SlideShare une entreprise Scribd logo
1  sur  147
Télécharger pour lire hors ligne
MOISTURE CONTROL
                         FOR MASONRY




presented by International Masonry Institute
International Union                    International
     of Bricklayers and                         Masonry
     Allied Craftworkers                        Institute

LIFELONG LEARNING
        Pre-job and apprentice training
                     Journeyman upgrade training
                           Safety, scaffold, OSHA training
                               Craftworker
                               certification training
                                  Supervisor certification
                                    Sustainable Masonry
                                    Certification Program
                                      Contractor College
BUILDING CODES
  IBC: the legally
  adopted model code
  MSJC: the
  referenced standard
  IBC supersedes MSJC
  at points of conflict
  MSJC date will be
  one year prior to
  companion IBC
  2009 IBC goes
  with 2008 MSJC
  2012 IBC goes
  with 2011 MSJC
IBC & MSJC
2012 INTERNATIONAL BUILDING CODE

                       CHAPTER 21 - MASONRY
                        SECTION 2101 GENERAL
                          2101.2.6 Masonry Veneer
                          Masonry veneer shall comply
                          with the provisions of Chapter
                          14 or Chapter 6 of TMS
                          402/ACI 530/ASCE 5.
                        SECTION 2104 CONSTRUCTION
                          2104.1 Masonry Construction
                          Masonry construction shall
                          comply with the requirements
                          of Sections 2104.1.1 through
                          2104.4 and with TMS 402/ACI
                          530/ASCE 5.
MOISTURE
RESISTANCE
MOISTURE RESISTANCE




Brick & mortar leak
Wall system must address moisture penetration
2011 MSJC
            2011 Building Code Requirements for Masonry
            Structures (TMS 402/ACI 530/ASCE 5)
             CHAPTER 6 - VENEER
               6.1 GENERAL
                6.1.2 Design of Anchored Veneer
                  e) Water will penetrate the veneer and
                     the wall system should be designed,
                     detailed, and constructed to prevent
                     water penetration into the building.
                     (commentary)

                6.1.6 General Design Requirements
                    Water penetration through the
                    exterior veneer is expected. The wall
                    system must be designed and
                    constructed to prevent water from
                    entering the building. (commentary)
MOISTURE RESISTANCE




CAVITY WALL
[DRAINAGE WALL]
MOISTURE RESISTANCE


REQUIRED by Code
  Air space
  Flashing
  Weep holes
  Air Barrier*

OPTIONAL
  Mortar Dropping
   Collection Device
  (MDCD)
 * depends on project location
MOISTURE RESISTANCE




AIR SPACE
MOISTURE RESISTANCE




             2” recommended
             1” min.
              for veneers,
              per code
             4½” max. btwn.
              brick & backup
AIR SPACE            © 2009 INTERNATIONAL MASONRY INSTITUTE
MOISTURE RESISTANCE



            2” recommended
            1” min. for veneers
            per ACI 530 Code




            4½” max. between
            brick and backup
AIR SPACE                © 2009 INTERNATIONAL MASONRY INSTITUTE
MOISTURE RESISTANCE


No mortar bridging
across the cavity!




AIR SPACE                     © 2009 INTERNATIONAL MASONRY INSTITUTE
MOISTURE RESISTANCE




            2”       2”

AIR SPACE
MOISTURE RESISTANCE




CLEAN CAVITIES
MOISTURE RESISTANCE




     Bevel the bed joints

CLEAN CAVITIES
MOISTURE RESISTANCE




  Mortar Dropping Collection Device (MDCD)
CLEAN CAVITIES
MOISTURE RESISTANCE




  Mortar Dropping Collection Device (MDCD)
CLEAN CAVITIES
CONCRETE MASONRY
                                            BACKUP
                                                               AIR/WATER/VAPOR
                                                               BARRIER AS REQ’D




                                                                                                             BRICK & BLOCK CAVITY WALL
                                                                         HORIZONTAL JOINT
                                                                         REINFORCEMENT W/
                                                                         INTEGRAL WALL TIES



                                                                                  2” AIR SPACE
                                                                                  RECOMMENDED;
                                                                                  1” MIN. REQ’D FOR
                                                                                  DRAINAGE WALLS

                                                                            THRU-WALL FLASHING
                                                                            TO EXTEND PAST TOP
                                                                            OF CAVITY INSERT




                                                                            CAVITY INSERT/MORTAR
                                                                            COLLECTION DEVICE

     RIGID INSUL.

         BRICK VENEER


                WEEP VENT

                            METAL DRIP EDGE SET
                            IN MASTIC OR SEALANT
                                                                                    International Masonry Institute
                                                                                                  MASONRY
                                                                                                  DETAILING
FOUNDATION DETAIL                                                                                 SERIES
DETAIL 01.102       REV. 10/14/07                                                   800-IMI-0988 www.imiweb.org
                                                                              © 2007 INTERNATIONAL MASONRY INSTITUTE
MOISTURE RESISTANCE




Full-height cavity insert
CLEAN CAVITIES
MOISTURE RESISTANCE




Cleanout openings



CLEAN CAVITIES
MOISTURE RESISTANCE




AIR BARRIER
AIR BARRIER: DEFINITION

 The International Energy Conservation Code defines
 an air barrier as:
      “material(s) assembled and joined together to
      provide a barrier to air leakage through the
      building envelope. An air barrier may be a
      single material or a combination of materials.”

 ABAA and IECC recognize air barriers in terms of:
          • materials
          • components
          • assemblies
          • systems
AIR BARRIER: DEFINITION



   A material, assembly, or system that restricts
   air leakage (flow)…
    L/s (cf/m)

            over an area of wall…
                   m2 (sf)

                             at a difference of air pressure
                                  Pa (psf)




                 Source: ASTM E 2178, Standard Test Method for Air Permeance of Building Materials
IBC: WATER-RESISTIVE BARRIER
  2012 International Building Code
      CHAPTER 14 – EXTERIOR WALLS
           Section 1403 Performance Requirements
                1403.2 Weather protection
                     Exterior walls shall provide the building with a
                     weather-resistant exterior wall envelope. The
                     envelope shall be designed and constructed in
                     such a manner as to prevent the accumulation of
                     water within the wall assembly by providing a
                     water-resistive barrier behind the exterior veneer,
                     as described in Section 1404.2.
                     Protection against condensation in the exterior
                     wall assembly shall be provided in accordance
                     with Section 1405.3

                     Exception:
                     A weather-resistant exterior wall envelope shall
                     not be required over masonry walls designed in
                     accordance with Chapter 21.
MSJC: WATER-RESISTANT MEMBRANE


             2011 Building Code Requirements for Masonry
             Structures (TMS 402/ACI 530/ASCE 5)
              CHAPTER 6 - VENEER
                6.1 GENERAL
                 6.1.6 General Design
                       Requirements

                       6.1.6.1
                        Design and detail the backing system
                        of exterior veneer to resist water
                        penetration. Exterior sheathing shall
                        be covered with a water-resistant
                        membrane, unless the sheathing is
                        water resistant and the joints are
                        sealed.
IBC REFERENCES IECC



             2012 International Building Code
              CHAPTER 13 – ENERGY EFFICIENCY
                    Section 1301 GENERAL
                        1301.1.1 Criteria
                           Buildings shall be designed and
                           constructed in accordance with the
                           International Energy Conservation
                           Code.
AIR LEAKAGE

              2012 International Energy Conservation Code

               CHAPTER 4
               COMMERCIAL ENERGY EFFICIENCY
                 SECTION C402
                 BUILDING ENVELOPE REQUIREMENTS

                  C402.4 Air Leakage (Mandatory)
                     The thermal envelope of buildings
                     shall comply with Sections C402.4.1
                     through C402.4.8
AIR BARRIERS
               2012 International Energy Conservation Code

                CHAPTER 4
                COMMERCIAL ENERGY EFFICIENCY
                  SECTION C402
                  BUILDING ENVELOPE REQUIREMENTS
                     C402.4.1 Air Barriers
                        A continuous air barrier shall be
                        provided throughout the building
                        thermal envelope. The air barriers shall
                        be permitted to be located on the inside
                        our outside of the building envelope,
                        located    within    the    assemblies
                        composing the envelope, or any
                        combination thereof. The air barrier
                        shall comply with C402.4.1.1. and
                        C402.4.1.2

                        Exception: Air barriers are not required
                        in buildings located in Climate Zones 1,
                        2, and 3.
AIR BARRIER CONSTRUCTION
             2012 International Energy Conservation Code

               C402.4.1.1 Air Barrier Construction
                 1. The air barrier shall be continuous for all
                    assemblies that are the thermal envelope of
                    the building, and across the joints and
                    assemblies.*
                       * Not required if building envelope passes ASTM
                         E779 Standard Test Method for Determining
                         Air Leakage Rate by Fan Pressurization.

                 2. Air barrier joints and seams shall be sealed,
                    including sealing transitions in places and
                    changes in materials.           Air barrier
                    penetrations shall be sealed in accordance
                    with Section C402.4.2
                    The joints and seals shall be securely
                    installed… as not to … impair its ability to
                    resist positive and negative pressure from
                    wind, stack effect, and mechanical
                    ventilation.
AIR BARRIER COMPLIANCE OPTIONS
              2012 International Energy Conservation Code

               C402.4.1.2 Air Barrier Compliance Options
                    A continuous air barrier for the opaque
                    building envelope shall comply with any one
                    of the following:


                        C402.4.1.2.1 Materials & Components
                                  or
                        C402.4.1.2.2 Assemblies
                                  or
                        C402.4.1.2.3 System
AIR BARRIER DEFINITIONS

   An AB material is a primary material used to resist air
   leakage.

   An AB component is a product like sealant or tape used
   to create continuity between air barrier materials.

   An AB assembly is a collection of AB materials and
   components assembled together in a specific manner to
   create continuity.

   An AB system is a system of building assemblies within
   the building enclosure designed, installed, and integrated
   in such a manner as to stop the uncontrolled flow of air
   into and out of the building enclosure.
                                   Source: Air Barrier Association of America (ABAA)
AIR BARRIER DEFINITIONS


   A material or component is an air barrier if it meets these
   maximum criteria:
  .02 L/s per m2 @ 75 Pa          (.004 cfm/sf @ 1.56 psf)




     1/2” sheet of gypsum board without seams, joints, or penetrations
AIR BARRIER DEFINITIONS


   A material or component is an air barrier if it meets these
   maximum criteria:
  .02 L/s per m2 @ 75 Pa     (.004 cfm/sf @ 1.56 psf)

   An assembly is an air barrier if it meets these maximum
   criteria:
   0.2 L/s per m2 @ 75 Pa     (0.04 cfm/sf @ 1.56 psf)

   A system is an air barrier if it meets these maximum
   criteria:
   2.0 L/s per m2 @ 75 Pa     (0.4 cfm/sf @ 1.56 psf)
AIR BARRIER MATERIALS
 2012 International Energy Conservation Code
 C402.4.1.2.1 Air Barrier Materials

    These materials meet the criteria of
    .02 L/s per m2 @ 75 Pa (.004 cfm/sf @ 1.56 psf)
                       • 3/8” thick plywood
                       • 3/8” thick OSB
                       • 1/2” thick XPS insulation
                       • 1/2” thick foil-backed polyisocyanurate insul.
                       • 1½” thick, 1.5 pcf closed cell spray foam
                       • 1/2” thick exterior or interior gyp bd. or cement bd.
                       • 5/8” thick Portland cement/sand parge
                       • 5/8” thick gypsum plaster
                       • C.I.P. or precast concrete
                       • Fully grouted CMU
AIR BARRIER ASSEMBLIES
 2012 International Energy Conservation Code
 C402.4.1.2.2 Air Barrier Assemblies

    These assemblies meet the criteria of
    0.2 L/s per m2 @ 75 Pa (.04 cfm/sf @ 1.56 psf)

                        • Concrete masonry walls coated with one
                          application of block filler and two
                          applications of a paint or sealer coating.
                        • A Portland cement/sand parge, stucco or
                          plaster minimum 1/2” thick.
AIR BARRIER SYSTEM
 2012 International Energy Conservation Code
 C402.4.1.2.3 Building Test

    Completed building (system) shall be tested and meet
    criteria of
    2.0 L/s per m2 @ 75 Pa    (0.4 cfm/sf @ 1.56 psf)




                                    ASTM E779 Standard Test
                                    Method for Determining Air
                                    Leakage Rate by Fan
                                    Pressurization
AIR BARRIER ATTRIBUTES



   •   Impermeable
   •   Continuous Coverage
   •   Bridging Capability
   •   Expected Service Life (Durability)
   •   Secure
   •   Environmentally & Worker Friendly
MOISTURE PENETRATION RESISTANCE




Parged Mortar         Sprayed Bituminous




                     Spray polyurethane foam

Rolled Bituminous
                                               Sheet membranes
AIR BARRIER TYPES
MOISTURE PENETRATION RESISTANCE




Prep wall by caulking any open joints   Tool caulk joints




AIR BARRIER                                                 © 2009 INTERNATIONAL MASONRY INSTITUTE
MOISTURE PENETRATION RESISTANCE




Spray on first coat          Roll membrane to required thickness




AIR BARRIER                                          © 2009 INTERNATIONAL MASONRY INSTITUTE
OPTION 1: AB, FLASHING   OPTION 2: FLASHING, AB
AIR BARRIER PENETRATIONS & JOINTS

 2012 International Energy Conservation Code

   C402.4.2 Air Barrier Penetrations
    Penetrations of the air barrier and paths of
    air leakage shall be caulked, gasketed, or
    otherwise sealed.
    Joints and seals shall be sealed in the same
    manner or taped or covered with a moisture
    permeable wrapping material.
    Joints and seals shall be securely installed in
    or on the joint for its entire length so as not to
    dislodge, loosen or otherwise impair its
    ability to resist positive and negative
    pressure from wind, stack effect and
    mechanical ventilation.
MOISTURE RESISTANCE




FLASHING
MOISTURE RESISTANCE


 Design and detail flashing and weep holes
 in exterior veneer wall systems to resist
 water penetration into the building interior.
  ACI 530-02/ASCE 5-02/TMS 402-02, Chapter 6 Veneer, Section 6.1.5.2




     What type?
     What thickness?
     What locations?


