OPTIONS FOR MANAGING SAFETY WITH ELDERLY SWITCHGEAR 
 
Richard Blakeley, R.P.S. Switchgear,
SWITCHGEAR – WHAT DOES IT DO? 
 
MAKE AND BREAK NORMAL LOAD CURRENTS 
 
OPERATE CONTINUOUSLY UP TO NORMAL RATINGS 
 
WITHSTAND THE PASSAGE OF THROUGH-FAULT CURRENT FOR SUFFICIENT TIME TO ALLOW THE DOWNSTREAM PROTECTION TO OPERATE 
 
SAFELY SWITCH ON TO FAULT, HANDLING THE ENERGIES INVOLVED 
 
SAFELY INTERRUPT FAULT CURRENT AND THEREBY REMOVING THE FAULTED EQUIPMENT FROM THE SOURCE OF ELECTRICAL SUPPLY 
 
ACT AS A POINT OF ISOLATION AND EARTHING TO ENABLE WORK TO BE DONE SAFELY
Reyrolle, Type ‘AR’ 33kv, 800A Switchgear, 
 
PRIMARY CONTACTS -- FIXED AND MOVING. 
 
ARCING CONTACTS -- FIXED AND MOVING. 
 
CLOSING MECHANISM -- (Stored Energy, MO or Manual), 
 
OPENING MECHANISM -- STORED ENERGY 
 
PRIMARY INSULATION SYSTEM, 
 
ENCLOSURE, 
 
MEANS OF ISOLATION FROM THE SYSTEM. 
CIRCUIT BREAKER DESIGN -- TRADITIONAL COMPONENTS
Risk Factors with Elderly Switchgear
AGING SWITCHGEAR – RISKS & ISSUES 
 
Lack of knowledge/training 
 
Network changes resulting in the switchgear being overstressed 
 
Not being modified as per manufacturer’s advice/updates 
 
Not being maintained or operated properly 
 
Dependent-manual switchgear 
 
Spares & Technical Support not being available 
 
Age related failure, 
 
Switchgear is normally ‘quiescent’ 
 
Continuous assessment not justifiable 
 
True condition difficult to determine
ELDERLY SWITCHGEAR – TRUE CONDITION?? 
“In on-site evaluation tests carried out by Reyrolle on aging oil switchgear worldwide, it was found that on more than 50% of oil switchgear thought to be in good condition, the circuit breakers had faults or were operating outside of their design envelope and in some cases would have failed to operate correctly under system fault conditions”
SWITCHGEAR FAULT CLEARANCE – KEY FUNCTION FOR SAFETY
ISSUES WITH ELDERLY SWITCHGEAR 
 
ELDERLY OIL SWITCHGEAR PRESENTS INCREASING RISK , (Consequences of a flashover can be severe) 
 
CONDITION ASSESSMENT OF DISTRIBUTION SWITCHGEAR IS DIFFICULT 
 
SPARES ARE NOT AVAILABLE FOR MOST ELDERLY SWITCHGEAR, 
 
NOT UPGRADED TO LATEST REVISION, 
 
NOT COMPLIANT WITH MODERN SAFETY STANDARDS, 
 
SWITCHING PERFORMANCE OF OIL CB’s NOT GOOD AT LOWER FAULT LEVELS,
Internal Arc/Arc Flash Faults
ARC FLASH FAULTS 
HOW OFTEN DO THEY HAPPEN? 
“EVERY DAY, 1 TO 2 ARC FLASH RELATED FATALITIES OCCUR ACROSS NORTH AMERICA”
INTERNAL ARC FAULTS – CAUSES 
 
Badly Designed Switchgear 
 
Incorrect Installation 
 
Insulation Failure 
▫ 
Contamination 
▫ 
Age Deterioration 
▫ 
Overstressing 
▫ 
Human Intervention 
▫ 
Vermin Ingress 
 
Lack of/Inadequate Maintenance 
 
Human Error or Misuse 
 
Over-stressing
ENERGY RELEASED BY ARC FAULT 
PRESSURE RISE 
VISUAL & ACCOUSTIC PHENOMENA 
TEMPERATURE RISE 
EFFECTS OF FAULT ARC 
CONSEQUENCES FOR PLANT 
MECHANICAL STRESSING OF ENCLOSURES 
THERMAL STRESSING, MELTING, VAPOURISATION 
CONSEQUENCES FOR PERSONNEL 
SHOCK WAVE, FLYING DEBRIS, OPENING PANELS 
EJECTION OF FLAMES & HOT GASES, METAL VAPOUR 
EFFECTS AND CONSEQUENCES OF AN ARC FAULT IN HIGH VOLTAGE SWITCHGEAR
THE CONSEQUENCES OF AN INTERNAL ARC FAULT IN HV SWITCHGEAR
THE CONSEQUENCES OF AN INTERNAL ARC FAULT IN HV OIL SWITCHGEAR
ARC-FAULT IN NON-VENTED SWITCHGEAR 
SOME INTERESTING DATA FROM RPS TESTING OF ELDERLY SWITCHGEAR 
 
Current starts: 0 
 
Pressure starts: 0.4 ms 
 
Pressure peak: 4.7 ms 
 
Pressure duration: 6.6 ms 
 
Current peak: <10 ms 
Data & Test evidence supports that the covers will be flying off in 5 – 10 ms 
Maximum pressure on switchgear panels/doors can be 1-2 bar
Safety Solutions & Improvements for Existing Switchboards
 
TO IMPROVE SAFETY FOR OPERATORS AND STAFF, 
 
TO REDUCE MAINTENANCE AND LIFETIME OWNERSHIP COSTS, 
 
TO IMPROVE THE RELIABILITY AND THE SERVICE-ABILITY OF THE CIRCUIT BREAKERS. 
 
TO INCREASE THE RATING OF THE SWITCHBOARD, (X/R, Normal & Short cct) 
 
TO FURTHER EXTEND THE REMAINING LIFE OF THE ASSET BY REPLACING KEY COMPONENTS AS REQUIRED, (BUSHINGS, CT’S, VT’S ETC) 
 
TO MODERNISE THE CONTROL & PROTECTION EQUIPMENT. 
 
TO ACHIEVE THE ABOVE WITH MINIMUM SYSTEM DISRUPTION. 
KEY STRATEGIC OBJECTIVES FOR LIFETIME SUPPORT OF AGING SWITCHGEAR ASSETS.
SUMMARY OF SWITCHGEAR SOLUTIONS, 
 
SAFETY RETROFITS, 
 
CIRCUIT BREAKER RETROFIT, 
 
ARC DOOR + END SHIELD RETROFIT, 
 
3-SIDED ‘CONTAINMENT’ 
 
‘REMOTE OPERATION’ 
 
UPGRADES & LIFE EXTENSION, 
 
CURRENT TRANSFORMER REPLACEMENT, 
 
CABLE BOX RETROFIT, 
 
REPLACEMENT OF ORIFICE BUSHINGS, 
 
REPLACEMENT OF VT’s 
 
PROTECTION & CONTROL UPGRADE,
Circuit Breaker Retrofit
CIRCUIT BREAKER RETROFIT 
Existing LMT panel 
Oil Circuit Breaker out 
Vacuum Circuit Breaker in 
(Brand new unit) 
OCB TO VCB REPLACEMENT 
 
ABOUT A DAY PER CIRCUIT 
 
MINIMAL DISRUPTION 
 
SIGNIFICANT SAFETY IMPROVEMENT 
>6,000 units in service world-wide
RETROFIT CIRCUIT BREAKER FOR REYROLLE ‘LM’ SWITCHGEAR 
 
SIMPLE MODULAR DESIGN 
 
PROVEN CAST EPOXY RESIN INSULATION SYSTEM 
 
CAPABLE OF MORE THAN 10,000 LOAD CURRENT OPERATIONS 
 
PROVEN LONG LIFE, LOW MAINTENANCE MECHANISM 
 
LESS THAN 30% OF THE PARTS OF LMT 
 
CAPABLE OF OVER 50 SHORT-CIRCUIT OPERATIONS AT 25KA AT 12KV 
 
EXCELLENT SWITCHING PERFORMANCE, (25ms opening, >45% dc component)
 
