BUILDING SERVICES - II:

ELECTRICAL SERVICES:
Unit – V:
Lighting Calculation:
NBC standards, nominal
illumination
levels
in
building
interiors, lux, lumen, intensity, lighting schemes.
ILLUMINATION AND LUX:
What is the method for calculating illumination ?
The problem of the Architect / Lighting Designer at the
functional level is to determine how many lights and
where to place them to get the correct level of illumination
for a given activity.
What do we understand by LUX ?
The lux (symbol: lx) is the SI unit of illuminance and
luminous emittance, measuring luminous flux per unit
area. It is used in photometry as a measure of the
intensity, as perceived by the human eye, of light that hits
or passes through a surface. It is analogous to the
radiometric unit watts per square metre, but with the
power at each wavelength weighted according to the
luminosity function, a standardized model of human
visual brightness perception. In English, "lux" is used in
both singular and plural.
ILLUMINATION AND LUX:
One lux is equal to one lumen per square metre:

A lux meter for measuring illuminances in work places.
ILLUMINATION AND LUX:
One lux is equal to one lumen per square metre:
In other words ..

LUX =

Level of Illumination.

OR

LUX (lx)

=

Lumens / Sq.M.

Level of Illumination ?
LUMEN METHOD:
This method works perfectly in most cases where the
height of the ceiling is within 3000 mm from floor
level, the Working Plane is between 750 to 1000 mm and
proportions of the area are proper.
ILLUMINATION AND LUX:
How To Calculate Lux ?
How do I calculate lux - the formula?
Lux level = total light output (lumens) / area (square
meters)

Total Light Output = lumens per fixture * number of
fixtures
Therefore
Number of Fixtures = (Lux level * area) / lumens per
fixture
ILLUMINATION AND LUX:
Every Lamp has certain Lumens.

You need to look up the manufacturer data for your light
fitting to get the lumens per fixture.
S.No.
1.
2.
3.

Type of Lamp.
36 W Tube Light.
60 W GLS Lamp.
10 W CFL.

Lumens Output.
2400 Lumens.
600 Lumens.
600 Lumens.
ILLUMINATION AND LUX:
Example:
Assume a Room size of = 10000 x 8000 x 3000 = 80 Sq.M.
Area =
80 Sq.M.
Suppose the desired lux level or Illumination = 300 lx.
Total Lumens required = 300 x 80 = 24,000 lumens.
Assuming that you are using 36W Lamp (FTL) and the
same has 2,400 lumens illumination.
Number of Fixtures required = 24,000 / 2400 = 10 Nos.
So you need 10 Nos. of 36W Tube Light Fittings.
ILLUMINATION AND LUX:
What we did above is still not sufficient as there are
certain Correction Factors involved. There are basically
two Correction Factors i.e., Utilization Factor = UF and
Maintenance Factor = MF.
UTILIZATION FACTOR: (UF)
This may be due different
Reflectance's, Dimensions etc.,

reasons

viz.,

Room

The utilization factor (UF) is a Direct ratio. This is the
proportion of the downward luminous flux that reaches
the work area directly without reflection. It depends on
the shape of the room. The Direct ratio has a low value
with a tall narrow room (small RI) and a high value for a
wide room (large RI).
ILLUMINATION AND LUX:
The light distribution from the luminaries. Luminaries
that emit light through a larger solid angle will generally
have a smaller direct ratio that luminaries that emit light
in a narrower beam.
There exist data sheets of UF for rooms of different shapes
and luminaries of a common type.
Catalogues of luminaries often provide data sheets of UF
for rooms.

Normally we take 0.8 as the Utilization Factor.
ILLUMINATION AND LUX:
This utilization factor is somewhat more complicated to
determine than the maintenance factor.
The utilization factor will depend on the following:
The luminarie properties. One needs the light output ratio
(LOR). How much of the light emitted by the lamps
actually leaves the luminarie? An enclosed lamp in a
luminarie with low reflectivity will have a smaller LOR
than a naked lamp.

The light emitted downwards will probably reach the
work area without reflections. However light emitted
upwards can only reach the work area after reflection(s)
from surfaces.
ILLUMINATION AND LUX:
The utilization factor will depend on the following:
The reflectance of the room surfaces. Are the surfaces
(walls, ceiling) light or dark in color?
(A color with strong chroma does not reflect other colors).
Reflectance's are available from manufacturers of paints
and furniture finishing's.
It is usual to make the reflectance of the ceiling highest,
walls slightly lower and the floor darker.
Reflectance's of desks should be 20-40%. Do not choose
very dark wood, or bright surfaces.
The geometric proportion of the room. The geometric
shape of the room will affect the UF. A factor called the
room index (RI) is defined from the horizontal vertical
areas of the room.
ILLUMINATION AND LUX:
MAINTENANCE FACTOR: (MF)
It is also known as LLF OR Light Loss Factor. This may be
due different reasons viz., Time, Temperature, Cleanliness
etc.,
The maintenance factor gives an estimate of how lighting
conditions will deteriorate through use.
Some factors are:
• Dust and dirt inside luminaries surfaces.
• Aging of light bulbs emitting less light.
• Cleaning of room surfaces, e.g. ceiling.
Normally we take 0.75 to 0.8 as the Maintenance Factor.
ILLUMINATION AND LUX:
Coming back to our earlier Example where we said that
we need 10 Nos. of 36W Tube Light Fittings.
Now with application of UF and MF it will be as follows:
No. of Fixtures = 10 / 0.8 x 0.8 = 15.625 i.e., 16 Nos.
But practically many times to maintain the balance we
may use upto 12 Nos. of fixtures also.
Formula
for
Number of
Fixtures.

Lux x Area /
Lumen
Output x MF
x UF

300 x 80 /
2400 x 0.8 x 0.8

15.625
LIMITATION OF LUMEN METHOD:
There are certain limitations to this method, but all said
and done this works perfectly for 90% of the installations
where the parameters are within the limits.
Height is not considered.
Fixtures or luminaries changes are not considered. (Polar
curve etc.,)
Room Reflectance's are not considered.
It does not distinguish between different fixture behaviors
i.e., point source or linear source etc.,
For this there is one more complicated method known as
POIINT BY POINT METHOD. This is more specific for
experts in Lighting Design and detailing.
GLARE:
The control of glare:
Glare occurs in both natural (daylight) and in interior
lighting situations. It is most annoying in the interior light
environment where the lighting is under human control.
The glare annoyance depends on a number of factors
In a supermarket people are on the move and not always
looking in same direction.
In a classroom students are usually looking in a fixed
direction.
In a classroom, students are reading, this is a moderately
difficult visual task.
Students are fixed for a long period of time.
Standards for glare depend on the use of the visual
environment.
GLARE:
The glare index

There is quantity called the discomfort glare constant (g)
which is:
Glare index.
0 - 10
10 - 16
16 - 22
22 – 28

Reaction.
Imperceptible
Noticeable
Acceptable
Uncomfortable

> 28

Intolerable
GLARE:
More visually demanding tasks with high illuminance
levels are less tolerant of glare.
Limiting Occupations
GI
16
Drawing offices, very fine visual inspections.
Offices, libraries, keyboard and VDT work
19
(reflections from screen).

