LG ELECTRONICS
R410A Refrigerant




       LG ELECTRONICS
R410A Refrigerant Characteristic


  R410A vs R22




                      Item              R-22                      R-410A

                                                             Mixed Refrigerant
            Composition            Mono Refrigerant
                                                            (R32:R125 = 50:50)
            Ozone Depletion
                                       0.0055                        0
            Potential (ODP)
            Global Warming
                                        1700                       1370
            Potential (GWP)
            Saturation Pressure
                                         150                        240
            (at 25℃. Psi)
            Boiling Point (℃)           -40.8                      -51.4
                                    No change in
            Leakage                                        Composition changes
                                    composition
                                   Liquid/Gas/Both        Must be charged in liquid
            Recharging
                                     (Liquid+Gas)                  state


                                         LG ELECTRONICS
R410A Temperature-Pressure Chart

       How its different from R22?
 A temperature-pressure chart can easily be used for charging, refrigerant cycle
   analysis and diagnosis.
 R410A is 1.6 times higher vapor pressure than R-22 when saturated.


                                                                     Caution during installation :
  Temp R410A    R22              Temp     R410A              R22
  -40°     26                      20°      210                132            HIGH PRESSURE
                                                                                  R410A
   15
                                   25°      240                150                         1.6 times higher
  -35°        32
       19                          30°      275               173                             than R22

  -30°     40                      35°      312                196
   24                              40°      353                222
                                                                       Problem :

  -25°     48                      45°      397                250                        High possibility of
   30                                                                                       gas leakage
  -20°     58                      50°      446                282
   35                              55°      500                315
                                                                       Solution :
  -15°     70                      60°      556                352
   43                                                                                 Larger flare size
                                   65°      618                392
  -10°     84                                                                                    R410A
   51                              70°      686                435
                                                                                                R22
  -5°     100                      75°       -                 480
   61
  0°      118                               LG ELECTRONICS
R410A Procedure

        Why its different from R22?
 R410A must be charged in liquid state.
 It’s a mixed refrigerant, if charging in vapor state the composition might changed.



      Why?                                                              Right procedure :
                       Open                  
                                              Open



             Gas                      Gas



         Liquid                  Liquid




                     Mono              Mixed  Different ratio
                   Refrigerant

      Caution during installation :
         Charge R410A cylinder in upright position to avoid loss in performance.


                                                     LG ELECTRONICS
R410A Special Tool

         Why its different from R22?
 As pressure is high,it is impossible to measure using conventional gauge,
 To increase pressure resisting strength,hose materials and port size are different.



                 New Tools             Applicable to R22                        Changes

      Gauge Manifold                                               High Pressure : R410A 0.1 ~ 5.3 MPa
                                       X                           (R22 ~ 3.5 MPa)
                                                                   Low Pressure : R410A 0.1 ~ 3.8 MPa
                                                                   (R22 ~ 1.7 MPa)
      Charge Hose                                                  R410A : 1/2 UNF 20 threads per inch
                                       X                           (R22 : 7/16 UNF)
                                                                   R410A : 5.1 Mpa (51 kgf/ ㎠ )
                                                                   (R22 : 3.4 Mpa (34 kgf/ ㎠ ))
      Vacuum Pump                                                  Pumps used with CFC and HCFC
                                       X                           charged systems may also be used
                                                                   on R410A systems



    Caution during installation :
        DO NOT mix refrigerants in your tools.
               Dissimilar oils will become
        contaminated.
                                                  LG ELECTRONICS
R410A Lubrication

     Why its different from R22?
 The chemistry of R-410A makes it incompatible with mineral based lubricants
 The preferred lubricants are the Polyolester or Ether based oils.
  Exposure to the atmosphere must be limited.




                                           
                Esther oil                  Ether oil               Mineral oil
   Caution during installation :
      The oil is miscible, so it is very important to remove as much particulates
        and moisture from the system  Vacuum MUST be performed.
             Moisture can be absorb very easily.
                                                 LG ELECTRONICS
General Operation Logic




          LG ELECTRONICS
Basic Mode Controls


 Modo de refriamento :                                        Modo Aquecimento:

     Temp.                3min                                          Temp.
                                                                                                      Thermo OFF
                                          Thermo OFF             +4℃
  +0.5℃
                                                                 +2℃                                  Thermo ON
Set temp.
                      1)                   Thermo ON
  -0.5℃                                                   Set temp.
  -1.5℃
                           2)
   Comp.     High ↔ Low         Comp Off High ↔ Low             Comp. High ↔ Low Comp Off High ↔ Low Comp Off
   Frequency                                                    Frequency
    O operacional Hz depende da condição de carga, como a diferença entre a temperatura ambiente e
    conjunto ou restrições de frequência.

    • Após compressor está desligado, pode reiniciar novamente em 3 minutos o tempo de atraso > proteger
    condição compressor

    • No modo de resfriamento há dois casos quando o compressor está desligado (ver gráfico sup.)
      1)Em quanto ΔTroom-set is lower than 0.5℃ for 3mins continuously or
      2) when ΔTroom-set is lower than 1.5 ℃.

    • No modo de aquecimento, quando ΔTroom Maior Conjunto E fazer Que 4 ℃, compressor Ira Parar de
    trabalhar Há
       e começar de novo quando ΔTroom conjunto-é inferior a 2 ℃.

    • Por quê? Para garantir a capacidade de arrefecimento / aquecimento ideal

                                                       LG ELECTRONICS
Basic Mode Controls


 Compressor Frequency Restriction :

   • Uma das restrições de frequência é muitas limite de temperatura exterior.
   • Isto significa que o máximo de trabalho Hz para o compressor é limitada pelo ambiente exterior
       temperature. Por quê? para proteger o compressor e manter responsabilidade do produto.




                  Outdoor Temp        Resfriament       Outdoor Temp (℃)     Aquecimento
                      (℃)                  o                                 (Max Step)
                                      (Max Step)
                  Outdoor ≤ 0              3                 Outdoor ≤ -7        16
                 0< Outdoor ≤10            3               -7< Outdoor ≤-2       15
               10< Outdoor ≤ 23            4              -2< Outdoor ≤ 4        13
               23< Outdoor ≤ 30            10             4< Outdoor ≤ 10        11
                30< Outdoor ≤40            12             10< Outdoor ≤21        11
                46< Outdoor ≤10            8              21< Outdoor ≤27         5
                  46< Outdoor              7                  27< Outdoor         3




                                                 LG ELECTRONICS
Basic Mode Controls
 Defrosting Control :
 •Durante o modo de aquecimento, o ciclo é invertido para o ciclo de aquecimento para descongelar o
 evaporador
   tubo da unidade exterior. Por quê? Para proteger o tubo da unidade exterior do congelamento.
 • Em desgelo controle, a amostra. é, que a ventoinha interior, ventilador ao ar livre, ea válvula de 4 vias
 estão fora.
 • Durante a descongelação, o min. temp. do tubo interior é medido e é comparado com o
   apresentar temp. do tubo interior para obter a diferença de que a temperatura interior. (Se a diferença
 for
   5 ℃ ou superior, controlo de descongelação é completada e no modo de aquecimento é levada a cabo
 de novo)                                                    Heating Cycle
                                                                                         HOT START
                                                                                              End            Max Temp
                                             Max Temp        (40 minutes)



                                                                              ΔTmax

                                                                  Defrost
                        Pipe Temp                                 Start

                                                                                                 Defrost
                                                                                                 End
                        Intake Air.
                                                                                                     ΔTmin=5℃ Over
                         Temp                                Min Temp

                                                                               Defrost
                                                                               Time


                        Compressor                                       ON
                        Outdoor Fan               ON                             OFF                    ON
                        Indoor Fan                ON                             OFF                    ON
                        4_way Valve               ON                             OFF                    ON


                                                        LG ELECTRONICS
Basic Mode Controls

 Hot Start Operation :

 • Durante o início de funcionamento de aquecimento, este sistema foi concebido para evitar que o ar frio
 a partir de serem descarregados,
   enquanto espera depois de atingir uma certa temperatura (desta vez, ventilador interno está desligado).
   Após a temperatura interior do tubo atinge 28 ℃ (opção), o ar quente vai sair na seguinte ordem da
 velocidade do ventilador
   Velocidade baixa velocidade do ventilador -> definido pelo controle remoto
 • O diagrama de funcionamento é como a seguir




                    Pipe Temp
                    (Indoor)       Pipe Temp(Indoor)

                    28℃(Option)



                    20℃(Option)




                     Compressor                                        ON
                     Outdoor Fan                                       ON
                    Indoor Fan           STOP          LOW         Set Fan Speed   STOP   LOW   Set Fan Speed

                    4_way Valve                                        ON




                                                             LG ELECTRONICS
Basic Mode Controls

 Sleep Timer Operation :

      • A temperatura de regulação será automaticamente aumentada de 1 ℃ 30 minutos
        mais tarde, e por 2 ℃ 1 hora mais tarde (arrefecimento / desumidificação saudável)
      • A operação será interrompida depois (1,2,3,4,5,6,7: opção) horas

      • Indoor fan control :
             - cooling/ Healthy Dehumidification/ Auto Mode          ▶   Low speed
             - Heating/Auto Mode ▶ Mid speed


 Auto Change over Operation :

      •O condicionador de ar muda automaticamente o modo de funcionamento de arrefecimento ou
      com aquecimentoou aquecimento para o arrefecimento para manter a temperatura da sala interior
      constante.
      •Quando temp. variar ao longo ± 2 ℃, ar condicionado mantém a temperatura ambiente. em ± 2
      ℃ com
        respeitar para ajustar a temperatura, alterando o modo de arrefecimento ou com aquecimento e
      vice-versa.
 Healthy Dehumidification Operation :

  • Quando a entrada de operação de desumidificação pelo controle remoto é recebido,
     a temperatura do ar de admissão é detectada ea temperatura ambiente é automaticamente ajustado
    de acordo a temperatura do ar de admissão.


                                                LG ELECTRONICS
Basic Features


 Different angle of vane for each operation mode:


   • Isto é especialmente concebido para proporcionar o fluxo de ar ideal durante cada operação.

   • Como o ar frio é mais pesado que o ar quente na mesma umidade. Assim, o fluxo de ar é gerado
   por o lançamento de mais pesado do ar
   • Usando o mesmo princípio, é por isso que o ângulo de palhetas do modo de resfriamento é
   maior do que o modo de aquecimento.



     Mode           Cooling / Dehumidification                  Heating        Defrost / AutoClean




   Remote Control
      Display
                               /                                                       /



                                                    LG ELECTRONICS
Processo de instalação.




         LG ELECTRONICS
Installation Work Flow

                               Fixing             Drilling      Setting      Setting
     Installation Location   Inst. Plate           Hole         Indoor       Outdoor


                                                               Standard       Flare
         Piping Work         Precautions         Processing
                                                                Length        Fitting
                                                  Welding/
                               Joints
                                                  Brazing


     Electric Wiring Work                         Connecting     Improper
                             Wiring Spec
                                                     Wire          Case


       Insulation Work       Wrapping Pipe & Drain



           Vacuum             Leak Test            Vacuum       Recharging     Finishing



        Finishing Job                                             Checking
                               Indoor               Outdoor
                                                                  Drainage


          Trial Run                                                Basic
                             Check Point          Symptoms
                                                                   Logic

                                LG ELECTRONICS
Fluxo de instalação de passo a passo principal




 Installation Location                Piping work & Flare Check                  Piping Connection




               Electric Wiring Work                                Insulation         Vacuuming




      Test Run                 Check : Pressure, voltage, current and temperature difference

                                                  LG ELECTRONICS
Installation Tools

 Some of the tools used on R22 systems may be unacceptable for use on R410A.

