Baykee CHP series industrial low frequency ups 3 phase
1. CHPCHPCHPCHP SeriesSeriesSeriesSeries ThreeThreeThreeThree PhasePhasePhasePhase OnlineOnlineOnlineOnline upsupsupsups (10kva~120kva)(10kva~120kva)(10kva~120kva)(10kva~120kva)
SalientSalientSalientSalient Features:Features:Features:Features:
CHP Series 3/3 Online UPS --- Intelligent & Digital UPS
BriefBriefBriefBrief Introduction:Introduction:Introduction:Introduction:
CHP series ups includes the 10 KVA to 400 KVA (3 phase input
& 3 phase output) double conversion On-Line UPS with an
isolation transformer at Output. The Load is supplied
continuously by the inverter with clean, stabilized and regulated
sine wave output power. Input & Output filters increase the
immunity of load from power disturbances and surges.
CHP series - Double Conversion Online UPS is useful for
mission critical applications like IT, Data Centers, Hospitals,
Precision Instrument, Intelligent Equipments and Industrial
Automation etc.---Applications
Thanks to state-of-the-art microprocessor / DSP based outstanding advanced technology design. CHP series Double Conversion
Online UPS can be used for monitoring various parameters of the UPS and also can be useful for remote monitoring / control on
the web by adding SNMP Card ( Optional ).
� Pure sine wave output, true on-line dual conversion design
� Adopt 4 layer PCB, and SMD technology
� High efficiency IGBT (Insulated Gate Bipolar Transistor) inverter technology.
The sixth generation low-exhaust and big-power IGBT with excellent high speed switch feature, high voltage feature and
large current feature. Drives by electric voltage, only need small control power. The sixth generation with lower saturation
voltage, the inverter has high efficiency, low temperature, high reliability.
� Touch screen display, with simple operation and Intuitive data, optional display language and logo.
� Set work modes on the display directly, UPS mode, ECO mode, EPS mode
� Intelligent detecting function
This system microprocessor can continually online detect power status, the breaker status and all the working status of the
circuit
� Excellent load feature Completely capable to load from 0-100% while no need to change to bypass, which make sure the
output reliable.
� Isolation Transformer in output for Better Performance
� Static & Manual Bypass Inbuilt
� Three phase separately control, realizes the control of instantaneous over-loading balance, so as to reach 100% unbalanced
load.
� DC cold start function
When mains failure, can directly use the battery to start the ups until the battery discharge to low voltage, when mains
recover, can self start UPS
� Generator compatible
According to the real electric circumstances, UPS can be compatible to the generator, highly improve the generator input
efficiency, save the energy.
� Intelligent communication
With RS232 and RS485 standard collocation, optional SNMP and dry contact
� Perfect protection.
Input/output over/low voltage protection, input surge protection, phase sequence protection, battery over charge/discharge
2. Specifications:Specifications:Specifications:Specifications:
model
CHP
3010K
CHP
3020K
CHP
3030K
CHP
3040K
CHP
3050K
CHP
3060K
CHP
3080K
CHP
3100K
CHP
3120K
Nominal capacity (KVA) 10KVA 20KVA 30KVA 40KVA 50KVA 60KVA 80KVA 100KVA 120KVA
Working mode Low frequency double conversion True Online
Phase number 3L+N+G
Input power factor ≥0.9(pulse rectifier), ≥0.99(12 pulses rectifier)
Rectifier(Input)
Input rated voltage 190V/200V/208V or 380V/400V/415V/
range ±25%
Input nominal
frequency
50Hz±10%,60Hz±10%
Input overtone
current
6pulses rectifier<30%, 12pulses rectifier plus filter <5%
Output ripple wave < 2%
Soft start 0~100% 5sec
Charging
Charge mode
Constant current first then constant voltage, charge with temperature compensation, automatic
switch of even charge and float charge, programmable timing battery charge-discharge
automatic maintenance
Float charging
voltage
432VDC
Equalized charging
voltage
464VDC
Temperature
compensation
voltage
3mV/℃(cell battery)
Charging current 0.1C(automatic adjust according to battery capacity) 10A~50A Adjustable
Charging power 20%of rated capacity
Battery
type maintenance free lead-acid battery
capacity 7~999AH settable (capacity vary with power)
battery number 12V-32pcs, 2V-192pcs (nominal voltage 384VDC)
Invertor
Phase number 3L+N
Rated power Rated capacity×0.9
Nominal voltage 190V/200V/208V or 380V/400V/415V/
Output voltage
stability
±1%(steady load), ±3%(fluctuation of load)
protection, short circuit protection, over-temperature protection and so on, as well as alarm function.
� Selectable battery inspection module
Can test the single parameter and display on the LCD, battery failure will immediately alarm and inform the administrator
� High-powered dynamic feature
Adopt kinds of feedback control such as instantaneous control mode and virtual value, not only reach the high dynamic
adjustment, but also reduce the output voltage distortion.
� Optional input harmonic filter or 12 pulse rectifier
Effectively restrain the input THD,raise UPS input power factor, reduce the input THD current
3. Frequency stability 50Hz,60Hz<±0.5%(desynchronised)
Factor of wave crest > 3:1
Output Waveform
distortion degree
sine wave,linear load < 3%, non-linear load<5%
Dynamic feature Transient voltage<±5%(jump form 0% to 100%),instant recovery time<10ms
Unbalance load
voltage
< ±5%
Overload protection 115% normal work, 125%60 min, 150%10min, 200%10s
Invertor efficiency > 92%(full load) > 93%(full load)
Bypass
Phase number 3L+N
Input nominal
voltage
190V/200V/208V or 380V/400V/415V/
Output nominal
voltage
190V/200V/208V or 380V/400V/415V/
Switching time 0ms(adopted static switch )
Protection
Input protection Voltage, frequency ultra limit, phase wrong, phase lost
Output protection Over current, short circuit, power factor low
Battery protection Over-charge, Over-discharge
Overheat protection Environmental thermal, inverter overheat protection
Hardware fault
protection
Auxiliary power supply abnormal, breaker trip, fuse break, power device over current or
overvoltage
System
specifications
Economic running
mode
Economic mode available, overall efficiency reach up to 98%
Audio alert function Any failure will be alerted
Work environment
Ambient temperature: 0~40℃,relative humidity: 30%~90%,altitude: <1000M (power
reduce 1% every 100M raised, 4000M utmost)
Cooling method Forced ventilation
Telecom interface RS232,RS485. Dry contact interface, Optional SNMP card (network remote control)
Redundancy function Cascade or multiple hot spare
Anti-surge 10/700μS, 5KV; 8/20μS, 20KA
Protection level IP31
Safety performance
I/O on ground resistance (3000VAC), stray current less than 3.5mA; insulation resistance
exceeding 2MΩ(500VDC)
Noise(dB) 48~55 55~60 60~65
Mechanical
dimension (W×D×H)
mm
600×620×1250 700×620×1530 980×800×1800
Package dimension
(W×D×H) mm
670*690*1460 800*690*1760 1050*870*2030
Net Weight (Kg) 205 265 310 407 485 506 770 913 937
Gross Weight (Kg) 236 296 342 447 525 520 812 955 980
AnyAnyAnyAny CustomisedCustomisedCustomisedCustomised parametersparametersparametersparameters areareareare availableavailableavailableavailable
4. BAYKEE NEW ENERGY TECHNOLOGY INCORPORATED COMPANY --- All Right Revised