SlideShare une entreprise Scribd logo
1  sur  53
INDEX


     LAYOUT                            pg. no
1.   INTRODUCTION [SUB STATION]             -1
2.   BUS BARS                               -4
3.   ISOLATORS                            -7
4.   PROTECTIVE RELAYS                   -11
5.   CIRCUIT BREAKERS                     -16
6.   POWER TRANSFORMER                    -25
7.   CURRENT TRANSFORMER                   -31
8.   CAPACITIVE VOLTAGE TRANSFORMERS       -33
9. TRASNFORMER OIL AND ITS TESTING        -36
10. LIGHTENING ARRESTORS                  -38
11. CONTROL ROOM                           -41
12. EARTHING OF THE SYSTEM                 -44
13. POWER LINE CARRIER COMMUNICATION      -46
14. CORONA                                -47
     CONCLUSION
     REFERENCES
INTRODUCTION



Electric power is generated, transmitted and distributed in the form of alternating
current. The electric power produced at the power stations is delivered to the
consumers through a large network of transmission & distribution.
The transmission network is inevitable long and high power lines are necessary to
maintain a huge block of power from source of generation to the load centers to

inter connected. Power house for increased reliability of supply greater.


The assembly of apparatus used to change some characteristics (e.g. voltage, ac to
dc, frequency, power factor etc.) of electric supply keeping the power constant is
called a sub-station.
Depending on the constructional feature, the high voltage sub-stations may be
further subdivided:
      a) Out door substation.
      b) Indoor substation.
      c) Basement or Underground substation.




                                          2                  Dept. of Electrical Engg.
fig 1


220 KV G.S.S. SANGANER


  1) It is an outdoor type substation.
  2) It is primary as well as distribution substation.
  3) One and half breaker scheme is applied.



                                         3               Dept. of Electrical Engg.
The power mainly comes from HIRAPURA-1 and HIRAPURA-2 & KOTA
THERMAL .




Out going feeders
1) One feeder of 220kv to KTPS
2) One feeder of 220kv to Sakatpura.
3) One feeder of 220kv to KTPS2
4) One feeder of 220kv to Phulera
5) One feeder of 400kv to Merta
6) One feeder of 220kv to Sanganer




At this substation following feeders are established.


       1. TIE FEEDERS.
       2. RADIAL FEEDERS.


       TIE FEEDERS:
       There are 220KV tie feeders as follows.
       1.220 KV KOTA-JAIPUR 1st & 2nd
      2. Inter state 220KV KOTA –DELHI
       3. Tie from 220 KV Heerapura.
       4. 220KV KTPS first & second.


       RADIAL FEEDERS

                                          4             Dept. of Electrical Engg.
1. 220 KV JAIPUR –KOTA 1st & 2nd feeders
      2. 132KV KOTA –BUNDI 1st
      3. 132KV KOTA –SAWAI MADHOPUR 1st & 2nd
      4.132 KV KOTA –SANGOD
       5. 132 KV KOTA –MORAR


                                 BUS BARS



                 Bus Bars are the common electrical component through which a
large no. of feeders operating at same voltage have to be connected.


 If the bus bars are of rigid type (Aluminum types) the structure heights are low
and minimum clearance is required. While in case of strain type of bus bars
suitable ACSR conductors are strung / tensioned by tension insulator discs
according to system voltages. In the widely used strain type bus bars stringing
tension is about 500 - 900 kg depending upon the size of conductor used.


Here proper clearance would be achieved only if require tension is achieved. Loose
bus bars would effect the clearances when it swings while over tensioning may
damage insulators. Clamps or even effect the supporting structures in low
temperature conditions.


The clamping should be proper, as loose clamp would spark under in full load
condition damaging the bus bars itself.




                                          5                  Dept. of Electrical Engg.
BUS BAR ARRANGEMENT MAY BE OF FOLLOWING TYPES WHICH
ARE BEING ADOPTED BY R.R.V.P.N.L
1.) Single bus arrangement.
2.) Double bus bar arrangement.
                  a) Main bus with transformer bus.
                  b.) Main bus-I with Main bus-II.
3.) Double bus bar arrangement with auxiliary bus.




DOUBLE BUS BAR CONTAINING MAIN BUS I WITH MAIN BUS II:


1. Each load may be fed from either bus.
2. The load circuits may be divided in two separate groups if needed from
operational consideration. Two supplies from different sources can be put on each
bus separately.
3. Either bus bar may be taken out from maintenance and cleaning of insulators.


This arrangement has been quite frequently adopted where the loads and continuity
of supply is necessary. In such a scheme a bus coupler breaker is mostly provided
as it enables on load change over from one bus bar to other.
The normal bus selection isolators cannot be used for breaking load currents. The
arrangement does not permit breaker maintenance without causing stoppage of
supply.


DOUBLE BUS BAR ARRANGEMENTS CONTAINS MAIN BUS WITH
AUXILIARY BUS:

                                           6                   Dept. of Electrical Engg.
The double bus bar arrangement provides facility to change over to either bus to
carry out maintenance on the other but provide no facility to carry over breaker
maintenance. The main and transfer bus works the other way round .It provides
facility for carrying out breaker maintenance but does not permit bus
maintenance. Wherever maintenance is required on any breaker the circuit is
changed over to the transfer bus and is controlled through bus coupler breaker.




                             fig 2


                                      7                  Dept. of Electrical Engg.
ISOLATORS


            Isolators which are also called disconnect switches or air break
switches after the assembly as per drawings on the leveled structures the
adjustment of connecting pipes, moving and fixed contacts is done so that all the
three phase of the isolator close and open simultaneously and there is a full surface
contact between moving and fixed contacts. Such switches are generally used on
both sides of equipment in order that repairs and replacement of the equipment can
be made without any danger. They should never be opened until the equipment in
the same circuit has been turned off and should always be closed before the
equipment is turned on.
The adjustment of the tendon pipes leveling of post insulator, stop holts in the
fixed contacts etc. is done for smooth operation of insulator. Following type of
insulator are being used in R.S.E.B-
   a) Isolator without earth blades.
   b) Isolator with earth blade.

                                          8                   Dept. of Electrical Engg.
c) Tendon isolator.




                                INSULATORS



The insulators for the overhead lines provide insulation to the power conductors
from the ground so that currents from conductors do not flow to earth through
supports. The insulators are connected to the cross arm of supporting structure and
the power conductors passes through the clamp of the insulator. The insulators
provide necessary insulation between line conductors and supports and thus
prevent any leakage current from conductors to earth. In general, the insulators
should have the following desirable properties:
   1. High mechanical strength in order to withstand conductor load, wind load
      etc.
   2. High electrical resistance of insulator material in order to avoid leakage
      currents to earth.
   3. High relative permittivity of insulator material in order that dielectric
      strength is high.
   4. The insulator material should be non porous, free from impurities and cracks
      otherwise the permitivity will be lowered.
   5. High ratio of puncture strength to flash over.


These insulators are generally made of glazed porcelain or toughened glass. Poly
come type insulators [solid core] are also being supplied in place of hast insulators
if available indigenously. The design of the insulator is such that the stress due to
contraction and expansion in any part of the insulator does not lead to any defect. It

                                           9                   Dept. of Electrical Engg.
is desirable not to allow porcelain to come in direct contact with a hard metal
screw thread.


TYPES OF INSULATORS:


There are three types of insulators used for overhead lines:


      1.   Pin type- pin type insulator consists of a single or multiple shells adapted
           to be mounted on a spindle to be fixed to the cross arm of the supporting
           structure.
           When the upper most shell is wet due to rain the lower shells are dry and
           provide sufficient leakage resistance. These are used for transmission and
           distribution of electric power at voltage up to voltage 33KV. Beyond
           operating voltage of 33KV the pin type insulators thus become too bulky
           and hence uneconomical.




                                          Fig 3.1
      2.   Suspension type- suspension type insulators consist of a number of
           porcelain disc connected in series by metal links in the form of a string.

                                           10                  Dept. of Electrical Engg.
Its working voltage is 66KV. Each disc is designed for low voltage for
     11KV.




                                  Fig 3.2
3.   Strain insulator- the strain insulators are exactly identical in shape with
     the suspension insulators. These strings are placed in the horizontal plane
     rather than the vertical plane. These insulators are used where line is
     subjected to greater tension. For low voltage lines (<11kV) shackle
     insulators are used as strain insulator.




                                      11                  Dept. of Electrical Engg.
Fig 3.3




                         PROTECTIVE RELAYS




A Protective relay is a device that detects the fault and initiates the operation of the
circuit breaker to isolate the defective element from the rest of the system.
   The relays detect the abnormal condition in the electrical circuits by constantly
measuring the electrical quantities i.e. voltage, current, frequency, phase angle
which are different under normal and fault conditions. Having detected the fault,
the relay operates to close the trip circuit of the breaker, which results in opening
of the breaker and disconnection of the faulty circuit.


Relay circuit connections can be divided in three parts:
1.) Primary winding of a C.T. that is connected in series with the line to be


                                           12                   Dept. of Electrical Engg.
protected.
2.) Secondary winding of C.T. and the relay operating coil.
3.)Third part is the tripping circuit, which may be either a.c. or d.c. . It consists of a
source of a supply, the trip coil of a circuit breaker and the relays stationary
contacts.


   When a short circuit occurs at point F on the transmission line the current
increases to enormous value. This results in a heavy current flow through the relay
coil, causing the relay to operate by closing its contacts. This in turn closes the trip
circuit of the breaker, making the C.B. open and isolating the family section from
the rest of the system. In this way, the relay ensures the safety of the circuit
equipment
from damage and normal working of the healthy portion of the system.




                                           13                    Dept. of Electrical Engg.
Fig 4
Basic qualities that a protective relay must possess are:


1.) Selectivity
2.) Speed
3.) Sensitivity
4.) Reliability
5.) Simplicity
6.) Economy




DIFFERENTIAL RELAYS



                                            14              Dept. of Electrical Engg.
A differential relay is one that operates when the phasor difference of two or more
similar electrical quantities exceeds a predetermined value.
Thus the current differential relay is one that compares the current entering and
current leaving the section. Under normal operating conditions, the two currents
are equal but as soon as fault occurs, this condition is no longer applied.
The difference between the incoming and outgoing currents is arranged to flow
through the operating coil of the relay. If this differential current is equal to or
greater than the pick up value, the relay will operate and open the C.B. to isolate
the faulty section.




BUCHHOLZ RELAY


It is a gas-actuated relay installed in oil immersed transformers for protection
against all kinds of faults. it is used to give an alarm in case of incipient (i.e. slow
developing)faults in the transformer and to disconnect the transformer from the
supply in the event of severe internal faults. it is usually installed in the pipe
connecting the conservator to the main tank. It is a universal practice to use
BUCHHOLZ relay on all such oil immersed transformers having ratings in excess
of 750kVA.




CONSTRUCTION


It takes the form of a domed vessel pipe between the main tank and the

                                           15                    Dept. of Electrical Engg.
conservator. The device has two elements. the upper element consists
of a mercury type switch attached to a float. The lower element contains
a mercury switch mounted on a hinged type flap located in the direct path
of the flow of oil from the transformer to the conservator. the upper element
closes an alarm circuit during incipient faults whereas the lower element is
arranged to trip the circuit breaker in case of server internal faults.


OPERATION


The operation of Buchholz relay is as follows:
(i)In case of incipient faults within the transformer, the heat due to fault
causes the decomposition of some transformer oil in the main tank the
products of decomposition contain more than 70% of hydrogen gas. the
hydrogen gas being light tries to go into the conservator and in the process


gets entrapped in the upper part of the relay chamber. when a pre determined
amount of gas gets accumulated, it exerts sufficient pressure on the float to
cause it tilt and close the contacts of the mercury switch attached tom it.
This completes the alarm circuits to to sound an alarm.
(ii)If a serious fault occurs in the transformer, enormous amount of gas
is generated in the main tank. The oil in the main tank rushes to the
conservator via the Buchholz relay and in doing so tilts the flap to close
the contacts of the mercury switch. This completes the trip circuit to open
the circuit breaker controlling the transformer.




ADVANTAGES

                                           16                   Dept. of Electrical Engg.
(i) It is the simplest form of transformer protection.
(ii) It detects the incipient faults at a stage much earlier than possible with
other forms of protection.




DISADVANTAGES


(i) It can only be used with oil immersed transformers equipped with conservator
tanks.
(ii) The device can detect only faults below oil level in the transformer. therefore
separate protection is needed for connecting cables.




                          CIRCUIT BREAKERS




                                           17                   Dept. of Electrical Engg.
Thus circuit breakers are used for switching & protection of various parts of power
system. Circuit breaker is a piece of equipment, which can


   1) Make or break a circuit either manually or automatically under normal
       condition.
   2) Break a circuit automatically under fault condition
   3) Make a circuit either manually or by remote control under fault conditions.




OPERATING PRINCIPLES


       A C.B. consists of fixed and moving contacts called electrodes. Under
normal operating conditions, these contacts remain closed and will not open
automatically until and unless the system becomes faulty. When a fault occurs on
any part of the system, the trip coils of the circuit breaker get energised and the
moving contacts are pulled apart, thereby opening the circuit.
       When the contacts of the C.B. are seperated under fault conditions, an arc is
struck between them. The current is thus able to continue until the discharge
ceaeses. The production of arc not only delays the current interruption process but
it also generates enormous heat which may cause damage to the system or to the
C.B.
It is thus necessary to extinguish the arc within the shortest possible time so that
the heat generated by it may not reach a dangerous value.




