Arc Flash Protection and Mitigation




           Tim Cotter, P.E.
            Staff Engineer
Schneider Electric Engineering Services
A Quick Look Back…


“I introduced into my ears two metal rods with rounded
   ends and joined them to the terminals of the
   apparatus.

  At the moment the circuit was completed, I received
  a shock in the head – and began to hear a noise – a
  crackling and boiling.

  This disagreeable sensation, which I feared might be
  dangerous, has deterred me so that I have not
  repeated the experiment.”
We’ve come a long way…


“I introduced into my ears two metal rods with
rounded ends and joined them to the terminals of
the apparatus.
 
  At the moment the circuit was completed, I
received a shock in the head – and began to hear a
noise – a crackling and boiling.
 
This disagreeable sensation, which I feared might
be dangerous, has deterred me so that I have not
repeated the experiment.”


-Alessandro Volta, inventor of the first electric
battery, 1745-1827
even from … more recent times.




 154. Electricians often test circuits for the presence
  of voltage by touching the conductors with the
  fingers. This method is safe where the voltage does
  not exceed 250 and is often very convenient for
  locating a blown-out fuse or for ascertaining whether
  or not a circuit is alive. Some men can endure the
  electric shock that results without discomfort
  whereas others cannot. Therefore, the method is not
  feasible in some cases.

      AMERICAN ELECTRICIANS’ HANDBOOK
      7th Edition 1953   McGraw-Hill
But where are we now?


 NIOSH Study covering 1980-1995:
    93,338 total work-related fatalities in the US
    Approximately 1 in 15 were related to electrical hazards (> 1 fatality/
     day in the US)
    #5 hazard overall
      Auto accidents were #1
 More recent data – # of deaths down, but proportion
  that is related to electrical work is about the same!
 Lots of work still to do!
Electric Arcs & Arc Flash




 Passage of substantial electric current through air
 “Short-circuit in air”
 May simply flow through ionized air
 May flow through vapor of arc-terminal material
    Copper, Carbon, etc.
 Not necessarily harmful
    Arc welding, “static electricity”
 Arc Flash Hazard: A dangerous condition associated with the
  possible release of energy caused by an electric arc. (NPFA
  70E definition)
Severity of Arc Flash



Depends on several factors, including:
   Magnitude of fault current
   System voltage
   Duration of arcing fault
   Proximity of worker to arc source

Complex issue!
Typical power distribution system – levels may
 be severe enough to cause serious injury or
 death
Measurements taken from
                          atop the ladder




Note melting of steel &
copper
Relevant Codes & Standards


National Electrical Code NFPA 70 (2011 ed.)
OSHA
NFPA 70E (2012 ed.), Standard for Electrical
 Safety In the Workplace
IEEE 1584-2002
National Electrical Code – NFPA 70


 Best known of all electrical standards?
 Dates back to 1897
 In general, does not address work practices
 Still, starting in 2002, some reference to Arc Flash

   NEC 110.16. Flash Protection. Electrical equipment, such as
   switchboards, panelboards, industrial control panels, meter socket
   enclosures, and motor control centers, that are in other than dwelling
   occupancies, and are likely to require examination, adjustment, servicing,
   or maintenance while energized shall be field marked to warn qualified
   persons of potential electric arc flash hazards. The marking shall be
   located so as to be clearly visible to qualified persons before
   examination, adjustment, servicing, or maintenance of the equipment.
NEC & Arc Flash



 Requires equipment to be labeled, but does not
  specify a label format
   We’ll discuss labeling in more detail later
 An NEC-compliant system does not necessarily do a
  thing to reduce, eliminate, or manage arc flash
  hazards
OSHA



 Occupational Safety and Health Administration
 Created by Occupational Safety and Health Act of
  1970
 Mission: “To save lives, prevent injuries, and protect
  the health of America’s workers.”
 29.CFR 1910, Subpart S—deals with electrical
  systems
 “Law of the Land”!
 www.osha.gov
OSHA & Arc Flash


 OSHA requires use of Personal Protective
  Equipment (PPE)
 Does not prescribe nature of PPE required for
  various tasks
   NFPA 70E is referenced in an appendix of OSHA
    1910 Subpart S, but is not “incorporated by
    reference”
 Most serious injuries involve ignition of clothing
   Proper clothing must be selected based on
    industry standards or practices
   NFPA 70E: an industry consensus standard
OSHA General Duty Clause


 Each employer shall furnish to each of his employees
  employment and a place of employment which are free
  from recognized hazards that are causing or are likely to
  cause death or serious physical harm to his employees.
   [OSHA’s PPE requirements] are written in general terms, requiring, for example, that personal protective
    equipment be provided "where necessary by reason of hazards..." (§1910.132(a)), and requiring the employer to
    select equipment "that will protect the affected employee from the hazards...." (§1910.132(d)(1)). Also,
    §1910.132(c) requires the equipment to "be of safe design and construction for the work performed."

    Similarly, §1910.335 contains requirements such as the provision and use of "electrical protective equipment that
    is appropriate for the specific parts of the body to be protected and the work to be performed (§1910.335(a)(i)).

    Industry consensus standards, such as NFPA 70E, can be used by employers as guides to making the
    assessments and equipment selections required by the standard. Similarly, in OSHA enforcement actions,
    they can be used as evidence of whether the employer acted reasonably.




         From OSHA interpretation of the General Duty Clause, 7/25/2003
NFPA 70E


“Standard for Electrical Safety In the
 Workplace”
Current edition published in September, 2011
  Approx. 3-year revision cycle
  Revision process underway!
Latest edition: 2012
NFPA 70E: Key Provisions


 Article 90: Scope
 Facilities covered include public and private buildings,
  parking lots, carnivals, industrial substations, service-
  entrance equipment, and electric utility equipment that is
  NOT a generating station, substation, or control center
 Facilities NOT covered include ships or automobiles/trucks,
  underground installations in mines, “3rd rail”, communications
  equipment under the control of communications utilities, and
  remaining electric utility installations
 Basically the same as the NEC
NFPA 70E: Key Provisions


 Qualified Employees – ones allowed to do work
 Knowledgeable about a piece of equipment or specific work
  method
   70E defines specific items that should be known
 Can recognize and avoid electrical hazards (including arc
  flash)
 Is familiar with proper use of PPE, insulated tools, and
  insulating/shielding materials
 Not necessarily synonymous with:
   Master Electrician
   Professional Engineer
   CEO
NFPA 70E: Key Provisions


 “Live parts to which an employee might be exposed shall be
  put into an electrically safe work condition before an
  employee works on or near them, unless work on energized
  components can be justified according to 130.1”—110.8(A)(1)
 Basic protection strategy: de-energize the equipment!




   Excerpt from typical Square
   D instruction bulletin.
NFPA 70E: Key Provisions


Exceptions to the previous rule include the
 following: (130.1)
When de-energizing introduces additional or
 increased hazards
  Deactivation of emergency alarm systems
  Life support system
  Ventilation in hazardous area
When de-energizing is infeasible
  Performing diagnostics or testing that requires
   energized circuit
NFPA 70E: Key Provisions


 If parts not placed in an electrically safe condition, then work
  to be performed shall be considered energized electrical work
  and shall be performed by written permit only
 Decision-making taken out of workers’ hands and shifted to
  management
 Why a permit?
    Make you think twice before doing energized work
    Create a “Paper trail”
 This applies to the “exemptions”
    Management can’t just sign a permit and OK any
      energized work
Flash Hazard Analysis


 The analysis shall determine the flash protection
  boundary and the PPE that workers within this
  boundary should use
 Intended to protect personnel from the possibility of
  being injured by an arc flash
 How does one perform a flash hazard analysis?
   PPE Tables
   Calculations
   More on this later
Flash Protection Boundary


  Arc Flash Boundary (100):
  An approach limit at a distance
  from a prospective arc source
  within which a person could
  receive a second degree burn if
  an electric arc flash were to
  occur.
Flash Protection Boundary




             D
Dfb
How Much Energy is Too Much?


