Innovative Systems Design and Engineering
ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
Vol.4, No.14, 2013

www.iiste.org

Shunt Active Power Filters Based On Diode Clamped Multilevel
Inverter and Hysteresis Band Current Controller
PROF. DR. EMİN TACER, Akram Qashou and Nezihe yildiran
Bahçeşehir University

Email: akram11_qashou@hotmail.com
Abstract
This work focused to design and implementing the three phase shunt Active Power Filter (SAPF) based in
instantaneous reactive power theory which we used to generate the reference current and measure the power and
reactive power and power factor and using Hysteresis Band Current Controller to obtain the gating signals for
11-steps diode clamped multilevel inverter (DCMLI). The proposed system represent two inverter Shunt Active
filters is less total harmonic distortion (THD) and reduced semiconductor ratings compared with conventional
inverter. The current drawn by the non- linear load and improve the source side power factor by compensate the
reactive power. Also, the shunt Active Power Filter (SAPF) system response has been tested under steady state
and transient conditions for real time current compensation harmonics. A study of its performance through
simulation results will be investigated through MATLAB Simulink.
Keywords: Shunt Active power filter (SHAPF), diode clamped Multilevel Inverter (DCMLI), Hysteresis band
controller.
1.1 Introduction
Most researchers studied shunt active power filters (APF) based on conventional two-level inverters with
conventional controllers requiring a complex and a complicated mathematical model. In order to overcome this
problem a hysteresis band controller based diode clamped multilevel inverter is used and extended to an 11- Step
two inverters shunt active power filter.
1.2 Objectives
(a)-Two inverter Shunt active power filter will be used in this thesis to decrease harmonics in current wave and
compensate reactive power of non-linear loads. A control system based on hysteresis band controller with Shunt
Active Power Filter (SAPF) is proposed to study the system results and performance.
(b)-Three phase 11- Step Diode Clamped Multi-Level Inverter (DCMLI) proposed as a voltage source inverter
instead of other inverters because specification of this type of lowest Total Harmonic Distortion (THD) and 11Step according to the cost condition. [Harmonics current generation will be used by Diode Clamped Multi-Level
Inverter (DCMLI) with the same magnitude of the source current harmonic but in opposite phase]. The DCMLI
output will be connected at the point of common coupling of the system in order to avoid or cancel the current
source harmonics.
(c)-Instantaneous reactive power theory based on proposed system, it will be employed to obtained the reference
current of the DCMLI, the theory based on instantaneous values in three-phase power systems with or without
neutral wire, and is valid for steady-state or transitory operations, in this theory instantaneous active current ( ip)
and instantaneous reactive current (iq) of three phase system are calculated based on Clark transformation which
applied to the voltage and current vectors.
(d)-Hysteresis band controller will be used to optimize the switching pattern of diode clump inverter to
compensate harmonic and reactive load currents.
(e)-Analyze the obtained results and compare it with other published results.

1.3 Problem Statement
The operation of non-linear loads in power system and applications almost creates harmonics currents and
harmonics voltages especially in industrial systems. Therefore, the harmonic current and voltage exist at the
same frequency where inductive and capacitive of industrial power system are equal, this situation reflected to
the harmonic current and voltages and raise it and become much greater.