                                          18                   Dept. of Electrical Engg.
ARC PHENOMENON




When a short circuit occurs, a heavy current flows through the contacts of the C.B.
before they are opened by the protective system. At the instant when the contacts
begin to separate, the contact area decreases rapidly and large fault current causes
increased current density and hence rise in temperature. The heat produced in the
medium
between contacts is sufficient to ionize the arc or vaporize and ionize the oil. The
ionized air or vapour acts as conductor and an arc is set between the contacts. The
potential difference between the contacts is quite small and is sufficient to maintain
the arc. the arc provides a low resistance path and as a result the current in the
circuit remains uninterrupted so long as the arc persists.
       During the arcing period the current flowing between the contacts depends
on the arc resistance. The greater the arc resistance, the smaller the current that
flows between the contacts. The arc resistance depends upon:


(i) Degree of ionization.
(ii) Length of arc.
(iii) Cross section of arc.




CLASSIFICATION OF THE CIRCUIT BREAKERS:



                                          19                   Dept. of Electrical Engg.
There are several ways of classifying the circuit breakers. However, the most
general way of classification is on the basis of medium used for arc extinction.
The medium used for arc extinction is usually oil, air, sulphur hexafluoride (SF6)
or vacuum. Accordingly, circuit breakers may be classified into:




They are generally classified on the basis of the medium used for arc elimination
(i) Oil circuit breakers, which employ some insulating oil for arc extinction.
(ii) Air-blast circuit breakers in which high pressure air blast is used for
extinguishing the arc.
(iii) Sulphur hexa fluroide C.B. in which SF6 gas is used for arc extinction.
(iv) Vacuum C.B. in which vacuum is used for arc extinction.




 SULPHUR HEXAFLOURIDE (SF6) CIRCUIT BREAKER


   In such breakers, sulphur hexaflouride (SF6) gas is used as the arc quenching
medium. The sf6 is an electro-negative gas and has a strong tendency to absorb
free electrons. The SF6 circuit breakers have been found to be very effective for
high power and high voltage service.




CONSTRUCTION



                                           20                   Dept. of Electrical Engg.
The cylindrical large size steel tanks are mounted horizontally parallel to
each other. Each tank consists of SF6 under pressure. The interruption is of multi
break type & is placed along the axis of each tank. The interruption assembly is
supported inside the tank by the vertical bushing, which are mounted near the end
of each tank. Gas at high pressure is supplied to the interrupter from a gas
reservoir.


       The bushing are also insulated with SF6 the conductor is in the from of
copper tube supported at both end by porcelain shields. SF6 gas is supplied from
the high pressure tanks. Shields are provided with gasket seals to eliminate leakage
of gas from beginnings.




                                         21                   Dept. of Electrical Engg.
22   Dept. of Electrical Engg.
Fig 5
WORKING


In the closed position of the breaker the contacts remain surrounded by SF6 gas at
a pressure of about 2.8 kg/sq cm. When the breaker operates, the moving contact is
pulled apart and an arc is struck between the contacts. The
movement of the moving contact is synchronised with the opening of a valve
which permits SF6 gas at 14kg/sq cm pressure from the reservoir to the arc
interruption chamber. the high pressure flow of SF6 rapidly absorbs the free
electrons in the arc path to form immobile negative ions which are ineffective as
charge carriers. The result is that the medium between the contacts quickly builds
up high dielectric strength and causes the extinction of the arc. After
the breaker operation the valve is closed by the action of a set of springs.




400 KV SF6 C.B. [RATINGS]: -


Manufacture:                                         BHEL Hyderabad.
Type:                                                HLR245/2503 B.S.
Rated voltage:                        Normally 420 KV, maximum 440 KV.
Rated frequency:                                                   50 HZ.
Rated power frequency: voltage:                                   520 KV
Rated Impulse withstand voltage:
                 Lightning:                                       1425KV
                 Switching:                                       1050KV



                                           23                  Dept. of Electrical Engg.
Normal current rating
At 50 c ambient:                           2240Amps
At 40 c ambient:                           2500Amps


Short time current rating:                      40 KA for 3 sec.
Rated operating duty:                  0 to 0.3 sec. c-0-3min-mb.
Rated short circuit duration:               1 sec.




BREAKING CAPACITY [BASED ON SPECIFIED DUTY CYCLE]:
(a) Capacity at rated voltage:                 29000MVA [440KV].
(b) Symmetry current:                                40 KA.
(c) Asymmetry current:                               49 KA.


Making capacity:                                     100KA [peak]
Rated pressure of hydraulic operating (gauge): 250-350bar.
Rated pressure of SF6 gas at degree:             7.5bars.


Weight of complete breaker:                     11700 Kg.
Weight of SF6 gas:                                    76.5Kg.
Rated trip coil voltage:                             220 V. AC.
Rated closing voltage:                               220 V. DC.

                                          24                      Dept. of Electrical Engg.
First poll to clear factor:                         1.3




             ADVANTAGES OF SF6 CIRCUIT BREAKER:


   1. Due to the superior arc quenching property of SF6, such circuit breakers

       have very short arching time.
   2. Since the dielectric strength of SF6 gas is 2 to 3 times that of air, such

       breakers can interrupt much larger currents.
   3. The SF6 circuit breakers gives noiseless operation due to its closed gas
       circuit and no exhaust to the atmosphere unlike the air blast circuit breaker.
   4. The closest gas enclosure keeps the interior dry so that there is no moisture
       problem.
   5. There is on risk of fire in such breakers because SF6 gas is not inflammable.

       There are no carbon deposits so that tracking and insulation problems are
       eliminated.
   6. The SF6 breakers have low maintenance cost, light foundation requirement
       and minimum auxiliary equipment.
   7. Since SF6 breakers are totally enclosed and sealed from atmosphere they are
       particularly suitable where explosion hazard exists e.g., coal mines.




                                          25                   Dept. of Electrical Engg.
DEMERITS OF SF6 CIRCUIT BREKER:


    1. Sealing problems arise due to the type of the construction used.
    2. The presence of moisture in the system is very dangerous to SF6
       circuit breaker.
    3. Arced Sf6 gas is poisonous & should not be let out.
    4. The double pressure SF6 CB is cost liner due to complex gas system.
    5. The internal parts should be cleaned thoroughly during periodic       maintenance
under clean dry environment.
    6. Dust of Teflon & sulfide should be removed.
     7. Special facilities are needed for transporting the gas.




APPLICATIONS


SF6 C.B. have been developed for voltages 115 KV to 230 KV, power ratings 10
MVA to 20 MVA and interrupting time less than 3 cycles.




S.N      I.E.    MAK      TYPE        VOLTAGE         CURREN         STC          SF6/HY
O                E                            T                              D
1        552A    3AT3     3AT3   420/520      2000A                  40KA/S 7.5/350
2        552T    DO       DO     DO           DO                     DO      DO
3        552B    MG       FAR2   DO           3150A                  DO      7/300
4        452T    NGEF     S2M420 420/610/1425 2000A                  DO      8/35
5        252A    BHEL     3AT3   420/520/1050 DO                     DO      7.5/350
6        252B    ABB      EL(V)  420/1050     3150                   40KA/3S 7/31.5



                                            26                    Dept. of Electrical Engg.
POWER TRANSFORMER



The transformer is a static apparatus, which receives power/energy at it, one circuit
and transmits it to other circuit without changing the frequency. With this basic
conception we can use the voltages at our desired level while utilizing the power.
As, the voltage used to generate at modern power houses at 11 KV or so and
afterwards we get it step up at a level of 33 KV, 66 KV, 132 V, 220 KV or 400
KV, 750 KV for transmission to minimize the distribution losses. Again we get it
step down with the help of transformer to use at our wishes at 11 KV, 6.6 KV or
even 415, 230 volts at our houses.




BASIC PARTS OF TRANSFORMER



The following are the inherent parts of a modern day transformer:




                                         27                  Dept. of Electrical Engg.
1.    Primary and secondary coils (circuit) or windings.
2.    Core
3.    Main Tank
4.    Conservator
5.    Breather
6.    Radiator
7.    Buchholz relay
8.    Explosive vent
9.    Bushings (HT & LT) (Primary or secondary)
10.   Cooling fans
11.   Tap changer (on load and off load)
12.   NGR (Neutral Grounding Resistance) to minimize the earth fault current




                         Fig 6.1




DESCRIPTION OF PLANT:

                                        28                 Dept. of Electrical Engg.
The three transformer are oil immersed with rating of 250 MVA
& one with 315 MVA. However a synchronous loading of 100MVA at 0.8 power
factor (lag) and 18 MVA 0.8 pf (lag) on the tertiary can also be loaded to 20MVA
loading with 100MVA 0.8 pf on LV without exceeding the generated temperature
rise.
                    The transformer is also provided with a separate bank of
radiation, fans, and associated control equipments. The control equipments are
housed in a tank mounted miscalling.




                                   Fig 6.2




RATING DATAS.


Type of cooling:   ONAN / ONAF/ ODAF



                                         29                 Dept. of Electrical Engg.
MVA
HV:          189 / 252 / 315
IV:             189 / 252 / 315
LV:             63 / 84 / 105


VOLTS
HV: 400 KV
IV: 220 KV
LV:     33 KV


LINE AMPERES
HV:     273 / 364 / 455
IV:      497 / 662 / 828
LV:     1104 / 1471 /1839


IMPEDANCE VOLTAGE
HV to IV 12.65% on 315 MVA Base
HV to LV 39.16 % on 315MVA Base
IV to LV    26.66 % on 315 MVA Base




NUMBER OF PHASES
Three    HV, LV, IV
FREQUENCY IN Hz
50 Hz

                                      30   Dept. of Electrical Engg.
YEAR OF MANUFACTURE: 1985




    Mass of Core & Windings:                        1,32,000 kg
    Mass of Oil:                                    65,150 kg
    Total weight:                                    261,200 kg
    Oil in tank:                                    73,200 kg
    Oil in radiator:                               8400 kg


    Oil in tap changer:                         83,850 kg
    Transportation mass:                        168,000 kg
    Unmaking height:                            7760 mm
    Unmaking mass                               18000 Kg




    Guaranteed maximum temperature rise of:
        Oil                                        45ºC
        Winding                                    50ºC




COOLING FANS:


Rating:            2000 m3 of air per minute.
Type:              915 mm dial GEC (India) make.
Numbers per transformer: two

                                        31                   Dept. of Electrical Engg.
Fan motor: direct on line starts weather proof.
                          Squirrel cage IM 1400 W 400/440
                          Volt 3-φ , 50 Hz 720 rpm


PUMPS:
Rating:     1818 liters per minute.
Type:         a landless A to 8c sentiment.
Number of pump per transformer: one working, one standby.
Pump motor:         direct on line starts weather proof.
                          Squirrel cage IM




                                         32                 Dept. of Electrical Engg.
CURRENT TRANSFORMER


These transformers are used with low range ammeter to measure currents in high
voltage alternating current circuits where it is not practicable to connect
instruments and meters directly to lines. In addition to insulating the instrument
from the high voltage line, they step down the current in the known ratio. The
current (or series) transformers has a primary coil of 1 or more turns of thick wires
connected in series with the line whose current is to be measured. The secondary
consist of a large number of turns of fine wire and is connected across the ammeter
terminals (usually of 5 amp bracket should be removed or 1 amp range)




                                         33                  Dept. of Electrical Engg.
Fig 7




                      POTENTIAL TRANSFORMER


These transformers are extremely accurate ratio step down transformers and are
used in conjunction with standard low range voltmeter (usually 150 volt) whose
deflection when divided by voltage transformation ratio, gives the true voltage on
the high voltage side. In general, they are of the shell type and do not differ much
from the ordinary two winding transformer, except that their power rating is
extremely small. Up to voltage of 5000 potential transformers are usually of dry
type, between 5000 and 13800 volts, they may be either dry type or oil immersed
type, although for voltage above 13800 they are oil type. Since their secondary
windings are required to operate instruments or relays or pilot lights, their ratings
are usually 42 to 100 watts.


                                         34                  Dept. of Electrical Engg.
CAPACITIVE VOLTAGE TRANSFORMERS (CVT)



          Capacitive voltage transformers are special kind of power
transformers using capacitors to step down the voltage.


DESCRIPTION:




                                     35                   Dept. of Electrical Engg.
The capacitive voltage transformer comprises of a capacitor divider
with its associated electromagnetic unit. The divider provides an accurate
proportioned voltage, while the magnetic unit transforms this voltage, in both
magnitude and phase to convenient levels suitable for measuring, metering,
protection etc. all WSI capacitor units has metallic bellows to compensate the
volumetric expansion of oil inside. The porcelain in multi unit stack, all the
potential points are electrically tied and suitably shielded to overcome the effect
of corona RIV etc. Capacitive voltage transformers are available for system
voltages of 33 KV to 420KV.