DIRECT REPLACEMENT FOR LM RANGE, 
 
SIGNIFICANTLY IMPROVES SAFETY IN THE SUBSTATION, 
 
LESS THAN 1 DAY PER CIRCUIT, (Fast Implementation, minimum disruption) 
 
SHORT CIRCUIT WITHSTAND RATING OF THE SWITCHBOARD CAN BE INCREASED UP TO 31.5kA , 
 
REMOVES OIL HANDLING, 
 
REPLACES CB WITH LONG LIFE, LOW MAINTENANCE UNIT, 
 
LOW COST W.R.T. COMPLETE SWITCHBOARD REPLACEMENT, (<30%) 
 
ALLOWS SUBSTATION ASSETS TO BE RENEWED & REVALUED COST EFFECTIVELY, 
RPS LMT SWITCHGEAR RETROFIT -- SUMMARY
FURTHER SAFETY FOR EXISTING SUBSTATIONS 
“REPLACEMENT OF THE O.C.B. WITH OUR VACUUM UNIT IS A SIGNIFICANT IMPROVEMENT IN OPERATOR SAFETY” 
BUT THERE ARE OTHER IMPORTANT SAFETY FEATURES THAT ARE AVAILABLE TO SIGNIFICANTLY IMPROVE SAFETY AND BRING THE EXISTING SWITCHBOARD TOWARDS 62271-200 FOR INTERNAL ARC SAFETY”
FURTHER SAFETY FOR EXISTING SUBSTATIONS 
SWITCHGEAR SAFETY UPGRADES: 
 
Arc-proof doors + end shields 
 
3 sided containment 
 
Electrical operation ‘not-in-front’
EXISTING SWITCHGEAR & INTERNAL ARC SAFETY 
 
EXISTING SWITCHBOARDS HAVE NO INTERNAL ARC WITHSTAND OR PRESSURE RELIEF DESIGN, 
 
HUMAN PRESENCE IN FRONT OF THE LIVE SWITCHBOARD IS UNAVOIDABLE 
 
SAFETY FOR OPERATORS, STAFF AND VISITORS IN FRONT OF THE EXISTING SWITCHBOARD IS ACHIEVABLE, 
 
RACKING THROUGH A CLOSED ARC-PROOF DOOR IS ESSENTIAL. 
TYPICAL EXISTING LMT SWITCHBOARDS
 
WHY HAVE AN ARC-PROOF DOOR? 
 
WHY HAVE RACKING THROUGH AN ARC-PROOF DOOR? 
TWO IMPORTANT QUESTIONS:- 
EXISTING SWITCHGEAR & INTERNAL ARC SAFETY
WHY HAVE AN ARC-PROOF DOOR? 
LMT TEST ARRANGEMENT 
 
STANDARD LMT PANEL 
 
FAULT IN BREAKER COMPARTMENT 
 
25KA, 1S DURATION 
 
OCB WOULD BE MUCH WORSE
WHY HAVE AN ARC-PROOF DOOR? 
...from a different angle
WHY HAVE RACKING THROUGH AN ARC-PROOF DOOR?
BEHIND CLOSED DOOR RACKING 
RETROFIT ARC-PROOF DOOR – OPERATOR SAFETY 
Behind Closed Door Racking
RETROFIT END SHIELDS – OPERATOR SAFETY 
 
PREVENTS BURN-THROUGH, 
 
PROVIDES LATERAL SAFETY 
 
SIMPLE INSTALLATION 
 
NO BUS OUTAGE REQUIRED 
 
END PANEL CCT OUTAGE ONLY
RETROFIT OF , 25kA, 1s ARC WITHSTAND FRONT DOOR & END SHIELDS FOR OPERATOR SAFETY` 
 
LMT SWITCHBOARDS RETROFITTED WITH ARC DOORS & END SHIELDS. 
END SHIELD.
RETROFIT OF ARC-WITHSTAND FRONT DOOR 
Brunei 
Australia 
South Africa 
United Kingdom
ARC DOORS REDUCE THE HRC – NFPA 70E 
Activity 
Existing switchgear 
With arc-doors & end shields 
Circuit breaker operation 
4 
0/1 
Circuit breaker racking 
4 
0/1 
Instrument cubicle work/inspection 
4 
0/1 
Maintenance work in front of switchboard 
4 
0/1 
Relay inspection/testing 
4 
0/1 
General presence in the switch-room in front of the switchboard 
4 
0/1
3-SIDED CONTAINMENT SYSTEM
3-SIDED CONTAINMENT SYSTEM
TEST ARRANGEMENT 
 
LMT PANELS FITTED WITH ARC WITHSTAND KIT 
 
FAULT IN BREAKER COMPARTMENT 
 
25KA, 1S DURATION 
 
CERTIFIED TO IEC 62271-200 
 
3-SIDED SAFETY, 2.8M ROOF 
ARC DOOR TEST TO LATEST STANDARD
‘REMOTE’ OPERATION 
Option 1 – Remote Control Panel 
• 
Dedicated control for each panel 
• 
One set of trip & close operators with key to determine panel 
Option 2 – Remote Control Pendant 
• 
Lead length: 10m, 15m or request 
• 
Plugs into panel to be operated
Other Retrofit & Upgrade Solutions
RETROFIT OF CT CHAMBER & CABLE BOX 
PITCH-FILLED CABLE BOX REPLACED WITH AIR CABLE BOX. 
ENCAPSULATED CAST RESIN CT’s REPLACED WITH SLIP-OVER TYPE
RETROFIT OF CT CHAMBER 
 
SLIP-OVER CT RETROFIT KIT FOR LMT 
 
ASSEMBLED, JIGGED AND POURED IN THE FACTORY 
 
COMPLETE INSTALLATION
 
REPLACES THE CABLE BOX & CABLE BOX BUSHINGS ONLY, -- OR 
 
ALSO REPLACES THE EXISTING CAST RESIN CT’S WITH SLIP-OVER TYPE, 
 
INCLUDES NEW CT ORIFICE BUSHINGS AND CT BUSHINGS, 
 
IMPROVED FUTURE PROTECTION FLEXIBILITY, 
 
LIVE LINE INDICATION & PHASING AVAILABLE, 
 
CONVERTS EXISTING CAST PITCH-FILLED BOX TO AIR TERMINATION, 
 
EASY TO IMPLEMENT, -- PER CCT OUTAGE ONLY, 
CABLE BOX REPLACEMENT 
400A/800A FEEDER PANEL CONVERTED TO AIR BOX. 
400A/800A FEEDER PANEL BEING CONVERTED TO AIR BOX.
VT REPLACEMENT – MOVING PORTION 
 
RPS manufacture & supply a direct replacement truck for the existing Reyrolle LMT VT’s 
 
Fast replacement – no bus-bar outage required 
 
Isolating and Engaging the VT through the Instrument cubicle is available for the new VT arrangement 
Replacement VT trucks for LMT
PROTECTION & CONTROL UPGRADE 
 
Replaces the existing RMI “top-box” 
 
Complete new RMI modernisation 
 
Equipped, wired & tested in the factory 
 
Customised to specific customer requirements 
 
Simplifies site work
LMT SWITCHBOARD FITTED WITH SAFETY, PROTECTION & CONTROL IMPROVEMENTS
LMT SWITCHBOARD FITTED WITH RPS IMPROVEMENTS 
 
RETROFIT VCB’S, 
 
RETROFIT ARC DOORS 
 
PROTECTION & CONTROL UPGRADE, 
 
RETROFIT RMI CUBICLES, 
 
CT & VT UPGRADES, 
 
SWITCHBOARD FAULT RATING INCREASED FROM 13.1kA UP TO 31.5kA. 
“Upgraded to modern standards for 40% of the cost of switchboard replacement”
SUMMARY – ELDERLY SWITCHGEAR RETROFIT OPTIONS 
SAFETY UPGRADES: 
 
OCB to VCB upgrade 
 
Arc-proof doors + end shields 
 
3 sided containment 
 
Electrical operation ‘not-in-front’ 
ADDITIONAL RETROFITS: 
 
RMI cubicles 
 
Busbars 
 
VT’s – bus and circuit 
 
CT’s 
 
Cable boxes 
Existing aged switchgear can be made safer & upgraded

Contenu connexe

Tendances

Practical Power System Protection for Engineers and Technicians
Practical Power System Protection for Engineers and TechniciansPractical Power System Protection for Engineers and Technicians
Practical Power System Protection for Engineers and TechniciansLiving Online
 
