Air Velocity Test

1.0   PURPOSE
      To describe a procedure for carrying out Air Velocity Test.

2.0   SCOPE
      This Procedure includes guidelines for carrying out the Air Velocity Test.

3.0   RESPONSIBILITY
      Validation Team and Engineering/Maintenance Department is responsible for
      carry out the Test.

4.0   PRINCIPLE

      This test is performed to determine the average airflow velocity, volume and
      Uniformity in a clean room, as well as to determine air supply volume flow rate.
      Air velocity test will be performed and the results will be required to determine
      the air changes per hour for the clean room.

5.0   DEFINITION

      5.1    Air Changes per Hour

             The rate of air exchange in a particular room is expressed as Air Changes
             Per Hour and is calculated by dividing the total volume of air delivered in
             the time unit by the volume of the space.

      5.2    Non-Unidirectional air flow

             Air distribution where the supply air entering the clean zone mixes with
             the internal air by means of induction.

      5.3    Unidirectional Airflow

             Controlled airflow through the entire cross section of a clean zone with
             steady velocity approximately parallel streamlines.

6.0   PROCEDURE

      6.1    Airflow velocity measurement in unidirectional airflow

             6.1.1   Before starting the work take the details of the whole area that to
                     be validated.
             6.1.2   Clean all the instruments with IPA before entering the clean area.
             6.1.3   System should be kept ON before starting the measurements.
6.1.4 Hot wire Anemometer or Vane type Anemometer is used for
      measuring air velocity.
6.1.5 Measure the filter size of the installation for which the test is to be
      carried out.
6.1.6 Measuring point should be defined at a distance between 150mm
      from the filter face.
6.1.7 For measuring the filter face velocity, the distance should be about
      150mm, and for checking the uniformity, it should be more than
      300mm.Measuring time at each position should be at least 10
      second, and the average,maximum and minimum values should be
      recorded.
6.1.8 Note down the readings.

6.2     Airflow velocity measurement for non-unidirectional airflow

6.2.1  Before starting the work take the details of the whole area that to
       be validated.
6.2.2 Clean all the instruments with IPA before entering the clean area.
6.2.3 System should be kept ON before starting the measurements.
6.2.4 Hot wire Anemometer or Vane type Anemometer is used for
       measuring air velocity.
6.2.5 Measure the filter size of the installation for which the test is to be
       carried out.
6.2.6 Measuring point should be defined at a distance 150mm from the
       filter face.
6.2.7 Measuring time at each position should be at least 10 second.
6.2.8 Calculate the average velocity for each filter.
6.2.9 Calculate the CFM of each filter by using following formula;
       CFM=Avg.Velocity (fpm) x Area of grill (ft2)
6.2.10 Calculate the total CFM of room by adding each filter CFM.

6.2.11 Find out the ACPH by using following formula:

        No. of Air Changes /Hr =         Total CFM      X 60
                                                      3
                                     Room Volume (ft )
6.2.12 Calculated the air changes should not less than the designed air
       changes.
6.2.13 If the air changes are lesser than required, adjust the dampers to
       desired CFM.
6.2.14 Note down the readings.
7.0   REFERENCE
      ISO 14644

8.0   ABBREVIATION

      SOP            Standard Operating Procedure
      ISO            International Standard Operating
      CFM            Cubic Feet per Minute
      Ft             Feet
      Avg            Average
      Hr             Hour
      ACPH           Air Changes per Hour
DOP/PAO leak integrity test.



1.0     PURPOSE
        To describe a procedure for carrying out DOP/PAO leak integrity test.

2.0     SCOPE
        This Procedure includes guidelines for detection of defects or pinhole leaks of HEPA
        filter

3.0     RESPONSIBILITY
        Validation Team and Engineers/ Maintenance Department is responsible for carryout the
        Test.

4.0     PRINCIPLE
        This test is performed to confirm that the HEPA filter is properly installed by verifying
        the absence of bypass leakage in the installation and the filters are free of defects and
        leaks in the filter frame and gasket seals, leaks in the filter bank framework. The test is
        performed by injecting and aerosol challenge upstream of the filters and immediately
        scanning down stream of the filters and supporting frame.

5.0     DEFINITION

         5.1     DOP (Di octyl Phthalate) / PAO (Poly Alfa Olefin)
         A mono-dispersed test aerosol of sub-micron particles, generated to challenge (evaluate
integrity ) of HEPA filters for HVAC

        5.2    Aerosol Challenge
        Challenging of filter or an installed filter system by test aerosol.

        5.3      Aerosol Generator
        System wherein aerosol is mixed with particle –free dilution air in a known volumetric
        ratio to reduce concentration.

        5.4     Installed Filter Leakage Test
        Test performed to confirm that the final filters are properly installed by verifying that
there
        is absence of bypass leakage in the installation, and that the filters and the grid system are
        free of defects and leak.

        5.4     Installed Filter Leakage Test
        Test performed to confirm that the final filters are properly installed by verifying that
there
        is absence of bypass leakage in the installation, and that the filters and the grid system
        are free of defects and leak.


        5.5    Aerosol
        A gaseous suspension of fine (100µm or smaller in size) solid or liquid particles.
5.6     Aerosol Photometer
       Light-scattering mass concentration indicating instrument which uses a forward
       Scattered optical chamber to make measurements.
       5.7     Scanning
       Method for disclosing leaks in units, whereby the probe inlet of an aerosol photometer is
moved in overlapping strokes across the defined filter area.