FLASHING – CODE REQUIREMENT
MOISTURE RESISTANCE



  “Approved, corrosion-resistant
  flashing” shall be provided in the
  exterior wall envelope in such a
  manner as to prevent entry of
  water into the wall cavity or
  penetration of water into the
  building structural framing
  components.
  ACI 530-02/ASCE 5-02/TMS 402-02,
  Chapter 6 Veneer, Section 6.1.5.2




FLASHING TYPES
MOISTURE RESISTANCE


  Plastic flashing
 should be at least 30
 mil thick
   BIA Tech Note 28: Anchored Brick Veneer
   Wood Frame Construction




FLASHING THICKNESS
MOISTURE RESISTANCE




      sills       shelf angles


                                       top of wall



  base of wall   above openings
FLASHING APPLICATIONS
MOISTURE RESISTANCE

   Beneath the first course of masonry
   above finished ground level
   Other points of support such as
   shelf angles and lintels
   At top of all exterior window
   and door openings
   At intersection of chimneys
   Under sills
   At wall and roof intersections
 ACI 530-02/ASCE 5-02/TMS 402-02, Chapter 6 Veneers



FLASHING LOCATIONS
FLASHING LOCATIONS
MOISTURE RESISTANCE




BASE OF WALL
FLASHING – BASE OF WALL
MOISTURE RESISTANCE



              Keep top of foundation
              above grade if possible
              Don’t bury the weeps!




RISING DAMP
MOISTURE RESISTANCE




 best
 practice           alternate

FOUNDATION HEIGHT                © 2009 INTERNATIONAL MASONRY INSTITUTE
2” AIR SPACE RECOMMENDED;
                                                            1” MIN. REQ’D FOR DRAINAGE WALLS



                                                                   AIR/MOISTURE/VAPOR
                                                                   BARRIER AS REQUIRED

                                                                          HORIZONTAL JOINT REIN-
                                                                          FORCEMENT W/ EYE & PINTLE
                                                                          WALL TIES @ 16” O.C.

                                                                          RIGID INSULATION

                                                                          GROUT & REINFORCEMENT
                                                                          AS REQUIRED




                                                                                 RETURN FLASHING INTO
                                                                                 BED JOINT OF BLOCK
                                                                                CONCRETE
                                                                                MASONRY BACKUP



     BRICK VENEER

                                                                                    FLEXIBLE FLASHING – SEAL
                                                                                    & ADHERE TO DRIP EDGE

           WEEP VENT INSERTS (TOP &
           BOTTOM OF WALL; SEE NOTES
           ON COMPARTMENTALIZATION)
                         DRIP EDGE – SEAL AND
                         ADHERE TO FOUNDATION



FOUNDATION DETAIL              FLEX. FLASHING IN CMU, DRIP EDGE
DETAIL 01.030.0305                                 REV. 07/01/09
                                                                                               © 2009 INTERNATIONAL MASONRY INSTITUTE
2” AIR SPACE RECOMMENDED;
                                                             1” MIN. REQ’D FOR DRAINAGE WALLS



                                                                   AIR/MOISTURE/VAPOR
                                                                   BARRIER AS REQUIRED

                                                                           HORIZONTAL JOINT REIN-
                                                                           FORCEMENT W/ EYE & PINTLE
                                                                           WALL TIES @ 16” O.C.

                                                                           RIGID INSULATION

                                                                           GROUT & REINFORCEMENT
                                                                           AS REQUIRED




                                                                                  MECH. FASTENED
                                                                                  TERMINATION BAR W/
                                                                                  CONT. SEALANT @ TOP



                                                                                     CONCRETE
                                                                                     MASONRY BACKUP
     BRICK VENEER

                                                                                     FLEXIBLE FLASHING – SEAL
                                                                                     & ADHERE TO DRIP EDGE
           WEEP VENT INSERTS (TOP &
           BOTTOM OF WALL; SEE NOTES
           ON COMPARTMENTALIZATION)

                        DRIP EDGE – SEAL AND
                        ADHERE TO FOUNDATION



FOUNDATION DETAIL               FLEX. FLASHING, DRIP EDGE, TERM. BAR
DETAIL 01.030.0301                                      REV. 07/01/09
                                                                                                © 2009 INTERNATIONAL MASONRY INSTITUTE
2” AIR SPACE RECOMMENDED;
                                                             1” MIN. REQ’D FOR DRAINAGE WALLS



                                                                    AIR/MOISTURE/VAPOR
                                                                    BARRIER AS REQUIRED

                                                                           HORIZONTAL JOINT REIN-
                                                                           FORCEMENT W/ EYE & PINTLE
                                                                           WALL TIES @ 16” O.C.

                                                                           RIGID INSULATION

                                                                           GROUT & REINFORCEMENT
                                                                           AS REQUIRED




                                                                                  MECH. FASTENED
                                                                                  TERMINATION BAR W/
                                                                                  CONT. SEALANT @ TOP




                                                                                     CONCRETE
                                                                                     MASONRY BACKUP
     BRICK VENEER

                                                                                     FLEXIBLE FLASHING – SEAL
      MORTAR DROPPING                                                                & ADHERE TO DRIP EDGE
      COLLECTION DEVICE (MDCD)

            WEEP VENT INSERTS (TOP &
            BOTTOM OF WALL; SEE NOTES
            ON COMPARTMENTALIZATION)
                         DRIP EDGE – SEAL AND
                         ADHERE TO FOUNDATION


FOUNDATION DETAIL                FLEX. FLASHING, DRIP EDGE, TERM. BAR, MDCD
DETAIL 01.030.0302                                             REV. 07/01/09
                                                                                                © 2009 INTERNATIONAL MASONRY INSTITUTE
2” AIR SPACE RECOMMENDED;
                                                              1” MIN. REQ’D FOR DRAINAGE WALLS



                                                                     AIR/MOISTURE/VAPOR
                                                                     BARRIER AS REQUIRED

                                                                             HORIZONTAL JOINT REIN-
                                                                             FORCEMENT W/ EYE & PINTLE
                                                                             WALL TIES @ 16” O.C.

                                                                             RIGID INSULATION

                                                                             GROUT & REINFORCEMENT
                                                                             AS REQUIRED




                                                                                   MECH. FASTENED
                                                                                   TERMINATION BAR W/
                                                                                   CONT. SEALANT @ TOP




                                                                                       CONCRETE
                                                                                       MASONRY BACKUP
     BRICK VENEER

                                                                                       FLEXIBLE FLASHING FLUSH
       MORTAR DROPPING                                                                 W/ OUTSIDE FACE OF BRICK
       COLLECTION DEVICE (MDCD)

           WEEP VENT INSERTS (TOP &
           BOTTOM OF WALL; SEE NOTES
           ON COMPARTMENTALIZATION)




FOUNDATION DETAIL                 FLEX. FLASHING NO DRIP; TERM. BAR, MDCD
DETAIL 01.030.0303                                           REV. 07/01/09
                                                                                                 © 2009 INTERNATIONAL MASONRY INSTITUTE
2” AIR SPACE RECOMMENDED;
                                                               1” MIN. REQ’D FOR DRAINAGE WALLS



                                                                      AIR/MOISTURE/VAPOR
                                                                      BARRIER AS REQUIRED

                                                                             HORIZONTAL JOINT REIN-
                                                                             FORCEMENT W/ EYE & PINTLE
                                                                             WALL TIES @ 16” O.C.

                                                                             RIGID INSULATION

                                                                             GROUT & REINFORCEMENT
                                                                             AS REQUIRED

                                                                                    RETURN FLASHING INTO
                                                                                    BED JOINT OF BLOCK




                                                                                   CONCRETE
                                                                                   MASONRY BACKUP



     BRICK VENEER

                                                                                       FLEXIBLE FLASHING – SEAL
       MORTAR DROPPING                                                                 & ADHERE TO DRIP EDGE
       COLLECTION DEVICE (MDCD)
           WEEP VENT INSERTS (TOP &
           BOTTOM OF WALL; SEE NOTES
           ON COMPARTMENTALIZATION)
                         DRIP EDGE – SEAL AND
                         ADHERE TO FOUNDATION



FOUNDATION DETAIL                 FLEX. FLASHING IN CMU, DRIP EDGE
DETAIL 01.030.0306                                    REV. 07/01/09
                                                                                                  © 2009 INTERNATIONAL MASONRY INSTITUTE
2” AIR SPACE RECOMMENDED;
                                                          1” MIN. REQ’D FOR DRAINAGE WALLS



                                                                  AIR/MOISTURE/VAPOR
                                                                  BARRIER AS REQUIRED

                                                                         HORIZONTAL JOINT REIN-
                                                                         FORCEMENT W/ EYE & PINTLE
                                                                         WALL TIES @ 16” O.C.

                                                                         RIGID INSULATION

                                                                         GROUT & REINFORCEMENT
                                                                         AS REQUIRED


                                                                                MECH. FASTENED
                                                                                TERMINATION BAR W/
                                                                                CONT. SEALANT @ TOP




   BRICK VENEER
                                                                                   CONCRETE
                                                                                   MASONRY BACKUP

   MORTAR DROPPING
   COLLECTION DEVICE (MDCD)
                                                                                   METAL FLASHING W/
                                                                                   INTEGRAL DRIP EDGE
               WEEP VENT INSERTS (TOP &
               BOTTOM OF WALL; SEE NOTES
               ON COMPARTMENTALIZATION)




FOUNDATION DETAIL              METAL FLASHING, TERM. BAR, MDCD
DETAIL 01.030.0311                                REV. 07/01/09
                                                                                             © 2009 INTERNATIONAL MASONRY INSTITUTE
MOISTURE RESISTANCE




SILLS
FLASHING – SILL
SILL/JAMB DETAIL
HIGH PERFORMING MASONRY WALL
WOOD BLOCKING FOR
  WINDOW ANCHORAGE                                     ALTERNATE
                                                       FLASHING
                                                       LOCATION

                                                       WINDOW STOOL
                                                       NOT SHOWN

  WINDOW ASSEMBLY




  FLASHING                                                            RIGID FLASHING TO SPAN
  END DAM                                                             ACROSS DRAINAGE CAVITY
                                                                      RIGID INSULATION
                                                                      HORIZONTAL JOINT
                                                                      REINFORCEMENT




             MASONRY EXPANSION
             JOINT AS REQUIRED

                     MASONRY SILL W/ 1/8” x
                     1/8” CONT. SAW-CUT DRIP




SILL DETAIL            MASONRY SILL, RIGID FLASHING
DETAIL 01.030.0401                     REV. 07/28/09
                                                                                 © 2009 INTERNATIONAL MASONRY INSTITUTE
MOISTURE RESISTANCE




FLASHING - SILLS
MOISTURE RESISTANCE




                          Best practice: Use limestone
                          or precast sills


 Slope rowlocks at least 15º
SILLS
MOISTURE RESISTANCE




HEADS
FLASHING – HEAD
HEAD DETAIL

HIGH PERFORMING MASONRY WALL
MOISTURE RESISTANCE




  Larger unit modules make end dams difficult

FLASHING – END DAMS
BRICK & BLOCK CAVITY WALL
DETAIL FEATURES                   EXTERIOR VIEW             INTERIOR VIEW
• LOOSE LINTEL AT BRICK
• STEEL ANGLES AT BLOCK
• LIGHT GAUGE SUPPORT                                              International Masonry Institute
  ACROSS CAVITY
                                                                                  MASONRY
                                                                                  DETAILING
HEAD DETAIL               STEEL LINTEL W/ DOUBLE ANGLE                            SERIES
DETAIL 01.303                               REV. 09/06/07          800-IMI-0988 www.imiweb.org
                                                               © 2007 INTERNATIONAL MASONRY INSTITUTE
BRICK & BLOCK CAVITY WALL
                                                       INTERIOR VIEW




DETAIL FEATURES
• LOOSE LINTEL AT BRICK
• BOND BEAM AT BLOCK                                                       International Masonry Institute
• LIGHT GAUGE SUPPORT                EXTERIOR VIEW
  ACROSS CAVITY                                                                           MASONRY
                                                                                          DETAILING
HEAD DETAIL               STEEL LINTEL & BOND BEAM                                        SERIES
DETAIL 01.301                          REV. 09/04/07                       800-IMI-0988 www.imiweb.org
                                                                       © 2007 INTERNATIONAL MASONRY INSTITUTE
SPANNING OPENINGS




     Poly-wrapped steel angles used for temporary support

CAST-IN-PLACE MASONRY LINTEL
SPANNING OPENINGS




    Precast masonry lintel fabricated on the ground

PRECAST LINTELS
SPANNING OPENINGS




     Lintel is hoisted by lift

PRECAST LINTELS
SPANNING OPENINGS




     Precast lintel set into place

PRECAST LINTELS
SPANNING OPENINGS




     10-foot span

PRECAST LINTELS
FLASHING – HEAD
MOISTURE RESISTANCE




RELIEVING ANGLES
2” AIR SPACE
                                                         RECOMMENDED; 1”
                                HORIZONTAL JOINT         MIN. REQ’D FOR




                                                                                         BRICK & BLOCK CAVITY WALL
                                REINFORCEMENT W/         DRAINAGE WALLS
                                INTEGRAL WALL TIES
                                                         RIGID INSUL.
                                THRU-WALL FLASHING W/
                                METAL DRIP EDGE SET IN   ADJUSTABLE
                                MASTIC OR SEALANT        SHELF ANGLE




    WEEP/VENT

                  TYPICAL FACE
    ADJUSTABLE    BRICK ABOVE &
    SHELF ANGLE   BELOW ANGLE
                  SEALANT & BACKER ROD
                                                               International Masonry Institute
                  COMPRESSIBLE
                  FILLER, OPTIONAL                                            MASONRY
                                                                              DETAILING
SHELF ANGLE DETAIL   TYP. FACE BRICK                                          SERIES
DETAIL 01.501            REV. 06/19/08                         800-IMI-0988 www.imiweb.org
                                                           © 2008 INTERNATIONAL MASONRY INSTITUTE
HORIZONTAL JOINT               2” AIR SPACE
                     REINFORCEMENT W/               RECOMMENDED; 1”
                     INTEGRAL WALL TIES             MIN. REQ’D FOR
                                                    DRAINAGE WALLS




                                                                                   BRICK & BLOCK CAVITY WALL
                          THRU-WALL FLASHING W/
                          METAL DRIP EDGE SET IN
                          MASTIC OR SEALANT
                                   RIGID INSUL.