Using High Resistance Grounding to Mitigate Arc Flash Hazards
Using High Resistance Grounding to Mitigate Arc Flash HazardsUsing High Resistance Grounding to Mitigate Arc Flash Hazards
Using High Resistance Grounding to Mitigate Arc Flash Hazardsmichaeljmack
 
Siemens ngg-molded-case-circuit-breaker-product presentation
Siemens ngg-molded-case-circuit-breaker-product presentationSiemens ngg-molded-case-circuit-breaker-product presentation
Siemens ngg-molded-case-circuit-breaker-product presentationHazem El-Henawy
 
digital testing of high voltage circuit breaker
digital testing of high voltage circuit breakerdigital testing of high voltage circuit breaker
digital testing of high voltage circuit breakerRenuka Verma
 
17th Edition Part 701
17th  Edition Part 70117th  Edition Part 701
17th Edition Part 701Paul Holden
 
Pd Maintenance
Pd MaintenancePd Maintenance
Pd Maintenancedwessin
 
Testing of c.b.(hk & hr) nihal
Testing of c.b.(hk & hr) nihalTesting of c.b.(hk & hr) nihal
Testing of c.b.(hk & hr) nihalNihal Shiroya
 
Selective Coordination
Selective CoordinationSelective Coordination
Selective Coordinationmichaeljmack
 
17th Edition Part 4
17th  Edition  Part 417th  Edition  Part 4
17th Edition Part 4Paul Holden
 
Dalroad Norslo - Electric Equipment - Contactor training level 1 - LS Industr...
Dalroad Norslo - Electric Equipment - Contactor training level 1 - LS Industr...Dalroad Norslo - Electric Equipment - Contactor training level 1 - LS Industr...
Dalroad Norslo - Electric Equipment - Contactor training level 1 - LS Industr...Dalroad Norslo
 
Protection and switch gear
Protection and switch gearProtection and switch gear
Protection and switch gearswathi_gren11
 
Guide to Surge Protection Devices
Guide to Surge Protection DevicesGuide to Surge Protection Devices
Guide to Surge Protection DevicesJason Koffler
 
Presentation o surge protection devices
Presentation o surge protection devicesPresentation o surge protection devices
Presentation o surge protection devicesRAM PRAKASH PATEL
 
Electrical Lessons learned
Electrical Lessons learnedElectrical Lessons learned
Electrical Lessons learnedmichaeljmack
 
Electrical safety ppt(1)
Electrical safety ppt(1)Electrical safety ppt(1)
Electrical safety ppt(1)Er Ramgarhia
 

Tendances (20)

Practical Power System Protection for Engineers and Technicians
Practical Power System Protection for Engineers and TechniciansPractical Power System Protection for Engineers and Technicians
Practical Power System Protection for Engineers and Technicians
 
Surge supressor
Surge supressorSurge supressor
Surge supressor
 
Using High Resistance Grounding to Mitigate Arc Flash Hazards
Using High Resistance Grounding to Mitigate Arc Flash HazardsUsing High Resistance Grounding to Mitigate Arc Flash Hazards
Using High Resistance Grounding to Mitigate Arc Flash Hazards
 
Siemens ngg-molded-case-circuit-breaker-product presentation
Siemens ngg-molded-case-circuit-breaker-product presentationSiemens ngg-molded-case-circuit-breaker-product presentation
Siemens ngg-molded-case-circuit-breaker-product presentation
 
Vcb ppt.
Vcb ppt.Vcb ppt.
Vcb ppt.
 
digital testing of high voltage circuit breaker
digital testing of high voltage circuit breakerdigital testing of high voltage circuit breaker
digital testing of high voltage circuit breaker
 
17th Edition Part 701
17th  Edition Part 70117th  Edition Part 701
17th Edition Part 701
 
Pd Maintenance
Pd MaintenancePd Maintenance
Pd Maintenance
 
Testing of c.b.(hk & hr) nihal
Testing of c.b.(hk & hr) nihalTesting of c.b.(hk & hr) nihal
Testing of c.b.(hk & hr) nihal
 
Breakers v. fuses[1]
Breakers v. fuses[1]Breakers v. fuses[1]
Breakers v. fuses[1]
 
Selective Coordination
Selective CoordinationSelective Coordination
Selective Coordination
 
17th Edition Part 4
17th  Edition  Part 417th  Edition  Part 4
17th Edition Part 4
 
Fuses and mcb
Fuses and mcbFuses and mcb
Fuses and mcb
 
Dalroad Norslo - Electric Equipment - Contactor training level 1 - LS Industr...
Dalroad Norslo - Electric Equipment - Contactor training level 1 - LS Industr...Dalroad Norslo - Electric Equipment - Contactor training level 1 - LS Industr...
Dalroad Norslo - Electric Equipment - Contactor training level 1 - LS Industr...
 
Protection and switch gear
Protection and switch gearProtection and switch gear
Protection and switch gear
 
Guide to Surge Protection Devices
Guide to Surge Protection DevicesGuide to Surge Protection Devices
Guide to Surge Protection Devices
 
Presentation o surge protection devices
Presentation o surge protection devicesPresentation o surge protection devices
Presentation o surge protection devices
 
Surge Protection
Surge ProtectionSurge Protection
Surge Protection
 
Electrical Lessons learned
Electrical Lessons learnedElectrical Lessons learned
Electrical Lessons learned
 
Electrical safety ppt(1)
Electrical safety ppt(1)Electrical safety ppt(1)
Electrical safety ppt(1)
 

En vedette

Circuits breakers for industrial automation and process controling
Circuits breakers for industrial automation and process controlingCircuits breakers for industrial automation and process controling
Circuits breakers for industrial automation and process controlingfairautomation
 
Komsas soniyah 2015
Komsas soniyah 2015Komsas soniyah 2015
Komsas soniyah 2015lolita riyah
 
Bebelusii nu cauta scurtaturi si nu tin cont de gura lumii
Bebelusii nu cauta scurtaturi si nu tin cont de gura lumiiBebelusii nu cauta scurtaturi si nu tin cont de gura lumii
Bebelusii nu cauta scurtaturi si nu tin cont de gura lumiiFani Rarinca
 
Exploration in the House 2015: NSW Seamless Geology Project: Progress to date...
Exploration in the House 2015: NSW Seamless Geology Project: Progress to date...Exploration in the House 2015: NSW Seamless Geology Project: Progress to date...
Exploration in the House 2015: NSW Seamless Geology Project: Progress to date...NSW Environment and Planning
 
Exploration in the House 2015: Geology Survey of NSW Overview and highlights ...
Exploration in the House 2015: Geology Survey of NSW Overview and highlights ...Exploration in the House 2015: Geology Survey of NSW Overview and highlights ...
Exploration in the House 2015: Geology Survey of NSW Overview and highlights ...NSW Environment and Planning
 
Calculations with personal
Calculations with personalCalculations with personal
Calculations with personalssnet2
 
Exploration in the House 2015: The Importance of the Junior Sector for minera...
Exploration in the House 2015: The Importance of the Junior Sector for minera...Exploration in the House 2015: The Importance of the Junior Sector for minera...
Exploration in the House 2015: The Importance of the Junior Sector for minera...NSW Environment and Planning
 
Tony Linnane NSW Trade & Investment Mine Safety - new WHS laws for mining
Tony Linnane NSW Trade & Investment Mine Safety - new WHS laws for miningTony Linnane NSW Trade & Investment Mine Safety - new WHS laws for mining
Tony Linnane NSW Trade & Investment Mine Safety - new WHS laws for miningNSW Environment and Planning
 
Quest learning institute outbound activities
Quest learning institute outbound activitiesQuest learning institute outbound activities
Quest learning institute outbound activitiesQuest Adventure Group
 
Aychel jimenez manga
Aychel jimenez mangaAychel jimenez manga
Aychel jimenez mangaaychellmanga
 
Intelligent industrial wireless technology cliff rogers
Intelligent industrial wireless technology   cliff rogersIntelligent industrial wireless technology   cliff rogers
Intelligent industrial wireless technology cliff rogersNSW Environment and Planning
 

En vedette (20)

Circuits breakers for industrial automation and process controling
Circuits breakers for industrial automation and process controlingCircuits breakers for industrial automation and process controling
Circuits breakers for industrial automation and process controling
 
Komsas soniyah 2015
Komsas soniyah 2015Komsas soniyah 2015
Komsas soniyah 2015
 
Mark Parcell - History of mining legislation nsw
Mark Parcell - History of mining legislation nswMark Parcell - History of mining legislation nsw
Mark Parcell - History of mining legislation nsw
 
Bebelusii nu cauta scurtaturi si nu tin cont de gura lumii
Bebelusii nu cauta scurtaturi si nu tin cont de gura lumiiBebelusii nu cauta scurtaturi si nu tin cont de gura lumii
Bebelusii nu cauta scurtaturi si nu tin cont de gura lumii
 
Dr David Sweeting - Update on arcing hazards
Dr David Sweeting - Update on arcing hazardsDr David Sweeting - Update on arcing hazards
Dr David Sweeting - Update on arcing hazards
 
Exploration in the House 2015: NSW Seamless Geology Project: Progress to date...
Exploration in the House 2015: NSW Seamless Geology Project: Progress to date...Exploration in the House 2015: NSW Seamless Geology Project: Progress to date...
Exploration in the House 2015: NSW Seamless Geology Project: Progress to date...
 