          Figure                     Name                             Figure            Name

                             Screw driver, Spanner                                  Vacuum pump


                                                                                     Multi-meter
                            Measuring tape, Knife



                             Pincher plier, Nipper                                  Ampere_meter



                              Hexagonal wrench                                 Manifold Gauge for R410A



                                 Hole core drill                                     Thermometer



                                   Vinyl tape                                       Flaring tool set



                            Ladder, Horizontal Level                                 R410A tank




                                                     LG ELECTRONICS
Installation Location




        LG ELECTRONICS
Iocal de instalação/ Selecting Best Location
    How?                                                                  Why?
   Make sure there is no heat or steam around                            Reduce cooling capacity.
  indoor unit.                                                            Cause low performance.
   Make sure heat radiation from condenser is not                        Prevent noise problem.
  blocked.
   Place where noise & vibration are minimum.
    Indoor & Outdoor Unit Space Requirement :
     Unit : mm                                                                       Unit : mm
                                                                                                 More than 300
                             More than 200                           More than 300
      More than
      100


                                             More than
                                               100
                                                                                                                 More than 600
                                                                     More than 700
                     More than 2300


    Case of field defect :
                                                                                                         •Blocked in/outlet
                                                                                                          air flow
                                                                                                         Low performance




    •Limited inlet airflow       •Difficult when servicing
      Low cooling
                                                         LG ELECTRONICS
Installation location / Selecting Best Location

   Case of field defect :                                               Tips :

       Outdoor unit is installed on top of each other without             When installing the unit at a high place be sure
        safely anchoring the unit.                                          to fix the unit legs (safety precautions)
         Noise/vibration                                                  Consider enough space for service when
         Hard to service
                                                                            installing outdoor unit.
         Safety issues


                                                                 



                                                               


                                                       LG ELECTRONICS
Installation location / Selecting Best Location

   Case of field defect :                                                  Tips :

    Hot discharge air will enter the unit cause a work                         Always consider enough space when
     overload and starts OLP system(On/Off)                                      installing outdoor unit.
     Low Performance                                                           Avoid small installation places as possible.



                                                                                                
                  ~


          ~
                   ~
                   ~
         ~
         ~
           discharge air


    Inlet airflow to condenser is blocked                                      Always follow the given space requirement
     Operating pressure will be high and the unit may
                                                                                    when selecting install location.
        repeatedly on-off resulting in low Cooling/Heating


                                                                                                            

                                                          LG ELECTRONICS
Installation location / Selecting Best Location

   Cases of field defect :                                      Tips :
     Inlet airflow to evaporator is blocked                     Where inlet/outlet airflow is not blocked.
       product low cooling/heating                               Low cooling performance.
       noise might occurs                                        Always follow the space requirements
                                                                   to prevent such cases.

                                                                        Space Requirements for Indoor Unit




                                         




                                               LG ELECTRONICS
Installation location / Selecting Best Location

   Cases of field defect :                                                  Tips :

     Indoor unit is installed too high.                                     Where inlet/outlet airflow is not blocked.
       Discharge air can not be fully distributed to user.                   Low cooling performance.
       Low cooling/heating                                                   Always follow the space requirements
                                                                               to prevent such cases.

                                                                             Consider safety, servicing space when
                                                                               selecting installation place.



                                                                          Unproper unit installation place.
          3.5 M.                                                            Difficult during servicing


                                                                                 
     Unproper unit installation place.
       Safety issues


                                                                               

                                                        LG ELECTRONICS
Installation location / Fixing Installation Plate
    How?                                                                            Why?
  Select strong and solid wall.                                                    Prevent vibration and unit fall off 
  Measure the wall and mark the centerline.                                        damage.
  Horizontally align the plate centerline using                                    Easy wiring and piping through the wall.
 horizontal level                                                                   If unit is slanted, water leakage may
   Work Process :                                                                   occurs.

                                         Place level on a raised tab
                          Unit Outline                                               Fixing point



           Left rear

           piping hole   Φ70                                            Φ70
                                                                                  Right rear
                                                                                                           Measuring & leveling
                                         Center hole                              piping hole




   Case of field defect :
             • Product fall off            • Bad fixing plate Noise!                       • Horizontally misalign  Water leakage




                                                                 LG ELECTRONICS
Installation location / Drilling Hole
    How?                                                              Why?
  Select strong and solid wall.                                      Prevent vibration and unit fall
  Drill the piping hole with a ø70mm hole core drill.                offdamage.
                                                                      Easy wiring and piping through the wall.
  Drill at either right or left with the hole                        Slanted to outdoor to ensure proper water
 slightly slanted
   Work Process :                                                     flow.

                • Reference for dimensions   Product Size

   Left rear

  piping hole    Φ70                          Φ7
                                                         Right rear
                                              0
                                                        piping hole




                                                   • Slightly slanted to outdoor side.
                                                      Why?Ensure water properly flow in downward
                                                      direction.




                                                 LG ELECTRONICS
Installation location / Settling Indoor Unit
    How bend the pipe properly?                                 Why?
  Hold and press at the corner of the piping.                  Use it as a center of rotation to prevent
  When bending downward or to the left side, do it             damage.
 gently.                                                        Prevent damage to pipe which can cause cycle
                                                                blocking.
   Work Process :
                                       Slowly unfold the pipe
   Hold at the corner of piping                                            Bend to the left side slowly
                                               downward




   Case of field defect :
                                               • Damage indoor piping during bending.
                                                Clogged refrigerant cycle




                                               LG ELECTRONICS
Installation location / Settling Indoor Unit
    How?                                                        Why?
  Drill the wall if customer wants the piping through          Customer satisfaction.
 the wall.                                                      Sufficient space for easy piping.
  Use the tubing holder when bending the pipe for              Piping may get damagedclogged
 connecting.                                                    cycle.
 Work Process :be extra careful when bending the pipe.
    Make sure to

           Detach the                     Hang the unit &                               Position
            Chassis                        unlock tubing                              the pipe for
              bottom                           holder                                  connection




   Caution :

                                                                • Make sure the unit and install plate are
                                                                  just in the right position and stable.
                                                                 Unit might fall off during working.




                                               LG ELECTRONICS
Installation location / Settling Outdoor Unit
   How?                                                                    Why?
  Secure the unit with an anti-vibration damper.                          Prevent the vibration to the unit
  Secure the unit with nail or wire  strong wind or                      Product fall offdamage
 earthquake.                                                               Prevent from product or part
  If install site is close to seaside, avoid direct                       corrosion.
 exposure.
   Work Process :
                                • Anchor the unit with a bolt & nut               • Set up a wind breaker
                 Nut
                                                                                      Windbreak
                                                                                                     
                 Washer
                 Leg                                                                 Sea wind
                 Damper                                                                      
                 Angle




  Case of field defect :

     • Unstable  Fall off   • No damper  Vibration               • Corrosion due to sea windpart malfunction




                                                  LG ELECTRONICS
Piping work




    LG ELECTRONICS
Piping Work
    How?                                                                  Why?
   Do not use collapsed,deformed or discolored copper                    Expansion valve may become blocked.
  pipe.                                                                   Pipe may get damaged during flaring work .
   Never use copper pipes thinner than 0.8mm.

   Precaution :                                                          Selecting Copper Pipe :

      • Sealed ends of pipes with a cap until connected.                                            Thickness (mm)
                                                                             Nominal       Outer
      • Avoid piping installation on a rainy day.                            diameter    diameter      R410A
                                                                                           (mm)
      • Carry out the work in short time as possible.
                                                                                 1/4       6.35          0.80
      • Water or dust does not enter the pipe.                                   3/8       9.52          0.80
                                                                                 1/2       12.70         0.80
                                                                                 5/8       15.88         1.00
   Case of field defect :

              After Flaring
                                  • 0.6t Copper Pipe

                                  Condition : Not round shape, Burr exist
                                                        → resulting in egg-shaped flare
                                  work

                                  High possibility of gas leakage
                                                        LG ELECTRONICS
Piping Work / Pipe Flaring Work
   How?                                                          Why?
  Remove the burrs after cutting work.                          Prevent burrs from enteringclogged
  Never use copper pipes thinner than 0.8mm.                    cycle.
                                                                 Pipe may damage during flaring work .

   Work Process :


           Cutting the pipe                Burr removal                       Place the pipe




           Tighten the clamp            Apply the torque                   Finish & check flare




                                                LG ELECTRONICS
Piping Work / Pipe Flaring Work


   Flaring Position :             The use of flare clutch type is preferable.
                                   ⓐ(inc        ⓐ(m          R410A / ⓑ (mm)
                                    h)           m)
                                                        Clutch type     Wing nut type


                                     1/4        6.35     1.1 ~ 1.3        1.5 ~ 2.0

                                     3/8        9.52     1.5 ~ 1.7        1.5 ~ 2.0
                                     1/2       12.70     1.6 ~ 1.8        2.0 ~ 2.5
                                     5/8       15.88     1.6 ~ 1.8        2.0 ~ 2.5
            Defect          OK

                                   Checking Flare Work
                                     Compare the flaring work with the figure.
                                     If a flaring section is defective, cut it off
                                   and do
                                        flaring work again.
   Case of field defect :
                                                                     • Improper flaringGas leakage




                                       LG ELECTRONICS
Piping Work / Piping Connection
   How?                                                                Why?
  Make sure that the flare do not have any scar or                    Prevent strange material from entering
 dust, etc.                                                            system.
  Make sure to follow the given applied torque.                       If applied torque is too strong, flare
                                                                       will get damaged.
  Work Process :                                                              Tightening Torque :

        Alignment              Indoor Unit             Outdoor Unit
                                                                                  Outside diameter   Torque
                                                                                   mm        inch    kgf· ㎜
                                                                                  Ø6.35      1/4     1.8~2.5
                                                                                  Ø9.52      3/8     3.4~4.2
                                                                                  Ø12.7      1/2     5.5~6.5
                                                                                 Ø15.88      5/8     6.3~8.2
   • Tighten the flare     • Tighten the flare nut with torque wrench            Ø19.05      3/4     9.9~12.1
     nut by hand.            untill the wrench clicks.

  Case of field defect :
                                                       • Applied torque is too strong
                                                         Flare will get damaged  Gas leakage




                                                      LG ELECTRONICS
Piping Work / Standard Pipe Length
   How?                                                                       Why?
  Always follow the pipe length specification.                               When it is too short, cycle will be
  Always remember to add refrigerant if the pipe                             overloaded.
 length is                                                                    When it is too long, can cause over work
    more than 5m.                                                             at
  Pipe Installation Length : AFTA Model                                       compressor

                                       Pipe Size
                              Gas Φ              Liquid Φ
                                                                                        Max.                  Additiona
                                                                    Standard                       Min/Max
                                                                                     Elevation                    l
                                                                     Length                        Length
          Capacity                                                                                            Refrigera
                                                                       (m)                          (B) (m)
                                                                                      (A) (m)                 nt (g/m)
                            mm        inch      mm      inch


      2.5kW(9kBtu/h)       9.52       3/8      6.35     1/4               5              7          3 / 15       10
      3.5kW(12kBtu/h)      12.7       3/8      6.35     1/4               5              7         3 / 15        10
      5.2kW(18kBtu/h)      12.7       1/2      6.35     1/4               5              7          3 / 20       20
  Case of field defect :
      7.0kW(24kBtu/h)      15.88       5/8      9.52    3/8          5                   7          3 / 20       20
                                   • Short Piping
                                      Refrigerant inflow noise is directly                  (B)
        1m                             transmitted to indoor unit.                                  (A)
                                      Cycle overload.