22
25
28

Kitchen, reception area, fine assembly.
Stock rooms, assembly line for easy tasks.
Indoor car park, rough industrial work.

(At present time, do not require you to calculate the glare
index, require you to know what it is and when it is most
important to eliminate.)
GLARE:
CONTROL OF GLARE:
First of all, glare from all sources is additive and people
get annoyed by all sources of discomfort glare.
Obviously, cutting down the illuminance of the glare
source, Ls is a good idea. This does not mean reducing the
light level in the room. The higher the illumination of the
background, the smaller the glare constant. So rather than
having one very bright luminaire, have a number of
dimmer luminaries.
Most of the visual tasks involve looking horizontally or
slightly down. So keep luminaries out of the low angle
vision. So do not gives walls too high a reflectance. Do not
give the floors too high reflectance (no glossy light floors!).
GLARE:
TIPS TO CONTROL GLARE:
Keep luminance of source down. Use of diffusers and
louvres. Cutting down glare also cuts down total light
emitted and this problem also needs to be tackled.
Reflected light can also be a source of glare.
Keep luminaires out of field of view. High ceilings are good.
Keep area of source small.
To cut down glare, avoid luminaires that emit light to
sides (e.g. battern luminaire with a diffuser at the
sides), light emitted more in downward direction avoids
visual discomfort.
GLARE:
UPLIGHTING:
In this form of lighting, lighting is directed upwards to the
ceiling. Reflected light from the ceiling provides the
general illumination in the room.
Advantages, elimination of glare is one of the major
advantages.
Re-introduction driven by the increasing use of
computers.
Disadvantage, it is somewhat inefficient. Low conversion
of electrical energy into usable light.
If the Ceiling is quite bright, it will have less visual
emphasis on other areas of room, furniture, floors.
To get an even illumination on the ceiling requires that
you have a high ceiling.
GLARE:
UPLIGHTING:
You either like it or not. It is possible to use combinations
of direct diffuse and indirect lighting.
Illumination can be calculated using lumen method in
conjunction with transfer function tables.
Need to maintain a uniform illumination on ceiling.
Eliminates light hot-spots that can result in glare.
Harder with low ceiling.
Besides less glare, concentrated beam downlights result in
darker ceiling. This can result in an oppressive
psychological effect.
LIGHTING STANDARDS:
What are the legal requirements for office lighting? Is
there a legal requirement for daylight?
The only legal requirements are 'sufficient and suitable'
and similar wording in health and safety legislation. There
is no absolute legal requirement for daylight, but it is a
requirement that it be provided if practicable. Various
guidance documents suggest good practice, but are not
themselves mandatory.
What is the recommended lighting level for offices?
The Code for Lighting recommends a maintained
illuminance of 500 lux for general offices (e.g. writing,
typing, reading, data processing, etc.) and for CAD work
stations and conference/meetings rooms. Where the main
task is less demanding, e.g. filing, a lower level of 300 lux
is recommended.
ILLUMINATION LEVELS AND LIMITING GLARE:
The table following lists illumination levels suitable for a
range of situations: the quality of these levels could be
influenced by glare and an acceptable limiting index is
also shown. The glare index is calculated by considering
the light source location, the luminances of the source, the
effect of surroundings and the size of the source.
Glare indices for artificial light range from about 10 for a
shaded light fitting having low output to about 30 for an
un shaded lamp.
ILLUMINATION LEVELS AND LIMITING GLARE:
As seen from this illustration, various basic decisions have
to be made concerning lighting objectives and whether the
system involves daylight, electric light or a combined
system. With electric or combined systems, further
decisions must be taken concerning the way light is
distributed by particular fittings, and upon their positions
relative to each other as well as in relation to the surface to
be illuminated. As with day lighting, light-coloured and
highly reflective room surfaces help to provide more
illumination from the same amount of energy source – it
preserves the luminance effect of the light source.
ILLUMINATION LEVELS AND LIMITING GLARE:
Location.

Illuminance. (lx)

Limiting Glare Index.

Entrance Hall.

150

22

Staircase.

150

22

Corridors.

100

22

Outdoor Entrances.

30

22

Casual Assembly Work.

200

25

Rough / Heavy Work.

300

28

Medium Assembly Work.

500

25

Fine Assembly Work.

1,000

22

Precision Work.

1,500

16

General Office Work.

500

19

Computer Room.

750

16

Drawing Office.

750

16

Filing Room.

300

22

Shop Counter.

500

22

Super Market.

500

22
ILLUMINATION LEVELS AND LIMITING GLARE:
Location.

Illuminance. (lx)

Limiting Glare Index.

Class Room.

300

16

Laboratory.

500

16

Public House Bar.

150

22

Restaurant.

100

22

Kitchen.

500

22

Living Room.

50

NA.

Reading Room.

150

NA.

Study Room.

300

NA.

Kitchen.

300

NA.

Bed Room.

50

NA.

Hall.

150

NA.

Library – Reading Area.

200

19

Library – Tables.

600

16

Library – Counter.

600

16

Dwellings:
LIGHTING LEVELS:
(lx)

Activity.

100 Casual seeing

300
500
750
1000
1500
2000

Corridors, changing rooms, stores

Loading bays, switch rooms, plant
rooms
Continuously occupied
Foyers, entrance halls, dining rooms
Libraries, sports halls, lecture
Visual tasks moderately easy
theatres.
General
offices,
kitchens,
Visual tasks moderately difficult
laboratories, retail shops.
Drawing offices, meat inspection,
Visual tasks difficult
chain stores.
General
inspection,
electronic
Visual tasks very difficult
assembly, paint work, super
markets.
Fine work and inspection, precision
Visual tasks extremely difficult
assembly.
Visual tasks exceptionally
Assembly of minute items, finished
difficult
fabric inspection.