Exploration in the House 2015: Geology Survey of NSW Overview and highlights ...
Exploration in the House 2015: Geology Survey of NSW Overview and highlights ...Exploration in the House 2015: Geology Survey of NSW Overview and highlights ...
Exploration in the House 2015: Geology Survey of NSW Overview and highlights ...
 
Calculations with personal
Calculations with personalCalculations with personal
Calculations with personal
 
Sport
SportSport
Sport
 
ιός
ιόςιός
ιός
 
The Centre
The CentreThe Centre
The Centre
 
Exploration in the House 2015: The Importance of the Junior Sector for minera...
Exploration in the House 2015: The Importance of the Junior Sector for minera...Exploration in the House 2015: The Importance of the Junior Sector for minera...
Exploration in the House 2015: The Importance of the Junior Sector for minera...
 
Tony Linnane NSW Trade & Investment Mine Safety - new WHS laws for mining
Tony Linnane NSW Trade & Investment Mine Safety - new WHS laws for miningTony Linnane NSW Trade & Investment Mine Safety - new WHS laws for mining
Tony Linnane NSW Trade & Investment Mine Safety - new WHS laws for mining
 
Quest learning institute outbound activities
Quest learning institute outbound activitiesQuest learning institute outbound activities
Quest learning institute outbound activities
 
Aychel jimenez manga
Aychel jimenez mangaAychel jimenez manga
Aychel jimenez manga
 
Intelligent industrial wireless technology cliff rogers
Intelligent industrial wireless technology   cliff rogersIntelligent industrial wireless technology   cliff rogers
Intelligent industrial wireless technology cliff rogers
 
Rtca proximity detection gavin white
Rtca proximity detection   gavin whiteRtca proximity detection   gavin white
Rtca proximity detection gavin white
 
Implementing proximity detection
Implementing proximity detectionImplementing proximity detection
Implementing proximity detection
 
Human factors additional paper Ronny Lardner
Human factors additional paper  Ronny LardnerHuman factors additional paper  Ronny Lardner
Human factors additional paper Ronny Lardner
 
CV_KAhmed
CV_KAhmedCV_KAhmed
CV_KAhmed
 

Similaire à Richard Blakeley - Options for managing safety with elderly switchgear

2.components in a substation breaker
2.components in a substation   breaker2.components in a substation   breaker
2.components in a substation breakerayyadurai SHANMUGAM
 
Selective Coordination "The Rest of the Story"
Selective Coordination "The Rest of the Story"Selective Coordination "The Rest of the Story"
Selective Coordination "The Rest of the Story"michaeljmack
 
SCR Power Controllers Out-Perform Contactors and Solid State Relays
SCR Power Controllers Out-Perform Contactors and Solid State RelaysSCR Power Controllers Out-Perform Contactors and Solid State Relays
SCR Power Controllers Out-Perform Contactors and Solid State RelaysAdvanced Energy
 
C.S.P.D.C.L.AMBIKAPUR (TOWN)
C.S.P.D.C.L.AMBIKAPUR (TOWN)C.S.P.D.C.L.AMBIKAPUR (TOWN)
C.S.P.D.C.L.AMBIKAPUR (TOWN)saurabhVEC
 
220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance220 KV Substation Operation & Maintenance
220 KV Substation Operation & MaintenanceHimansu Pradhan
 
Relay and Indications by sgm for protection engineers.pdf
Relay and Indications by sgm for protection engineers.pdfRelay and Indications by sgm for protection engineers.pdf
Relay and Indications by sgm for protection engineers.pdfEngrSyedGhulamMustaf
 
2 CIRCUIT BKR MAINT PRESENTATION 11kv VCB.ppt
2 CIRCUIT BKR MAINT PRESENTATION 11kv VCB.ppt2 CIRCUIT BKR MAINT PRESENTATION 11kv VCB.ppt
2 CIRCUIT BKR MAINT PRESENTATION 11kv VCB.pptManishPandya29
 
Analysis of example_capacitor_bank_switching_solution_and_recommendations_for...
Analysis of example_capacitor_bank_switching_solution_and_recommendations_for...Analysis of example_capacitor_bank_switching_solution_and_recommendations_for...
Analysis of example_capacitor_bank_switching_solution_and_recommendations_for...f95346
 
Littelfuse Fuseology Basics
Littelfuse Fuseology BasicsLittelfuse Fuseology Basics
Littelfuse Fuseology BasicsLittelfuse
 
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKERDIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKERRitesh Kumawat
 

Similaire à Richard Blakeley - Options for managing safety with elderly switchgear (20)

2.components in a substation breaker
2.components in a substation   breaker2.components in a substation   breaker
2.components in a substation breaker
 
Breaker Operation & Maintenance
Breaker Operation & MaintenanceBreaker Operation & Maintenance
Breaker Operation & Maintenance
 
Selective Coordination "The Rest of the Story"
Selective Coordination "The Rest of the Story"Selective Coordination "The Rest of the Story"
Selective Coordination "The Rest of the Story"
 
05 - Limit Switch - Fuji Electric
05 - Limit Switch - Fuji Electric05 - Limit Switch - Fuji Electric
05 - Limit Switch - Fuji Electric
 
Epcos 5
Epcos 5Epcos 5
Epcos 5
 
SCR Power Controllers Out-Perform Contactors and Solid State Relays
SCR Power Controllers Out-Perform Contactors and Solid State RelaysSCR Power Controllers Out-Perform Contactors and Solid State Relays
SCR Power Controllers Out-Perform Contactors and Solid State Relays
 
Training Adobe
Training AdobeTraining Adobe
Training Adobe
 
C.S.P.D.C.L.AMBIKAPUR (TOWN)
C.S.P.D.C.L.AMBIKAPUR (TOWN)C.S.P.D.C.L.AMBIKAPUR (TOWN)
C.S.P.D.C.L.AMBIKAPUR (TOWN)
 
220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance
 
Relay and Indications by sgm for protection engineers.pdf
Relay and Indications by sgm for protection engineers.pdfRelay and Indications by sgm for protection engineers.pdf
Relay and Indications by sgm for protection engineers.pdf
 
RPS-SF6LBS-PKE
RPS-SF6LBS-PKERPS-SF6LBS-PKE
RPS-SF6LBS-PKE
 
DC Drive Selection Guide
DC Drive Selection GuideDC Drive Selection Guide
DC Drive Selection Guide
 
2 CIRCUIT BKR MAINT PRESENTATION 11kv VCB.ppt
2 CIRCUIT BKR MAINT PRESENTATION 11kv VCB.ppt2 CIRCUIT BKR MAINT PRESENTATION 11kv VCB.ppt
2 CIRCUIT BKR MAINT PRESENTATION 11kv VCB.ppt
 
Standing type outdoor full sf6 gas insualted ring main unit
Standing type outdoor full sf6 gas insualted ring main unitStanding type outdoor full sf6 gas insualted ring main unit
Standing type outdoor full sf6 gas insualted ring main unit
 
Standing type GIS RMU
Standing type GIS RMUStanding type GIS RMU
Standing type GIS RMU
 
ABB Price List of Capacitors 008
ABB Price List of Capacitors 008ABB Price List of Capacitors 008
ABB Price List of Capacitors 008
 
Analysis of example_capacitor_bank_switching_solution_and_recommendations_for...
Analysis of example_capacitor_bank_switching_solution_and_recommendations_for...Analysis of example_capacitor_bank_switching_solution_and_recommendations_for...
Analysis of example_capacitor_bank_switching_solution_and_recommendations_for...
 