                                                         LG ELECTRONICS
Piping Work / Pipe Joints Connection
   How?                                                            Why?
   Prior to use, be sure to remove all contaminants.              Prevent from entering the system.
   Used to connect the copper pipes.                              Case of pipe diameter is not the same with
   Connections during brazing work.                               SVC
                                                                   valve diameter.
  Joint Type :
    Flare Joints                                                Socket Joints




     Flare Joints Assembly                                      Socket Joints Assembly




                                               LG ELECTRONICS
Welding / Brazing Guide
    How?                                                               Why?
   Nitrogen should be allowed to flow without building                Prevent from carbon scales clogging.
  up
      a pressure in the pipeline.                                      Safety precautions and to make sure the
   Brazing requires sophisticated techniques, it must                 work is
  be
                                                                       done properly without any leakage.
      performed by qualified person.
   Brazing with Nitrogen :

                                               Turn on the gas                          Continue the flow
    Connect a nitrogen cylinder
                                                       and                            until the joints have
     to one end of the pipework                                                               cooled
                                               regulate the flow
             10 mm↑
                             0.05 ~ 0.12 mm.




   Caution point :                                                             Nitrogen release
                                                                                   .
   Pressure :0.1~0.2kgf/ ㎠
   (1.4~2.8psi)

                                                        .

                                                                    Taping
                                                   LG ELECTRONICS
Welding / Brazing Guide

   Case of field defect :
     Brazing without Nitrogen release :




                                          Problem: Carbon scales clogging filters
                                          Troubles during circulation in a cycle, like clogging EEV,
                                          Compressor, moving parts, piping etc




                                                                       • Pipe frozen  Cycle blocked


                                                LG ELECTRONICS
Elec. wiring Work




       LG ELECTRONICS
Electric Wiring Work
    How?                                                           Why?
   Do not use spliced wires or extension cord.                    Fire or electric shock may occur.
   Inverter product  higher harmonic                             Product or earth leak detector
       Therefore,be sure to install an earth leak                  malfunction.
  detector.
  Indoor & Outdoor Unit Wiring :                                                   Note :

                                                        Terminal Block
              Indoor                                     Remote Controller
                                                              Cable
                                                        Connection Cable
                                                       Cable Retainer

                                                                                       Use end-terminal for
                         Live   Neutral   Connector     Earth                          safety precautions


                                                                                       Excessive strip length
               Outdoor
                                                                                        shock or leakage




                                                  LG ELECTRONICS
Electric Wiring Work / Wire specification
    How?                                                               Why?
   Always follow the wiring & circuit breaker spec.                   Cause abnormal heat/terminal overheating.
  Do not overload the circuit by adding drain pump or                 They may cause overheating or electrical
  other                                                                shock.
      electrical equipment.
  Wire & Circuit Breaker Selection :
     Power Code                Connection Cable                                     Outdoor          Indoor

            10±3mm                     10±3mm




                                                                 Circuit
       GND :20mm                    GND :20mm
                                                                 Breaker
                                     (mm²)                                                                      (A)
                                                                 Earth
                        Grade(kBtu)                                                               Grade(kBtu)
                                                                Leakage
         Cross       9/12      18      24                                            Circuit   9/12       18    24
       -section                                                                      Breaker
                                                              Power Supply
         area
                     1.0      1.5     2.5                                                       15        20    30
  Note :
           Circuit breaker size selection (Refer to Label Quality for current value)
              Normal              : Running current x 1.75
              Inverter            : Running current x 2.0

                                                      LG ELECTRONICS
Electric Wiring Work / Wiring Connection

                                                                            How :
  Indoor Power Supplied Type

                    IN           1(L) 2(N) 3(C)                              Connect the wires between indoor &
                                                                            outdoor
                         Brown          Red                                     units so that the terminal numbers and
                                                   Green/                   colors
   Connection cable                  Blue          yellow                       are matched.
                                                                             Tighten the terminal screws securely.

                 OUT             1(L) 2(N) 3(C)                              Do not extend cable connections.

                                                         Power
                                                          Code
                                                                             Why?
  Outdoor Power Supplied Type                                                If the wires are not matched,
                                                                             communication
               IN                                                            error will occurs CH05,53.
                                        1(L) 2(N) 3(C)
                                                                             If the connection is loosen, electric
                                 Brown               Red        Green/       shock may
                                            Blue                yellow
                                                                             occur.
   Connection cable
                                                                             Extending cable will create noise or
                         (L)   (N)      1(L) 2(N) 3(C)                       electric
                OUT
                                                                             short CH05,53

                         Power Supply


                                                           LG ELECTRONICS
Electric Wiring Work / Wiring Connection

  Case of field defect :                                             Tips :
    Unproper power supply wiring / absent ground wire                 1. Check if there is ground terminal at the plug,
      Heat ignition of terminal block can cause fire                     to prevent electrical short,perform an additional
      Electric shock                                                     3rd grounding at outdoor unit or carry out a
                                                                          separate grounded work.
                                                                         Ground
                                                                         Terminal


        
                                               
                                                                                                       Ground
                                                                                                        Wire

                                                                                   Power
                                                                                    Plug

                                                                        2. Electrical work such as Indoor↔Outdoor
                                                                           connection,earth leakage breaker ground wire
                                                                           must be carried out in accordance with state &
                                                                           local electrical wiring codes.



                                              

                                                                                                   d
                                                                                           Electric
                                                                                           Standar

                                                                                            Code
                                                                                                                 Main Power
                                                                                                                  Switch
                                                                          Ground
                                                                           Wire                                 Earth Leakage
                                                                                                                   Breaker




                                                    LG ELECTRONICS
Electric Wiring Work / Wiring Connection

  Case of field defect :                                           Tips :
    Unproper extended wiring connection
                                                                      Electrical part is not used for only 1~2 years .
      Cable over heat or fire might occur                           Most of time, it will have to endure the same period
      Communication Error CH05 occur(operation stop)                as air conditioner’s lifetime itself.

                                                                      Therefore, temporary dan simple wiring work will
                                                                     only cause likely fire or electrical shock.


                                                                   Extending electric wire;

                                                                     1st layer of insulation :
                                                                     Make sure to solder the wires to reduce the contact
                                                                     resistance and by using thermal contraction tube.

                                                                     2nd layer of insulation :
                                                                     Wrap the connection with insulation tape to prevent
                                                                     exposure to moisture/surrounding



                                
                                                                      


                                                  LG ELECTRONICS
Electric Wiring Work / Wiring Connection

  Case of field defect :                                                Tips :
    Wrong wiring connection during installation of large                 In case like this, make sure to double check that
     numbers of the same model at the same site.                           wiring connection and piping connection are
     Inoperative unit /abnormal operation                                 connected to the same model.




       Room A                     Room B                                   Room A                      Room B




                                                  piping                                   piping



                                                 wiring                                   wiring




                                                       LG ELECTRONICS
Insulation & Drain Work




          LG ELECTRONICS
Insulation & Drain Work / Standard
   How?                                                                  Why?
   Do the insulation after leak test is done.                           Gas leakage must be checked during test
   Bundle the pipe and drain hose together with vinyl                   run.
  tape.                                                                  Prevent possible water leakage.

  Work Process :
     Wrap together refrigerant piping, cable and drain hose with vinyl tape.

                                                        Refrigerant Pipe




                                                                           Drain Hose
                                               Connecting
                                                 Cable

  Caution :   Set the tubing line upward  prevent possible water leakage.
                                                                                        Cutting Line

                                                                                                       
                                                                                                       Cutting Line
                                                                        Gas Pipe   Liquid Pipe

                                                       LG ELECTRONICS
Insulation & Drain Work / Case

Case of field defect :                                            Tips :
  Water leakage at pipe connection due to bad                                     Indoor   Outdoor
   insulation.
   Mold gathers at the wall.                                                                           Insulator
                                                                                                              Extension
                                                                                                                Hose




                                                                    Indoor
                                                                  drain hose

                                                                     Fully insulate the connection part between indoor
                                                                      drain hose & extension hose.

                                                                     If not,leakage may occur as the water will
                                                                      condensate due to temperature changes.


                                                                           Fully insulate drain hose connection!




                                  Mold




                                                 LG ELECTRONICS
Insulation & Drain Work / Water Leak Test
   How?                                                         Why?
   Pour a water to make sure well drainage.                    Prevent water leakage during operation.
   Make sure the route of drainage is done properly.           If the drain hose curled, water leakage
                                                                occurs.

  Checking Drainage :

      Pour a glass of water                Check possible                  Ensure water flows out the
          onto evaporator                      leakage                     drain exit without leakage




  Tips :
             Indoor     Downward Slope
                                                The drain hose should point downward for
                                                 easy drain flow.
                                                Fix drain hose to prevent bending or curling
                                d




           OK!
                            Fixe




                                                Drain hose connection must be easy
                                                 accessible & serviceable!



                                               LG ELECTRONICS
Insulation & Drain Work / Water Leakage Defect

Case of field defect :                                       Tips :

   Drain hose is in upward slanted direction                   Set the drain hose in the downward position
     drain water can not flow to outdoor unit.                   drain water can flow smoothly.

                         Slanted hose
                                                                           Indoor        Downward Slope
      
     Water
    Leakage
                                                                      OK!




                                       

                                                  LG ELECTRONICS
Insulation & Drain Work / Water Leakage Defect


Case of field defect :                                         Tips :

   Curled drain hose will block water flow                        Fix drain hose to prevent bending or curling
     water leaks at indoor unit




                                        
    
   Water                                                                
                                                                        OK!




                                                                                                      d
  Leakage




                                                                                                  Fixe
                                              LG ELECTRONICS
Insulation & Drain Work / Water Leakage Defect


 Case of field defect :                                                   Tips :
     In case of when pipe connection have to be installed                Wrap the area which accommodates the refrigerant
      in upward direction                                                  piping, electric cable,drain hose with vinyl tape in
     Vinyl tape has to be wrapped from bottom to the top!                 Bottom-Up direction!
      Why?Prevent possible leakage to indoor when raining




                                                                                                           Wrap in the
                                                                                                       Bottom-Up direction




                                                        LG ELECTRONICS
Insulation & Drain Work / Water Leakage Defect


 Case of field defect :                                    Tips :

      Water back-flow occurs when the drain line                For every 1m, fix the drain pipe with clip/tie wrap
       is all the way drooping for over 2m
        Water leakage at indoor side


                                                                                                     Clip




                                                                                                              ∝
                                                                                                   1m


                          


                          

                                                    LG ELECTRONICS
Vacuum & Test run




       LG ELECTRONICS
Vacuum / Gas Leak Test
    How?                                                                                Why?
    Top of cylinder must be higher than its bottom.                                    To avoid nitrogen from entering the system.
    Use soap bubble to identify the location of leak.                                  Insufficient gas will reduce the cooling
                                                                                        capacity.
      (flare connection)

   Work Process :
                                                                                                    Charge nitrogen-gas


                      .
                                                            Close                                                         Tightened, repair
                                                                                                                          location of leak
                                     Liquid side
                                                                         .
                                                                                                         Leak test
                                                      2(3)-way                                                            Leakage
                                                                                                      with soap water
                                                        valve                      .
                                       Gas side                                   .
                                                               Close                                    No leakage

                                 Low   High

           Nitrogen
                          Open                Close                                                     Gas release
                                 .                     3-way
                                                       valve
                                                                                                      Go to next step
      Nitrogen-Gas                                                                                      (Vacuum)
        Cylinder



                                                                       LG ELECTRONICS
Vacuum / process-1
    How?                                                                         Why?
   Air evacuation with vacuum pump is a MUST.                                   Air and moisture in system have bad
                                                                                 effects as:
   Liquid and the gas side SVC valves are kept closed.
                                                                                 • Pressure in the system rises.
                                                                                 • Cooling/heating efficiency drops
  Work Process :                                                                                   Vacuum
                                                                                                        15mins

             .                                                                               Check manifold low
                                                     Close
                                                                                             side pressure reach
                                                                                             to 76cmHg(30inHg)      ..
                            Liquid side
                                                                  .
                                               2(3)-way                                                               Tightened,
                                                 valve                                       Close low side valve
                                                                            .                                         repair
                                                                                                 of manifold
                                Gas side                                   .                                          location
                                                                                                                      of leak
                                                        Close
                                                                                              Turn off vacuum
                          Low   High                                                               pump