                             Fig 8




APPLICATION:


1. Capacitive voltage transformers can be effectively as potential sources for
   measuring ,metering, protection, carrier communication and other vital
   functions of an electrical network.

                                         36                Dept. of Electrical Engg.
2. CVT are constructed in single or multi unit porcelain housing with there
       associated magnetic units. For EHV systemcuts are always supplied in multi
       unit construction.
    3. In case of EHV cuts the multi unit system has many advantage easy to
       transport and storing, convenience in handling.




    RATING OF CVT


    Voltage:          22/sqrt 3 KV
    Total o/p:   500MVA
    Operating voltage: 400/sqrt 3 max.
    Voltage factor:     1.5/30 sec.
    Test voltage:             630 KV for 1 min
    Impulse withstands voltage: 1.2/ 50 µs. 1425KV max.
    Frequency : 50Hz
    High frequency capacitance:       4400pF
    Primary capacitance:      4657pF
    Secondary capacitance: 80000 pF




S no       Ie           Make           Ratio     Burden      Class         Sec cap
1          Bassi        Wsi/cve/420    400       200,200,    3p,3p,0.5     80000pf
                        /1425                    100
2          Bassi 2      Wsi/cve/420    400       200,200,    3p,3p,0.5     80000pf
                        /1425                    100
3          Bus 1        Wsi/cve/420    400       200,200,    3p,3p,0.5     80000pf

                                          37                Dept. of Electrical Engg.
/1425                       100
4          Bus 2      Wsi/cve/420     400         200,200,    3p,3p,0.5      80000pf
                      /1425                       100




               TRANSFORMER OIL & ITS TESTING




The prime function of oil is to convey the heat from the core and winding to the
tank where it can be dissipated. Besides these, the oil provides additional insulation
between primary and secondary windings. So, the oil must be completely free from
dirt, moisture and other un-wanted solid matter. The oil used in the transformer is
natural mineral oil and should undergo the following tests if required:


BREAKDOWN VOLTAGE:
      The voltage at which the oil breaks down when subjected to an electric field.




FLASH POINT:
The temperature, at which the oil gives off so many vapors, when mixed with air
forms an ignitable mixture and gives a momentary flash with small pilot flame.



                                         38                   Dept. of Electrical Engg.
For checking above values, various tests are done. These are
categorized as:
   1. Physical test.
   2. Chemical test.
   3. Electrical test.




   The results must be close to standard results that are follows-


   S.N               TYPE OF TEST                        STD. RESULTS
   1.             Density (gm/cubic cm.)at 27°C            .85 to .89
   2.             Flash point                              >125°C
   3.             B.D.V Test K.V (rms.)                      >50 KV
   4.             Tan delta at 90°C                        < 20%
   5.             Water content (PPM.)             25(max.)above 145KV
   6.             Gas contents (PPM.)
                   (a) Hydrogen                               100 to150
                   (b) Methane                                50 to 70
                   (c) Ethane                                 30 to 50
                   (d) Ethylene                               100 to 150
                   (e) Acetylene                               20 to 30
                   (f) Carbon dioxide                      3000 to 3500
                   (h) Carbon mono-oxide                      200 to300




                                            39                 Dept. of Electrical Engg.
LIGHTENING ARRESTORS


An electric discharge between cloud and earth, between cloud and the charge
centers of the same cloud is known as lightening.
The earthing screens and the ground wires can well protect the electrical system
against direct lightening strokes but they fail to provide protection against
travelling waves which may reach the terminal apparatus. The lightening arrestors
or the surge diverters provide protections against such surges.




THYRITE TYPE:
                    Ground wire run over the tower provides an adequate protection
against lighting and reduce the induced electrostatic or electromagnetic voltage but
such a shield is inadequate to protect any traveling wave, which reaches the
terminal of the electrical equipment, and such wave can cause the following
damage.




                                          40                   Dept. of Electrical Engg.
1      the high peak of the surge may cause a flashover in the internal wiring
          thus it may spoil the insulation of the winding .
   2      the steep wave front may cause internal flash over between their turns of
          transformer.
   3      The stop wave front resulting into resonance and high voltage may cause
          internal or external flashover causing building up the oscillator is the
          electrical operation.


Lightening arrestors are provided between the line and earth provided the
protection against traveling wave surge the thyrite lightening arrestor are provided
at GSS. This type of LA has a basic cell made of thirties, which is a particular type
of clay, mixed with carborendum. Thirties has a particular property of being
insulator one voltage


At high voltage It will behave like a conducting material the electrical resistance of
thyrite depends upon the voltage each time the voltage is made twice the resistance
decrease in such a manner as to allow an increased current of 12.5 times the
change in current is independent of rate of application voltage and its instantaneous
value.
The above law is followed by this material without any limit on the voltage
increase and after the surge has passed the thyrite againretain its original property


A standard cell is rated for 1KV and is formed into a disc, which is sprayed on
both the sides of to give good contact with each disc. The dimensions of the discs
are stacked i.e. 16 cm in diameter and 17.5 cm thick these discs are stacked one
upon each other and they are further placed in to a porcelien container with a
suitable arrangement of gap between them.

                                          41                   Dept. of Electrical Engg.
These gaps serves as the purpose of preventing any current flow during
normal operating voltage in case of any transients the gap are punctured. The
Thyrite type arrestor will discharge several thousands ampere without the slightest
tendency of flashover on the edges of most important of the advance is that there is
absolutely no time lag in its performance.




400KV LIGHTNENIG ARRESTOR


manufacture: English electric company
no of phases: one
rated voltage: 360 KV
nominal discharge current         (8×20µs) 10KA
high current impulse(4×110 µs ) 100KA
long duration rating(200 µs)           500KA


Sno           Ie               Make            Type       Current        Voltage
1             Bassi1           Wsi             Cpl        10KA           360KV
2             bassi2           Elpro           Alugard2   10KA           360KV
3             ILT1             Elpro           Alugard2   10KA           360KV
4             ILT2             Elpro           Alugard2   10KA           360KVh
5             ILT3             WSI             CDV303     10KA           398KV
6             ILT4             WSI             CDV03      10KA           398KV




                                          42                 Dept. of Electrical Engg.
CONTROL PANEL


The diagram made on the control panel is known as mimic diagram.


COLOUR CODING


* 33KV GREEN
* 132 KV BLACK
* 220KV BROWN
* 440 VOLTS VOILET/INDIGO
* 110 VOLTS ORANGE




    REACTOR


It is used to lower the over excited capacitor. Capacitor bank is connected in shunt
over the reactor. Capacitors main purpose is to boost up the voltage. so when we
want to lower the voltage we use reactors. it is also use to stop the sudden change.
the commonly used reactor is NGR(Neutral ground reactor).




                                         43                  Dept. of Electrical Engg.
 CIRCUIT BREAKER
There is a one and half breaker scheme i.e. 3 breakers for 2 buses used in 400 KV
G.S.S.




    BUS COUPLERS
It is used to equalize the load on both Bus bars.




    DISTURBANCE RECORDER
It records the distance & fault on graph with voltage w.r.t time.




    EVENT LOGGER
it monitors as well as provides the details as a printed material.
These details may contain the sequence of operation, switching time, closing time
etc.




    ON LOAD TAP CHANGER (OLTC)
In this method a number of tappings are provided on the secondary of the
transformer. The voltage drop in the line is supplied by changing the secondary
emf of the transformer through the adjustment of its number of turns by using
transition resistor
which are placed in between each tapping.

                                          44                  Dept. of Electrical Engg.
In supply system, tap changing has to be performed on load so that here is no
interruption to supply. By using transition resister therefore shut down is not
required.




                                          Fig 11
    NO LOAD TAP CHANGER (NLTC)
in this we change the tap manually for which we have to shut down the
transformer.
When the load increases the voltage across the primary drops but the secondary
voltage can be kept at the previous value by placing the movable arm on to a
higher stud. Whenever a tapping is to be changed in this type of transformer, the
load is kept off and hence the name off load tap-changing transformer.




    SYNCHRONOSCOPE


A synchronoscope is used to determine the correct instance of closing the switch
with connect the new supply to bus bar the correct instance of synchronizing is
indicated when bus bar and incoming voltage



                                          45                  Dept. of Electrical Engg.
* are equal in magnitude
* are equal in phase
* have the same frequency
   the phase sequence is same


EARTHING OF THE SYSTEM:
The provision of an earthling system for an electric system is necessary by the
following reason.
   1     In the event of over voltage on the system due to lightening discharge or
         other system fault. These parts of equipment, which are normally dead, as
         for as voltage, are concerned do not attain dangerously high potential.
   2     In a three phase, circuit the neutral of the system is earthed in order to
         stabilize the potential of circuit with respect to earth.
The resistance of earthling system is depending on
   1     Shape and material of earth electrode used.
   2     Depth in the soil
   3     Specific resistance of soil surrounding in the neighborhood of system
         electrodes.
PROCEDURE OF EARTHING:
Technical consideration the current carrying path should have enough capacity to
deal with more faults current. The resistance of earth and current path should be
low enough to prevent voltage rise between earth and neutral. The earth electrode
must be driven into the ground to a sufficient depth to as to obtain lower value of
earth resistance. To sufficient lowered earth resistance a number of electrodes are
inserted in the earth to a depth they are connected together to form a mesh. The
resistance of earth should be for the mesh in generally inserted in the earth at 0.5m



                                          46                    Dept. of Electrical Engg.
depths the several point of mesh then connected to earth electrode or ground
conduction. The earth electrode is metal plate copper is used for earth plate.
Neutral Earthing:
             Neutral earthing of power transformer all power system operates with
grounded neutral. Grounding of neutral offers several advantages the neutral point
of generator transformer is connected to earth directly or through a reactance in
some cases the neutral points is earthed through an adjustable reactor of reactance
matched with the line. The earthling is one of the most important feature of system
design for switchgear protection neutral grounding is important because:




   1     The earth fault protection is based on the method of neutral earthling.
   2     The neutral earthling is associated switchgear.
   3     The neutral earthling is provided for the purpose of protection arcing
         grounds unbalanced voltages with respect to protection from lightening
         and for improvement of system.




                                         47                   Dept. of Electrical Engg.
POWER LINE CARRIER COMMUNICATION



As electronics plays a vital role in the industrial growth, communication is also a
backbone of any power station, communication between various generating and
receiving station is very essential for proper operation of power system. This is
more so in case of a large interconnected system where a control load dispatch
station has to coordinate
the working of various units to see that the system is maintained in the optimum
working condition, power line communication is the most economical and reliable
method of communication for medium and long distance in a power network.
PLCC system in Rajasthan: -


1 HEERAPURA: JAIPUR, AJMER, BYAWAR, BHILWARA, PALI, JODHPUR
2 HISSAR: KHETRI, HEERAPURA, KOTA, RAPP
3 HEERAPURA: KOTS, JSP, RPS, GSD
4 BHILWARA:        RPS
5 PALI:      FALANA
6 HEERAPURA: ALWAR, BHARATPUR
7 NEEMUCH:         DEBARI
8 DEBARI: SIROHI


                                         48                   Dept. of Electrical Engg.
9 DEBARI: ZAWAR MINES
10 HEERAPURA: SIKAR, RATANGARH, BIKANER
11 HANUM, ANGARH: HISSAR, SHRIGANGANAGAR
12 HEERAPURA: BADHERPUB




                          CORONA EFFECT



When an alternating potential difference is applied across two conductors whose
spacing is as large as compared to their diameters, there is no apparent change in
the condition of atmospheric air surrounding the wires if the applied voltage is low.
However when the applied voltage exceeds a certain value called critical
disruptive voltage, the conductors are surrounded by a faint violet glow called
corona.


      The phenomenon of corona is accompanied by a hissing sound, production
of ozone, power loss and radio interference. The higher the voltage is raised, the
larger and higher the luminous envelope becomes, and greater are the sound, the
power loss and the radio noise. If the applied voltage is increased to breakdown
value, a flash over will occur between the conductors due to the breakdown of air
insulation.


      The phenomenon of violet glow, hissing noise and production of ozone gas
in an overhead transmission line is known as corona.



                                         49                  Dept. of Electrical Engg.
If the conductors are polished and smooth, the corona glow will be uniform
throughout the length of the conductors, otherwise the rough points will appear
brighter. The positive wire has uniform glow about it, while the negative
conductors has spotty glow.




FACTORS AFFECTING CORONA


The phenomenon of corona is affected by the physical state of the atmosphere as
well as by the conditions of the line. The following are the factors on which corona
depends:
   1. Atmosphere. In the stormy weather, the number of ions is more than normal

      and as such corona occurs at much less voltage as compared with fair
      weather.
   2. Conductor size. The rough and irregular surface will give rise to more

      corona because unevenness of the surface decreases the value of breakdown
      voltage.
   3. Spacing between conductors. Larger space between conductors reduces the

      electro-static stresses at the conductor surface, thus avoiding corona
      formation.
   4. Line voltage. If the line voltage is low, there is no chance in the condition of

      air surrounding the conductors and hence no corona is formed.




                                          50                  Dept. of Electrical Engg.
ADVANTAGES AND DISADVANTAGES OF CORONA


Corona has many advantages and disadvantages. In the correct design of a high
 voltage overhead line, a balance should be struck between the advantages and
 disadvantages.


