
 
AI Trends in Creative Operations 2024 by Artwork Flow.pdf
AI Trends in Creative Operations 2024 by Artwork Flow.pdfAI Trends in Creative Operations 2024 by Artwork Flow.pdf
AI Trends in Creative Operations 2024 by Artwork Flow.pdf
 
Skeleton Culture Code
Skeleton Culture CodeSkeleton Culture Code
Skeleton Culture Code
 
PEPSICO Presentation to CAGNY Conference Feb 2024
PEPSICO Presentation to CAGNY Conference Feb 2024PEPSICO Presentation to CAGNY Conference Feb 2024
PEPSICO Presentation to CAGNY Conference Feb 2024
 
Content Methodology: A Best Practices Report (Webinar)
Content Methodology: A Best Practices Report (Webinar)Content Methodology: A Best Practices Report (Webinar)
Content Methodology: A Best Practices Report (Webinar)
 
How to Prepare For a Successful Job Search for 2024
How to Prepare For a Successful Job Search for 2024How to Prepare For a Successful Job Search for 2024
How to Prepare For a Successful Job Search for 2024
 
Social Media Marketing Trends 2024 // The Global Indie Insights
Social Media Marketing Trends 2024 // The Global Indie InsightsSocial Media Marketing Trends 2024 // The Global Indie Insights
Social Media Marketing Trends 2024 // The Global Indie Insights
 
Trends In Paid Search: Navigating The Digital Landscape In 2024
Trends In Paid Search: Navigating The Digital Landscape In 2024Trends In Paid Search: Navigating The Digital Landscape In 2024
Trends In Paid Search: Navigating The Digital Landscape In 2024
 
5 Public speaking tips from TED - Visualized summary
5 Public speaking tips from TED - Visualized summary5 Public speaking tips from TED - Visualized summary
5 Public speaking tips from TED - Visualized summary
 
ChatGPT and the Future of Work - Clark Boyd
ChatGPT and the Future of Work - Clark Boyd ChatGPT and the Future of Work - Clark Boyd
ChatGPT and the Future of Work - Clark Boyd
 
Getting into the tech field. what next
Getting into the tech field. what next Getting into the tech field. what next
Getting into the tech field. what next
 
Google's Just Not That Into You: Understanding Core Updates & Search Intent
Google's Just Not That Into You: Understanding Core Updates & Search IntentGoogle's Just Not That Into You: Understanding Core Updates & Search Intent
Google's Just Not That Into You: Understanding Core Updates & Search Intent
 
How to have difficult conversations
How to have difficult conversations How to have difficult conversations
How to have difficult conversations
 
Introduction to Data Science
Introduction to Data ScienceIntroduction to Data Science
Introduction to Data Science
 
Time Management & Productivity - Best Practices
Time Management & Productivity -  Best PracticesTime Management & Productivity -  Best Practices
Time Management & Productivity - Best Practices
 
The six step guide to practical project management
The six step guide to practical project managementThe six step guide to practical project management
The six step guide to practical project management
 
Beginners Guide to TikTok for Search - Rachel Pearson - We are Tilt __ Bright...
Beginners Guide to TikTok for Search - Rachel Pearson - We are Tilt __ Bright...Beginners Guide to TikTok for Search - Rachel Pearson - We are Tilt __ Bright...
Beginners Guide to TikTok for Search - Rachel Pearson - We are Tilt __ Bright...
 