                   Open                Close
                          . .                   3-way
                                                valve                                      Needle gauge does not
                                                                                            move after 5 minutes.     Leakage

    Vacuum Pump
                                                                                                 No leakage

    Required time for evacuation when 30 gal/h vacuum pump is                               Disconnect vacuum
   used.
                                                                LG ELECTRONICS
Vacuum / Process-2
    How?                                                                          Why?
    Air evacuation with vacuum pump is a MUST.                                   Air and moisture in system have bad
                                                                                  effects as:
    Liquid and the gas side SVC valves are kept closed.
                                                                                  • Pressure in the system rises.
                                                                                  • Cooling/heating efficiency drops
   Work Process :
                                                                                                   Vacuum

                                                                                                         15mins
             .
                                                       Close
                                                                                               Check Vacuum            Tightened,
                             Liquid side                                                           gauge               repair
                                                                   .
                                                                                              pressure reach to        location
                                                2(3)-way                                         760 mmHg              of leak
                                                  valve                      .
                                 Gas side                                   .                   Close both side
                                                         Close                                 valve of manifold   Leakage

                           Low   High

                    Open                 Open                                                    No leakage
                           . . .                 3-way
                                                 valve
                                                                                                 Turn off the
                                                                                                vacuum pump
    Vacuum Pump                         Vacuum gauge

                                                                                             Disconnect vacuum
   Required time for evacuation when 30 gal/h vacuum pump is
  used.
                                                                 LG ELECTRONICS
Vacuum / Finishing Vacuum Work
   How?                                                                             Why?
  Now, the gas is ready to be released to the system.                              Gas leakage must be checked during test
  Be sure to mount all the caps onto 2way & 3way SVC                               run.
 valve                                                                              Prevent small possible leakage in future
                                                                                    use.
  Work Process :
                                                                                                  Disconnect the manifold from
                                                                                                        the vacuum pump
                                                                                                   and from the service port of
            .                                                                                               3way valve
                                                        Open

                             Liquid side
                                                                     .
                                                2(3)-way
                                                  valve                        .                    Position both of the SVC
                                 Gas side                                     .                     valves to “Open” using a
                                                            Open                                    hexagonal wrench(4mm)

                           Low   High

                   Close                Close                                                      Mount valve caps onto the
                           . . .                    3-way                                          2way valve and the 3way
                                                    valve                                                    valve
                                                .
   Vacuum Pump
                                                                                                          Gas Release




                                                                   LG ELECTRONICS
Vacuum / Additional Refrigerant
   How?                                                                         Why?
   Charge in standing upright position.                                        Charging 410A must be in liquid state for
   Before recharging, check whether the cylinder has a                         right
     siphon or not.                                                             composition  effect such as low cooling.


  Work Process :
                                                                                                   Connect gas cylinder
                                                                                                       to manifold

              .
                                                     Close
                                                                                                      Open Gas side
                            Liquid side                                                                 SVC valve
                                                                 .
                                               2(3)-way
                                                 valve                                                 Balance zero
                                                                           .                             setting
                                Gas side                                  .
   Upright                                              Open
   Position                                                                                        Open low side valve
                          Low   High                                                                of manifold slowly

                   Open                Close
                          . . .                 3-way
                                                                                                Until target weight is reached
                                                valve

   Balance                                                                                         Close low side valve
                                                                                                       of manifold

   Refer manual Installation for gas weight(g) / pipe
   length(m)
                                                               LG ELECTRONICS
Test Run
    How?                                                              Why?
    Press “On/Off” button and hold for 3~6 secs.                     To enter a mode that is specially designed
                                                                      for Test Run.
    Check operating pressure,current, voltage etc.
                                                                      Ensure the product work properly or not.


   Test Run Operating Logic :
                                   In this mode, regardless of the outside temperature, the unit will operate
                                   for 18±1 minute in below conditions:

                                   -Cooling Mode                             -Indoor Fan High RPM

                   ON/OFF
                                   -Thermal On/Comp On                       -Vertical Auto Swing Airflow
                    Button
                                   - Comp. fixed frequency

   Check Items :
   1. Measure the temperature of the intake & discharge air.

                                                                     Ensure the difference between the intake
                                                                       & discharge temp. is more than
                                                                       8℃ (Cooling) & 14℃(Heating)




                                                   LG ELECTRONICS
Test Run

   Check Items :

 2. Measure the pressure of the gas side service valve.

                                                                 Outside   Pressure of the gas
                                               Refri.            ambient
                                                                  TEMP     Side Service valve.

                                                                            8.5~11.2 ㎏ / ㎠ G
                                              R410A          35℃(95℉)
                                                                            (120~160 P.S.I.G)




   If the pressure is drop or significantly     higher than specification:

                         Pressure is low:                                       Pressure is high:
                         Gas leakage / insufficient                             System is overloaded
                                                                                Possibility of overcharge
                                                                                Closed SVC valve - Recheck



                           Recheck gas leak


                                                LG ELECTRONICS
Test Run

    Check Items :
 3. Measure the voltage & operating current.(Refer to Label Quality for specification)




               Power supply voltage/current complied with the rated value


    Other Check Items :

                     Check Items                          Symptom       Check
           Indoor & Outdoor units are      Fall, vibration, noise
           installed on solid bases.
           System is properly ground to    Electrical leakage
           earth
           Wiring connection               Inoperative or error code
                                           05
           Drain line is properly          Water leakage
           installed

                                              LG ELECTRONICS

Contenu connexe

Tendances

Sweetening and sulfur recovery of sour associated gas and lean acid gas in th...
Sweetening and sulfur recovery of sour associated gas and lean acid gas in th...Sweetening and sulfur recovery of sour associated gas and lean acid gas in th...
Sweetening and sulfur recovery of sour associated gas and lean acid gas in th...Frames
 
A presentation on reformer new
A presentation on reformer newA presentation on reformer new
A presentation on reformer newGowri Shankar
 
Natural Gas Processing - Magnetrol
Natural Gas Processing - MagnetrolNatural Gas Processing - Magnetrol
Natural Gas Processing - MagnetrolBenjamin Kyalo
 
Air liquide lurgi 2016 overview of coal heavy oil ch4 to syngas h2 ammonia me...
Air liquide lurgi 2016 overview of coal heavy oil ch4 to syngas h2 ammonia me...Air liquide lurgi 2016 overview of coal heavy oil ch4 to syngas h2 ammonia me...
Air liquide lurgi 2016 overview of coal heavy oil ch4 to syngas h2 ammonia me...Steve Wittrig
 
Feedstock Purification Flowsheet Options
Feedstock Purification Flowsheet OptionsFeedstock Purification Flowsheet Options
Feedstock Purification Flowsheet OptionsGerard B. Hawkins
 
Transformer Maintenance
Transformer Maintenance Transformer Maintenance
Transformer Maintenance Molla Morshad
 
Ammonia plant fundamentals
Ammonia plant fundamentalsAmmonia plant fundamentals
Ammonia plant fundamentalsPrem Baboo
 
Fischer-Tropsch Catalysts: Preparation, Thermal Pretreatment and Behavior Du...
Fischer-Tropsch Catalysts: Preparation, Thermal Pretreatment and Behavior Du...Fischer-Tropsch Catalysts: Preparation, Thermal Pretreatment and Behavior Du...
Fischer-Tropsch Catalysts: Preparation, Thermal Pretreatment and Behavior Du...Gerard B. Hawkins
 
Bp31250253
Bp31250253Bp31250253
Bp31250253IJMER
 
VULCAN VGP-1000 High Temperature Mn Sulfur Guard Technology
VULCAN VGP-1000 High Temperature Mn Sulfur Guard TechnologyVULCAN VGP-1000 High Temperature Mn Sulfur Guard Technology
VULCAN VGP-1000 High Temperature Mn Sulfur Guard TechnologyGerard B. Hawkins
 
Various ammonia technology
Various ammonia technologyVarious ammonia technology
Various ammonia technologyPrem Baboo
 
Naphtha Characterization and Hydrodesulfurization
Naphtha Characterization and HydrodesulfurizationNaphtha Characterization and Hydrodesulfurization
Naphtha Characterization and HydrodesulfurizationGerard B. Hawkins
 
Important Conversion Factors in Petroleum Technology
Important Conversion Factors in Petroleum Technology Important Conversion Factors in Petroleum Technology
Important Conversion Factors in Petroleum Technology Muhammed Fuad Al-Barznji
 
Methanol Steam Reforming in Pd-Ag Membrane Reactor for High Purity Hydrogen G...
Methanol Steam Reforming in Pd-Ag Membrane Reactor for High Purity Hydrogen G...Methanol Steam Reforming in Pd-Ag Membrane Reactor for High Purity Hydrogen G...
Methanol Steam Reforming in Pd-Ag Membrane Reactor for High Purity Hydrogen G...sameer_israni
 
VULCAN Xc 300 Jet Fuel Sweetening Technology
VULCAN Xc 300 Jet Fuel Sweetening TechnologyVULCAN Xc 300 Jet Fuel Sweetening Technology
VULCAN Xc 300 Jet Fuel Sweetening TechnologyGerard B. Hawkins
 
VULCAN VGP CRT Chloride Guard Technology
VULCAN VGP CRT Chloride Guard TechnologyVULCAN VGP CRT Chloride Guard Technology
VULCAN VGP CRT Chloride Guard TechnologyGerard B. Hawkins
 

Tendances (20)

Sweetening and sulfur recovery of sour associated gas and lean acid gas in th...
Sweetening and sulfur recovery of sour associated gas and lean acid gas in th...Sweetening and sulfur recovery of sour associated gas and lean acid gas in th...
Sweetening and sulfur recovery of sour associated gas and lean acid gas in th...
 
A presentation on reformer new
A presentation on reformer newA presentation on reformer new
A presentation on reformer new
 
Ammonia converter
Ammonia converterAmmonia converter
Ammonia converter
 
Natural Gas Processing - Magnetrol
Natural Gas Processing - MagnetrolNatural Gas Processing - Magnetrol
Natural Gas Processing - Magnetrol
 
Air liquide lurgi 2016 overview of coal heavy oil ch4 to syngas h2 ammonia me...
Air liquide lurgi 2016 overview of coal heavy oil ch4 to syngas h2 ammonia me...Air liquide lurgi 2016 overview of coal heavy oil ch4 to syngas h2 ammonia me...
Air liquide lurgi 2016 overview of coal heavy oil ch4 to syngas h2 ammonia me...
 
Feedstock Purification Flowsheet Options
Feedstock Purification Flowsheet OptionsFeedstock Purification Flowsheet Options
Feedstock Purification Flowsheet Options
 
Transformer Maintenance
Transformer Maintenance Transformer Maintenance
Transformer Maintenance
 
Ammonia plant fundamentals
Ammonia plant fundamentalsAmmonia plant fundamentals
Ammonia plant fundamentals
 
Fischer-Tropsch Catalysts: Preparation, Thermal Pretreatment and Behavior Du...
Fischer-Tropsch Catalysts: Preparation, Thermal Pretreatment and Behavior Du...Fischer-Tropsch Catalysts: Preparation, Thermal Pretreatment and Behavior Du...
Fischer-Tropsch Catalysts: Preparation, Thermal Pretreatment and Behavior Du...
 