Advantages
  1. Due to corona formation, the air surrounding the conductor becomes
     conducting and hence virtual diameter of the conductor is increased. The
     increased diameter reduces the electro-static stresses between the
     conductors.
  2. Corona reduces the effect of the transients produced by surges.


Disadvantages


  1. Corona is accompanied by a loss of energy. This affects the transmission
     efficiency of the line.
  2. Ozone is produced by corona and may cause corrosion of the conductor due
     to chemical action.
  3. The current drawn by the line due to corona is non-sinusoidal and hence
     non-sinusoidal voltage drop occurs in the line. This may cause inductive
     interference with neighboring communication lines.




                                       51                  Dept. of Electrical Engg.
CONCLUSION



       A technician needs to have not just theoretical but practical as well and so
every student is supposed to undergo a practical training session after III year
where I have imbibed the knowledge about transmission, distribution, generation
and maintenance with economical issues related to it.
     During our 30 days training session we were acquainted with the repairing of
the transformers and also the testing of oil which is a major component of
transformer.
      At last I would like to say that practical training taken at 220KV GSS has
broadened my knowledge and has widened my thinking as a professional.




                                          52                  Dept. of Electrical Engg.
REFERENCES:
Principles of Power System-by V.K.MEHTA

Electrical Power System-by C.L.WADHWA



                                        REPORT BY-

                                          Kapil Kumar

                                        SKIT,JAIPUR




                                 53                Dept. of Electrical Engg.

Contenu connexe

Tendances

DISTANCE PROTECTION RELAY
DISTANCE PROTECTION RELAYDISTANCE PROTECTION RELAY
DISTANCE PROTECTION RELAYRaviraj solanki
 
Electric substation
Electric substation Electric substation
Electric substation ANNU KUMAR
 
Installation, Testing and Troubleshooting of Transformers
Installation, Testing and Troubleshooting of TransformersInstallation, Testing and Troubleshooting of Transformers
Installation, Testing and Troubleshooting of TransformersLiving Online
 
Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentationNadir Baloch
 
Electrical distribution system
Electrical distribution system Electrical distribution system
Electrical distribution system Ankush Bharti
 
HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGH
HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGHHIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGH
HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGHShankar Singh
 
Transmission &amp; distribution of electrical power
Transmission &amp; distribution of electrical powerTransmission &amp; distribution of electrical power
Transmission &amp; distribution of electrical powerpriyanka1432
 
Short circuit test in brief
Short circuit test in briefShort circuit test in brief
Short circuit test in briefMuthar Hussain
 
Presentation on substations
Presentation on substationsPresentation on substations
Presentation on substationsvishalgohel12195
 
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMSSWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMSPartha Parida
 
Protection against overvoltage
Protection against overvoltageProtection against overvoltage
Protection against overvoltagevishalgohel12195
 
Basics of overcurrent protection
Basics of overcurrent protectionBasics of overcurrent protection
Basics of overcurrent protectionSalim Palayi
 
Er rahul sharma feeder protection
Er rahul sharma feeder protectionEr rahul sharma feeder protection
Er rahul sharma feeder protectionRahul Ruddra
 
Testing of circuit breakers
Testing of circuit breakersTesting of circuit breakers
Testing of circuit breakersKabilesh K
 
PPt on 220 kV substation
PPt on 220 kV substationPPt on 220 kV substation
PPt on 220 kV substationIshank Ranjan
 
Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentationNikhil Kachare
 

Tendances (20)

DISTANCE PROTECTION RELAY
DISTANCE PROTECTION RELAYDISTANCE PROTECTION RELAY
DISTANCE PROTECTION RELAY
 
Introduction to mv switchgear
Introduction to mv switchgearIntroduction to mv switchgear
Introduction to mv switchgear
 
Electric substation
Electric substation Electric substation
Electric substation
 
Installation, Testing and Troubleshooting of Transformers
Installation, Testing and Troubleshooting of TransformersInstallation, Testing and Troubleshooting of Transformers
Installation, Testing and Troubleshooting of Transformers
 
Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentation
 
Electrical distribution system
Electrical distribution system Electrical distribution system
Electrical distribution system
 
HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGH
HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGHHIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGH
HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGH
 
Transmission &amp; distribution of electrical power
Transmission &amp; distribution of electrical powerTransmission &amp; distribution of electrical power
Transmission &amp; distribution of electrical power
 
Short circuit test in brief
Short circuit test in briefShort circuit test in brief
Short circuit test in brief
 
Presentation on substations
Presentation on substationsPresentation on substations
Presentation on substations
 
Electric power system
Electric power systemElectric power system
Electric power system
 
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMSSWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
 
Protection against overvoltage
Protection against overvoltageProtection against overvoltage
Protection against overvoltage
 
Basics of overcurrent protection
Basics of overcurrent protectionBasics of overcurrent protection
Basics of overcurrent protection
 
SWITCHGEAR
SWITCHGEARSWITCHGEAR
SWITCHGEAR
 
Er rahul sharma feeder protection
Er rahul sharma feeder protectionEr rahul sharma feeder protection
Er rahul sharma feeder protection
 
Testing of circuit breakers
Testing of circuit breakersTesting of circuit breakers
Testing of circuit breakers
 
Substations
Substations Substations
Substations
 
PPt on 220 kV substation
PPt on 220 kV substationPPt on 220 kV substation
PPt on 220 kV substation
 
Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentation
 

En vedette

presentation on 400kv gss heerapura @mnit
presentation on 400kv gss heerapura @mnitpresentation on 400kv gss heerapura @mnit
presentation on 400kv gss heerapura @mnitSuresh Choudhary
 
Training Report on 220 KV G.S.S. HINDAUN CITY
Training Report on 220 KV G.S.S. HINDAUN CITYTraining Report on 220 KV G.S.S. HINDAUN CITY
Training Report on 220 KV G.S.S. HINDAUN CITYRohitashav Goyal
 
400kv sub-station-final-ppt-by-mohit
400kv sub-station-final-ppt-by-mohit400kv sub-station-final-ppt-by-mohit
400kv sub-station-final-ppt-by-mohitMohit Awasthi
 
Substation Training presentation
Substation Training presentationSubstation Training presentation
Substation Training presentationKamal Mittal
 
Visit to 400 kV substation, Hadala
Visit to 400 kV substation, HadalaVisit to 400 kV substation, Hadala
Visit to 400 kV substation, HadalaNandan Desai
 
Training from 220kv GSS Sanganer, which is located on Muhana Road, Jaipur
Training from 220kv GSS Sanganer, which is located on Muhana Road, JaipurTraining from 220kv GSS Sanganer, which is located on Muhana Road, Jaipur
Training from 220kv GSS Sanganer, which is located on Muhana Road, JaipurR-One Power
 
A report on 220 kv gss mansarovar, jaipur by ravindra kumar goma
A report on 220 kv gss mansarovar, jaipur by ravindra kumar gomaA report on 220 kv gss mansarovar, jaipur by ravindra kumar goma
A report on 220 kv gss mansarovar, jaipur by ravindra kumar gomaravindragoma
 
Operational description of 400kv switchyard NTPC Ramagundam RSTPS
Operational description of 400kv switchyard NTPC Ramagundam RSTPSOperational description of 400kv switchyard NTPC Ramagundam RSTPS
Operational description of 400kv switchyard NTPC Ramagundam RSTPSPradeep Avanigadda
 
Protection & relayppt 100
Protection & relayppt 100Protection & relayppt 100
Protection & relayppt 100Jay Shah
 
A PPT ON 220 KV GSS HINDAUN CITY
A PPT ON 220 KV GSS HINDAUN CITYA PPT ON 220 KV GSS HINDAUN CITY
A PPT ON 220 KV GSS HINDAUN CITYRohitashav Goyal
 
Autodesk revit design(bus station)
Autodesk revit design(bus station)Autodesk revit design(bus station)
Autodesk revit design(bus station)Miguel Zamarripa
 
Report bsnl training at patna
Report bsnl training at patnaReport bsnl training at patna
Report bsnl training at patnaAbhishek Prasad
 
Industrial Training Presentation
Industrial Training PresentationIndustrial Training Presentation
Industrial Training Presentationkumarmayursinha
 
132kv Substation
132kv Substation132kv Substation
132kv Substationguestecdd58
 

En vedette (20)

presentation on 400kv gss heerapura @mnit
presentation on 400kv gss heerapura @mnitpresentation on 400kv gss heerapura @mnit
presentation on 400kv gss heerapura @mnit
 
PPT ON 220KV GSS
PPT ON 220KV GSSPPT ON 220KV GSS
PPT ON 220KV GSS
 
Training Report on 220 KV G.S.S. HINDAUN CITY
Training Report on 220 KV G.S.S. HINDAUN CITYTraining Report on 220 KV G.S.S. HINDAUN CITY
Training Report on 220 KV G.S.S. HINDAUN CITY
 
400kv sub-station-final-ppt-by-mohit
400kv sub-station-final-ppt-by-mohit400kv sub-station-final-ppt-by-mohit
400kv sub-station-final-ppt-by-mohit
 
Substation Training presentation
Substation Training presentationSubstation Training presentation
Substation Training presentation
 
Visit to 400 kV substation, Hadala
Visit to 400 kV substation, HadalaVisit to 400 kV substation, Hadala
Visit to 400 kV substation, Hadala
 
A 220kV Substation
A 220kV SubstationA 220kV Substation
A 220kV Substation
 
Training from 220kv GSS Sanganer, which is located on Muhana Road, Jaipur
Training from 220kv GSS Sanganer, which is located on Muhana Road, JaipurTraining from 220kv GSS Sanganer, which is located on Muhana Road, Jaipur
Training from 220kv GSS Sanganer, which is located on Muhana Road, Jaipur
 
220 kv gss renwal ppt
220 kv gss renwal ppt220 kv gss renwal ppt
220 kv gss renwal ppt
 
Substation overview
Substation overviewSubstation overview
Substation overview
 
A report on 220 kv gss mansarovar, jaipur by ravindra kumar goma
A report on 220 kv gss mansarovar, jaipur by ravindra kumar gomaA report on 220 kv gss mansarovar, jaipur by ravindra kumar goma
A report on 220 kv gss mansarovar, jaipur by ravindra kumar goma
 
Operational description of 400kv switchyard NTPC Ramagundam RSTPS
Operational description of 400kv switchyard NTPC Ramagundam RSTPSOperational description of 400kv switchyard NTPC Ramagundam RSTPS
Operational description of 400kv switchyard NTPC Ramagundam RSTPS
 
220 kv G.S.S (report)
220 kv G.S.S (report)220 kv G.S.S (report)
220 kv G.S.S (report)
 
Protection & relayppt 100
Protection & relayppt 100Protection & relayppt 100
Protection & relayppt 100
 
A PPT ON 220 KV GSS HINDAUN CITY
A PPT ON 220 KV GSS HINDAUN CITYA PPT ON 220 KV GSS HINDAUN CITY
A PPT ON 220 KV GSS HINDAUN CITY
 
Autodesk revit design(bus station)
Autodesk revit design(bus station)Autodesk revit design(bus station)
Autodesk revit design(bus station)
 
Report bsnl training at patna
Report bsnl training at patnaReport bsnl training at patna
Report bsnl training at patna
 
Shanghai Long Distance Bus Station
Shanghai Long Distance Bus StationShanghai Long Distance Bus Station
Shanghai Long Distance Bus Station
 
Industrial Training Presentation
Industrial Training PresentationIndustrial Training Presentation
Industrial Training Presentation
 
132kv Substation
132kv Substation132kv Substation
132kv Substation
 

Similaire à Gss herapura report

Gssherap 110901224655-phpapp02
Gssherap 110901224655-phpapp02Gssherap 110901224655-phpapp02
Gssherap 110901224655-phpapp02Mohit Kothari
 
Gssherap 110901224655-phpapp0
Gssherap 110901224655-phpapp0Gssherap 110901224655-phpapp0
Gssherap 110901224655-phpapp0Mohit Kothari
 
Gssherap 110901224655-phpapp02
Gssherap 110901224655-phpapp02Gssherap 110901224655-phpapp02
Gssherap 110901224655-phpapp02Mohit Kothari
 
REPORT ON 33/11KV SUBSTATION
REPORT ON 33/11KV SUBSTATION REPORT ON 33/11KV SUBSTATION
REPORT ON 33/11KV SUBSTATION Ravi Phadtare
 
A Training Report Of Saltlake 132/33kv Substation
A Training Report Of Saltlake 132/33kv SubstationA Training Report Of Saltlake 132/33kv Substation
A Training Report Of Saltlake 132/33kv SubstationSubhrajit Ghosh
 
Lab manual psd v sem experiment no 7
Lab manual psd v sem experiment no 7Lab manual psd v sem experiment no 7
Lab manual psd v sem experiment no 7Sachin Airan
 
Electrical Installation PPT (Basic Electrical Engineering)
Electrical Installation PPT (Basic Electrical Engineering)Electrical Installation PPT (Basic Electrical Engineering)
Electrical Installation PPT (Basic Electrical Engineering)Dhrumil Maniar
 
132 KV GSS NPH jodhpur treaning report
132 KV GSS NPH jodhpur treaning report 132 KV GSS NPH jodhpur treaning report
132 KV GSS NPH jodhpur treaning report imkanhaiyalal
 
