• Three categories based on Aspect Ratio (ln/h) and Shear Demand (ACI
318, Sect. 21.9.7)
a) Coupling beams (ln/h ≥ 4)
• Design as special moment frame beam (Conventional reinforced)
b) Coupling beams (ln/h < 2 and Vu > 4λ√(fc’) Acw) (Unit: English unit)
• Design as diagonal reinforced beams
c) Other coupling beams (Not falling within above two limits)
• Design as either special moment frame beam or diagonal reinforced
beam
• Right side of dashed line can be designed efficientas moment frame
beam
• Left side are better designed with diagonal reinforcement
2
3
• Flexure Design
– Design as special moment frame beams (ACI 318, Sect. 21.5)
– Reinforcement placed horizontally at top and bottom
• Shear Design
– Shear design is based on probable moment strength (use 1.25 fy)
– Within 2h of member ends, shear strength is calculated based on steel
only
• Confinement
– Hoops confine at end regions
– If ln/h is relatively small, longitudinal cannot be lapped
– Easier to use closed hoops over entire beam rather than only 2h at
each end
5
• Development Length in Tension (ACI 318, Sect. 21.7.5)
– For standard 90 deg. Hook, located within confined core
• ldh = fy db / (65 √fc’), not less than 8 db, 6 in.
– For straight bar
• ld = 2.5 x ldh for 90 deg. Hook, if depth of concrete cast in one lift
beneath the bar does not exceed 12 in.
• ld = 3.5 x ldh for 90 deg. Hook, if depth of concrete cast in one lift
beneath the bar exceeds 12 in.
• Straight bars terminated at a joint shall pass through confined core.
• Any portion of ld not within the confined core shall be increased by a
factor of 1.6.
6
7
• Shear Design
Tu = Cu = Ф As fy
Vu = 2 Tu sinα = 2ФAsfy sinα
Vn = 2Avdfy sinα ≤ 10√fc’ Acw (ACI 318, Eq. 21-9)
– Minimum four bars in each group of diagonal
• Confinement (2 Options)
a) Confine individual diagonals
b) Confine entire beam cross section
9
10
11
Confinement of Individual Diagonals
– Diagonal bars shall be enclosed by transverse reinforcement out-to-out
dimensions not smaller than bw/2 in the direction parallel to bw and
bw/5 along the other sides
– Volumetric ratio of confinement,
ρs = max (0.12 fc’ / fyt , 0.45 (Ag/Ach – 1) fc’ / fyt)
– Max. spacing = min (s0, 6db)
– s0 = 4 + (14 – hx) / 3
12
Confinement of Entire Beam Section
– Volumetric ratio of confinement,
ρs = max (0.12 fc’ / fyt , 0.45 (Ag/Ach – 1) fc’ / fyt)
– Max. spacing = min (6 in., 6db)
• Development Length
– Design for 1.25 fy in tension
• Regardless of the confinement option selected, longitudinal and transverse
reinforcement shall be distributed around the beam perimeter with total
area in each direction not less than 0.002 bw s with min. spacing of 12 in.
• Typically No. 4 or 5 bars should extend only a short distance into the wall
boundary not to develop significant tensile stress due to beam flexure
13
14
0
10
20
30
40
50
60
70
80
-0.01 0 0.01 0.02 0.03 0.04
Story
Coupling Beam Rotation
Coupling Beam Shear Hinge Rotation at V1
LOM_STG
TAB
UNI
KOC
DUZ
STL
LOM_LGP
Average
15
Coupling Beam Reinforcement Details

Contenu connexe

Tendances

Eurocode 2 design of composite concrete
Eurocode 2 design of composite concreteEurocode 2 design of composite concrete
Eurocode 2 design of composite concrete
Jo Gijbels
 

Tendances (20)

Eurocode 2 design of composite concrete
Eurocode 2 design of composite concreteEurocode 2 design of composite concrete
Eurocode 2 design of composite concrete
 
CE 72.32 (January 2016 Semester) Lecture 8 - Structural Analysis for Lateral ...
CE 72.32 (January 2016 Semester) Lecture 8 - Structural Analysis for Lateral ...CE 72.32 (January 2016 Semester) Lecture 8 - Structural Analysis for Lateral ...
CE 72.32 (January 2016 Semester) Lecture 8 - Structural Analysis for Lateral ...
 