150 Some perception of detail
200

Area.
ELECTRICAL FORMULAS:
Demand for Power (kW) = System Input Wattage (W) ÷
1,000
Energy Consumption (kWh) = System Input Wattage (kW)
x Hours of Operation/Year
Hours of Operation / Year = Operating Hours / Day x
Operating Days / Week x Operating Weeks / Year
Lighting System Efficacy (Lumens per Watt or LPW) =
System Lumen Output ÷ Input Wattage
Unit Power Density (W/ Sq.M.) = Total System Input
ELECTRICAL FORMULAS:
Wattage (W) ÷ Total Area (Sq. m.)
Watts (W) = Volts (V) x Current in Amperes (A) x Power
Factor (PF)
Voltage (V) = Current in Amperes (A) x Impedance
(Ohms) [Ohm's Law]
ECONOMIC FORMULAS:
Simple Payback on an Investment (Years) = Net
Installation Cost ÷ Annual Energy Savings.
5-Year Cash Flow = 5 Years - Payback (Years) x Annual
Energy Savings.
Simple Return on Investment (%) = [Annual Energy
Savings ÷ Net Installation Cost ] x 100
DESIGN FORMULAS:
Footcandles & Lumens
Footcandles (fc) = Total Lumens (lm) ÷ Area in Square Feet
1 Lux (lx) = 1 Footcandle (fc) x 10.76
Lux = Total Lumens ÷ Area in Square Meters
SUNLIGHT:
400 lux:

Sunrise or sunset on a clear day.

1,000 lux:

Overcast day.

10,000–25,000 lux:

Full daylight (not direct sun)

32,000–130,000 lux: Direct sunlight.

Contenu connexe

Tendances (20)

artificial lighting
artificial lightingartificial lighting
artificial lighting
 
Daylighting
Daylighting  Daylighting
Daylighting
 
Illumination basic and schemes
Illumination basic and schemesIllumination basic and schemes
Illumination basic and schemes
 
Daylighting Buildings
Daylighting BuildingsDaylighting Buildings
Daylighting Buildings
 
INTERIOR LIGHTING DESIGN A STUDENT'S GUIDE
INTERIOR LIGHTING DESIGN A STUDENT'S GUIDEINTERIOR LIGHTING DESIGN A STUDENT'S GUIDE
INTERIOR LIGHTING DESIGN A STUDENT'S GUIDE
 
Lighting
Lighting Lighting
Lighting
 
Electrical lighting design
Electrical lighting designElectrical lighting design
Electrical lighting design
 
Interior Designing: Lighting
Interior Designing: LightingInterior Designing: Lighting
Interior Designing: Lighting
 
Lighting
LightingLighting
Lighting
 
The illumination
The illuminationThe illumination
The illumination
 
Daylighting slideshare
Daylighting slideshareDaylighting slideshare
Daylighting slideshare
 
Daylight factor architecture
Daylight factor architectureDaylight factor architecture
Daylight factor architecture
 
Daylighting
DaylightingDaylighting
Daylighting
 
Solar control
Solar controlSolar control
Solar control
 
Daylighting
DaylightingDaylighting
Daylighting
 
Lighting fixtures types
Lighting fixtures typesLighting fixtures types
Lighting fixtures types
 
Natural lighting
Natural lightingNatural lighting
Natural lighting
 
Lighting design
Lighting designLighting design
Lighting design
 
Energy Efficient and sustainable Buildings
Energy Efficient  and sustainable BuildingsEnergy Efficient  and sustainable Buildings
Energy Efficient and sustainable Buildings
 
Artificial lighting
Artificial lightingArtificial lighting
Artificial lighting
 

En vedette

Bs ii-electricity-unit-iv-2012-four
Bs ii-electricity-unit-iv-2012-fourBs ii-electricity-unit-iv-2012-four
Bs ii-electricity-unit-iv-2012-fourBattula Choudary
 
Illumination - Method of calculation
Illumination - Method of calculationIllumination - Method of calculation
Illumination - Method of calculationVijay Raskar
 
Illumination Lighting
Illumination LightingIllumination Lighting
Illumination LightingVijay Raskar
 
Lighting Powerpoint
Lighting PowerpointLighting Powerpoint
Lighting Powerpointshawn8492
 
LIGHT AND LIGHTING FIXTURES
LIGHT AND LIGHTING FIXTURESLIGHT AND LIGHTING FIXTURES
LIGHT AND LIGHTING FIXTURESShamba Sarkar
 
Overview of Lighting Design using Dialux 4.6
Overview of Lighting Design using Dialux 4.6Overview of Lighting Design using Dialux 4.6
Overview of Lighting Design using Dialux 4.6Michael Santiago
 
Types of Lighting and Luminaire
Types of Lighting and LuminaireTypes of Lighting and Luminaire
Types of Lighting and Luminairekaycelles
 
Electrical Systems in a Building
Electrical Systems in a BuildingElectrical Systems in a Building
Electrical Systems in a BuildingGAURAV. H .TANDON
 
barch intro on building service
barch intro on building servicebarch intro on building service
barch intro on building serviceNivedhan Archi
 
BS 2 Electrical installation 2
BS 2 Electrical installation 2BS 2 Electrical installation 2
BS 2 Electrical installation 2Est
 
LED Bulbs: Making the Light Choice
LED Bulbs: Making the Light Choice LED Bulbs: Making the Light Choice
LED Bulbs: Making the Light Choice Eenovators Limited
 
Illumination Example 5
Illumination Example 5Illumination Example 5
Illumination Example 5Vijay Raskar
 
Artificial illumination and night lighting
Artificial illumination and night lightingArtificial illumination and night lighting
Artificial illumination and night lightingAbhi Vallabhaneni
 

En vedette (20)

Bs ii-electricity-unit-iv-2012-four
Bs ii-electricity-unit-iv-2012-fourBs ii-electricity-unit-iv-2012-four
Bs ii-electricity-unit-iv-2012-four
 
Illumination - Method of calculation
Illumination - Method of calculationIllumination - Method of calculation
Illumination - Method of calculation
 
Illumination Lighting
Illumination LightingIllumination Lighting
Illumination Lighting
 
Lighting ppt 1
Lighting ppt 1Lighting ppt 1
Lighting ppt 1
 
Lighting Powerpoint
Lighting PowerpointLighting Powerpoint
Lighting Powerpoint
 
LIGHT AND LIGHTING FIXTURES
LIGHT AND LIGHTING FIXTURESLIGHT AND LIGHTING FIXTURES
LIGHT AND LIGHTING FIXTURES
 
Overview of Lighting Design using Dialux 4.6
Overview of Lighting Design using Dialux 4.6Overview of Lighting Design using Dialux 4.6
Overview of Lighting Design using Dialux 4.6
 
Illumination.
Illumination.Illumination.
Illumination.
 