132 KV Grid Station Intern ship training report
132 KV Grid Station Intern ship training report132 KV Grid Station Intern ship training report
132 KV Grid Station Intern ship training reportMuntazir Mehdi
 
Busduct___Busbar.pptx
Busduct___Busbar.pptxBusduct___Busbar.pptx
Busduct___Busbar.pptxpramod719257
 
the substation components study
the substation components study the substation components study
the substation components study Krishnaveni Reddy
 
substation internship report
substation internship report substation internship report
substation internship report Arun Thapa
 
Design of substation
Design of substationDesign of substation
Design of substationSayanSarkar55
 
132 kv sub-station, power transmission
132 kv sub-station, power transmission132 kv sub-station, power transmission
132 kv sub-station, power transmissionprasantakcs
 
insulators, conductors, transformer and ac motors
insulators, conductors, transformer and ac motorsinsulators, conductors, transformer and ac motors
insulators, conductors, transformer and ac motorsChippa Srikanth
 

Similaire à Gss herapura report (20)

Gssherap 110901224655-phpapp02
Gssherap 110901224655-phpapp02Gssherap 110901224655-phpapp02
Gssherap 110901224655-phpapp02
 
Gssherap 110901224655-phpapp0
Gssherap 110901224655-phpapp0Gssherap 110901224655-phpapp0
Gssherap 110901224655-phpapp0
 
Gssherap 110901224655-phpapp02
Gssherap 110901224655-phpapp02Gssherap 110901224655-phpapp02
Gssherap 110901224655-phpapp02
 
Gss report
Gss reportGss report
Gss report
 
REPORT ON 33/11KV SUBSTATION
REPORT ON 33/11KV SUBSTATION REPORT ON 33/11KV SUBSTATION
REPORT ON 33/11KV SUBSTATION
 
A Training Report Of Saltlake 132/33kv Substation
A Training Report Of Saltlake 132/33kv SubstationA Training Report Of Saltlake 132/33kv Substation
A Training Report Of Saltlake 132/33kv Substation
 
Lab manual psd v sem experiment no 7
Lab manual psd v sem experiment no 7Lab manual psd v sem experiment no 7
Lab manual psd v sem experiment no 7
 
Electrical Installation PPT (Basic Electrical Engineering)
Electrical Installation PPT (Basic Electrical Engineering)Electrical Installation PPT (Basic Electrical Engineering)
Electrical Installation PPT (Basic Electrical Engineering)
 
132 KV GSS NPH jodhpur treaning report
132 KV GSS NPH jodhpur treaning report 132 KV GSS NPH jodhpur treaning report
132 KV GSS NPH jodhpur treaning report
 
132 KV Grid Station Intern ship training report
132 KV Grid Station Intern ship training report132 KV Grid Station Intern ship training report
132 KV Grid Station Intern ship training report
 
Busduct___Busbar.pptx
Busduct___Busbar.pptxBusduct___Busbar.pptx
Busduct___Busbar.pptx
 
Distribution system 2
Distribution system  2Distribution system  2
Distribution system 2
 
SOUMADIP-FACT.pptx
SOUMADIP-FACT.pptxSOUMADIP-FACT.pptx
SOUMADIP-FACT.pptx
 
the substation components study
the substation components study the substation components study
the substation components study
 
Lec no. 01
Lec no. 01Lec no. 01
Lec no. 01
 
substation internship report
substation internship report substation internship report
substation internship report
 
Design of substation
Design of substationDesign of substation
Design of substation
 
132 kv sub-station, power transmission
132 kv sub-station, power transmission132 kv sub-station, power transmission
132 kv sub-station, power transmission
 
5 power house
5 power house5 power house
5 power house
 
insulators, conductors, transformer and ac motors
insulators, conductors, transformer and ac motorsinsulators, conductors, transformer and ac motors
insulators, conductors, transformer and ac motors
 

Dernier

INTRODUCTION TO CATHOLIC CHRISTOLOGY.pptx
INTRODUCTION TO CATHOLIC CHRISTOLOGY.pptxINTRODUCTION TO CATHOLIC CHRISTOLOGY.pptx
INTRODUCTION TO CATHOLIC CHRISTOLOGY.pptxHumphrey A Beña
 
Influencing policy (training slides from Fast Track Impact)
Influencing policy (training slides from Fast Track Impact)Influencing policy (training slides from Fast Track Impact)
Influencing policy (training slides from Fast Track Impact)Mark Reed
 
Like-prefer-love -hate+verb+ing & silent letters & citizenship text.pdf
Like-prefer-love -hate+verb+ing & silent letters & citizenship text.pdfLike-prefer-love -hate+verb+ing & silent letters & citizenship text.pdf
Like-prefer-love -hate+verb+ing & silent letters & citizenship text.pdfMr Bounab Samir
 
Computed Fields and api Depends in the Odoo 17
Computed Fields and api Depends in the Odoo 17Computed Fields and api Depends in the Odoo 17
Computed Fields and api Depends in the Odoo 17Celine George
 
Proudly South Africa powerpoint Thorisha.pptx
Proudly South Africa powerpoint Thorisha.pptxProudly South Africa powerpoint Thorisha.pptx
Proudly South Africa powerpoint Thorisha.pptxthorishapillay1
 
Procuring digital preservation CAN be quick and painless with our new dynamic...
Procuring digital preservation CAN be quick and painless with our new dynamic...Procuring digital preservation CAN be quick and painless with our new dynamic...
Procuring digital preservation CAN be quick and painless with our new dynamic...Jisc
 
Incoming and Outgoing Shipments in 3 STEPS Using Odoo 17
Incoming and Outgoing Shipments in 3 STEPS Using Odoo 17Incoming and Outgoing Shipments in 3 STEPS Using Odoo 17
Incoming and Outgoing Shipments in 3 STEPS Using Odoo 17Celine George
 
Full Stack Web Development Course for Beginners
Full Stack Web Development Course  for BeginnersFull Stack Web Development Course  for Beginners
Full Stack Web Development Course for BeginnersSabitha Banu
 
4.18.24 Movement Legacies, Reflection, and Review.pptx
4.18.24 Movement Legacies, Reflection, and Review.pptx4.18.24 Movement Legacies, Reflection, and Review.pptx
4.18.24 Movement Legacies, Reflection, and Review.pptxmary850239
 
Q4 English4 Week3 PPT Melcnmg-based.pptx
Q4 English4 Week3 PPT Melcnmg-based.pptxQ4 English4 Week3 PPT Melcnmg-based.pptx
Q4 English4 Week3 PPT Melcnmg-based.pptxnelietumpap1
 
Choosing the Right CBSE School A Comprehensive Guide for Parents
Choosing the Right CBSE School A Comprehensive Guide for ParentsChoosing the Right CBSE School A Comprehensive Guide for Parents
Choosing the Right CBSE School A Comprehensive Guide for Parentsnavabharathschool99
 
Roles & Responsibilities in Pharmacovigilance
Roles & Responsibilities in PharmacovigilanceRoles & Responsibilities in Pharmacovigilance
Roles & Responsibilities in PharmacovigilanceSamikshaHamane
 
ECONOMIC CONTEXT - PAPER 1 Q3: NEWSPAPERS.pptx
ECONOMIC CONTEXT - PAPER 1 Q3: NEWSPAPERS.pptxECONOMIC CONTEXT - PAPER 1 Q3: NEWSPAPERS.pptx
ECONOMIC CONTEXT - PAPER 1 Q3: NEWSPAPERS.pptxiammrhaywood
 
AMERICAN LANGUAGE HUB_Level2_Student'sBook_Answerkey.pdf
AMERICAN LANGUAGE HUB_Level2_Student'sBook_Answerkey.pdfAMERICAN LANGUAGE HUB_Level2_Student'sBook_Answerkey.pdf
AMERICAN LANGUAGE HUB_Level2_Student'sBook_Answerkey.pdfphamnguyenenglishnb
 
Keynote by Prof. Wurzer at Nordex about IP-design
Keynote by Prof. Wurzer at Nordex about IP-designKeynote by Prof. Wurzer at Nordex about IP-design
Keynote by Prof. Wurzer at Nordex about IP-designMIPLM
 
ENGLISH6-Q4-W3.pptxqurter our high choom
ENGLISH6-Q4-W3.pptxqurter our high choomENGLISH6-Q4-W3.pptxqurter our high choom
ENGLISH6-Q4-W3.pptxqurter our high choomnelietumpap1
 

Dernier (20)

LEFT_ON_C'N_ PRELIMS_EL_DORADO_2024.pptx
LEFT_ON_C'N_ PRELIMS_EL_DORADO_2024.pptxLEFT_ON_C'N_ PRELIMS_EL_DORADO_2024.pptx
LEFT_ON_C'N_ PRELIMS_EL_DORADO_2024.pptx
 
INTRODUCTION TO CATHOLIC CHRISTOLOGY.pptx
INTRODUCTION TO CATHOLIC CHRISTOLOGY.pptxINTRODUCTION TO CATHOLIC CHRISTOLOGY.pptx
INTRODUCTION TO CATHOLIC CHRISTOLOGY.pptx
 
Influencing policy (training slides from Fast Track Impact)
Influencing policy (training slides from Fast Track Impact)Influencing policy (training slides from Fast Track Impact)
Influencing policy (training slides from Fast Track Impact)
 
Like-prefer-love -hate+verb+ing & silent letters & citizenship text.pdf
Like-prefer-love -hate+verb+ing & silent letters & citizenship text.pdfLike-prefer-love -hate+verb+ing & silent letters & citizenship text.pdf
Like-prefer-love -hate+verb+ing & silent letters & citizenship text.pdf
 
Computed Fields and api Depends in the Odoo 17
Computed Fields and api Depends in the Odoo 17Computed Fields and api Depends in the Odoo 17
Computed Fields and api Depends in the Odoo 17
 
Proudly South Africa powerpoint Thorisha.pptx
Proudly South Africa powerpoint Thorisha.pptxProudly South Africa powerpoint Thorisha.pptx
Proudly South Africa powerpoint Thorisha.pptx
 
Procuring digital preservation CAN be quick and painless with our new dynamic...
Procuring digital preservation CAN be quick and painless with our new dynamic...Procuring digital preservation CAN be quick and painless with our new dynamic...
Procuring digital preservation CAN be quick and painless with our new dynamic...
 
Incoming and Outgoing Shipments in 3 STEPS Using Odoo 17
Incoming and Outgoing Shipments in 3 STEPS Using Odoo 17Incoming and Outgoing Shipments in 3 STEPS Using Odoo 17
Incoming and Outgoing Shipments in 3 STEPS Using Odoo 17
 
YOUVE_GOT_EMAIL_PRELIMS_EL_DORADO_2024.pptx
YOUVE_GOT_EMAIL_PRELIMS_EL_DORADO_2024.pptxYOUVE_GOT_EMAIL_PRELIMS_EL_DORADO_2024.pptx
YOUVE_GOT_EMAIL_PRELIMS_EL_DORADO_2024.pptx
 
TataKelola dan KamSiber Kecerdasan Buatan v022.pdf
TataKelola dan KamSiber Kecerdasan Buatan v022.pdfTataKelola dan KamSiber Kecerdasan Buatan v022.pdf
TataKelola dan KamSiber Kecerdasan Buatan v022.pdf
 
Full Stack Web Development Course for Beginners
Full Stack Web Development Course  for BeginnersFull Stack Web Development Course  for Beginners
Full Stack Web Development Course for Beginners
 
4.18.24 Movement Legacies, Reflection, and Review.pptx
4.18.24 Movement Legacies, Reflection, and Review.pptx4.18.24 Movement Legacies, Reflection, and Review.pptx
4.18.24 Movement Legacies, Reflection, and Review.pptx
 
Q4 English4 Week3 PPT Melcnmg-based.pptx
Q4 English4 Week3 PPT Melcnmg-based.pptxQ4 English4 Week3 PPT Melcnmg-based.pptx
Q4 English4 Week3 PPT Melcnmg-based.pptx
 
Choosing the Right CBSE School A Comprehensive Guide for Parents
Choosing the Right CBSE School A Comprehensive Guide for ParentsChoosing the Right CBSE School A Comprehensive Guide for Parents
Choosing the Right CBSE School A Comprehensive Guide for Parents
 
YOUVE GOT EMAIL_FINALS_EL_DORADO_2024.pptx
YOUVE GOT EMAIL_FINALS_EL_DORADO_2024.pptxYOUVE GOT EMAIL_FINALS_EL_DORADO_2024.pptx
YOUVE GOT EMAIL_FINALS_EL_DORADO_2024.pptx
 
Roles & Responsibilities in Pharmacovigilance
Roles & Responsibilities in PharmacovigilanceRoles & Responsibilities in Pharmacovigilance
Roles & Responsibilities in Pharmacovigilance
 
ECONOMIC CONTEXT - PAPER 1 Q3: NEWSPAPERS.pptx
ECONOMIC CONTEXT - PAPER 1 Q3: NEWSPAPERS.pptxECONOMIC CONTEXT - PAPER 1 Q3: NEWSPAPERS.pptx
ECONOMIC CONTEXT - PAPER 1 Q3: NEWSPAPERS.pptx
 