 WEEP/VENT
     ADJUSTABLE.
     SHELF ANGLE
                   LIPPED BRICK,
                   OPTIONAL

                   SEALANT & BACKER ROD
                                                         International Masonry Institute
                   COMPRESSIBLE
                   FILLER, OPTIONAL                                     MASONRY
                                                                        DETAILING
SHELF ANGLE DETAIL – LIPPED BRICK                                       SERIES
DETAIL 01.502                       REV. 10/14/07        800-IMI-0988 www.imiweb.org
                                                     © 2007 INTERNATIONAL MASONRY INSTITUTE
MOISTURE RESISTANCE




                              Too many
                              relieving angles




FLASHING – RELIEVING ANGLES
MOISTURE RESISTANCE




 ROOF-WALL
CONNECTION
FLASHING – ROOF/WALL CONNECTION
CMU BACKUP

            FACE BRICK                                               CAVITY INSUL.
                                                                     THRU-WALL




                                                                                             BRICK & BLOCK CAVITY WALL
                                                                     FLASHING
            ROOF MEMBRANE                                            CUT BLOCK
                                                                     BELOW FLASHING


            COUNTER-
            FLASHING
            SHEET METAL
            RECEIVER




                                      THRU-WALL
                                      FLASHING

                                      WEEP
                                      VENT




                                     TERMINATION BAR
                                     W/ CONT. SEALANT
                                     ROOF STRUCTURE
                                     HORIZONTAL JOINT REINF.       International Masonry Institute
                                     @ 16” O.C. W/ INTEGRAL
                                     WALL TIES                                    MASONRY
                                                                                  DETAILING
ROOF DETAIL              HIGH WALL – LOW ROOF                                     SERIES
DETAIL 01.704                        REV. 11/6/07                  800-IMI-0988 www.imiweb.org
                                                               © 2007 INTERNATIONAL MASONRY INSTITUTE
MOISTURE RESISTANCE




TOP OF WALL
FLASHING – TOP OF WALL
BRICK & BLOCK CAVITY WALL
    MASONRY COPING: LIMESTONE, CAST
    STONE, CALCIUM SILICATE, OR
    PRECAST CONCRETE; OVERHANG                                  S.S. DOWEL W/ SEALANT
    MASONRY WALL 1½” MIN.; SLOPED                               AROUND PENETRATIONS
    TOP                                                         THROUGH FLASHING
    1/8” SAW-CUT DRIP,
    BOTH SIDES OF
    WALL CAP                                                    SEE DETAIL 01.759 FOR
                                                                WALL CAP JOINT OPTIONS

    SEALANT & BACKER
    ROD, BOTH SIDES                                             THROUGH-WALL
    OF WALL CAP                                                 FLASHING W/
                                                                1/2” DRIP EDGE
    GROUT OR MORTAR
    FILL FOR DOWEL
    ANCHORAGE AND
    FLASHING SUPPORT                                            SEALANT BELOW DRIP,
                                                                OPT. (NOT SHOWN)
    MESH TO RETAIN
    GROUT OR MORTAR
    FILL


    DRAINAGE CAVITY

                                                      GROUT & REINFORCING
    FACE BRICK                                        AS REQ’D.

                                                      HORIZONTAL JOINT
    RIGID INSULATION                                  REINFORCEMENT
                                                      W/ WALL TIES
                                                                         International Masonry Institute
                                                                                       MASONRY
                                                                                       DETAILING
MASONRY WALL CAP                 FILLED CAVITY                                         SERIES
DETAIL 01.752                         REV. 11/04/08                      800-IMI-0988 www.imiweb.org
                                                                   © 2008 INTERNATIONAL MASONRY INSTITUTE
BRICK & BLOCK CAVITY WALL
    MASONRY COPING: LIMESTONE, CAST
    STONE, CALCIUM SILICATE, OR                                 S.S. DOWEL W/ SEALANT
    PRECAST CONCRETE; OVERHANG                                  AROUND PENETRATIONS
    MASONRY WALL 1½” MIN.; SLOPED                               THROUGH FLASHING
    TOP
    1/8” SAW-CUT DRIP,
    BOTH SIDES OF
    WALL CAP                                                    SEE DETAIL 01.759 FOR
                                                                WALL CAP JOINT OPTIONS

    SEALANT & BACKER
    ROD, BOTH SIDES                                             CANTED S.S. THRU-WALL
    OF WALL CAP                                                 FLASHING W/ 1/2”
                                                                EXPOSED DRIP EDGE
    FACE BRICK
    SLOPED MORTAR
    BED TO SUPPORT
    CANTED FLASHING,                                            SEALANT BELOW DRIP,
    OPT.                                                        OPT. (NOT SHOWN)

    RIGID INSULATION


    OPEN DRAINAGE
    CAVITY, OPTIONAL
    ABOVE ROOF LINE;
    ALSO SEE DETAIL                                   GROUT & REINFORCING
    01.752                                            AS REQ’D.

                                                      HORIZONTAL JOINT
                                                      REINFORCEMENT
                                                      W/ WALL TIES
                                                                         International Masonry Institute
                                                                                       MASONRY
                                                                                       DETAILING
MASONRY WALL CAP                 OPEN CAVITY                                           SERIES
DETAIL 01.751                         REV. 11/04/08                      800-IMI-0988 www.imiweb.org
                                                                   © 2008 INTERNATIONAL MASONRY INSTITUTE
MOISTURE RESISTANCE




Drill through flashing for anchor Seal around dowel penetration



TOP OF WALL
SINGLE WYTHE BLOCK
    MASONRY COPING: LIMESTONE, CAST
    STONE, CALCIUM SILICATE, OR
    PRECAST CONCRETE; OVERHANG
    MASONRY WALL 1½” MIN.; SLOPED TOP

                                                         SEE DETAIL 01.759 FOR
    S.S. DOWEL W/ SEALANT                                WALL CAP JOINT OPTIONS
    AROUND PENETRATIONS
    THROUGH FLASHING

                                                         S.S. FLASHING DRIP,
    SEALANT & BACKER                                     BOTH SIDES OF CAP
    ROD, BOTH SIDES
    OF WALL CAP                                          1/8” SAW-CUT DRIP,
                                                         BOTH SIDES OF WALL
                                                         CAP
    GROUT OR MORTAR FILL
    FOR DOWEL ANCHORAGE
    AND FLASHING SUPPORT                                  SEALANT BELOW DRIP,
                                                          OPT. (NOT SHOWN)
    MESH TO RETAIN
    GROUT OR MORTAR FILL

                                                         HORIZONTAL JOINT
                                                         REINFORCEMENT




                                                                International Masonry Institute
                                                                               MASONRY
                                                                               DETAILING
MASONRY WALL CAP                  SINGLE WYTHE CMU                             SERIES
DETAIL 03.701                            REV. 11/04/08          800-IMI-0988 www.imiweb.org
                                                            © 2008 INTERNATIONAL MASONRY INSTITUTE
MOISTURE RESISTANCE




FLASHING – TOP OF WALL
MOISTURE RESISTANCE




Rowlock caps not   Limestone, manufactured stone, or
recommended        precast concrete caps are better

TOP OF WALL
BRICK & BLOCK CAVITY WALL
                OPTION 1                            OPTION 2
                TOOLED MORTAR JOINT                 RAKE BACK MORTAR AND
                                                    APPLY SEALANT JOINT




                                      OPTION 3
                                      SEALANT AND
                                      BACKER ROD


 Rowlock caps not                                              International Masonry Institute
 recommended                                                                 MASONRY
                                                                             DETAILING
MASONRY COPING JOINTS                                                        SERIES
DETAIL 01.759     REV. 11/04/08                                800-IMI-0988 www.imiweb.org
                                                          © 2008 INTERNATIONAL MASONRY INSTITUTE
MOISTURE RESISTANCE




TOP OF WALL
MOISTURE RESISTANCE

         Damage is more severe
         below joints in coping




Freeze-thaw damage           Flashing is held back from face
at top courses


FLASHING – PROBLEMS TO AVOID
MOISTURE RESISTANCE




LAPS AND
DRIP EDGES
MOISTURE RESISTANCE


How far should flashing extend?




Too much!               Not enough!



FLASHING – DRIP EDGES
MOISTURE RESISTANCE




                                 Metal drip edge
                                 is best practice!
 “The flashing shall extend to the surface of
 the exterior wall finish, and shall be installed
 to prevent water from reentering the exterior
 wall envelope.” - IRC Section R703 Flashing



FLASHING – DRIP EDGES
3/4” MIN. OVERLAP, SEALED
     W/ MFR-APPROVED ADHESIVE




     1/2” MIN. IF RUBBERIZED
     ASPHALT IS USED FOR
     FLEXIBLE FLASHING, TO
     PREVENT DROOL
                                                       FLEXIBLE THRU-WALL
                                                       FLASHING


     METAL DRIP EDGE W/ HEM,
     30º OR 45º FROM HORIZONTAL,
     SEALED TO FOUNDATION W/
     MFR.-APPROVED ADHESIVE




                           1/4” – 3/4”
                                         1 5/8” MIN.




METAL DRIP EDGE
DETAIL 15.000.0201    REV. 05/18/09
                                                              © 2009 INTERNATIONAL MASONRY INSTITUTE
MOISTURE RESISTANCE




Lap all seams           …and adequately seal!

FLASHING – PROBLEMS TO AVOID
PRIMER PER
                  RETURN FLASHING INTO                                                                 MANUF’R
                  BLOCK COURSE (SHOWN)
                  OR SECURE TO BACKUP W/
                  TERMINATION BAR




                                                                                                   SEAL FLASHING
                                                                                                   LAPS W/ MASTIC
                                                                                                   PER MANUF’R

                                                                                          6” LAP




                                                      DRIP EDGE SET IN
                                                      SEALANT



SUBJECT OF DETAIL                       EXCLUDED FROM SUBJECT
THROUGH-WALL FLASHING OVERLAPS (LAPS)   FLASHING DRIP EDGE LAPS, TERM. BAR, FACE BRICK,
AND SEALING RECOMMENDATIONS             CAVITY INSULATION, AND OTHER WALL
                                        COMPONENTS


FLASHING LAP
DIAGRAM 15.410.4101 REV. 02/10/11
                                                                                                        © 2009 INTERNATIONAL MASONRY INSTITUTE
OUTER FACE
                                         OF MASONRY
    THROUGH-WALL FLASHING
    LAPPED AND SEALED
    OUTER FACE
    OF MASONRY




                                                     NOTCHED DRIP EDGE


                                        3/4”±




                                                METAL DRIP W/ HEMMED
                                                EDGE SET IN MASTIC
                                                OR SEALANT

                                 NOTCH DRIP EDGE
                                 FOR BUTT JOINT,      International Masonry Institute
                                 SEE INSET ABOVE
                                                                       masonry
                                                                       detailing
DRIP EDGE DETAIL                                                       series
DETAIL 03.01     REV. 02/13/07                        1-800-IMI-0988    www.imiweb.org
                                                  © 2007 INTERNATIONAL MASONRY INSTITUTE
MOISTURE RESISTANCE




                               6” LAP




FLASHING – LAPS
MOISTURE RESISTANCE




   Seal laps



FLASHING LAPS
MOISTURE RESISTANCE




FLASHING FAILURES
MOISTURE RESISTANCE




                  Keep top of
                  foundation
                  above grade

                  Don’t bury
                  the weeps!

FLASHING – INSTALLATION
MOISTURE RESISTANCE




 Flashing must be intact!