6.0     PROCEDURE

        6.1     Before starting the work take the details of the whole area that to be validated.
        6.2     Ask engineering / maintenance person to arrange single phase power supply as
                well as air connection with 20psi (1.5kg) pressure.
        6.3     Clean all the instruments with IPA before entering the clean area
        6.4     Ensure that the floor and area as well as Equipment is visually cleaned.
        6.5     System should be kept ON before starting the measurements.
        6.6     Connect the Spike Guard to Photometer before starting it.
        6.7     Start the air to generate the aerosol particles at 20psi pressure.
        6.8     Direct the generator face to the return air point or fresh air intake of the AHU.
        6.9     Take a tube and connect on end to the filter face Upstream port and other to the
                photometer in Upstream mode.
        6.10    Switch ON the photometer and set it to zero.
        6.11    Put the photometer to upstream mode and note the reading, the reading should be
                in between 20mg/Ltr to 80mg/Ltr.
        6.12    If it is between the above range then set the value to 100%, wait until the
                photometer displays 100% upstream concentration.
        6.13    Put the photometer switch on clear mode and enter zero for machine to become
                zero.
        6.14    Wait until photometer display ‘0’ (zero).
        6.15    Now put the switch to down stream mode and scan the filter by holding the probe
                approximately one inch away from the filter face.
        6.16    Scan the corners of HEPA filter for checking the installation leakages.
        6.17    If the reading on the photometer is more than 0.01%, rectify the leakages by
                tightening the locking bolts.
        6.18    Repair patches on filters should not exceed maximum of 5% of the total filter
                face area and the maximum width x length of each patch should not be more than
                1.5 inches. Total number of patches should not exceed 5 numbers / filters.
        6.19    Note down the final readings after rectification.
7.0   REFERENCE

      ISO 14644

8.0   ABBREVIATION

      SOP            Standard Operating Procedure
      ISO            International Standard Operating
      CFM            Cubic Feet per Minute
      Psi            Pascal per Square Inch
      HVAC           Heating Ventilation and Air Conditioning
      AHU            Air Handling Unit
Non- Viable Particle Count Test.




1.0   PURPOSE
      To describe a procedure for carrying out Non- Viable Particle Count Test.

4.0   SCOPE
      This Procedure includes guidelines for Carrying out Non-Viable Particle Count Test
      which includes the classification of air classification of air cleanliness in clean rooms and
      associated controlled environments in terms of Concentration of airborne particles.

5.0   RESPONSIBILITY
      Validation Team and Engineers/ Maintenance Department is responsible for carryout the
      Test.

4.0   PRINCIPLE
      This test is method specifies the measurement of air borne particle concentrations with
      size distributions having a threshold size between 0.5µm and 5.0µm. Measurements can
      be made in any of three defined occupancy states as-built, at-rest and operational. The
      measurements are made to certify the cleanliness classification.

5.0   DEFINITION

      5.1     AIRBORNE PARTICLES

              5.1.1   Particle
                      Solid or liquid object which, for purposes of classification of air
                      cleanliness, falls with in a cumulative distribution that is based upon a
                      threshold (lower limit) size in the range from 0.1µm to 5.0µm.

              5.1.2   Particle Size
                      Diameter of a sphere that produces a response, by a given particle-sizing
                      instruments, that is equivalent to the response produced by the particle
                      being measured.

              5.1.3   Particle Concentration
                      Number of individual particles per unit volume of air.

              5.1.4   Particle Size Distribution
                      Cumulative distribution of particle concentration as a function of particle
                      size.

5.2   OCCUPANCY STATES
5.2.1   As-Built
                       Conditions where the installation is complete with all services
                       connected and functioning but with no production equipment,
                       materials, or personnel present.

               4.2.1   At-Rest
                       Condition where the installation is complete with equipment
                       installed and operating, but with no personnel present.

6.0     CLASSICATION

               6.1     Classification for Cleanliness Classes for Clean Rooms and Clean Zones

ISO Classification Number                               Particles / M3
                                            0.5µm                            5.0µm
        ISO CLASS 5                           3520                              29
        ISO CLASS 6                          35200                             293
        ISO CLASS 7                         352000                            2930
        ISO CLASS 8                        3520000                           29300

7.0     SAMPLING
        7.1    ESTABLISHMENT OF SAMPLING LOCATION


               7.1.1   Calculation for No. of Locations
                       To calculate the minimum number of sampling point locations:
                       NL = √A
                       Where,
                       NL       is the minimum number of sampling locations ( rounded up
                       to a whole number
                       A         is the area of clean room or clean zone in square meters
7.1.2   Sampling Point
                       Ensure that the sampling locations are evenly distributed
                       throughout the area of the clean room and positioned at a working
                       level.
        7.2.   ESTABLISHMENT OF SINGLE SAMPLE VOLUME PER

LOCATION
7.2.1   Sampling Volume

                    At each sampling location, sampling a sufficient volume of air that

                    a minimum of 20 particles would be detected if the particle

                    concentration for the largest considered particles sized were at the

                    class limit for the designed ISO Class.

                    The single sample volume VS per locations is :

                    Vs =20/Cnm x 1000

                    Where,

                    Vs       is the minimum single sample volume per location in liters

                    Cnm      is the class limit ( number of particles per cubic meter ) for

                             the largest considered particles size specified for the

                             relevant class.

                    20       is the defined number of particle that could be counted if

                             the particle concentration were at the class limit.

8.0   PROCEDURE

      8.1   Before starting the work take the details of the whole are that to be
            validate.
      8.2   Ask Engineering / maintenance person to arrange single phase power
            supply.
      8.3   Clean all the instruments with IPA before entering the clean area.
      8.4   Ensure that the floor and area as well as Equipment is visually cleaned.
      8.5   System should be kept ON 2 hours before starting the measurements.
      8.6   Connect the Spike Guard to particle counter before starting the counter.
      8.7   Set the Particle counter as per the given details of rooms/LAFs.
      8.8   The sampling probe shall be positioned vertically upward.
      8.9   Switch ON the Air Borne Particle Counter.
8.10   Set the Particle Counter for 0 Purging before starting the measurement
       8.11   Place the probe at working level height.
       8.12   Start taking samples at different location as per the details and take print
              of the reading.
       8.13   The Thermal paper reading should be pasted on a blank page and should
              be Xeroxed immediately.

