Inspection Services & Consulting LLC
                                          26291 Chisholm St NE Isanti MN 55040
                              Tel: 763-444-7348 Fax: 763-444-6718 Mobile: 763-350-3516
                                     Infrared-Inspector.com mninspector@msn.com




                         CONFIDENTIAL HOME INSPECTION
                                                       PREPARED FOR:
                                                 Sample Report
                   _______________________________________________________________

                                           INSPECTION ADDRESS
                               2233 Your Address, Hometown, MN 55023

                                                   INSPECTION DATE
                                             8/16/2010 7:00 AM to 1:00 PM




This report is the exclusive property of the Inspection Company and the client whose
name appears herewith, and its use by any unauthorized persons is prohibited.
_____________________________________________________________________________________________
    This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein.
                       All printed comments and the opinions expressed herein are those of the Inspection Company.
                                                      Inspection Narratives - Page 1
GENERAL INFORMATION
Inspection Address:                   2233 Your Address, Hometown, MN 55023
Inspection Date:                      8/16/2010 Time: 7:00 AM to 1:00 PM

Weather:                              Overcast - Temperature at time of inspection: 58-69
                                      Humidity at time of inspection: 55

Inspected by:                         Jon Anderson

Client Information:                   Sample Report



Structure Type:                       Wood Frame
Foundation Type:                      Basement
Furnished:                            Yes
Structure Occupied:                   Yes
Number of Stories:                    1 story walkout


Structure Orientation:                South

Estimated Year Built:                 2002
Unofficial Sq.Ft.:                    4500

People on Site At Time of Inspection:                     Owners

Report File: Dale Beumer




_____________________________________________________________________________________________
     This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein.
                        All printed comments and the opinions expressed herein are those of the Inspection Company.
                                                       Inspection Narratives - Page 2
Inspection Address:      2233 Your Address, Hometown, MN 55023
 Inspection Date/Time:    8/16/2010 7:00 AM to 1:00 PM
_____________________________________________________________________________________________


                                                          Summary
SUMMARY
General Information
Informational Conditions
   Moisture level readings, inspections, and testing are a snap shot in time which can change over a short period
   by storms, rain dry weather patterns, humidity, temperature, lack of maintenance, structural (seismic
   movement, grade issues, life style changes, heating and cooling seasons, unrealized storm damage, gutter
   and roof ice dams, broken or leaking water pipes, and a host of other issues.

  Every effort is made to insure the accuracy of our findings, by using the best state of the art testing equipment
  available, However moisture testing is not an exact science. So all elevated moisture readings should be
  further explored to verify the readings obtained in this report.

  This is not a guarantee that every anomaly or issue will be discovered.

  If it is determined that there is structural damage, you should protect your rights.
  Contact your builder in writing of the findings, and discuss your options with an attorney.

  If there is any part of this inspection report that you do not understand, it is your responsibility to contact us to
  clarify the issue.

  Moisture wood content readings of 6% to 15% are considered normal, levels of 16% to 19% are cautionary and
  could possibly indicate a low level of moisture infiltration, Levels of 20% to 100% are considered elevated and
  should be further explored for possible damaged sheathing, framing members, and or a fungal growth

  Additional copies of your report are available for $39.00

Home Builder
Informational Conditions
   Gorham Homes

Precipitation
Informational Conditions
   No Measurable precipitation within the last 24 hours

Weep Screed
Informational Conditions
   There is no weep screed installed along the foundation line.

Grade Issues
Informational Conditions
   The grade is high in certain areas of your home

Kick Out Flashing
Informational Conditions
   Kick out flashing's are installed

Window Details
Informational Conditions
   The windows of your home were manufactured by Andersen Windows


_____________________________________________________________________________________________
      This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein.
                         All printed comments and the opinions expressed herein are those of the Inspection Company.
                                                        Inspection Narratives - Page 3
Inspection Address:      2233 Your Address, Hometown, MN 55023
 Inspection Date/Time:    8/16/2010 7:00 AM to 1:00 PM
_____________________________________________________________________________________________


Drip Cap Flashing
Informational Conditions
   The windows lack drip cap flashing's

Caulking Details
Informational Conditions
   The window to stucco joints are not caulked

  No caulking at dissimilar materials and breaches of the stucco cladding

Moisture Levels
Informational Conditions
    Area(s) of your home have elevated moisture readings over 20% which are noted within the pin probe section
   of the report.

Stains
Informational Conditions
   There is staining of the stucco below windows and the deck ledger board.
   This may or may not indicate moisture intrusion issues.

Cracks
Informational Conditions
   There are cracks in the stucco which could indicate a structural condition, seismic movement, or moisture
   intrusion. Stucco applied to thin, dry weather or wind when the basecoats were applied, in correct 2-1 or 3-1
   ratio with the common sand.

Gutters
Informational Conditions
   The home is guttered

Casing Beads
Informational Conditions
   There are no casing beads wherever the stucco intersects a hard surface

SHEATHING
Informational Conditions
   The sheathing on your home is buildrite




_____________________________________________________________________________________________

     This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein.
                        All printed comments and the opinions expressed herein are those of the Inspection Company.
                                                       Inspection Narratives - Page 4
Inspection Address:      2233 Your Address, Hometown, MN 55023
 Inspection Date/Time:    8/16/2010 7:00 AM to 1:00 PM
_____________________________________________________________________________________________


                                                              Interior
Miscellaneous conditions
RIM JOIST
Informational Conditions
   The insulation of the rim joist cavity where visual was insulated with a foil faced foam insulation, and batten
   insulation.
   Access was limited due to storage of household items.
   There is no moisture staining on the surface of the foil faced foam




       clean
       rim
       joist


FLOOR REGISTERS
Informational Conditions
   The floor registers that were accessible were visually inspected for moisture staining.
   No staining was noted at this time




                          floor
                          registers
                          are clean




_____________________________________________________________________________________________

      This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein.
                         All printed comments and the opinions expressed herein are those of the Inspection Company.
                                                        Inspection Narratives - Page 5
Inspection Address:      2233 Your Address, Hometown, MN 55023
 Inspection Date/Time:    8/16/2010 7:00 AM to 1:00 PM
_____________________________________________________________________________________________

WINDOW STAINS
Informational Conditions
   There is moisture staining or damaged finish of the window sill extension jamb area.
   This is a high indicator of moisture from within the wall cavity below the window



                                                                                                       30+%
                                                                                                       moisture
                                                                                                       reading




                            lower
                            level
                            bedroom




                            19%
                            moisture
                            reading




PIN PROBE
Informational Conditions
   The front elevation of your home was pin probed to the back side of the sheathing from the interior due to the
   brick cladding of the exterior.