FLASHING – PROBLEMS TO AVOID
MOISTURE RESISTANCE




Hold rubberized as-      Don’t use membrane
phalt back from face     as a drip edge

FLASHING – PROBLEMS TO AVOID
MOISTURE RESISTANCE




                                      not stable




  Avoid using PVC


FLASHING – PROBLEMS TO AVOID
MOISTURE RESISTANCE




Avoid sharp corners     Use rounded corners

FLASHING – PROBLEMS TO AVOID
MOISTURE RESISTANCE




Flashing held back from face



FLASHING – PROBLEMS TO AVOID
MOISTURE RESISTANCE




CORNER BOOTS
 & END DAMS
MOISTURE RESISTANCE




Flashing discontinuous   Continuous flashing
at corner


FLASHING – CORNERS
OUTSIDE CORNER
                                FLASHING PIECE



                                                 VIEW OF FINISHED CONTINUOUS
                                                 FLASHING INSTALLATION
                                                 (DRIP EDGES NOT SHOWN)
  INSIDE CORNER
  FLASHING PIECE




             OVERLAP FLASHING
             NOTE: FLASHING DRIP EDGES
             NOT SHOWN FOR CLARITY




FLASHING CORNERS
DETAIL 15.000.0204       REV. 08/24/09
                                                                 © 2009 INTERNATIONAL MASONRY INSTITUTE
NOTE: FLASHING DRIP EDGE
       NOT SHOWN FOR CLARITY




FLASHING CORNERS
DETAIL 15.000.0204.PH    REV. 08/24/09
                                         © 2009 INTERNATIONAL MASONRY INSTITUTE
MOISTURE RESISTANCE




 Field-applied corner boot
FLASHING – CORNERS
MOISTURE RESISTANCE




end dam
required!




FLASHING – END DAMS
NOTE:
                                                                      STRUCTURAL ELEMENTS
                                                                      MAY VARY, AND ARE SHOWN
                                                                      FOR ILLUSTRATION ONLY


                                                                      CAVITY INSULATION NOT
                                                                      SHOWN FOR CLARITY OF
                                                                      DETAIL



                                                                      CARRY FLASHING ½” MIN.
                                                                      BEYOND END OF LINTEL
                                                                      AND TURN UP TO FORM
                                                                      END DAM IN HEAD JOINT



                                                                    2” RECOMMENDED;
                                                                    1” MIN.




                      SEALANT                           EXTEND FLASHING
                                                        FLUSH OR BEYOND
                                                        FACE OF MASONRY




END DAM DIAGRAM                 FIELD-FORMED FLASHING END DAM
DIAGRAM 01.410.0201                               REV. 02/04/11
                                                                                         © 2009 INTERNATIONAL MASONRY INSTITUTE
NOTE:
                                                                            STRUCTURAL ELEMENTS
                                                                            MAY VARY, AND ARE SHOWN
                                                                            FOR ILLUSTRATION ONLY
                                                                            CAVITY INSULATION NOT
                                                                            SHOWN FOR CLARITY OF
                                                                            DETAIL



                                                                            CARRY FLASHING ½” MIN.
                                                                            BEYOND END OF LINTEL
                                                                                 PREFABRICATED END DAM
                                                                                 IN HEAD JOINT; SET IN
                                                                                 MASTIC IF FLASHING IS NOT
                                                                                 SELF-ADHERING. END DAM
                                                                                 PLACED PRIOR TO
                                                                                 THROUGH-WALL FLASHING

                                                                                      2” RECOMMENDED;
                                                                                      1” MIN.



                                                          EXTEND FLASHING
                      SEALANT                             FLUSH OR BEYOND
                                                          FACE OF MASONRY




END DAM DIAGRAM                 PREFABRICATED FLASHING END DAM
DIAGRAM 01.410.0202                                 REV. 02/04/11
                                                                                              © 2009 INTERNATIONAL MASONRY INSTITUTE
MOISTURE RESISTANCE




FLASHING – END DAMS
MOISTURE RESISTANCE




FLASHING – END DAMS
MOISTURE RESISTANCE




FLASHING – END DAMS
MOISTURE RESISTANCE




WEEP VENTS
MOISTURE RESISTANCE




 Weep holes shall be at least 3/16” in diameter
 and spaced less than 33” on center.
 International Residential Code 2000, Section R703.7.6 Weep Holes
 ACI 530-02/ASCE 5-02/TMS 402-02, Chapter 6 Veneer, Section 6.1.5.2




  Best practice: 16” o.c. max for rope wicks,
  24” o.c. for open head joints or vents

WEEP HOLES
MOISTURE RESISTANCE




                     head joint      fiber mesh vent
plastic
                     vent
sleeve




                           plastic
 sash cord                 tube             cell vent

WEEP HOLES - TYPES
MOISTURE RESISTANCE



 “Weep holes shall be at least 3/16” in diameter
 and spaced less than 33” on center”
 International Residential Code 2000, Section R703.7.6 Weep Holes
 ACI 530-02/ASCE 5-02/TMS 402-02, Chapter 6 Veneer, Section 6.1.5.2


       Best practice: Don’t use rope wicks!


      Best practice: 16” o.c. max for rope wicks (if you
      must), 24” o.c. for open head joints or vents


WEEP HOLES – SIZE & SPACING
Best practice: Don’t use rope wicks!
RESIDENTIAL MASONRY   WEEP HOLES



Best practice: if you must use rope
wicks, lay them continuously along
bottom of cavity
MOISTURE RESISTANCE

                         Best practice: Don’t use
                         rope wicks!
                         Best practice: if you must
                         use rope wicks, lay them
                         continuously along bottom
                         of cavity




WEEP HOLES – PLACEMENT
MOISTURE RESISTANCE




  Vulnerable to mortar blockage
  Do not ventilate


WEEP HOLES – ROPE WICKS
MOISTURE RESISTANCE




  Vulnerable to mortar blockage
  Do not ventilate


WEEP HOLES – TUBES
MOISTURE RESISTANCE




  Better moisture relieve & ventilation
  May attract insects
  May mistakenly be caulked


WEEP HOLES – OPEN HEAD JOINTS
MOISTURE RESISTANCE




WEEP VENTS
MOISTURE RESISTANCE




WEEP VENTS
MOISTURE RESISTANCE




WEEP VENTS
MOISTURE RESISTANCE




RECESSED AND
 PROJECTING
  COURSES
MOISTURE RESISTANCE




RECESSED COURSE
BRICK & BLOCK CAVITY WALL
                MORTAR
                WASH




                                         International Masonry Institute
                                                       MASONRY
                                                       DETAILING
ARCHITECTURAL EFFECT                                   SERIES
DETAIL 01.601            REV. 08/31/07   800-IMI-0988 www.imiweb.org
MOISTURE RESISTANCE




RECESSED COURSE
MOISTURE RESISTANCE




FULL HEAD JOINTS
MOISTURE RESISTANCE




EFFLORESCENCE
MOISTURE RESISTANCE




EFFLORESCENCE
BENEFITS OF BUILDING WITH MASONRY
  Beauty
  Versatility of Design
  Contextual / Relatable
  Ease of Construction
  Structural
  Fire & Impact Resistant
  Durable / Low Maintenance
  Economical
  Sustainable
  Energy Efficient
  High Performance
  Acoustic
  Qualified Local Labor
Moisture Control for Masonry

Contenu connexe

Tendances (20)

Autoclaved Aerated Concrete Blocks
Autoclaved Aerated Concrete BlocksAutoclaved Aerated Concrete Blocks
Autoclaved Aerated Concrete Blocks
 
Bricks Monsonary
Bricks MonsonaryBricks Monsonary
Bricks Monsonary
 
Plain and reinforced cement concrete
Plain and reinforced cement concretePlain and reinforced cement concrete
Plain and reinforced cement concrete
 
Aggregates of Concrete
Aggregates of ConcreteAggregates of Concrete
Aggregates of Concrete
 
Bricks bats and closers
Bricks bats and closersBricks bats and closers
Bricks bats and closers
 
Brick masonry
Brick masonryBrick masonry
Brick masonry
 
Retaining wall
Retaining wallRetaining wall
Retaining wall
 
Concrete
ConcreteConcrete
Concrete
 
basement excavation, underpinning
basement excavation, underpinningbasement excavation, underpinning
basement excavation, underpinning
 
Cement morter
Cement morterCement morter
Cement morter
 
Cracks in concrete
Cracks in concreteCracks in concrete
Cracks in concrete
 
Waterproofing methods & materials used in construction
Waterproofing methods & materials used in constructionWaterproofing methods & materials used in construction
Waterproofing methods & materials used in construction
 
advance concrete technology
advance concrete technologyadvance concrete technology
advance concrete technology
 
Timber roofs
Timber roofsTimber roofs
Timber roofs
 
Brick masonary
Brick masonaryBrick masonary
Brick masonary
 
CHEMICAL ADMIXTURES FOR CONCRETE
CHEMICAL ADMIXTURES FOR CONCRETECHEMICAL ADMIXTURES FOR CONCRETE
CHEMICAL ADMIXTURES FOR CONCRETE
 
Stone masonry ppt
Stone masonry pptStone masonry ppt
Stone masonry ppt
 
Steels as building material
Steels as building materialSteels as building material
Steels as building material
 
Construction material cement
Construction material cementConstruction material cement
Construction material cement
 
Defects in buildings & remedies
Defects in buildings & remediesDefects in buildings & remedies
Defects in buildings & remedies
 

En vedette (17)

Quality Control for Masonry
Quality Control for MasonryQuality Control for Masonry
Quality Control for Masonry
 
Roof Specifications
Roof SpecificationsRoof Specifications
Roof Specifications
 
Specifications for rcc
Specifications for rcc Specifications for rcc
Specifications for rcc
 
Detailing : Exterior Wall Assemblies
Detailing : Exterior Wall AssembliesDetailing : Exterior Wall Assemblies
Detailing : Exterior Wall Assemblies
 
Sound insulation materials
Sound insulation materials Sound insulation materials
Sound insulation materials
 
Cavity Walling
Cavity WallingCavity Walling
Cavity Walling
 
Presentation on walls and wall opening
Presentation on walls and wall openingPresentation on walls and wall opening
Presentation on walls and wall opening
 
Superstructure design
Superstructure designSuperstructure design
Superstructure design
 
Wall types
Wall typesWall types
Wall types
 
Heat & sound insulation
Heat & sound insulationHeat & sound insulation
Heat & sound insulation
 
Steel-vs-concrete and timber
Steel-vs-concrete and timberSteel-vs-concrete and timber
Steel-vs-concrete and timber
 
Cavity walls
Cavity wallsCavity walls
Cavity walls
 
Wall type
Wall typeWall type
Wall type
 
Wall types
Wall typesWall types
Wall types
 
ACH 121 Lecture 11b (Thermal & Moisture Protection)
ACH 121 Lecture 11b (Thermal & Moisture Protection)ACH 121 Lecture 11b (Thermal & Moisture Protection)
ACH 121 Lecture 11b (Thermal & Moisture Protection)
 
Sp10designers 2
Sp10designers 2Sp10designers 2
Sp10designers 2
 
ADVANTAGES OF CAVITY WALLS
ADVANTAGES OF CAVITY WALLSADVANTAGES OF CAVITY WALLS
ADVANTAGES OF CAVITY WALLS
 

Similaire à Moisture Control for Masonry

TECH TIPS Slab on Grade Vapor Retarders
TECH TIPS Slab on Grade Vapor RetardersTECH TIPS Slab on Grade Vapor Retarders
TECH TIPS Slab on Grade Vapor RetardersRandal Reifsnider
 
Housing construction technology
Housing construction technology Housing construction technology
Housing construction technology Ar.Vijay Kumar
 
Compaction
CompactionCompaction
CompactionGopinan
 
MEKA K SERIES CONCRETE BATCHING PLANTS
MEKA K SERIES CONCRETE BATCHING PLANTSMEKA K SERIES CONCRETE BATCHING PLANTS
MEKA K SERIES CONCRETE BATCHING PLANTSMehmet Kaybal 🌿
 
Deq wb-dwehs-wcu-waterwellconst 221591-7(1)
Deq wb-dwehs-wcu-waterwellconst 221591-7(1)Deq wb-dwehs-wcu-waterwellconst 221591-7(1)
Deq wb-dwehs-wcu-waterwellconst 221591-7(1)m_idrees520
 
Hastings future cities retrofit training manual v1.01
Hastings future cities retrofit training manual v1.01Hastings future cities retrofit training manual v1.01
Hastings future cities retrofit training manual v1.01EnergiseHastings
 
Steel In Concrete Overview(1)
Steel In Concrete Overview(1)Steel In Concrete Overview(1)
Steel In Concrete Overview(1)JOHN BARLOS
 
Nano-Clear Protects Concrete Block in Shower Stall
Nano-Clear Protects Concrete Block in Shower StallNano-Clear Protects Concrete Block in Shower Stall
Nano-Clear Protects Concrete Block in Shower StallIndustrial Solutions USA
 
Summary of water vapor reducing admixture technology
Summary of water vapor reducing admixture technologySummary of water vapor reducing admixture technology
Summary of water vapor reducing admixture technologyEd Grabinski, CSI
 
Waterproofing in building construction
Waterproofing in building constructionWaterproofing in building construction
Waterproofing in building constructionRiya Bagchi
 
FSBP Masonry Magazine January 2015
FSBP Masonry Magazine January 2015FSBP Masonry Magazine January 2015
FSBP Masonry Magazine January 2015Carrie Frillman
 
Ground Engineering Datasheets
Ground Engineering DatasheetsGround Engineering Datasheets
Ground Engineering Datasheetskavdavid
 
Experimental Characterization of Mortar Made From Local Fine Aggregate Used F...
Experimental Characterization of Mortar Made From Local Fine Aggregate Used F...Experimental Characterization of Mortar Made From Local Fine Aggregate Used F...
Experimental Characterization of Mortar Made From Local Fine Aggregate Used F...ijceronline
 