Types of Lighting and Luminaire
Types of Lighting and LuminaireTypes of Lighting and Luminaire
Types of Lighting and Luminaire
 
Building services
Building servicesBuilding services
Building services
 
Electrical Systems in a Building
Electrical Systems in a BuildingElectrical Systems in a Building
Electrical Systems in a Building
 
barch intro on building service
barch intro on building servicebarch intro on building service
barch intro on building service
 
288 lecture23 2011
288 lecture23 2011288 lecture23 2011
288 lecture23 2011
 
BS 2 Electrical installation 2
BS 2 Electrical installation 2BS 2 Electrical installation 2
BS 2 Electrical installation 2
 
Illumination
IlluminationIllumination
Illumination
 
LED Bulbs: Making the Light Choice
LED Bulbs: Making the Light Choice LED Bulbs: Making the Light Choice
LED Bulbs: Making the Light Choice
 
Illumination Example 5
Illumination Example 5Illumination Example 5
Illumination Example 5
 
Mpls
MplsMpls
Mpls
 
Artificial illumination and night lighting
Artificial illumination and night lightingArtificial illumination and night lighting
Artificial illumination and night lighting
 
MET 211 steam-tables
MET 211 steam-tablesMET 211 steam-tables
MET 211 steam-tables
 

Similaire à (5) bs-ii-electricity-unit-v-2012-five

lighting-design-essentials.pdf
lighting-design-essentials.pdflighting-design-essentials.pdf
lighting-design-essentials.pdfRaymondRivera41
 
Lighting Design - Theory and Calculations
Lighting Design - Theory and CalculationsLighting Design - Theory and Calculations
Lighting Design - Theory and CalculationsIsham Rashik
 
Electrical lighting design and calculations
Electrical lighting design and calculationsElectrical lighting design and calculations
Electrical lighting design and calculationsMusaib ul Hassan Bhat
 
How to measure illumination
How to measure illuminationHow to measure illumination
How to measure illuminationajsatienza
 
BUILDING SCIENCE 2 PROJECT 2 REPORT
BUILDING SCIENCE 2 PROJECT 2 REPORTBUILDING SCIENCE 2 PROJECT 2 REPORT
BUILDING SCIENCE 2 PROJECT 2 REPORTYvonne Chin
 
Energy performance assessment of lighting systems
Energy performance assessment of lighting systemsEnergy performance assessment of lighting systems
Energy performance assessment of lighting systemsSajid Sheikh
 
Lighting architecture lecture 3
Lighting architecture  lecture 3Lighting architecture  lecture 3
Lighting architecture lecture 3MRKextreme
 
Illumination
IlluminationIllumination
IlluminationVima Mali
 
Lighting systems 2014
Lighting systems 2014Lighting systems 2014
Lighting systems 2014ahmed salman
 
Day 3 Energy Audits of Lighting Systems
Day 3 Energy Audits of Lighting SystemsDay 3 Energy Audits of Lighting Systems
Day 3 Energy Audits of Lighting SystemsRCREEE
 
Lighting For Libraries
Lighting For LibrariesLighting For Libraries
Lighting For LibrariesDavid Aloi
 
Light analysis
Light analysisLight analysis
Light analysismrstore
 
Lighting systems and their design..mau --jmi-2014
Lighting systems and their design..mau --jmi-2014Lighting systems and their design..mau --jmi-2014
Lighting systems and their design..mau --jmi-2014Mohd Azmatullah
 
LIGHTING SYSTEMS AND THEIR DESIGN..MAU---JMI-2014
LIGHTING SYSTEMS AND THEIR DESIGN..MAU---JMI-2014LIGHTING SYSTEMS AND THEIR DESIGN..MAU---JMI-2014
LIGHTING SYSTEMS AND THEIR DESIGN..MAU---JMI-2014Mohammed Azmatullah
 

Similaire à (5) bs-ii-electricity-unit-v-2012-five (20)

Unit v
Unit vUnit v
Unit v
 
lighting-design-essentials.pdf
lighting-design-essentials.pdflighting-design-essentials.pdf
lighting-design-essentials.pdf
 
Lighting Design - Theory and Calculations
Lighting Design - Theory and CalculationsLighting Design - Theory and Calculations
Lighting Design - Theory and Calculations
 
Electrical lighting design and calculations
Electrical lighting design and calculationsElectrical lighting design and calculations
Electrical lighting design and calculations
 
How to measure illumination
How to measure illuminationHow to measure illumination
How to measure illumination
 
A guide to lux levels
A guide to lux levelsA guide to lux levels
A guide to lux levels
 
BUILDING SCIENCE 2 PROJECT 2 REPORT
BUILDING SCIENCE 2 PROJECT 2 REPORTBUILDING SCIENCE 2 PROJECT 2 REPORT
BUILDING SCIENCE 2 PROJECT 2 REPORT
 
Energy performance assessment of lighting systems
Energy performance assessment of lighting systemsEnergy performance assessment of lighting systems
Energy performance assessment of lighting systems
 
Lighting architecture lecture 3
Lighting architecture  lecture 3Lighting architecture  lecture 3
Lighting architecture lecture 3
 
Illumination
IlluminationIllumination
Illumination
 
Lighting basics book
Lighting basics bookLighting basics book
Lighting basics book
 
Lighting systems 2014
Lighting systems 2014Lighting systems 2014
Lighting systems 2014
 
Illumination of an IT building
Illumination of an IT buildingIllumination of an IT building
Illumination of an IT building
 
Day 3 Energy Audits of Lighting Systems
Day 3 Energy Audits of Lighting SystemsDay 3 Energy Audits of Lighting Systems
Day 3 Energy Audits of Lighting Systems
 
electric light sources
electric light sourceselectric light sources
electric light sources
 
seminar 2021.pptx
seminar 2021.pptxseminar 2021.pptx
seminar 2021.pptx
 
Lighting For Libraries
Lighting For LibrariesLighting For Libraries
Lighting For Libraries
 