Bp31250253
Bp31250253Bp31250253
Bp31250253
 
VULCAN VGP-1000 High Temperature Mn Sulfur Guard Technology
VULCAN VGP-1000 High Temperature Mn Sulfur Guard TechnologyVULCAN VGP-1000 High Temperature Mn Sulfur Guard Technology
VULCAN VGP-1000 High Temperature Mn Sulfur Guard Technology
 
Various ammonia technology
Various ammonia technologyVarious ammonia technology
Various ammonia technology
 
Naphtha Characterization and Hydrodesulfurization
Naphtha Characterization and HydrodesulfurizationNaphtha Characterization and Hydrodesulfurization
Naphtha Characterization and Hydrodesulfurization
 
C3 Technology - When and How to Use
C3 Technology - When and How to UseC3 Technology - When and How to Use
C3 Technology - When and How to Use
 
Important Conversion Factors in Petroleum Technology
Important Conversion Factors in Petroleum Technology Important Conversion Factors in Petroleum Technology
Important Conversion Factors in Petroleum Technology
 
SYNGAS production
SYNGAS productionSYNGAS production
SYNGAS production
 
Methanol Steam Reforming in Pd-Ag Membrane Reactor for High Purity Hydrogen G...
Methanol Steam Reforming in Pd-Ag Membrane Reactor for High Purity Hydrogen G...Methanol Steam Reforming in Pd-Ag Membrane Reactor for High Purity Hydrogen G...
Methanol Steam Reforming in Pd-Ag Membrane Reactor for High Purity Hydrogen G...
 
VULCAN Xc 300 Jet Fuel Sweetening Technology
VULCAN Xc 300 Jet Fuel Sweetening TechnologyVULCAN Xc 300 Jet Fuel Sweetening Technology
VULCAN Xc 300 Jet Fuel Sweetening Technology
 
VULCAN VGP CRT Chloride Guard Technology
VULCAN VGP CRT Chloride Guard TechnologyVULCAN VGP CRT Chloride Guard Technology
VULCAN VGP CRT Chloride Guard Technology
 
DPD.PPT
DPD.PPTDPD.PPT
DPD.PPT
 

Similaire à Treinamento da tecnologia invert

Refrigeranti a basso GWP per il condizionamento e le pompe di calore - B. Bel...
Refrigeranti a basso GWP per il condizionamento e le pompe di calore - B. Bel...Refrigeranti a basso GWP per il condizionamento e le pompe di calore - B. Bel...
Refrigeranti a basso GWP per il condizionamento e le pompe di calore - B. Bel...Centro Studi Galileo
 
ART RS-45 Brochure
ART RS-45 BrochureART RS-45 Brochure
ART RS-45 BrochureRoger Tello
 
Bock HG Compressors – R410A
Bock HG Compressors – R410ABock HG Compressors – R410A
Bock HG Compressors – R410AGEA Bock GmbH
 
Bachir Bella - Emerson Climate Technologies - REFRIGERANTI A BASSO GWP IN APP...
Bachir Bella - Emerson Climate Technologies - REFRIGERANTI A BASSO GWP IN APP...Bachir Bella - Emerson Climate Technologies - REFRIGERANTI A BASSO GWP IN APP...
Bachir Bella - Emerson Climate Technologies - REFRIGERANTI A BASSO GWP IN APP...Centro Studi Galileo
 
Aicarr vicenza 2016 emerson
Aicarr vicenza 2016 emersonAicarr vicenza 2016 emerson
Aicarr vicenza 2016 emersonVenu Kandi
 
Presentation_Power_Transformers-1
Presentation_Power_Transformers-1Presentation_Power_Transformers-1
Presentation_Power_Transformers-1Nageswar Rao
 
DESIGN AND ANALYSIS OF ALTERNATIVE AZEOTROPE REFRIGERANT
DESIGN AND ANALYSIS OF ALTERNATIVE AZEOTROPE REFRIGERANTDESIGN AND ANALYSIS OF ALTERNATIVE AZEOTROPE REFRIGERANT
DESIGN AND ANALYSIS OF ALTERNATIVE AZEOTROPE REFRIGERANTIRJET Journal
 
Thermal cracking (2)
Thermal cracking (2)Thermal cracking (2)
Thermal cracking (2)Kumar
 
Scroll compressors for propane (R290)
Scroll compressors for propane (R290)Scroll compressors for propane (R290)
Scroll compressors for propane (R290)Venu Kandi
 
Sergio Bobbo - CNR DI PADOVA - APPLICAZIONI DEI NANOFLUIDI
Sergio Bobbo - CNR DI PADOVA - APPLICAZIONI DEI NANOFLUIDISergio Bobbo - CNR DI PADOVA - APPLICAZIONI DEI NANOFLUIDI
Sergio Bobbo - CNR DI PADOVA - APPLICAZIONI DEI NANOFLUIDICentro Studi Galileo
 
ammonia National Fertilizer Limited Bathinda
ammonia National Fertilizer Limited Bathindaammonia National Fertilizer Limited Bathinda
ammonia National Fertilizer Limited BathindaDngL611667
 
XVI CONVEGNO EUROPEO H. Dhont - Refrigerant R32 for air conditioners and heat...
XVI CONVEGNO EUROPEO H. Dhont - Refrigerant R32 for air conditioners and heat...XVI CONVEGNO EUROPEO H. Dhont - Refrigerant R32 for air conditioners and heat...
XVI CONVEGNO EUROPEO H. Dhont - Refrigerant R32 for air conditioners and heat...Centro Studi Galileo
 
Ammonia production from natural gas, haldor topsoe process
Ammonia production from natural gas, haldor topsoe processAmmonia production from natural gas, haldor topsoe process
Ammonia production from natural gas, haldor topsoe processGaurav Soni
 
Testo 550 datasheet 2012
Testo 550 datasheet 2012Testo 550 datasheet 2012
Testo 550 datasheet 2012Testo Limited
 
Ammonia Plant - Methanation Operations
Ammonia Plant - Methanation OperationsAmmonia Plant - Methanation Operations
Ammonia Plant - Methanation OperationsGerard B. Hawkins
 
Refrigerant ppt
Refrigerant pptRefrigerant ppt
Refrigerant pptdineshucer
 

Similaire à Treinamento da tecnologia invert (20)

Refrigeranti a basso GWP per il condizionamento e le pompe di calore - B. Bel...
Refrigeranti a basso GWP per il condizionamento e le pompe di calore - B. Bel...Refrigeranti a basso GWP per il condizionamento e le pompe di calore - B. Bel...
Refrigeranti a basso GWP per il condizionamento e le pompe di calore - B. Bel...
 
ART RS-45 Brochure
ART RS-45 BrochureART RS-45 Brochure
ART RS-45 Brochure
 
Bock HG Compressors – R410A
Bock HG Compressors – R410ABock HG Compressors – R410A
Bock HG Compressors – R410A
 
Bachir Bella - Emerson Climate Technologies - REFRIGERANTI A BASSO GWP IN APP...
Bachir Bella - Emerson Climate Technologies - REFRIGERANTI A BASSO GWP IN APP...Bachir Bella - Emerson Climate Technologies - REFRIGERANTI A BASSO GWP IN APP...
Bachir Bella - Emerson Climate Technologies - REFRIGERANTI A BASSO GWP IN APP...
 
Aicarr vicenza 2016 emerson
Aicarr vicenza 2016 emersonAicarr vicenza 2016 emerson
Aicarr vicenza 2016 emerson
 
Presentation_Power_Transformers-1
Presentation_Power_Transformers-1Presentation_Power_Transformers-1
Presentation_Power_Transformers-1
 
DESIGN AND ANALYSIS OF ALTERNATIVE AZEOTROPE REFRIGERANT
DESIGN AND ANALYSIS OF ALTERNATIVE AZEOTROPE REFRIGERANTDESIGN AND ANALYSIS OF ALTERNATIVE AZEOTROPE REFRIGERANT
DESIGN AND ANALYSIS OF ALTERNATIVE AZEOTROPE REFRIGERANT
 
MCE 2016 - B. Bella - EMERSON
MCE 2016 - B. Bella - EMERSONMCE 2016 - B. Bella - EMERSON
MCE 2016 - B. Bella - EMERSON
 
Thermal cracking (2)
Thermal cracking (2)Thermal cracking (2)
Thermal cracking (2)
 
Scroll compressors for propane (R290)
Scroll compressors for propane (R290)Scroll compressors for propane (R290)
Scroll compressors for propane (R290)
 
K022 Series new.pdf
K022 Series new.pdfK022 Series new.pdf
K022 Series new.pdf
 
Sergio Bobbo - CNR DI PADOVA - APPLICAZIONI DEI NANOFLUIDI
Sergio Bobbo - CNR DI PADOVA - APPLICAZIONI DEI NANOFLUIDISergio Bobbo - CNR DI PADOVA - APPLICAZIONI DEI NANOFLUIDI
Sergio Bobbo - CNR DI PADOVA - APPLICAZIONI DEI NANOFLUIDI
 
ammonia National Fertilizer Limited Bathinda
ammonia National Fertilizer Limited Bathindaammonia National Fertilizer Limited Bathinda
ammonia National Fertilizer Limited Bathinda
 
XVI CONVEGNO EUROPEO H. Dhont - Refrigerant R32 for air conditioners and heat...
XVI CONVEGNO EUROPEO H. Dhont - Refrigerant R32 for air conditioners and heat...XVI CONVEGNO EUROPEO H. Dhont - Refrigerant R32 for air conditioners and heat...
XVI CONVEGNO EUROPEO H. Dhont - Refrigerant R32 for air conditioners and heat...
 
Ammonia production from natural gas, haldor topsoe process
Ammonia production from natural gas, haldor topsoe processAmmonia production from natural gas, haldor topsoe process
Ammonia production from natural gas, haldor topsoe process
 
Testo 550 datasheet 2012
Testo 550 datasheet 2012Testo 550 datasheet 2012
Testo 550 datasheet 2012
 
Refrigerant
RefrigerantRefrigerant
Refrigerant
 
Refrigerant
RefrigerantRefrigerant
Refrigerant
 
Ammonia Plant - Methanation Operations
Ammonia Plant - Methanation OperationsAmmonia Plant - Methanation Operations
Ammonia Plant - Methanation Operations
 
Refrigerant ppt
Refrigerant pptRefrigerant ppt
Refrigerant ppt
 

Plus de Agassis Rodrigues

O que significa ter um direito
O que significa ter um direitoO que significa ter um direito
O que significa ter um direitoAgassis Rodrigues
 
Estatuto criança adolescente_comentado
Estatuto criança adolescente_comentadoEstatuto criança adolescente_comentado
Estatuto criança adolescente_comentadoAgassis Rodrigues
 
Defesa da defensoria do para
Defesa da defensoria do paraDefesa da defensoria do para
Defesa da defensoria do paraAgassis Rodrigues
 
Constituição federal anotada - stf
Constituição federal   anotada - stfConstituição federal   anotada - stf
Constituição federal anotada - stfAgassis Rodrigues
 
Como fazer uma redação dissertativa argumentativa
Como fazer uma redação dissertativa argumentativaComo fazer uma redação dissertativa argumentativa
Como fazer uma redação dissertativa argumentativaAgassis Rodrigues
 
44361736 lei-11-340-lei-maria-da-penha-comentada
44361736 lei-11-340-lei-maria-da-penha-comentada44361736 lei-11-340-lei-maria-da-penha-comentada
44361736 lei-11-340-lei-maria-da-penha-comentadaAgassis Rodrigues
 
Vale transporte como funciona
Vale transporte como funcionaVale transporte como funciona
Vale transporte como funcionaAgassis Rodrigues
 
Ada pelegrini-grinover-antonio-carlos-de-araujo-cintra-candido-rangel-dinamar...
Ada pelegrini-grinover-antonio-carlos-de-araujo-cintra-candido-rangel-dinamar...Ada pelegrini-grinover-antonio-carlos-de-araujo-cintra-candido-rangel-dinamar...
Ada pelegrini-grinover-antonio-carlos-de-araujo-cintra-candido-rangel-dinamar...Agassis Rodrigues
 