Selfcompacting concrete a anaysis-2-2
Selfcompacting concrete   a anaysis-2-2Selfcompacting concrete   a anaysis-2-2
Selfcompacting concrete a anaysis-2-2Santhanam Velayutham
 

Similaire à Moisture Control for Masonry (20)

Benefits of Building With Masonry
Benefits of Building With MasonryBenefits of Building With Masonry
Benefits of Building With Masonry
 
TECH TIPS Slab on Grade Vapor Retarders
TECH TIPS Slab on Grade Vapor RetardersTECH TIPS Slab on Grade Vapor Retarders
TECH TIPS Slab on Grade Vapor Retarders
 
Housing construction technology
Housing construction technology Housing construction technology
Housing construction technology
 
Kryton parking brochure2012
Kryton parking brochure2012Kryton parking brochure2012
Kryton parking brochure2012
 
Compaction
CompactionCompaction
Compaction
 
MEKA K SERIES CONCRETE BATCHING PLANTS
MEKA K SERIES CONCRETE BATCHING PLANTSMEKA K SERIES CONCRETE BATCHING PLANTS
MEKA K SERIES CONCRETE BATCHING PLANTS
 
Watershell Catalogue Specto Ct August 2009
Watershell Catalogue Specto Ct August 2009Watershell Catalogue Specto Ct August 2009
Watershell Catalogue Specto Ct August 2009
 
Deq wb-dwehs-wcu-waterwellconst 221591-7(1)
Deq wb-dwehs-wcu-waterwellconst 221591-7(1)Deq wb-dwehs-wcu-waterwellconst 221591-7(1)
Deq wb-dwehs-wcu-waterwellconst 221591-7(1)
 
Haener Board
Haener BoardHaener Board
Haener Board
 
Hastings future cities retrofit training manual v1.01
Hastings future cities retrofit training manual v1.01Hastings future cities retrofit training manual v1.01
Hastings future cities retrofit training manual v1.01
 
Steel In Concrete Overview(1)
Steel In Concrete Overview(1)Steel In Concrete Overview(1)
Steel In Concrete Overview(1)
 
Nano-Clear Protects Concrete Block in Shower Stall
Nano-Clear Protects Concrete Block in Shower StallNano-Clear Protects Concrete Block in Shower Stall
Nano-Clear Protects Concrete Block in Shower Stall
 
Lamanna engineering consultant
Lamanna engineering consultantLamanna engineering consultant
Lamanna engineering consultant
 
Polymeric Surge Arrester
Polymeric Surge ArresterPolymeric Surge Arrester
Polymeric Surge Arrester
 
Summary of water vapor reducing admixture technology
Summary of water vapor reducing admixture technologySummary of water vapor reducing admixture technology
Summary of water vapor reducing admixture technology
 
Waterproofing in building construction
Waterproofing in building constructionWaterproofing in building construction
Waterproofing in building construction
 
FSBP Masonry Magazine January 2015
FSBP Masonry Magazine January 2015FSBP Masonry Magazine January 2015
FSBP Masonry Magazine January 2015
 
Ground Engineering Datasheets
Ground Engineering DatasheetsGround Engineering Datasheets
Ground Engineering Datasheets
 
Experimental Characterization of Mortar Made From Local Fine Aggregate Used F...
Experimental Characterization of Mortar Made From Local Fine Aggregate Used F...Experimental Characterization of Mortar Made From Local Fine Aggregate Used F...
Experimental Characterization of Mortar Made From Local Fine Aggregate Used F...
 
Selfcompacting concrete a anaysis-2-2
Selfcompacting concrete   a anaysis-2-2Selfcompacting concrete   a anaysis-2-2
Selfcompacting concrete a anaysis-2-2
 

Plus de Scott Conwell, FAIA, FCSI (10)

Design Considerations for Large Format Tile
Design Considerations for Large Format TileDesign Considerations for Large Format Tile
Design Considerations for Large Format Tile
 
Cold Weather Requirements for Masonry Construction
Cold Weather Requirements for Masonry ConstructionCold Weather Requirements for Masonry Construction
Cold Weather Requirements for Masonry Construction
 
Flashing & Air Barrier
Flashing & Air BarrierFlashing & Air Barrier
Flashing & Air Barrier
 
Air Barrier & Flashing
Air Barrier & FlashingAir Barrier & Flashing
Air Barrier & Flashing
 
Terra Cotta Rainscreen
Terra Cotta RainscreenTerra Cotta Rainscreen
Terra Cotta Rainscreen
 
Brick Veneer Steel Stud Wall
Brick Veneer Steel Stud WallBrick Veneer Steel Stud Wall
Brick Veneer Steel Stud Wall
 
Brick and Block Cavity Wall
Brick and Block Cavity WallBrick and Block Cavity Wall
Brick and Block Cavity Wall
 
Tips for optimizing structural masonry
Tips for optimizing structural masonryTips for optimizing structural masonry
Tips for optimizing structural masonry
 
Designing with Tile
Designing with TileDesigning with Tile
Designing with Tile
 
Masonry for sustainability
Masonry for sustainabilityMasonry for sustainability
Masonry for sustainability
 

Dernier

SOCIAL AND HISTORICAL CONTEXT - LFTVD.pptx
SOCIAL AND HISTORICAL CONTEXT - LFTVD.pptxSOCIAL AND HISTORICAL CONTEXT - LFTVD.pptx
SOCIAL AND HISTORICAL CONTEXT - LFTVD.pptxiammrhaywood
 
Measures of Central Tendency: Mean, Median and Mode
Measures of Central Tendency: Mean, Median and ModeMeasures of Central Tendency: Mean, Median and Mode
Measures of Central Tendency: Mean, Median and ModeThiyagu K
 
Call Girls in Dwarka Mor Delhi Contact Us 9654467111
Call Girls in Dwarka Mor Delhi Contact Us 9654467111Call Girls in Dwarka Mor Delhi Contact Us 9654467111
Call Girls in Dwarka Mor Delhi Contact Us 9654467111Sapana Sha
 
URLs and Routing in the Odoo 17 Website App
URLs and Routing in the Odoo 17 Website AppURLs and Routing in the Odoo 17 Website App
URLs and Routing in the Odoo 17 Website AppCeline George
 
A Critique of the Proposed National Education Policy Reform
A Critique of the Proposed National Education Policy ReformA Critique of the Proposed National Education Policy Reform
A Critique of the Proposed National Education Policy ReformChameera Dedduwage
 
How to Make a Pirate ship Primary Education.pptx
How to Make a Pirate ship Primary Education.pptxHow to Make a Pirate ship Primary Education.pptx
How to Make a Pirate ship Primary Education.pptxmanuelaromero2013
 
18-04-UA_REPORT_MEDIALITERAСY_INDEX-DM_23-1-final-eng.pdf
18-04-UA_REPORT_MEDIALITERAСY_INDEX-DM_23-1-final-eng.pdf18-04-UA_REPORT_MEDIALITERAСY_INDEX-DM_23-1-final-eng.pdf
18-04-UA_REPORT_MEDIALITERAСY_INDEX-DM_23-1-final-eng.pdfssuser54595a
 
Software Engineering Methodologies (overview)
Software Engineering Methodologies (overview)Software Engineering Methodologies (overview)
Software Engineering Methodologies (overview)eniolaolutunde
 
Introduction to ArtificiaI Intelligence in Higher Education
Introduction to ArtificiaI Intelligence in Higher EducationIntroduction to ArtificiaI Intelligence in Higher Education
Introduction to ArtificiaI Intelligence in Higher Educationpboyjonauth
 
Organic Name Reactions for the students and aspirants of Chemistry12th.pptx
Organic Name Reactions  for the students and aspirants of Chemistry12th.pptxOrganic Name Reactions  for the students and aspirants of Chemistry12th.pptx
Organic Name Reactions for the students and aspirants of Chemistry12th.pptxVS Mahajan Coaching Centre
 
1029-Danh muc Sach Giao Khoa khoi 6.pdf
1029-Danh muc Sach Giao Khoa khoi  6.pdf1029-Danh muc Sach Giao Khoa khoi  6.pdf
1029-Danh muc Sach Giao Khoa khoi 6.pdfQucHHunhnh
 
Contemporary philippine arts from the regions_PPT_Module_12 [Autosaved] (1).pptx
Contemporary philippine arts from the regions_PPT_Module_12 [Autosaved] (1).pptxContemporary philippine arts from the regions_PPT_Module_12 [Autosaved] (1).pptx
Contemporary philippine arts from the regions_PPT_Module_12 [Autosaved] (1).pptxRoyAbrique
 
Separation of Lanthanides/ Lanthanides and Actinides
Separation of Lanthanides/ Lanthanides and ActinidesSeparation of Lanthanides/ Lanthanides and Actinides
Separation of Lanthanides/ Lanthanides and ActinidesFatimaKhan178732
 
Advanced Views - Calendar View in Odoo 17
Advanced Views - Calendar View in Odoo 17Advanced Views - Calendar View in Odoo 17
Advanced Views - Calendar View in Odoo 17Celine George
 
mini mental status format.docx
mini    mental       status     format.docxmini    mental       status     format.docx
mini mental status format.docxPoojaSen20
 
Privatization and Disinvestment - Meaning, Objectives, Advantages and Disadva...
Privatization and Disinvestment - Meaning, Objectives, Advantages and Disadva...Privatization and Disinvestment - Meaning, Objectives, Advantages and Disadva...
Privatization and Disinvestment - Meaning, Objectives, Advantages and Disadva...RKavithamani
 
Nutritional Needs Presentation - HLTH 104
Nutritional Needs Presentation - HLTH 104Nutritional Needs Presentation - HLTH 104
Nutritional Needs Presentation - HLTH 104misteraugie
 
Grant Readiness 101 TechSoup and Remy Consulting
Grant Readiness 101 TechSoup and Remy ConsultingGrant Readiness 101 TechSoup and Remy Consulting
Grant Readiness 101 TechSoup and Remy ConsultingTechSoup
 
“Oh GOSH! Reflecting on Hackteria's Collaborative Practices in a Global Do-It...
“Oh GOSH! Reflecting on Hackteria's Collaborative Practices in a Global Do-It...“Oh GOSH! Reflecting on Hackteria's Collaborative Practices in a Global Do-It...
“Oh GOSH! Reflecting on Hackteria's Collaborative Practices in a Global Do-It...Marc Dusseiller Dusjagr
 

Dernier (20)

SOCIAL AND HISTORICAL CONTEXT - LFTVD.pptx
SOCIAL AND HISTORICAL CONTEXT - LFTVD.pptxSOCIAL AND HISTORICAL CONTEXT - LFTVD.pptx
SOCIAL AND HISTORICAL CONTEXT - LFTVD.pptx
 
Measures of Central Tendency: Mean, Median and Mode
Measures of Central Tendency: Mean, Median and ModeMeasures of Central Tendency: Mean, Median and Mode
Measures of Central Tendency: Mean, Median and Mode
 
INDIA QUIZ 2024 RLAC DELHI UNIVERSITY.pptx
INDIA QUIZ 2024 RLAC DELHI UNIVERSITY.pptxINDIA QUIZ 2024 RLAC DELHI UNIVERSITY.pptx
INDIA QUIZ 2024 RLAC DELHI UNIVERSITY.pptx
 
Call Girls in Dwarka Mor Delhi Contact Us 9654467111
Call Girls in Dwarka Mor Delhi Contact Us 9654467111Call Girls in Dwarka Mor Delhi Contact Us 9654467111
Call Girls in Dwarka Mor Delhi Contact Us 9654467111
 
URLs and Routing in the Odoo 17 Website App
URLs and Routing in the Odoo 17 Website AppURLs and Routing in the Odoo 17 Website App
URLs and Routing in the Odoo 17 Website App
 
A Critique of the Proposed National Education Policy Reform
A Critique of the Proposed National Education Policy ReformA Critique of the Proposed National Education Policy Reform
A Critique of the Proposed National Education Policy Reform
 
How to Make a Pirate ship Primary Education.pptx
How to Make a Pirate ship Primary Education.pptxHow to Make a Pirate ship Primary Education.pptx
How to Make a Pirate ship Primary Education.pptx
 
18-04-UA_REPORT_MEDIALITERAСY_INDEX-DM_23-1-final-eng.pdf
18-04-UA_REPORT_MEDIALITERAСY_INDEX-DM_23-1-final-eng.pdf18-04-UA_REPORT_MEDIALITERAСY_INDEX-DM_23-1-final-eng.pdf
18-04-UA_REPORT_MEDIALITERAСY_INDEX-DM_23-1-final-eng.pdf
 
Software Engineering Methodologies (overview)
Software Engineering Methodologies (overview)Software Engineering Methodologies (overview)
Software Engineering Methodologies (overview)
 
Introduction to ArtificiaI Intelligence in Higher Education
Introduction to ArtificiaI Intelligence in Higher EducationIntroduction to ArtificiaI Intelligence in Higher Education
Introduction to ArtificiaI Intelligence in Higher Education
 
Organic Name Reactions for the students and aspirants of Chemistry12th.pptx
Organic Name Reactions  for the students and aspirants of Chemistry12th.pptxOrganic Name Reactions  for the students and aspirants of Chemistry12th.pptx
Organic Name Reactions for the students and aspirants of Chemistry12th.pptx
 
1029-Danh muc Sach Giao Khoa khoi 6.pdf
1029-Danh muc Sach Giao Khoa khoi  6.pdf1029-Danh muc Sach Giao Khoa khoi  6.pdf
1029-Danh muc Sach Giao Khoa khoi 6.pdf
 
Contemporary philippine arts from the regions_PPT_Module_12 [Autosaved] (1).pptx
Contemporary philippine arts from the regions_PPT_Module_12 [Autosaved] (1).pptxContemporary philippine arts from the regions_PPT_Module_12 [Autosaved] (1).pptx
Contemporary philippine arts from the regions_PPT_Module_12 [Autosaved] (1).pptx
 
Separation of Lanthanides/ Lanthanides and Actinides
Separation of Lanthanides/ Lanthanides and ActinidesSeparation of Lanthanides/ Lanthanides and Actinides
Separation of Lanthanides/ Lanthanides and Actinides
 
Advanced Views - Calendar View in Odoo 17
Advanced Views - Calendar View in Odoo 17Advanced Views - Calendar View in Odoo 17
Advanced Views - Calendar View in Odoo 17
 
mini mental status format.docx
mini    mental       status     format.docxmini    mental       status     format.docx
mini mental status format.docx
 
Privatization and Disinvestment - Meaning, Objectives, Advantages and Disadva...
Privatization and Disinvestment - Meaning, Objectives, Advantages and Disadva...Privatization and Disinvestment - Meaning, Objectives, Advantages and Disadva...
Privatization and Disinvestment - Meaning, Objectives, Advantages and Disadva...
 