Littelfuse Fuseology Basics
Littelfuse Fuseology BasicsLittelfuse Fuseology Basics
Littelfuse Fuseology Basics
 
220 kv gss renwal ppt
220 kv gss renwal ppt220 kv gss renwal ppt
220 kv gss renwal ppt
 
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKERDIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
 

Plus de NSW Environment and Planning

06. how the regulator communicates with the industry
06. how the regulator communicates with the industry06. how the regulator communicates with the industry
06. how the regulator communicates with the industryNSW Environment and Planning
 
Fires on mobile plant refuelling (Ross Stutchbury)
Fires on mobile plant refuelling (Ross Stutchbury)Fires on mobile plant refuelling (Ross Stutchbury)
Fires on mobile plant refuelling (Ross Stutchbury)NSW Environment and Planning
 
Mobile plant rollovers and collisions (Bill McGlynn)
Mobile plant rollovers and collisions (Bill McGlynn)Mobile plant rollovers and collisions (Bill McGlynn)
Mobile plant rollovers and collisions (Bill McGlynn)NSW Environment and Planning
 
Electrical performance presentation (Craig Harris)
Electrical performance presentation (Craig Harris)Electrical performance presentation (Craig Harris)
Electrical performance presentation (Craig Harris)NSW Environment and Planning
 
Where do I stand for fire protection on mobile and transportable equipment an...
Where do I stand for fire protection on mobile and transportable equipment an...Where do I stand for fire protection on mobile and transportable equipment an...
Where do I stand for fire protection on mobile and transportable equipment an...NSW Environment and Planning
 

Plus de NSW Environment and Planning (20)

12 Small mines report card 2020
12 Small mines report card 202012 Small mines report card 2020
12 Small mines report card 2020
 
11 occupational hygiene monitoring of dust
11 occupational hygiene monitoring of dust11 occupational hygiene monitoring of dust
11 occupational hygiene monitoring of dust
 
09 learning from disasters
09 learning from disasters09 learning from disasters
09 learning from disasters
 
13 explosives awareness
13 explosives awareness13 explosives awareness
13 explosives awareness
 
10 incident reporting to the regulator 2020
10 incident reporting to the regulator 202010 incident reporting to the regulator 2020
10 incident reporting to the regulator 2020
 
08 dust safety and health surveillance
08 dust safety and health surveillance08 dust safety and health surveillance
08 dust safety and health surveillance
 
07 feedback and consultation
07 feedback and consultation07 feedback and consultation
07 feedback and consultation
 
06. how the regulator communicates with the industry
06. how the regulator communicates with the industry06. how the regulator communicates with the industry
06. how the regulator communicates with the industry
 
05 reviewing your SMS
05 reviewing your SMS05 reviewing your SMS
05 reviewing your SMS
 
04. slinging and lifting equipment
04. slinging and lifting equipment04. slinging and lifting equipment
04. slinging and lifting equipment
 
Control focused inspection tools (Mark Smith)
Control focused inspection tools (Mark Smith)Control focused inspection tools (Mark Smith)
Control focused inspection tools (Mark Smith)
 
Central assessment unit CAU(Steve Bentham)
Central assessment unit CAU(Steve Bentham)Central assessment unit CAU(Steve Bentham)
Central assessment unit CAU(Steve Bentham)
 
Autonomous mining equipment (Owen Barry)
Autonomous mining equipment (Owen Barry)Autonomous mining equipment (Owen Barry)
Autonomous mining equipment (Owen Barry)
 
Fires on mobile plant refuelling (Ross Stutchbury)
Fires on mobile plant refuelling (Ross Stutchbury)Fires on mobile plant refuelling (Ross Stutchbury)
Fires on mobile plant refuelling (Ross Stutchbury)
 
Mobile plant rollovers and collisions (Bill McGlynn)
Mobile plant rollovers and collisions (Bill McGlynn)Mobile plant rollovers and collisions (Bill McGlynn)
Mobile plant rollovers and collisions (Bill McGlynn)
 
Metropolitan colliery gas (Dave Gordon)
Metropolitan colliery gas (Dave Gordon)Metropolitan colliery gas (Dave Gordon)
Metropolitan colliery gas (Dave Gordon)
 
Airborne dust update (Mark Shepherd)
Airborne dust update (Mark Shepherd)Airborne dust update (Mark Shepherd)
Airborne dust update (Mark Shepherd)
 
Emergency planning (Matt U'Brien)
Emergency planning (Matt U'Brien)Emergency planning (Matt U'Brien)
Emergency planning (Matt U'Brien)
 
Electrical performance presentation (Craig Harris)
Electrical performance presentation (Craig Harris)Electrical performance presentation (Craig Harris)
Electrical performance presentation (Craig Harris)
 
Where do I stand for fire protection on mobile and transportable equipment an...
Where do I stand for fire protection on mobile and transportable equipment an...Where do I stand for fire protection on mobile and transportable equipment an...
Where do I stand for fire protection on mobile and transportable equipment an...
 

Dernier

Russian Escorts in Abu Dhabi 0508644382 Abu Dhabi Escorts
Russian Escorts in Abu Dhabi 0508644382 Abu Dhabi EscortsRussian Escorts in Abu Dhabi 0508644382 Abu Dhabi Escorts
Russian Escorts in Abu Dhabi 0508644382 Abu Dhabi EscortsMonica Sydney
 
sponsor for poor old age person food.pdf
sponsor for poor old age person food.pdfsponsor for poor old age person food.pdf
sponsor for poor old age person food.pdfSERUDS INDIA
 
Top profile Call Girls In Morena [ 7014168258 ] Call Me For Genuine Models We...
Top profile Call Girls In Morena [ 7014168258 ] Call Me For Genuine Models We...Top profile Call Girls In Morena [ 7014168258 ] Call Me For Genuine Models We...
Top profile Call Girls In Morena [ 7014168258 ] Call Me For Genuine Models We...gajnagarg
 
Election 2024 Presiding Duty Keypoints_01.pdf
Election 2024 Presiding Duty Keypoints_01.pdfElection 2024 Presiding Duty Keypoints_01.pdf
Election 2024 Presiding Duty Keypoints_01.pdfSamirsinh Parmar
 
Just Call VIP Call Girls In Bangalore Kr Puram ☎️ 6378878445 Independent Fem...
Just Call VIP Call Girls In  Bangalore Kr Puram ☎️ 6378878445 Independent Fem...Just Call VIP Call Girls In  Bangalore Kr Puram ☎️ 6378878445 Independent Fem...
Just Call VIP Call Girls In Bangalore Kr Puram ☎️ 6378878445 Independent Fem...HyderabadDolls
 
Vasai Call Girls In 07506202331, Nalasopara Call Girls In Mumbai
Vasai Call Girls In 07506202331, Nalasopara Call Girls In MumbaiVasai Call Girls In 07506202331, Nalasopara Call Girls In Mumbai
Vasai Call Girls In 07506202331, Nalasopara Call Girls In MumbaiPriya Reddy
 
Call Girl Service in Korba 9332606886 High Profile Call Girls You Can Get ...
Call Girl Service in Korba   9332606886  High Profile Call Girls You Can Get ...Call Girl Service in Korba   9332606886  High Profile Call Girls You Can Get ...
Call Girl Service in Korba 9332606886 High Profile Call Girls You Can Get ...kumargunjan9515
 
The NAP process & South-South peer learning
The NAP process & South-South peer learningThe NAP process & South-South peer learning
The NAP process & South-South peer learningNAP Global Network
 
Cheap Call Girls In Hyderabad Phone No 📞 9352988975 📞 Elite Escort Service Av...
Cheap Call Girls In Hyderabad Phone No 📞 9352988975 📞 Elite Escort Service Av...Cheap Call Girls In Hyderabad Phone No 📞 9352988975 📞 Elite Escort Service Av...
Cheap Call Girls In Hyderabad Phone No 📞 9352988975 📞 Elite Escort Service Av...kajalverma014
 