9.0    REFERENCE

       ISO    14644

10.0   ABBREVIATION

       SOP            Standard Operating Procedure
       ISO            International Standard Operating
       LAF            Laminar Air Flow Unit
       AHU            Air Handling Unit

More Related Content

What's hot

Change management system
Change management systemChange management system
Change management systemmanusb07
 
Control on Cleanroom Environmental Monitoring (Pharmaceutical)
Control on Cleanroom Environmental Monitoring (Pharmaceutical)Control on Cleanroom Environmental Monitoring (Pharmaceutical)
Control on Cleanroom Environmental Monitoring (Pharmaceutical)Srinath Sasidharan
 
Protocol for compressed air validation
Protocol for compressed air  validationProtocol for compressed air  validation
Protocol for compressed air validationAvinash Verma
 
Validation Of System For Compressed Air Quality
Validation Of System For Compressed Air Quality   Validation Of System For Compressed Air Quality
Validation Of System For Compressed Air Quality Imtiaz Rastgar
 
Air circulation maintenance industry for sterile and non sterile area
Air circulation maintenance  industry for sterile and non sterile areaAir circulation maintenance  industry for sterile and non sterile area
Air circulation maintenance industry for sterile and non sterile areaGNIPST
 
Validation of Heat ventilation air conditioning
Validation of Heat ventilation air conditioningValidation of Heat ventilation air conditioning
Validation of Heat ventilation air conditioningPrashant Tomar
 
Containments - (Isolator & RABS)
Containments - (Isolator & RABS)Containments - (Isolator & RABS)
Containments - (Isolator & RABS)Ravindra Kushwaha
 
Clean Room_Presentation
Clean Room_PresentationClean Room_Presentation
Clean Room_PresentationManoj Verma
 
Cleaning validation
Cleaning validationCleaning validation
Cleaning validationSagar Savale
 
Qualification of HVAC Systems As Per WHO
Qualification of HVAC Systems As Per WHOQualification of HVAC Systems As Per WHO
Qualification of HVAC Systems As Per WHOAditya Sharma
 
Auditing of quality assurance and maintenance of engineering department
Auditing of quality assurance and   maintenance of engineering departmentAuditing of quality assurance and   maintenance of engineering department
Auditing of quality assurance and maintenance of engineering departmentPriyanka Kandhare
 
Aseptic process tech & advanced sterile product mfg rashmi nasare
Aseptic process tech & advanced sterile product mfg  rashmi nasareAseptic process tech & advanced sterile product mfg  rashmi nasare
Aseptic process tech & advanced sterile product mfg rashmi nasareRASHMINasare
 

What's hot (20)

Cleanroom sop slides
Cleanroom sop slidesCleanroom sop slides
Cleanroom sop slides
 
Change management system
Change management systemChange management system
Change management system
 
Control on Cleanroom Environmental Monitoring (Pharmaceutical)
Control on Cleanroom Environmental Monitoring (Pharmaceutical)Control on Cleanroom Environmental Monitoring (Pharmaceutical)
Control on Cleanroom Environmental Monitoring (Pharmaceutical)
 
Hvac
HvacHvac
Hvac
 
Protocol for compressed air validation
Protocol for compressed air  validationProtocol for compressed air  validation
Protocol for compressed air validation
 
Validation Of System For Compressed Air Quality
Validation Of System For Compressed Air Quality   Validation Of System For Compressed Air Quality
Validation Of System For Compressed Air Quality
 
Water system validation
Water system validationWater system validation
Water system validation
 
Process Validation.pdf
Process Validation.pdfProcess Validation.pdf
Process Validation.pdf
 
EU GMP Annex1 Review
EU GMP Annex1 ReviewEU GMP Annex1 Review
EU GMP Annex1 Review
 
Air circulation maintenance industry for sterile and non sterile area
Air circulation maintenance  industry for sterile and non sterile areaAir circulation maintenance  industry for sterile and non sterile area
Air circulation maintenance industry for sterile and non sterile area
 
Validation of Heat ventilation air conditioning
Validation of Heat ventilation air conditioningValidation of Heat ventilation air conditioning
Validation of Heat ventilation air conditioning
 
Containments - (Isolator & RABS)
Containments - (Isolator & RABS)Containments - (Isolator & RABS)
Containments - (Isolator & RABS)
 
Clean Room
Clean RoomClean Room
Clean Room
 
Clean Room_Presentation
Clean Room_PresentationClean Room_Presentation
Clean Room_Presentation
 
Cleaning validation
Cleaning validationCleaning validation
Cleaning validation
 
Qualification of HVAC Systems As Per WHO
Qualification of HVAC Systems As Per WHOQualification of HVAC Systems As Per WHO
Qualification of HVAC Systems As Per WHO
 
Auditing of quality assurance and maintenance of engineering department
Auditing of quality assurance and   maintenance of engineering departmentAuditing of quality assurance and   maintenance of engineering department
Auditing of quality assurance and maintenance of engineering department
 
Aseptic Processing & Media Fill
Aseptic Processing & Media FillAseptic Processing & Media Fill
Aseptic Processing & Media Fill
 
Temperature Mapping (WHO).pdf
Temperature Mapping (WHO).pdfTemperature Mapping (WHO).pdf
Temperature Mapping (WHO).pdf
 
Aseptic process tech & advanced sterile product mfg rashmi nasare
Aseptic process tech & advanced sterile product mfg  rashmi nasareAseptic process tech & advanced sterile product mfg  rashmi nasare
Aseptic process tech & advanced sterile product mfg rashmi nasare
 

Viewers also liked

Microbial limit test 112070804013
Microbial limit test  112070804013Microbial limit test  112070804013
Microbial limit test 112070804013Patel Parth
 
HVAC SYSTEM IN PHARMACEUTICAL INDUSTRY
HVAC SYSTEM IN PHARMACEUTICAL INDUSTRYHVAC SYSTEM IN PHARMACEUTICAL INDUSTRY
HVAC SYSTEM IN PHARMACEUTICAL INDUSTRYNamdeo Shinde
 
