1. meitav-tec
M6000-T1-T2-AN
M6000 (12V) PS104
Multi-stage display controller with
individually programmable outputs,
2 outputs for Fan, 2 temperature
sensors and Fault.
General Features
The M6000-T1-T2-AN controller is the • Main Supply - 230Vac with power supply.
best multi-stage display controller on • Range temperature from 0°C-65°C
the market today. As opposed to many • Range set point for each output 0°C-60°C
complicated units, the M6000-T1-T2-AN • 6 programmable outputs, each output
makes it incredibly easy to pre-set corresponds to a stage- parameters that can be
stages and all other parameters. This, set are:
plus the 6 individually programmed - Set point
outputs, gives users the unique ability - Input to operate by: Analog, T1 or T2 (2
to “custom-build” their entire HVAC different temperature sensors) – inputs may be
control system. combined
- Differential (∆T between stages)
The M6000-T1-T2-AN offers the - Logic for output- COOL or HEAT
following: Ex: Humidifier- If HEAT is selected, output will be
• 6 outputs- fully programmable activated only if set point is HIGHER than actual
• 2 outputs for On Indication (fan) humidity
• Input for 2 temperature sensors to be - Compressor delay – Yes or No
used separately for each output (Meitav- - All outputs have Random start
tec sensors) • Analogue input can be set for different scales
•Analog Inputs (0-10Vdc) to be used (0 to 100 as % or 0 to adjustable)
separately for each output (humidity, • Fault input – Normally Open (all unit OFF)
pressure, water flow, etc)
The M6000-T1-T2-AN is suitable for even
the largest of applications such as
chillers and big air-handling units.
File: M6000-T1-T2.PPT
Pg.1 www.meitavtec.com | Email: info@meitavtec.com | Tel: +972 (3) 962 6462 Rev. 1.1 Date: 16.03.06
2. meitav-tec
M6000-T1-T2-AN
Electrical Diagram – Connection to PS-104
On
Return Air Sensor
Return Air Sensor
Indication
Stages (Fan)
Analog Input
T2 (Option)
T1 (Option)
Main Input
Out 1 (2A)
Out 2 (2A)
Out 3 (2A)
Out 4 (2A)
Out 6 (2A)
Out 5 (2A)
Out 7 (2A)
Out 8 (2A)
(Option)
230Vac
15 14 17 13 12 11 16 17 ~ 0 T1 T1 T2 T2 T3 T3
PS-104
2 3 21 4 5 6 1 22 7 8 9 10 20
13x0.5 12Vdc
10 20 1 2 3 4 5 6 7 8 22 21 9
M6000-T1-T2-AN
Electrical Diagram – Connection to PS-104-DRY
Temperature Sensor
Temperature Sensor
Dry Contact Outputs – Max 220Vac,6A
Outdoor Coil Unit B
Outdoor Coil Unit A
Return Air Sensor
On/Off Command
On/Off Command
Temp. Controller
T1 (Option)
Not Working
Not Working
Main Input
High Temp.
Low Temp.
A/C Unit A
A/C Unit A
A/C Unit B
A/C Unit B
Not in use
230Vac
Failure
Alarm
Alarm
~ 0 T1 T1 T2 T2 T3 T3
A8 B8 A3 B3 A7 B7 A1 B1 A2 B2 A4 B4
ז A5 B5 A6 B6
PS-104-DRY
22 21 1 2 3 4 5 6 7 8 9 10 20
12x0.5 12Vdc
10 20 1 2 3 4 5 6 7 8 22 21 9
M6000-T1-T2-AN
File: M6000-T1-T2.PPT
Pg.2 www.meitavtec.com | Email: info@meitavtec.com | Tel: +972 (3) 962 6462 Rev. 1.1 Date: 16.03.06
3. meitav-tec
M6000-T1-T2-AN
Sample Application
Air Handler with:
• 2 stages of cool (compressors) • Outdoor Temperature Sensor
• 2 stages of heat • Dehumidifier with stage cool 1
• Humidifier • Fresh Air damper based on outdoor temp.
Configuration for Sample Application
Stage/ System Control
Logic Setting Remarks
Output connection By
Tset – 20 First stage of cool and Dehumidifier
Cool 1
1 T1+Analog Cool An On – 55 With Time Delay (Td 1)
(Compressor)
An Off - 70 Differential 2˚C
Second stage of cool to start on 25˚C
Cool 2 With Time delay (Td 1)
2 T1 Cool Tset - 25
(Compressor)
Differential 2˚C
An On – 50 Humidifier set point 50%
3 Humidifier Analog -
An Off - 40 With a dead band of 10% bellow
First stage of Heat and reheat when
Dehumidifier On
4 Heat 1 T1 Heat Tset - 25
No time delay (Td 0)
Differential 2˚C
This is for Freeze protection – based
5 Heat 2 T2 Heat Tset - 3
on outdoor temperature
The fresh air damper will open only
Fresh Air
6 T2 Heat Tset – 21 when the outdoor temperature will be
Damper
less than 21˚C
This output will switch on the fan when
7 Fan for Cool On - -
outputs 1 to 3 are active
This output will switch on the fan when
8 Fan for Heat On - -
outputs 4 to 6 are active
File: M6000-T1-T2.PPT
Pg.3 www.meitavtec.com | Email: info@meitavtec.com | Tel: +972 (3) 962 6462 Rev. 1.1 Date: 16.03.06
4. meitav-tec
M6000-T1-T2-AN
Dimensions
15mm 53mm 15mm
38mm 45mm 43mm 40mm 30mm
Specifications – M6000 Dimensions –PS104
Temperature Range 10°C ÷ 30°C Length 147 mm
Weight 0.25 Kg Width 87 mm
Scale °C Height 40 mm
Color White Weight 0.368 Kg
Accuracy 1°C
Plastic PC/ABS
Flammability UL94V-0
Temperature Input 50K@25°C
Accessories
Part Number Description
PS-104 Power Supply
PS-104-DRY Power Supply with dry contacts
RS01 Temperature Sensor into decorative box
TS01 Temperature Sensor - 80 cm Cable
RS02 Average Temperature Sensor into decorative box
RS03 Room Temperature Sensor ±3°C
DT02 Duct Temperature Sensor
File: M6000-T1-T2.PPT
Pg.4 www.meitavtec.com | Email: info@meitavtec.com | Tel: +972 (3) 962 6462 Rev. 1.1 Date: 16.03.06