Contributi dei parlamentari del PD - Contributi L. 3/2019
Contributi dei parlamentari del PD - Contributi L. 3/2019Contributi dei parlamentari del PD - Contributi L. 3/2019
Contributi dei parlamentari del PD - Contributi L. 3/2019Partito democratico
 
Unique Value Prop slide deck________.pdf
Unique Value Prop slide deck________.pdfUnique Value Prop slide deck________.pdf
Unique Value Prop slide deck________.pdfScottMeyers35
 
9867746289 Independent Call Girls in Mumbai Airport 24/7 - Mumbai Escorts
9867746289 Independent Call Girls in Mumbai Airport 24/7 - Mumbai Escorts9867746289 Independent Call Girls in Mumbai Airport 24/7 - Mumbai Escorts
9867746289 Independent Call Girls in Mumbai Airport 24/7 - Mumbai EscortsPooja Nehwal
 
Vivek @ Cheap Call Girls In Kamla Nagar | Book 8448380779 Extreme Call Girls ...
Vivek @ Cheap Call Girls In Kamla Nagar | Book 8448380779 Extreme Call Girls ...Vivek @ Cheap Call Girls In Kamla Nagar | Book 8448380779 Extreme Call Girls ...
Vivek @ Cheap Call Girls In Kamla Nagar | Book 8448380779 Extreme Call Girls ...Delhi Call girls
 
Top profile Call Girls In Haldia [ 7014168258 ] Call Me For Genuine Models We...
Top profile Call Girls In Haldia [ 7014168258 ] Call Me For Genuine Models We...Top profile Call Girls In Haldia [ 7014168258 ] Call Me For Genuine Models We...
Top profile Call Girls In Haldia [ 7014168258 ] Call Me For Genuine Models We...gajnagarg
 
Call Girls Mehsana / 8250092165 Genuine Call girls with real Photos and Number
Call Girls Mehsana / 8250092165 Genuine Call girls with real Photos and NumberCall Girls Mehsana / 8250092165 Genuine Call girls with real Photos and Number
Call Girls Mehsana / 8250092165 Genuine Call girls with real Photos and NumberSareena Khatun
 
Genuine Call Girls in Salem 9332606886 HOT & SEXY Models beautiful and charm...
Genuine Call Girls in Salem  9332606886 HOT & SEXY Models beautiful and charm...Genuine Call Girls in Salem  9332606886 HOT & SEXY Models beautiful and charm...
Genuine Call Girls in Salem 9332606886 HOT & SEXY Models beautiful and charm...Sareena Khatun
 
2024: The FAR, Federal Acquisition Regulations, Part 32
2024: The FAR, Federal Acquisition Regulations, Part 322024: The FAR, Federal Acquisition Regulations, Part 32
2024: The FAR, Federal Acquisition Regulations, Part 32JSchaus & Associates
 
2024 UN Civil Society Conference in Support of the Summit of the Future.
2024 UN Civil Society Conference in Support of the Summit of the Future.2024 UN Civil Society Conference in Support of the Summit of the Future.
2024 UN Civil Society Conference in Support of the Summit of the Future.Christina Parmionova
 

Dernier (20)

Russian Escorts in Abu Dhabi 0508644382 Abu Dhabi Escorts
Russian Escorts in Abu Dhabi 0508644382 Abu Dhabi EscortsRussian Escorts in Abu Dhabi 0508644382 Abu Dhabi Escorts
Russian Escorts in Abu Dhabi 0508644382 Abu Dhabi Escorts
 
Panchayath circular KLC -Panchayath raj act s 169, 218
Panchayath circular KLC -Panchayath raj act s 169, 218Panchayath circular KLC -Panchayath raj act s 169, 218
Panchayath circular KLC -Panchayath raj act s 169, 218
 
sponsor for poor old age person food.pdf
sponsor for poor old age person food.pdfsponsor for poor old age person food.pdf
sponsor for poor old age person food.pdf
 
Top profile Call Girls In Morena [ 7014168258 ] Call Me For Genuine Models We...
Top profile Call Girls In Morena [ 7014168258 ] Call Me For Genuine Models We...Top profile Call Girls In Morena [ 7014168258 ] Call Me For Genuine Models We...
Top profile Call Girls In Morena [ 7014168258 ] Call Me For Genuine Models We...
 
Election 2024 Presiding Duty Keypoints_01.pdf
Election 2024 Presiding Duty Keypoints_01.pdfElection 2024 Presiding Duty Keypoints_01.pdf
Election 2024 Presiding Duty Keypoints_01.pdf
 
Just Call VIP Call Girls In Bangalore Kr Puram ☎️ 6378878445 Independent Fem...
Just Call VIP Call Girls In  Bangalore Kr Puram ☎️ 6378878445 Independent Fem...Just Call VIP Call Girls In  Bangalore Kr Puram ☎️ 6378878445 Independent Fem...
Just Call VIP Call Girls In Bangalore Kr Puram ☎️ 6378878445 Independent Fem...
 
Vasai Call Girls In 07506202331, Nalasopara Call Girls In Mumbai
Vasai Call Girls In 07506202331, Nalasopara Call Girls In MumbaiVasai Call Girls In 07506202331, Nalasopara Call Girls In Mumbai
Vasai Call Girls In 07506202331, Nalasopara Call Girls In Mumbai
 
Call Girl Service in Korba 9332606886 High Profile Call Girls You Can Get ...
Call Girl Service in Korba   9332606886  High Profile Call Girls You Can Get ...Call Girl Service in Korba   9332606886  High Profile Call Girls You Can Get ...
Call Girl Service in Korba 9332606886 High Profile Call Girls You Can Get ...
 
The NAP process & South-South peer learning
The NAP process & South-South peer learningThe NAP process & South-South peer learning
The NAP process & South-South peer learning
 
Cheap Call Girls In Hyderabad Phone No 📞 9352988975 📞 Elite Escort Service Av...
Cheap Call Girls In Hyderabad Phone No 📞 9352988975 📞 Elite Escort Service Av...Cheap Call Girls In Hyderabad Phone No 📞 9352988975 📞 Elite Escort Service Av...
Cheap Call Girls In Hyderabad Phone No 📞 9352988975 📞 Elite Escort Service Av...
 
Contributi dei parlamentari del PD - Contributi L. 3/2019
Contributi dei parlamentari del PD - Contributi L. 3/2019Contributi dei parlamentari del PD - Contributi L. 3/2019
Contributi dei parlamentari del PD - Contributi L. 3/2019
 
Unique Value Prop slide deck________.pdf
Unique Value Prop slide deck________.pdfUnique Value Prop slide deck________.pdf
Unique Value Prop slide deck________.pdf
 
9867746289 Independent Call Girls in Mumbai Airport 24/7 - Mumbai Escorts
9867746289 Independent Call Girls in Mumbai Airport 24/7 - Mumbai Escorts9867746289 Independent Call Girls in Mumbai Airport 24/7 - Mumbai Escorts
9867746289 Independent Call Girls in Mumbai Airport 24/7 - Mumbai Escorts
 
Vivek @ Cheap Call Girls In Kamla Nagar | Book 8448380779 Extreme Call Girls ...
Vivek @ Cheap Call Girls In Kamla Nagar | Book 8448380779 Extreme Call Girls ...Vivek @ Cheap Call Girls In Kamla Nagar | Book 8448380779 Extreme Call Girls ...
Vivek @ Cheap Call Girls In Kamla Nagar | Book 8448380779 Extreme Call Girls ...
 
Top profile Call Girls In Haldia [ 7014168258 ] Call Me For Genuine Models We...
Top profile Call Girls In Haldia [ 7014168258 ] Call Me For Genuine Models We...Top profile Call Girls In Haldia [ 7014168258 ] Call Me For Genuine Models We...
Top profile Call Girls In Haldia [ 7014168258 ] Call Me For Genuine Models We...
 
