Electricity distribution

Electricity distribution is the final stage in the delivery of electricity to end users. A distribution
system's network carries electricity from the transmission system and delivers it to consumers.
Typically, the network would include medium-voltage (less than 50 kV) power lines, substations
and pole-mounted transformers, low-voltage (less than 1 kV) distribution wiring and sometimes
meters.




History
In the early days of electricity distribution, direct current (DC) generators were connected to
loads at the same voltage. The generation, transmission and loads had to be of the same voltage
because there was no way of changing DC voltage levels, other than inefficient motor-generator
sets. Low DC voltages were used (on the order of 100 volts) since that was a practical voltage for
incandescent lamps, which were the primary electrical load. Low voltage also required less
insulation for safe distribution within buildings.

The losses in a cable are proportional to the square of the current, the length of the cable, and the
resistivity of the material, and are inversely proportional to cross-sectional area. Early
transmission networks used copper cable, which is one of the best economically feasible
conductors for this application. To reduce the current and copper required for a given quantity of
power transmitted would require a higher transmission voltage, but no efficient method existed
to change the voltage of DC power circuits. To keep losses to an economically practical level the
Edison DC system needed thick cables and local generators. Early DC generating plants needed
to be within about 1.5 miles (2.4 km) of the farthest customer to avoid excessively large and
expensive conductors.

[edit] Introduction of alternating current
General layout of electricity networks

The competition between the direct current (DC) of Thomas Edison and the alternating current
(AC) of Nikola Tesla and George Westinghouse was known as the War of Currents. At the
conclusion of their campaigning, AC became the dominant form of transmission of power.
Power transformers, installed at power stations, could be used to raise the voltage from the
generators, and transformers at local substations could reduce voltage to supply loads. Increasing
the voltage reduced the current in the transmission and distribution lines and hence the size of
conductors and distribution losses. This made it more economical to distribute power over long
distances. Generators (such as hydroelectric sites) could be located far from the loads.

In North America, early distribution systems used a voltage of 2.2 kV corner-grounded delta.
Over time, this was gradually increased to 2.4 kV. As cities grew, most 2.4 kV systems were
upgraded to 2.4/4.16 kV, three-phase systems. In three phase networks that permit connections
between phase and neutral, both the phase-to-phase voltage (4160, in this example) and the
phase-to-neutral voltage are given; if only one value is shown, the network does not serve single-
phase loads connected phase-to-neutral. Some city and suburban distribution systems continue to
use this range of voltages, but most have been converted to 7200/12470Y, 7620/13200Y,
14400/24940Y, and 19920/34500Y.

European systems used 3.3 kV to ground, in support of the 220/380Y volt power systems used in
those countries. In the UK, urban systems progressed to 6.6 kV and then 11 kV (phase to phase),
the most common distribution voltage.
North American and European power distribution systems also differ in that North American
systems tend to have a greater number of low-voltage step-down transformers located close to
customers' premises. For example, in the US a pole-mounted transformer in a suburban setting
may supply 7-8 houses, whereas in the UK a typical urban or suburban low-voltage substation
would normally be rated between 315 kVA and 1 MVA and supply a whole neighbourhood. This
is because the higher voltage used in Europe (415 V vs 230 V) may be carried over a greater
distance with acceptable power loss. An advantage of the North American setup is that failure or
maintenance on a single transformer will only affect a few customers. Advantages of the UK
setup are that the transformers may be fewer, larger and more efficient, and due to diversity there
need be less spare capacity in the transformers, reducing power wastage. In North American city
areas with many customers per unit area, network distribution will be used, with multiple
transformers and low-voltage buses interconnected over several city blocks.

Rural Electrification systems, in contrast to urban systems, tend to use higher voltages because of
the longer distances covered by those distribution lines (see Rural Electrification
Administration). 7.2, 12.47, 25, and 34.5 kV distribution is common in the United States; 11 kV
and 33 kV are common in the UK, New Zealand and Australia; 11 kV and 22 kV are common in
South Africa. Other voltages are occasionally used.

In New Zealand, Australia, Saskatchewan, Canada, and South Africa, single wire earth return
systems (SWER) are used to electrify remote rural areas.