  Area # 1
  Dining room area




_____________________________________________________________________________________________
     This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein.
                        All printed comments and the opinions expressed herein are those of the Inspection Company.
                                                       Inspection Narratives - Page 6
Inspection Address:      2233 Your Address, Hometown, MN 55023
 Inspection Date/Time:    8/16/2010 7:00 AM to 1:00 PM
_____________________________________________________________________________________________

Area # 1 - Continued




           18%
                      15%
                                        12%
                                                         14%




_____________________________________________________________________________________________

     This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein.
                        All printed comments and the opinions expressed herein are those of the Inspection Company.
                                                       Inspection Narratives - Page 7
Inspection Address:      2233 Your Address, Hometown, MN 55023
 Inspection Date/Time:    8/16/2010 7:00 AM to 1:00 PM
_____________________________________________________________________________________________


                                                          Exterior II
EXTERIOR VISUAL (STUCCO)
KICK OUT FLASHING'S
Informational Conditions
   The roof rakes have kick out flashing's installed




     kick out
     flashing




CASING BEADS
Informational Conditions
   There are no casing bead or weep screed separating the stucco from the shingles, and or hard surfaces such as
   steps, patios, and driveway surfaces.




                 no
                 casing
                 bead


                                                                                              no
                                                                                              casing
                                                                                              bead




DRIP CAP FLASHING'S
Informational Conditions
   There are no drip cap flashing's over the head of the window's and or door's,
   Drip cap flashing's should be installed to prevent water intrusion at these locations.
   Check with your window manufacturer about proper installation

_____________________________________________________________________________________________
      This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein.
                         All printed comments and the opinions expressed herein are those of the Inspection Company.
                                                        Inspection Narratives - Page 8
Inspection Address:      2233 Your Address, Hometown, MN 55023
 Inspection Date/Time:    8/16/2010 7:00 AM to 1:00 PM
_____________________________________________________________________________________________


No Drip Cap Flashing's - Continued




                  no drip
                  cap
                  flashing's




WINDOW ISSUES
Informational Conditions
   The window to stucco intersections are not caulked.
   Caulking can help prevent water infiltration around the frames




                                                        no
                                                        caulking
                                                                                 no
                                                                                 caulking
                                                                                 and open
                                                                                 hole in
                                                                                 mortar
                                                                                 joint




_____________________________________________________________________________________________
     This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein.
                        All printed comments and the opinions expressed herein are those of the Inspection Company.
                                                       Inspection Narratives - Page 9
Inspection Address:      2233 Your Address, Hometown, MN 55023
 Inspection Date/Time:    8/16/2010 7:00 AM to 1:00 PM
_____________________________________________________________________________________________

No Caulking - Continued




                            no
                            caulking




WEEP SCREEDS
Informational Conditions
   No weep screed is installed separating the stucco from grade at the foundation line.
   Stucco by code is to terminate above the finished grade by 4" to 6" and is not to terminate into the grade
   (Earth)
   Properly installed weep screed prevents ground moisture from wicking up into the stucco which can attack the
   stud wall cavity and cause wood rot and a fungal growth.
   Weep screed also provides a separation so that any bulk water that is behind the stucco cladding can drain out.
   The weep screed also is used as a guide for the elevation height for any grade or landscape work.




                                no
                                weep
                                screed




STUCCO CRACKING
Informational Conditions
   There is cracking of the stucco cladding which resembles a road map.
   This type of cracking may indicate the presence of moisture behind the water resistant barrier, especially under
   windows, roof rakes, feature boards, and deck ledger boards.


_____________________________________________________________________________________________
     This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein.
                        All printed comments and the opinions expressed herein are those of the Inspection Company.
                                                      Inspection Narratives - Page 10
Inspection Address:      2233 Your Address, Hometown, MN 55023
 Inspection Date/Time:    8/16/2010 7:00 AM to 1:00 PM
_____________________________________________________________________________________________


STUCCO STAINING
Informational Conditions
   There are stains in the stucco cladding which can indicate moisture intrusion in certain circumstances

CAULKING DETAILS
Informational Conditions
   There is no caulking where the stucco meets a dissimilar material such as brick, siding water pipes electrical
   boxes, lights or vents




         caulk all
         breaches




GRADE ISSUES
Informational Conditions
   The grade is high on the rear elevation of your home
   The grade should be down onto the foundation 4 to 6"




                                                                                            grade
                              grade                                                         is high
                              is high




_____________________________________________________________________________________________
     This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein.
                        All printed comments and the opinions expressed herein are those of the Inspection Company.
                                                      Inspection Narratives - Page 11
Inspection Address:      2233 Your Address, Hometown, MN 55023
 Inspection Date/Time:    8/16/2010 7:00 AM to 1:00 PM
_____________________________________________________________________________________________

The Grade Is High - Continued




                                                                                              grade
                        grade                                                                 is high
                        is high




ROOF LINE VALLEY'S
Informational Conditions
   The roof line on the right side of the greatroom is wet and covered with green moss

                   roofline
                   is wet
                   and
                   moss
                   covered




GUTTER'S
Informational Conditions
   The downspouts are not sealed at the anchors




_____________________________________________________________________________________________
     This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein.
                        All printed comments and the opinions expressed herein are those of the Inspection Company.
                                                      Inspection Narratives - Page 12
Inspection Address:      2233 Your Address, Hometown, MN 55023
 Inspection Date/Time:    8/16/2010 7:00 AM to 1:00 PM
_____________________________________________________________________________________________

Downspouts Not Sealed - Continued




           downspouts
           are not
           sealed




FEATURE BOARDS AND QUOINS
Informational Conditions
   The feature boards are installed flush with or over the window frame with little slope to the outward edge.
   This can cause severe water infiltration



                                                   feature
                                                   board
                                                   over
                                                   window
                                                   frame




DECK LEDGER BOARDS
Informational Conditions
   There is no caulking or bottom flashing at the deck ledger board.
   This is a high probability area for water infiltration




_____________________________________________________________________________________________
     This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein.
                        All printed comments and the opinions expressed herein are those of the Inspection Company.
                                                      Inspection Narratives - Page 13
Inspection Address:      2233 Your Address, Hometown, MN 55023
 Inspection Date/Time:    8/16/2010 7:00 AM to 1:00 PM
_____________________________________________________________________________________________