 It is generally accepted that an incident energy of 1.2 cal/cm2
  is sufficient to cause 2nd-degree burns on unprotected skin
    Tolerance may be higher for very short exposures
 Why cal/cm2?
 Just how hot is 1.2 cal/cm2???
 Typical incident energy ranges:
    0-200+ cal/cm2
 Equipment that has been placed in an electrically safe work
  condition: energy level = zero!!
Working Inside the FPB


 Employer shall determine and document the incident energy
  exposure of the worker (cal/cm2)
    Based on a working distance from source of arc to
     employee’s face and chest
 Use FR clothing and PPE appropriate for hazard level
    Use additional PPE for parts of the body closer than the
     distance at which the incident energy was determined
 (Alt.) Select PPE from tables
Equipment Labeling


 Now required in the 2012 edition of NFPA 70E
 130.5 (C) – Several options listed for identifying the arc
  flash hazard along with nominal voltage and arc flash
  boundary.
    Field marked – can’t determine at factory
    Minimal information actually required
    Most labels contain significantly more information
IEEE Standard 1584


 “IEEE Guide for Performing Arc-Flash Hazard
  Calculations”
 Incorporates results of extensive testing performed
  by several parties
 Provides method for calculating incident arc-flash
  energy
 Does not replace NEC or NFPA 70E—instead, it
  works with and alongside of them
 More on this when we talk about calculations
NFPA 70E PPE Requirements


PPE should:
   Cover all ignitable clothing (130.7(C)(2))
   Allow for movement and visibility (130.7(C)(2))
   Include head, face, neck, and chin protection
    (130.7(C)(3))
   Include eye protection (safety glasses)
    (130.7(C)(4))
   Include FR clothing for body (130.7(C)(6)) for
    all exposures over 1.2 cal/cm2
   Include hand and arm protection (130.7(C)(7))
   Include foot protection (130.7(C)(8))
   Conform to relevant ANSI and/or ASTM
    standards (130.7(C)(14))
Additional PPE Requirements


 Outer layers over FR clothing also must be FR
 Avoid tight-fitting clothes
 Choose PPE that poses minimal interference while
  still providing adequate protection
 Wear safety glasses under face shields/hoods
 Visor in flash suit should protect as well as the rest of
  the suit
 Non-FR synthetic fabrics not permitted*
Selection of PPE


 Based on Hazard/Risk Analysis
 NFPA 70E Tables
    List common work tasks for several types of equipment
    Each task assigned a HRC
    PPE defined for these HRCs
 Calculations
    Calculations define AFIE for a given location
    Select protective clothing that will protect against that AFIE
    Technically, HRCs don’t apply to calculated results, but in
     practice, most still correlate calculated AFIE levels to
     clothing systems listed in NFPA 70E Table 130.7.C.15
Protective Clothing Classes


                                                    Min Arc
                                                    Rating
Class                 Description                  (cal/cm2)
 0         Nonmelting, flammable materials           N/A

 1        FR shirt + FR pants or FR coverall          4

 2        FR shirt + FR pants or FR coverall          8

 3      (2) + additional PPE to reach 25 cal/cm2      25

 4      (2) + additional PPE to reach 40 cal/cm2      40




 Category 0 Clothing OK for up to 1.2 cal/cm2
H/R Category 0 (Non-FR)


Untreated, long-sleeve shirt
Untreated, long pants
Hearing protection
Safety Glasses

  Good for up to 1.2 cal/cm2




                        Photos courtesy of Oberon
H/R Category 1 (one FR layer)


 FR pants with ATPV of at least 4 cal/cm2
    No more untreated denim!
 FR long-sleeve shirt
 Optional FR coverall in lieu of FR shirt/pants
 FR jacket/parka/rainwear (as needed)
 Hard hat
 Safety Glasses
 Hearing protection
 Arc Rated Face Shield
 Leather gloves & leather work shoes (as needed)

             Good for up to 4.0 cal/cm2
H/R Category 2 (one FR layer + cotton)

                             FR long-sleeve shirt (minimum arc rating
                              of 8)
                             Pants: FR with min arc rating of 8
                             FR Coverall (Arc Rating 8 or more)
                              permissible in lieu of other FR clothing
                             FR jacket/parka/rainwear (as needed)
                             Hard Hat
                             Safety glasses or Safety Goggles
                             Leather gloves & leather work shoes
                             Hearing protection
                             Face Shield & Arc Rated Balaclava or Arc
                              Rated Hood
Photos courtesy of Oberon
                                Good for up to 8.0 cal/cm2
H/R Category 3 (two FR layers)


 Option 1:
    FR shirt/pants
    FR coverall
 Option 2:
    FR clothing system w/arc rating of 25
 FR jacket/parka/rainwear (as needed)
 Hard hat
 Safety glasses or safety goggles
 Double-layer switching hood           Photos courtesy of Oberon

 Hearing protection
 Arc rated gloves or rubber gloves w/leather
  protectors
                           Good for up to 25 cal/cm2
 Leather work shoes
H/R Category 4
    FR clothing with arc rating of 40
        Flash suit
        Shirt/pants/coverall combination providing
         equivalent protection
    FR jacket/parka/rainwear (as needed)
    Hard hat w/FR liner
    Safety glasses or safety goggles
    Double-layer switching hood
    Hearing protection
    Arc rated gloves or rubber insulating gloves
     w/leather protectors
    Leather work shoes
                                                      Photos courtesy of Oberon



Good for up to 40 cal/cm2
Beyond 40 cal/cm2…


 PPE vendors: 100 calorie suits
 NFPA 70E: defines no clothing class higher than 40 cal/cm2

    Does not explicitly prohibit work at such locations
    70E Handbook: appears to have backed off a
     statement in the earlier editions that allowing work
     at such locations was never the intent of 70E
 Other issues to consider

    Blast effects
    Equipment integrity
        Is PPE rated against shrapnel?
        No “ballistics rated” flash suit or face shield
    Hearing damage
Why is PPE Important?


 Has major impact on burn survival
  rates
    Major factor: total % of body burned
 Burn of 75% of body (easily
  possible if clothing ignites) results
  in:
    < 50% survival rate for males aged
     30-39
    < 20% survival rate for males aged
     50-59
 Rule of thumb: one day in hospital
  for each 1% of body burned                Photos courtesy of Oberon
Clothing Performance Benchmarks


Ease of ignition
Tendency to continue burning after heat
 source removed
Degree/ease of flame spread
Amount of heat transmitted
Tendency to melt
Strength—does arc flash tear it apart, or does
 it hold together?
Relative Performance – non-FR
                                           Clothing

 Natural fibers are fairly good, at least if they don’t ignite
    Cotton may continue to burn after heat removed
    Wool does not normally sustain a fire
 Non-FR Synthetics particularly bad either when alone or when
  blended w/cotton
    Easily ignited
    Melt
    Increase chance of infection
    Exception?
PPE Selection Principles


 Heavier fabrics provide more protection
 Multiple layers more effective than single layer of equivalent
  weight
 No non-FR synthetics next to skin
    “Performance underwear” may contain polyester or
     nylon/spandex blend—good for a ski trip, but bad for
     electrical work!!
Head and Face Protection


 Face shields provide some protection against molten splatter
 Non-FR face shields provide little or no protection against
  burns
 Tinted face shield with ATPV rating—better
 Protective shield inside FR hood—best
    Beware old FR hoods with non-FR shields!
 If visibility is a concern, provide lighting!
 Safety glasses always required
Arc Rating Values


 Based on testing
 Shown on equipment label
 Some PPE—no tests performed, so no official arc rating
  assigned
    Leather work gloves (unofficially 12 cal/cm2)
    Leather glove protectors
    Rubber insulating gloves
      Class 0 yellow gloves: limited testing indicated ignition
        10% of the time at 25 cal/cm2; 50% of the time at 31 cal/
        cm2
    Shoes (limited testing indicates resistance of 50-60
     cal/cm2)
PPE Innovations – Arc Hood Cooling
                          Systems
PPE Innovations – Improved Visibility




Warning: older clear faceshields may not be FR. In the
presence of a high energy arc, they can melt. The pressure
wave will tend to push the molten plastic into your face.
PPE “Gotchas”


 Not all FR rainwear is “arc resistant” – i.e., may have
  elements that can melt
 EVERYTHING needs to be arc resistant (or at least made out
  of something that won’t melt or burst into flame) during
  energized work
    Underwear
    Safety vests
    Hair nets
    Employee ID cards
    Logos / names sewn on to FR clothing
    Paper towels stuffed in hard hat to catch sweat
 Maintain the PPE
 Carefully observe laundering instructions
Use Your Head


 Use PPE correctly…no rolled-up sleeves or unzipped
  coveralls
 Body positioning when operating devices
   But: don’t make face shield an “arc scoop”
 No more workers than necessary in vicinity of
  energized work
 Remove yourself from the source when possible
   Hot stick
   Remote operations
Disclaimers


 NFPA 70E, 130.7.C.16, Informational Note #2:
   The PPE requirements of this section are intended to protect a person
    from arc flash and shock hazards. While some situations could result
    in burns to the skin, even with the protection described in Table
    130.7.C.16, burn injury should be reduced and survivable. Due to the
    explosive effect of some arc events, physical trauma injuries could
    occur. The PPE requirements of this section do not address protection
    against physical trauma other an exposure to the thermal effects of an
    arc flash.
 PPE is supposed to be your last line of defense.
 How do you feel about sustaining a “survivable”
  injury?
Thank You