Cleanroom, Classification, Design and
Cleanroom, Classification, Design and Cleanroom, Classification, Design and
Cleanroom, Classification, Design and Ahmadreza Barazesh
 
Hvac presentation for beginers
Hvac presentation for beginersHvac presentation for beginers
Hvac presentation for beginersguestf11b52
 

Viewers also liked (6)

Validation Master Plan
Validation Master PlanValidation Master Plan
Validation Master Plan
 
Microbial limit test 112070804013
Microbial limit test  112070804013Microbial limit test  112070804013
Microbial limit test 112070804013
 
HVAC SYSTEM IN PHARMACEUTICAL INDUSTRY
HVAC SYSTEM IN PHARMACEUTICAL INDUSTRYHVAC SYSTEM IN PHARMACEUTICAL INDUSTRY
HVAC SYSTEM IN PHARMACEUTICAL INDUSTRY
 
Cleanroom, Classification, Design and
Cleanroom, Classification, Design and Cleanroom, Classification, Design and
Cleanroom, Classification, Design and
 
HVAC Basic Concepts of Air Conditioning
HVAC Basic Concepts of Air ConditioningHVAC Basic Concepts of Air Conditioning
HVAC Basic Concepts of Air Conditioning
 
Hvac presentation for beginers
Hvac presentation for beginersHvac presentation for beginers
Hvac presentation for beginers
 

Similar to Hvac validation protocol

Pharmaceutical Engineering Downflow Booth Testing
Pharmaceutical Engineering Downflow Booth TestingPharmaceutical Engineering Downflow Booth Testing
Pharmaceutical Engineering Downflow Booth TestingEric Ferguson
 
One slider for qualification and validation of depyrogenation and sterilizati...
One slider for qualification and validation of depyrogenation and sterilizati...One slider for qualification and validation of depyrogenation and sterilizati...
One slider for qualification and validation of depyrogenation and sterilizati...Palash Das
 
Measurement of Respirable Suspended Pm10 Particles
Measurement of Respirable Suspended Pm10 ParticlesMeasurement of Respirable Suspended Pm10 Particles
Measurement of Respirable Suspended Pm10 ParticlesECRD IN
 
Measurement of respirable
Measurement of respirableMeasurement of respirable
Measurement of respirableECRD IN
 
Measurement of respirable suspended pm10
Measurement of respirable suspended pm10Measurement of respirable suspended pm10
Measurement of respirable suspended pm10ECRD2015
 
VALIDATION OF UTILITY ( HVAC , CLEANING VALIDATION,)
VALIDATION OF UTILITY ( HVAC , CLEANING VALIDATION,)VALIDATION OF UTILITY ( HVAC , CLEANING VALIDATION,)
VALIDATION OF UTILITY ( HVAC , CLEANING VALIDATION,)workfordhandiadeepak
 
Technology reqmts-hvac-design-ses-2-aseptic-wkshp-pune-f
Technology reqmts-hvac-design-ses-2-aseptic-wkshp-pune-fTechnology reqmts-hvac-design-ses-2-aseptic-wkshp-pune-f
Technology reqmts-hvac-design-ses-2-aseptic-wkshp-pune-fsachin kumar
 
Classifications: The 4 Elements of Cleanroom Construction Part 3
Classifications: The 4 Elements of Cleanroom Construction Part 3Classifications: The 4 Elements of Cleanroom Construction Part 3
Classifications: The 4 Elements of Cleanroom Construction Part 3AM Technical Solutions, Inc
 
GMP Requirements for Sterile Products manufacturing
GMP Requirements for Sterile Products manufacturingGMP Requirements for Sterile Products manufacturing
GMP Requirements for Sterile Products manufacturingsurafel kebede
 
GMP Requirements for Sterile Products manufacturing
GMP Requirements for Sterile Products manufacturingGMP Requirements for Sterile Products manufacturing
GMP Requirements for Sterile Products manufacturingsurafel kebede
 
Testing/Manufacture/ASHRE 52.2 Filter Test Rig
Testing/Manufacture/ASHRE 52.2 Filter Test RigTesting/Manufacture/ASHRE 52.2 Filter Test Rig
Testing/Manufacture/ASHRE 52.2 Filter Test Rigfec2020
 
Testing/Manufacture/Hepa Filter Drop Tester
Testing/Manufacture/Hepa Filter Drop TesterTesting/Manufacture/Hepa Filter Drop Tester
Testing/Manufacture/Hepa Filter Drop Testerfec2020
 
Testing/Manufacture/Pre & Fine Filter Packaging Test Equipments
Testing/Manufacture/Pre & Fine Filter Packaging Test EquipmentsTesting/Manufacture/Pre & Fine Filter Packaging Test Equipments
Testing/Manufacture/Pre & Fine Filter Packaging Test Equipmentsfec2020
 

Similar to Hvac validation protocol (20)

HVAC validation.pdf
HVAC validation.pdfHVAC validation.pdf
HVAC validation.pdf
 
HVAC
HVACHVAC
HVAC
 
HVAC training 2020
HVAC  training 2020HVAC  training 2020
HVAC training 2020
 
Pharmaceutical Engineering Downflow Booth Testing
Pharmaceutical Engineering Downflow Booth TestingPharmaceutical Engineering Downflow Booth Testing
Pharmaceutical Engineering Downflow Booth Testing
 
One slider for qualification and validation of depyrogenation and sterilizati...
One slider for qualification and validation of depyrogenation and sterilizati...One slider for qualification and validation of depyrogenation and sterilizati...
One slider for qualification and validation of depyrogenation and sterilizati...
 