No caulking at the deck ledger boards - Continued




         no
         caulking
         or bottom
         flashing




BRICK
Informational Conditions
   The top of the brick lacks adequate slope outward to drain rainwater




               no
               slope




  There are no visible weep ropes in the brick near grade.
  Weep ropes provide for draining of water from behind the brick




_____________________________________________________________________________________________
     This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein.
                        All printed comments and the opinions expressed herein are those of the Inspection Company.
                                                      Inspection Narratives - Page 14
Inspection Address:      2233 Your Address, Hometown, MN 55023
 Inspection Date/Time:    8/16/2010 7:00 AM to 1:00 PM
_____________________________________________________________________________________________

No Weep Ropes - Continued




                            no
                            visible
                            weep
                            ropes
                            or
                            tubes




  The brick cap flashing is not caulked




                            no                                                                                            no brick
                            caulking                                                                                      cap
                                                                                                                          flashing




_____________________________________________________________________________________________

     This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein.
                        All printed comments and the opinions expressed herein are those of the Inspection Company.
                                                      Inspection Narratives - Page 15
Inspection Address:      2233 Your Address, Hometown, MN 55023
 Inspection Date/Time:    8/16/2010 7:00 AM to 1:00 PM
_____________________________________________________________________________________________


                                                         Pin Probe
PIN PROBE RESULTS
GENERAL PIN PROBE INFORMATION
Informational Conditions
   The following photo's are the results of your pin probe moisture level inspection.
   All moisture readings are from the sheathing unless otherwise specified.
   All moisture readings are given at the location where they were taken on the photo's.
   All readings are of wood moisture content from 6% to 100% with 6% being dry, and 100% being saturated.
   Moisture readings of 6% to 15% are considered to be normal,
   Moisture readings of 16% to 19% are considered cautionary,
   Moisture readings of 20% and higher can support mold growth and wood rot if sustained for more than 36 to 48
   hours or more and are considered elevated and should be further evaluated.

  If there is an "ss" after a moisture reading on the photo's, this indicates that the sheathing felt soft or
  deteriorated when the pin probe holes were drilled, or when the pin probes were inserted.

  If there is an "ns" or 0 on the photo's this indicates that no sheathing was detected when the pin probe holes
  where drilled, and no reading was obtained, This indicates that the sheathing is deteriorated and or completely
  missing. If there is a reading it is generally off a framing member.

  If there is a "2" after the moisture reading this indicates that the reading was taken twice for accuracy.


REFERENCE PHOTOS
Informational Conditions
   The following photos are for referencing the location of the individual pin probe photos per each elevation

  Front Elevation




  Rear Elevation




_____________________________________________________________________________________________
     This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein.
                        All printed comments and the opinions expressed herein are those of the Inspection Company.
                                                      Inspection Narratives - Page 16
Inspection Address:      2233 Your Address, Hometown, MN 55023
 Inspection Date/Time:    8/16/2010 7:00 AM to 1:00 PM
_____________________________________________________________________________________________

Rear Elevation Reference Photos 1 - Continued




  Left Elevation




FRONT ELEVATION
Informational Conditions
   FRONT ELEVATION PIN PROBE RESULTS




_____________________________________________________________________________________________
     This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein.
                        All printed comments and the opinions expressed herein are those of the Inspection Company.
                                                      Inspection Narratives - Page 17
Inspection Address:      2233 Your Address, Hometown, MN 55023
 Inspection Date/Time:    8/16/2010 7:00 AM to 1:00 PM
_____________________________________________________________________________________________

FRONT ELEVATION 1 - Continued




                                                                                                                 window
                                                                                                                 area
                                                                                                                 tested
                                                                                                                 from the
                    6% 8% 8%                 7% 7% 7%                                                            interior

                                     9%




                                                                                                                     11%
                                    12%




                                                                                                                  10%
                                      9%                                                                           15%




_____________________________________________________________________________________________
     This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein.
                        All printed comments and the opinions expressed herein are those of the Inspection Company.
                                                      Inspection Narratives - Page 18
Inspection Address:      2233 Your Address, Hometown, MN 55023
 Inspection Date/Time:    8/16/2010 7:00 AM to 1:00 PM
_____________________________________________________________________________________________

FRONT ELEVATION 1 - Continued




       moisture
       stains
       under
       garage
       round
       window




RIGHT ELEVATION
Informational Conditions
   RIGHT ELEVATION PIN PROBE RESULTS
   Garage walls




                                           9%
                         9%
                                                                                                                     10%




  RIGHT ELEVATION RESULTS




_____________________________________________________________________________________________
     This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein.
                        All printed comments and the opinions expressed herein are those of the Inspection Company.
                                                      Inspection Narratives - Page 19
Inspection Address:      2233 Your Address, Hometown, MN 55023
 Inspection Date/Time:    8/16/2010 7:00 AM to 1:00 PM
_____________________________________________________________________________________________

RIGHT ELEVATION 2 - Continued




                     7%

                                                                                                 13%




                                    11%                    9%




  RIGHT ELEVATION RESULTS
  Area under the deck




                                                                                                      12%
                              17%                                  12%




_____________________________________________________________________________________________
     This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein.
                        All printed comments and the opinions expressed herein are those of the Inspection Company.
                                                      Inspection Narratives - Page 20
Inspection Address:      2233 Your Address, Hometown, MN 55023
 Inspection Date/Time:    8/16/2010 7:00 AM to 1:00 PM
_____________________________________________________________________________________________

RIGHT ELEVATION 3 - Continued




                              19.4%

                                                                                                             15%




REAR ELEVATION
Informational Conditions
   REAR ELEVATION PIN PROBE RESULTS
   left side area




                                                                                                    24%               15%              18%
        18%     14% 22% 21% 14% 16% 19% 13% 16%                                            0
                                                                                                                                16%
                                                                                           ns




  REAR ELEVATION PIN PROBE RESULTS
  Rear center section




_____________________________________________________________________________________________
     This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein.
                        All printed comments and the opinions expressed herein are those of the Inspection Company.
                                                      Inspection Narratives - Page 21
Inspection Address:      2233 Your Address, Hometown, MN 55023
 Inspection Date/Time:    8/16/2010 7:00 AM to 1:00 PM
_____________________________________________________________________________________________

REAR ELEVATION 2 - Continued




                                                                                        11%        17%      17%          17%       23% 11%
                                                                                                                         ss        ss