              Tim Cotter, P.E.
               Staff Engineer
Schneider Electric Engineering Services, LLC

Contenu connexe

Tendances

Electrical safety
Electrical safetyElectrical safety
Electrical safetyRaj Patel
 
Understanding Arc Flash
Understanding Arc FlashUnderstanding Arc Flash
Understanding Arc Flashmichaeljmack
 
Electrical safety
Electrical safetyElectrical safety
Electrical safety1186429
 
Electrical Safety In The Workplace
Electrical Safety In The WorkplaceElectrical Safety In The Workplace
Electrical Safety In The WorkplaceCurrent Solutions PC
 
Electrical Safety Joliet Distribution Center
Electrical Safety Joliet Distribution CenterElectrical Safety Joliet Distribution Center
Electrical Safety Joliet Distribution Centertrevor_heller
 
Electrical safety slideshare
Electrical safety slideshareElectrical safety slideshare
Electrical safety slideshareYokeshDhanabal
 
Electrical 2
Electrical 2Electrical 2
Electrical 2FFSafety
 
Electrical safety training based on osha 1910 standards sw
Electrical safety training based on osha 1910 standards swElectrical safety training based on osha 1910 standards sw
Electrical safety training based on osha 1910 standards swAniruddha Kulkarni
 
Electrical Safety Techniques
Electrical Safety TechniquesElectrical Safety Techniques
Electrical Safety TechniquesLiving Online
 
Complete Guide to Electrical Safety in the Workplace
Complete Guide to Electrical Safety in the WorkplaceComplete Guide to Electrical Safety in the Workplace
Complete Guide to Electrical Safety in the Workplacehudsonelectrical
 
High Voltage Electrical Compliance and Safety Operating Procedures
High Voltage Electrical Compliance and Safety Operating ProceduresHigh Voltage Electrical Compliance and Safety Operating Procedures
High Voltage Electrical Compliance and Safety Operating ProceduresLiving Online
 
Basic electrical safety.. or safety and protection.
Basic electrical safety.. or   safety and protection.Basic electrical safety.. or   safety and protection.
Basic electrical safety.. or safety and protection.Mihir Dixit
 
ABB switchgear safety hazards passive & active arc fault protection by David ...
ABB switchgear safety hazards passive & active arc fault protection by David ...ABB switchgear safety hazards passive & active arc fault protection by David ...
ABB switchgear safety hazards passive & active arc fault protection by David ...Keren Meers
 
Practical Electrical Substation Safety for Engineers and Technicians
Practical Electrical Substation Safety for Engineers and TechniciansPractical Electrical Substation Safety for Engineers and Technicians
Practical Electrical Substation Safety for Engineers and TechniciansLiving Online
 
Lv switchgear &amp; lv cable sizing
Lv switchgear &amp; lv cable sizingLv switchgear &amp; lv cable sizing
Lv switchgear &amp; lv cable sizingAsif Eqbal
 

Tendances (20)

Electrical safety
Electrical safetyElectrical safety
Electrical safety
 
Understanding Arc Flash
Understanding Arc FlashUnderstanding Arc Flash
Understanding Arc Flash
 
Electrical safety
Electrical safetyElectrical safety
Electrical safety
 
Electrical Hazards in the Workplace
Electrical Hazards in the WorkplaceElectrical Hazards in the Workplace
Electrical Hazards in the Workplace
 
Electrical Safety In The Workplace
Electrical Safety In The WorkplaceElectrical Safety In The Workplace
Electrical Safety In The Workplace
 
Electrical safety
Electrical safetyElectrical safety
Electrical safety
 
Electrical Safety Joliet Distribution Center
Electrical Safety Joliet Distribution CenterElectrical Safety Joliet Distribution Center
Electrical Safety Joliet Distribution Center
 
Electrical safety slideshare
Electrical safety slideshareElectrical safety slideshare
Electrical safety slideshare
 
Electrical 2
Electrical 2Electrical 2
Electrical 2
 
Electrical safety
Electrical safetyElectrical safety
Electrical safety
 
Electrical safety training based on osha 1910 standards sw
Electrical safety training based on osha 1910 standards swElectrical safety training based on osha 1910 standards sw
Electrical safety training based on osha 1910 standards sw
 
Electrical Safety Techniques
Electrical Safety TechniquesElectrical Safety Techniques
Electrical Safety Techniques
 
Complete Guide to Electrical Safety in the Workplace
Complete Guide to Electrical Safety in the WorkplaceComplete Guide to Electrical Safety in the Workplace
Complete Guide to Electrical Safety in the Workplace
 
High Voltage Electrical Compliance and Safety Operating Procedures
High Voltage Electrical Compliance and Safety Operating ProceduresHigh Voltage Electrical Compliance and Safety Operating Procedures
High Voltage Electrical Compliance and Safety Operating Procedures
 
Electrical Safety Training by ISRI
Electrical Safety Training by ISRIElectrical Safety Training by ISRI
Electrical Safety Training by ISRI
 
Basic electrical safety.. or safety and protection.
Basic electrical safety.. or   safety and protection.Basic electrical safety.. or   safety and protection.
Basic electrical safety.. or safety and protection.
 
ABB switchgear safety hazards passive & active arc fault protection by David ...
ABB switchgear safety hazards passive & active arc fault protection by David ...ABB switchgear safety hazards passive & active arc fault protection by David ...
ABB switchgear safety hazards passive & active arc fault protection by David ...
 
Practical Electrical Substation Safety for Engineers and Technicians
Practical Electrical Substation Safety for Engineers and TechniciansPractical Electrical Substation Safety for Engineers and Technicians
Practical Electrical Substation Safety for Engineers and Technicians
 
Lv switchgear &amp; lv cable sizing
Lv switchgear &amp; lv cable sizingLv switchgear &amp; lv cable sizing
Lv switchgear &amp; lv cable sizing
 
Arc Flash Solutions
Arc Flash SolutionsArc Flash Solutions
Arc Flash Solutions
 

En vedette

Permitting part3 9.2.2010
Permitting part3 9.2.2010Permitting part3 9.2.2010
Permitting part3 9.2.2010CCSE Host
 
Safety grounding lightning protection and building
Safety grounding lightning protection and buildingSafety grounding lightning protection and building
Safety grounding lightning protection and buildingEdy Iskanto
 
Electrical Measurment Safety
Electrical Measurment SafetyElectrical Measurment Safety
Electrical Measurment SafetyFlukeMalta
 
70 e ppt short 2012
70 e ppt short 201270 e ppt short 2012
70 e ppt short 2012dalerj
 
Electrical Hazard & Safety
Electrical Hazard & SafetyElectrical Hazard & Safety
Electrical Hazard & SafetyYusrizal Azmi
 
Electrical Hazards on Airport
Electrical Hazards on AirportElectrical Hazards on Airport
Electrical Hazards on AirportRLarivee
 
Effective Workplace Safety Inspections
Effective Workplace Safety InspectionsEffective Workplace Safety Inspections
Effective Workplace Safety Inspectionsnolajoe
 
Investigating Ways to Prevent Electrical Arc Flash
Investigating Ways to Prevent Electrical Arc FlashInvestigating Ways to Prevent Electrical Arc Flash
Investigating Ways to Prevent Electrical Arc FlashGSE Systems, Inc.
 
Solar PV Codes and Standards
Solar PV Codes and StandardsSolar PV Codes and Standards
Solar PV Codes and StandardsSolar Reference
 
National Electrical Code: 2014 Code Changes
National Electrical Code: 2014 Code ChangesNational Electrical Code: 2014 Code Changes
National Electrical Code: 2014 Code ChangesSchneider Electric
 
Introduction on indian codes as applied in electrical design
Introduction on indian codes as applied in electrical designIntroduction on indian codes as applied in electrical design
Introduction on indian codes as applied in electrical designAsif Eqbal
 
Electrical Safety
Electrical SafetyElectrical Safety
Electrical Safetymrmackenzie
 
Electrical Commissioning and Arc-Flash Safety presentation
Electrical Commissioning and Arc-Flash Safety presentationElectrical Commissioning and Arc-Flash Safety presentation
Electrical Commissioning and Arc-Flash Safety presentationMichael Luffred
 
Workplace Inspection
Workplace InspectionWorkplace Inspection
Workplace Inspectioncflbuilder
 
Critical Power: NFPA 110: Standard for Emergency and Standby Power
Critical Power: NFPA 110: Standard for Emergency and Standby Power Critical Power: NFPA 110: Standard for Emergency and Standby Power
Critical Power: NFPA 110: Standard for Emergency and Standby Power ConsultingSpecifyingEngineer
 

En vedette (20)

Permitting part3 9.2.2010
Permitting part3 9.2.2010Permitting part3 9.2.2010
Permitting part3 9.2.2010
 