1
Innovative Systems Design and Engineering
ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
Vol.4, No.14, 2013

www.iiste.org

1.4 Literature Review
The power quality problem was as old as electrical system, but the interest in these problems starts from thirty
years only. However, the use of active power filters has started only in the last twenty years. There are some of
researches in this field in the last two decades are summarized as follows:
A distributed active filter system (DAFS) was discussed by (Po-Tai Cheng and Zhung-Lin Lee.2004), to
alleviate power systems harmonic distribution. Multiple active filter units of the DAFS are proposed to install on
the same location or different locations within the power system. In order to reduce the power lines voltage
harmonic distortion, the active filter units of the proposed DAFS cooperate without any communication among
them. They reduce voltage harmonics by work like a harmonic conductance. A controller of each unit is
programmed by droop relationship between the volt-ampere of the active filter unit and the harmonic
conductance so multiple active filter units can share the workload of harmonic filtering. The volt-ampere rating
of the active filter unit decides the slope of the relation in order to evenly distribute the workload according to
the each unit rated capacity. The distributed deployment of active filter units also shows that they can effectively
improve the power lines voltage THDs more than installing active filter in the radial system terminals.
The converter absorbed a current rich in harmonics. This would disrupt the network and the consumers joined at
the same node will influences. Several techniques used including active filtering and/or passive, to minimize the
harmonics of side network. (M. T. Benchouia, M.E.H. Benbouzid, A.Golea, S.E.Zouzou, 2007), have discussed
these techniques. Adaptive controller Referenced by The Fuzzy Model is used to minimize the converter
harmonics of the side network, including the DC-link voltage and power factor control. The result shows the line
current wave is approximately sinusoidal. They found that, the system has adequate dynamic response to load
variation according to the rapid change of the line current results. Also they found that any external disturbance
has not affected the reactive power. Also the study ends with the result that the increasing or decreasing of step
load torque determines the sign of the Input real power peaks.
Harmonic current-source load generates the harmonics and by using both of the shunt passive filter and shunt
active filter this harmonics can be compensated. Passive filter is not recommended to use because the system
impedance strongly determined the performance of passive filter and it may cause resonance problem, and so,
the active filter is more attractive.
If the harmonic of the voltage source load compensated by using shunt passive filters or shunt active filters, an
over current problems may occurs due to the amplification of the load current. The active filter capacity may be
the same or larger than that of the load. Hence, it is neither practical nor economical to use shunt active filter to
compensate harmonic voltage source. The power factor improvement is the determinant of the capacity of
passive filter; it may be overloaded in the harmonic voltage source application. When applying active filter with
harmonic voltage source load, a series reactor must be placed on the load side.
Another research discuss the design and simulation of Harmonic and power factor compensation of multiple
non-linear loads of a single phase shunt active power filter by (Z.F. Hussien, N. Atan, I.Z Abidin,2003). Whereas
the active filter is based on a full bridge single phase inverter. The system was modeled in Mat lab Simulink to
consist of an AC controller as nonlinear loads connected to active filter to enhance the harmonic of the current
injected by the load, and an uncontrolled rectifier.
The differences between the proposed model and other models are as follows:
- Topology is a Shunt Active Power Filter, current source for Ibrahim.A. Altawil, (2011), while it is a
comparison between two techniques to reduce THD multilevel voltage source inverter using cascaded
inverters with separated DC sources for Siriroj Sirisukprasert , (1999), and it is a shunt hybrid active
power filter system, for current source inverter based induction furnace(CSI-IF) for Adnan Tan, (2011),
but it is a Two inverter Shunt Active Power Filter Current source for the proposed model
- Load is a nonlinear load with inductive load for Ibrahim.A. Altawil, (2011), while it is in each phase, a
resistor and inductor are connected in series for Siriroj Sirisukprasert , (1999), and it is a Nonlinear
(CSI-IF) for Adnan Tan, (2011), but it is a nonlinear load (rectifier load bridge, inductive and DC
motor) for the proposed model.
- Simulation model is a three phase nine steps diode clamped multi level inverter Ibrahim.A. Altawil,
(2011), while it is three phase seven steps Multilevel voltage source inverter using cascaded inverters
with separated DC sources using triangular-carrier method for Siriroj Sirisukprasert, (1999), and it is
a Three phase three Step bridge inverter for Adnan Tan, (2011), but it is a three phase 11- Step diode
clamped multi-level inverter for the proposed model.
- Results are (THD=2.8%), (PF=0.95), (P=20kW), (Q=6kVAR) for Ibrahim.A. Altawil, (2011), while it
is a line voltage THD = 12.3% (P=1.8KW), (PF= 0.92), (Q=2.5 KVRA) for Siriroj Sirisukprasert,
(1999), and they are (THD=1.8- 3.2%), (PF=31. 5), (P=0.95), (Q=4kVAR) Adnan Tan, (2011), but
they are (THD=1.8%), (PF=0.99), (P=10MW), (Q=0.3MVAR) for the proposed model.

2
Innovative Systems Design and Engineering
ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
Vol.4, No.14, 2013

www.iiste.org

1.5 Power circuit topology
Many non-linear loads are the cause of non-sinusoidal current drawn from electrical power supply. This current
will produce voltage harmonics when passing through different kind of power system impedances. The
connected sensitive equipment which attached to the same power system will affected by these harmonics,
(Hussien, Atan, Abidin,2003). To reduce these harmonics, regularly, passive filters (LC filters) used, but other
unnecessary effects may occur it may result in parallel resonances with the network impedance. Active power
filters is proposed to use instead of the passive filter due to the harmful of resonance. Improve the power quality
without the disadvanteges of passive filters is the main objective to use shunt active power filters.
The Power Circuit Topology will be explained by the headings below.
1234-

Two Inverter Shunt Active Filters (SAFS).
Hysteresis PWM current controller.
Generation of Reference current using p-q theories
Diode-clamped multilevel inverter

1.5.1 Two Inverter Shunt Active Filters (SAFS)
SAFs are attached to the distribution line shunt, and they compensate the harmonics by injecting compensating
currents. The injected currents magnitude is equals to the disturbances in the system magnitude but opposite in
phase. This eliminates the harmonics in the transmission system to restore the waveforms of source voltage and
source current sinusoidal again. Depending upon the objective of the SAF, harmonic compensation yields real
power oscillations elimination; power factor correction or reduction of current harmonics from the distribution
system. Constant real power compensation can be provided by SAPF by compensating the oscillating active
power (P) and reactive power (Q) of the load.