CE 72.32 (January 2016 Semester) Lecture 2 - Design Philosophy
CE 72.32 (January 2016 Semester) Lecture 2 - Design PhilosophyCE 72.32 (January 2016 Semester) Lecture 2 - Design Philosophy
CE 72.32 (January 2016 Semester) Lecture 2 - Design Philosophy
 
Strut and Tie Model for Pile Cap
Strut and Tie Model for Pile CapStrut and Tie Model for Pile Cap
Strut and Tie Model for Pile Cap
 
CSI ETABS & SAFE MANUAL: Slab Analysis and Design to EC2
CSI ETABS & SAFE MANUAL: Slab Analysis and Design to EC2CSI ETABS & SAFE MANUAL: Slab Analysis and Design to EC2
CSI ETABS & SAFE MANUAL: Slab Analysis and Design to EC2
 
CE 72.52 - Lecture6 - Member Behavior
CE 72.52 - Lecture6 - Member BehaviorCE 72.52 - Lecture6 - Member Behavior
CE 72.52 - Lecture6 - Member Behavior
 
EC3 design
EC3 designEC3 design
EC3 design
 
Seismic Design Of Structures Project
Seismic Design Of Structures ProjectSeismic Design Of Structures Project
Seismic Design Of Structures Project
 
CE 72.52 - Lecture 8a - Retrofitting of RC Members
CE 72.52 - Lecture 8a - Retrofitting of RC MembersCE 72.52 - Lecture 8a - Retrofitting of RC Members
CE 72.52 - Lecture 8a - Retrofitting of RC Members
 
CE 72.52 - Lecture 7 - Strut and Tie Models
CE 72.52 - Lecture 7 - Strut and Tie ModelsCE 72.52 - Lecture 7 - Strut and Tie Models
CE 72.52 - Lecture 7 - Strut and Tie Models
 
CE 72.32 (January 2016 Semester): Lecture 1a - Overview of Tall Buildings
CE 72.32 (January 2016 Semester): Lecture 1a - Overview of Tall BuildingsCE 72.32 (January 2016 Semester): Lecture 1a - Overview of Tall Buildings
CE 72.32 (January 2016 Semester): Lecture 1a - Overview of Tall Buildings
 
CE 72.32 (January 2016 Semester) Lecture 5 - Preliminary Design and Sizing
CE 72.32 (January 2016 Semester) Lecture 5 - Preliminary Design and SizingCE 72.32 (January 2016 Semester) Lecture 5 - Preliminary Design and Sizing
CE 72.32 (January 2016 Semester) Lecture 5 - Preliminary Design and Sizing
 
Beam design
Beam designBeam design
Beam design
 
Dynamic Response
Dynamic ResponseDynamic Response
Dynamic Response
 
Simplified notes of calculate Wind & Snow loads based on CYS EC1
Simplified notes of calculate Wind & Snow loads based on CYS EC1Simplified notes of calculate Wind & Snow loads based on CYS EC1
Simplified notes of calculate Wind & Snow loads based on CYS EC1
 
Rcc structure design by etabs (acecoms)
Rcc structure design by etabs (acecoms)Rcc structure design by etabs (acecoms)
Rcc structure design by etabs (acecoms)
 
Conceptual Design in Structural System Development
Conceptual Design in Structural System DevelopmentConceptual Design in Structural System Development
Conceptual Design in Structural System Development
 
Seismic assessment of buildings accordance to Eurocode 8 Part 3
Seismic assessment of buildings accordance to Eurocode 8 Part 3Seismic assessment of buildings accordance to Eurocode 8 Part 3
Seismic assessment of buildings accordance to Eurocode 8 Part 3
 