AMERICAN LANGUAGE HUB_Level2_Student'sBook_Answerkey.pdf
AMERICAN LANGUAGE HUB_Level2_Student'sBook_Answerkey.pdfAMERICAN LANGUAGE HUB_Level2_Student'sBook_Answerkey.pdf
AMERICAN LANGUAGE HUB_Level2_Student'sBook_Answerkey.pdf
 
Keynote by Prof. Wurzer at Nordex about IP-design
Keynote by Prof. Wurzer at Nordex about IP-designKeynote by Prof. Wurzer at Nordex about IP-design
Keynote by Prof. Wurzer at Nordex about IP-design
 
ENGLISH6-Q4-W3.pptxqurter our high choom
ENGLISH6-Q4-W3.pptxqurter our high choomENGLISH6-Q4-W3.pptxqurter our high choom
ENGLISH6-Q4-W3.pptxqurter our high choom
 

Gss herapura report

  • 1. INDEX LAYOUT pg. no 1. INTRODUCTION [SUB STATION] -1 2. BUS BARS -4 3. ISOLATORS -7 4. PROTECTIVE RELAYS -11 5. CIRCUIT BREAKERS -16 6. POWER TRANSFORMER -25 7. CURRENT TRANSFORMER -31 8. CAPACITIVE VOLTAGE TRANSFORMERS -33 9. TRASNFORMER OIL AND ITS TESTING -36 10. LIGHTENING ARRESTORS -38 11. CONTROL ROOM -41 12. EARTHING OF THE SYSTEM -44 13. POWER LINE CARRIER COMMUNICATION -46 14. CORONA -47 CONCLUSION REFERENCES
  • 2. INTRODUCTION Electric power is generated, transmitted and distributed in the form of alternating current. The electric power produced at the power stations is delivered to the consumers through a large network of transmission & distribution. The transmission network is inevitable long and high power lines are necessary to maintain a huge block of power from source of generation to the load centers to inter connected. Power house for increased reliability of supply greater. The assembly of apparatus used to change some characteristics (e.g. voltage, ac to dc, frequency, power factor etc.) of electric supply keeping the power constant is called a sub-station. Depending on the constructional feature, the high voltage sub-stations may be further subdivided: a) Out door substation. b) Indoor substation. c) Basement or Underground substation. 2 Dept. of Electrical Engg.
  • 3. fig 1 220 KV G.S.S. SANGANER 1) It is an outdoor type substation. 2) It is primary as well as distribution substation. 3) One and half breaker scheme is applied. 3 Dept. of Electrical Engg.
  • 4. The power mainly comes from HIRAPURA-1 and HIRAPURA-2 & KOTA THERMAL . Out going feeders 1) One feeder of 220kv to KTPS 2) One feeder of 220kv to Sakatpura. 3) One feeder of 220kv to KTPS2 4) One feeder of 220kv to Phulera 5) One feeder of 400kv to Merta 6) One feeder of 220kv to Sanganer At this substation following feeders are established. 1. TIE FEEDERS. 2. RADIAL FEEDERS. TIE FEEDERS: There are 220KV tie feeders as follows. 1.220 KV KOTA-JAIPUR 1st & 2nd 2. Inter state 220KV KOTA –DELHI 3. Tie from 220 KV Heerapura. 4. 220KV KTPS first & second. RADIAL FEEDERS 4 Dept. of Electrical Engg.
  • 5. 1. 220 KV JAIPUR –KOTA 1st & 2nd feeders 2. 132KV KOTA –BUNDI 1st 3. 132KV KOTA –SAWAI MADHOPUR 1st & 2nd 4.132 KV KOTA –SANGOD 5. 132 KV KOTA –MORAR BUS BARS Bus Bars are the common electrical component through which a large no. of feeders operating at same voltage have to be connected. If the bus bars are of rigid type (Aluminum types) the structure heights are low and minimum clearance is required. While in case of strain type of bus bars suitable ACSR conductors are strung / tensioned by tension insulator discs according to system voltages. In the widely used strain type bus bars stringing tension is about 500 - 900 kg depending upon the size of conductor used. Here proper clearance would be achieved only if require tension is achieved. Loose bus bars would effect the clearances when it swings while over tensioning may damage insulators. Clamps or even effect the supporting structures in low temperature conditions. The clamping should be proper, as loose clamp would spark under in full load condition damaging the bus bars itself. 5 Dept. of Electrical Engg.
  • 6. BUS BAR ARRANGEMENT MAY BE OF FOLLOWING TYPES WHICH ARE BEING ADOPTED BY R.R.V.P.N.L 1.) Single bus arrangement. 2.) Double bus bar arrangement. a) Main bus with transformer bus. b.) Main bus-I with Main bus-II. 3.) Double bus bar arrangement with auxiliary bus. DOUBLE BUS BAR CONTAINING MAIN BUS I WITH MAIN BUS II: 1. Each load may be fed from either bus. 2. The load circuits may be divided in two separate groups if needed from operational consideration. Two supplies from different sources can be put on each bus separately. 3. Either bus bar may be taken out from maintenance and cleaning of insulators. This arrangement has been quite frequently adopted where the loads and continuity of supply is necessary. In such a scheme a bus coupler breaker is mostly provided as it enables on load change over from one bus bar to other. The normal bus selection isolators cannot be used for breaking load currents. The arrangement does not permit breaker maintenance without causing stoppage of supply. DOUBLE BUS BAR ARRANGEMENTS CONTAINS MAIN BUS WITH AUXILIARY BUS: 6 Dept. of Electrical Engg.
  • 7. The double bus bar arrangement provides facility to change over to either bus to carry out maintenance on the other but provide no facility to carry over breaker maintenance. The main and transfer bus works the other way round .It provides facility for carrying out breaker maintenance but does not permit bus maintenance. Wherever maintenance is required on any breaker the circuit is changed over to the transfer bus and is controlled through bus coupler breaker. fig 2 7 Dept. of Electrical Engg.
  • 8. ISOLATORS Isolators which are also called disconnect switches or air break switches after the assembly as per drawings on the leveled structures the adjustment of connecting pipes, moving and fixed contacts is done so that all the three phase of the isolator close and open simultaneously and there is a full surface contact between moving and fixed contacts. Such switches are generally used on both sides of equipment in order that repairs and replacement of the equipment can be made without any danger. They should never be opened until the equipment in the same circuit has been turned off and should always be closed before the equipment is turned on. The adjustment of the tendon pipes leveling of post insulator, stop holts in the fixed contacts etc. is done for smooth operation of insulator. Following type of insulator are being used in R.S.E.B- a) Isolator without earth blades. b) Isolator with earth blade. 8 Dept. of Electrical Engg.
  • 9. c) Tendon isolator. INSULATORS The insulators for the overhead lines provide insulation to the power conductors from the ground so that currents from conductors do not flow to earth through supports. The insulators are connected to the cross arm of supporting structure and the power conductors passes through the clamp of the insulator. The insulators provide necessary insulation between line conductors and supports and thus prevent any leakage current from conductors to earth. In general, the insulators should have the following desirable properties: 1. High mechanical strength in order to withstand conductor load, wind load etc. 2. High electrical resistance of insulator material in order to avoid leakage currents to earth. 3. High relative permittivity of insulator material in order that dielectric strength is high. 4. The insulator material should be non porous, free from impurities and cracks otherwise the permitivity will be lowered. 5. High ratio of puncture strength to flash over. These insulators are generally made of glazed porcelain or toughened glass. Poly come type insulators [solid core] are also being supplied in place of hast insulators if available indigenously. The design of the insulator is such that the stress due to contraction and expansion in any part of the insulator does not lead to any defect. It 9 Dept. of Electrical Engg.
  • 10. is desirable not to allow porcelain to come in direct contact with a hard metal screw thread. TYPES OF INSULATORS: There are three types of insulators used for overhead lines: 1. Pin type- pin type insulator consists of a single or multiple shells adapted to be mounted on a spindle to be fixed to the cross arm of the supporting structure. When the upper most shell is wet due to rain the lower shells are dry and provide sufficient leakage resistance. These are used for transmission and distribution of electric power at voltage up to voltage 33KV. Beyond operating voltage of 33KV the pin type insulators thus become too bulky and hence uneconomical. Fig 3.1 2. Suspension type- suspension type insulators consist of a number of porcelain disc connected in series by metal links in the form of a string. 10 Dept. of Electrical Engg.
  • 11. Its working voltage is 66KV. Each disc is designed for low voltage for 11KV. Fig 3.2 3. Strain insulator- the strain insulators are exactly identical in shape with the suspension insulators. These strings are placed in the horizontal plane rather than the vertical plane. These insulators are used where line is subjected to greater tension. For low voltage lines (<11kV) shackle insulators are used as strain insulator. 11 Dept. of Electrical Engg.
  • 12. Fig 3.3 PROTECTIVE RELAYS A Protective relay is a device that detects the fault and initiates the operation of the circuit breaker to isolate the defective element from the rest of the system. The relays detect the abnormal condition in the electrical circuits by constantly measuring the electrical quantities i.e. voltage, current, frequency, phase angle which are different under normal and fault conditions. Having detected the fault, the relay operates to close the trip circuit of the breaker, which results in opening of the breaker and disconnection of the faulty circuit. Relay circuit connections can be divided in three parts: 1.) Primary winding of a C.T. that is connected in series with the line to be 12 Dept. of Electrical Engg.
  • 13. protected. 2.) Secondary winding of C.T. and the relay operating coil. 3.)Third part is the tripping circuit, which may be either a.c. or d.c. . It consists of a source of a supply, the trip coil of a circuit breaker and the relays stationary contacts. When a short circuit occurs at point F on the transmission line the current increases to enormous value. This results in a heavy current flow through the relay coil, causing the relay to operate by closing its contacts. This in turn closes the trip circuit of the breaker, making the C.B. open and isolating the family section from the rest of the system. In this way, the relay ensures the safety of the circuit equipment from damage and normal working of the healthy portion of the system. 13 Dept. of Electrical Engg.
  • 14. Fig 4 Basic qualities that a protective relay must possess are: 1.) Selectivity 2.) Speed 3.) Sensitivity 4.) Reliability 5.) Simplicity 6.) Economy DIFFERENTIAL RELAYS 14 Dept. of Electrical Engg.
  • 15. A differential relay is one that operates when the phasor difference of two or more similar electrical quantities exceeds a predetermined value. Thus the current differential relay is one that compares the current entering and current leaving the section. Under normal operating conditions, the two currents are equal but as soon as fault occurs, this condition is no longer applied. The difference between the incoming and outgoing currents is arranged to flow through the operating coil of the relay. If this differential current is equal to or greater than the pick up value, the relay will operate and open the C.B. to isolate the faulty section. BUCHHOLZ RELAY It is a gas-actuated relay installed in oil immersed transformers for protection against all kinds of faults. it is used to give an alarm in case of incipient (i.e. slow developing)faults in the transformer and to disconnect the transformer from the supply in the event of severe internal faults. it is usually installed in the pipe connecting the conservator to the main tank. It is a universal practice to use BUCHHOLZ relay on all such oil immersed transformers having ratings in excess of 750kVA. CONSTRUCTION It takes the form of a domed vessel pipe between the main tank and the 15 Dept. of Electrical Engg.
  • 16. conservator. The device has two elements. the upper element consists of a mercury type switch attached to a float. The lower element contains a mercury switch mounted on a hinged type flap located in the direct path of the flow of oil from the transformer to the conservator. the upper element closes an alarm circuit during incipient faults whereas the lower element is arranged to trip the circuit breaker in case of server internal faults. OPERATION The operation of Buchholz relay is as follows: (i)In case of incipient faults within the transformer, the heat due to fault causes the decomposition of some transformer oil in the main tank the products of decomposition contain more than 70% of hydrogen gas. the hydrogen gas being light tries to go into the conservator and in the process gets entrapped in the upper part of the relay chamber. when a pre determined amount of gas gets accumulated, it exerts sufficient pressure on the float to cause it tilt and close the contacts of the mercury switch attached tom it. This completes the alarm circuits to to sound an alarm. (ii)If a serious fault occurs in the transformer, enormous amount of gas is generated in the main tank. The oil in the main tank rushes to the conservator via the Buchholz relay and in doing so tilts the flap to close the contacts of the mercury switch. This completes the trip circuit to open the circuit breaker controlling the transformer. ADVANTAGES 16 Dept. of Electrical Engg.
  • 17. (i) It is the simplest form of transformer protection. (ii) It detects the incipient faults at a stage much earlier than possible with other forms of protection. DISADVANTAGES (i) It can only be used with oil immersed transformers equipped with conservator tanks. (ii) The device can detect only faults below oil level in the transformer. therefore separate protection is needed for connecting cables. CIRCUIT BREAKERS 17 Dept. of Electrical Engg.