Figure 5.1: Two parallel
inverters Shunt Active Filters

1.5.2 Hysteresis PWM current controller
The current controller of the hysteresis band for shunt active power filter can be approved for inverter switching
pattern generation. The proposed current control methods has an assortment for the configurations of such active
power filter, but in terms of immediate current controllability and straight forward the control method of
hysteresis current has the biggest rate of implementation than other current control methods. Hysteresis band
current controller has properties like sturdiness, fastest control, and tremendous dynamics with minimum
hardware. (L. Hongda and K. Cao)
The conventional hysteresis band current control scheme used for the control of active power filter line current is
shown in figure three, composed of active a hysteresis around the reference line current (I*L) and actual line

3
Innovative Systems Design and Engineering
ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
Vol.4, No.14, 2013

www.iiste.org

current of the active power filter is referred to as (IL). The hysteresis band current controller decides the
switching pattern of active power filter. The switching logic is formulated as follows: (S. Buso, S. Fasolo, L.
Malesani, P. Mattavelli, July 2000).
If IL < (I*L- HB) upper switch of the leg is OFF and lower switch of the leg is ON.
If IL > (I*L + HB) upper switch of the leg is ON and lower switch of the leg is OFF.

Figure 5.2: Conventional Hysteresis Band Current Controller

Figure 5.3: Simulation of Hysteresis Band Current Controller
1.5.3 Generation of Reference current using p-q theories
The three phase instantaneous reactive current (Iq) and instantaneous active current (Ip) are calculated by this
theory based on instantaneous reactive power theory. The current and voltage vector is calculated according to
the Clark transformation. The following equations illustrates the method to obtain the instantaneous values of
currents and voltages in the (α, β) coordinates. (FERRACCI, 2001).

(5.1)
Where:

4
Innovative Systems Design and Engineering
ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
Vol.4, No.14, 2013

www.iiste.org

A: transformation matrix and obtained of (FERRACCI, 2001) .And given as:

(5.2)

The transformation can be used in case of that the voltages are balanced and sinusoidal, as a summary
+

+

=0

(5.3)

The instantaneous reactive and active power in the coordinates of α, β is given according to the coming formula:
(FERRACCI, 2001)
(5.4)
(5.5)
According to the α–β plane, the equation of the currents as a function of the instantaneous power is addressed in
the following expression:

This yields that:

(5.8)

(5.9)

(5.10)
Equations (5.4) and (5.5), expressed in terms of the AC components in addition to the DC components the values
of p and q, which is:

Where:
the instantaneous power (p) DC component, and belongs to the conventional fundamental active
current. : Is the instantaneous power (p) AC component and belongs to the harmonic currents caused by the
instantaneous real power AC component.
: Is the imaginary instantaneous power (q) DC component, and belongs to the reactive power generated by the
voltages and currents fundamental components.
: Is the instantaneous imaginary power (q) AC component, and belongs to the harmonic currents caused by the
instantaneous reactive power ac component.
The active power filter reference signal must have the values of , and for compensation of the reactive
power (displacement power factor) and non-linear loads current harmonics. The following equations calculate
the reference currents needed by the active power filters:
(5.13)

5
Innovative Systems Design and Engineering
ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
Vol.4, No.14, 2013

www.iiste.org

The following matrix equation 5.14 presents the final compensating currents gathered with a, b, c reference
frames zero sequence components:
(5.14)

Where the zero sequence current components
=

( + + ).

Start

Input phase voltages

Input load currents

Voltages and Currents calculations
(Vα Vβ V0) and (Iα

Iβ I0)

P, q Transformation theory units

Input Vref and VDC

Calculation
PI Controller Correction

Calculation Currents after filtering (Icα’, Icβ’)

Phase Currents outputs

Figure 5.4: Generation of Reference current
using p-q theories

End

This block diagram (fig 5.4): chooses the instantaneous reactive power theory which we used to generate the
reference current and measure the power and reactive power and power factor. First of all we transfer the phase
voltage and load current from (a, b, c) reference frame to (0, α, β) reference frame, then we find the power and
reactive power and power factor.
1.5.4 Diode-clamped multilevel inverter
The shunt active power filter is operated as a controlled current source connected in parallel with the non-linear
loads driven by PWM to inject current harmonics into the ac source. 11-steps diode clamped inverter is used in
this work to generate compensation current (Z. F. Hussien. N. Atan, I. Z. Abidin, 2003) (F. Z. Peng, J-S Lai,

6
Innovative Systems Design and Engineering
ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
Vol.4, No.14, 2013

www.iiste.org

1996).A diode clamped multilevel inverter (M-level) inverter typically consists of (M-1) capacitors on the dc bus
and produces M-levels on the phase voltage. Also it contains 2*(M-1) switching devices and (M- 1)*(M-2)
clamping diodes. The dc voltage applied to the capacitors terminals, C1, C2, C3, C4 and C5 and each capacitor
has a voltage Vdc/5 and each devices voltage stress is limited to one capacitor voltage level through clamping
diode. The numbering order of the switches is S1, S2, S3, S4, S5, S1*, S2*, S3*, S4* and S5*.