Call Girls Mehsana / 8250092165 Genuine Call girls with real Photos and Number
Call Girls Mehsana / 8250092165 Genuine Call girls with real Photos and NumberCall Girls Mehsana / 8250092165 Genuine Call girls with real Photos and Number
Call Girls Mehsana / 8250092165 Genuine Call girls with real Photos and Number
 
Genuine Call Girls in Salem 9332606886 HOT & SEXY Models beautiful and charm...
Genuine Call Girls in Salem  9332606886 HOT & SEXY Models beautiful and charm...Genuine Call Girls in Salem  9332606886 HOT & SEXY Models beautiful and charm...
Genuine Call Girls in Salem 9332606886 HOT & SEXY Models beautiful and charm...
 
2024: The FAR, Federal Acquisition Regulations, Part 32
2024: The FAR, Federal Acquisition Regulations, Part 322024: The FAR, Federal Acquisition Regulations, Part 32
2024: The FAR, Federal Acquisition Regulations, Part 32
 
AHMR volume 10 number 1 January-April 2024
AHMR volume 10 number 1 January-April 2024AHMR volume 10 number 1 January-April 2024
AHMR volume 10 number 1 January-April 2024
 
2024 UN Civil Society Conference in Support of the Summit of the Future.
2024 UN Civil Society Conference in Support of the Summit of the Future.2024 UN Civil Society Conference in Support of the Summit of the Future.
2024 UN Civil Society Conference in Support of the Summit of the Future.
 

