Hyperautomation and AI/ML: A Strategy for Digital Transformation Success.pdf
DEXGate2 datasheet
1. A completely redesigned web configuration application
enables a fast and easy configuration of the DEXGate2. This
web interface can be accessed using an Smartphone, a tablet
or a PC thrnough the WiFi connection. The web interface can
also be accessed from inside DEXCell Energy Manager,
creating a seemless integration that makes future configura-
tions and upgrades even easier.
Remote and Wifi based
Configuration Interface
Connection and
supported protocols
Custom modbus drivers
DEXGate2 connects to the internet to send data to DEXCell
Energy Manager using Ethernet or its integrated 3G optional
module. It supports Modbus-RTU using RS485 (thanks to an
integrated RS845 Port) and Modbus TCP. DEXGate2 has built
in drivers for more than 80 devices from 17 manufacturers. If
no internet connection is available, the datalogger can keep
data for days or even weeks.
If some devices are not supported natively, custom drivers can
be defined using a completely new interface to get data from
virtually any Modbus device, PLC or automation software.
Description
Technical Specifications
Device Information
Interfaces
RS485: Integrated RS485 port
RS232: Integrated RS232 port
Ethernet: Ethernet port. The default address is 192.168.1.150.
WiFi: An access point is created for configuration. Just join the
network and point your smartphone browser to 172.16.0.1.
SIMCard: standard SIM card for 3G connectivity
USB: Serial USB client port for console administration.
Compatible technologies
Internet connectivity:
• Ethernet
• 3G integrated as an option
Compatible protocols:
• Modbus-RTU over RS485 port
• Modbus-TCP
Devices:
• Compatible with more than 80 modbus devices
Get the full list in: http://support.dexmatech.com
DEXGate2 is DEXMA’s new generation datalogger based on
the succesful DEXGate. It is one of the most advanced and
flexible dataloggers available for the energy management
market. With its integrated RS485 port, it enables the
cloud-based DEXCell Energy Manager EMS to acquire data
from meters and sensors using MODBUS protocol. Installa-
tion has never been easier thanks to its DIN-Rail Adapter.
Configuration is very fast thanks to a smartphone compati-
ble web interface used through WiFi.
2. The DEXGate2 is the perfect gateway for Modbus wired and wireless meter networks. It’s connectivity using 3G and Ethernet, combined
with an easy web configuration interface used through WiFi make it the right choice for your energy efficiency project.
The DEXGate2 has 1 RS485 and 1
RS232 integrated ports to be
connected to the optical probe
and a Modbus BUS. A USB Serial
port can be connected to a
computer for console tasks. A red
and green LED indicates if
everything is OK. Ethernet and 3g
(optional) are provided for the
internet connection.
Device measures
and connections
Architecture and connectivity
GSM antenna
WIFI (SMA F)
USB Serial Console
Power Supply
Sim Card
Bi-color Led Indicator
RS485 & RS232
(DB15)
3,7 cm
7,8 cm
6,7 cm
Marie Curie, 8-14
08042 Barcelona
Spain
E-mail: sales@dexmatech.com
www.dexmatech.com
@dexma
Ethernet (RJ45)
DEXGate2
Ethernet
3G
Internet
Wireless
868 Mhz/Zigbee
Modbus-RTU or Modbus-TCP
Mobile Wifi
configuration
Technical Specifications
Processor: Freescale i.MX28 at 545 MHz (ARM)
DRAM: 128MB DDR2 DRAM.
Power requirements: 7V - 50V DC.
3G Modem: Integrated optional 3G module.
Storage: 4GB eMMC Flash.
DC in: Power input 7-50V
DINRail adapter: included in package.
Consumption: 2,32W @12V
Other details
Administration:
• Configurable from smartphone through Wifi
• Web interface
• Remote Web configuration via DEXCell Energy Manager
• Use of DEXCell Energy Manager latest generation API,
which guarantees the most efficient data transmission.
Physical details:
• Operating Temperature Range: -40ºC to +85ºC
• Size and Weight: 7.8 x 6.7 x 3.7 cm <190g
• Enclosure: IP30