Presentation on HVAC
Presentation on HVAC Presentation on HVAC
Presentation on HVAC
 
Measurement of Respirable Suspended Pm10 Particles
Measurement of Respirable Suspended Pm10 ParticlesMeasurement of Respirable Suspended Pm10 Particles
Measurement of Respirable Suspended Pm10 Particles
 
Measurement of respirable
Measurement of respirableMeasurement of respirable
Measurement of respirable
 
Measurement of respirable suspended pm10
Measurement of respirable suspended pm10Measurement of respirable suspended pm10
Measurement of respirable suspended pm10
 
VALIDATION OF UTILITY ( HVAC , CLEANING VALIDATION,)
VALIDATION OF UTILITY ( HVAC , CLEANING VALIDATION,)VALIDATION OF UTILITY ( HVAC , CLEANING VALIDATION,)
VALIDATION OF UTILITY ( HVAC , CLEANING VALIDATION,)
 
Technology reqmts-hvac-design-ses-2-aseptic-wkshp-pune-f
Technology reqmts-hvac-design-ses-2-aseptic-wkshp-pune-fTechnology reqmts-hvac-design-ses-2-aseptic-wkshp-pune-f
Technology reqmts-hvac-design-ses-2-aseptic-wkshp-pune-f
 
Cleanrooms 101
Cleanrooms 101Cleanrooms 101
Cleanrooms 101
 
Classifications: The 4 Elements of Cleanroom Construction Part 3
Classifications: The 4 Elements of Cleanroom Construction Part 3Classifications: The 4 Elements of Cleanroom Construction Part 3
Classifications: The 4 Elements of Cleanroom Construction Part 3
 
GMP Requirements for Sterile Products manufacturing
GMP Requirements for Sterile Products manufacturingGMP Requirements for Sterile Products manufacturing
GMP Requirements for Sterile Products manufacturing
 
GMP Requirements for Sterile Products manufacturing
GMP Requirements for Sterile Products manufacturingGMP Requirements for Sterile Products manufacturing
GMP Requirements for Sterile Products manufacturing
 
GMP sterile products
GMP sterile products GMP sterile products
GMP sterile products
 
Us federal standard 209 E
Us federal standard 209 EUs federal standard 209 E
Us federal standard 209 E
 
Testing/Manufacture/ASHRE 52.2 Filter Test Rig
Testing/Manufacture/ASHRE 52.2 Filter Test RigTesting/Manufacture/ASHRE 52.2 Filter Test Rig
Testing/Manufacture/ASHRE 52.2 Filter Test Rig
 
Testing/Manufacture/Hepa Filter Drop Tester
Testing/Manufacture/Hepa Filter Drop TesterTesting/Manufacture/Hepa Filter Drop Tester
Testing/Manufacture/Hepa Filter Drop Tester
 
Testing/Manufacture/Pre & Fine Filter Packaging Test Equipments
Testing/Manufacture/Pre & Fine Filter Packaging Test EquipmentsTesting/Manufacture/Pre & Fine Filter Packaging Test Equipments
Testing/Manufacture/Pre & Fine Filter Packaging Test Equipments
 

Recently uploaded

Organizational Transformation Lead with Culture
Organizational Transformation Lead with CultureOrganizational Transformation Lead with Culture
Organizational Transformation Lead with CultureSeta Wicaksana
 
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...amitlee9823
 
BAGALUR CALL GIRL IN 98274*61493 ❤CALL GIRLS IN ESCORT SERVICE❤CALL GIRL
BAGALUR CALL GIRL IN 98274*61493 ❤CALL GIRLS IN ESCORT SERVICE❤CALL GIRLBAGALUR CALL GIRL IN 98274*61493 ❤CALL GIRLS IN ESCORT SERVICE❤CALL GIRL
BAGALUR CALL GIRL IN 98274*61493 ❤CALL GIRLS IN ESCORT SERVICE❤CALL GIRLkapoorjyoti4444
 
Cheap Rate Call Girls In Noida Sector 62 Metro 959961乂3876
Cheap Rate Call Girls In Noida Sector 62 Metro 959961乂3876Cheap Rate Call Girls In Noida Sector 62 Metro 959961乂3876
Cheap Rate Call Girls In Noida Sector 62 Metro 959961乂3876dlhescort
 
Call Girls Kengeri Satellite Town Just Call 👗 7737669865 👗 Top Class Call Gir...
Call Girls Kengeri Satellite Town Just Call 👗 7737669865 👗 Top Class Call Gir...Call Girls Kengeri Satellite Town Just Call 👗 7737669865 👗 Top Class Call Gir...
Call Girls Kengeri Satellite Town Just Call 👗 7737669865 👗 Top Class Call Gir...amitlee9823
 
Nelamangala Call Girls: 🍓 7737669865 🍓 High Profile Model Escorts | Bangalore...
Nelamangala Call Girls: 🍓 7737669865 🍓 High Profile Model Escorts | Bangalore...Nelamangala Call Girls: 🍓 7737669865 🍓 High Profile Model Escorts | Bangalore...
Nelamangala Call Girls: 🍓 7737669865 🍓 High Profile Model Escorts | Bangalore...amitlee9823
 
It will be International Nurses' Day on 12 May
It will be International Nurses' Day on 12 MayIt will be International Nurses' Day on 12 May
It will be International Nurses' Day on 12 MayNZSG
 
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...Aggregage
 
Falcon Invoice Discounting: The best investment platform in india for investors
Falcon Invoice Discounting: The best investment platform in india for investorsFalcon Invoice Discounting: The best investment platform in india for investors
Falcon Invoice Discounting: The best investment platform in india for investorsFalcon Invoice Discounting
 
Value Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and painsValue Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and painsP&CO
 
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best ServicesMysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best ServicesDipal Arora
 
👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...
👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...
👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...rajveerescorts2022
 