Light analysis
Light analysisLight analysis
Light analysis
 
Lighting systems and their design..mau --jmi-2014
Lighting systems and their design..mau --jmi-2014Lighting systems and their design..mau --jmi-2014
Lighting systems and their design..mau --jmi-2014
 
LIGHTING SYSTEMS AND THEIR DESIGN..MAU---JMI-2014
LIGHTING SYSTEMS AND THEIR DESIGN..MAU---JMI-2014LIGHTING SYSTEMS AND THEIR DESIGN..MAU---JMI-2014
LIGHTING SYSTEMS AND THEIR DESIGN..MAU---JMI-2014
 

Dernier

NewBase 19 April 2024 Energy News issue - 1717 by Khaled Al Awadi.pdf
NewBase  19 April  2024  Energy News issue - 1717 by Khaled Al Awadi.pdfNewBase  19 April  2024  Energy News issue - 1717 by Khaled Al Awadi.pdf
NewBase 19 April 2024 Energy News issue - 1717 by Khaled Al Awadi.pdfKhaled Al Awadi
 
Organizational Structure Running A Successful Business
Organizational Structure Running A Successful BusinessOrganizational Structure Running A Successful Business
Organizational Structure Running A Successful BusinessSeta Wicaksana
 
Ms Motilal Padampat Sugar Mills vs. State of Uttar Pradesh & Ors. - A Milesto...
Ms Motilal Padampat Sugar Mills vs. State of Uttar Pradesh & Ors. - A Milesto...Ms Motilal Padampat Sugar Mills vs. State of Uttar Pradesh & Ors. - A Milesto...
Ms Motilal Padampat Sugar Mills vs. State of Uttar Pradesh & Ors. - A Milesto...ShrutiBose4
 
Cybersecurity Awareness Training Presentation v2024.03
Cybersecurity Awareness Training Presentation v2024.03Cybersecurity Awareness Training Presentation v2024.03
Cybersecurity Awareness Training Presentation v2024.03DallasHaselhorst
 
PSCC - Capability Statement Presentation
PSCC - Capability Statement PresentationPSCC - Capability Statement Presentation
PSCC - Capability Statement PresentationAnamaria Contreras
 
(Best) ENJOY Call Girls in Faridabad Ex | 8377087607
(Best) ENJOY Call Girls in Faridabad Ex | 8377087607(Best) ENJOY Call Girls in Faridabad Ex | 8377087607
(Best) ENJOY Call Girls in Faridabad Ex | 8377087607dollysharma2066
 
Annual General Meeting Presentation Slides
Annual General Meeting Presentation SlidesAnnual General Meeting Presentation Slides
Annual General Meeting Presentation SlidesKeppelCorporation
 
Global Scenario On Sustainable and Resilient Coconut Industry by Dr. Jelfina...
Global Scenario On Sustainable  and Resilient Coconut Industry by Dr. Jelfina...Global Scenario On Sustainable  and Resilient Coconut Industry by Dr. Jelfina...
Global Scenario On Sustainable and Resilient Coconut Industry by Dr. Jelfina...ictsugar
 
IoT Insurance Observatory: summary 2024
IoT Insurance Observatory:  summary 2024IoT Insurance Observatory:  summary 2024
IoT Insurance Observatory: summary 2024Matteo Carbone
 
Memorándum de Entendimiento (MoU) entre Codelco y SQM
Memorándum de Entendimiento (MoU) entre Codelco y SQMMemorándum de Entendimiento (MoU) entre Codelco y SQM
Memorándum de Entendimiento (MoU) entre Codelco y SQMVoces Mineras
 
Islamabad Escorts | Call 03070433345 | Escort Service in Islamabad
Islamabad Escorts | Call 03070433345 | Escort Service in IslamabadIslamabad Escorts | Call 03070433345 | Escort Service in Islamabad
Islamabad Escorts | Call 03070433345 | Escort Service in IslamabadAyesha Khan
 
Call US-88OO1O2216 Call Girls In Mahipalpur Female Escort Service
Call US-88OO1O2216 Call Girls In Mahipalpur Female Escort ServiceCall US-88OO1O2216 Call Girls In Mahipalpur Female Escort Service
Call US-88OO1O2216 Call Girls In Mahipalpur Female Escort Servicecallgirls2057
 
Pitch Deck Teardown: Geodesic.Life's $500k Pre-seed deck
Pitch Deck Teardown: Geodesic.Life's $500k Pre-seed deckPitch Deck Teardown: Geodesic.Life's $500k Pre-seed deck
Pitch Deck Teardown: Geodesic.Life's $500k Pre-seed deckHajeJanKamps
 
8447779800, Low rate Call girls in New Ashok Nagar Delhi NCR
8447779800, Low rate Call girls in New Ashok Nagar Delhi NCR8447779800, Low rate Call girls in New Ashok Nagar Delhi NCR
8447779800, Low rate Call girls in New Ashok Nagar Delhi NCRashishs7044
 
Kenya Coconut Production Presentation by Dr. Lalith Perera
Kenya Coconut Production Presentation by Dr. Lalith PereraKenya Coconut Production Presentation by Dr. Lalith Perera
Kenya Coconut Production Presentation by Dr. Lalith Pereraictsugar
 
Kenya’s Coconut Value Chain by Gatsby Africa
Kenya’s Coconut Value Chain by Gatsby AfricaKenya’s Coconut Value Chain by Gatsby Africa
Kenya’s Coconut Value Chain by Gatsby Africaictsugar
 
Digital Transformation in the PLM domain - distrib.pdf
Digital Transformation in the PLM domain - distrib.pdfDigital Transformation in the PLM domain - distrib.pdf
Digital Transformation in the PLM domain - distrib.pdfJos Voskuil
 
MAHA Global and IPR: Do Actions Speak Louder Than Words?
MAHA Global and IPR: Do Actions Speak Louder Than Words?MAHA Global and IPR: Do Actions Speak Louder Than Words?
MAHA Global and IPR: Do Actions Speak Louder Than Words?Olivia Kresic
 

Dernier (20)

NewBase 19 April 2024 Energy News issue - 1717 by Khaled Al Awadi.pdf
NewBase  19 April  2024  Energy News issue - 1717 by Khaled Al Awadi.pdfNewBase  19 April  2024  Energy News issue - 1717 by Khaled Al Awadi.pdf
NewBase 19 April 2024 Energy News issue - 1717 by Khaled Al Awadi.pdf
 
Organizational Structure Running A Successful Business
Organizational Structure Running A Successful BusinessOrganizational Structure Running A Successful Business
Organizational Structure Running A Successful Business
 
Ms Motilal Padampat Sugar Mills vs. State of Uttar Pradesh & Ors. - A Milesto...
Ms Motilal Padampat Sugar Mills vs. State of Uttar Pradesh & Ors. - A Milesto...Ms Motilal Padampat Sugar Mills vs. State of Uttar Pradesh & Ors. - A Milesto...
Ms Motilal Padampat Sugar Mills vs. State of Uttar Pradesh & Ors. - A Milesto...
 