Nutritional Needs Presentation - HLTH 104
Nutritional Needs Presentation - HLTH 104Nutritional Needs Presentation - HLTH 104
Nutritional Needs Presentation - HLTH 104
 
Grant Readiness 101 TechSoup and Remy Consulting
Grant Readiness 101 TechSoup and Remy ConsultingGrant Readiness 101 TechSoup and Remy Consulting
Grant Readiness 101 TechSoup and Remy Consulting
 
“Oh GOSH! Reflecting on Hackteria's Collaborative Practices in a Global Do-It...
“Oh GOSH! Reflecting on Hackteria's Collaborative Practices in a Global Do-It...“Oh GOSH! Reflecting on Hackteria's Collaborative Practices in a Global Do-It...
“Oh GOSH! Reflecting on Hackteria's Collaborative Practices in a Global Do-It...
 

Moisture Control for Masonry

  • 1. MOISTURE CONTROL FOR MASONRY presented by International Masonry Institute
  • 2. International Union International of Bricklayers and Masonry Allied Craftworkers Institute LIFELONG LEARNING Pre-job and apprentice training Journeyman upgrade training Safety, scaffold, OSHA training Craftworker certification training Supervisor certification Sustainable Masonry Certification Program Contractor College
  • 3. BUILDING CODES IBC: the legally adopted model code MSJC: the referenced standard IBC supersedes MSJC at points of conflict MSJC date will be one year prior to companion IBC 2009 IBC goes with 2008 MSJC 2012 IBC goes with 2011 MSJC IBC & MSJC
  • 4. 2012 INTERNATIONAL BUILDING CODE CHAPTER 21 - MASONRY SECTION 2101 GENERAL 2101.2.6 Masonry Veneer Masonry veneer shall comply with the provisions of Chapter 14 or Chapter 6 of TMS 402/ACI 530/ASCE 5. SECTION 2104 CONSTRUCTION 2104.1 Masonry Construction Masonry construction shall comply with the requirements of Sections 2104.1.1 through 2104.4 and with TMS 402/ACI 530/ASCE 5.
  • 6. MOISTURE RESISTANCE Brick & mortar leak Wall system must address moisture penetration
  • 7. 2011 MSJC 2011 Building Code Requirements for Masonry Structures (TMS 402/ACI 530/ASCE 5) CHAPTER 6 - VENEER 6.1 GENERAL 6.1.2 Design of Anchored Veneer e) Water will penetrate the veneer and the wall system should be designed, detailed, and constructed to prevent water penetration into the building. (commentary) 6.1.6 General Design Requirements Water penetration through the exterior veneer is expected. The wall system must be designed and constructed to prevent water from entering the building. (commentary)
  • 9. MOISTURE RESISTANCE REQUIRED by Code Air space Flashing Weep holes Air Barrier* OPTIONAL Mortar Dropping Collection Device (MDCD) * depends on project location
  • 10.
  • 12. MOISTURE RESISTANCE  2” recommended  1” min. for veneers, per code  4½” max. btwn. brick & backup AIR SPACE © 2009 INTERNATIONAL MASONRY INSTITUTE
  • 13. MOISTURE RESISTANCE 2” recommended 1” min. for veneers per ACI 530 Code 4½” max. between brick and backup AIR SPACE © 2009 INTERNATIONAL MASONRY INSTITUTE
  • 14. MOISTURE RESISTANCE No mortar bridging across the cavity! AIR SPACE © 2009 INTERNATIONAL MASONRY INSTITUTE
  • 15. MOISTURE RESISTANCE 2” 2” AIR SPACE
  • 17. MOISTURE RESISTANCE Bevel the bed joints CLEAN CAVITIES
  • 18. MOISTURE RESISTANCE Mortar Dropping Collection Device (MDCD) CLEAN CAVITIES
  • 19. MOISTURE RESISTANCE Mortar Dropping Collection Device (MDCD) CLEAN CAVITIES
  • 20. CONCRETE MASONRY BACKUP AIR/WATER/VAPOR BARRIER AS REQ’D BRICK & BLOCK CAVITY WALL HORIZONTAL JOINT REINFORCEMENT W/ INTEGRAL WALL TIES 2” AIR SPACE RECOMMENDED; 1” MIN. REQ’D FOR DRAINAGE WALLS THRU-WALL FLASHING TO EXTEND PAST TOP OF CAVITY INSERT CAVITY INSERT/MORTAR COLLECTION DEVICE RIGID INSUL. BRICK VENEER WEEP VENT METAL DRIP EDGE SET IN MASTIC OR SEALANT International Masonry Institute MASONRY DETAILING FOUNDATION DETAIL SERIES DETAIL 01.102 REV. 10/14/07 800-IMI-0988 www.imiweb.org © 2007 INTERNATIONAL MASONRY INSTITUTE
  • 21. MOISTURE RESISTANCE Full-height cavity insert CLEAN CAVITIES
  • 24. AIR BARRIER: DEFINITION The International Energy Conservation Code defines an air barrier as: “material(s) assembled and joined together to provide a barrier to air leakage through the building envelope. An air barrier may be a single material or a combination of materials.” ABAA and IECC recognize air barriers in terms of: • materials • components • assemblies • systems
  • 25. AIR BARRIER: DEFINITION A material, assembly, or system that restricts air leakage (flow)… L/s (cf/m) over an area of wall… m2 (sf) at a difference of air pressure Pa (psf) Source: ASTM E 2178, Standard Test Method for Air Permeance of Building Materials
  • 26. IBC: WATER-RESISTIVE BARRIER 2012 International Building Code CHAPTER 14 – EXTERIOR WALLS Section 1403 Performance Requirements 1403.2 Weather protection Exterior walls shall provide the building with a weather-resistant exterior wall envelope. The envelope shall be designed and constructed in such a manner as to prevent the accumulation of water within the wall assembly by providing a water-resistive barrier behind the exterior veneer, as described in Section 1404.2. Protection against condensation in the exterior wall assembly shall be provided in accordance with Section 1405.3 Exception: A weather-resistant exterior wall envelope shall not be required over masonry walls designed in accordance with Chapter 21.
  • 27. MSJC: WATER-RESISTANT MEMBRANE 2011 Building Code Requirements for Masonry Structures (TMS 402/ACI 530/ASCE 5) CHAPTER 6 - VENEER 6.1 GENERAL 6.1.6 General Design Requirements 6.1.6.1 Design and detail the backing system of exterior veneer to resist water penetration. Exterior sheathing shall be covered with a water-resistant membrane, unless the sheathing is water resistant and the joints are sealed.
  • 28. IBC REFERENCES IECC 2012 International Building Code CHAPTER 13 – ENERGY EFFICIENCY Section 1301 GENERAL 1301.1.1 Criteria Buildings shall be designed and constructed in accordance with the International Energy Conservation Code.
  • 29. AIR LEAKAGE 2012 International Energy Conservation Code CHAPTER 4 COMMERCIAL ENERGY EFFICIENCY SECTION C402 BUILDING ENVELOPE REQUIREMENTS C402.4 Air Leakage (Mandatory) The thermal envelope of buildings shall comply with Sections C402.4.1 through C402.4.8
  • 30. AIR BARRIERS 2012 International Energy Conservation Code CHAPTER 4 COMMERCIAL ENERGY EFFICIENCY SECTION C402 BUILDING ENVELOPE REQUIREMENTS C402.4.1 Air Barriers A continuous air barrier shall be provided throughout the building thermal envelope. The air barriers shall be permitted to be located on the inside our outside of the building envelope, located within the assemblies composing the envelope, or any combination thereof. The air barrier shall comply with C402.4.1.1. and C402.4.1.2 Exception: Air barriers are not required in buildings located in Climate Zones 1, 2, and 3.
  • 31. AIR BARRIER CONSTRUCTION 2012 International Energy Conservation Code C402.4.1.1 Air Barrier Construction 1. The air barrier shall be continuous for all assemblies that are the thermal envelope of the building, and across the joints and assemblies.* * Not required if building envelope passes ASTM E779 Standard Test Method for Determining Air Leakage Rate by Fan Pressurization. 2. Air barrier joints and seams shall be sealed, including sealing transitions in places and changes in materials. Air barrier penetrations shall be sealed in accordance with Section C402.4.2 The joints and seals shall be securely installed… as not to … impair its ability to resist positive and negative pressure from wind, stack effect, and mechanical ventilation.
  • 32. AIR BARRIER COMPLIANCE OPTIONS 2012 International Energy Conservation Code C402.4.1.2 Air Barrier Compliance Options A continuous air barrier for the opaque building envelope shall comply with any one of the following: C402.4.1.2.1 Materials & Components or C402.4.1.2.2 Assemblies or C402.4.1.2.3 System
  • 33. AIR BARRIER DEFINITIONS An AB material is a primary material used to resist air leakage. An AB component is a product like sealant or tape used to create continuity between air barrier materials. An AB assembly is a collection of AB materials and components assembled together in a specific manner to create continuity. An AB system is a system of building assemblies within the building enclosure designed, installed, and integrated in such a manner as to stop the uncontrolled flow of air into and out of the building enclosure. Source: Air Barrier Association of America (ABAA)
  • 34. AIR BARRIER DEFINITIONS A material or component is an air barrier if it meets these maximum criteria: .02 L/s per m2 @ 75 Pa (.004 cfm/sf @ 1.56 psf) 1/2” sheet of gypsum board without seams, joints, or penetrations
  • 35. AIR BARRIER DEFINITIONS A material or component is an air barrier if it meets these maximum criteria: .02 L/s per m2 @ 75 Pa (.004 cfm/sf @ 1.56 psf) An assembly is an air barrier if it meets these maximum criteria: 0.2 L/s per m2 @ 75 Pa (0.04 cfm/sf @ 1.56 psf) A system is an air barrier if it meets these maximum criteria: 2.0 L/s per m2 @ 75 Pa (0.4 cfm/sf @ 1.56 psf)
  • 36. AIR BARRIER MATERIALS 2012 International Energy Conservation Code C402.4.1.2.1 Air Barrier Materials These materials meet the criteria of .02 L/s per m2 @ 75 Pa (.004 cfm/sf @ 1.56 psf) • 3/8” thick plywood • 3/8” thick OSB • 1/2” thick XPS insulation • 1/2” thick foil-backed polyisocyanurate insul. • 1½” thick, 1.5 pcf closed cell spray foam • 1/2” thick exterior or interior gyp bd. or cement bd. • 5/8” thick Portland cement/sand parge • 5/8” thick gypsum plaster • C.I.P. or precast concrete • Fully grouted CMU
  • 37. AIR BARRIER ASSEMBLIES 2012 International Energy Conservation Code C402.4.1.2.2 Air Barrier Assemblies These assemblies meet the criteria of 0.2 L/s per m2 @ 75 Pa (.04 cfm/sf @ 1.56 psf) • Concrete masonry walls coated with one application of block filler and two applications of a paint or sealer coating. • A Portland cement/sand parge, stucco or plaster minimum 1/2” thick.