WP17 UPS and Surge Terms

  • 1. Understanding Power Factor, Crest Factor, and Surge Factor White Paper 17 Revision 1 by Neil Rasmussen Contents > Executive summary Click on a section to jump to it Introduction 2 This white paper explains the technical terms of power factor, crest factor, and surge factor. The use of these Power factor 2 terms in specifying UPS is explained. Crest factor 3 Surge factor 4 Conclusion 5 Resources 6
  • 2. Understanding Power Factor, Crest Factor, and Surge Factor Introduction The terms power factor, crest factor, and surge factor refer to completely different and unrelated phenomena. These characteristics are often specified for UPS systems, and customers will sometimes place them in specifications. Power factor Power factor is a quantity which has important implications when sizing a UPS system and power distribution equipment. Power is a measure of the delivery rate of energy and in DC (direct current) electrical circuits is expressed as the mathematical product of Volts and Amps (Power = Volts x Amps). However, in AC (alternating current) power system, a complication is introduced; namely that some AC current (Amps) may flow into and back out of the load without delivering energy. This current, called reactive or harmonic current, gives rise to an “apparent” power (Volt x Amps) which is larger than the actual power consumed. This difference between the apparent power and the actual power gives rise to the power factor. The power factor is equal to the ratio of the actual power to the apparent power. The apparent power is expressed as the Volt-Amp or VA rating. Therefore, the actual power in any AC system is the VA rating multiplied by the power factor. For many types of electrical equipment the difference between apparent power (VA) and actual power (Watts) is very slight and can be ignored, but for some computers the difference is very large and important. Many desktop personal computers present a nonlinear load to the AC supply. This is because they have a power supply design known as a "capacitor input switch mode power supply". In a study done by PC Magazine, it was found that typical personal computer systems exhibit a power factor of .65 which means that the apparent power (VA) was 50% larger than the actual power (Watts)! Information technology (IT) equipment including servers, routers, hubs, and storage systems almost universally use a different power supply design known as "Power Factor Corrected". These devices present a very linear load to the AC supply and do not generate harmonic currents. In fact they are one of the cleanest loads on the power grid and generate less harmonic current than many other devices such as fluorescent lighting or variable speed motors. Ten years ago, these devices were nonlinear loads like personal computers, but today all of these loads are subject to international regulation IEC 1000-3-2 which require them to be made with the "Power Factor Corrected" design. Sizing a UPS To size a UPS and ensure that the UPS output capacity is sufficient, both the VA rating and the Watt rating of the load are important. The watt rating of the UPS relates to the amount of power it can deliver, and the VA rating of the UPS relates to the amount of current it can deliver. Neither the Watt nor the VA rating of the UPS can be exceeded. In practice, the best approach is to size a UPS the Watt rating of the load. This is particularly true for larger IT installations where the power factors of the loads are nearly 1. If there is confusion regarding power ratings or power factor, and it is desirable to ensure the load can be powered by the UPS, then choosing a UPS with a Watt rating greater than or equal to the VA rating of the load will always ensure a safety margin. Power factor has an important implication in the specification of UPS run time on battery. Battery run time is dictated by the watt load on the UPS. However, when many UPS manu- facturers specify run time at full load they are referring to full VA load, not the full watt load. For example, a UPS rated at 10,000 VA may be rated for 20 minutes of run time at full load. In the fine print it notes that this full load is at a .65 power factor. Therefore the load for the run time specification is really only 6500 Watts. The same UPS may have a 9000 W rating. APC by Schneider Electric White Paper 17 Rev 1 2
  • 3. Understanding Power Factor, Crest Factor, and Surge Factor This means that the run time was provided at 6500/9000 or 72% of the full load watt rating of the UPS. At 72% of the Watt rating the UPS may run almost 70% longer than at the real full load Watt rating. So this UPS which claimed to have 20 minutes of run time may only provide 12 minutes of run time at the true full load Watt rating. To overcome this confusion, always make sure run time specifications are based on Watt loads, and not VA loads. Manufacturers of smaller desktop UPS often only include VA specifications for their UPS products. When the Watt rating of a UPS is not furnished, it can be very difficult to determine if the UPS is capable of supplying a specific load. Lower cost UPS products often have a Watt rating of 50% of the nameplate VA rating. This can cause confusion, for example a 1000 VA UPS that will not run a 600 W load (the Watt load rating is either not provided or in the fine print and in reality is only 500 W). Link to resource In addition to their contribution to power factor, harmonics have other implications in power APC White Paper 26 system design. These are discussed in detail in APC White Paper 26, Hazards of Harmonics Hazards of Harmonics and and Neutral Overloads. Neutral Overloads Crest factor In addition to a low power factor, some computer loads are also unusual in that they exhibit a very high crest factor. Crest factor is the ratio between the instantaneous peak current required by the load and the RMS current (RMS stands for Root Mean Square, which is a type of average). Most common electrical appliances exhibit a crest factor of 1.4 (1.4 is the ratio of the peak value of a sine wave to its RMS value). Computers and IT equipment with Power Factor Corrected power supplies exhibit a crest factor of 1.4. Personal computers and stackable hubs exhibit a crest factor of 2 to 3. When a load exhibits a crest factor of more than 1.4, the source (UPS) must supply the peak current desired by the load. If the source does not supply the current, then the source voltage will become deformed (distorted) by the excess peak