While power electronics now allow for conversion between DC voltage levels, AC is still used in
distribution due to the economy, efficiency and reliability of transformers. High-voltage DC is
used for transmission of large blocks of power over long distances, or for interconnecting
adjacent AC networks, but not for distribution to customers. Electric power is normally
generated at 11-25kV in a power station. To transmit over long distances, it is then stepped-up to
400kV, 220kV or 132kV as necessary. Power is carried through a transmission network of high
voltage lines. Usually, these lines run into hundreds of kilometres and deliver the power into a
common power pool called the grid. The grid is connected to load centres (cities) through a sub-
transmission network of normally 33kV (or sometimes 66kV) lines. These lines terminate into a
33kV (or 66kV) substation, where the voltage is stepped-down to 11kV for power distribution to
load points through a distribution network of lines at 11kV and lower
Modern distribution systems




Electric distribution substations transform power from transmission voltage to the lower voltage
used for local distribution to homes and businesses

The modern distribution system begins as the primary circuit leaves the sub-station and ends as
the secondary service enters the customer's meter socket. Distribution circuits serve many
customers. The voltage used is appropriate for the shorter distance and varies from 2,300 to
about 35,000 volts depending on utility standard practice, distance, and load to be served.
Distribution circuits are fed from a transformer located in an electrical substation, where the
voltage is reduced from the high values used for power transmission.

Conductors for distribution may be carried on overhead pole lines, or in densely-populated areas
where they are buried underground. Urban and suburban distribution is done with three-phase
systems to serve both residential, commercial, and industrial loads. Distribution in rural areas
may be only single-phase if it is not economical to install three-phase power for relatively few
and small customers.

Only large consumers are fed directly from distribution voltages; most utility customers are
connected to a transformer, which reduces the distribution voltage to the relatively low voltage
used by lighting and interior wiring systems. The transformer may be pole-mounted or set on the
ground in a protective enclosure. In rural areas a pole-mount transformer may serve only one
customer, but in more built-up areas multiple customers may be connected. In very dense city
areas, a secondary network may be formed with many transformers feeding into a common bus
at the utilization voltage. Each customer has an "electrical service" or "service drop" connection
and a meter for billing. (Some very small loads, such as yard lights, may be too small to meter
and so are charged only a monthly rate.)

A ground connection to local earth is normally provided for the customer's system as well as for
the equipment owned by the utility. The purpose of connecting the customer's system to ground
is to limit the voltage that may develop if high voltage conductors fall on the lower-voltage
conductors, or if a failure occurs within a distribution transformer. If all conductive objects are
bonded to the same earth grounding system, the risk of electric shock is minimized. However,
multiple connections between the utility ground and customer ground can lead to stray voltage
problems; customer piping, swimming pools or other equipment may develop objectionable
voltages. These problems may be difficult to resolve since they often originate from places other
than the customer's premises.

International differences

In many areas, "delta" three phase service is common. Delta service has no distributed neutral
wire and is therefore less expensive. In North America and Latin America, three phase service is
often a Y (wye) in which the neutral is directly connected to the center of the generator rotor. The
neutral provides a low-resistance metallic return to the distribution transformer. Wye service is
recognizable when a line has four conductors, one of which is lightly insulated. Three-phase wye
service is excellent for motors and heavy power use.

Many areas in the world use single-phase 220 V or 230 V residential and light industrial service.
In this system, the high voltage distribution network supplies a few substations per area, and the
230 V power from each substation is directly distributed. A live (hot) wire and neutral are
connected to the building from one phase of three phase service. Single-phase distribution is
used where motor loads are small.

Americas

In the U.S. and parts of Canada and Latin America, split phase service is the most common. Split
phase provides both 120 V and 240 V service with only three wires. The house voltages are
provided by local transformers. The neutral is directly connected to the three-phase neutral.
Socket voltages are only 120 V, but 240 V is available for heavy appliances because the two
halves of a phase oppose each other.[1]

Europe

In Europe, electricity is normally distributed for industry and domestic use by the three-phase,
four wire system. This gives a three-phase voltage of 400 volts and a single-phase voltage of 230
volts. For industrial customers, 3-phase 690 / 400 volt is also available.[citation needed]

Japan

Japan has a large number of small industrial manufacturers, and therefore supplies standard low-
voltage three phase-service in many suburbs. Also, Japan normally supplies residential service as
two phases of a three phase service, with a neutral. These work well for both lighting and motors.

Rural services

Rural services normally try to minimize the number of poles and wires. Single-wire earth return
(SWER) is the least expensive, with one wire. It uses high voltages, which in turn permit use of
galvanized steel wire. The strong steel wire permits inexpensive wide pole spacings. Other areas
use high voltage split-phase or three phase service at higher cost.

Metering
Electricity meters use different metering equations depending on the form of electrical service.
Since the math differs from service to service, the number of conductors and sensors in the
meters also vary.

[edit] Terms

Besides referring to the physical wiring, the term electrical service also refers in an abstract
sense to the provision of electricity to a building.