Safety grounding lightning protection and building
Safety grounding lightning protection and buildingSafety grounding lightning protection and building
Safety grounding lightning protection and building
 
Ee09 801 eed ppt
Ee09 801 eed pptEe09 801 eed ppt
Ee09 801 eed ppt
 
Dl arc flash presentation2013 r3
Dl arc flash presentation2013 r3Dl arc flash presentation2013 r3
Dl arc flash presentation2013 r3
 
Electrical Measurment Safety
Electrical Measurment SafetyElectrical Measurment Safety
Electrical Measurment Safety
 
70 e ppt short 2012
70 e ppt short 201270 e ppt short 2012
70 e ppt short 2012
 
Electrical Hazard & Safety
Electrical Hazard & SafetyElectrical Hazard & Safety
Electrical Hazard & Safety
 
Electrical Hazards on Airport
Electrical Hazards on AirportElectrical Hazards on Airport
Electrical Hazards on Airport
 
Effective Workplace Safety Inspections
Effective Workplace Safety InspectionsEffective Workplace Safety Inspections
Effective Workplace Safety Inspections
 
Inspecting Photovoltaic (PV) Systems for Code Compliance
Inspecting Photovoltaic (PV) Systems for Code ComplianceInspecting Photovoltaic (PV) Systems for Code Compliance
Inspecting Photovoltaic (PV) Systems for Code Compliance
 
Investigating Ways to Prevent Electrical Arc Flash
Investigating Ways to Prevent Electrical Arc FlashInvestigating Ways to Prevent Electrical Arc Flash
Investigating Ways to Prevent Electrical Arc Flash
 
Electrical Installation Design Project_DUBAI STANDARD_ by Mohnad Ibrahim
Electrical Installation Design Project_DUBAI STANDARD_ by Mohnad IbrahimElectrical Installation Design Project_DUBAI STANDARD_ by Mohnad Ibrahim
Electrical Installation Design Project_DUBAI STANDARD_ by Mohnad Ibrahim
 
Solar PV Codes and Standards
Solar PV Codes and StandardsSolar PV Codes and Standards
Solar PV Codes and Standards
 
National Electrical Code: 2014 Code Changes
National Electrical Code: 2014 Code ChangesNational Electrical Code: 2014 Code Changes
National Electrical Code: 2014 Code Changes
 
Introduction on indian codes as applied in electrical design
Introduction on indian codes as applied in electrical designIntroduction on indian codes as applied in electrical design
Introduction on indian codes as applied in electrical design
 
Electrical Safety
Electrical SafetyElectrical Safety
Electrical Safety
 
Electrical Commissioning and Arc-Flash Safety presentation
Electrical Commissioning and Arc-Flash Safety presentationElectrical Commissioning and Arc-Flash Safety presentation
Electrical Commissioning and Arc-Flash Safety presentation
 
Workplace Inspection
Workplace InspectionWorkplace Inspection
Workplace Inspection
 
Critical Power: NFPA 110: Standard for Emergency and Standby Power
Critical Power: NFPA 110: Standard for Emergency and Standby Power Critical Power: NFPA 110: Standard for Emergency and Standby Power
Critical Power: NFPA 110: Standard for Emergency and Standby Power
 
NFPA 70E Training By SASCO
NFPA 70E Training By SASCONFPA 70E Training By SASCO
NFPA 70E Training By SASCO
 

Similaire à Electrical Arc Flash Safety and Risk Management

Why Test Series - Arc Flash Evaluations CS-00158
Why Test Series - Arc Flash Evaluations CS-00158Why Test Series - Arc Flash Evaluations CS-00158
Why Test Series - Arc Flash Evaluations CS-00158Carolyn Dakis
 
Understanding Arc Flash presentation engineering
Understanding Arc Flash presentation engineeringUnderstanding Arc Flash presentation engineering
Understanding Arc Flash presentation engineeringSheeda2
 
NFPA 70E Electrical Safety in the Workplace by Hortica
NFPA 70E  Electrical Safety in the Workplace by HorticaNFPA 70E  Electrical Safety in the Workplace by Hortica
NFPA 70E Electrical Safety in the Workplace by HorticaAtlantic Training, LLC.
 
Introduction to Arc Flash Training by West Virginia University
Introduction to Arc Flash Training by West Virginia UniversityIntroduction to Arc Flash Training by West Virginia University
Introduction to Arc Flash Training by West Virginia UniversityAtlantic Training, LLC.
 
Introduction to Arc Flash - Revisions to the NFPA 70E, Electrically Safe Wor...
Introduction to Arc Flash - Revisions to the NFPA 70E, Electrically Safe Wor...Introduction to Arc Flash - Revisions to the NFPA 70E, Electrically Safe Wor...
Introduction to Arc Flash - Revisions to the NFPA 70E, Electrically Safe Wor...Thorne & Derrick International
 
Arc Flash Analysis Training by Illinois Institute of Technology
Arc Flash Analysis Training by Illinois Institute of TechnologyArc Flash Analysis Training by Illinois Institute of Technology
Arc Flash Analysis Training by Illinois Institute of TechnologyAtlantic Training, LLC.
 
Arc Flash Calculations What Does It All Mean
Arc Flash Calculations What Does It All MeanArc Flash Calculations What Does It All Mean
Arc Flash Calculations What Does It All MeanB Bhargav Reddy
 
Electrical hazards
Electrical hazardsElectrical hazards
Electrical hazardsKashif Riaz
 
Make India Safer with JMV LPS Ltd Electrical Equipment & Human Safety
Make India Safer with JMV LPS Ltd  Electrical Equipment & Human SafetyMake India Safer with JMV LPS Ltd  Electrical Equipment & Human Safety
Make India Safer with JMV LPS Ltd Electrical Equipment & Human SafetyMahesh Chandra Manav
 
Webinar - Electrical Arc Flash Hazards - Is your company in compliance?
Webinar - Electrical Arc Flash Hazards - Is your company in compliance?Webinar - Electrical Arc Flash Hazards - Is your company in compliance?
Webinar - Electrical Arc Flash Hazards - Is your company in compliance?Leonardo ENERGY
 
Elec hazard awareness_study_guide
Elec hazard awareness_study_guideElec hazard awareness_study_guide
Elec hazard awareness_study_guideRobin George
 

Similaire à Electrical Arc Flash Safety and Risk Management (20)

Why Test Series - Arc Flash Evaluations CS-00158
Why Test Series - Arc Flash Evaluations CS-00158Why Test Series - Arc Flash Evaluations CS-00158
Why Test Series - Arc Flash Evaluations CS-00158
 
Understanding Arc Flash presentation engineering
Understanding Arc Flash presentation engineeringUnderstanding Arc Flash presentation engineering
Understanding Arc Flash presentation engineering
 
Understanding Arc Flash
Understanding Arc FlashUnderstanding Arc Flash
Understanding Arc Flash
 
Arc flash
Arc flashArc flash
Arc flash
 
Arc flash
Arc flashArc flash
Arc flash
 
NFPA 70E Electrical Safety in the Workplace by Hortica
NFPA 70E  Electrical Safety in the Workplace by HorticaNFPA 70E  Electrical Safety in the Workplace by Hortica
NFPA 70E Electrical Safety in the Workplace by Hortica
 
Introduction to Arc Flash Training by West Virginia University
Introduction to Arc Flash Training by West Virginia UniversityIntroduction to Arc Flash Training by West Virginia University
Introduction to Arc Flash Training by West Virginia University
 
Introduction to Arc Flash - Revisions to the NFPA 70E, Electrically Safe Wor...
Introduction to Arc Flash - Revisions to the NFPA 70E, Electrically Safe Wor...Introduction to Arc Flash - Revisions to the NFPA 70E, Electrically Safe Wor...
Introduction to Arc Flash - Revisions to the NFPA 70E, Electrically Safe Wor...
 
Arc Flash Analysis Training by Illinois Institute of Technology
Arc Flash Analysis Training by Illinois Institute of TechnologyArc Flash Analysis Training by Illinois Institute of Technology
Arc Flash Analysis Training by Illinois Institute of Technology
 
Arc flash guidebook
Arc flash guidebookArc flash guidebook
Arc flash guidebook
 
Arc flash guidebook
Arc flash guidebookArc flash guidebook
Arc flash guidebook
 
Arc flash q
Arc flash qArc flash q
Arc flash q
 
Arc Flash Calculations What Does It All Mean
Arc Flash Calculations What Does It All MeanArc Flash Calculations What Does It All Mean
Arc Flash Calculations What Does It All Mean
 
Electrical hazards
Electrical hazardsElectrical hazards
Electrical hazards
 
Safety In Electrical Jobs.pdf
Safety In Electrical Jobs.pdfSafety In Electrical Jobs.pdf
Safety In Electrical Jobs.pdf
 
Make India Safer with JMV LPS Ltd Electrical Equipment & Human Safety
Make India Safer with JMV LPS Ltd  Electrical Equipment & Human SafetyMake India Safer with JMV LPS Ltd  Electrical Equipment & Human Safety
Make India Safer with JMV LPS Ltd Electrical Equipment & Human Safety
 
Webinar - Electrical Arc Flash Hazards - Is your company in compliance?
Webinar - Electrical Arc Flash Hazards - Is your company in compliance?Webinar - Electrical Arc Flash Hazards - Is your company in compliance?
Webinar - Electrical Arc Flash Hazards - Is your company in compliance?
 