                        26%        15%          10%
                                                                                              0          0 0            0 0             19%
                                                                                              ns         ns ns          ns ns           ss




                                                       0                                                                        14%
                                               0                                                            9%
                                               ns      ns
                          8%

                                                                                                            9%
                         8%


                                                                                                          13%        8%
                19%
                            12%


  REAR ELEVATION PIN PROBE RESULTS
  Right side area




_____________________________________________________________________________________________
     This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein.
                        All printed comments and the opinions expressed herein are those of the Inspection Company.
                                                      Inspection Narratives - Page 22
Inspection Address:      2233 Your Address, Hometown, MN 55023
 Inspection Date/Time:    8/16/2010 7:00 AM to 1:00 PM
_____________________________________________________________________________________________

REAR ELEVATION 3 - Continued




                     19%                 17%               12%                                             19%       11%       17% 23%

                                                                                                            16%                         21%




                                       16%




LEFT ELEVATION
Informational Conditions
   LEFT ELEVATION PIN PROBE RESULTS




_____________________________________________________________________________________________
     This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein.
                        All printed comments and the opinions expressed herein are those of the Inspection Company.
                                                      Inspection Narratives - Page 23
Inspection Address:      2233 Your Address, Hometown, MN 55023
 Inspection Date/Time:    8/16/2010 7:00 AM to 1:00 PM
_____________________________________________________________________________________________

LEFT ELEVATION 1 - Continued




                            9%


                                              sheathing
                                              felt soft
                                                                                                                  8%        11%
                                              further
                                              exploration
                             17               is advised
                             ss




                                  15%      19.1%                                         19.6%                                         16%




                                                         retaining
                                                         blocks
                                                         are on the
                                                         stud wall
                                                         area


                                                  99%
              11%




_____________________________________________________________________________________________
     This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein.
                        All printed comments and the opinions expressed herein are those of the Inspection Company.
                                                      Inspection Narratives - Page 24
Inspection Address:      2233 Your Address, Hometown, MN 55023
 Inspection Date/Time:    8/16/2010 7:00 AM to 1:00 PM
_____________________________________________________________________________________________




_____________________________________________________________________________________________

     This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein.
                        All printed comments and the opinions expressed herein are those of the Inspection Company.
                                                      Inspection Narratives - Page 25
Inspection Address:      2233 Your Address, Hometown, MN 55023
 Inspection Date/Time:    8/16/2010 7:00 AM to 1:00 PM
_____________________________________________________________________________________________


CONFIDENTIAL HOME INSPECTION                                                                                                                1
GENERAL INFORMATION                                                                                                                         2
Summary                                                                                                                                     3
   SUMMARY                                                                                                                                  3
Interior                                                                                                                                    5
   Miscellaneous conditions                                                                                                                 5
Exterior II                                                                                                                                 8
   EXTERIOR VISUAL (STUCCO)                                                                                                                 8
Pin Probe                                                                                                                                   16
   PIN PROBE RESULTS                                                                                                                        16
INDEX                                                                                                                                       25




_____________________________________________________________________________________________
     This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein.
                        All printed comments and the opinions expressed herein are those of the Inspection Company.
                                                      Inspection Narratives - Page 25
Inspection Services & Consulting LLC
                                    26291 Chisholm St NE Isanti MN 55040
                         Tel: 763-444-7348 Fax: 763-444-6718 Mobile: 763-350-3516
                                    Email Address: mninspector@msn.com



Property Address:     2233 Your Address, Hometown, MN 55023
Inspection Date:      8/16/2010 Time: 7:00 AM to 1:00 PM

763-123-4567

Dear Sample Report:

  Thank you for hiring Inspection Services & Consulting LLC to be of service. We hope that you were pleased
  with the quality of our service, and that you would recommend us to others. Please read the report carefully,
  and call us with any questions that you might have. We remain your consultant, and would be happy to assist
  you in any way that we can. We sincerely hope that you and your family will be happy and healthy in your
  home.

  Sincerely,
  Jon Anderson CEI CIT CHI CEI
  Inspection Services & Consulting LLC
Sample report
Sample report
Sample report
Sample report
Sample report
Sample report
Sample report
Sample report
Sample report
Sample report
Sample report
Sample report
Sample report
Sample report
Sample report
Sample report
Sample report
Sample report
Sample report
Sample report
Sample report
Sample report
Sample report
Sample report
Sample report

Contenu connexe

Similaire à Sample report

Similaire à Sample report (20)

Full House Inspections Sample Report
Full House Inspections Sample ReportFull House Inspections Sample Report
Full House Inspections Sample Report
 
1 house-inspections report
1 house-inspections report1 house-inspections report
1 house-inspections report
 
Sample 2007 built_rural_area
Sample 2007 built_rural_areaSample 2007 built_rural_area
Sample 2007 built_rural_area
 
Sample Residential Inspection Report
Sample Residential Inspection ReportSample Residential Inspection Report
Sample Residential Inspection Report
 
Sample one year_builder_warranty
Sample one year_builder_warrantySample one year_builder_warranty
Sample one year_builder_warranty
 
Pre insp contract
Pre insp contractPre insp contract
Pre insp contract
 
Sample 1994with deferred_maintenance
Sample 1994with deferred_maintenanceSample 1994with deferred_maintenance
Sample 1994with deferred_maintenance
 
Sample commercial inspection
Sample commercial inspectionSample commercial inspection
Sample commercial inspection
 
Home inspection-agreement
Home inspection-agreementHome inspection-agreement
Home inspection-agreement
 
Sample newer home
Sample newer homeSample newer home
Sample newer home
 
Sample report
Sample reportSample report
Sample report
 
Sample report
Sample reportSample report
Sample report
 
Sample new construction-completed_over_a_year_earlier
Sample new construction-completed_over_a_year_earlierSample new construction-completed_over_a_year_earlier
Sample new construction-completed_over_a_year_earlier
 
Sample carbon monoxide_issue
Sample carbon monoxide_issueSample carbon monoxide_issue
Sample carbon monoxide_issue
 
Sample carbon monoxide_issue
Sample carbon monoxide_issueSample carbon monoxide_issue
Sample carbon monoxide_issue
 
Home pro pi_2011
Home pro pi_2011Home pro pi_2011
Home pro pi_2011
 
Accurateinspections sample-report
Accurateinspections sample-reportAccurateinspections sample-report
Accurateinspections sample-report
 
Sample Home Inspection Report.
Sample Home Inspection Report.Sample Home Inspection Report.
Sample Home Inspection Report.
 