[edit] Distribution network configurations




Substation near Yellowknife, in the Northwest Territories of Canada

Distribution networks are typically of two types, radial or interconnected (see spot network). A
radial network leaves the station and passes through the network area with no normal connection
to any other supply. This is typical of long rural lines with isolated load areas. An interconnected
network is generally found in more urban areas and will have multiple connections to other
points of supply. These points of connection are normally open but allow various configurations
by the operating utility by closing and opening switches. Operation of these switches may be by
remote control from a control center or by a lineman. The benefit of the interconnected model is
that in the event of a fault or required maintenance a small area of network can be isolated and
the remainder kept on supply.

Within these networks there may be a mix of overhead line construction utilizing traditional
utility poles and wires and, increasingly, underground construction with cables and indoor or
cabinet substations. However, underground distribution is significantly more expensive than
overhead construction. In part to reduce this cost, underground power lines are sometimes co-
located with other utility lines in what are called common utility ducts. Distribution feeders
emanating from a substation are generally controlled by a circuit breaker which will open when a
fault is detected. Automatic circuit reclosers may be installed to further segregate the feeder thus
minimizing the impact of faults.

Long feeders experience voltage drop requiring capacitors or voltage regulators to be installed.

Characteristics of the supply given to customers are generally mandated by contract between the
supplier and customer. Variables of the supply include:
AC or DC - Virtually all public electricity supplies are AC today. Users of large amounts
       of DC power such as some electric railways, telephone exchanges and industrial
       processes such as aluminium smelting usually either operate their own or have adjacent
       dedicated generating equipment, or use rectifiers to derive DC from the public AC supply
       Voltage, including tolerance (usually +10 or -15 percent)
       Frequency, commonly 50 or 60 Hz, 16.6 Hz for some railways and, in a few older
       industrial and mining locations, 25 Hz.[2]
       Phase configuration (single phase, polyphase including two-phase and three phase)
       Maximum demand (usually measured as the largest amount of power delivered within a
       15 or 30 minute period during a billing period)
       Load factor, expressed as a ratio of average load to peak load over a period of time. Load
       factor indicates the degree of effective utilization of equipment (and capital investment)
       of distribution line or system.
       Power factor of connected load
       Earthing arrangements - TT, TN-S, TN-C-S or TN-C
       Prospective short circuit current
       Maximum level and frequency of occurrence of transients

Distribution industry
Traditionally the electricity industry has been a publicly owned institution but starting in the
1970s nations began the process of deregulation and privatisation, leading to electricity markets.
A major focus of these was the elimination of the former so called natural monopoly of
generation, transmission, and distribution. As a consequence, electricity has become more of a
commodity. The separation has also led to the development of new terminology to describe the
business units (e.g., line company, wires business and network company).

Contenu connexe

Tendances

Tendances (20)

Electrical distribution system
Electrical distribution system Electrical distribution system
Electrical distribution system
 
STUDY OF ELECTRICAL POWER GENERATION, TRANSMISSION AND DISTRIBUTION IN BANG...
STUDY OF  ELECTRICAL POWER GENERATION,  TRANSMISSION AND DISTRIBUTION IN BANG...STUDY OF  ELECTRICAL POWER GENERATION,  TRANSMISSION AND DISTRIBUTION IN BANG...
STUDY OF ELECTRICAL POWER GENERATION, TRANSMISSION AND DISTRIBUTION IN BANG...
 
Electric system
Electric systemElectric system
Electric system
 
Comparison of overhead and underground transmission lines
Comparison of overhead and underground transmission linesComparison of overhead and underground transmission lines
Comparison of overhead and underground transmission lines
 
Ac distribution system
Ac distribution systemAc distribution system
Ac distribution system
 
Electrical Installation PPT (Basic Electrical Engineering)
Electrical Installation PPT (Basic Electrical Engineering)Electrical Installation PPT (Basic Electrical Engineering)
Electrical Installation PPT (Basic Electrical Engineering)
 
Electrical wiring system - and estimation
Electrical wiring system -  and estimation Electrical wiring system -  and estimation
Electrical wiring system - and estimation
 
Overhead line work ppt
Overhead line work pptOverhead line work ppt
Overhead line work ppt
 
Distribution boards and Protection devices ppt
Distribution boards and Protection devices  pptDistribution boards and Protection devices  ppt
Distribution boards and Protection devices ppt
 
Electrical Wiring Practices and Diagrams
Electrical Wiring Practices and DiagramsElectrical Wiring Practices and Diagrams
Electrical Wiring Practices and Diagrams
 