Call Us ➥9319373153▻Call Girls In North Goa
Call Us ➥9319373153▻Call Girls In North GoaCall Us ➥9319373153▻Call Girls In North Goa
Call Us ➥9319373153▻Call Girls In North Goa
 
Cybersecurity Awareness Training Presentation v2024.03
Cybersecurity Awareness Training Presentation v2024.03Cybersecurity Awareness Training Presentation v2024.03
Cybersecurity Awareness Training Presentation v2024.03
 
PSCC - Capability Statement Presentation
PSCC - Capability Statement PresentationPSCC - Capability Statement Presentation
PSCC - Capability Statement Presentation
 
(Best) ENJOY Call Girls in Faridabad Ex | 8377087607
(Best) ENJOY Call Girls in Faridabad Ex | 8377087607(Best) ENJOY Call Girls in Faridabad Ex | 8377087607
(Best) ENJOY Call Girls in Faridabad Ex | 8377087607
 
Annual General Meeting Presentation Slides
Annual General Meeting Presentation SlidesAnnual General Meeting Presentation Slides
Annual General Meeting Presentation Slides
 
Global Scenario On Sustainable and Resilient Coconut Industry by Dr. Jelfina...
Global Scenario On Sustainable  and Resilient Coconut Industry by Dr. Jelfina...Global Scenario On Sustainable  and Resilient Coconut Industry by Dr. Jelfina...
Global Scenario On Sustainable and Resilient Coconut Industry by Dr. Jelfina...
 
IoT Insurance Observatory: summary 2024
IoT Insurance Observatory:  summary 2024IoT Insurance Observatory:  summary 2024
IoT Insurance Observatory: summary 2024
 
Memorándum de Entendimiento (MoU) entre Codelco y SQM
Memorándum de Entendimiento (MoU) entre Codelco y SQMMemorándum de Entendimiento (MoU) entre Codelco y SQM
Memorándum de Entendimiento (MoU) entre Codelco y SQM
 
Islamabad Escorts | Call 03070433345 | Escort Service in Islamabad
Islamabad Escorts | Call 03070433345 | Escort Service in IslamabadIslamabad Escorts | Call 03070433345 | Escort Service in Islamabad
Islamabad Escorts | Call 03070433345 | Escort Service in Islamabad
 
No-1 Call Girls In Goa 93193 VIP 73153 Escort service In North Goa Panaji, Ca...
No-1 Call Girls In Goa 93193 VIP 73153 Escort service In North Goa Panaji, Ca...No-1 Call Girls In Goa 93193 VIP 73153 Escort service In North Goa Panaji, Ca...
No-1 Call Girls In Goa 93193 VIP 73153 Escort service In North Goa Panaji, Ca...
 
Call US-88OO1O2216 Call Girls In Mahipalpur Female Escort Service
Call US-88OO1O2216 Call Girls In Mahipalpur Female Escort ServiceCall US-88OO1O2216 Call Girls In Mahipalpur Female Escort Service
Call US-88OO1O2216 Call Girls In Mahipalpur Female Escort Service
 
Pitch Deck Teardown: Geodesic.Life's $500k Pre-seed deck
Pitch Deck Teardown: Geodesic.Life's $500k Pre-seed deckPitch Deck Teardown: Geodesic.Life's $500k Pre-seed deck
Pitch Deck Teardown: Geodesic.Life's $500k Pre-seed deck
 
8447779800, Low rate Call girls in New Ashok Nagar Delhi NCR
8447779800, Low rate Call girls in New Ashok Nagar Delhi NCR8447779800, Low rate Call girls in New Ashok Nagar Delhi NCR
8447779800, Low rate Call girls in New Ashok Nagar Delhi NCR
 
Kenya Coconut Production Presentation by Dr. Lalith Perera
Kenya Coconut Production Presentation by Dr. Lalith PereraKenya Coconut Production Presentation by Dr. Lalith Perera
Kenya Coconut Production Presentation by Dr. Lalith Perera
 
Kenya’s Coconut Value Chain by Gatsby Africa
Kenya’s Coconut Value Chain by Gatsby AfricaKenya’s Coconut Value Chain by Gatsby Africa
Kenya’s Coconut Value Chain by Gatsby Africa
 
Digital Transformation in the PLM domain - distrib.pdf
Digital Transformation in the PLM domain - distrib.pdfDigital Transformation in the PLM domain - distrib.pdf
Digital Transformation in the PLM domain - distrib.pdf
 
MAHA Global and IPR: Do Actions Speak Louder Than Words?
MAHA Global and IPR: Do Actions Speak Louder Than Words?MAHA Global and IPR: Do Actions Speak Louder Than Words?
MAHA Global and IPR: Do Actions Speak Louder Than Words?
 