Sample Report
Sample ReportSample Report
Sample Report
 
Insp. auth. form.
Insp. auth. form.Insp. auth. form.
Insp. auth. form.
 

Dernier

Dernier (20)

Towards a code of practice for AI in AT.pptx
Towards a code of practice for AI in AT.pptxTowards a code of practice for AI in AT.pptx
Towards a code of practice for AI in AT.pptx
 
UGC NET Paper 1 Mathematical Reasoning & Aptitude.pdf
UGC NET Paper 1 Mathematical Reasoning & Aptitude.pdfUGC NET Paper 1 Mathematical Reasoning & Aptitude.pdf
UGC NET Paper 1 Mathematical Reasoning & Aptitude.pdf
 
Jamworks pilot and AI at Jisc (20/03/2024)
Jamworks pilot and AI at Jisc (20/03/2024)Jamworks pilot and AI at Jisc (20/03/2024)
Jamworks pilot and AI at Jisc (20/03/2024)
 
Application orientated numerical on hev.ppt
Application orientated numerical on hev.pptApplication orientated numerical on hev.ppt
Application orientated numerical on hev.ppt
 
How to Manage Global Discount in Odoo 17 POS
How to Manage Global Discount in Odoo 17 POSHow to Manage Global Discount in Odoo 17 POS
How to Manage Global Discount in Odoo 17 POS
 
Kodo Millet PPT made by Ghanshyam bairwa college of Agriculture kumher bhara...
Kodo Millet  PPT made by Ghanshyam bairwa college of Agriculture kumher bhara...Kodo Millet  PPT made by Ghanshyam bairwa college of Agriculture kumher bhara...
Kodo Millet PPT made by Ghanshyam bairwa college of Agriculture kumher bhara...
 
Fostering Friendships - Enhancing Social Bonds in the Classroom
Fostering Friendships - Enhancing Social Bonds  in the ClassroomFostering Friendships - Enhancing Social Bonds  in the Classroom
Fostering Friendships - Enhancing Social Bonds in the Classroom
 
ICT Role in 21st Century Education & its Challenges.pptx
ICT Role in 21st Century Education & its Challenges.pptxICT Role in 21st Century Education & its Challenges.pptx
ICT Role in 21st Century Education & its Challenges.pptx
 
Wellbeing inclusion and digital dystopias.pptx
Wellbeing inclusion and digital dystopias.pptxWellbeing inclusion and digital dystopias.pptx
Wellbeing inclusion and digital dystopias.pptx
 
Accessible Digital Futures project (20/03/2024)
Accessible Digital Futures project (20/03/2024)Accessible Digital Futures project (20/03/2024)
Accessible Digital Futures project (20/03/2024)
 
Unit 3 Emotional Intelligence and Spiritual Intelligence.pdf
Unit 3 Emotional Intelligence and Spiritual Intelligence.pdfUnit 3 Emotional Intelligence and Spiritual Intelligence.pdf
Unit 3 Emotional Intelligence and Spiritual Intelligence.pdf
 
Understanding Accommodations and Modifications
Understanding  Accommodations and ModificationsUnderstanding  Accommodations and Modifications
Understanding Accommodations and Modifications
 
On_Translating_a_Tamil_Poem_by_A_K_Ramanujan.pptx
On_Translating_a_Tamil_Poem_by_A_K_Ramanujan.pptxOn_Translating_a_Tamil_Poem_by_A_K_Ramanujan.pptx
On_Translating_a_Tamil_Poem_by_A_K_Ramanujan.pptx
 
2024-NATIONAL-LEARNING-CAMP-AND-OTHER.pptx
2024-NATIONAL-LEARNING-CAMP-AND-OTHER.pptx2024-NATIONAL-LEARNING-CAMP-AND-OTHER.pptx
2024-NATIONAL-LEARNING-CAMP-AND-OTHER.pptx
 
How to Give a Domain for a Field in Odoo 17
How to Give a Domain for a Field in Odoo 17How to Give a Domain for a Field in Odoo 17
How to Give a Domain for a Field in Odoo 17
 
General Principles of Intellectual Property: Concepts of Intellectual Proper...
General Principles of Intellectual Property: Concepts of Intellectual  Proper...General Principles of Intellectual Property: Concepts of Intellectual  Proper...
General Principles of Intellectual Property: Concepts of Intellectual Proper...
 
ICT role in 21st century education and it's challenges.
ICT role in 21st century education and it's challenges.ICT role in 21st century education and it's challenges.
ICT role in 21st century education and it's challenges.
 
Beyond_Borders_Understanding_Anime_and_Manga_Fandom_A_Comprehensive_Audience_...
Beyond_Borders_Understanding_Anime_and_Manga_Fandom_A_Comprehensive_Audience_...Beyond_Borders_Understanding_Anime_and_Manga_Fandom_A_Comprehensive_Audience_...
Beyond_Borders_Understanding_Anime_and_Manga_Fandom_A_Comprehensive_Audience_...
 
Interdisciplinary_Insights_Data_Collection_Methods.pptx
Interdisciplinary_Insights_Data_Collection_Methods.pptxInterdisciplinary_Insights_Data_Collection_Methods.pptx
Interdisciplinary_Insights_Data_Collection_Methods.pptx
 
Sensory_Experience_and_Emotional_Resonance_in_Gabriel_Okaras_The_Piano_and_Th...
Sensory_Experience_and_Emotional_Resonance_in_Gabriel_Okaras_The_Piano_and_Th...Sensory_Experience_and_Emotional_Resonance_in_Gabriel_Okaras_The_Piano_and_Th...
Sensory_Experience_and_Emotional_Resonance_in_Gabriel_Okaras_The_Piano_and_Th...
 