WIRING ACCESORIES AND LIGHTING.pptx
WIRING ACCESORIES AND LIGHTING.pptxWIRING ACCESORIES AND LIGHTING.pptx
WIRING ACCESORIES AND LIGHTING.pptx
 
Electrical Power substation
Electrical Power substationElectrical Power substation
Electrical Power substation
 
INSULATORS AND ITS TYPES
INSULATORS AND ITS TYPESINSULATORS AND ITS TYPES
INSULATORS AND ITS TYPES
 
Substation Training presentation
Substation Training presentationSubstation Training presentation
Substation Training presentation
 
Electrical wiring system
Electrical wiring systemElectrical wiring system
Electrical wiring system
 
Domestic wiring ppt
Domestic wiring pptDomestic wiring ppt
Domestic wiring ppt
 
electrical distribution system ppt/13b61a0221
electrical distribution system ppt/13b61a0221electrical distribution system ppt/13b61a0221
electrical distribution system ppt/13b61a0221
 
Introduction to electric power transmission and distribution
Introduction to electric power transmission and distributionIntroduction to electric power transmission and distribution
Introduction to electric power transmission and distribution
 
Wiring systems
Wiring systemsWiring systems
Wiring systems
 
Transmission and distribution system of electricity
Transmission and distribution system of electricity Transmission and distribution system of electricity
Transmission and distribution system of electricity
 

En vedette (9)

Euthanasia presentation
Euthanasia presentationEuthanasia presentation
Euthanasia presentation
 
Should Euthanasia Be Legal?
Should Euthanasia Be Legal?Should Euthanasia Be Legal?
Should Euthanasia Be Legal?
 
Euthanasia and physician assisted suicide
Euthanasia and physician assisted suicideEuthanasia and physician assisted suicide
Euthanasia and physician assisted suicide
 
Euthanasia
EuthanasiaEuthanasia
Euthanasia
 
Euthanasia Slide Presentation ..
Euthanasia Slide Presentation ..Euthanasia Slide Presentation ..
Euthanasia Slide Presentation ..
 
Euthanasia Presentation
Euthanasia PresentationEuthanasia Presentation
Euthanasia Presentation
 
Sean Davison - Euthanasia: The right to die with dignity
Sean Davison - Euthanasia: The right to die with dignitySean Davison - Euthanasia: The right to die with dignity
Sean Davison - Euthanasia: The right to die with dignity
 
Euthanasia
EuthanasiaEuthanasia
Euthanasia
 
Euthanasia - Types, Arguments For and Against
Euthanasia - Types, Arguments For and AgainstEuthanasia - Types, Arguments For and Against
Euthanasia - Types, Arguments For and Against
 

Similaire à Electricity distribution

8575R 50% Complete
8575R 50% Complete8575R 50% Complete
8575R 50% Complete
hiidrasidi
 

Similaire à Electricity distribution (20)

Electrical Transmission System Notes 3a.pptx
Electrical Transmission System Notes 3a.pptxElectrical Transmission System Notes 3a.pptx
Electrical Transmission System Notes 3a.pptx
 
Basics of AC transmission
Basics of AC transmissionBasics of AC transmission
Basics of AC transmission
 
HIGH VOLTAGE AC TRANSMISSION.pptx
HIGH VOLTAGE AC TRANSMISSION.pptxHIGH VOLTAGE AC TRANSMISSION.pptx
HIGH VOLTAGE AC TRANSMISSION.pptx
 
Electric power grid
Electric power gridElectric power grid
Electric power grid
 
Electric09
Electric09Electric09
Electric09
 
Chapter 2 transmission line parameters
Chapter 2  transmission line parametersChapter 2  transmission line parameters
Chapter 2 transmission line parameters
 
8575R 50% Complete
8575R 50% Complete8575R 50% Complete
8575R 50% Complete
 
Thermal power plant working
Thermal power plant workingThermal power plant working
Thermal power plant working
 
Electrical power distribution and utilization
Electrical power distribution and utilizationElectrical power distribution and utilization
Electrical power distribution and utilization
 
Theory of HVDC transmission
Theory of HVDC transmission Theory of HVDC transmission
Theory of HVDC transmission
 
Pdu 2021 s2
Pdu 2021 s2Pdu 2021 s2
Pdu 2021 s2
 
Electric power transmission full explanation and presentation
Electric power transmission full explanation and presentationElectric power transmission full explanation and presentation
Electric power transmission full explanation and presentation
 
315564438 hvdc-transmission-ppt
315564438 hvdc-transmission-ppt315564438 hvdc-transmission-ppt
315564438 hvdc-transmission-ppt
 
Comparative evaluation of hvdc
Comparative evaluation of hvdcComparative evaluation of hvdc
Comparative evaluation of hvdc
 