(5) bs-ii-electricity-unit-v-2012-five

  • 1. AR 4.5 BUILDING SERVICES - II: ELECTRICAL SERVICES: Unit – V: Lighting Calculation: NBC standards, nominal illumination levels in building interiors, lux, lumen, intensity, lighting schemes.
  • 2. ILLUMINATION AND LUX: What is the method for calculating illumination ? The problem of the Architect / Lighting Designer at the functional level is to determine how many lights and where to place them to get the correct level of illumination for a given activity. What do we understand by LUX ? The lux (symbol: lx) is the SI unit of illuminance and luminous emittance, measuring luminous flux per unit area. It is used in photometry as a measure of the intensity, as perceived by the human eye, of light that hits or passes through a surface. It is analogous to the radiometric unit watts per square metre, but with the power at each wavelength weighted according to the luminosity function, a standardized model of human visual brightness perception. In English, "lux" is used in both singular and plural.
  • 3. ILLUMINATION AND LUX: One lux is equal to one lumen per square metre: A lux meter for measuring illuminances in work places.
  • 4. ILLUMINATION AND LUX: One lux is equal to one lumen per square metre: In other words .. LUX = Level of Illumination. OR LUX (lx) = Lumens / Sq.M. Level of Illumination ? LUMEN METHOD: This method works perfectly in most cases where the height of the ceiling is within 3000 mm from floor level, the Working Plane is between 750 to 1000 mm and proportions of the area are proper.
  • 5. ILLUMINATION AND LUX: How To Calculate Lux ? How do I calculate lux - the formula? Lux level = total light output (lumens) / area (square meters) Total Light Output = lumens per fixture * number of fixtures Therefore Number of Fixtures = (Lux level * area) / lumens per fixture
  • 6. ILLUMINATION AND LUX: Every Lamp has certain Lumens. You need to look up the manufacturer data for your light fitting to get the lumens per fixture. S.No. 1. 2. 3. Type of Lamp. 36 W Tube Light. 60 W GLS Lamp. 10 W CFL. Lumens Output. 2400 Lumens. 600 Lumens. 600 Lumens.
  • 7. ILLUMINATION AND LUX: Example: Assume a Room size of = 10000 x 8000 x 3000 = 80 Sq.M. Area = 80 Sq.M. Suppose the desired lux level or Illumination = 300 lx. Total Lumens required = 300 x 80 = 24,000 lumens. Assuming that you are using 36W Lamp (FTL) and the same has 2,400 lumens illumination. Number of Fixtures required = 24,000 / 2400 = 10 Nos. So you need 10 Nos. of 36W Tube Light Fittings.
  • 8. ILLUMINATION AND LUX: What we did above is still not sufficient as there are certain Correction Factors involved. There are basically two Correction Factors i.e., Utilization Factor = UF and Maintenance Factor = MF. UTILIZATION FACTOR: (UF) This may be due different Reflectance's, Dimensions etc., reasons viz., Room The utilization factor (UF) is a Direct ratio. This is the proportion of the downward luminous flux that reaches the work area directly without reflection. It depends on the shape of the room. The Direct ratio has a low value with a tall narrow room (small RI) and a high value for a wide room (large RI).
  • 9. ILLUMINATION AND LUX: The light distribution from the luminaries. Luminaries that emit light through a larger solid angle will generally have a smaller direct ratio that luminaries that emit light in a narrower beam. There exist data sheets of UF for rooms of different shapes and luminaries of a common type. Catalogues of luminaries often provide data sheets of UF for rooms. Normally we take 0.8 as the Utilization Factor.
  • 10. ILLUMINATION AND LUX: This utilization factor is somewhat more complicated to determine than the maintenance factor. The utilization factor will depend on the following: The luminarie properties. One needs the light output ratio (LOR). How much of the light emitted by the lamps actually leaves the luminarie? An enclosed lamp in a luminarie with low reflectivity will have a smaller LOR than a naked lamp. The light emitted downwards will probably reach the work area without reflections. However light emitted upwards can only reach the work area after reflection(s) from surfaces.
  • 11. ILLUMINATION AND LUX: The utilization factor will depend on the following: The reflectance of the room surfaces. Are the surfaces (walls, ceiling) light or dark in color? (A color with strong chroma does not reflect other colors). Reflectance's are available from manufacturers of paints and furniture finishing's. It is usual to make the reflectance of the ceiling highest, walls slightly lower and the floor darker. Reflectance's of desks should be 20-40%. Do not choose very dark wood, or bright surfaces. The geometric proportion of the room. The geometric shape of the room will affect the UF. A factor called the room index (RI) is defined from the horizontal vertical areas of the room.
  • 12. ILLUMINATION AND LUX: MAINTENANCE FACTOR: (MF) It is also known as LLF OR Light Loss Factor. This may be due different reasons viz., Time, Temperature, Cleanliness etc., The maintenance factor gives an estimate of how lighting conditions will deteriorate through use. Some factors are: • Dust and dirt inside luminaries surfaces. • Aging of light bulbs emitting less light. • Cleaning of room surfaces, e.g. ceiling. Normally we take 0.75 to 0.8 as the Maintenance Factor.
  • 13. ILLUMINATION AND LUX: Coming back to our earlier Example where we said that we need 10 Nos. of 36W Tube Light Fittings. Now with application of UF and MF it will be as follows: No. of Fixtures = 10 / 0.8 x 0.8 = 15.625 i.e., 16 Nos. But practically many times to maintain the balance we may use upto 12 Nos. of fixtures also. Formula for Number of Fixtures. Lux x Area / Lumen Output x MF x UF 300 x 80 / 2400 x 0.8 x 0.8 15.625
  • 14. LIMITATION OF LUMEN METHOD: There are certain limitations to this method, but all said and done this works perfectly for 90% of the installations where the parameters are within the limits. Height is not considered. Fixtures or luminaries changes are not considered. (Polar curve etc.,) Room Reflectance's are not considered. It does not distinguish between different fixture behaviors i.e., point source or linear source etc., For this there is one more complicated method known as POIINT BY POINT METHOD. This is more specific for experts in Lighting Design and detailing.
  • 15. GLARE: The control of glare: Glare occurs in both natural (daylight) and in interior lighting situations. It is most annoying in the interior light environment where the lighting is under human control. The glare annoyance depends on a number of factors In a supermarket people are on the move and not always looking in same direction. In a classroom students are usually looking in a fixed direction. In a classroom, students are reading, this is a moderately difficult visual task. Students are fixed for a long period of time. Standards for glare depend on the use of the visual environment.
  • 16. GLARE: The glare index There is quantity called the discomfort glare constant (g) which is: Glare index. 0 - 10 10 - 16 16 - 22 22 – 28 Reaction. Imperceptible Noticeable Acceptable Uncomfortable > 28 Intolerable