Sample report

  • 1. Inspection Services & Consulting LLC 26291 Chisholm St NE Isanti MN 55040 Tel: 763-444-7348 Fax: 763-444-6718 Mobile: 763-350-3516 Infrared-Inspector.com mninspector@msn.com CONFIDENTIAL HOME INSPECTION PREPARED FOR: Sample Report _______________________________________________________________ INSPECTION ADDRESS 2233 Your Address, Hometown, MN 55023 INSPECTION DATE 8/16/2010 7:00 AM to 1:00 PM This report is the exclusive property of the Inspection Company and the client whose name appears herewith, and its use by any unauthorized persons is prohibited. _____________________________________________________________________________________________ This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein. All printed comments and the opinions expressed herein are those of the Inspection Company. Inspection Narratives - Page 1
  • 2. GENERAL INFORMATION Inspection Address: 2233 Your Address, Hometown, MN 55023 Inspection Date: 8/16/2010 Time: 7:00 AM to 1:00 PM Weather: Overcast - Temperature at time of inspection: 58-69 Humidity at time of inspection: 55 Inspected by: Jon Anderson Client Information: Sample Report Structure Type: Wood Frame Foundation Type: Basement Furnished: Yes Structure Occupied: Yes Number of Stories: 1 story walkout Structure Orientation: South Estimated Year Built: 2002 Unofficial Sq.Ft.: 4500 People on Site At Time of Inspection: Owners Report File: Dale Beumer _____________________________________________________________________________________________ This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein. All printed comments and the opinions expressed herein are those of the Inspection Company. Inspection Narratives - Page 2
  • 3. Inspection Address: 2233 Your Address, Hometown, MN 55023 Inspection Date/Time: 8/16/2010 7:00 AM to 1:00 PM _____________________________________________________________________________________________ Summary SUMMARY General Information Informational Conditions Moisture level readings, inspections, and testing are a snap shot in time which can change over a short period by storms, rain dry weather patterns, humidity, temperature, lack of maintenance, structural (seismic movement, grade issues, life style changes, heating and cooling seasons, unrealized storm damage, gutter and roof ice dams, broken or leaking water pipes, and a host of other issues. Every effort is made to insure the accuracy of our findings, by using the best state of the art testing equipment available, However moisture testing is not an exact science. So all elevated moisture readings should be further explored to verify the readings obtained in this report. This is not a guarantee that every anomaly or issue will be discovered. If it is determined that there is structural damage, you should protect your rights. Contact your builder in writing of the findings, and discuss your options with an attorney. If there is any part of this inspection report that you do not understand, it is your responsibility to contact us to clarify the issue. Moisture wood content readings of 6% to 15% are considered normal, levels of 16% to 19% are cautionary and could possibly indicate a low level of moisture infiltration, Levels of 20% to 100% are considered elevated and should be further explored for possible damaged sheathing, framing members, and or a fungal growth Additional copies of your report are available for $39.00 Home Builder Informational Conditions Gorham Homes Precipitation Informational Conditions No Measurable precipitation within the last 24 hours Weep Screed Informational Conditions There is no weep screed installed along the foundation line. Grade Issues Informational Conditions The grade is high in certain areas of your home Kick Out Flashing Informational Conditions Kick out flashing's are installed Window Details Informational Conditions The windows of your home were manufactured by Andersen Windows _____________________________________________________________________________________________ This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein. All printed comments and the opinions expressed herein are those of the Inspection Company. Inspection Narratives - Page 3
  • 4. Inspection Address: 2233 Your Address, Hometown, MN 55023 Inspection Date/Time: 8/16/2010 7:00 AM to 1:00 PM _____________________________________________________________________________________________ Drip Cap Flashing Informational Conditions The windows lack drip cap flashing's Caulking Details Informational Conditions The window to stucco joints are not caulked No caulking at dissimilar materials and breaches of the stucco cladding Moisture Levels Informational Conditions Area(s) of your home have elevated moisture readings over 20% which are noted within the pin probe section of the report. Stains Informational Conditions There is staining of the stucco below windows and the deck ledger board. This may or may not indicate moisture intrusion issues. Cracks Informational Conditions There are cracks in the stucco which could indicate a structural condition, seismic movement, or moisture intrusion. Stucco applied to thin, dry weather or wind when the basecoats were applied, in correct 2-1 or 3-1 ratio with the common sand. Gutters Informational Conditions The home is guttered Casing Beads Informational Conditions There are no casing beads wherever the stucco intersects a hard surface SHEATHING Informational Conditions The sheathing on your home is buildrite _____________________________________________________________________________________________ This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein. All printed comments and the opinions expressed herein are those of the Inspection Company. Inspection Narratives - Page 4
  • 5. Inspection Address: 2233 Your Address, Hometown, MN 55023 Inspection Date/Time: 8/16/2010 7:00 AM to 1:00 PM _____________________________________________________________________________________________ Interior Miscellaneous conditions RIM JOIST Informational Conditions The insulation of the rim joist cavity where visual was insulated with a foil faced foam insulation, and batten insulation. Access was limited due to storage of household items. There is no moisture staining on the surface of the foil faced foam clean rim joist FLOOR REGISTERS Informational Conditions The floor registers that were accessible were visually inspected for moisture staining. No staining was noted at this time floor registers are clean _____________________________________________________________________________________________ This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein. All printed comments and the opinions expressed herein are those of the Inspection Company. Inspection Narratives - Page 5
  • 6. Inspection Address: 2233 Your Address, Hometown, MN 55023 Inspection Date/Time: 8/16/2010 7:00 AM to 1:00 PM _____________________________________________________________________________________________ WINDOW STAINS Informational Conditions There is moisture staining or damaged finish of the window sill extension jamb area. This is a high indicator of moisture from within the wall cavity below the window 30+% moisture reading lower level bedroom 19% moisture reading PIN PROBE Informational Conditions The front elevation of your home was pin probed to the back side of the sheathing from the interior due to the brick cladding of the exterior. Area # 1 Dining room area _____________________________________________________________________________________________ This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein. All printed comments and the opinions expressed herein are those of the Inspection Company. Inspection Narratives - Page 6
  • 7. Inspection Address: 2233 Your Address, Hometown, MN 55023 Inspection Date/Time: 8/16/2010 7:00 AM to 1:00 PM _____________________________________________________________________________________________ Area # 1 - Continued 18% 15% 12% 14% _____________________________________________________________________________________________ This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein. All printed comments and the opinions expressed herein are those of the Inspection Company. Inspection Narratives - Page 7