Aula iv fluxos reais e monetários
Aula iv fluxos reais e monetáriosAula iv fluxos reais e monetários
Aula iv fluxos reais e monetáriosAgassis Rodrigues
 
Aula iii estrutura de mercado
Aula iii estrutura de mercadoAula iii estrutura de mercado
Aula iii estrutura de mercadoAgassis Rodrigues
 

Plus de Agassis Rodrigues (20)

Termo ciência fabiola
Termo ciência fabiolaTermo ciência fabiola
Termo ciência fabiola
 
Reunião 13 08
Reunião 13 08Reunião 13 08
Reunião 13 08
 
Resumo acesso a justiça
Resumo acesso a justiçaResumo acesso a justiça
Resumo acesso a justiça
 
O que significa ter um direito
O que significa ter um direitoO que significa ter um direito
O que significa ter um direito
 
Manual tecnicas redacao
Manual tecnicas redacaoManual tecnicas redacao
Manual tecnicas redacao
 
Guia trabalho acadêmico
Guia trabalho acadêmicoGuia trabalho acadêmico
Guia trabalho acadêmico
 
Estatuto criança adolescente_comentado
Estatuto criança adolescente_comentadoEstatuto criança adolescente_comentado
Estatuto criança adolescente_comentado
 
Defesa da defensoria do para
Defesa da defensoria do paraDefesa da defensoria do para
Defesa da defensoria do para
 
Constituição federal anotada - stf
Constituição federal   anotada - stfConstituição federal   anotada - stf
Constituição federal anotada - stf
 
Como fazer uma redação dissertativa argumentativa
Como fazer uma redação dissertativa argumentativaComo fazer uma redação dissertativa argumentativa
Como fazer uma redação dissertativa argumentativa
 
C digo penal comentado
C digo penal comentadoC digo penal comentado
C digo penal comentado
 
44361736 lei-11-340-lei-maria-da-penha-comentada
44361736 lei-11-340-lei-maria-da-penha-comentada44361736 lei-11-340-lei-maria-da-penha-comentada
44361736 lei-11-340-lei-maria-da-penha-comentada
 
0027 primeiro aditamento
0027 primeiro aditamento0027 primeiro aditamento
0027 primeiro aditamento
 
Vale transporte como funciona
Vale transporte como funcionaVale transporte como funciona
Vale transporte como funciona
 
Ada pelegrini-grinover-antonio-carlos-de-araujo-cintra-candido-rangel-dinamar...
Ada pelegrini-grinover-antonio-carlos-de-araujo-cintra-candido-rangel-dinamar...Ada pelegrini-grinover-antonio-carlos-de-araujo-cintra-candido-rangel-dinamar...
Ada pelegrini-grinover-antonio-carlos-de-araujo-cintra-candido-rangel-dinamar...
 
Trabalho tgp
Trabalho tgpTrabalho tgp
Trabalho tgp
 
Mercado e concorrência
Mercado e concorrênciaMercado e concorrência
Mercado e concorrência
 
Aula iv fluxos reais e monetários
Aula iv fluxos reais e monetáriosAula iv fluxos reais e monetários
Aula iv fluxos reais e monetários
 
Aula iii estrutura de mercado
Aula iii estrutura de mercadoAula iii estrutura de mercado
Aula iii estrutura de mercado
 
Aula ii economia tópicos
Aula ii economia tópicosAula ii economia tópicos
Aula ii economia tópicos
 