ETABS manual - Seismic design of steel buildings according to Eurocode 3 & 8
ETABS manual - Seismic design of steel buildings according to Eurocode 3 & 8 ETABS manual - Seismic design of steel buildings according to Eurocode 3 & 8
ETABS manual - Seismic design of steel buildings according to Eurocode 3 & 8
 
CE 72.32 (January 2016 Semester) Lecture 7 - Structural Analysis for Gravity ...
CE 72.32 (January 2016 Semester) Lecture 7 - Structural Analysis for Gravity ...CE 72.32 (January 2016 Semester) Lecture 7 - Structural Analysis for Gravity ...
CE 72.32 (January 2016 Semester) Lecture 7 - Structural Analysis for Gravity ...
 

En vedette (7)

CE72.52 - Lecture 2 - Material Behavior
CE72.52 - Lecture 2 - Material BehaviorCE72.52 - Lecture 2 - Material Behavior
CE72.52 - Lecture 2 - Material Behavior
 
CE72.52 - Lecture 3a - Section Behavior - Flexure
CE72.52 - Lecture 3a - Section Behavior - FlexureCE72.52 - Lecture 3a - Section Behavior - Flexure
CE72.52 - Lecture 3a - Section Behavior - Flexure
 
CE72.52 - Lecture1 - Introduction
CE72.52 - Lecture1 - IntroductionCE72.52 - Lecture1 - Introduction
CE72.52 - Lecture1 - Introduction
 
CE 72.32 (January 2016 Semester) Lecture 4 - Selection of Structural Systems
CE 72.32 (January 2016 Semester) Lecture 4 - Selection of Structural SystemsCE 72.32 (January 2016 Semester) Lecture 4 - Selection of Structural Systems
CE 72.32 (January 2016 Semester) Lecture 4 - Selection of Structural Systems
 
CE 72.52 - Lecture 8b - Retrofitting of RC Members
CE 72.52 - Lecture 8b - Retrofitting of RC MembersCE 72.52 - Lecture 8b - Retrofitting of RC Members
CE 72.52 - Lecture 8b - Retrofitting of RC Members
 
CE 72.32 (January 2016 Semester) Lecture 6 - Overview of Finite Element Analysis
CE 72.32 (January 2016 Semester) Lecture 6 - Overview of Finite Element AnalysisCE 72.32 (January 2016 Semester) Lecture 6 - Overview of Finite Element Analysis
CE 72.32 (January 2016 Semester) Lecture 6 - Overview of Finite Element Analysis
 
CE 72.52 Lecture 4 - Ductility of Cross-sections
CE 72.52 Lecture 4 - Ductility of Cross-sectionsCE 72.52 Lecture 4 - Ductility of Cross-sections
CE 72.52 Lecture 4 - Ductility of Cross-sections
 

Similaire à AITC Coupling Beam Design Procedure (20151106)

140204-5-PTI EDC-130-Continuous Members-41.pdf
140204-5-PTI EDC-130-Continuous Members-41.pdf140204-5-PTI EDC-130-Continuous Members-41.pdf
140204-5-PTI EDC-130-Continuous Members-41.pdf
ephrem53
 
fdocuments.in_design-of-singly-reinforced-5681874f52c1b.ppt
fdocuments.in_design-of-singly-reinforced-5681874f52c1b.pptfdocuments.in_design-of-singly-reinforced-5681874f52c1b.ppt
fdocuments.in_design-of-singly-reinforced-5681874f52c1b.ppt
SuvenduMajumder
 
Welcometothepresentationon 131127120041-phpapp01
Welcometothepresentationon 131127120041-phpapp01Welcometothepresentationon 131127120041-phpapp01
Welcometothepresentationon 131127120041-phpapp01
Alemu Workeneh
 

Similaire à AITC Coupling Beam Design Procedure (20151106) (20)