Chandigarh Escorts Service 📞8868886958📞 Just📲 Call Nihal Chandigarh Call Girl...
Chandigarh Escorts Service 📞8868886958📞 Just📲 Call Nihal Chandigarh Call Girl...Chandigarh Escorts Service 📞8868886958📞 Just📲 Call Nihal Chandigarh Call Girl...
Chandigarh Escorts Service 📞8868886958📞 Just📲 Call Nihal Chandigarh Call Girl...Sheetaleventcompany
 
Call Girls From Pari Chowk Greater Noida ❤️8448577510 ⊹Best Escorts Service I...
Call Girls From Pari Chowk Greater Noida ❤️8448577510 ⊹Best Escorts Service I...Call Girls From Pari Chowk Greater Noida ❤️8448577510 ⊹Best Escorts Service I...
Call Girls From Pari Chowk Greater Noida ❤️8448577510 ⊹Best Escorts Service I...lizamodels9
 
How to Get Started in Social Media for Art League City
How to Get Started in Social Media for Art League CityHow to Get Started in Social Media for Art League City
How to Get Started in Social Media for Art League CityEric T. Tung
 
Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...
Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...
Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...daisycvs
 
Marel Q1 2024 Investor Presentation from May 8, 2024
Marel Q1 2024 Investor Presentation from May 8, 2024Marel Q1 2024 Investor Presentation from May 8, 2024
Marel Q1 2024 Investor Presentation from May 8, 2024Marel
 
Katrina Personal Brand Project and portfolio 1
Katrina Personal Brand Project and portfolio 1Katrina Personal Brand Project and portfolio 1
Katrina Personal Brand Project and portfolio 1kcpayne
 
Dr. Admir Softic_ presentation_Green Club_ENG.pdf
Dr. Admir Softic_ presentation_Green Club_ENG.pdfDr. Admir Softic_ presentation_Green Club_ENG.pdf
Dr. Admir Softic_ presentation_Green Club_ENG.pdfAdmir Softic
 

Recently uploaded (20)

Organizational Transformation Lead with Culture
Organizational Transformation Lead with CultureOrganizational Transformation Lead with Culture
Organizational Transformation Lead with Culture
 
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
 
BAGALUR CALL GIRL IN 98274*61493 ❤CALL GIRLS IN ESCORT SERVICE❤CALL GIRL
BAGALUR CALL GIRL IN 98274*61493 ❤CALL GIRLS IN ESCORT SERVICE❤CALL GIRLBAGALUR CALL GIRL IN 98274*61493 ❤CALL GIRLS IN ESCORT SERVICE❤CALL GIRL
BAGALUR CALL GIRL IN 98274*61493 ❤CALL GIRLS IN ESCORT SERVICE❤CALL GIRL
 
Cheap Rate Call Girls In Noida Sector 62 Metro 959961乂3876
Cheap Rate Call Girls In Noida Sector 62 Metro 959961乂3876Cheap Rate Call Girls In Noida Sector 62 Metro 959961乂3876
Cheap Rate Call Girls In Noida Sector 62 Metro 959961乂3876
 
Call Girls Kengeri Satellite Town Just Call 👗 7737669865 👗 Top Class Call Gir...
Call Girls Kengeri Satellite Town Just Call 👗 7737669865 👗 Top Class Call Gir...Call Girls Kengeri Satellite Town Just Call 👗 7737669865 👗 Top Class Call Gir...
Call Girls Kengeri Satellite Town Just Call 👗 7737669865 👗 Top Class Call Gir...
 
Nelamangala Call Girls: 🍓 7737669865 🍓 High Profile Model Escorts | Bangalore...
Nelamangala Call Girls: 🍓 7737669865 🍓 High Profile Model Escorts | Bangalore...Nelamangala Call Girls: 🍓 7737669865 🍓 High Profile Model Escorts | Bangalore...
Nelamangala Call Girls: 🍓 7737669865 🍓 High Profile Model Escorts | Bangalore...
 
It will be International Nurses' Day on 12 May
It will be International Nurses' Day on 12 MayIt will be International Nurses' Day on 12 May
It will be International Nurses' Day on 12 May
 
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...
 
Falcon Invoice Discounting: The best investment platform in india for investors
Falcon Invoice Discounting: The best investment platform in india for investorsFalcon Invoice Discounting: The best investment platform in india for investors
Falcon Invoice Discounting: The best investment platform in india for investors
 
Value Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and painsValue Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and pains
 
(Anamika) VIP Call Girls Napur Call Now 8617697112 Napur Escorts 24x7
(Anamika) VIP Call Girls Napur Call Now 8617697112 Napur Escorts 24x7(Anamika) VIP Call Girls Napur Call Now 8617697112 Napur Escorts 24x7
(Anamika) VIP Call Girls Napur Call Now 8617697112 Napur Escorts 24x7
 
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best ServicesMysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
 
👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...
👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...
👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...
 
Chandigarh Escorts Service 📞8868886958📞 Just📲 Call Nihal Chandigarh Call Girl...
Chandigarh Escorts Service 📞8868886958📞 Just📲 Call Nihal Chandigarh Call Girl...Chandigarh Escorts Service 📞8868886958📞 Just📲 Call Nihal Chandigarh Call Girl...
Chandigarh Escorts Service 📞8868886958📞 Just📲 Call Nihal Chandigarh Call Girl...
 
Call Girls From Pari Chowk Greater Noida ❤️8448577510 ⊹Best Escorts Service I...
Call Girls From Pari Chowk Greater Noida ❤️8448577510 ⊹Best Escorts Service I...Call Girls From Pari Chowk Greater Noida ❤️8448577510 ⊹Best Escorts Service I...
Call Girls From Pari Chowk Greater Noida ❤️8448577510 ⊹Best Escorts Service I...
 
How to Get Started in Social Media for Art League City
How to Get Started in Social Media for Art League CityHow to Get Started in Social Media for Art League City
How to Get Started in Social Media for Art League City
 
Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...
Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...
Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...
 