Treinamento da tecnologia invert

  • 2. R410A Refrigerant LG ELECTRONICS
  • 3. R410A Refrigerant Characteristic R410A vs R22 Item R-22 R-410A Mixed Refrigerant Composition Mono Refrigerant (R32:R125 = 50:50) Ozone Depletion 0.0055 0 Potential (ODP) Global Warming 1700 1370 Potential (GWP) Saturation Pressure 150 240 (at 25℃. Psi) Boiling Point (℃) -40.8 -51.4 No change in Leakage Composition changes composition Liquid/Gas/Both Must be charged in liquid Recharging (Liquid+Gas) state LG ELECTRONICS
  • 4. R410A Temperature-Pressure Chart How its different from R22?  A temperature-pressure chart can easily be used for charging, refrigerant cycle analysis and diagnosis.  R410A is 1.6 times higher vapor pressure than R-22 when saturated. Caution during installation : Temp R410A R22 Temp R410A R22 -40° 26 20° 210 132 HIGH PRESSURE R410A 15 25° 240 150 1.6 times higher -35° 32 19 30° 275 173 than R22 -30° 40 35° 312 196 24 40° 353 222 Problem : -25° 48 45° 397 250 High possibility of 30 gas leakage -20° 58 50° 446 282 35 55° 500 315 Solution : -15° 70 60° 556 352 43 Larger flare size 65° 618 392 -10° 84 R410A 51 70° 686 435 R22 -5° 100 75° - 480 61 0° 118 LG ELECTRONICS
  • 5. R410A Procedure Why its different from R22?  R410A must be charged in liquid state.  It’s a mixed refrigerant, if charging in vapor state the composition might changed. Why? Right procedure : Open  Open Gas Gas Liquid Liquid Mono Mixed  Different ratio Refrigerant Caution during installation :  Charge R410A cylinder in upright position to avoid loss in performance. LG ELECTRONICS
  • 6. R410A Special Tool Why its different from R22?  As pressure is high,it is impossible to measure using conventional gauge,  To increase pressure resisting strength,hose materials and port size are different. New Tools Applicable to R22 Changes Gauge Manifold High Pressure : R410A 0.1 ~ 5.3 MPa X (R22 ~ 3.5 MPa) Low Pressure : R410A 0.1 ~ 3.8 MPa (R22 ~ 1.7 MPa) Charge Hose R410A : 1/2 UNF 20 threads per inch X (R22 : 7/16 UNF) R410A : 5.1 Mpa (51 kgf/ ㎠ ) (R22 : 3.4 Mpa (34 kgf/ ㎠ )) Vacuum Pump Pumps used with CFC and HCFC X charged systems may also be used on R410A systems Caution during installation : DO NOT mix refrigerants in your tools.  Dissimilar oils will become contaminated. LG ELECTRONICS
  • 7. R410A Lubrication Why its different from R22? The chemistry of R-410A makes it incompatible with mineral based lubricants The preferred lubricants are the Polyolester or Ether based oils.  Exposure to the atmosphere must be limited.    Esther oil Ether oil Mineral oil Caution during installation : The oil is miscible, so it is very important to remove as much particulates and moisture from the system  Vacuum MUST be performed.  Moisture can be absorb very easily. LG ELECTRONICS
  • 8. General Operation Logic LG ELECTRONICS
  • 9. Basic Mode Controls Modo de refriamento : Modo Aquecimento: Temp. 3min Temp. Thermo OFF Thermo OFF +4℃ +0.5℃ +2℃ Thermo ON Set temp. 1) Thermo ON -0.5℃ Set temp. -1.5℃ 2) Comp. High ↔ Low Comp Off High ↔ Low Comp. High ↔ Low Comp Off High ↔ Low Comp Off Frequency Frequency O operacional Hz depende da condição de carga, como a diferença entre a temperatura ambiente e conjunto ou restrições de frequência. • Após compressor está desligado, pode reiniciar novamente em 3 minutos o tempo de atraso > proteger condição compressor • No modo de resfriamento há dois casos quando o compressor está desligado (ver gráfico sup.) 1)Em quanto ΔTroom-set is lower than 0.5℃ for 3mins continuously or 2) when ΔTroom-set is lower than 1.5 ℃. • No modo de aquecimento, quando ΔTroom Maior Conjunto E fazer Que 4 ℃, compressor Ira Parar de trabalhar Há e começar de novo quando ΔTroom conjunto-é inferior a 2 ℃. • Por quê? Para garantir a capacidade de arrefecimento / aquecimento ideal LG ELECTRONICS
  • 10. Basic Mode Controls Compressor Frequency Restriction : • Uma das restrições de frequência é muitas limite de temperatura exterior. • Isto significa que o máximo de trabalho Hz para o compressor é limitada pelo ambiente exterior temperature. Por quê? para proteger o compressor e manter responsabilidade do produto. Outdoor Temp Resfriament Outdoor Temp (℃) Aquecimento (℃) o (Max Step) (Max Step) Outdoor ≤ 0 3 Outdoor ≤ -7 16 0< Outdoor ≤10 3 -7< Outdoor ≤-2 15 10< Outdoor ≤ 23 4 -2< Outdoor ≤ 4 13 23< Outdoor ≤ 30 10 4< Outdoor ≤ 10 11 30< Outdoor ≤40 12 10< Outdoor ≤21 11 46< Outdoor ≤10 8 21< Outdoor ≤27 5 46< Outdoor 7 27< Outdoor 3 LG ELECTRONICS
  • 11. Basic Mode Controls Defrosting Control : •Durante o modo de aquecimento, o ciclo é invertido para o ciclo de aquecimento para descongelar o evaporador tubo da unidade exterior. Por quê? Para proteger o tubo da unidade exterior do congelamento. • Em desgelo controle, a amostra. é, que a ventoinha interior, ventilador ao ar livre, ea válvula de 4 vias estão fora. • Durante a descongelação, o min. temp. do tubo interior é medido e é comparado com o apresentar temp. do tubo interior para obter a diferença de que a temperatura interior. (Se a diferença for 5 ℃ ou superior, controlo de descongelação é completada e no modo de aquecimento é levada a cabo de novo) Heating Cycle HOT START End Max Temp Max Temp (40 minutes) ΔTmax Defrost Pipe Temp Start Defrost End Intake Air. ΔTmin=5℃ Over Temp Min Temp Defrost Time Compressor ON Outdoor Fan ON OFF ON Indoor Fan ON OFF ON 4_way Valve ON OFF ON LG ELECTRONICS
  • 12. Basic Mode Controls Hot Start Operation : • Durante o início de funcionamento de aquecimento, este sistema foi concebido para evitar que o ar frio a partir de serem descarregados, enquanto espera depois de atingir uma certa temperatura (desta vez, ventilador interno está desligado). Após a temperatura interior do tubo atinge 28 ℃ (opção), o ar quente vai sair na seguinte ordem da velocidade do ventilador Velocidade baixa velocidade do ventilador -> definido pelo controle remoto • O diagrama de funcionamento é como a seguir Pipe Temp (Indoor) Pipe Temp(Indoor) 28℃(Option) 20℃(Option) Compressor ON Outdoor Fan ON Indoor Fan STOP LOW Set Fan Speed STOP LOW Set Fan Speed 4_way Valve ON LG ELECTRONICS
  • 13. Basic Mode Controls Sleep Timer Operation : • A temperatura de regulação será automaticamente aumentada de 1 ℃ 30 minutos mais tarde, e por 2 ℃ 1 hora mais tarde (arrefecimento / desumidificação saudável) • A operação será interrompida depois (1,2,3,4,5,6,7: opção) horas • Indoor fan control : - cooling/ Healthy Dehumidification/ Auto Mode ▶ Low speed - Heating/Auto Mode ▶ Mid speed Auto Change over Operation : •O condicionador de ar muda automaticamente o modo de funcionamento de arrefecimento ou com aquecimentoou aquecimento para o arrefecimento para manter a temperatura da sala interior constante. •Quando temp. variar ao longo ± 2 ℃, ar condicionado mantém a temperatura ambiente. em ± 2 ℃ com respeitar para ajustar a temperatura, alterando o modo de arrefecimento ou com aquecimento e vice-versa. Healthy Dehumidification Operation : • Quando a entrada de operação de desumidificação pelo controle remoto é recebido, a temperatura do ar de admissão é detectada ea temperatura ambiente é automaticamente ajustado de acordo a temperatura do ar de admissão. LG ELECTRONICS
  • 14. Basic Features Different angle of vane for each operation mode: • Isto é especialmente concebido para proporcionar o fluxo de ar ideal durante cada operação. • Como o ar frio é mais pesado que o ar quente na mesma umidade. Assim, o fluxo de ar é gerado por o lançamento de mais pesado do ar • Usando o mesmo princípio, é por isso que o ângulo de palhetas do modo de resfriamento é maior do que o modo de aquecimento. Mode Cooling / Dehumidification Heating Defrost / AutoClean Remote Control Display / / LG ELECTRONICS
  • 15. Processo de instalação. LG ELECTRONICS
  • 16. Installation Work Flow Fixing Drilling Setting Setting Installation Location Inst. Plate Hole Indoor Outdoor Standard Flare Piping Work Precautions Processing Length Fitting Welding/ Joints Brazing Electric Wiring Work Connecting Improper Wiring Spec Wire Case Insulation Work Wrapping Pipe & Drain Vacuum Leak Test Vacuum Recharging Finishing Finishing Job Checking Indoor Outdoor Drainage Trial Run Basic Check Point Symptoms Logic LG ELECTRONICS
  • 17. Fluxo de instalação de passo a passo principal Installation Location Piping work & Flare Check Piping Connection Electric Wiring Work Insulation Vacuuming Test Run Check : Pressure, voltage, current and temperature difference LG ELECTRONICS
  • 18. Installation Tools  Some of the tools used on R22 systems may be unacceptable for use on R410A. Figure Name Figure Name Screw driver, Spanner Vacuum pump Multi-meter Measuring tape, Knife Pincher plier, Nipper Ampere_meter Hexagonal wrench Manifold Gauge for R410A Hole core drill Thermometer Vinyl tape Flaring tool set Ladder, Horizontal Level R410A tank LG ELECTRONICS
  • 19. Installation Location LG ELECTRONICS
  • 20. Iocal de instalação/ Selecting Best Location How? Why?  Make sure there is no heat or steam around Reduce cooling capacity. indoor unit. Cause low performance.  Make sure heat radiation from condenser is not Prevent noise problem. blocked.  Place where noise & vibration are minimum. Indoor & Outdoor Unit Space Requirement : Unit : mm Unit : mm More than 300 More than 200 More than 300 More than 100 More than 100 More than 600 More than 700 More than 2300 Case of field defect : •Blocked in/outlet air flow Low performance •Limited inlet airflow •Difficult when servicing  Low cooling LG ELECTRONICS
  • 21. Installation location / Selecting Best Location Case of field defect : Tips :  Outdoor unit is installed on top of each other without  When installing the unit at a high place be sure safely anchoring the unit. to fix the unit legs (safety precautions)  Noise/vibration  Consider enough space for service when  Hard to service installing outdoor unit.  Safety issues     LG ELECTRONICS
  • 22. Installation location / Selecting Best Location Case of field defect : Tips :  Hot discharge air will enter the unit cause a work  Always consider enough space when overload and starts OLP system(On/Off) installing outdoor unit.  Low Performance  Avoid small installation places as possible.    ~ ~ ~ ~ ~ ~ discharge air  Inlet airflow to condenser is blocked  Always follow the given space requirement  Operating pressure will be high and the unit may when selecting install location. repeatedly on-off resulting in low Cooling/Heating    LG ELECTRONICS
  • 23. Installation location / Selecting Best Location Cases of field defect : Tips :  Inlet airflow to evaporator is blocked Where inlet/outlet airflow is not blocked.  product low cooling/heating Low cooling performance.  noise might occurs  Always follow the space requirements to prevent such cases.  Space Requirements for Indoor Unit  LG ELECTRONICS
  • 24. Installation location / Selecting Best Location Cases of field defect : Tips :  Indoor unit is installed too high. Where inlet/outlet airflow is not blocked.  Discharge air can not be fully distributed to user. Low cooling performance.  Low cooling/heating  Always follow the space requirements to prevent such cases.   Consider safety, servicing space when selecting installation place.  Unproper unit installation place. 3.5 M.  Difficult during servicing   Unproper unit installation place.  Safety issues    LG ELECTRONICS
  • 25. Installation location / Fixing Installation Plate How? Why?  Select strong and solid wall. Prevent vibration and unit fall off   Measure the wall and mark the centerline. damage.  Horizontally align the plate centerline using Easy wiring and piping through the wall. horizontal level If unit is slanted, water leakage may Work Process : occurs. Place level on a raised tab Unit Outline Fixing point Left rear piping hole Φ70 Φ70 Right rear Measuring & leveling Center hole piping hole Case of field defect : • Product fall off • Bad fixing plate Noise! • Horizontally misalign  Water leakage LG ELECTRONICS
  • 26. Installation location / Drilling Hole How? Why?  Select strong and solid wall. Prevent vibration and unit fall  Drill the piping hole with a ø70mm hole core drill. offdamage. Easy wiring and piping through the wall.  Drill at either right or left with the hole Slanted to outdoor to ensure proper water slightly slanted Work Process : flow. • Reference for dimensions Product Size Left rear piping hole Φ70 Φ7 Right rear 0 piping hole • Slightly slanted to outdoor side. Why?Ensure water properly flow in downward direction. LG ELECTRONICS
  • 27. Installation location / Settling Indoor Unit How bend the pipe properly? Why?  Hold and press at the corner of the piping. Use it as a center of rotation to prevent  When bending downward or to the left side, do it damage. gently. Prevent damage to pipe which can cause cycle blocking. Work Process : Slowly unfold the pipe Hold at the corner of piping Bend to the left side slowly downward Case of field defect : • Damage indoor piping during bending.  Clogged refrigerant cycle LG ELECTRONICS
  • 28. Installation location / Settling Indoor Unit How? Why?  Drill the wall if customer wants the piping through Customer satisfaction. the wall. Sufficient space for easy piping.  Use the tubing holder when bending the pipe for Piping may get damagedclogged connecting. cycle. Work Process :be extra careful when bending the pipe. Make sure to Detach the Hang the unit & Position Chassis unlock tubing the pipe for bottom holder connection Caution : • Make sure the unit and install plate are just in the right position and stable.  Unit might fall off during working. LG ELECTRONICS
  • 29. Installation location / Settling Outdoor Unit How? Why?  Secure the unit with an anti-vibration damper. Prevent the vibration to the unit  Secure the unit with nail or wire  strong wind or Product fall offdamage earthquake. Prevent from product or part  If install site is close to seaside, avoid direct corrosion. exposure. Work Process : • Anchor the unit with a bolt & nut • Set up a wind breaker Nut Windbreak  Washer Leg Sea wind Damper  Angle Case of field defect : • Unstable  Fall off • No damper  Vibration • Corrosion due to sea windpart malfunction LG ELECTRONICS
  • 30. Piping work LG ELECTRONICS
  • 31. Piping Work How? Why?  Do not use collapsed,deformed or discolored copper Expansion valve may become blocked. pipe. Pipe may get damaged during flaring work .  Never use copper pipes thinner than 0.8mm. Precaution : Selecting Copper Pipe : • Sealed ends of pipes with a cap until connected. Thickness (mm) Nominal Outer • Avoid piping installation on a rainy day. diameter diameter R410A (mm) • Carry out the work in short time as possible. 1/4 6.35 0.80 • Water or dust does not enter the pipe. 3/8 9.52 0.80 1/2 12.70 0.80 5/8 15.88 1.00 Case of field defect : After Flaring • 0.6t Copper Pipe Condition : Not round shape, Burr exist → resulting in egg-shaped flare work High possibility of gas leakage LG ELECTRONICS
  • 32. Piping Work / Pipe Flaring Work How? Why?  Remove the burrs after cutting work. Prevent burrs from enteringclogged  Never use copper pipes thinner than 0.8mm. cycle. Pipe may damage during flaring work . Work Process : Cutting the pipe Burr removal Place the pipe Tighten the clamp Apply the torque Finish & check flare LG ELECTRONICS