Column Design - As per BS Code.ppt
Column Design  - As per BS Code.pptColumn Design  - As per BS Code.ppt
Column Design - As per BS Code.ppt
 
Column_Design_As_per_BS_Code and IS .ppt
Column_Design_As_per_BS_Code and IS .pptColumn_Design_As_per_BS_Code and IS .ppt
Column_Design_As_per_BS_Code and IS .ppt
 
Column design as per bs code
Column design    as per bs codeColumn design    as per bs code
Column design as per bs code
 
Column design: as per bs code
Column design: as per bs codeColumn design: as per bs code
Column design: as per bs code
 
140204-5-PTI EDC-130-Continuous Members-41.pdf
140204-5-PTI EDC-130-Continuous Members-41.pdf140204-5-PTI EDC-130-Continuous Members-41.pdf
140204-5-PTI EDC-130-Continuous Members-41.pdf
 
Axially Loaded Column
Axially Loaded ColumnAxially Loaded Column
Axially Loaded Column
 
Design of singly reinforced.
Design of singly reinforced.Design of singly reinforced.
Design of singly reinforced.
 
3 Beams.pptx
3 Beams.pptx3 Beams.pptx
3 Beams.pptx
 
Column math
Column mathColumn math
Column math
 
3F TO 5F BEAM DESIGN SUMMARY.pdf
3F TO 5F BEAM DESIGN SUMMARY.pdf3F TO 5F BEAM DESIGN SUMMARY.pdf
3F TO 5F BEAM DESIGN SUMMARY.pdf
 
3F TO 5F BEAM DESIGN SUMMARY.pdf
3F TO 5F BEAM DESIGN SUMMARY.pdf3F TO 5F BEAM DESIGN SUMMARY.pdf
3F TO 5F BEAM DESIGN SUMMARY.pdf
 
fdocuments.in_design-of-singly-reinforced-5681874f52c1b.ppt
fdocuments.in_design-of-singly-reinforced-5681874f52c1b.pptfdocuments.in_design-of-singly-reinforced-5681874f52c1b.ppt
fdocuments.in_design-of-singly-reinforced-5681874f52c1b.ppt
 
RCC column_Shortly Axially Loaded column.pptx
RCC column_Shortly Axially Loaded column.pptxRCC column_Shortly Axially Loaded column.pptx
RCC column_Shortly Axially Loaded column.pptx
 
DACS_UNIT-3- RCC Flat slab ARP.pptx
DACS_UNIT-3- RCC Flat slab ARP.pptxDACS_UNIT-3- RCC Flat slab ARP.pptx
DACS_UNIT-3- RCC Flat slab ARP.pptx
 
design-of-singly-reinforced-beam.ppt
design-of-singly-reinforced-beam.pptdesign-of-singly-reinforced-beam.ppt
design-of-singly-reinforced-beam.ppt
 
Lec.8 strength design method t beams
Lec.8   strength design method t beamsLec.8   strength design method t beams
Lec.8 strength design method t beams
 
James Wight - ACI Building Code-01-54.pdf
James Wight - ACI Building Code-01-54.pdfJames Wight - ACI Building Code-01-54.pdf
James Wight - ACI Building Code-01-54.pdf
 
Building project rc column
Building project rc columnBuilding project rc column
Building project rc column
 
Welcometothepresentationon 131127120041-phpapp01
Welcometothepresentationon 131127120041-phpapp01Welcometothepresentationon 131127120041-phpapp01
Welcometothepresentationon 131127120041-phpapp01
 
0 ne way slab
0 ne way slab0 ne way slab
0 ne way slab
 

Dernier

XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
ssuser89054b
 
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
MsecMca
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
dollysharma2066
 
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Kandungan 087776558899
 
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
dharasingh5698
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
dharasingh5698
 

Dernier (20)

Generative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPTGenerative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPT
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
 
chapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringchapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineering
 
22-prompt engineering noted slide shown.pdf
22-prompt engineering noted slide shown.pdf22-prompt engineering noted slide shown.pdf
22-prompt engineering noted slide shown.pdf
 