  • 17. GLARE: More visually demanding tasks with high illuminance levels are less tolerant of glare. Limiting Occupations GI 16 Drawing offices, very fine visual inspections. Offices, libraries, keyboard and VDT work 19 (reflections from screen). 22 25 28 Kitchen, reception area, fine assembly. Stock rooms, assembly line for easy tasks. Indoor car park, rough industrial work. (At present time, do not require you to calculate the glare index, require you to know what it is and when it is most important to eliminate.)
  • 18. GLARE: CONTROL OF GLARE: First of all, glare from all sources is additive and people get annoyed by all sources of discomfort glare. Obviously, cutting down the illuminance of the glare source, Ls is a good idea. This does not mean reducing the light level in the room. The higher the illumination of the background, the smaller the glare constant. So rather than having one very bright luminaire, have a number of dimmer luminaries. Most of the visual tasks involve looking horizontally or slightly down. So keep luminaries out of the low angle vision. So do not gives walls too high a reflectance. Do not give the floors too high reflectance (no glossy light floors!).
  • 19. GLARE: TIPS TO CONTROL GLARE: Keep luminance of source down. Use of diffusers and louvres. Cutting down glare also cuts down total light emitted and this problem also needs to be tackled. Reflected light can also be a source of glare. Keep luminaires out of field of view. High ceilings are good. Keep area of source small. To cut down glare, avoid luminaires that emit light to sides (e.g. battern luminaire with a diffuser at the sides), light emitted more in downward direction avoids visual discomfort.
  • 20. GLARE: UPLIGHTING: In this form of lighting, lighting is directed upwards to the ceiling. Reflected light from the ceiling provides the general illumination in the room. Advantages, elimination of glare is one of the major advantages. Re-introduction driven by the increasing use of computers. Disadvantage, it is somewhat inefficient. Low conversion of electrical energy into usable light. If the Ceiling is quite bright, it will have less visual emphasis on other areas of room, furniture, floors. To get an even illumination on the ceiling requires that you have a high ceiling.
  • 21. GLARE: UPLIGHTING: You either like it or not. It is possible to use combinations of direct diffuse and indirect lighting. Illumination can be calculated using lumen method in conjunction with transfer function tables. Need to maintain a uniform illumination on ceiling. Eliminates light hot-spots that can result in glare. Harder with low ceiling. Besides less glare, concentrated beam downlights result in darker ceiling. This can result in an oppressive psychological effect.
  • 22. LIGHTING STANDARDS: What are the legal requirements for office lighting? Is there a legal requirement for daylight? The only legal requirements are 'sufficient and suitable' and similar wording in health and safety legislation. There is no absolute legal requirement for daylight, but it is a requirement that it be provided if practicable. Various guidance documents suggest good practice, but are not themselves mandatory. What is the recommended lighting level for offices? The Code for Lighting recommends a maintained illuminance of 500 lux for general offices (e.g. writing, typing, reading, data processing, etc.) and for CAD work stations and conference/meetings rooms. Where the main task is less demanding, e.g. filing, a lower level of 300 lux is recommended.
  • 23. ILLUMINATION LEVELS AND LIMITING GLARE: The table following lists illumination levels suitable for a range of situations: the quality of these levels could be influenced by glare and an acceptable limiting index is also shown. The glare index is calculated by considering the light source location, the luminances of the source, the effect of surroundings and the size of the source. Glare indices for artificial light range from about 10 for a shaded light fitting having low output to about 30 for an un shaded lamp.
  • 24. ILLUMINATION LEVELS AND LIMITING GLARE: As seen from this illustration, various basic decisions have to be made concerning lighting objectives and whether the system involves daylight, electric light or a combined system. With electric or combined systems, further decisions must be taken concerning the way light is distributed by particular fittings, and upon their positions relative to each other as well as in relation to the surface to be illuminated. As with day lighting, light-coloured and highly reflective room surfaces help to provide more illumination from the same amount of energy source – it preserves the luminance effect of the light source.
  • 25. ILLUMINATION LEVELS AND LIMITING GLARE: Location. Illuminance. (lx) Limiting Glare Index. Entrance Hall. 150 22 Staircase. 150 22 Corridors. 100 22 Outdoor Entrances. 30 22 Casual Assembly Work. 200 25 Rough / Heavy Work. 300 28 Medium Assembly Work. 500 25 Fine Assembly Work. 1,000 22 Precision Work. 1,500 16 General Office Work. 500 19 Computer Room. 750 16 Drawing Office. 750 16 Filing Room. 300 22 Shop Counter. 500 22 Super Market. 500 22
  • 26. ILLUMINATION LEVELS AND LIMITING GLARE: Location. Illuminance. (lx) Limiting Glare Index. Class Room. 300 16 Laboratory. 500 16 Public House Bar. 150 22 Restaurant. 100 22 Kitchen. 500 22 Living Room. 50 NA. Reading Room. 150 NA. Study Room. 300 NA. Kitchen. 300 NA. Bed Room. 50 NA. Hall. 150 NA. Library – Reading Area. 200 19 Library – Tables. 600 16 Library – Counter. 600 16 Dwellings:
  • 27. LIGHTING LEVELS: (lx) Activity. 100 Casual seeing 300 500 750 1000 1500 2000 Corridors, changing rooms, stores Loading bays, switch rooms, plant rooms Continuously occupied Foyers, entrance halls, dining rooms Libraries, sports halls, lecture Visual tasks moderately easy theatres. General offices, kitchens, Visual tasks moderately difficult laboratories, retail shops. Drawing offices, meat inspection, Visual tasks difficult chain stores. General inspection, electronic Visual tasks very difficult assembly, paint work, super markets. Fine work and inspection, precision Visual tasks extremely difficult assembly. Visual tasks exceptionally Assembly of minute items, finished difficult fabric inspection. 150 Some perception of detail 200 Area.
  • 28. ELECTRICAL FORMULAS: Demand for Power (kW) = System Input Wattage (W) ÷ 1,000 Energy Consumption (kWh) = System Input Wattage (kW) x Hours of Operation/Year Hours of Operation / Year = Operating Hours / Day x Operating Days / Week x Operating Weeks / Year Lighting System Efficacy (Lumens per Watt or LPW) = System Lumen Output ÷ Input Wattage Unit Power Density (W/ Sq.M.) = Total System Input
  • 29. ELECTRICAL FORMULAS: Wattage (W) ÷ Total Area (Sq. m.) Watts (W) = Volts (V) x Current in Amperes (A) x Power Factor (PF) Voltage (V) = Current in Amperes (A) x Impedance (Ohms) [Ohm's Law]
  • 30. ECONOMIC FORMULAS: Simple Payback on an Investment (Years) = Net Installation Cost ÷ Annual Energy Savings. 5-Year Cash Flow = 5 Years - Payback (Years) x Annual Energy Savings. Simple Return on Investment (%) = [Annual Energy Savings ÷ Net Installation Cost ] x 100
  • 31. DESIGN FORMULAS: Footcandles & Lumens Footcandles (fc) = Total Lumens (lm) ÷ Area in Square Feet 1 Lux (lx) = 1 Footcandle (fc) x 10.76 Lux = Total Lumens ÷ Area in Square Meters
  • 32. SUNLIGHT: 400 lux: Sunrise or sunset on a clear day. 1,000 lux: Overcast day. 10,000–25,000 lux: Full daylight (not direct sun) 32,000–130,000 lux: Direct sunlight.