Marel Q1 2024 Investor Presentation from May 8, 2024
Marel Q1 2024 Investor Presentation from May 8, 2024Marel Q1 2024 Investor Presentation from May 8, 2024
Marel Q1 2024 Investor Presentation from May 8, 2024
 
Katrina Personal Brand Project and portfolio 1
Katrina Personal Brand Project and portfolio 1Katrina Personal Brand Project and portfolio 1
Katrina Personal Brand Project and portfolio 1
 
Dr. Admir Softic_ presentation_Green Club_ENG.pdf
Dr. Admir Softic_ presentation_Green Club_ENG.pdfDr. Admir Softic_ presentation_Green Club_ENG.pdf
Dr. Admir Softic_ presentation_Green Club_ENG.pdf
 

Hvac validation protocol

  • 1. Air Velocity Test 1.0 PURPOSE To describe a procedure for carrying out Air Velocity Test. 2.0 SCOPE This Procedure includes guidelines for carrying out the Air Velocity Test. 3.0 RESPONSIBILITY Validation Team and Engineering/Maintenance Department is responsible for carry out the Test. 4.0 PRINCIPLE This test is performed to determine the average airflow velocity, volume and Uniformity in a clean room, as well as to determine air supply volume flow rate. Air velocity test will be performed and the results will be required to determine the air changes per hour for the clean room. 5.0 DEFINITION 5.1 Air Changes per Hour The rate of air exchange in a particular room is expressed as Air Changes Per Hour and is calculated by dividing the total volume of air delivered in the time unit by the volume of the space. 5.2 Non-Unidirectional air flow Air distribution where the supply air entering the clean zone mixes with the internal air by means of induction. 5.3 Unidirectional Airflow Controlled airflow through the entire cross section of a clean zone with steady velocity approximately parallel streamlines. 6.0 PROCEDURE 6.1 Airflow velocity measurement in unidirectional airflow 6.1.1 Before starting the work take the details of the whole area that to be validated. 6.1.2 Clean all the instruments with IPA before entering the clean area. 6.1.3 System should be kept ON before starting the measurements.
  • 2. 6.1.4 Hot wire Anemometer or Vane type Anemometer is used for measuring air velocity. 6.1.5 Measure the filter size of the installation for which the test is to be carried out. 6.1.6 Measuring point should be defined at a distance between 150mm from the filter face. 6.1.7 For measuring the filter face velocity, the distance should be about 150mm, and for checking the uniformity, it should be more than 300mm.Measuring time at each position should be at least 10 second, and the average,maximum and minimum values should be recorded. 6.1.8 Note down the readings. 6.2 Airflow velocity measurement for non-unidirectional airflow 6.2.1 Before starting the work take the details of the whole area that to be validated. 6.2.2 Clean all the instruments with IPA before entering the clean area. 6.2.3 System should be kept ON before starting the measurements. 6.2.4 Hot wire Anemometer or Vane type Anemometer is used for measuring air velocity. 6.2.5 Measure the filter size of the installation for which the test is to be carried out. 6.2.6 Measuring point should be defined at a distance 150mm from the filter face. 6.2.7 Measuring time at each position should be at least 10 second. 6.2.8 Calculate the average velocity for each filter. 6.2.9 Calculate the CFM of each filter by using following formula; CFM=Avg.Velocity (fpm) x Area of grill (ft2) 6.2.10 Calculate the total CFM of room by adding each filter CFM. 6.2.11 Find out the ACPH by using following formula: No. of Air Changes /Hr = Total CFM X 60 3 Room Volume (ft ) 6.2.12 Calculated the air changes should not less than the designed air changes. 6.2.13 If the air changes are lesser than required, adjust the dampers to desired CFM. 6.2.14 Note down the readings.
  • 3. 7.0 REFERENCE ISO 14644 8.0 ABBREVIATION SOP Standard Operating Procedure ISO International Standard Operating CFM Cubic Feet per Minute Ft Feet Avg Average Hr Hour ACPH Air Changes per Hour
  • 4. DOP/PAO leak integrity test. 1.0 PURPOSE To describe a procedure for carrying out DOP/PAO leak integrity test. 2.0 SCOPE This Procedure includes guidelines for detection of defects or pinhole leaks of HEPA filter 3.0 RESPONSIBILITY Validation Team and Engineers/ Maintenance Department is responsible for carryout the Test. 4.0 PRINCIPLE This test is performed to confirm that the HEPA filter is properly installed by verifying the absence of bypass leakage in the installation and the filters are free of defects and leaks in the filter frame and gasket seals, leaks in the filter bank framework. The test is performed by injecting and aerosol challenge upstream of the filters and immediately scanning down stream of the filters and supporting frame. 5.0 DEFINITION 5.1 DOP (Di octyl Phthalate) / PAO (Poly Alfa Olefin) A mono-dispersed test aerosol of sub-micron particles, generated to challenge (evaluate integrity ) of HEPA filters for HVAC 5.2 Aerosol Challenge Challenging of filter or an installed filter system by test aerosol. 5.3 Aerosol Generator System wherein aerosol is mixed with particle –free dilution air in a known volumetric ratio to reduce concentration. 5.4 Installed Filter Leakage Test Test performed to confirm that the final filters are properly installed by verifying that there is absence of bypass leakage in the installation, and that the filters and the grid system are free of defects and leak. 5.4 Installed Filter Leakage Test Test performed to confirm that the final filters are properly installed by verifying that there is absence of bypass leakage in the installation, and that the filters and the grid system are free of defects and leak. 5.5 Aerosol A gaseous suspension of fine (100µm or smaller in size) solid or liquid particles.