Figure 5.5: Structure of three-phase, 11-Step of a diode-clamped inverter
1.6 Simulation and Results
1.6.1 OVERALL CIRCUIT DIAGRAM (SIMULATION MODEL): Fig 6.1
The overall diagram of the simulation circuit contains in the table 6.1
Table 6.1: system parameters
Parameter
Source Voltage
Source frequency f
Voltage phase angle
Source resistance
Source Inductance
Load inductance
Load Resistance
Armature Dc Motor Load inductance
Armature Dc Motor Load Resistance
Field Dc Motor Load inductance
Field Dc Motor Load Resistance
Field of Dc Motor

Value
11KVp-p
50 Hz
0.1 Ω
10 mH
1.5 mH
20 Ω
3H
2Ω
13 H
84Ω
400 V

7
Innovative Systems Design and Engineering
ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
Vol.4, No.14, 2013

www.iiste.org

Fig 6.1: Overall circuit diagram.
This figure is show overall system which mainly consists of:
1.
2.
3.
4.
5.
6.

AC voltage source.
Nonlinear load.
Two inverter Shunt active power filters (SAPF).
Instantaneous reactive power model (IRPT).
Gate signal (hysteresis band current control).
Discrete time.

Instantaneous reactive power theory is used in simulation to generate the reference of main system elements of
current, power, reactive power and power factor which it is used in the current control of hysteresis band. The
current control signals compared with actual current to produce the gating signal, figure 6.2 represent the
instantaneous reactive power simulation.

8
Innovative Systems Design and Engineering
ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
Vol.4, No.14, 2013

www.iiste.org

Fig 6.2: Inside instantaneous reactive power simulation.
Fast Fourier Transform (FFT) is suitable algorithms to discrete time sinusoidal signals founded in modern
software such as Mat lab. FFT algorithm required in discrete Fourier transforms (DFT) computation as well as
FFT inverse. FFT algorithms have varied type’s mentions as involving, number theory, group theory and also the
arithmetic of simple complex-number.
In MATLAB/Simulink, FFT algorithms used to explore the compensated source current. This tool is very simple
and easy to use. The main reason of used FFT is to order of harmonics by analyses the source current in the
system. Otherwise, FFT gives the proportion of harmonics magnitude with respect to fundamental magnitude.
Many features can found in this tool it can compute the signal and make many operations such as Total
Harmonic Distortion (THD). Figure 6.3 (c), 6.4 (b) and 6.5 (b) represents the current source fast Fourier
transform (FFT) analysis without SHAPF (THD = 20.18%) which is connected with one inverter SHAPF (THD
= 4.35%). also with connected two inverters SHAPF (THD = 2.05%) which shows further decries in THD when
using two inverter SHAPF for medium distribution system 11Kv is less than 5% the harmonic limit imposed by
IEEE-519 standard.
By using the initial elements and parameter represented on figure 6.1, and the diode rectifier of three phase with
impedance R =20 Ω, L= 1.5 mH as a load, the system simulated from t=0 s to t=0.4s. To be illustrated to only
balance three phase load is considered, the three phase load current is very high distorted. Otherwise, figure 6.3
(a) represents the pre-compensation current source.
Power Factor Before Filtering
1

0.8

pf

0.6

0.4

0.2

0
0

0.05

0.1

0.15

0.2

0.25

0.3

Time(S)

Fig 6.3 (a): unfaltering Load current.
Fig 6.3 (b): (APF) unless power factor (PF=0.77%).

9
Innovative Systems Design and Engineering
ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
Vol.4, No.14, 2013

www.iiste.org

Figure 6.3 (a) shows the highly distorted load current in the simulation.

Fundamental (50Hz) , THD= 20.18%
18

Mag (% of Fundamental)