  • 8. Inspection Address: 2233 Your Address, Hometown, MN 55023 Inspection Date/Time: 8/16/2010 7:00 AM to 1:00 PM _____________________________________________________________________________________________ Exterior II EXTERIOR VISUAL (STUCCO) KICK OUT FLASHING'S Informational Conditions The roof rakes have kick out flashing's installed kick out flashing CASING BEADS Informational Conditions There are no casing bead or weep screed separating the stucco from the shingles, and or hard surfaces such as steps, patios, and driveway surfaces. no casing bead no casing bead DRIP CAP FLASHING'S Informational Conditions There are no drip cap flashing's over the head of the window's and or door's, Drip cap flashing's should be installed to prevent water intrusion at these locations. Check with your window manufacturer about proper installation _____________________________________________________________________________________________ This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein. All printed comments and the opinions expressed herein are those of the Inspection Company. Inspection Narratives - Page 8
  • 9. Inspection Address: 2233 Your Address, Hometown, MN 55023 Inspection Date/Time: 8/16/2010 7:00 AM to 1:00 PM _____________________________________________________________________________________________ No Drip Cap Flashing's - Continued no drip cap flashing's WINDOW ISSUES Informational Conditions The window to stucco intersections are not caulked. Caulking can help prevent water infiltration around the frames no caulking no caulking and open hole in mortar joint _____________________________________________________________________________________________ This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein. All printed comments and the opinions expressed herein are those of the Inspection Company. Inspection Narratives - Page 9
  • 10. Inspection Address: 2233 Your Address, Hometown, MN 55023 Inspection Date/Time: 8/16/2010 7:00 AM to 1:00 PM _____________________________________________________________________________________________ No Caulking - Continued no caulking WEEP SCREEDS Informational Conditions No weep screed is installed separating the stucco from grade at the foundation line. Stucco by code is to terminate above the finished grade by 4" to 6" and is not to terminate into the grade (Earth) Properly installed weep screed prevents ground moisture from wicking up into the stucco which can attack the stud wall cavity and cause wood rot and a fungal growth. Weep screed also provides a separation so that any bulk water that is behind the stucco cladding can drain out. The weep screed also is used as a guide for the elevation height for any grade or landscape work. no weep screed STUCCO CRACKING Informational Conditions There is cracking of the stucco cladding which resembles a road map. This type of cracking may indicate the presence of moisture behind the water resistant barrier, especially under windows, roof rakes, feature boards, and deck ledger boards. _____________________________________________________________________________________________ This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein. All printed comments and the opinions expressed herein are those of the Inspection Company. Inspection Narratives - Page 10
  • 11. Inspection Address: 2233 Your Address, Hometown, MN 55023 Inspection Date/Time: 8/16/2010 7:00 AM to 1:00 PM _____________________________________________________________________________________________ STUCCO STAINING Informational Conditions There are stains in the stucco cladding which can indicate moisture intrusion in certain circumstances CAULKING DETAILS Informational Conditions There is no caulking where the stucco meets a dissimilar material such as brick, siding water pipes electrical boxes, lights or vents caulk all breaches GRADE ISSUES Informational Conditions The grade is high on the rear elevation of your home The grade should be down onto the foundation 4 to 6" grade grade is high is high _____________________________________________________________________________________________ This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein. All printed comments and the opinions expressed herein are those of the Inspection Company. Inspection Narratives - Page 11
  • 12. Inspection Address: 2233 Your Address, Hometown, MN 55023 Inspection Date/Time: 8/16/2010 7:00 AM to 1:00 PM _____________________________________________________________________________________________ The Grade Is High - Continued grade grade is high is high ROOF LINE VALLEY'S Informational Conditions The roof line on the right side of the greatroom is wet and covered with green moss roofline is wet and moss covered GUTTER'S Informational Conditions The downspouts are not sealed at the anchors _____________________________________________________________________________________________ This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein. All printed comments and the opinions expressed herein are those of the Inspection Company. Inspection Narratives - Page 12
  • 13. Inspection Address: 2233 Your Address, Hometown, MN 55023 Inspection Date/Time: 8/16/2010 7:00 AM to 1:00 PM _____________________________________________________________________________________________ Downspouts Not Sealed - Continued downspouts are not sealed FEATURE BOARDS AND QUOINS Informational Conditions The feature boards are installed flush with or over the window frame with little slope to the outward edge. This can cause severe water infiltration feature board over window frame DECK LEDGER BOARDS Informational Conditions There is no caulking or bottom flashing at the deck ledger board. This is a high probability area for water infiltration _____________________________________________________________________________________________ This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein. All printed comments and the opinions expressed herein are those of the Inspection Company. Inspection Narratives - Page 13
  • 14. Inspection Address: 2233 Your Address, Hometown, MN 55023 Inspection Date/Time: 8/16/2010 7:00 AM to 1:00 PM _____________________________________________________________________________________________ No caulking at the deck ledger boards - Continued no caulking or bottom flashing BRICK Informational Conditions The top of the brick lacks adequate slope outward to drain rainwater no slope There are no visible weep ropes in the brick near grade. Weep ropes provide for draining of water from behind the brick _____________________________________________________________________________________________ This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein. All printed comments and the opinions expressed herein are those of the Inspection Company. Inspection Narratives - Page 14
  • 15. Inspection Address: 2233 Your Address, Hometown, MN 55023 Inspection Date/Time: 8/16/2010 7:00 AM to 1:00 PM _____________________________________________________________________________________________ No Weep Ropes - Continued no visible weep ropes or tubes The brick cap flashing is not caulked no no brick caulking cap flashing _____________________________________________________________________________________________ This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein. All printed comments and the opinions expressed herein are those of the Inspection Company. Inspection Narratives - Page 15