  • 33. Piping Work / Pipe Flaring Work Flaring Position : The use of flare clutch type is preferable. ⓐ(inc ⓐ(m R410A / ⓑ (mm) h) m) Clutch type Wing nut type 1/4 6.35 1.1 ~ 1.3 1.5 ~ 2.0 3/8 9.52 1.5 ~ 1.7 1.5 ~ 2.0 1/2 12.70 1.6 ~ 1.8 2.0 ~ 2.5 5/8 15.88 1.6 ~ 1.8 2.0 ~ 2.5 Defect OK  Checking Flare Work  Compare the flaring work with the figure.  If a flaring section is defective, cut it off  and do flaring work again. Case of field defect : • Improper flaringGas leakage LG ELECTRONICS
  • 34. Piping Work / Piping Connection How? Why?  Make sure that the flare do not have any scar or Prevent strange material from entering dust, etc. system.  Make sure to follow the given applied torque. If applied torque is too strong, flare will get damaged. Work Process : Tightening Torque : Alignment Indoor Unit Outdoor Unit Outside diameter Torque mm inch kgf· ㎜ Ø6.35 1/4 1.8~2.5 Ø9.52 3/8 3.4~4.2 Ø12.7 1/2 5.5~6.5 Ø15.88 5/8 6.3~8.2 • Tighten the flare • Tighten the flare nut with torque wrench Ø19.05 3/4 9.9~12.1 nut by hand. untill the wrench clicks. Case of field defect : • Applied torque is too strong Flare will get damaged  Gas leakage LG ELECTRONICS
  • 35. Piping Work / Standard Pipe Length How? Why?  Always follow the pipe length specification. When it is too short, cycle will be  Always remember to add refrigerant if the pipe overloaded. length is When it is too long, can cause over work more than 5m. at Pipe Installation Length : AFTA Model compressor Pipe Size Gas Φ Liquid Φ Max. Additiona Standard Min/Max Elevation l Length Length Capacity Refrigera (m) (B) (m) (A) (m) nt (g/m) mm inch mm inch 2.5kW(9kBtu/h) 9.52 3/8 6.35 1/4 5 7 3 / 15 10 3.5kW(12kBtu/h) 12.7 3/8 6.35 1/4 5 7 3 / 15 10 5.2kW(18kBtu/h) 12.7 1/2 6.35 1/4 5 7 3 / 20 20 Case of field defect : 7.0kW(24kBtu/h) 15.88 5/8 9.52 3/8 5 7 3 / 20 20 • Short Piping  Refrigerant inflow noise is directly (B) 1m transmitted to indoor unit. (A)  Cycle overload. LG ELECTRONICS
  • 36. Piping Work / Pipe Joints Connection How? Why?  Prior to use, be sure to remove all contaminants. Prevent from entering the system.  Used to connect the copper pipes. Case of pipe diameter is not the same with  Connections during brazing work. SVC valve diameter. Joint Type : Flare Joints Socket Joints Flare Joints Assembly Socket Joints Assembly LG ELECTRONICS
  • 37. Welding / Brazing Guide How? Why?  Nitrogen should be allowed to flow without building Prevent from carbon scales clogging. up a pressure in the pipeline. Safety precautions and to make sure the  Brazing requires sophisticated techniques, it must work is be done properly without any leakage. performed by qualified person. Brazing with Nitrogen : Turn on the gas Continue the flow Connect a nitrogen cylinder and until the joints have to one end of the pipework cooled regulate the flow 10 mm↑ 0.05 ~ 0.12 mm. Caution point : Nitrogen release . Pressure :0.1~0.2kgf/ ㎠ (1.4~2.8psi) . Taping LG ELECTRONICS
  • 38. Welding / Brazing Guide Case of field defect : Brazing without Nitrogen release : Problem: Carbon scales clogging filters Troubles during circulation in a cycle, like clogging EEV, Compressor, moving parts, piping etc • Pipe frozen  Cycle blocked LG ELECTRONICS
  • 39. Elec. wiring Work LG ELECTRONICS
  • 40. Electric Wiring Work How? Why?  Do not use spliced wires or extension cord. Fire or electric shock may occur.  Inverter product  higher harmonic Product or earth leak detector Therefore,be sure to install an earth leak malfunction. detector. Indoor & Outdoor Unit Wiring : Note : Terminal Block Indoor Remote Controller Cable Connection Cable Cable Retainer Use end-terminal for Live Neutral Connector Earth safety precautions Excessive strip length Outdoor  shock or leakage LG ELECTRONICS
  • 41. Electric Wiring Work / Wire specification How? Why?  Always follow the wiring & circuit breaker spec. Cause abnormal heat/terminal overheating. Do not overload the circuit by adding drain pump or They may cause overheating or electrical other shock. electrical equipment. Wire & Circuit Breaker Selection : Power Code Connection Cable Outdoor Indoor 10±3mm 10±3mm Circuit GND :20mm GND :20mm Breaker (mm²) (A) Earth Grade(kBtu) Grade(kBtu) Leakage Cross 9/12 18 24 Circuit 9/12 18 24 -section Breaker Power Supply area 1.0 1.5 2.5 15 20 30 Note : Circuit breaker size selection (Refer to Label Quality for current value)  Normal : Running current x 1.75  Inverter : Running current x 2.0 LG ELECTRONICS
  • 42. Electric Wiring Work / Wiring Connection How : Indoor Power Supplied Type IN 1(L) 2(N) 3(C)  Connect the wires between indoor & outdoor Brown Red units so that the terminal numbers and Green/ colors Connection cable Blue yellow are matched.  Tighten the terminal screws securely. OUT 1(L) 2(N) 3(C)  Do not extend cable connections. Power Code Why? Outdoor Power Supplied Type If the wires are not matched, communication IN error will occurs CH05,53. 1(L) 2(N) 3(C) If the connection is loosen, electric Brown Red Green/ shock may Blue yellow occur. Connection cable Extending cable will create noise or (L) (N) 1(L) 2(N) 3(C) electric OUT short CH05,53 Power Supply LG ELECTRONICS
  • 43. Electric Wiring Work / Wiring Connection Case of field defect : Tips :  Unproper power supply wiring / absent ground wire 1. Check if there is ground terminal at the plug,  Heat ignition of terminal block can cause fire to prevent electrical short,perform an additional  Electric shock 3rd grounding at outdoor unit or carry out a separate grounded work. Ground Terminal   Ground Wire Power Plug 2. Electrical work such as Indoor↔Outdoor connection,earth leakage breaker ground wire must be carried out in accordance with state & local electrical wiring codes.  d Electric Standar Code Main Power Switch Ground Wire Earth Leakage Breaker LG ELECTRONICS
  • 44. Electric Wiring Work / Wiring Connection Case of field defect : Tips :  Unproper extended wiring connection  Electrical part is not used for only 1~2 years .  Cable over heat or fire might occur Most of time, it will have to endure the same period  Communication Error CH05 occur(operation stop) as air conditioner’s lifetime itself.  Therefore, temporary dan simple wiring work will only cause likely fire or electrical shock.   Extending electric wire; 1st layer of insulation : Make sure to solder the wires to reduce the contact resistance and by using thermal contraction tube. 2nd layer of insulation : Wrap the connection with insulation tape to prevent exposure to moisture/surrounding    LG ELECTRONICS
  • 45. Electric Wiring Work / Wiring Connection Case of field defect : Tips :  Wrong wiring connection during installation of large  In case like this, make sure to double check that numbers of the same model at the same site. wiring connection and piping connection are  Inoperative unit /abnormal operation connected to the same model. Room A Room B Room A Room B piping piping  wiring wiring LG ELECTRONICS
  • 46. Insulation & Drain Work LG ELECTRONICS
  • 47. Insulation & Drain Work / Standard How? Why?  Do the insulation after leak test is done. Gas leakage must be checked during test  Bundle the pipe and drain hose together with vinyl run. tape. Prevent possible water leakage. Work Process : Wrap together refrigerant piping, cable and drain hose with vinyl tape. Refrigerant Pipe Drain Hose Connecting Cable Caution : Set the tubing line upward  prevent possible water leakage. Cutting Line   Cutting Line Gas Pipe Liquid Pipe LG ELECTRONICS
  • 48. Insulation & Drain Work / Case Case of field defect : Tips :  Water leakage at pipe connection due to bad Indoor Outdoor insulation.  Mold gathers at the wall. Insulator Extension Hose Indoor drain hose  Fully insulate the connection part between indoor drain hose & extension hose.  If not,leakage may occur as the water will condensate due to temperature changes. Fully insulate drain hose connection! Mold LG ELECTRONICS
  • 49. Insulation & Drain Work / Water Leak Test How? Why?  Pour a water to make sure well drainage. Prevent water leakage during operation.  Make sure the route of drainage is done properly. If the drain hose curled, water leakage occurs. Checking Drainage : Pour a glass of water Check possible Ensure water flows out the onto evaporator leakage drain exit without leakage Tips : Indoor Downward Slope  The drain hose should point downward for easy drain flow.  Fix drain hose to prevent bending or curling d OK! Fixe  Drain hose connection must be easy accessible & serviceable! LG ELECTRONICS
  • 50. Insulation & Drain Work / Water Leakage Defect Case of field defect : Tips :  Drain hose is in upward slanted direction  Set the drain hose in the downward position  drain water can not flow to outdoor unit.  drain water can flow smoothly. Slanted hose Indoor Downward Slope  Water Leakage OK!   LG ELECTRONICS
  • 51. Insulation & Drain Work / Water Leakage Defect Case of field defect : Tips :  Curled drain hose will block water flow  Fix drain hose to prevent bending or curling  water leaks at indoor unit   Water  OK! d Leakage Fixe LG ELECTRONICS
  • 52. Insulation & Drain Work / Water Leakage Defect Case of field defect : Tips :  In case of when pipe connection have to be installed  Wrap the area which accommodates the refrigerant in upward direction piping, electric cable,drain hose with vinyl tape in  Vinyl tape has to be wrapped from bottom to the top! Bottom-Up direction! Why?Prevent possible leakage to indoor when raining  Wrap in the  Bottom-Up direction LG ELECTRONICS
  • 53. Insulation & Drain Work / Water Leakage Defect Case of field defect : Tips :  Water back-flow occurs when the drain line  For every 1m, fix the drain pipe with clip/tie wrap is all the way drooping for over 2m  Water leakage at indoor side Clip ∝ 1m   LG ELECTRONICS
  • 54. Vacuum & Test run LG ELECTRONICS
  • 55. Vacuum / Gas Leak Test How? Why?  Top of cylinder must be higher than its bottom. To avoid nitrogen from entering the system.  Use soap bubble to identify the location of leak. Insufficient gas will reduce the cooling capacity. (flare connection) Work Process : Charge nitrogen-gas . Close Tightened, repair location of leak Liquid side . Leak test 2(3)-way Leakage with soap water valve . Gas side . Close No leakage Low High Nitrogen Open Close Gas release . 3-way valve Go to next step Nitrogen-Gas (Vacuum) Cylinder LG ELECTRONICS
  • 56. Vacuum / process-1 How? Why?  Air evacuation with vacuum pump is a MUST. Air and moisture in system have bad effects as:  Liquid and the gas side SVC valves are kept closed. • Pressure in the system rises. • Cooling/heating efficiency drops Work Process : Vacuum  15mins . Check manifold low Close side pressure reach to 76cmHg(30inHg) .. Liquid side . 2(3)-way Tightened, valve Close low side valve . repair of manifold Gas side . location of leak Close Turn off vacuum Low High pump Open Close . . 3-way valve Needle gauge does not move after 5 minutes. Leakage Vacuum Pump No leakage  Required time for evacuation when 30 gal/h vacuum pump is Disconnect vacuum used. LG ELECTRONICS
  • 57. Vacuum / Process-2 How? Why?  Air evacuation with vacuum pump is a MUST. Air and moisture in system have bad effects as:  Liquid and the gas side SVC valves are kept closed. • Pressure in the system rises. • Cooling/heating efficiency drops Work Process : Vacuum  15mins . Close Check Vacuum Tightened, Liquid side gauge repair . pressure reach to location 2(3)-way 760 mmHg of leak valve . Gas side . Close both side Close valve of manifold Leakage Low High Open Open No leakage . . . 3-way valve Turn off the vacuum pump Vacuum Pump Vacuum gauge Disconnect vacuum  Required time for evacuation when 30 gal/h vacuum pump is used. LG ELECTRONICS
  • 58. Vacuum / Finishing Vacuum Work How? Why?  Now, the gas is ready to be released to the system. Gas leakage must be checked during test  Be sure to mount all the caps onto 2way & 3way SVC run. valve Prevent small possible leakage in future use. Work Process : Disconnect the manifold from the vacuum pump and from the service port of . 3way valve Open Liquid side . 2(3)-way valve . Position both of the SVC Gas side . valves to “Open” using a Open hexagonal wrench(4mm) Low High Close Close Mount valve caps onto the . . . 3-way 2way valve and the 3way valve valve . Vacuum Pump Gas Release LG ELECTRONICS
  • 59. Vacuum / Additional Refrigerant How? Why?  Charge in standing upright position. Charging 410A must be in liquid state for  Before recharging, check whether the cylinder has a right siphon or not. composition  effect such as low cooling. Work Process : Connect gas cylinder to manifold . Close Open Gas side Liquid side SVC valve . 2(3)-way valve Balance zero . setting Gas side . Upright Open Position Open low side valve Low High of manifold slowly Open Close . . . 3-way Until target weight is reached valve Balance Close low side valve of manifold Refer manual Installation for gas weight(g) / pipe length(m) LG ELECTRONICS
  • 60. Test Run How? Why?  Press “On/Off” button and hold for 3~6 secs. To enter a mode that is specially designed for Test Run.  Check operating pressure,current, voltage etc. Ensure the product work properly or not. Test Run Operating Logic : In this mode, regardless of the outside temperature, the unit will operate for 18±1 minute in below conditions: -Cooling Mode -Indoor Fan High RPM ON/OFF -Thermal On/Comp On -Vertical Auto Swing Airflow Button - Comp. fixed frequency Check Items : 1. Measure the temperature of the intake & discharge air.  Ensure the difference between the intake & discharge temp. is more than 8℃ (Cooling) & 14℃(Heating) LG ELECTRONICS
  • 61. Test Run Check Items : 2. Measure the pressure of the gas side service valve. Outside Pressure of the gas Refri. ambient TEMP Side Service valve. 8.5~11.2 ㎏ / ㎠ G R410A 35℃(95℉) (120~160 P.S.I.G)  If the pressure is drop or significantly higher than specification: Pressure is low: Pressure is high: Gas leakage / insufficient System is overloaded Possibility of overcharge Closed SVC valve - Recheck Recheck gas leak LG ELECTRONICS
  • 62. Test Run Check Items : 3. Measure the voltage & operating current.(Refer to Label Quality for specification)  Power supply voltage/current complied with the rated value Other Check Items : Check Items Symptom Check Indoor & Outdoor units are Fall, vibration, noise installed on solid bases. System is properly ground to Electrical leakage earth Wiring connection Inoperative or error code 05 Drain line is properly Water leakage installed LG ELECTRONICS

Notes de l'éditeur

  1. The procedure must be as follows: ·Connect a nitrogen cylinder to one end of the pipework to be jointed using a regulator set to a low pressure,the far end of the pipework to be open to atmosphere ·Turn on the gas and regulate the flow to a flow rate can easily be felt on the back of a moistened hand about 0.03 to 0.06 CFM (1 to 2 liters per minute). ·The nitrogen should be allowed to flow without building up a pressure in the pipeline. ·Continue the flow until the joints have cooled.
  2. NOTE: As brazing work requires sophisticated techniques, experiences based upon a theoretical knowledge, it must be performed by a person qualified.