16
14
12
10
8
6
4
2
0

0

5

10

15

20

25

Harmonic order

Fig 6.3 (c): (FFT) unless APF for source current. (THD =20.18%).
Figure 6.3 (c) deepened on choose of the harmonic in the source current unless active power filters. The figure
represents a high destroyed as we see. Furthermore, the total harmonic distortion is very high (20.18%) and the
most appearance harmonic is in the fifth.
Typically, by studying the steady state conditions, a small comparison must represented on thesis about the
waveforms before and after load also between source currents with two and one inverters APF and study the
effects on the harmonics
In the transient state conditions, it was observed that when the load current before and after filtering is increased
and becomes more sinusoidal from 0.1 to 0.2, resulting that the harmonics is decreased. But the harmonics are
not the same in Steady state and Transient state.
6.3 CASE1: STEADY STATE CONDITION
Two parallel inverters Shunt Active Power Filter (SHAPF) model is considered to a study state condition. Study
state test is made to evaluate the response of the two parallel SHAPF inverters. on this thesis focused to design a
simulation to study the behavior of distribution power system with one inverter shunt active power filter
(SHAPF), and with two parallel inverter together without shunt active power filter (SHAPF) to ensure that the
SHAPF is able to compensate the current harmonic which produced by non-linear load and compare the best
way to choose solution.
Figure 6.4 (a) represents the post-compensation current source with single inverter for particular phase A. This
shows the current have a sinusoidal form. Otherwise, and the Total Harmonic Distortion (THD) by using one
SHAPF inverter is illustrated in Figure 6.4(b)
Fundamental (50Hz) , THD= 4.35%
100
90
80

Mag (% of Fundamental)

70
60
50
40
30
20
10
0

0

5

10

15

20

Harmonic order

Fig 6.4 (a): Source current with filtering

Fig 6.4 (b): (FFT) for source current with single

and single inverter.

inverter (THD =4.35%).

10

25
Innovative Systems Design and Engineering
ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
Vol.4, No.14, 2013

www.iiste.org

Figure 8.10 deepened on the parameters of the harmonic from the source current after using single inverter active
power filter which is become small. The total harmonic distortion around (4.35%) which is a small and the most
appearance harmonic is around fifth.
The particular phase current source after compensation with two inverters Shunt Active Power Filter (SHAPF)
presented in Figure 8.11a to indicate that the current become more sinusoidal. Figure8.11b represents the three
phase’s current and the THD by using two inverters Shunt Active Power Filter (SHAPF) is shown in figure 8.11.c.
The results shows that when using two inverters is much better

Fundamental (50Hz) , THD= 2.06%
100
90
80

Mag (% of Fundamental)

70
60
50
40
30
20
10
0

0

5

10

15

20

Harmonic order

Fig 6.5 (a): Source current with filtering and

Fig 6.5 (b): FFT for source current and two inverter

two inverters.

(THD =2.05 %).

Figure 6.5 (b) consider to choose the harmonic of the source current after using two inverter active power filter
which is become very small and

the total harmonic distortion around (2.05%) and the most appearance

harmonic is the are the fifth. Figure 6.7 (a) represents that that the power factor correction was achieved.

power factor after filtering
1

0.8

Pf

0.6

0.4

0.2

0
0

0.05

0.1

0.15

0.2

0.25

0.3

Time(S)

Fig 6.7 (a): Total PF with APF.
Each figures 6.7 (b) and 6.7 (c) represents the steady state conations with and without APF, the active and
reactive power at the diode rectifier load.

11

25
Innovative Systems Design and Engineering
ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
Vol.4, No.14, 2013

www.iiste.org

Fig 6.7 (b): Active power of the load.

Fig 6.7 (c): Reactive power of the load.

Fundamental (50Hz) , THD= 20.18%
18

Mag (% of Fundamental)

16
14
12
10
8
6
4
2
0

0

5

10

15

20

25

Harmonic order

Fig 6.8 (a): Source current (FFT) unless APF with THD =20.18%.

Fundamental (50Hz) , THD= 4.35%
100
90
80

Mag (% of Fundamental)

70
60
50
40
30
20
10
0

0

5

10

15

20

Harmonic order

Fig 6.8 (b): (FFT) for source current cabled with single inverter (THD=4.35 %).

12

25
Innovative Systems Design and Engineering
ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
Vol.4, No.14, 2013

www.iiste.org

Fundamental (50Hz) , THD= 2.06%
100
90
80

Mag (% of Fundamental)

70
60
50
40
30
20
10
0

0

5

10

15

20

25

Harmonic order

Fig 6.13 (c): (FFT) for source current with two inverter (THD =2.05%).

Fig 6.8 (c): (FFT) for source current with two inverter
8.4 CASE 2 TRANSIENT STATE CONDITIONS: (THD =2.05%).
In this condition of study, we consider to turn on both systems we can see that the effects on the transient system
is grater then the steady state ( harmonics), one inverter SHAPF and two inverters SHAPF model are presented
to a transient condition. The transient test is used to evaluate the response and waveforms of the shunt active
power filter (SHAPF). This simulation is modeled under environment of MATLAB/ Simulink to ensure that the
shunt active power filter (SHAPF) is able to recover from this transient condition without affecting on the
stability of the overall system.
To declare the idea the DC motor load is added in parallel during period of time and the transient behavior of the
system was studied. The motor parameters summarized on table 6.1. The current waveform and the Total
Harmonic Distortion (THD) shown in Figure 6.9 (a, b) respectively

Fig.6.9 (a): transient condition with load current without filtering.