  • 18. Thus circuit breakers are used for switching & protection of various parts of power system. Circuit breaker is a piece of equipment, which can 1) Make or break a circuit either manually or automatically under normal condition. 2) Break a circuit automatically under fault condition 3) Make a circuit either manually or by remote control under fault conditions. OPERATING PRINCIPLES A C.B. consists of fixed and moving contacts called electrodes. Under normal operating conditions, these contacts remain closed and will not open automatically until and unless the system becomes faulty. When a fault occurs on any part of the system, the trip coils of the circuit breaker get energised and the moving contacts are pulled apart, thereby opening the circuit. When the contacts of the C.B. are seperated under fault conditions, an arc is struck between them. The current is thus able to continue until the discharge ceaeses. The production of arc not only delays the current interruption process but it also generates enormous heat which may cause damage to the system or to the C.B. It is thus necessary to extinguish the arc within the shortest possible time so that the heat generated by it may not reach a dangerous value. 18 Dept. of Electrical Engg.
  • 19. ARC PHENOMENON When a short circuit occurs, a heavy current flows through the contacts of the C.B. before they are opened by the protective system. At the instant when the contacts begin to separate, the contact area decreases rapidly and large fault current causes increased current density and hence rise in temperature. The heat produced in the medium between contacts is sufficient to ionize the arc or vaporize and ionize the oil. The ionized air or vapour acts as conductor and an arc is set between the contacts. The potential difference between the contacts is quite small and is sufficient to maintain the arc. the arc provides a low resistance path and as a result the current in the circuit remains uninterrupted so long as the arc persists. During the arcing period the current flowing between the contacts depends on the arc resistance. The greater the arc resistance, the smaller the current that flows between the contacts. The arc resistance depends upon: (i) Degree of ionization. (ii) Length of arc. (iii) Cross section of arc. CLASSIFICATION OF THE CIRCUIT BREAKERS: 19 Dept. of Electrical Engg.
  • 20. There are several ways of classifying the circuit breakers. However, the most general way of classification is on the basis of medium used for arc extinction. The medium used for arc extinction is usually oil, air, sulphur hexafluoride (SF6) or vacuum. Accordingly, circuit breakers may be classified into: They are generally classified on the basis of the medium used for arc elimination (i) Oil circuit breakers, which employ some insulating oil for arc extinction. (ii) Air-blast circuit breakers in which high pressure air blast is used for extinguishing the arc. (iii) Sulphur hexa fluroide C.B. in which SF6 gas is used for arc extinction. (iv) Vacuum C.B. in which vacuum is used for arc extinction. SULPHUR HEXAFLOURIDE (SF6) CIRCUIT BREAKER In such breakers, sulphur hexaflouride (SF6) gas is used as the arc quenching medium. The sf6 is an electro-negative gas and has a strong tendency to absorb free electrons. The SF6 circuit breakers have been found to be very effective for high power and high voltage service. CONSTRUCTION 20 Dept. of Electrical Engg.
  • 21. The cylindrical large size steel tanks are mounted horizontally parallel to each other. Each tank consists of SF6 under pressure. The interruption is of multi break type & is placed along the axis of each tank. The interruption assembly is supported inside the tank by the vertical bushing, which are mounted near the end of each tank. Gas at high pressure is supplied to the interrupter from a gas reservoir. The bushing are also insulated with SF6 the conductor is in the from of copper tube supported at both end by porcelain shields. SF6 gas is supplied from the high pressure tanks. Shields are provided with gasket seals to eliminate leakage of gas from beginnings. 21 Dept. of Electrical Engg.
  • 22. 22 Dept. of Electrical Engg.
  • 23. Fig 5 WORKING In the closed position of the breaker the contacts remain surrounded by SF6 gas at a pressure of about 2.8 kg/sq cm. When the breaker operates, the moving contact is pulled apart and an arc is struck between the contacts. The movement of the moving contact is synchronised with the opening of a valve which permits SF6 gas at 14kg/sq cm pressure from the reservoir to the arc interruption chamber. the high pressure flow of SF6 rapidly absorbs the free electrons in the arc path to form immobile negative ions which are ineffective as charge carriers. The result is that the medium between the contacts quickly builds up high dielectric strength and causes the extinction of the arc. After the breaker operation the valve is closed by the action of a set of springs. 400 KV SF6 C.B. [RATINGS]: - Manufacture: BHEL Hyderabad. Type: HLR245/2503 B.S. Rated voltage: Normally 420 KV, maximum 440 KV. Rated frequency: 50 HZ. Rated power frequency: voltage: 520 KV Rated Impulse withstand voltage: Lightning: 1425KV Switching: 1050KV 23 Dept. of Electrical Engg.
  • 24. Normal current rating At 50 c ambient: 2240Amps At 40 c ambient: 2500Amps Short time current rating: 40 KA for 3 sec. Rated operating duty: 0 to 0.3 sec. c-0-3min-mb. Rated short circuit duration: 1 sec. BREAKING CAPACITY [BASED ON SPECIFIED DUTY CYCLE]: (a) Capacity at rated voltage: 29000MVA [440KV]. (b) Symmetry current: 40 KA. (c) Asymmetry current: 49 KA. Making capacity: 100KA [peak] Rated pressure of hydraulic operating (gauge): 250-350bar. Rated pressure of SF6 gas at degree: 7.5bars. Weight of complete breaker: 11700 Kg. Weight of SF6 gas: 76.5Kg. Rated trip coil voltage: 220 V. AC. Rated closing voltage: 220 V. DC. 24 Dept. of Electrical Engg.
  • 25. First poll to clear factor: 1.3 ADVANTAGES OF SF6 CIRCUIT BREAKER: 1. Due to the superior arc quenching property of SF6, such circuit breakers have very short arching time. 2. Since the dielectric strength of SF6 gas is 2 to 3 times that of air, such breakers can interrupt much larger currents. 3. The SF6 circuit breakers gives noiseless operation due to its closed gas circuit and no exhaust to the atmosphere unlike the air blast circuit breaker. 4. The closest gas enclosure keeps the interior dry so that there is no moisture problem. 5. There is on risk of fire in such breakers because SF6 gas is not inflammable. There are no carbon deposits so that tracking and insulation problems are eliminated. 6. The SF6 breakers have low maintenance cost, light foundation requirement and minimum auxiliary equipment. 7. Since SF6 breakers are totally enclosed and sealed from atmosphere they are particularly suitable where explosion hazard exists e.g., coal mines. 25 Dept. of Electrical Engg.
  • 26. DEMERITS OF SF6 CIRCUIT BREKER: 1. Sealing problems arise due to the type of the construction used. 2. The presence of moisture in the system is very dangerous to SF6 circuit breaker. 3. Arced Sf6 gas is poisonous & should not be let out. 4. The double pressure SF6 CB is cost liner due to complex gas system. 5. The internal parts should be cleaned thoroughly during periodic maintenance under clean dry environment. 6. Dust of Teflon & sulfide should be removed. 7. Special facilities are needed for transporting the gas. APPLICATIONS SF6 C.B. have been developed for voltages 115 KV to 230 KV, power ratings 10 MVA to 20 MVA and interrupting time less than 3 cycles. S.N I.E. MAK TYPE VOLTAGE CURREN STC SF6/HY O E T D 1 552A 3AT3 3AT3 420/520 2000A 40KA/S 7.5/350 2 552T DO DO DO DO DO DO 3 552B MG FAR2 DO 3150A DO 7/300 4 452T NGEF S2M420 420/610/1425 2000A DO 8/35 5 252A BHEL 3AT3 420/520/1050 DO DO 7.5/350 6 252B ABB EL(V) 420/1050 3150 40KA/3S 7/31.5 26 Dept. of Electrical Engg.
  • 27. POWER TRANSFORMER The transformer is a static apparatus, which receives power/energy at it, one circuit and transmits it to other circuit without changing the frequency. With this basic conception we can use the voltages at our desired level while utilizing the power. As, the voltage used to generate at modern power houses at 11 KV or so and afterwards we get it step up at a level of 33 KV, 66 KV, 132 V, 220 KV or 400 KV, 750 KV for transmission to minimize the distribution losses. Again we get it step down with the help of transformer to use at our wishes at 11 KV, 6.6 KV or even 415, 230 volts at our houses. BASIC PARTS OF TRANSFORMER The following are the inherent parts of a modern day transformer: 27 Dept. of Electrical Engg.
  • 28. 1. Primary and secondary coils (circuit) or windings. 2. Core 3. Main Tank 4. Conservator 5. Breather 6. Radiator 7. Buchholz relay 8. Explosive vent 9. Bushings (HT & LT) (Primary or secondary) 10. Cooling fans 11. Tap changer (on load and off load) 12. NGR (Neutral Grounding Resistance) to minimize the earth fault current Fig 6.1 DESCRIPTION OF PLANT: 28 Dept. of Electrical Engg.
  • 29. The three transformer are oil immersed with rating of 250 MVA & one with 315 MVA. However a synchronous loading of 100MVA at 0.8 power factor (lag) and 18 MVA 0.8 pf (lag) on the tertiary can also be loaded to 20MVA loading with 100MVA 0.8 pf on LV without exceeding the generated temperature rise. The transformer is also provided with a separate bank of radiation, fans, and associated control equipments. The control equipments are housed in a tank mounted miscalling. Fig 6.2 RATING DATAS. Type of cooling: ONAN / ONAF/ ODAF 29 Dept. of Electrical Engg.
  • 30. MVA HV: 189 / 252 / 315 IV: 189 / 252 / 315 LV: 63 / 84 / 105 VOLTS HV: 400 KV IV: 220 KV LV: 33 KV LINE AMPERES HV: 273 / 364 / 455 IV: 497 / 662 / 828 LV: 1104 / 1471 /1839 IMPEDANCE VOLTAGE HV to IV 12.65% on 315 MVA Base HV to LV 39.16 % on 315MVA Base IV to LV 26.66 % on 315 MVA Base NUMBER OF PHASES Three HV, LV, IV FREQUENCY IN Hz 50 Hz 30 Dept. of Electrical Engg.
  • 31. YEAR OF MANUFACTURE: 1985 Mass of Core & Windings: 1,32,000 kg Mass of Oil: 65,150 kg Total weight: 261,200 kg Oil in tank: 73,200 kg Oil in radiator: 8400 kg Oil in tap changer: 83,850 kg Transportation mass: 168,000 kg Unmaking height: 7760 mm Unmaking mass 18000 Kg Guaranteed maximum temperature rise of: Oil 45ºC Winding 50ºC COOLING FANS: Rating: 2000 m3 of air per minute. Type: 915 mm dial GEC (India) make. Numbers per transformer: two 31 Dept. of Electrical Engg.
  • 32. Fan motor: direct on line starts weather proof. Squirrel cage IM 1400 W 400/440 Volt 3-φ , 50 Hz 720 rpm PUMPS: Rating: 1818 liters per minute. Type: a landless A to 8c sentiment. Number of pump per transformer: one working, one standby. Pump motor: direct on line starts weather proof. Squirrel cage IM 32 Dept. of Electrical Engg.
  • 33. CURRENT TRANSFORMER These transformers are used with low range ammeter to measure currents in high voltage alternating current circuits where it is not practicable to connect instruments and meters directly to lines. In addition to insulating the instrument from the high voltage line, they step down the current in the known ratio. The current (or series) transformers has a primary coil of 1 or more turns of thick wires connected in series with the line whose current is to be measured. The secondary consist of a large number of turns of fine wire and is connected across the ammeter terminals (usually of 5 amp bracket should be removed or 1 amp range) 33 Dept. of Electrical Engg.
  • 34. Fig 7 POTENTIAL TRANSFORMER These transformers are extremely accurate ratio step down transformers and are used in conjunction with standard low range voltmeter (usually 150 volt) whose deflection when divided by voltage transformation ratio, gives the true voltage on the high voltage side. In general, they are of the shell type and do not differ much from the ordinary two winding transformer, except that their power rating is extremely small. Up to voltage of 5000 potential transformers are usually of dry type, between 5000 and 13800 volts, they may be either dry type or oil immersed type, although for voltage above 13800 they are oil type. Since their secondary windings are required to operate instruments or relays or pilot lights, their ratings are usually 42 to 100 watts. 34 Dept. of Electrical Engg.
  • 35. CAPACITIVE VOLTAGE TRANSFORMERS (CVT) Capacitive voltage transformers are special kind of power transformers using capacitors to step down the voltage. DESCRIPTION: 35 Dept. of Electrical Engg.
  • 36. The capacitive voltage transformer comprises of a capacitor divider with its associated electromagnetic unit. The divider provides an accurate proportioned voltage, while the magnetic unit transforms this voltage, in both magnitude and phase to convenient levels suitable for measuring, metering, protection etc. all WSI capacitor units has metallic bellows to compensate the volumetric expansion of oil inside. The porcelain in multi unit stack, all the potential points are electrically tied and suitably shielded to overcome the effect of corona RIV etc. Capacitive voltage transformers are available for system voltages of 33 KV to 420KV. Fig 8 APPLICATION: 1. Capacitive voltage transformers can be effectively as potential sources for measuring ,metering, protection, carrier communication and other vital functions of an electrical network. 36 Dept. of Electrical Engg.
  • 37. 2. CVT are constructed in single or multi unit porcelain housing with there associated magnetic units. For EHV systemcuts are always supplied in multi unit construction. 3. In case of EHV cuts the multi unit system has many advantage easy to transport and storing, convenience in handling. RATING OF CVT Voltage: 22/sqrt 3 KV Total o/p: 500MVA Operating voltage: 400/sqrt 3 max. Voltage factor: 1.5/30 sec. Test voltage: 630 KV for 1 min Impulse withstands voltage: 1.2/ 50 µs. 1425KV max. Frequency : 50Hz High frequency capacitance: 4400pF Primary capacitance: 4657pF Secondary capacitance: 80000 pF S no Ie Make Ratio Burden Class Sec cap 1 Bassi Wsi/cve/420 400 200,200, 3p,3p,0.5 80000pf /1425 100 2 Bassi 2 Wsi/cve/420 400 200,200, 3p,3p,0.5 80000pf /1425 100 3 Bus 1 Wsi/cve/420 400 200,200, 3p,3p,0.5 80000pf 37 Dept. of Electrical Engg.