Edited hvdc2222upload
Edited hvdc2222uploadEdited hvdc2222upload
Edited hvdc2222upload
 
Principles of Power Systems V.K Mehta Complete Book - Chapter 7
Principles of Power Systems V.K Mehta Complete Book - Chapter 7Principles of Power Systems V.K Mehta Complete Book - Chapter 7
Principles of Power Systems V.K Mehta Complete Book - Chapter 7
 
Electric power system
Electric power systemElectric power system
Electric power system
 
PPT_1_Electrical services_By group no. 1.pptx
PPT_1_Electrical services_By group no. 1.pptxPPT_1_Electrical services_By group no. 1.pptx
PPT_1_Electrical services_By group no. 1.pptx
 
PPT_1_Electrical services_By group no. 1.pptx
PPT_1_Electrical services_By group no. 1.pptxPPT_1_Electrical services_By group no. 1.pptx
PPT_1_Electrical services_By group no. 1.pptx
 
Ch.1.1.pdf
Ch.1.1.pdfCh.1.1.pdf
Ch.1.1.pdf
 

Dernier

Russian Call Girls In Rajiv Chowk Gurgaon ❤️8448577510 ⊹Best Escorts Service ...
Russian Call Girls In Rajiv Chowk Gurgaon ❤️8448577510 ⊹Best Escorts Service ...Russian Call Girls In Rajiv Chowk Gurgaon ❤️8448577510 ⊹Best Escorts Service ...
Russian Call Girls In Rajiv Chowk Gurgaon ❤️8448577510 ⊹Best Escorts Service ...
lizamodels9
 
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
amitlee9823
 

Dernier (20)

Value Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and painsValue Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and pains
 
Russian Call Girls In Rajiv Chowk Gurgaon ❤️8448577510 ⊹Best Escorts Service ...
Russian Call Girls In Rajiv Chowk Gurgaon ❤️8448577510 ⊹Best Escorts Service ...Russian Call Girls In Rajiv Chowk Gurgaon ❤️8448577510 ⊹Best Escorts Service ...
Russian Call Girls In Rajiv Chowk Gurgaon ❤️8448577510 ⊹Best Escorts Service ...
 
Organizational Transformation Lead with Culture
Organizational Transformation Lead with CultureOrganizational Transformation Lead with Culture
Organizational Transformation Lead with Culture
 
Call Girls Service In Old Town Dubai ((0551707352)) Old Town Dubai Call Girl ...
Call Girls Service In Old Town Dubai ((0551707352)) Old Town Dubai Call Girl ...Call Girls Service In Old Town Dubai ((0551707352)) Old Town Dubai Call Girl ...
Call Girls Service In Old Town Dubai ((0551707352)) Old Town Dubai Call Girl ...
 
Falcon Invoice Discounting platform in india
Falcon Invoice Discounting platform in indiaFalcon Invoice Discounting platform in india
Falcon Invoice Discounting platform in india
 
Business Model Canvas (BMC)- A new venture concept
Business Model Canvas (BMC)-  A new venture conceptBusiness Model Canvas (BMC)-  A new venture concept
Business Model Canvas (BMC)- A new venture concept
 
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...
 
Uneak White's Personal Brand Exploration Presentation
Uneak White's Personal Brand Exploration PresentationUneak White's Personal Brand Exploration Presentation
Uneak White's Personal Brand Exploration Presentation
 
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
 
PHX May 2024 Corporate Presentation Final
PHX May 2024 Corporate Presentation FinalPHX May 2024 Corporate Presentation Final
PHX May 2024 Corporate Presentation Final
 
Marel Q1 2024 Investor Presentation from May 8, 2024
Marel Q1 2024 Investor Presentation from May 8, 2024Marel Q1 2024 Investor Presentation from May 8, 2024
Marel Q1 2024 Investor Presentation from May 8, 2024
 
Cracking the Cultural Competence Code.pptx
Cracking the Cultural Competence Code.pptxCracking the Cultural Competence Code.pptx
Cracking the Cultural Competence Code.pptx
 
Call Girls Ludhiana Just Call 98765-12871 Top Class Call Girl Service Available
Call Girls Ludhiana Just Call 98765-12871 Top Class Call Girl Service AvailableCall Girls Ludhiana Just Call 98765-12871 Top Class Call Girl Service Available
Call Girls Ludhiana Just Call 98765-12871 Top Class Call Girl Service Available
 