current. Therefore, if a UPS is not sized to supply the crest factor desired by the load, the output voltage waveform of the UPS will be distorted. The crest factor requirement of a computer load will vary depending on the source which it is supplied from. The crest factor may even vary when the computer load is moved from one AC receptacle to another in the same room. It is widely believed that the crest factor is an inherent characteristic of a computer load, when in fact crest factor results from an interaction between the load and the AC source. The crest factor required by a computer load depends on the AC source waveform. For a sine wave source, a non-power factor corrected personal computer will typically exhibit a crest factor of 2 to 3. For a source waveform which is a stepped approximation to a sine wave, as used in most UPS below 1 kW, a computer will exhibit a crest factor of 1.4 to 1.9. It is widely but mistakenly believed that it is desirable to operate a computer at as high a crest factor as possible. In fact, computer manufacturers go to great lengths to reduce the crest factor of the computer because high crest factor causes overheating of power supply components. The reduction in crest factor which occurs when a computer load is operated from a UPS, surge suppressor, or power conditioner is a positive side benefit, except if the reduction is accompanied by excessive distortion of the input voltage waveform to the computer load. Such distortion may result in a significantly reduced peak voltage being supplied to the load, which is equivalent to a brownout condition. The UPS or line conditioner must be designed to maintain the proper peak voltage. Typical sine wave UPS systems such as the APC by Schneider Electric Symmetra or Smart- UPS models have a crest factor capability of approximately 3 when operated at full load, 4 APC by Schneider Electric White Paper 17 Rev 1 3
  • 4. Understanding Power Factor, Crest Factor, and Surge Factor when operated at 1/2 load, and 8 when operated at 1/4 load. Typical smaller stepped wave models such as the APC Back-UPS have a crest factor capability of 1.6 at full load and 2 at 1/2 load. UPS systems with this performance will maintain the proper peak voltage into the computer load for computers with any input crest factor specification. Lower quality UPS systems on the market have limited peak output current capability and consequently low crest factor performance and will distort the output voltage under personal computer loads. Typically this does not cause a malfunction with smaller PC installations. However in large multi-PC installations such as call centers can cause significant degradation of the UPS output waveform. In these cases it is not uncommon to see a UPS output waveform that is nearly a square-wave. This situation can cause various types of office machines to malfunction. The fact that virtually all equipment installed in data centers today such as servers, routers, and storage devices are power factor corrected has virtually eliminated crest factor as a problem in the data center. Crest factor problems today are limited to call center or trading floor installations with a high density of personal computers. Surge factor This term is often mistakenly related to the surge suppression characteristic of a UPS or surge suppressor, which is a different and unrelated characteristic. Surge factor relates to the momentary overload capacity of the UPS and is a measure of the ability of the UPS to start-up loads which temporarily require extra power when they start-up. Examples of loads which have a high surge factor requirement include motors, compressors, and to a lesser extent disk drives. For typical computer systems with hard disk drives, the surge factor required is approximately 1.15 times the steady-state power consumption. For large disk arrays, the surge factor required can be approximately 1.5 times the steady-state power consumption. APC by Schneider Electric White Paper 17 Rev 1 4
  • 5. Understanding Power Factor, Crest Factor, and Surge Factor Conclusion Most UPS systems today have sufficient crest factor and surge factor to meet virtually any requirement in a data room or data center. Therefore, their use in bid specifications is relatively unimportant. Power factor remains a misunderstood subject, and ignoring or misapplying the power factor concepts can result in a number of problems, including: overestimation of UPS run time; incorrect comparison of run time between competitive products, and under sizing of UPS systems. The guidelines and warnings regarding power factor that are summarized in this paper can prevent these misunderstandings. About the author Neil Rasmussen is the Senior VP of Innovation for APC, which is the IT Business Unit of Schneider Electric. He establishes the technology direction for the world’s largest R&D budget devoted to power, cooling, and rack infrastructure for critical networks. Neil holds 14 patents related to high efficiency and high density data center power and cooling infrastructure, and has published over 50 white papers related to power and cooling systems, many published in more than 10 languages, most recently with a focus on the improvement of energy efficiency. He is an internationally recognized keynote speaker on the subject of high efficiency data centers. Neil is currently working to advance the science of high-efficiency, high-density, scalable data center infrastructure solutions and is a principal architect of the APC InfraStruXure system. Prior to founding APC in 1981, Neil received his bachelors and masters degrees from MIT in electrical engineering, where he did his thesis on the analysis of a 200MW power supply for a tokamak fusion reactor. From 1979 to 1981 he worked at MIT Lincoln Laboratories on flywheel energy storage systems and solar electric power systems. APC by Schneider Electric White Paper 17 Rev 1 5
  • 6. Understanding Power Factor, Crest Factor, and Surge Factor Resources Click on icon to link to resource Hazards of Harmonics and Neutral Overloads APC White Paper 26 APC White Paper Library whitepapers.apc.com APC TradeOff Tools™ tools.apc.com Contact us For feedback and comments about the content of this white paper: Data Center Science Center, APC by Schneider Electric DCSC@Schneider-Electric.com If you are a customer and have questions specific to your data center project: Contact your APC by Schneider Electric representative APC by Schneider Electric White Paper 17 Rev 1 6