  • 38. /1425 100 4 Bus 2 Wsi/cve/420 400 200,200, 3p,3p,0.5 80000pf /1425 100 TRANSFORMER OIL & ITS TESTING The prime function of oil is to convey the heat from the core and winding to the tank where it can be dissipated. Besides these, the oil provides additional insulation between primary and secondary windings. So, the oil must be completely free from dirt, moisture and other un-wanted solid matter. The oil used in the transformer is natural mineral oil and should undergo the following tests if required: BREAKDOWN VOLTAGE: The voltage at which the oil breaks down when subjected to an electric field. FLASH POINT: The temperature, at which the oil gives off so many vapors, when mixed with air forms an ignitable mixture and gives a momentary flash with small pilot flame. 38 Dept. of Electrical Engg.
  • 39. For checking above values, various tests are done. These are categorized as: 1. Physical test. 2. Chemical test. 3. Electrical test. The results must be close to standard results that are follows- S.N TYPE OF TEST STD. RESULTS 1. Density (gm/cubic cm.)at 27°C .85 to .89 2. Flash point >125°C 3. B.D.V Test K.V (rms.) >50 KV 4. Tan delta at 90°C < 20% 5. Water content (PPM.) 25(max.)above 145KV 6. Gas contents (PPM.) (a) Hydrogen 100 to150 (b) Methane 50 to 70 (c) Ethane 30 to 50 (d) Ethylene 100 to 150 (e) Acetylene 20 to 30 (f) Carbon dioxide 3000 to 3500 (h) Carbon mono-oxide 200 to300 39 Dept. of Electrical Engg.
  • 40. LIGHTENING ARRESTORS An electric discharge between cloud and earth, between cloud and the charge centers of the same cloud is known as lightening. The earthing screens and the ground wires can well protect the electrical system against direct lightening strokes but they fail to provide protection against travelling waves which may reach the terminal apparatus. The lightening arrestors or the surge diverters provide protections against such surges. THYRITE TYPE: Ground wire run over the tower provides an adequate protection against lighting and reduce the induced electrostatic or electromagnetic voltage but such a shield is inadequate to protect any traveling wave, which reaches the terminal of the electrical equipment, and such wave can cause the following damage. 40 Dept. of Electrical Engg.
  • 41. 1 the high peak of the surge may cause a flashover in the internal wiring thus it may spoil the insulation of the winding . 2 the steep wave front may cause internal flash over between their turns of transformer. 3 The stop wave front resulting into resonance and high voltage may cause internal or external flashover causing building up the oscillator is the electrical operation. Lightening arrestors are provided between the line and earth provided the protection against traveling wave surge the thyrite lightening arrestor are provided at GSS. This type of LA has a basic cell made of thirties, which is a particular type of clay, mixed with carborendum. Thirties has a particular property of being insulator one voltage At high voltage It will behave like a conducting material the electrical resistance of thyrite depends upon the voltage each time the voltage is made twice the resistance decrease in such a manner as to allow an increased current of 12.5 times the change in current is independent of rate of application voltage and its instantaneous value. The above law is followed by this material without any limit on the voltage increase and after the surge has passed the thyrite againretain its original property A standard cell is rated for 1KV and is formed into a disc, which is sprayed on both the sides of to give good contact with each disc. The dimensions of the discs are stacked i.e. 16 cm in diameter and 17.5 cm thick these discs are stacked one upon each other and they are further placed in to a porcelien container with a suitable arrangement of gap between them. 41 Dept. of Electrical Engg.
  • 42. These gaps serves as the purpose of preventing any current flow during normal operating voltage in case of any transients the gap are punctured. The Thyrite type arrestor will discharge several thousands ampere without the slightest tendency of flashover on the edges of most important of the advance is that there is absolutely no time lag in its performance. 400KV LIGHTNENIG ARRESTOR manufacture: English electric company no of phases: one rated voltage: 360 KV nominal discharge current (8×20µs) 10KA high current impulse(4×110 µs ) 100KA long duration rating(200 µs) 500KA Sno Ie Make Type Current Voltage 1 Bassi1 Wsi Cpl 10KA 360KV 2 bassi2 Elpro Alugard2 10KA 360KV 3 ILT1 Elpro Alugard2 10KA 360KV 4 ILT2 Elpro Alugard2 10KA 360KVh 5 ILT3 WSI CDV303 10KA 398KV 6 ILT4 WSI CDV03 10KA 398KV 42 Dept. of Electrical Engg.
  • 43. CONTROL PANEL The diagram made on the control panel is known as mimic diagram. COLOUR CODING * 33KV GREEN * 132 KV BLACK * 220KV BROWN * 440 VOLTS VOILET/INDIGO * 110 VOLTS ORANGE  REACTOR It is used to lower the over excited capacitor. Capacitor bank is connected in shunt over the reactor. Capacitors main purpose is to boost up the voltage. so when we want to lower the voltage we use reactors. it is also use to stop the sudden change. the commonly used reactor is NGR(Neutral ground reactor). 43 Dept. of Electrical Engg.
  • 44.  CIRCUIT BREAKER There is a one and half breaker scheme i.e. 3 breakers for 2 buses used in 400 KV G.S.S.  BUS COUPLERS It is used to equalize the load on both Bus bars.  DISTURBANCE RECORDER It records the distance & fault on graph with voltage w.r.t time.  EVENT LOGGER it monitors as well as provides the details as a printed material. These details may contain the sequence of operation, switching time, closing time etc.  ON LOAD TAP CHANGER (OLTC) In this method a number of tappings are provided on the secondary of the transformer. The voltage drop in the line is supplied by changing the secondary emf of the transformer through the adjustment of its number of turns by using transition resistor which are placed in between each tapping. 44 Dept. of Electrical Engg.
  • 45. In supply system, tap changing has to be performed on load so that here is no interruption to supply. By using transition resister therefore shut down is not required. Fig 11  NO LOAD TAP CHANGER (NLTC) in this we change the tap manually for which we have to shut down the transformer. When the load increases the voltage across the primary drops but the secondary voltage can be kept at the previous value by placing the movable arm on to a higher stud. Whenever a tapping is to be changed in this type of transformer, the load is kept off and hence the name off load tap-changing transformer.  SYNCHRONOSCOPE A synchronoscope is used to determine the correct instance of closing the switch with connect the new supply to bus bar the correct instance of synchronizing is indicated when bus bar and incoming voltage 45 Dept. of Electrical Engg.
  • 46. * are equal in magnitude * are equal in phase * have the same frequency the phase sequence is same EARTHING OF THE SYSTEM: The provision of an earthling system for an electric system is necessary by the following reason. 1 In the event of over voltage on the system due to lightening discharge or other system fault. These parts of equipment, which are normally dead, as for as voltage, are concerned do not attain dangerously high potential. 2 In a three phase, circuit the neutral of the system is earthed in order to stabilize the potential of circuit with respect to earth. The resistance of earthling system is depending on 1 Shape and material of earth electrode used. 2 Depth in the soil 3 Specific resistance of soil surrounding in the neighborhood of system electrodes. PROCEDURE OF EARTHING: Technical consideration the current carrying path should have enough capacity to deal with more faults current. The resistance of earth and current path should be low enough to prevent voltage rise between earth and neutral. The earth electrode must be driven into the ground to a sufficient depth to as to obtain lower value of earth resistance. To sufficient lowered earth resistance a number of electrodes are inserted in the earth to a depth they are connected together to form a mesh. The resistance of earth should be for the mesh in generally inserted in the earth at 0.5m 46 Dept. of Electrical Engg.
  • 47. depths the several point of mesh then connected to earth electrode or ground conduction. The earth electrode is metal plate copper is used for earth plate. Neutral Earthing: Neutral earthing of power transformer all power system operates with grounded neutral. Grounding of neutral offers several advantages the neutral point of generator transformer is connected to earth directly or through a reactance in some cases the neutral points is earthed through an adjustable reactor of reactance matched with the line. The earthling is one of the most important feature of system design for switchgear protection neutral grounding is important because: 1 The earth fault protection is based on the method of neutral earthling. 2 The neutral earthling is associated switchgear. 3 The neutral earthling is provided for the purpose of protection arcing grounds unbalanced voltages with respect to protection from lightening and for improvement of system. 47 Dept. of Electrical Engg.
  • 48. POWER LINE CARRIER COMMUNICATION As electronics plays a vital role in the industrial growth, communication is also a backbone of any power station, communication between various generating and receiving station is very essential for proper operation of power system. This is more so in case of a large interconnected system where a control load dispatch station has to coordinate the working of various units to see that the system is maintained in the optimum working condition, power line communication is the most economical and reliable method of communication for medium and long distance in a power network. PLCC system in Rajasthan: - 1 HEERAPURA: JAIPUR, AJMER, BYAWAR, BHILWARA, PALI, JODHPUR 2 HISSAR: KHETRI, HEERAPURA, KOTA, RAPP 3 HEERAPURA: KOTS, JSP, RPS, GSD 4 BHILWARA: RPS 5 PALI: FALANA 6 HEERAPURA: ALWAR, BHARATPUR 7 NEEMUCH: DEBARI 8 DEBARI: SIROHI 48 Dept. of Electrical Engg.
  • 49. 9 DEBARI: ZAWAR MINES 10 HEERAPURA: SIKAR, RATANGARH, BIKANER 11 HANUM, ANGARH: HISSAR, SHRIGANGANAGAR 12 HEERAPURA: BADHERPUB CORONA EFFECT When an alternating potential difference is applied across two conductors whose spacing is as large as compared to their diameters, there is no apparent change in the condition of atmospheric air surrounding the wires if the applied voltage is low. However when the applied voltage exceeds a certain value called critical disruptive voltage, the conductors are surrounded by a faint violet glow called corona. The phenomenon of corona is accompanied by a hissing sound, production of ozone, power loss and radio interference. The higher the voltage is raised, the larger and higher the luminous envelope becomes, and greater are the sound, the power loss and the radio noise. If the applied voltage is increased to breakdown value, a flash over will occur between the conductors due to the breakdown of air insulation. The phenomenon of violet glow, hissing noise and production of ozone gas in an overhead transmission line is known as corona. 49 Dept. of Electrical Engg.
  • 50. If the conductors are polished and smooth, the corona glow will be uniform throughout the length of the conductors, otherwise the rough points will appear brighter. The positive wire has uniform glow about it, while the negative conductors has spotty glow. FACTORS AFFECTING CORONA The phenomenon of corona is affected by the physical state of the atmosphere as well as by the conditions of the line. The following are the factors on which corona depends: 1. Atmosphere. In the stormy weather, the number of ions is more than normal and as such corona occurs at much less voltage as compared with fair weather. 2. Conductor size. The rough and irregular surface will give rise to more corona because unevenness of the surface decreases the value of breakdown voltage. 3. Spacing between conductors. Larger space between conductors reduces the electro-static stresses at the conductor surface, thus avoiding corona formation. 4. Line voltage. If the line voltage is low, there is no chance in the condition of air surrounding the conductors and hence no corona is formed. 50 Dept. of Electrical Engg.
  • 51. ADVANTAGES AND DISADVANTAGES OF CORONA Corona has many advantages and disadvantages. In the correct design of a high voltage overhead line, a balance should be struck between the advantages and disadvantages. Advantages 1. Due to corona formation, the air surrounding the conductor becomes conducting and hence virtual diameter of the conductor is increased. The increased diameter reduces the electro-static stresses between the conductors. 2. Corona reduces the effect of the transients produced by surges. Disadvantages 1. Corona is accompanied by a loss of energy. This affects the transmission efficiency of the line. 2. Ozone is produced by corona and may cause corrosion of the conductor due to chemical action. 3. The current drawn by the line due to corona is non-sinusoidal and hence non-sinusoidal voltage drop occurs in the line. This may cause inductive interference with neighboring communication lines. 51 Dept. of Electrical Engg.
  • 52. CONCLUSION A technician needs to have not just theoretical but practical as well and so every student is supposed to undergo a practical training session after III year where I have imbibed the knowledge about transmission, distribution, generation and maintenance with economical issues related to it. During our 30 days training session we were acquainted with the repairing of the transformers and also the testing of oil which is a major component of transformer. At last I would like to say that practical training taken at 220KV GSS has broadened my knowledge and has widened my thinking as a professional. 52 Dept. of Electrical Engg.
  • 53. REFERENCES: Principles of Power System-by V.K.MEHTA Electrical Power System-by C.L.WADHWA REPORT BY- Kapil Kumar SKIT,JAIPUR 53 Dept. of Electrical Engg.