Richard Blakeley - Options for managing safety with elderly switchgear

  • 1. OPTIONS FOR MANAGING SAFETY WITH ELDERLY SWITCHGEAR  Richard Blakeley, R.P.S. Switchgear,
  • 2. SWITCHGEAR – WHAT DOES IT DO?  MAKE AND BREAK NORMAL LOAD CURRENTS  OPERATE CONTINUOUSLY UP TO NORMAL RATINGS  WITHSTAND THE PASSAGE OF THROUGH-FAULT CURRENT FOR SUFFICIENT TIME TO ALLOW THE DOWNSTREAM PROTECTION TO OPERATE  SAFELY SWITCH ON TO FAULT, HANDLING THE ENERGIES INVOLVED  SAFELY INTERRUPT FAULT CURRENT AND THEREBY REMOVING THE FAULTED EQUIPMENT FROM THE SOURCE OF ELECTRICAL SUPPLY  ACT AS A POINT OF ISOLATION AND EARTHING TO ENABLE WORK TO BE DONE SAFELY
  • 3. Reyrolle, Type ‘AR’ 33kv, 800A Switchgear,  PRIMARY CONTACTS -- FIXED AND MOVING.  ARCING CONTACTS -- FIXED AND MOVING.  CLOSING MECHANISM -- (Stored Energy, MO or Manual),  OPENING MECHANISM -- STORED ENERGY  PRIMARY INSULATION SYSTEM,  ENCLOSURE,  MEANS OF ISOLATION FROM THE SYSTEM. CIRCUIT BREAKER DESIGN -- TRADITIONAL COMPONENTS
  • 4. Risk Factors with Elderly Switchgear
  • 5. AGING SWITCHGEAR – RISKS & ISSUES  Lack of knowledge/training  Network changes resulting in the switchgear being overstressed  Not being modified as per manufacturer’s advice/updates  Not being maintained or operated properly  Dependent-manual switchgear  Spares & Technical Support not being available  Age related failure,  Switchgear is normally ‘quiescent’  Continuous assessment not justifiable  True condition difficult to determine
  • 6. ELDERLY SWITCHGEAR – TRUE CONDITION?? “In on-site evaluation tests carried out by Reyrolle on aging oil switchgear worldwide, it was found that on more than 50% of oil switchgear thought to be in good condition, the circuit breakers had faults or were operating outside of their design envelope and in some cases would have failed to operate correctly under system fault conditions”
  • 7. SWITCHGEAR FAULT CLEARANCE – KEY FUNCTION FOR SAFETY
  • 8. ISSUES WITH ELDERLY SWITCHGEAR  ELDERLY OIL SWITCHGEAR PRESENTS INCREASING RISK , (Consequences of a flashover can be severe)  CONDITION ASSESSMENT OF DISTRIBUTION SWITCHGEAR IS DIFFICULT  SPARES ARE NOT AVAILABLE FOR MOST ELDERLY SWITCHGEAR,  NOT UPGRADED TO LATEST REVISION,  NOT COMPLIANT WITH MODERN SAFETY STANDARDS,  SWITCHING PERFORMANCE OF OIL CB’s NOT GOOD AT LOWER FAULT LEVELS,
  • 10. ARC FLASH FAULTS HOW OFTEN DO THEY HAPPEN? “EVERY DAY, 1 TO 2 ARC FLASH RELATED FATALITIES OCCUR ACROSS NORTH AMERICA”
  • 11. INTERNAL ARC FAULTS – CAUSES  Badly Designed Switchgear  Incorrect Installation  Insulation Failure ▫ Contamination ▫ Age Deterioration ▫ Overstressing ▫ Human Intervention ▫ Vermin Ingress  Lack of/Inadequate Maintenance  Human Error or Misuse  Over-stressing
  • 12. ENERGY RELEASED BY ARC FAULT PRESSURE RISE VISUAL & ACCOUSTIC PHENOMENA TEMPERATURE RISE EFFECTS OF FAULT ARC CONSEQUENCES FOR PLANT MECHANICAL STRESSING OF ENCLOSURES THERMAL STRESSING, MELTING, VAPOURISATION CONSEQUENCES FOR PERSONNEL SHOCK WAVE, FLYING DEBRIS, OPENING PANELS EJECTION OF FLAMES & HOT GASES, METAL VAPOUR EFFECTS AND CONSEQUENCES OF AN ARC FAULT IN HIGH VOLTAGE SWITCHGEAR
  • 13. THE CONSEQUENCES OF AN INTERNAL ARC FAULT IN HV SWITCHGEAR
  • 14. THE CONSEQUENCES OF AN INTERNAL ARC FAULT IN HV OIL SWITCHGEAR
  • 15. ARC-FAULT IN NON-VENTED SWITCHGEAR SOME INTERESTING DATA FROM RPS TESTING OF ELDERLY SWITCHGEAR  Current starts: 0  Pressure starts: 0.4 ms  Pressure peak: 4.7 ms  Pressure duration: 6.6 ms  Current peak: <10 ms Data & Test evidence supports that the covers will be flying off in 5 – 10 ms Maximum pressure on switchgear panels/doors can be 1-2 bar
  • 16. Safety Solutions & Improvements for Existing Switchboards
  • 17.  TO IMPROVE SAFETY FOR OPERATORS AND STAFF,  TO REDUCE MAINTENANCE AND LIFETIME OWNERSHIP COSTS,  TO IMPROVE THE RELIABILITY AND THE SERVICE-ABILITY OF THE CIRCUIT BREAKERS.  TO INCREASE THE RATING OF THE SWITCHBOARD, (X/R, Normal & Short cct)  TO FURTHER EXTEND THE REMAINING LIFE OF THE ASSET BY REPLACING KEY COMPONENTS AS REQUIRED, (BUSHINGS, CT’S, VT’S ETC)  TO MODERNISE THE CONTROL & PROTECTION EQUIPMENT.  TO ACHIEVE THE ABOVE WITH MINIMUM SYSTEM DISRUPTION. KEY STRATEGIC OBJECTIVES FOR LIFETIME SUPPORT OF AGING SWITCHGEAR ASSETS.
  • 18. SUMMARY OF SWITCHGEAR SOLUTIONS,  SAFETY RETROFITS,  CIRCUIT BREAKER RETROFIT,  ARC DOOR + END SHIELD RETROFIT,  3-SIDED ‘CONTAINMENT’  ‘REMOTE OPERATION’  UPGRADES & LIFE EXTENSION,  CURRENT TRANSFORMER REPLACEMENT,  CABLE BOX RETROFIT,  REPLACEMENT OF ORIFICE BUSHINGS,  REPLACEMENT OF VT’s  PROTECTION & CONTROL UPGRADE,
  • 20. CIRCUIT BREAKER RETROFIT Existing LMT panel Oil Circuit Breaker out Vacuum Circuit Breaker in (Brand new unit) OCB TO VCB REPLACEMENT  ABOUT A DAY PER CIRCUIT  MINIMAL DISRUPTION  SIGNIFICANT SAFETY IMPROVEMENT >6,000 units in service world-wide
  • 21. RETROFIT CIRCUIT BREAKER FOR REYROLLE ‘LM’ SWITCHGEAR  SIMPLE MODULAR DESIGN  PROVEN CAST EPOXY RESIN INSULATION SYSTEM  CAPABLE OF MORE THAN 10,000 LOAD CURRENT OPERATIONS  PROVEN LONG LIFE, LOW MAINTENANCE MECHANISM  LESS THAN 30% OF THE PARTS OF LMT  CAPABLE OF OVER 50 SHORT-CIRCUIT OPERATIONS AT 25KA AT 12KV  EXCELLENT SWITCHING PERFORMANCE, (25ms opening, >45% dc component)
  • 22.  DIRECT REPLACEMENT FOR LM RANGE,  SIGNIFICANTLY IMPROVES SAFETY IN THE SUBSTATION,  LESS THAN 1 DAY PER CIRCUIT, (Fast Implementation, minimum disruption)  SHORT CIRCUIT WITHSTAND RATING OF THE SWITCHBOARD CAN BE INCREASED UP TO 31.5kA ,  REMOVES OIL HANDLING,  REPLACES CB WITH LONG LIFE, LOW MAINTENANCE UNIT,  LOW COST W.R.T. COMPLETE SWITCHBOARD REPLACEMENT, (<30%)  ALLOWS SUBSTATION ASSETS TO BE RENEWED & REVALUED COST EFFECTIVELY, RPS LMT SWITCHGEAR RETROFIT -- SUMMARY
  • 23. FURTHER SAFETY FOR EXISTING SUBSTATIONS “REPLACEMENT OF THE O.C.B. WITH OUR VACUUM UNIT IS A SIGNIFICANT IMPROVEMENT IN OPERATOR SAFETY” BUT THERE ARE OTHER IMPORTANT SAFETY FEATURES THAT ARE AVAILABLE TO SIGNIFICANTLY IMPROVE SAFETY AND BRING THE EXISTING SWITCHBOARD TOWARDS 62271-200 FOR INTERNAL ARC SAFETY”
  • 24. FURTHER SAFETY FOR EXISTING SUBSTATIONS SWITCHGEAR SAFETY UPGRADES:  Arc-proof doors + end shields  3 sided containment  Electrical operation ‘not-in-front’
  • 25. EXISTING SWITCHGEAR & INTERNAL ARC SAFETY  EXISTING SWITCHBOARDS HAVE NO INTERNAL ARC WITHSTAND OR PRESSURE RELIEF DESIGN,  HUMAN PRESENCE IN FRONT OF THE LIVE SWITCHBOARD IS UNAVOIDABLE  SAFETY FOR OPERATORS, STAFF AND VISITORS IN FRONT OF THE EXISTING SWITCHBOARD IS ACHIEVABLE,  RACKING THROUGH A CLOSED ARC-PROOF DOOR IS ESSENTIAL. TYPICAL EXISTING LMT SWITCHBOARDS
  • 26.  WHY HAVE AN ARC-PROOF DOOR?  WHY HAVE RACKING THROUGH AN ARC-PROOF DOOR? TWO IMPORTANT QUESTIONS:- EXISTING SWITCHGEAR & INTERNAL ARC SAFETY
  • 27. WHY HAVE AN ARC-PROOF DOOR? LMT TEST ARRANGEMENT  STANDARD LMT PANEL  FAULT IN BREAKER COMPARTMENT  25KA, 1S DURATION  OCB WOULD BE MUCH WORSE
  • 28. WHY HAVE AN ARC-PROOF DOOR? ...from a different angle
  • 29. WHY HAVE RACKING THROUGH AN ARC-PROOF DOOR?
  • 30. BEHIND CLOSED DOOR RACKING RETROFIT ARC-PROOF DOOR – OPERATOR SAFETY Behind Closed Door Racking
  • 31. RETROFIT END SHIELDS – OPERATOR SAFETY  PREVENTS BURN-THROUGH,  PROVIDES LATERAL SAFETY  SIMPLE INSTALLATION  NO BUS OUTAGE REQUIRED  END PANEL CCT OUTAGE ONLY
  • 32. RETROFIT OF , 25kA, 1s ARC WITHSTAND FRONT DOOR & END SHIELDS FOR OPERATOR SAFETY`  LMT SWITCHBOARDS RETROFITTED WITH ARC DOORS & END SHIELDS. END SHIELD.
  • 33. RETROFIT OF ARC-WITHSTAND FRONT DOOR Brunei Australia South Africa United Kingdom
  • 34. ARC DOORS REDUCE THE HRC – NFPA 70E Activity Existing switchgear With arc-doors & end shields Circuit breaker operation 4 0/1 Circuit breaker racking 4 0/1 Instrument cubicle work/inspection 4 0/1 Maintenance work in front of switchboard 4 0/1 Relay inspection/testing 4 0/1 General presence in the switch-room in front of the switchboard 4 0/1
  • 37. TEST ARRANGEMENT  LMT PANELS FITTED WITH ARC WITHSTAND KIT  FAULT IN BREAKER COMPARTMENT  25KA, 1S DURATION  CERTIFIED TO IEC 62271-200  3-SIDED SAFETY, 2.8M ROOF ARC DOOR TEST TO LATEST STANDARD
  • 38. ‘REMOTE’ OPERATION Option 1 – Remote Control Panel • Dedicated control for each panel • One set of trip & close operators with key to determine panel Option 2 – Remote Control Pendant • Lead length: 10m, 15m or request • Plugs into panel to be operated
  • 39. Other Retrofit & Upgrade Solutions
  • 40. RETROFIT OF CT CHAMBER & CABLE BOX PITCH-FILLED CABLE BOX REPLACED WITH AIR CABLE BOX. ENCAPSULATED CAST RESIN CT’s REPLACED WITH SLIP-OVER TYPE
  • 41. RETROFIT OF CT CHAMBER  SLIP-OVER CT RETROFIT KIT FOR LMT  ASSEMBLED, JIGGED AND POURED IN THE FACTORY  COMPLETE INSTALLATION
  • 42.  REPLACES THE CABLE BOX & CABLE BOX BUSHINGS ONLY, -- OR  ALSO REPLACES THE EXISTING CAST RESIN CT’S WITH SLIP-OVER TYPE,  INCLUDES NEW CT ORIFICE BUSHINGS AND CT BUSHINGS,  IMPROVED FUTURE PROTECTION FLEXIBILITY,  LIVE LINE INDICATION & PHASING AVAILABLE,  CONVERTS EXISTING CAST PITCH-FILLED BOX TO AIR TERMINATION,  EASY TO IMPLEMENT, -- PER CCT OUTAGE ONLY, CABLE BOX REPLACEMENT 400A/800A FEEDER PANEL CONVERTED TO AIR BOX. 400A/800A FEEDER PANEL BEING CONVERTED TO AIR BOX.
  • 43. VT REPLACEMENT – MOVING PORTION  RPS manufacture & supply a direct replacement truck for the existing Reyrolle LMT VT’s  Fast replacement – no bus-bar outage required  Isolating and Engaging the VT through the Instrument cubicle is available for the new VT arrangement Replacement VT trucks for LMT
  • 44. PROTECTION & CONTROL UPGRADE  Replaces the existing RMI “top-box”  Complete new RMI modernisation  Equipped, wired & tested in the factory  Customised to specific customer requirements  Simplifies site work
  • 45. LMT SWITCHBOARD FITTED WITH SAFETY, PROTECTION & CONTROL IMPROVEMENTS
  • 46. LMT SWITCHBOARD FITTED WITH RPS IMPROVEMENTS  RETROFIT VCB’S,  RETROFIT ARC DOORS  PROTECTION & CONTROL UPGRADE,  RETROFIT RMI CUBICLES,  CT & VT UPGRADES,  SWITCHBOARD FAULT RATING INCREASED FROM 13.1kA UP TO 31.5kA. “Upgraded to modern standards for 40% of the cost of switchboard replacement”
  • 47. SUMMARY – ELDERLY SWITCHGEAR RETROFIT OPTIONS SAFETY UPGRADES:  OCB to VCB upgrade  Arc-proof doors + end shields  3 sided containment  Electrical operation ‘not-in-front’ ADDITIONAL RETROFITS:  RMI cubicles  Busbars  VT’s – bus and circuit  CT’s  Cable boxes Existing aged switchgear can be made safer & upgraded