  • 5. 5.6 Aerosol Photometer Light-scattering mass concentration indicating instrument which uses a forward Scattered optical chamber to make measurements. 5.7 Scanning Method for disclosing leaks in units, whereby the probe inlet of an aerosol photometer is moved in overlapping strokes across the defined filter area. 6.0 PROCEDURE 6.1 Before starting the work take the details of the whole area that to be validated. 6.2 Ask engineering / maintenance person to arrange single phase power supply as well as air connection with 20psi (1.5kg) pressure. 6.3 Clean all the instruments with IPA before entering the clean area 6.4 Ensure that the floor and area as well as Equipment is visually cleaned. 6.5 System should be kept ON before starting the measurements. 6.6 Connect the Spike Guard to Photometer before starting it. 6.7 Start the air to generate the aerosol particles at 20psi pressure. 6.8 Direct the generator face to the return air point or fresh air intake of the AHU. 6.9 Take a tube and connect on end to the filter face Upstream port and other to the photometer in Upstream mode. 6.10 Switch ON the photometer and set it to zero. 6.11 Put the photometer to upstream mode and note the reading, the reading should be in between 20mg/Ltr to 80mg/Ltr. 6.12 If it is between the above range then set the value to 100%, wait until the photometer displays 100% upstream concentration. 6.13 Put the photometer switch on clear mode and enter zero for machine to become zero. 6.14 Wait until photometer display ‘0’ (zero). 6.15 Now put the switch to down stream mode and scan the filter by holding the probe approximately one inch away from the filter face. 6.16 Scan the corners of HEPA filter for checking the installation leakages. 6.17 If the reading on the photometer is more than 0.01%, rectify the leakages by tightening the locking bolts. 6.18 Repair patches on filters should not exceed maximum of 5% of the total filter face area and the maximum width x length of each patch should not be more than 1.5 inches. Total number of patches should not exceed 5 numbers / filters. 6.19 Note down the final readings after rectification.
  • 6. 7.0 REFERENCE ISO 14644 8.0 ABBREVIATION SOP Standard Operating Procedure ISO International Standard Operating CFM Cubic Feet per Minute Psi Pascal per Square Inch HVAC Heating Ventilation and Air Conditioning AHU Air Handling Unit
  • 7. Non- Viable Particle Count Test. 1.0 PURPOSE To describe a procedure for carrying out Non- Viable Particle Count Test. 4.0 SCOPE This Procedure includes guidelines for Carrying out Non-Viable Particle Count Test which includes the classification of air classification of air cleanliness in clean rooms and associated controlled environments in terms of Concentration of airborne particles. 5.0 RESPONSIBILITY Validation Team and Engineers/ Maintenance Department is responsible for carryout the Test. 4.0 PRINCIPLE This test is method specifies the measurement of air borne particle concentrations with size distributions having a threshold size between 0.5µm and 5.0µm. Measurements can be made in any of three defined occupancy states as-built, at-rest and operational. The measurements are made to certify the cleanliness classification. 5.0 DEFINITION 5.1 AIRBORNE PARTICLES 5.1.1 Particle Solid or liquid object which, for purposes of classification of air cleanliness, falls with in a cumulative distribution that is based upon a threshold (lower limit) size in the range from 0.1µm to 5.0µm. 5.1.2 Particle Size Diameter of a sphere that produces a response, by a given particle-sizing instruments, that is equivalent to the response produced by the particle being measured. 5.1.3 Particle Concentration Number of individual particles per unit volume of air. 5.1.4 Particle Size Distribution Cumulative distribution of particle concentration as a function of particle size. 5.2 OCCUPANCY STATES
  • 8. 5.2.1 As-Built Conditions where the installation is complete with all services connected and functioning but with no production equipment, materials, or personnel present. 4.2.1 At-Rest Condition where the installation is complete with equipment installed and operating, but with no personnel present. 6.0 CLASSICATION 6.1 Classification for Cleanliness Classes for Clean Rooms and Clean Zones ISO Classification Number Particles / M3 0.5µm 5.0µm ISO CLASS 5 3520 29 ISO CLASS 6 35200 293 ISO CLASS 7 352000 2930 ISO CLASS 8 3520000 29300 7.0 SAMPLING 7.1 ESTABLISHMENT OF SAMPLING LOCATION 7.1.1 Calculation for No. of Locations To calculate the minimum number of sampling point locations: NL = √A Where, NL is the minimum number of sampling locations ( rounded up to a whole number A is the area of clean room or clean zone in square meters 7.1.2 Sampling Point Ensure that the sampling locations are evenly distributed throughout the area of the clean room and positioned at a working level. 7.2. ESTABLISHMENT OF SINGLE SAMPLE VOLUME PER LOCATION
  • 9. 7.2.1 Sampling Volume At each sampling location, sampling a sufficient volume of air that a minimum of 20 particles would be detected if the particle concentration for the largest considered particles sized were at the class limit for the designed ISO Class. The single sample volume VS per locations is : Vs =20/Cnm x 1000 Where, Vs is the minimum single sample volume per location in liters Cnm is the class limit ( number of particles per cubic meter ) for the largest considered particles size specified for the relevant class. 20 is the defined number of particle that could be counted if the particle concentration were at the class limit. 8.0 PROCEDURE 8.1 Before starting the work take the details of the whole are that to be validate. 8.2 Ask Engineering / maintenance person to arrange single phase power supply. 8.3 Clean all the instruments with IPA before entering the clean area. 8.4 Ensure that the floor and area as well as Equipment is visually cleaned. 8.5 System should be kept ON 2 hours before starting the measurements. 8.6 Connect the Spike Guard to particle counter before starting the counter. 8.7 Set the Particle counter as per the given details of rooms/LAFs. 8.8 The sampling probe shall be positioned vertically upward. 8.9 Switch ON the Air Borne Particle Counter.
  • 10. 8.10 Set the Particle Counter for 0 Purging before starting the measurement 8.11 Place the probe at working level height. 8.12 Start taking samples at different location as per the details and take print of the reading. 8.13 The Thermal paper reading should be pasted on a blank page and should be Xeroxed immediately. 9.0 REFERENCE ISO 14644 10.0 ABBREVIATION SOP Standard Operating Procedure ISO International Standard Operating LAF Laminar Air Flow Unit AHU Air Handling Unit