  • 38. AIR BARRIER SYSTEM 2012 International Energy Conservation Code C402.4.1.2.3 Building Test Completed building (system) shall be tested and meet criteria of 2.0 L/s per m2 @ 75 Pa (0.4 cfm/sf @ 1.56 psf) ASTM E779 Standard Test Method for Determining Air Leakage Rate by Fan Pressurization
  • 39. AIR BARRIER ATTRIBUTES • Impermeable • Continuous Coverage • Bridging Capability • Expected Service Life (Durability) • Secure • Environmentally & Worker Friendly
  • 40. MOISTURE PENETRATION RESISTANCE Parged Mortar Sprayed Bituminous Spray polyurethane foam Rolled Bituminous Sheet membranes AIR BARRIER TYPES
  • 41. MOISTURE PENETRATION RESISTANCE Prep wall by caulking any open joints Tool caulk joints AIR BARRIER © 2009 INTERNATIONAL MASONRY INSTITUTE
  • 42. MOISTURE PENETRATION RESISTANCE Spray on first coat Roll membrane to required thickness AIR BARRIER © 2009 INTERNATIONAL MASONRY INSTITUTE
  • 43. OPTION 1: AB, FLASHING OPTION 2: FLASHING, AB
  • 44. AIR BARRIER PENETRATIONS & JOINTS 2012 International Energy Conservation Code C402.4.2 Air Barrier Penetrations Penetrations of the air barrier and paths of air leakage shall be caulked, gasketed, or otherwise sealed. Joints and seals shall be sealed in the same manner or taped or covered with a moisture permeable wrapping material. Joints and seals shall be securely installed in or on the joint for its entire length so as not to dislodge, loosen or otherwise impair its ability to resist positive and negative pressure from wind, stack effect and mechanical ventilation.
  • 46. MOISTURE RESISTANCE Design and detail flashing and weep holes in exterior veneer wall systems to resist water penetration into the building interior. ACI 530-02/ASCE 5-02/TMS 402-02, Chapter 6 Veneer, Section 6.1.5.2  What type?  What thickness?  What locations? FLASHING – CODE REQUIREMENT
  • 47. MOISTURE RESISTANCE “Approved, corrosion-resistant flashing” shall be provided in the exterior wall envelope in such a manner as to prevent entry of water into the wall cavity or penetration of water into the building structural framing components. ACI 530-02/ASCE 5-02/TMS 402-02, Chapter 6 Veneer, Section 6.1.5.2 FLASHING TYPES
  • 48.
  • 49.
  • 50. MOISTURE RESISTANCE Plastic flashing should be at least 30 mil thick BIA Tech Note 28: Anchored Brick Veneer Wood Frame Construction FLASHING THICKNESS
  • 51. MOISTURE RESISTANCE sills shelf angles top of wall base of wall above openings FLASHING APPLICATIONS
  • 52. MOISTURE RESISTANCE Beneath the first course of masonry above finished ground level Other points of support such as shelf angles and lintels At top of all exterior window and door openings At intersection of chimneys Under sills At wall and roof intersections ACI 530-02/ASCE 5-02/TMS 402-02, Chapter 6 Veneers FLASHING LOCATIONS
  • 55. FLASHING – BASE OF WALL
  • 56. MOISTURE RESISTANCE Keep top of foundation above grade if possible Don’t bury the weeps! RISING DAMP
  • 57. MOISTURE RESISTANCE best practice alternate FOUNDATION HEIGHT © 2009 INTERNATIONAL MASONRY INSTITUTE
  • 58. 2” AIR SPACE RECOMMENDED; 1” MIN. REQ’D FOR DRAINAGE WALLS AIR/MOISTURE/VAPOR BARRIER AS REQUIRED HORIZONTAL JOINT REIN- FORCEMENT W/ EYE & PINTLE WALL TIES @ 16” O.C. RIGID INSULATION GROUT & REINFORCEMENT AS REQUIRED RETURN FLASHING INTO BED JOINT OF BLOCK CONCRETE MASONRY BACKUP BRICK VENEER FLEXIBLE FLASHING – SEAL & ADHERE TO DRIP EDGE WEEP VENT INSERTS (TOP & BOTTOM OF WALL; SEE NOTES ON COMPARTMENTALIZATION) DRIP EDGE – SEAL AND ADHERE TO FOUNDATION FOUNDATION DETAIL FLEX. FLASHING IN CMU, DRIP EDGE DETAIL 01.030.0305 REV. 07/01/09 © 2009 INTERNATIONAL MASONRY INSTITUTE
  • 59. 2” AIR SPACE RECOMMENDED; 1” MIN. REQ’D FOR DRAINAGE WALLS AIR/MOISTURE/VAPOR BARRIER AS REQUIRED HORIZONTAL JOINT REIN- FORCEMENT W/ EYE & PINTLE WALL TIES @ 16” O.C. RIGID INSULATION GROUT & REINFORCEMENT AS REQUIRED MECH. FASTENED TERMINATION BAR W/ CONT. SEALANT @ TOP CONCRETE MASONRY BACKUP BRICK VENEER FLEXIBLE FLASHING – SEAL & ADHERE TO DRIP EDGE WEEP VENT INSERTS (TOP & BOTTOM OF WALL; SEE NOTES ON COMPARTMENTALIZATION) DRIP EDGE – SEAL AND ADHERE TO FOUNDATION FOUNDATION DETAIL FLEX. FLASHING, DRIP EDGE, TERM. BAR DETAIL 01.030.0301 REV. 07/01/09 © 2009 INTERNATIONAL MASONRY INSTITUTE
  • 60. 2” AIR SPACE RECOMMENDED; 1” MIN. REQ’D FOR DRAINAGE WALLS AIR/MOISTURE/VAPOR BARRIER AS REQUIRED HORIZONTAL JOINT REIN- FORCEMENT W/ EYE & PINTLE WALL TIES @ 16” O.C. RIGID INSULATION GROUT & REINFORCEMENT AS REQUIRED MECH. FASTENED TERMINATION BAR W/ CONT. SEALANT @ TOP CONCRETE MASONRY BACKUP BRICK VENEER FLEXIBLE FLASHING – SEAL MORTAR DROPPING & ADHERE TO DRIP EDGE COLLECTION DEVICE (MDCD) WEEP VENT INSERTS (TOP & BOTTOM OF WALL; SEE NOTES ON COMPARTMENTALIZATION) DRIP EDGE – SEAL AND ADHERE TO FOUNDATION FOUNDATION DETAIL FLEX. FLASHING, DRIP EDGE, TERM. BAR, MDCD DETAIL 01.030.0302 REV. 07/01/09 © 2009 INTERNATIONAL MASONRY INSTITUTE
  • 61. 2” AIR SPACE RECOMMENDED; 1” MIN. REQ’D FOR DRAINAGE WALLS AIR/MOISTURE/VAPOR BARRIER AS REQUIRED HORIZONTAL JOINT REIN- FORCEMENT W/ EYE & PINTLE WALL TIES @ 16” O.C. RIGID INSULATION GROUT & REINFORCEMENT AS REQUIRED MECH. FASTENED TERMINATION BAR W/ CONT. SEALANT @ TOP CONCRETE MASONRY BACKUP BRICK VENEER FLEXIBLE FLASHING FLUSH MORTAR DROPPING W/ OUTSIDE FACE OF BRICK COLLECTION DEVICE (MDCD) WEEP VENT INSERTS (TOP & BOTTOM OF WALL; SEE NOTES ON COMPARTMENTALIZATION) FOUNDATION DETAIL FLEX. FLASHING NO DRIP; TERM. BAR, MDCD DETAIL 01.030.0303 REV. 07/01/09 © 2009 INTERNATIONAL MASONRY INSTITUTE
  • 62. 2” AIR SPACE RECOMMENDED; 1” MIN. REQ’D FOR DRAINAGE WALLS AIR/MOISTURE/VAPOR BARRIER AS REQUIRED HORIZONTAL JOINT REIN- FORCEMENT W/ EYE & PINTLE WALL TIES @ 16” O.C. RIGID INSULATION GROUT & REINFORCEMENT AS REQUIRED RETURN FLASHING INTO BED JOINT OF BLOCK CONCRETE MASONRY BACKUP BRICK VENEER FLEXIBLE FLASHING – SEAL MORTAR DROPPING & ADHERE TO DRIP EDGE COLLECTION DEVICE (MDCD) WEEP VENT INSERTS (TOP & BOTTOM OF WALL; SEE NOTES ON COMPARTMENTALIZATION) DRIP EDGE – SEAL AND ADHERE TO FOUNDATION FOUNDATION DETAIL FLEX. FLASHING IN CMU, DRIP EDGE DETAIL 01.030.0306 REV. 07/01/09 © 2009 INTERNATIONAL MASONRY INSTITUTE
  • 63. 2” AIR SPACE RECOMMENDED; 1” MIN. REQ’D FOR DRAINAGE WALLS AIR/MOISTURE/VAPOR BARRIER AS REQUIRED HORIZONTAL JOINT REIN- FORCEMENT W/ EYE & PINTLE WALL TIES @ 16” O.C. RIGID INSULATION GROUT & REINFORCEMENT AS REQUIRED MECH. FASTENED TERMINATION BAR W/ CONT. SEALANT @ TOP BRICK VENEER CONCRETE MASONRY BACKUP MORTAR DROPPING COLLECTION DEVICE (MDCD) METAL FLASHING W/ INTEGRAL DRIP EDGE WEEP VENT INSERTS (TOP & BOTTOM OF WALL; SEE NOTES ON COMPARTMENTALIZATION) FOUNDATION DETAIL METAL FLASHING, TERM. BAR, MDCD DETAIL 01.030.0311 REV. 07/01/09 © 2009 INTERNATIONAL MASONRY INSTITUTE
  • 67. WOOD BLOCKING FOR WINDOW ANCHORAGE ALTERNATE FLASHING LOCATION WINDOW STOOL NOT SHOWN WINDOW ASSEMBLY FLASHING RIGID FLASHING TO SPAN END DAM ACROSS DRAINAGE CAVITY RIGID INSULATION HORIZONTAL JOINT REINFORCEMENT MASONRY EXPANSION JOINT AS REQUIRED MASONRY SILL W/ 1/8” x 1/8” CONT. SAW-CUT DRIP SILL DETAIL MASONRY SILL, RIGID FLASHING DETAIL 01.030.0401 REV. 07/28/09 © 2009 INTERNATIONAL MASONRY INSTITUTE
  • 69. MOISTURE RESISTANCE Best practice: Use limestone or precast sills Slope rowlocks at least 15º SILLS
  • 73. MOISTURE RESISTANCE Larger unit modules make end dams difficult FLASHING – END DAMS
  • 74. BRICK & BLOCK CAVITY WALL DETAIL FEATURES EXTERIOR VIEW INTERIOR VIEW • LOOSE LINTEL AT BRICK • STEEL ANGLES AT BLOCK • LIGHT GAUGE SUPPORT International Masonry Institute ACROSS CAVITY MASONRY DETAILING HEAD DETAIL STEEL LINTEL W/ DOUBLE ANGLE SERIES DETAIL 01.303 REV. 09/06/07 800-IMI-0988 www.imiweb.org © 2007 INTERNATIONAL MASONRY INSTITUTE
  • 75. BRICK & BLOCK CAVITY WALL INTERIOR VIEW DETAIL FEATURES • LOOSE LINTEL AT BRICK • BOND BEAM AT BLOCK International Masonry Institute • LIGHT GAUGE SUPPORT EXTERIOR VIEW ACROSS CAVITY MASONRY DETAILING HEAD DETAIL STEEL LINTEL & BOND BEAM SERIES DETAIL 01.301 REV. 09/04/07 800-IMI-0988 www.imiweb.org © 2007 INTERNATIONAL MASONRY INSTITUTE
  • 76. SPANNING OPENINGS Poly-wrapped steel angles used for temporary support CAST-IN-PLACE MASONRY LINTEL
  • 77. SPANNING OPENINGS Precast masonry lintel fabricated on the ground PRECAST LINTELS
  • 78. SPANNING OPENINGS Lintel is hoisted by lift PRECAST LINTELS
  • 79. SPANNING OPENINGS Precast lintel set into place PRECAST LINTELS
  • 80. SPANNING OPENINGS 10-foot span PRECAST LINTELS
  • 83. 2” AIR SPACE RECOMMENDED; 1” HORIZONTAL JOINT MIN. REQ’D FOR BRICK & BLOCK CAVITY WALL REINFORCEMENT W/ DRAINAGE WALLS INTEGRAL WALL TIES RIGID INSUL. THRU-WALL FLASHING W/ METAL DRIP EDGE SET IN ADJUSTABLE MASTIC OR SEALANT SHELF ANGLE WEEP/VENT TYPICAL FACE ADJUSTABLE BRICK ABOVE & SHELF ANGLE BELOW ANGLE SEALANT & BACKER ROD International Masonry Institute COMPRESSIBLE FILLER, OPTIONAL MASONRY DETAILING SHELF ANGLE DETAIL TYP. FACE BRICK SERIES DETAIL 01.501 REV. 06/19/08 800-IMI-0988 www.imiweb.org © 2008 INTERNATIONAL MASONRY INSTITUTE
  • 84. HORIZONTAL JOINT 2” AIR SPACE REINFORCEMENT W/ RECOMMENDED; 1” INTEGRAL WALL TIES MIN. REQ’D FOR DRAINAGE WALLS BRICK & BLOCK CAVITY WALL THRU-WALL FLASHING W/ METAL DRIP EDGE SET IN MASTIC OR SEALANT RIGID INSUL. WEEP/VENT ADJUSTABLE. SHELF ANGLE LIPPED BRICK, OPTIONAL SEALANT & BACKER ROD International Masonry Institute COMPRESSIBLE FILLER, OPTIONAL MASONRY DETAILING SHELF ANGLE DETAIL – LIPPED BRICK SERIES DETAIL 01.502 REV. 10/14/07 800-IMI-0988 www.imiweb.org © 2007 INTERNATIONAL MASONRY INSTITUTE