Elec hazard awareness_study_guide
Elec hazard awareness_study_guideElec hazard awareness_study_guide
Elec hazard awareness_study_guide
 
Electrical hazard awareness_study_guide
Electrical hazard awareness_study_guideElectrical hazard awareness_study_guide
Electrical hazard awareness_study_guide
 
What is an arc flash?
What is an arc flash? What is an arc flash?
What is an arc flash?
 

Plus de Schneider Electric

Secure Power Design Considerations
Secure Power Design ConsiderationsSecure Power Design Considerations
Secure Power Design ConsiderationsSchneider Electric
 
Digital International Colo Club: Attracting Investors
Digital International Colo Club: Attracting InvestorsDigital International Colo Club: Attracting Investors
Digital International Colo Club: Attracting InvestorsSchneider Electric
 
32 phaseo power supplies and transformers briefing
32 phaseo power supplies and transformers briefing 32 phaseo power supplies and transformers briefing
32 phaseo power supplies and transformers briefing Schneider Electric
 
Key Industry Trends, M&A Valuation Trends
Key Industry Trends, M&A Valuation TrendsKey Industry Trends, M&A Valuation Trends
Key Industry Trends, M&A Valuation TrendsSchneider Electric
 
EcoStruxure™ for Cloud & Service Providers
 EcoStruxure™ for Cloud & Service Providers EcoStruxure™ for Cloud & Service Providers
EcoStruxure™ for Cloud & Service ProvidersSchneider Electric
 
Zelio Time Electronic Relay Briefing
Zelio Time Electronic Relay BriefingZelio Time Electronic Relay Briefing
Zelio Time Electronic Relay BriefingSchneider Electric
 
Spacial, Thalassa, ClimaSys Universal enclosures Briefing
Spacial, Thalassa, ClimaSys Universal enclosures BriefingSpacial, Thalassa, ClimaSys Universal enclosures Briefing
Spacial, Thalassa, ClimaSys Universal enclosures BriefingSchneider Electric
 
Relay Control Zelio SSR Briefing
Relay Control Zelio SSR BriefingRelay Control Zelio SSR Briefing
Relay Control Zelio SSR BriefingSchneider Electric
 
Magelis HMI, iPC and software Briefing
Magelis HMI, iPC and software BriefingMagelis HMI, iPC and software Briefing
Magelis HMI, iPC and software BriefingSchneider Electric
 
Where will the next 80% improvement in data center performance come from?
Where will the next 80% improvement in data center performance come from?Where will the next 80% improvement in data center performance come from?
Where will the next 80% improvement in data center performance come from?Schneider Electric
 
EcoStruxure for Intuitive Industries
EcoStruxure for Intuitive IndustriesEcoStruxure for Intuitive Industries
EcoStruxure for Intuitive IndustriesSchneider Electric
 
Systems Integrator Alliance Program 2017
Systems Integrator Alliance Program 2017Systems Integrator Alliance Program 2017
Systems Integrator Alliance Program 2017Schneider Electric
 
EcoStruxure, IIoT-enabled architecture, delivering value in key segments.
EcoStruxure, IIoT-enabled architecture, delivering value in key segments.EcoStruxure, IIoT-enabled architecture, delivering value in key segments.
EcoStruxure, IIoT-enabled architecture, delivering value in key segments.Schneider Electric
 
It's time to modernize your industrial controls with Modicon M580
It's time to modernize your industrial controls with Modicon M580It's time to modernize your industrial controls with Modicon M580
It's time to modernize your industrial controls with Modicon M580Schneider Electric
 
A Practical Guide to Ensuring Business Continuity and High Performance in Hea...
A Practical Guide to Ensuring Business Continuity and High Performance in Hea...A Practical Guide to Ensuring Business Continuity and High Performance in Hea...
A Practical Guide to Ensuring Business Continuity and High Performance in Hea...Schneider Electric
 
Connected Services Study – Facility Managers Respond to IoT
Connected Services Study – Facility Managers Respond to IoTConnected Services Study – Facility Managers Respond to IoT
Connected Services Study – Facility Managers Respond to IoTSchneider Electric
 
Telemecanqiue Cabling and Accessories Briefing
Telemecanqiue Cabling and Accessories BriefingTelemecanqiue Cabling and Accessories Briefing
Telemecanqiue Cabling and Accessories BriefingSchneider Electric
 
Telemecanique Photoelectric Sensors Briefing
Telemecanique Photoelectric Sensors BriefingTelemecanique Photoelectric Sensors Briefing
Telemecanique Photoelectric Sensors BriefingSchneider Electric
 
Telemecanique Limit Switches Briefing
Telemecanique Limit Switches BriefingTelemecanique Limit Switches Briefing
Telemecanique Limit Switches BriefingSchneider Electric
 

Plus de Schneider Electric (20)

Secure Power Design Considerations
Secure Power Design ConsiderationsSecure Power Design Considerations
Secure Power Design Considerations
 
Digital International Colo Club: Attracting Investors
Digital International Colo Club: Attracting InvestorsDigital International Colo Club: Attracting Investors
Digital International Colo Club: Attracting Investors
 
32 phaseo power supplies and transformers briefing
32 phaseo power supplies and transformers briefing 32 phaseo power supplies and transformers briefing
32 phaseo power supplies and transformers briefing
 
Key Industry Trends, M&A Valuation Trends
Key Industry Trends, M&A Valuation TrendsKey Industry Trends, M&A Valuation Trends
Key Industry Trends, M&A Valuation Trends
 
EcoStruxure™ for Cloud & Service Providers
 EcoStruxure™ for Cloud & Service Providers EcoStruxure™ for Cloud & Service Providers
EcoStruxure™ for Cloud & Service Providers
 
Magelis Basic HMI Briefing
Magelis Basic HMI Briefing Magelis Basic HMI Briefing
Magelis Basic HMI Briefing
 
Zelio Time Electronic Relay Briefing
Zelio Time Electronic Relay BriefingZelio Time Electronic Relay Briefing
Zelio Time Electronic Relay Briefing
 
Spacial, Thalassa, ClimaSys Universal enclosures Briefing
Spacial, Thalassa, ClimaSys Universal enclosures BriefingSpacial, Thalassa, ClimaSys Universal enclosures Briefing
Spacial, Thalassa, ClimaSys Universal enclosures Briefing
 
Relay Control Zelio SSR Briefing
Relay Control Zelio SSR BriefingRelay Control Zelio SSR Briefing
Relay Control Zelio SSR Briefing
 
Magelis HMI, iPC and software Briefing
Magelis HMI, iPC and software BriefingMagelis HMI, iPC and software Briefing
Magelis HMI, iPC and software Briefing
 
Where will the next 80% improvement in data center performance come from?
Where will the next 80% improvement in data center performance come from?Where will the next 80% improvement in data center performance come from?
Where will the next 80% improvement in data center performance come from?
 
EcoStruxure for Intuitive Industries
EcoStruxure for Intuitive IndustriesEcoStruxure for Intuitive Industries
EcoStruxure for Intuitive Industries
 
Systems Integrator Alliance Program 2017
Systems Integrator Alliance Program 2017Systems Integrator Alliance Program 2017
Systems Integrator Alliance Program 2017
 
EcoStruxure, IIoT-enabled architecture, delivering value in key segments.
EcoStruxure, IIoT-enabled architecture, delivering value in key segments.EcoStruxure, IIoT-enabled architecture, delivering value in key segments.
EcoStruxure, IIoT-enabled architecture, delivering value in key segments.
 
It's time to modernize your industrial controls with Modicon M580
It's time to modernize your industrial controls with Modicon M580It's time to modernize your industrial controls with Modicon M580
It's time to modernize your industrial controls with Modicon M580
 
A Practical Guide to Ensuring Business Continuity and High Performance in Hea...
A Practical Guide to Ensuring Business Continuity and High Performance in Hea...A Practical Guide to Ensuring Business Continuity and High Performance in Hea...
A Practical Guide to Ensuring Business Continuity and High Performance in Hea...
 