(Anamika) VIP Call Girls Napur Call Now 8617697112 Napur Escorts 24x7
(Anamika) VIP Call Girls Napur Call Now 8617697112 Napur Escorts 24x7(Anamika) VIP Call Girls Napur Call Now 8617697112 Napur Escorts 24x7
(Anamika) VIP Call Girls Napur Call Now 8617697112 Napur Escorts 24x7
 
Falcon's Invoice Discounting: Your Path to Prosperity
Falcon's Invoice Discounting: Your Path to ProsperityFalcon's Invoice Discounting: Your Path to Prosperity
Falcon's Invoice Discounting: Your Path to Prosperity
 
Malegaon Call Girls Service ☎ ️82500–77686 ☎️ Enjoy 24/7 Escort Service
Malegaon Call Girls Service ☎ ️82500–77686 ☎️ Enjoy 24/7 Escort ServiceMalegaon Call Girls Service ☎ ️82500–77686 ☎️ Enjoy 24/7 Escort Service
Malegaon Call Girls Service ☎ ️82500–77686 ☎️ Enjoy 24/7 Escort Service
 
Cheap Rate Call Girls In Noida Sector 62 Metro 959961乂3876
Cheap Rate Call Girls In Noida Sector 62 Metro 959961乂3876Cheap Rate Call Girls In Noida Sector 62 Metro 959961乂3876
Cheap Rate Call Girls In Noida Sector 62 Metro 959961乂3876
 
Falcon Invoice Discounting: The best investment platform in india for investors
Falcon Invoice Discounting: The best investment platform in india for investorsFalcon Invoice Discounting: The best investment platform in india for investors
Falcon Invoice Discounting: The best investment platform in india for investors
 
Eluru Call Girls Service ☎ ️93326-06886 ❤️‍🔥 Enjoy 24/7 Escort Service
Eluru Call Girls Service ☎ ️93326-06886 ❤️‍🔥 Enjoy 24/7 Escort ServiceEluru Call Girls Service ☎ ️93326-06886 ❤️‍🔥 Enjoy 24/7 Escort Service
Eluru Call Girls Service ☎ ️93326-06886 ❤️‍🔥 Enjoy 24/7 Escort Service
 
Falcon Invoice Discounting: Empowering Your Business Growth
Falcon Invoice Discounting: Empowering Your Business GrowthFalcon Invoice Discounting: Empowering Your Business Growth
Falcon Invoice Discounting: Empowering Your Business Growth
 