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
 
A Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityA Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna Municipality
 
DC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationDC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equation
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
 
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
 
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
 
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced LoadsFEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
 
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
Minimum and Maximum Modes of microprocessor 8086
Minimum and Maximum Modes of microprocessor 8086Minimum and Maximum Modes of microprocessor 8086
Minimum and Maximum Modes of microprocessor 8086
 

AITC Coupling Beam Design Procedure (20151106)

  • 2. • Three categories based on Aspect Ratio (ln/h) and Shear Demand (ACI 318, Sect. 21.9.7) a) Coupling beams (ln/h ≥ 4) • Design as special moment frame beam (Conventional reinforced) b) Coupling beams (ln/h < 2 and Vu > 4λ√(fc’) Acw) (Unit: English unit) • Design as diagonal reinforced beams c) Other coupling beams (Not falling within above two limits) • Design as either special moment frame beam or diagonal reinforced beam • Right side of dashed line can be designed efficientas moment frame beam • Left side are better designed with diagonal reinforcement 2
  • 3. 3
  • 4.
  • 5. • Flexure Design – Design as special moment frame beams (ACI 318, Sect. 21.5) – Reinforcement placed horizontally at top and bottom • Shear Design – Shear design is based on probable moment strength (use 1.25 fy) – Within 2h of member ends, shear strength is calculated based on steel only • Confinement – Hoops confine at end regions – If ln/h is relatively small, longitudinal cannot be lapped – Easier to use closed hoops over entire beam rather than only 2h at each end 5
  • 6. • Development Length in Tension (ACI 318, Sect. 21.7.5) – For standard 90 deg. Hook, located within confined core • ldh = fy db / (65 √fc’), not less than 8 db, 6 in. – For straight bar • ld = 2.5 x ldh for 90 deg. Hook, if depth of concrete cast in one lift beneath the bar does not exceed 12 in. • ld = 3.5 x ldh for 90 deg. Hook, if depth of concrete cast in one lift beneath the bar exceeds 12 in. • Straight bars terminated at a joint shall pass through confined core. • Any portion of ld not within the confined core shall be increased by a factor of 1.6. 6
  • 7. 7
  • 8.
  • 9. • Shear Design Tu = Cu = Ф As fy Vu = 2 Tu sinα = 2ФAsfy sinα Vn = 2Avdfy sinα ≤ 10√fc’ Acw (ACI 318, Eq. 21-9) – Minimum four bars in each group of diagonal • Confinement (2 Options) a) Confine individual diagonals b) Confine entire beam cross section 9
  • 10. 10
  • 11. 11
  • 12. Confinement of Individual Diagonals – Diagonal bars shall be enclosed by transverse reinforcement out-to-out dimensions not smaller than bw/2 in the direction parallel to bw and bw/5 along the other sides – Volumetric ratio of confinement, ρs = max (0.12 fc’ / fyt , 0.45 (Ag/Ach – 1) fc’ / fyt) – Max. spacing = min (s0, 6db) – s0 = 4 + (14 – hx) / 3 12
  • 13. Confinement of Entire Beam Section – Volumetric ratio of confinement, ρs = max (0.12 fc’ / fyt , 0.45 (Ag/Ach – 1) fc’ / fyt) – Max. spacing = min (6 in., 6db) • Development Length – Design for 1.25 fy in tension • Regardless of the confinement option selected, longitudinal and transverse reinforcement shall be distributed around the beam perimeter with total area in each direction not less than 0.002 bw s with min. spacing of 12 in. • Typically No. 4 or 5 bars should extend only a short distance into the wall boundary not to develop significant tensile stress due to beam flexure 13
  • 14. 14 0 10 20 30 40 50 60 70 80 -0.01 0 0.01 0.02 0.03 0.04 Story Coupling Beam Rotation Coupling Beam Shear Hinge Rotation at V1 LOM_STG TAB UNI KOC DUZ STL LOM_LGP Average