Connected Services Study – Facility Managers Respond to IoT
Connected Services Study – Facility Managers Respond to IoTConnected Services Study – Facility Managers Respond to IoT
Connected Services Study – Facility Managers Respond to IoT
 
Telemecanqiue Cabling and Accessories Briefing
Telemecanqiue Cabling and Accessories BriefingTelemecanqiue Cabling and Accessories Briefing
Telemecanqiue Cabling and Accessories Briefing
 
Telemecanique Photoelectric Sensors Briefing
Telemecanique Photoelectric Sensors BriefingTelemecanique Photoelectric Sensors Briefing
Telemecanique Photoelectric Sensors Briefing
 
Telemecanique Limit Switches Briefing
Telemecanique Limit Switches BriefingTelemecanique Limit Switches Briefing
Telemecanique Limit Switches Briefing
 

Dernier

Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024BookNet Canada
 
Powerpoint exploring the locations used in television show Time Clash
Powerpoint exploring the locations used in television show Time ClashPowerpoint exploring the locations used in television show Time Clash
Powerpoint exploring the locations used in television show Time Clashcharlottematthew16
 
How to write a Business Continuity Plan
How to write a Business Continuity PlanHow to write a Business Continuity Plan
How to write a Business Continuity PlanDatabarracks
 
Human Factors of XR: Using Human Factors to Design XR Systems
Human Factors of XR: Using Human Factors to Design XR SystemsHuman Factors of XR: Using Human Factors to Design XR Systems
Human Factors of XR: Using Human Factors to Design XR SystemsMark Billinghurst
 
Commit 2024 - Secret Management made easy
Commit 2024 - Secret Management made easyCommit 2024 - Secret Management made easy
Commit 2024 - Secret Management made easyAlfredo García Lavilla
 
Take control of your SAP testing with UiPath Test Suite
Take control of your SAP testing with UiPath Test SuiteTake control of your SAP testing with UiPath Test Suite
Take control of your SAP testing with UiPath Test SuiteDianaGray10
 
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024BookNet Canada
 
Merck Moving Beyond Passwords: FIDO Paris Seminar.pptx
Merck Moving Beyond Passwords: FIDO Paris Seminar.pptxMerck Moving Beyond Passwords: FIDO Paris Seminar.pptx
Merck Moving Beyond Passwords: FIDO Paris Seminar.pptxLoriGlavin3
 
Developer Data Modeling Mistakes: From Postgres to NoSQL
Developer Data Modeling Mistakes: From Postgres to NoSQLDeveloper Data Modeling Mistakes: From Postgres to NoSQL
Developer Data Modeling Mistakes: From Postgres to NoSQLScyllaDB
 
Gen AI in Business - Global Trends Report 2024.pdf
Gen AI in Business - Global Trends Report 2024.pdfGen AI in Business - Global Trends Report 2024.pdf
Gen AI in Business - Global Trends Report 2024.pdfAddepto
 
Ensuring Technical Readiness For Copilot in Microsoft 365
Ensuring Technical Readiness For Copilot in Microsoft 365Ensuring Technical Readiness For Copilot in Microsoft 365
Ensuring Technical Readiness For Copilot in Microsoft 3652toLead Limited
 
DSPy a system for AI to Write Prompts and Do Fine Tuning
DSPy a system for AI to Write Prompts and Do Fine TuningDSPy a system for AI to Write Prompts and Do Fine Tuning
DSPy a system for AI to Write Prompts and Do Fine TuningLars Bell
 
TeamStation AI System Report LATAM IT Salaries 2024
TeamStation AI System Report LATAM IT Salaries 2024TeamStation AI System Report LATAM IT Salaries 2024
TeamStation AI System Report LATAM IT Salaries 2024Lonnie McRorey
 
H2O.ai CEO/Founder: Sri Ambati Keynote at Wells Fargo Day
H2O.ai CEO/Founder: Sri Ambati Keynote at Wells Fargo DayH2O.ai CEO/Founder: Sri Ambati Keynote at Wells Fargo Day
H2O.ai CEO/Founder: Sri Ambati Keynote at Wells Fargo DaySri Ambati
 
What's New in Teams Calling, Meetings and Devices March 2024
What's New in Teams Calling, Meetings and Devices March 2024What's New in Teams Calling, Meetings and Devices March 2024
What's New in Teams Calling, Meetings and Devices March 2024Stephanie Beckett
 
SIP trunking in Janus @ Kamailio World 2024
SIP trunking in Janus @ Kamailio World 2024SIP trunking in Janus @ Kamailio World 2024
SIP trunking in Janus @ Kamailio World 2024Lorenzo Miniero
 
"ML in Production",Oleksandr Bagan
"ML in Production",Oleksandr Bagan"ML in Production",Oleksandr Bagan
"ML in Production",Oleksandr BaganFwdays
 
Unleash Your Potential - Namagunga Girls Coding Club
Unleash Your Potential - Namagunga Girls Coding ClubUnleash Your Potential - Namagunga Girls Coding Club
Unleash Your Potential - Namagunga Girls Coding ClubKalema Edgar
 
Vertex AI Gemini Prompt Engineering Tips
Vertex AI Gemini Prompt Engineering TipsVertex AI Gemini Prompt Engineering Tips
Vertex AI Gemini Prompt Engineering TipsMiki Katsuragi
 
DevEX - reference for building teams, processes, and platforms
DevEX - reference for building teams, processes, and platformsDevEX - reference for building teams, processes, and platforms
DevEX - reference for building teams, processes, and platformsSergiu Bodiu
 

Dernier (20)

Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
 
Powerpoint exploring the locations used in television show Time Clash
Powerpoint exploring the locations used in television show Time ClashPowerpoint exploring the locations used in television show Time Clash
Powerpoint exploring the locations used in television show Time Clash
 
How to write a Business Continuity Plan
How to write a Business Continuity PlanHow to write a Business Continuity Plan
How to write a Business Continuity Plan
 
Human Factors of XR: Using Human Factors to Design XR Systems
Human Factors of XR: Using Human Factors to Design XR SystemsHuman Factors of XR: Using Human Factors to Design XR Systems
Human Factors of XR: Using Human Factors to Design XR Systems
 
Commit 2024 - Secret Management made easy
Commit 2024 - Secret Management made easyCommit 2024 - Secret Management made easy
Commit 2024 - Secret Management made easy
 
Take control of your SAP testing with UiPath Test Suite
Take control of your SAP testing with UiPath Test SuiteTake control of your SAP testing with UiPath Test Suite
Take control of your SAP testing with UiPath Test Suite
 
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
 
Merck Moving Beyond Passwords: FIDO Paris Seminar.pptx
Merck Moving Beyond Passwords: FIDO Paris Seminar.pptxMerck Moving Beyond Passwords: FIDO Paris Seminar.pptx
Merck Moving Beyond Passwords: FIDO Paris Seminar.pptx
 
Developer Data Modeling Mistakes: From Postgres to NoSQL
Developer Data Modeling Mistakes: From Postgres to NoSQLDeveloper Data Modeling Mistakes: From Postgres to NoSQL
Developer Data Modeling Mistakes: From Postgres to NoSQL
 
Gen AI in Business - Global Trends Report 2024.pdf
Gen AI in Business - Global Trends Report 2024.pdfGen AI in Business - Global Trends Report 2024.pdf
Gen AI in Business - Global Trends Report 2024.pdf
 
Ensuring Technical Readiness For Copilot in Microsoft 365
Ensuring Technical Readiness For Copilot in Microsoft 365Ensuring Technical Readiness For Copilot in Microsoft 365
Ensuring Technical Readiness For Copilot in Microsoft 365
 
DSPy a system for AI to Write Prompts and Do Fine Tuning
DSPy a system for AI to Write Prompts and Do Fine TuningDSPy a system for AI to Write Prompts and Do Fine Tuning
DSPy a system for AI to Write Prompts and Do Fine Tuning
 
TeamStation AI System Report LATAM IT Salaries 2024
TeamStation AI System Report LATAM IT Salaries 2024TeamStation AI System Report LATAM IT Salaries 2024
TeamStation AI System Report LATAM IT Salaries 2024
 
H2O.ai CEO/Founder: Sri Ambati Keynote at Wells Fargo Day
H2O.ai CEO/Founder: Sri Ambati Keynote at Wells Fargo DayH2O.ai CEO/Founder: Sri Ambati Keynote at Wells Fargo Day
H2O.ai CEO/Founder: Sri Ambati Keynote at Wells Fargo Day
 
What's New in Teams Calling, Meetings and Devices March 2024
What's New in Teams Calling, Meetings and Devices March 2024What's New in Teams Calling, Meetings and Devices March 2024
What's New in Teams Calling, Meetings and Devices March 2024
 
SIP trunking in Janus @ Kamailio World 2024
SIP trunking in Janus @ Kamailio World 2024SIP trunking in Janus @ Kamailio World 2024
SIP trunking in Janus @ Kamailio World 2024
 