13
Innovative Systems Design and Engineering
ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
Vol.4, No.14, 2013

www.iiste.org

Fundamental (50Hz) , THD= 14.38%
20

Mag (% of Fundamental)

18
16
14
12
10
8
6
4
2
0

0

5

10

15

20

25

Harmonic order

Fig 6.10 (b) : Source current (FFT) unless two inverters (THD =14.38%).
Figure 6.10 (a) represents the current source for particular phase after compensation with one inverter SHAPF, we
can mention and shows that the current is more sinusoidal and in this area the harmonic is decrease between 0.1 to
0.2, the THD by using two inverter SHAPF is shown in figure 6.10 (b).

Fundamental (50Hz) = 2040 , THD= 3.22%
100
90

Mag (% of Fundamental)

80
70
60
50
40
30
20
10
0

0

5

10

15

20

25

Harmonic order

Fig 6.10 (a): transient source current filter
with APF.

Fig 6.10 (b): (FFT) for source current by using single
inverter (THD =3.22%).

Figure 6.11 (a) represents the current source for a particular phase after compensation with two SHAPF inverters
which is depicted, we can see that the current is enhanced to be more sinusoidal and in this area the harmonic is
decrease between 0.1 to 0.2, the THD by using two inverters SHAPF is shown in figure 6.11 (b).

Fig 6.11 (a): transient source current filter with two inverters.

14
Innovative Systems Design and Engineering
ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
Vol.4, No.14, 2013

www.iiste.org

Fundamental (50Hz) , THD= 1.80%
100
90

Mag (% of Fundamental)

80
70
60
50
40
30
20
10
0

0

5

10

15

20

25

Harmonic order

Fig 6.11 (b): (FFT) for source current with two inverters (THD =1.80%).

Fig 6.12 (a): Active power of the load.

Fig 6.12 (b): Reactive power of the load.

15
Innovative Systems Design and Engineering
ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
Vol.4, No.14, 2013

www.iiste.org

Fig 6.13: Total power factor with (APF).

Table 6.2: Summary results.

without inverter SHAPF

with one inverter SHAPF

with two inverter SHAPF

20.18%
14.38%

10

10

10

4.35%
3.22%
2.05%

1.8%

THD Steady state THD Transient state

0.77 0.95 0.99
power factor

16

0.85
P(MW)

0.35 0.32

Q(MVAR)
Innovative Systems Design and Engineering
ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
Vol.4, No.14, 2013

www.iiste.org

1.7 CONCLUSIONS
In recent years, most researchers studied a Shunt Active Power Filters (SAPF) based on conventional two-shunt
inverter with conventional controllers that requires a complex and a complicated mathematical model. In order to
overcome this problem in the literature a Hysteresis band controller based diode clamped multilevel inverter has
been implemented and extended. In my thesis deal with implementing and design of three phase two inverters
shunt Active Power Filter (APF), in distribution system 11KV to enhance the reactive power and so eliminate
harmonics from a typical non-linear load, composed from (uncontrolled bridge rectifier with inductive load and
DC motor). In this research, almost a unity power factor and sinusoidal current source is achieved. The current
source total harmonic distortion (THD) after compensation by single inverter is 4.35% but by using two inverters
it decreases to 2.05% which is agreed and less than the harmonic limit imposed by the IEEE-519 standard (3%),
by using two parallel inverters with 11-Step diode clamped multi-level inverter the circuit is simulated by using
MATLAB/ Simulink.
REFERENCES
-

R. C. Dugan, M. F. McGranaghan, S. Santosa, and H. W. Beaty, “Electrical Power Systems Quality”,
second edition, McGraw-Hill, 2002.
C. Sankaran, “Power Quality, the Electric Power Engineering Series”, CRC PRESS, 2002.
Philippe FERRACCI, “Power Quality, Cahier technique”, Cahiers Techniques Electric, 2001, – No.
199.
Lund quist, Johan, Associated power technologies," Total harmonic distortion and effects in electrical
power systems", 2001.
Alexander Kusko, Marc Thompson, McGraw Hill P.C. Power Quality in Electrical Systems, 2007.
Angelo Baggini. ‘Hand book of power quality’, John Wiley and Sons, Ltd. The Atrium, Southern Gate,
Chichester, West Sussex PO19 8SQ, England.
Francisco C. De La Rosa, Harmonics and Power Systems, The Electric Power Engineering Series,
Taylor & Francis Group, 2006.
J. David Irwin, Power electronics handbook, Auburn University, Series editor.
Lander, Cyril W. (1993). “Rectifying Circuits". Power electronics (3rd ed. ed.). London: McGraw-Hill.
ISBN 9780077077143.
Z. F. Hussien. N. Atan, I. Z. Abidin, "Shunt active power filter for harmonic compensation of nonlinear
loads", 0-7803-8208-0/03/$17.00©2003 IEEE.
R. S. Herrera, P. Salmeron, "Instantaneous Reactive Power Theory: A Reference in Nonlinear Loads
Compensation", IEEETRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 56, NO. 6, JUNE
2009.
Guichum Huang, "The algorithm of a reference compensation current for Shunt Active Power Filters
control”, 978-0-7695-4116-7/10 $26.00 © 2010 IEEE.
L. Hongda and K. Cao,"Active power filter simulation based on instaneous reactive power theory and
the PWM hysteresis control mode",978-1-4244-8161-3/11/$26.00©2011 IEEE.
S. Buso, S. Fasolo, L. Malesani, P. Mattavelli, ''A dead beat adaptive hysteresis current control",IEEE
Transactions on industry applications, Vol.36, no.4, pp1174-1180, July 2000.
M. Kale, E. Ozdemir, "A novel adaptive hysteresis band current controller for shunt active power
filter", 0-7803-7729-X/03/$17.00©2003 IEEE.
F. Z. Peng, "Application Issues of active power filters", IEEE Industry applications magazineSeptember/October 1998, 1077-2618/98/$10.00 © 1998 IEEE.
A.de. Almeida, L. Moreira, J. Delgado "Power quality problems and new solutions", Department of
Electrical and Computer Engineering, University of Coimbra, Pó II, Coimbra (Portugal).
lo
H. Akagi, Y. Kanazawa, and A. Nabae, “Generalized theory of the instantaneous reactive power in
three-phase circuits,” in Proc. IPEC, Tokyo, Japan, 1983, pp. 1375-1386.
Modern power electronics and AC drives, Bimal K. Bose, Prentice hall PTR 2000, ISBN 0-13-0167436.