  • 16. Inspection Address: 2233 Your Address, Hometown, MN 55023 Inspection Date/Time: 8/16/2010 7:00 AM to 1:00 PM _____________________________________________________________________________________________ Pin Probe PIN PROBE RESULTS GENERAL PIN PROBE INFORMATION Informational Conditions The following photo's are the results of your pin probe moisture level inspection. All moisture readings are from the sheathing unless otherwise specified. All moisture readings are given at the location where they were taken on the photo's. All readings are of wood moisture content from 6% to 100% with 6% being dry, and 100% being saturated. Moisture readings of 6% to 15% are considered to be normal, Moisture readings of 16% to 19% are considered cautionary, Moisture readings of 20% and higher can support mold growth and wood rot if sustained for more than 36 to 48 hours or more and are considered elevated and should be further evaluated. If there is an "ss" after a moisture reading on the photo's, this indicates that the sheathing felt soft or deteriorated when the pin probe holes were drilled, or when the pin probes were inserted. If there is an "ns" or 0 on the photo's this indicates that no sheathing was detected when the pin probe holes where drilled, and no reading was obtained, This indicates that the sheathing is deteriorated and or completely missing. If there is a reading it is generally off a framing member. If there is a "2" after the moisture reading this indicates that the reading was taken twice for accuracy. REFERENCE PHOTOS Informational Conditions The following photos are for referencing the location of the individual pin probe photos per each elevation Front Elevation Rear Elevation _____________________________________________________________________________________________ This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein. All printed comments and the opinions expressed herein are those of the Inspection Company. Inspection Narratives - Page 16
  • 17. Inspection Address: 2233 Your Address, Hometown, MN 55023 Inspection Date/Time: 8/16/2010 7:00 AM to 1:00 PM _____________________________________________________________________________________________ Rear Elevation Reference Photos 1 - Continued Left Elevation FRONT ELEVATION Informational Conditions FRONT ELEVATION PIN PROBE RESULTS _____________________________________________________________________________________________ This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein. All printed comments and the opinions expressed herein are those of the Inspection Company. Inspection Narratives - Page 17
  • 18. Inspection Address: 2233 Your Address, Hometown, MN 55023 Inspection Date/Time: 8/16/2010 7:00 AM to 1:00 PM _____________________________________________________________________________________________ FRONT ELEVATION 1 - Continued window area tested from the 6% 8% 8% 7% 7% 7% interior 9% 11% 12% 10% 9% 15% _____________________________________________________________________________________________ This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein. All printed comments and the opinions expressed herein are those of the Inspection Company. Inspection Narratives - Page 18
  • 19. Inspection Address: 2233 Your Address, Hometown, MN 55023 Inspection Date/Time: 8/16/2010 7:00 AM to 1:00 PM _____________________________________________________________________________________________ FRONT ELEVATION 1 - Continued moisture stains under garage round window RIGHT ELEVATION Informational Conditions RIGHT ELEVATION PIN PROBE RESULTS Garage walls 9% 9% 10% RIGHT ELEVATION RESULTS _____________________________________________________________________________________________ This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein. All printed comments and the opinions expressed herein are those of the Inspection Company. Inspection Narratives - Page 19
  • 20. Inspection Address: 2233 Your Address, Hometown, MN 55023 Inspection Date/Time: 8/16/2010 7:00 AM to 1:00 PM _____________________________________________________________________________________________ RIGHT ELEVATION 2 - Continued 7% 13% 11% 9% RIGHT ELEVATION RESULTS Area under the deck 12% 17% 12% _____________________________________________________________________________________________ This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein. All printed comments and the opinions expressed herein are those of the Inspection Company. Inspection Narratives - Page 20
  • 21. Inspection Address: 2233 Your Address, Hometown, MN 55023 Inspection Date/Time: 8/16/2010 7:00 AM to 1:00 PM _____________________________________________________________________________________________ RIGHT ELEVATION 3 - Continued 19.4% 15% REAR ELEVATION Informational Conditions REAR ELEVATION PIN PROBE RESULTS left side area 24% 15% 18% 18% 14% 22% 21% 14% 16% 19% 13% 16% 0 16% ns REAR ELEVATION PIN PROBE RESULTS Rear center section _____________________________________________________________________________________________ This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein. All printed comments and the opinions expressed herein are those of the Inspection Company. Inspection Narratives - Page 21
  • 22. Inspection Address: 2233 Your Address, Hometown, MN 55023 Inspection Date/Time: 8/16/2010 7:00 AM to 1:00 PM _____________________________________________________________________________________________ REAR ELEVATION 2 - Continued 11% 17% 17% 17% 23% 11% ss ss 26% 15% 10% 0 0 0 0 0 19% ns ns ns ns ns ss 0 14% 0 9% ns ns 8% 9% 8% 13% 8% 19% 12% REAR ELEVATION PIN PROBE RESULTS Right side area _____________________________________________________________________________________________ This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein. All printed comments and the opinions expressed herein are those of the Inspection Company. Inspection Narratives - Page 22
  • 23. Inspection Address: 2233 Your Address, Hometown, MN 55023 Inspection Date/Time: 8/16/2010 7:00 AM to 1:00 PM _____________________________________________________________________________________________ REAR ELEVATION 3 - Continued 19% 17% 12% 19% 11% 17% 23% 16% 21% 16% LEFT ELEVATION Informational Conditions LEFT ELEVATION PIN PROBE RESULTS _____________________________________________________________________________________________ This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein. All printed comments and the opinions expressed herein are those of the Inspection Company. Inspection Narratives - Page 23
  • 24. Inspection Address: 2233 Your Address, Hometown, MN 55023 Inspection Date/Time: 8/16/2010 7:00 AM to 1:00 PM _____________________________________________________________________________________________ LEFT ELEVATION 1 - Continued 9% sheathing felt soft 8% 11% further exploration 17 is advised ss 15% 19.1% 19.6% 16% retaining blocks are on the stud wall area 99% 11% _____________________________________________________________________________________________ This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein. All printed comments and the opinions expressed herein are those of the Inspection Company. Inspection Narratives - Page 24
  • 25. Inspection Address: 2233 Your Address, Hometown, MN 55023 Inspection Date/Time: 8/16/2010 7:00 AM to 1:00 PM _____________________________________________________________________________________________ _____________________________________________________________________________________________ This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein. All printed comments and the opinions expressed herein are those of the Inspection Company. Inspection Narratives - Page 25
  • 26. Inspection Address: 2233 Your Address, Hometown, MN 55023 Inspection Date/Time: 8/16/2010 7:00 AM to 1:00 PM _____________________________________________________________________________________________ CONFIDENTIAL HOME INSPECTION 1 GENERAL INFORMATION 2 Summary 3 SUMMARY 3 Interior 5 Miscellaneous conditions 5 Exterior II 8 EXTERIOR VISUAL (STUCCO) 8 Pin Probe 16 PIN PROBE RESULTS 16 INDEX 25 _____________________________________________________________________________________________ This report has been produced in accordance with our signed contract and is subject to the terms and conditions agreed upon therein. All printed comments and the opinions expressed herein are those of the Inspection Company. Inspection Narratives - Page 25
  • 27. Inspection Services & Consulting LLC 26291 Chisholm St NE Isanti MN 55040 Tel: 763-444-7348 Fax: 763-444-6718 Mobile: 763-350-3516 Email Address: mninspector@msn.com Property Address: 2233 Your Address, Hometown, MN 55023 Inspection Date: 8/16/2010 Time: 7:00 AM to 1:00 PM 763-123-4567 Dear Sample Report: Thank you for hiring Inspection Services & Consulting LLC to be of service. We hope that you were pleased with the quality of our service, and that you would recommend us to others. Please read the report carefully, and call us with any questions that you might have. We remain your consultant, and would be happy to assist you in any way that we can. We sincerely hope that you and your family will be happy and healthy in your home. Sincerely, Jon Anderson CEI CIT CHI CEI Inspection Services & Consulting LLC