Electricity distribution

  • 1. Electricity distribution Electricity distribution is the final stage in the delivery of electricity to end users. A distribution system's network carries electricity from the transmission system and delivers it to consumers. Typically, the network would include medium-voltage (less than 50 kV) power lines, substations and pole-mounted transformers, low-voltage (less than 1 kV) distribution wiring and sometimes meters. History In the early days of electricity distribution, direct current (DC) generators were connected to loads at the same voltage. The generation, transmission and loads had to be of the same voltage because there was no way of changing DC voltage levels, other than inefficient motor-generator sets. Low DC voltages were used (on the order of 100 volts) since that was a practical voltage for incandescent lamps, which were the primary electrical load. Low voltage also required less insulation for safe distribution within buildings. The losses in a cable are proportional to the square of the current, the length of the cable, and the resistivity of the material, and are inversely proportional to cross-sectional area. Early transmission networks used copper cable, which is one of the best economically feasible conductors for this application. To reduce the current and copper required for a given quantity of power transmitted would require a higher transmission voltage, but no efficient method existed to change the voltage of DC power circuits. To keep losses to an economically practical level the Edison DC system needed thick cables and local generators. Early DC generating plants needed to be within about 1.5 miles (2.4 km) of the farthest customer to avoid excessively large and expensive conductors. [edit] Introduction of alternating current
  • 2. General layout of electricity networks The competition between the direct current (DC) of Thomas Edison and the alternating current (AC) of Nikola Tesla and George Westinghouse was known as the War of Currents. At the conclusion of their campaigning, AC became the dominant form of transmission of power. Power transformers, installed at power stations, could be used to raise the voltage from the generators, and transformers at local substations could reduce voltage to supply loads. Increasing the voltage reduced the current in the transmission and distribution lines and hence the size of conductors and distribution losses. This made it more economical to distribute power over long distances. Generators (such as hydroelectric sites) could be located far from the loads. In North America, early distribution systems used a voltage of 2.2 kV corner-grounded delta. Over time, this was gradually increased to 2.4 kV. As cities grew, most 2.4 kV systems were upgraded to 2.4/4.16 kV, three-phase systems. In three phase networks that permit connections between phase and neutral, both the phase-to-phase voltage (4160, in this example) and the phase-to-neutral voltage are given; if only one value is shown, the network does not serve single- phase loads connected phase-to-neutral. Some city and suburban distribution systems continue to use this range of voltages, but most have been converted to 7200/12470Y, 7620/13200Y, 14400/24940Y, and 19920/34500Y. European systems used 3.3 kV to ground, in support of the 220/380Y volt power systems used in those countries. In the UK, urban systems progressed to 6.6 kV and then 11 kV (phase to phase), the most common distribution voltage.
  • 3. North American and European power distribution systems also differ in that North American systems tend to have a greater number of low-voltage step-down transformers located close to customers' premises. For example, in the US a pole-mounted transformer in a suburban setting may supply 7-8 houses, whereas in the UK a typical urban or suburban low-voltage substation would normally be rated between 315 kVA and 1 MVA and supply a whole neighbourhood. This is because the higher voltage used in Europe (415 V vs 230 V) may be carried over a greater distance with acceptable power loss. An advantage of the North American setup is that failure or maintenance on a single transformer will only affect a few customers. Advantages of the UK setup are that the transformers may be fewer, larger and more efficient, and due to diversity there need be less spare capacity in the transformers, reducing power wastage. In North American city areas with many customers per unit area, network distribution will be used, with multiple transformers and low-voltage buses interconnected over several city blocks. Rural Electrification systems, in contrast to urban systems, tend to use higher voltages because of the longer distances covered by those distribution lines (see Rural Electrification Administration). 7.2, 12.47, 25, and 34.5 kV distribution is common in the United States; 11 kV and 33 kV are common in the UK, New Zealand and Australia; 11 kV and 22 kV are common in South Africa. Other voltages are occasionally used. In New Zealand, Australia, Saskatchewan, Canada, and South Africa, single wire earth return systems (SWER) are used to electrify remote rural areas. While power electronics now allow for conversion between DC voltage levels, AC is still used in distribution due to the economy, efficiency and reliability of transformers. High-voltage DC is used for transmission of large blocks of power over long distances, or for interconnecting adjacent AC networks, but not for distribution to customers. Electric power is normally generated at 11-25kV in a power station. To transmit over long distances, it is then stepped-up to 400kV, 220kV or 132kV as necessary. Power is carried through a transmission network of high voltage lines. Usually, these lines run into hundreds of kilometres and deliver the power into a common power pool called the grid. The grid is connected to load centres (cities) through a sub- transmission network of normally 33kV (or sometimes 66kV) lines. These lines terminate into a 33kV (or 66kV) substation, where the voltage is stepped-down to 11kV for power distribution to load points through a distribution network of lines at 11kV and lower
  • 4. Modern distribution systems Electric distribution substations transform power from transmission voltage to the lower voltage used for local distribution to homes and businesses The modern distribution system begins as the primary circuit leaves the sub-station and ends as the secondary service enters the customer's meter socket. Distribution circuits serve many customers. The voltage used is appropriate for the shorter distance and varies from 2,300 to about 35,000 volts depending on utility standard practice, distance, and load to be served. Distribution circuits are fed from a transformer located in an electrical substation, where the voltage is reduced from the high values used for power transmission. Conductors for distribution may be carried on overhead pole lines, or in densely-populated areas where they are buried underground. Urban and suburban distribution is done with three-phase systems to serve both residential, commercial, and industrial loads. Distribution in rural areas may be only single-phase if it is not economical to install three-phase power for relatively few and small customers. Only large consumers are fed directly from distribution voltages; most utility customers are connected to a transformer, which reduces the distribution voltage to the relatively low voltage used by lighting and interior wiring systems. The transformer may be pole-mounted or set on the