17
This academic article was published by The International Institute for Science,
Technology and Education (IISTE). The IISTE is a pioneer in the Open Access
Publishing service based in the U.S. and Europe. The aim of the institute is
Accelerating Global Knowledge Sharing.
More information about the publisher can be found in the IISTE’s homepage:
http://www.iiste.org
CALL FOR JOURNAL PAPERS
The IISTE is currently hosting more than 30 peer-reviewed academic journals and
collaborating with academic institutions around the world. There’s no deadline for
submission. Prospective authors of IISTE journals can find the submission
instruction on the following page: http://www.iiste.org/journals/
The IISTE
editorial team promises to the review and publish all the qualified submissions in a
fast manner. All the journals articles are available online to the readers all over the
world without financial, legal, or technical barriers other than those inseparable from
gaining access to the internet itself. Printed version of the journals is also available
upon request of readers and authors.
MORE RESOURCES
Book publication information: http://www.iiste.org/book/
Recent conferences: http://www.iiste.org/conference/
IISTE Knowledge Sharing Partners
EBSCO, Index Copernicus, Ulrich's Periodicals Directory, JournalTOCS, PKP Open
Archives Harvester, Bielefeld Academic Search Engine, Elektronische
Zeitschriftenbibliothek EZB, Open J-Gate, OCLC WorldCat, Universe Digtial
Library , NewJour, Google Scholar

More Related Content

What's hot

Hysteresis Current Control Based Shunt Active Power Filter for Six Pulse Ac/D...
Hysteresis Current Control Based Shunt Active Power Filter for Six Pulse Ac/D...Hysteresis Current Control Based Shunt Active Power Filter for Six Pulse Ac/D...
Hysteresis Current Control Based Shunt Active Power Filter for Six Pulse Ac/D...IJERA Editor
 
A NOVEL TCHNOLOGY FOR HARMONICS AND UNBALANCE COMPENSATION IN ELECTRIC TRACTI...
A NOVEL TCHNOLOGY FOR HARMONICS AND UNBALANCE COMPENSATION IN ELECTRIC TRACTI...A NOVEL TCHNOLOGY FOR HARMONICS AND UNBALANCE COMPENSATION IN ELECTRIC TRACTI...
A NOVEL TCHNOLOGY FOR HARMONICS AND UNBALANCE COMPENSATION IN ELECTRIC TRACTI...ijiert bestjournal
 
Improvement of the electric power quality using
Improvement of the electric power quality usingImprovement of the electric power quality using
Improvement of the electric power quality usingVikram Rawani
 
Power Quality Improvement in 3-Φ Power System with Shunt Active filter using ...
Power Quality Improvement in 3-Φ Power System with Shunt Active filter using ...Power Quality Improvement in 3-Φ Power System with Shunt Active filter using ...
Power Quality Improvement in 3-Φ Power System with Shunt Active filter using ...AI Publications
 
Design of Shunt Active Power Filter to eliminate harmonics generated by CFL
Design of Shunt Active Power Filter to eliminate harmonics generated by CFLDesign of Shunt Active Power Filter to eliminate harmonics generated by CFL
Design of Shunt Active Power Filter to eliminate harmonics generated by CFLpaperpublications3
 
Optimize Controlling of Active Filters Controlled by Pi Controller
Optimize Controlling of Active Filters Controlled by Pi ControllerOptimize Controlling of Active Filters Controlled by Pi Controller
Optimize Controlling of Active Filters Controlled by Pi ControllerIRJET Journal
 