"ML in Production",Oleksandr Bagan
"ML in Production",Oleksandr Bagan"ML in Production",Oleksandr Bagan
"ML in Production",Oleksandr Bagan
 
Unleash Your Potential - Namagunga Girls Coding Club
Unleash Your Potential - Namagunga Girls Coding ClubUnleash Your Potential - Namagunga Girls Coding Club
Unleash Your Potential - Namagunga Girls Coding Club
 
Vertex AI Gemini Prompt Engineering Tips
Vertex AI Gemini Prompt Engineering TipsVertex AI Gemini Prompt Engineering Tips
Vertex AI Gemini Prompt Engineering Tips
 
DevEX - reference for building teams, processes, and platforms
DevEX - reference for building teams, processes, and platformsDevEX - reference for building teams, processes, and platforms
DevEX - reference for building teams, processes, and platforms
 

Electrical Arc Flash Safety and Risk Management

  • 1. Arc Flash Protection and Mitigation Tim Cotter, P.E. Staff Engineer Schneider Electric Engineering Services
  • 2. A Quick Look Back… “I introduced into my ears two metal rods with rounded ends and joined them to the terminals of the apparatus. At the moment the circuit was completed, I received a shock in the head – and began to hear a noise – a crackling and boiling. This disagreeable sensation, which I feared might be dangerous, has deterred me so that I have not repeated the experiment.”
  • 3. We’ve come a long way… “I introduced into my ears two metal rods with rounded ends and joined them to the terminals of the apparatus.   At the moment the circuit was completed, I received a shock in the head – and began to hear a noise – a crackling and boiling.   This disagreeable sensation, which I feared might be dangerous, has deterred me so that I have not repeated the experiment.” -Alessandro Volta, inventor of the first electric battery, 1745-1827
  • 4. even from … more recent times.  154. Electricians often test circuits for the presence of voltage by touching the conductors with the fingers. This method is safe where the voltage does not exceed 250 and is often very convenient for locating a blown-out fuse or for ascertaining whether or not a circuit is alive. Some men can endure the electric shock that results without discomfort whereas others cannot. Therefore, the method is not feasible in some cases. AMERICAN ELECTRICIANS’ HANDBOOK 7th Edition 1953 McGraw-Hill
  • 5. But where are we now?  NIOSH Study covering 1980-1995:  93,338 total work-related fatalities in the US  Approximately 1 in 15 were related to electrical hazards (> 1 fatality/ day in the US)  #5 hazard overall Auto accidents were #1  More recent data – # of deaths down, but proportion that is related to electrical work is about the same!  Lots of work still to do!
  • 6. Electric Arcs & Arc Flash  Passage of substantial electric current through air  “Short-circuit in air”  May simply flow through ionized air  May flow through vapor of arc-terminal material  Copper, Carbon, etc.  Not necessarily harmful  Arc welding, “static electricity”  Arc Flash Hazard: A dangerous condition associated with the possible release of energy caused by an electric arc. (NPFA 70E definition)
  • 7. Severity of Arc Flash Depends on several factors, including:  Magnitude of fault current  System voltage  Duration of arcing fault  Proximity of worker to arc source Complex issue! Typical power distribution system – levels may be severe enough to cause serious injury or death
  • 8.
  • 9. Measurements taken from atop the ladder Note melting of steel & copper
  • 10.
  • 11.
  • 12.
  • 13. Relevant Codes & Standards National Electrical Code NFPA 70 (2011 ed.) OSHA NFPA 70E (2012 ed.), Standard for Electrical Safety In the Workplace IEEE 1584-2002
  • 14. National Electrical Code – NFPA 70  Best known of all electrical standards?  Dates back to 1897  In general, does not address work practices  Still, starting in 2002, some reference to Arc Flash NEC 110.16. Flash Protection. Electrical equipment, such as switchboards, panelboards, industrial control panels, meter socket enclosures, and motor control centers, that are in other than dwelling occupancies, and are likely to require examination, adjustment, servicing, or maintenance while energized shall be field marked to warn qualified persons of potential electric arc flash hazards. The marking shall be located so as to be clearly visible to qualified persons before examination, adjustment, servicing, or maintenance of the equipment.
  • 15. NEC & Arc Flash  Requires equipment to be labeled, but does not specify a label format  We’ll discuss labeling in more detail later  An NEC-compliant system does not necessarily do a thing to reduce, eliminate, or manage arc flash hazards
  • 16. OSHA  Occupational Safety and Health Administration  Created by Occupational Safety and Health Act of 1970  Mission: “To save lives, prevent injuries, and protect the health of America’s workers.”  29.CFR 1910, Subpart S—deals with electrical systems  “Law of the Land”!  www.osha.gov
  • 17. OSHA & Arc Flash  OSHA requires use of Personal Protective Equipment (PPE)  Does not prescribe nature of PPE required for various tasks NFPA 70E is referenced in an appendix of OSHA 1910 Subpart S, but is not “incorporated by reference”  Most serious injuries involve ignition of clothing Proper clothing must be selected based on industry standards or practices NFPA 70E: an industry consensus standard
  • 18. OSHA General Duty Clause  Each employer shall furnish to each of his employees employment and a place of employment which are free from recognized hazards that are causing or are likely to cause death or serious physical harm to his employees.  [OSHA’s PPE requirements] are written in general terms, requiring, for example, that personal protective equipment be provided "where necessary by reason of hazards..." (§1910.132(a)), and requiring the employer to select equipment "that will protect the affected employee from the hazards...." (§1910.132(d)(1)). Also, §1910.132(c) requires the equipment to "be of safe design and construction for the work performed." Similarly, §1910.335 contains requirements such as the provision and use of "electrical protective equipment that is appropriate for the specific parts of the body to be protected and the work to be performed (§1910.335(a)(i)). Industry consensus standards, such as NFPA 70E, can be used by employers as guides to making the assessments and equipment selections required by the standard. Similarly, in OSHA enforcement actions, they can be used as evidence of whether the employer acted reasonably. From OSHA interpretation of the General Duty Clause, 7/25/2003
  • 19. NFPA 70E “Standard for Electrical Safety In the Workplace” Current edition published in September, 2011 Approx. 3-year revision cycle Revision process underway! Latest edition: 2012
  • 20. NFPA 70E: Key Provisions  Article 90: Scope  Facilities covered include public and private buildings, parking lots, carnivals, industrial substations, service- entrance equipment, and electric utility equipment that is NOT a generating station, substation, or control center  Facilities NOT covered include ships or automobiles/trucks, underground installations in mines, “3rd rail”, communications equipment under the control of communications utilities, and remaining electric utility installations  Basically the same as the NEC
  • 21. NFPA 70E: Key Provisions  Qualified Employees – ones allowed to do work  Knowledgeable about a piece of equipment or specific work method 70E defines specific items that should be known  Can recognize and avoid electrical hazards (including arc flash)  Is familiar with proper use of PPE, insulated tools, and insulating/shielding materials  Not necessarily synonymous with: Master Electrician Professional Engineer CEO
  • 22. NFPA 70E: Key Provisions  “Live parts to which an employee might be exposed shall be put into an electrically safe work condition before an employee works on or near them, unless work on energized components can be justified according to 130.1”—110.8(A)(1)  Basic protection strategy: de-energize the equipment! Excerpt from typical Square D instruction bulletin.
  • 23. NFPA 70E: Key Provisions Exceptions to the previous rule include the following: (130.1) When de-energizing introduces additional or increased hazards Deactivation of emergency alarm systems Life support system Ventilation in hazardous area When de-energizing is infeasible Performing diagnostics or testing that requires energized circuit
  • 24. NFPA 70E: Key Provisions  If parts not placed in an electrically safe condition, then work to be performed shall be considered energized electrical work and shall be performed by written permit only  Decision-making taken out of workers’ hands and shifted to management  Why a permit?  Make you think twice before doing energized work  Create a “Paper trail”  This applies to the “exemptions”  Management can’t just sign a permit and OK any energized work
  • 25. Flash Hazard Analysis  The analysis shall determine the flash protection boundary and the PPE that workers within this boundary should use  Intended to protect personnel from the possibility of being injured by an arc flash  How does one perform a flash hazard analysis? PPE Tables Calculations More on this later