  • 85. MOISTURE RESISTANCE Too many relieving angles FLASHING – RELIEVING ANGLES
  • 88. CMU BACKUP FACE BRICK CAVITY INSUL. THRU-WALL BRICK & BLOCK CAVITY WALL FLASHING ROOF MEMBRANE CUT BLOCK BELOW FLASHING COUNTER- FLASHING SHEET METAL RECEIVER THRU-WALL FLASHING WEEP VENT TERMINATION BAR W/ CONT. SEALANT ROOF STRUCTURE HORIZONTAL JOINT REINF. International Masonry Institute @ 16” O.C. W/ INTEGRAL WALL TIES MASONRY DETAILING ROOF DETAIL HIGH WALL – LOW ROOF SERIES DETAIL 01.704 REV. 11/6/07 800-IMI-0988 www.imiweb.org © 2007 INTERNATIONAL MASONRY INSTITUTE
  • 90. FLASHING – TOP OF WALL
  • 91. BRICK & BLOCK CAVITY WALL MASONRY COPING: LIMESTONE, CAST STONE, CALCIUM SILICATE, OR PRECAST CONCRETE; OVERHANG S.S. DOWEL W/ SEALANT MASONRY WALL 1½” MIN.; SLOPED AROUND PENETRATIONS TOP THROUGH FLASHING 1/8” SAW-CUT DRIP, BOTH SIDES OF WALL CAP SEE DETAIL 01.759 FOR WALL CAP JOINT OPTIONS SEALANT & BACKER ROD, BOTH SIDES THROUGH-WALL OF WALL CAP FLASHING W/ 1/2” DRIP EDGE GROUT OR MORTAR FILL FOR DOWEL ANCHORAGE AND FLASHING SUPPORT SEALANT BELOW DRIP, OPT. (NOT SHOWN) MESH TO RETAIN GROUT OR MORTAR FILL DRAINAGE CAVITY GROUT & REINFORCING FACE BRICK AS REQ’D. HORIZONTAL JOINT RIGID INSULATION REINFORCEMENT W/ WALL TIES International Masonry Institute MASONRY DETAILING MASONRY WALL CAP FILLED CAVITY SERIES DETAIL 01.752 REV. 11/04/08 800-IMI-0988 www.imiweb.org © 2008 INTERNATIONAL MASONRY INSTITUTE
  • 92. BRICK & BLOCK CAVITY WALL MASONRY COPING: LIMESTONE, CAST STONE, CALCIUM SILICATE, OR S.S. DOWEL W/ SEALANT PRECAST CONCRETE; OVERHANG AROUND PENETRATIONS MASONRY WALL 1½” MIN.; SLOPED THROUGH FLASHING TOP 1/8” SAW-CUT DRIP, BOTH SIDES OF WALL CAP SEE DETAIL 01.759 FOR WALL CAP JOINT OPTIONS SEALANT & BACKER ROD, BOTH SIDES CANTED S.S. THRU-WALL OF WALL CAP FLASHING W/ 1/2” EXPOSED DRIP EDGE FACE BRICK SLOPED MORTAR BED TO SUPPORT CANTED FLASHING, SEALANT BELOW DRIP, OPT. OPT. (NOT SHOWN) RIGID INSULATION OPEN DRAINAGE CAVITY, OPTIONAL ABOVE ROOF LINE; ALSO SEE DETAIL GROUT & REINFORCING 01.752 AS REQ’D. HORIZONTAL JOINT REINFORCEMENT W/ WALL TIES International Masonry Institute MASONRY DETAILING MASONRY WALL CAP OPEN CAVITY SERIES DETAIL 01.751 REV. 11/04/08 800-IMI-0988 www.imiweb.org © 2008 INTERNATIONAL MASONRY INSTITUTE
  • 93. MOISTURE RESISTANCE Drill through flashing for anchor Seal around dowel penetration TOP OF WALL
  • 94. SINGLE WYTHE BLOCK MASONRY COPING: LIMESTONE, CAST STONE, CALCIUM SILICATE, OR PRECAST CONCRETE; OVERHANG MASONRY WALL 1½” MIN.; SLOPED TOP SEE DETAIL 01.759 FOR S.S. DOWEL W/ SEALANT WALL CAP JOINT OPTIONS AROUND PENETRATIONS THROUGH FLASHING S.S. FLASHING DRIP, SEALANT & BACKER BOTH SIDES OF CAP ROD, BOTH SIDES OF WALL CAP 1/8” SAW-CUT DRIP, BOTH SIDES OF WALL CAP GROUT OR MORTAR FILL FOR DOWEL ANCHORAGE AND FLASHING SUPPORT SEALANT BELOW DRIP, OPT. (NOT SHOWN) MESH TO RETAIN GROUT OR MORTAR FILL HORIZONTAL JOINT REINFORCEMENT International Masonry Institute MASONRY DETAILING MASONRY WALL CAP SINGLE WYTHE CMU SERIES DETAIL 03.701 REV. 11/04/08 800-IMI-0988 www.imiweb.org © 2008 INTERNATIONAL MASONRY INSTITUTE
  • 96. MOISTURE RESISTANCE Rowlock caps not Limestone, manufactured stone, or recommended precast concrete caps are better TOP OF WALL
  • 97. BRICK & BLOCK CAVITY WALL OPTION 1 OPTION 2 TOOLED MORTAR JOINT RAKE BACK MORTAR AND APPLY SEALANT JOINT OPTION 3 SEALANT AND BACKER ROD Rowlock caps not International Masonry Institute recommended MASONRY DETAILING MASONRY COPING JOINTS SERIES DETAIL 01.759 REV. 11/04/08 800-IMI-0988 www.imiweb.org © 2008 INTERNATIONAL MASONRY INSTITUTE
  • 99. MOISTURE RESISTANCE Damage is more severe below joints in coping Freeze-thaw damage Flashing is held back from face at top courses FLASHING – PROBLEMS TO AVOID
  • 101. MOISTURE RESISTANCE How far should flashing extend? Too much! Not enough! FLASHING – DRIP EDGES
  • 102. MOISTURE RESISTANCE Metal drip edge is best practice! “The flashing shall extend to the surface of the exterior wall finish, and shall be installed to prevent water from reentering the exterior wall envelope.” - IRC Section R703 Flashing FLASHING – DRIP EDGES
  • 103. 3/4” MIN. OVERLAP, SEALED W/ MFR-APPROVED ADHESIVE 1/2” MIN. IF RUBBERIZED ASPHALT IS USED FOR FLEXIBLE FLASHING, TO PREVENT DROOL FLEXIBLE THRU-WALL FLASHING METAL DRIP EDGE W/ HEM, 30º OR 45º FROM HORIZONTAL, SEALED TO FOUNDATION W/ MFR.-APPROVED ADHESIVE 1/4” – 3/4” 1 5/8” MIN. METAL DRIP EDGE DETAIL 15.000.0201 REV. 05/18/09 © 2009 INTERNATIONAL MASONRY INSTITUTE
  • 104. MOISTURE RESISTANCE Lap all seams …and adequately seal! FLASHING – PROBLEMS TO AVOID
  • 105. PRIMER PER RETURN FLASHING INTO MANUF’R BLOCK COURSE (SHOWN) OR SECURE TO BACKUP W/ TERMINATION BAR SEAL FLASHING LAPS W/ MASTIC PER MANUF’R 6” LAP DRIP EDGE SET IN SEALANT SUBJECT OF DETAIL EXCLUDED FROM SUBJECT THROUGH-WALL FLASHING OVERLAPS (LAPS) FLASHING DRIP EDGE LAPS, TERM. BAR, FACE BRICK, AND SEALING RECOMMENDATIONS CAVITY INSULATION, AND OTHER WALL COMPONENTS FLASHING LAP DIAGRAM 15.410.4101 REV. 02/10/11 © 2009 INTERNATIONAL MASONRY INSTITUTE
  • 106. OUTER FACE OF MASONRY THROUGH-WALL FLASHING LAPPED AND SEALED OUTER FACE OF MASONRY NOTCHED DRIP EDGE 3/4”± METAL DRIP W/ HEMMED EDGE SET IN MASTIC OR SEALANT NOTCH DRIP EDGE FOR BUTT JOINT, International Masonry Institute SEE INSET ABOVE masonry detailing DRIP EDGE DETAIL series DETAIL 03.01 REV. 02/13/07 1-800-IMI-0988 www.imiweb.org © 2007 INTERNATIONAL MASONRY INSTITUTE
  • 107. MOISTURE RESISTANCE 6” LAP FLASHING – LAPS
  • 108. MOISTURE RESISTANCE Seal laps FLASHING LAPS
  • 110. MOISTURE RESISTANCE Keep top of foundation above grade Don’t bury the weeps! FLASHING – INSTALLATION
  • 111. MOISTURE RESISTANCE Flashing must be intact! FLASHING – PROBLEMS TO AVOID
  • 112. MOISTURE RESISTANCE Hold rubberized as- Don’t use membrane phalt back from face as a drip edge FLASHING – PROBLEMS TO AVOID
  • 113. MOISTURE RESISTANCE not stable Avoid using PVC FLASHING – PROBLEMS TO AVOID
  • 114. MOISTURE RESISTANCE Avoid sharp corners Use rounded corners FLASHING – PROBLEMS TO AVOID
  • 115. MOISTURE RESISTANCE Flashing held back from face FLASHING – PROBLEMS TO AVOID
  • 117. MOISTURE RESISTANCE Flashing discontinuous Continuous flashing at corner FLASHING – CORNERS
  • 118. OUTSIDE CORNER FLASHING PIECE VIEW OF FINISHED CONTINUOUS FLASHING INSTALLATION (DRIP EDGES NOT SHOWN) INSIDE CORNER FLASHING PIECE OVERLAP FLASHING NOTE: FLASHING DRIP EDGES NOT SHOWN FOR CLARITY FLASHING CORNERS DETAIL 15.000.0204 REV. 08/24/09 © 2009 INTERNATIONAL MASONRY INSTITUTE
  • 119. NOTE: FLASHING DRIP EDGE NOT SHOWN FOR CLARITY FLASHING CORNERS DETAIL 15.000.0204.PH REV. 08/24/09 © 2009 INTERNATIONAL MASONRY INSTITUTE
  • 120. MOISTURE RESISTANCE Field-applied corner boot FLASHING – CORNERS
  • 122. NOTE: STRUCTURAL ELEMENTS MAY VARY, AND ARE SHOWN FOR ILLUSTRATION ONLY CAVITY INSULATION NOT SHOWN FOR CLARITY OF DETAIL CARRY FLASHING ½” MIN. BEYOND END OF LINTEL AND TURN UP TO FORM END DAM IN HEAD JOINT 2” RECOMMENDED; 1” MIN. SEALANT EXTEND FLASHING FLUSH OR BEYOND FACE OF MASONRY END DAM DIAGRAM FIELD-FORMED FLASHING END DAM DIAGRAM 01.410.0201 REV. 02/04/11 © 2009 INTERNATIONAL MASONRY INSTITUTE
  • 123. NOTE: STRUCTURAL ELEMENTS MAY VARY, AND ARE SHOWN FOR ILLUSTRATION ONLY CAVITY INSULATION NOT SHOWN FOR CLARITY OF DETAIL CARRY FLASHING ½” MIN. BEYOND END OF LINTEL PREFABRICATED END DAM IN HEAD JOINT; SET IN MASTIC IF FLASHING IS NOT SELF-ADHERING. END DAM PLACED PRIOR TO THROUGH-WALL FLASHING 2” RECOMMENDED; 1” MIN. EXTEND FLASHING SEALANT FLUSH OR BEYOND FACE OF MASONRY END DAM DIAGRAM PREFABRICATED FLASHING END DAM DIAGRAM 01.410.0202 REV. 02/04/11 © 2009 INTERNATIONAL MASONRY INSTITUTE
  • 128. MOISTURE RESISTANCE Weep holes shall be at least 3/16” in diameter and spaced less than 33” on center. International Residential Code 2000, Section R703.7.6 Weep Holes ACI 530-02/ASCE 5-02/TMS 402-02, Chapter 6 Veneer, Section 6.1.5.2 Best practice: 16” o.c. max for rope wicks, 24” o.c. for open head joints or vents WEEP HOLES
  • 129. MOISTURE RESISTANCE head joint fiber mesh vent plastic vent sleeve plastic sash cord tube cell vent WEEP HOLES - TYPES
  • 130. MOISTURE RESISTANCE “Weep holes shall be at least 3/16” in diameter and spaced less than 33” on center” International Residential Code 2000, Section R703.7.6 Weep Holes ACI 530-02/ASCE 5-02/TMS 402-02, Chapter 6 Veneer, Section 6.1.5.2 Best practice: Don’t use rope wicks! Best practice: 16” o.c. max for rope wicks (if you must), 24” o.c. for open head joints or vents WEEP HOLES – SIZE & SPACING
  • 131. Best practice: Don’t use rope wicks! RESIDENTIAL MASONRY WEEP HOLES Best practice: if you must use rope wicks, lay them continuously along bottom of cavity
  • 132. MOISTURE RESISTANCE Best practice: Don’t use rope wicks! Best practice: if you must use rope wicks, lay them continuously along bottom of cavity WEEP HOLES – PLACEMENT
  • 133. MOISTURE RESISTANCE  Vulnerable to mortar blockage  Do not ventilate WEEP HOLES – ROPE WICKS
  • 134. MOISTURE RESISTANCE  Vulnerable to mortar blockage  Do not ventilate WEEP HOLES – TUBES
  • 135. MOISTURE RESISTANCE  Better moisture relieve & ventilation  May attract insects  May mistakenly be caulked WEEP HOLES – OPEN HEAD JOINTS
  • 139. MOISTURE RESISTANCE RECESSED AND PROJECTING COURSES
  • 141. BRICK & BLOCK CAVITY WALL MORTAR WASH International Masonry Institute MASONRY DETAILING ARCHITECTURAL EFFECT SERIES DETAIL 01.601 REV. 08/31/07 800-IMI-0988 www.imiweb.org
  • 146. BENEFITS OF BUILDING WITH MASONRY Beauty Versatility of Design Contextual / Relatable Ease of Construction Structural Fire & Impact Resistant Durable / Low Maintenance Economical Sustainable Energy Efficient High Performance Acoustic Qualified Local Labor