ground in a protective enclosure. In rural areas a pole-mount transformer may serve only one customer, but in more built-up areas multiple customers may be connected. In very dense city areas, a secondary network may be formed with many transformers feeding into a common bus at the utilization voltage. Each customer has an "electrical service" or "service drop" connection and a meter for billing. (Some very small loads, such as yard lights, may be too small to meter and so are charged only a monthly rate.) A ground connection to local earth is normally provided for the customer's system as well as for the equipment owned by the utility. The purpose of connecting the customer's system to ground is to limit the voltage that may develop if high voltage conductors fall on the lower-voltage conductors, or if a failure occurs within a distribution transformer. If all conductive objects are bonded to the same earth grounding system, the risk of electric shock is minimized. However, multiple connections between the utility ground and customer ground can lead to stray voltage problems; customer piping, swimming pools or other equipment may develop objectionable
  • 5. voltages. These problems may be difficult to resolve since they often originate from places other than the customer's premises. International differences In many areas, "delta" three phase service is common. Delta service has no distributed neutral wire and is therefore less expensive. In North America and Latin America, three phase service is often a Y (wye) in which the neutral is directly connected to the center of the generator rotor. The neutral provides a low-resistance metallic return to the distribution transformer. Wye service is recognizable when a line has four conductors, one of which is lightly insulated. Three-phase wye service is excellent for motors and heavy power use. Many areas in the world use single-phase 220 V or 230 V residential and light industrial service. In this system, the high voltage distribution network supplies a few substations per area, and the 230 V power from each substation is directly distributed. A live (hot) wire and neutral are connected to the building from one phase of three phase service. Single-phase distribution is used where motor loads are small. Americas In the U.S. and parts of Canada and Latin America, split phase service is the most common. Split phase provides both 120 V and 240 V service with only three wires. The house voltages are provided by local transformers. The neutral is directly connected to the three-phase neutral. Socket voltages are only 120 V, but 240 V is available for heavy appliances because the two halves of a phase oppose each other.[1] Europe In Europe, electricity is normally distributed for industry and domestic use by the three-phase, four wire system. This gives a three-phase voltage of 400 volts and a single-phase voltage of 230 volts. For industrial customers, 3-phase 690 / 400 volt is also available.[citation needed] Japan Japan has a large number of small industrial manufacturers, and therefore supplies standard low- voltage three phase-service in many suburbs. Also, Japan normally supplies residential service as two phases of a three phase service, with a neutral. These work well for both lighting and motors. Rural services Rural services normally try to minimize the number of poles and wires. Single-wire earth return (SWER) is the least expensive, with one wire. It uses high voltages, which in turn permit use of galvanized steel wire. The strong steel wire permits inexpensive wide pole spacings. Other areas use high voltage split-phase or three phase service at higher cost. Metering
  • 6. Electricity meters use different metering equations depending on the form of electrical service. Since the math differs from service to service, the number of conductors and sensors in the meters also vary. [edit] Terms Besides referring to the physical wiring, the term electrical service also refers in an abstract sense to the provision of electricity to a building. [edit] Distribution network configurations Substation near Yellowknife, in the Northwest Territories of Canada Distribution networks are typically of two types, radial or interconnected (see spot network). A radial network leaves the station and passes through the network area with no normal connection to any other supply. This is typical of long rural lines with isolated load areas. An interconnected network is generally found in more urban areas and will have multiple connections to other points of supply. These points of connection are normally open but allow various configurations by the operating utility by closing and opening switches. Operation of these switches may be by remote control from a control center or by a lineman. The benefit of the interconnected model is that in the event of a fault or required maintenance a small area of network can be isolated and the remainder kept on supply. Within these networks there may be a mix of overhead line construction utilizing traditional utility poles and wires and, increasingly, underground construction with cables and indoor or cabinet substations. However, underground distribution is significantly more expensive than overhead construction. In part to reduce this cost, underground power lines are sometimes co- located with other utility lines in what are called common utility ducts. Distribution feeders emanating from a substation are generally controlled by a circuit breaker which will open when a fault is detected. Automatic circuit reclosers may be installed to further segregate the feeder thus minimizing the impact of faults. Long feeders experience voltage drop requiring capacitors or voltage regulators to be installed. Characteristics of the supply given to customers are generally mandated by contract between the supplier and customer. Variables of the supply include:
  • 7. AC or DC - Virtually all public electricity supplies are AC today. Users of large amounts of DC power such as some electric railways, telephone exchanges and industrial processes such as aluminium smelting usually either operate their own or have adjacent dedicated generating equipment, or use rectifiers to derive DC from the public AC supply Voltage, including tolerance (usually +10 or -15 percent) Frequency, commonly 50 or 60 Hz, 16.6 Hz for some railways and, in a few older industrial and mining locations, 25 Hz.[2] Phase configuration (single phase, polyphase including two-phase and three phase) Maximum demand (usually measured as the largest amount of power delivered within a 15 or 30 minute period during a billing period) Load factor, expressed as a ratio of average load to peak load over a period of time. Load factor indicates the degree of effective utilization of equipment (and capital investment) of distribution line or system. Power factor of connected load Earthing arrangements - TT, TN-S, TN-C-S or TN-C Prospective short circuit current Maximum level and frequency of occurrence of transients Distribution industry Traditionally the electricity industry has been a publicly owned institution but starting in the 1970s nations began the process of deregulation and privatisation, leading to electricity markets. A major focus of these was the elimination of the former so called natural monopoly of generation, transmission, and distribution. As a consequence, electricity has become more of a commodity. The separation has also led to the development of new terminology to describe the business units (e.g., line company, wires business and network company).