  • 26. Flash Protection Boundary Arc Flash Boundary (100): An approach limit at a distance from a prospective arc source within which a person could receive a second degree burn if an electric arc flash were to occur.
  • 28. How Much Energy is Too Much?  It is generally accepted that an incident energy of 1.2 cal/cm2 is sufficient to cause 2nd-degree burns on unprotected skin  Tolerance may be higher for very short exposures  Why cal/cm2?  Just how hot is 1.2 cal/cm2???  Typical incident energy ranges:  0-200+ cal/cm2  Equipment that has been placed in an electrically safe work condition: energy level = zero!!
  • 29. Working Inside the FPB  Employer shall determine and document the incident energy exposure of the worker (cal/cm2)  Based on a working distance from source of arc to employee’s face and chest  Use FR clothing and PPE appropriate for hazard level  Use additional PPE for parts of the body closer than the distance at which the incident energy was determined  (Alt.) Select PPE from tables
  • 30. Equipment Labeling  Now required in the 2012 edition of NFPA 70E  130.5 (C) – Several options listed for identifying the arc flash hazard along with nominal voltage and arc flash boundary.  Field marked – can’t determine at factory  Minimal information actually required  Most labels contain significantly more information
  • 31. IEEE Standard 1584  “IEEE Guide for Performing Arc-Flash Hazard Calculations”  Incorporates results of extensive testing performed by several parties  Provides method for calculating incident arc-flash energy  Does not replace NEC or NFPA 70E—instead, it works with and alongside of them  More on this when we talk about calculations
  • 32. NFPA 70E PPE Requirements PPE should:  Cover all ignitable clothing (130.7(C)(2))  Allow for movement and visibility (130.7(C)(2))  Include head, face, neck, and chin protection (130.7(C)(3))  Include eye protection (safety glasses) (130.7(C)(4))  Include FR clothing for body (130.7(C)(6)) for all exposures over 1.2 cal/cm2  Include hand and arm protection (130.7(C)(7))  Include foot protection (130.7(C)(8))  Conform to relevant ANSI and/or ASTM standards (130.7(C)(14))
  • 33. Additional PPE Requirements  Outer layers over FR clothing also must be FR  Avoid tight-fitting clothes  Choose PPE that poses minimal interference while still providing adequate protection  Wear safety glasses under face shields/hoods  Visor in flash suit should protect as well as the rest of the suit  Non-FR synthetic fabrics not permitted*
  • 34. Selection of PPE  Based on Hazard/Risk Analysis  NFPA 70E Tables  List common work tasks for several types of equipment  Each task assigned a HRC  PPE defined for these HRCs  Calculations  Calculations define AFIE for a given location  Select protective clothing that will protect against that AFIE  Technically, HRCs don’t apply to calculated results, but in practice, most still correlate calculated AFIE levels to clothing systems listed in NFPA 70E Table 130.7.C.15
  • 35. Protective Clothing Classes Min Arc Rating Class Description (cal/cm2) 0 Nonmelting, flammable materials N/A 1 FR shirt + FR pants or FR coverall 4 2 FR shirt + FR pants or FR coverall 8 3 (2) + additional PPE to reach 25 cal/cm2 25 4 (2) + additional PPE to reach 40 cal/cm2 40 Category 0 Clothing OK for up to 1.2 cal/cm2
  • 36. H/R Category 0 (Non-FR) Untreated, long-sleeve shirt Untreated, long pants Hearing protection Safety Glasses Good for up to 1.2 cal/cm2 Photos courtesy of Oberon
  • 37. H/R Category 1 (one FR layer)  FR pants with ATPV of at least 4 cal/cm2  No more untreated denim!  FR long-sleeve shirt  Optional FR coverall in lieu of FR shirt/pants  FR jacket/parka/rainwear (as needed)  Hard hat  Safety Glasses  Hearing protection  Arc Rated Face Shield  Leather gloves & leather work shoes (as needed) Good for up to 4.0 cal/cm2
  • 38. H/R Category 2 (one FR layer + cotton)  FR long-sleeve shirt (minimum arc rating of 8)  Pants: FR with min arc rating of 8  FR Coverall (Arc Rating 8 or more) permissible in lieu of other FR clothing  FR jacket/parka/rainwear (as needed)  Hard Hat  Safety glasses or Safety Goggles  Leather gloves & leather work shoes  Hearing protection  Face Shield & Arc Rated Balaclava or Arc Rated Hood Photos courtesy of Oberon Good for up to 8.0 cal/cm2
  • 39. H/R Category 3 (two FR layers)  Option 1:  FR shirt/pants  FR coverall  Option 2:  FR clothing system w/arc rating of 25  FR jacket/parka/rainwear (as needed)  Hard hat  Safety glasses or safety goggles  Double-layer switching hood Photos courtesy of Oberon  Hearing protection  Arc rated gloves or rubber gloves w/leather protectors Good for up to 25 cal/cm2  Leather work shoes
  • 40. H/R Category 4  FR clothing with arc rating of 40  Flash suit  Shirt/pants/coverall combination providing equivalent protection  FR jacket/parka/rainwear (as needed)  Hard hat w/FR liner  Safety glasses or safety goggles  Double-layer switching hood  Hearing protection  Arc rated gloves or rubber insulating gloves w/leather protectors  Leather work shoes Photos courtesy of Oberon Good for up to 40 cal/cm2
  • 41. Beyond 40 cal/cm2…  PPE vendors: 100 calorie suits  NFPA 70E: defines no clothing class higher than 40 cal/cm2 Does not explicitly prohibit work at such locations 70E Handbook: appears to have backed off a statement in the earlier editions that allowing work at such locations was never the intent of 70E  Other issues to consider Blast effects Equipment integrity Is PPE rated against shrapnel? No “ballistics rated” flash suit or face shield Hearing damage
  • 42. Why is PPE Important?  Has major impact on burn survival rates  Major factor: total % of body burned  Burn of 75% of body (easily possible if clothing ignites) results in:  < 50% survival rate for males aged 30-39  < 20% survival rate for males aged 50-59  Rule of thumb: one day in hospital for each 1% of body burned Photos courtesy of Oberon
  • 43. Clothing Performance Benchmarks Ease of ignition Tendency to continue burning after heat source removed Degree/ease of flame spread Amount of heat transmitted Tendency to melt Strength—does arc flash tear it apart, or does it hold together?
  • 44. Relative Performance – non-FR Clothing  Natural fibers are fairly good, at least if they don’t ignite  Cotton may continue to burn after heat removed  Wool does not normally sustain a fire  Non-FR Synthetics particularly bad either when alone or when blended w/cotton  Easily ignited  Melt  Increase chance of infection  Exception?
  • 45. PPE Selection Principles  Heavier fabrics provide more protection  Multiple layers more effective than single layer of equivalent weight  No non-FR synthetics next to skin  “Performance underwear” may contain polyester or nylon/spandex blend—good for a ski trip, but bad for electrical work!!
  • 46.
  • 47. Head and Face Protection  Face shields provide some protection against molten splatter  Non-FR face shields provide little or no protection against burns  Tinted face shield with ATPV rating—better  Protective shield inside FR hood—best  Beware old FR hoods with non-FR shields!  If visibility is a concern, provide lighting!  Safety glasses always required
  • 48. Arc Rating Values  Based on testing  Shown on equipment label  Some PPE—no tests performed, so no official arc rating assigned  Leather work gloves (unofficially 12 cal/cm2)  Leather glove protectors  Rubber insulating gloves Class 0 yellow gloves: limited testing indicated ignition 10% of the time at 25 cal/cm2; 50% of the time at 31 cal/ cm2  Shoes (limited testing indicates resistance of 50-60 cal/cm2)
  • 49. PPE Innovations – Arc Hood Cooling Systems
  • 50. PPE Innovations – Improved Visibility Warning: older clear faceshields may not be FR. In the presence of a high energy arc, they can melt. The pressure wave will tend to push the molten plastic into your face.
  • 51. PPE “Gotchas”  Not all FR rainwear is “arc resistant” – i.e., may have elements that can melt  EVERYTHING needs to be arc resistant (or at least made out of something that won’t melt or burst into flame) during energized work  Underwear  Safety vests  Hair nets  Employee ID cards  Logos / names sewn on to FR clothing  Paper towels stuffed in hard hat to catch sweat  Maintain the PPE  Carefully observe laundering instructions
  • 52. Use Your Head  Use PPE correctly…no rolled-up sleeves or unzipped coveralls  Body positioning when operating devices But: don’t make face shield an “arc scoop”  No more workers than necessary in vicinity of energized work  Remove yourself from the source when possible Hot stick Remote operations
  • 53. Disclaimers  NFPA 70E, 130.7.C.16, Informational Note #2:  The PPE requirements of this section are intended to protect a person from arc flash and shock hazards. While some situations could result in burns to the skin, even with the protection described in Table 130.7.C.16, burn injury should be reduced and survivable. Due to the explosive effect of some arc events, physical trauma injuries could occur. The PPE requirements of this section do not address protection against physical trauma other an exposure to the thermal effects of an arc flash.  PPE is supposed to be your last line of defense.  How do you feel about sustaining a “survivable” injury?
  • 54. Thank You Tim Cotter, P.E. Staff Engineer Schneider Electric Engineering Services, LLC