Enhancement of Power Quality Using the Combination of Thyristor-Controlled Re...
Enhancement of Power Quality Using the Combination of Thyristor-Controlled Re...Enhancement of Power Quality Using the Combination of Thyristor-Controlled Re...
Enhancement of Power Quality Using the Combination of Thyristor-Controlled Re...IJERD Editor
 
report of Improvement of the Electric Power Quality Using Series Active and S...
report of Improvement of the Electric Power Quality Using Series Active and S...report of Improvement of the Electric Power Quality Using Series Active and S...
report of Improvement of the Electric Power Quality Using Series Active and S...Vikram Rawani
 
IJCER (www.ijceronline.com) International Journal of computational Engineerin...
IJCER (www.ijceronline.com) International Journal of computational Engineerin...IJCER (www.ijceronline.com) International Journal of computational Engineerin...
IJCER (www.ijceronline.com) International Journal of computational Engineerin...ijceronline
 
Application of Active Power Filter for Power Factor Correction of Nonlinear L...
Application of Active Power Filter for Power Factor Correction of Nonlinear L...Application of Active Power Filter for Power Factor Correction of Nonlinear L...
Application of Active Power Filter for Power Factor Correction of Nonlinear L...Pravin Sonwane
 
Volume 2-issue-6-1950-1954
Volume 2-issue-6-1950-1954Volume 2-issue-6-1950-1954
Volume 2-issue-6-1950-1954Editor IJARCET
 
Simulation and Design of SRF based Control Algorithm for Three Phase Shunt Ac...
Simulation and Design of SRF based Control Algorithm for Three Phase Shunt Ac...Simulation and Design of SRF based Control Algorithm for Three Phase Shunt Ac...
Simulation and Design of SRF based Control Algorithm for Three Phase Shunt Ac...idescitation
 
04 28 oct16 13501 27650-1-sm(edit))
04 28 oct16 13501 27650-1-sm(edit))04 28 oct16 13501 27650-1-sm(edit))
04 28 oct16 13501 27650-1-sm(edit))IAESIJEECS
 
A fault-tolerant photovoltaic integrated shunt active power filter with a 27-...
A fault-tolerant photovoltaic integrated shunt active power filter with a 27-...A fault-tolerant photovoltaic integrated shunt active power filter with a 27-...
A fault-tolerant photovoltaic integrated shunt active power filter with a 27-...IJECEIAES
 
Application Of Shuntactive Power Filter Paper Presentation
Application Of Shuntactive Power Filter Paper PresentationApplication Of Shuntactive Power Filter Paper Presentation
Application Of Shuntactive Power Filter Paper Presentationguestac67362
 

What's hot (17)

Hysteresis Current Control Based Shunt Active Power Filter for Six Pulse Ac/D...
Hysteresis Current Control Based Shunt Active Power Filter for Six Pulse Ac/D...Hysteresis Current Control Based Shunt Active Power Filter for Six Pulse Ac/D...
Hysteresis Current Control Based Shunt Active Power Filter for Six Pulse Ac/D...
 
A NOVEL TCHNOLOGY FOR HARMONICS AND UNBALANCE COMPENSATION IN ELECTRIC TRACTI...
A NOVEL TCHNOLOGY FOR HARMONICS AND UNBALANCE COMPENSATION IN ELECTRIC TRACTI...A NOVEL TCHNOLOGY FOR HARMONICS AND UNBALANCE COMPENSATION IN ELECTRIC TRACTI...
A NOVEL TCHNOLOGY FOR HARMONICS AND UNBALANCE COMPENSATION IN ELECTRIC TRACTI...
 
Improvement of the electric power quality using
Improvement of the electric power quality usingImprovement of the electric power quality using
Improvement of the electric power quality using
 
Ijetr012048
Ijetr012048Ijetr012048
Ijetr012048
 
Power Quality Improvement in 3-Φ Power System with Shunt Active filter using ...
Power Quality Improvement in 3-Φ Power System with Shunt Active filter using ...Power Quality Improvement in 3-Φ Power System with Shunt Active filter using ...
Power Quality Improvement in 3-Φ Power System with Shunt Active filter using ...
 
Design of Shunt Active Power Filter to eliminate harmonics generated by CFL
Design of Shunt Active Power Filter to eliminate harmonics generated by CFLDesign of Shunt Active Power Filter to eliminate harmonics generated by CFL
Design of Shunt Active Power Filter to eliminate harmonics generated by CFL
 
Optimize Controlling of Active Filters Controlled by Pi Controller
Optimize Controlling of Active Filters Controlled by Pi ControllerOptimize Controlling of Active Filters Controlled by Pi Controller
Optimize Controlling of Active Filters Controlled by Pi Controller
 
Enhancement of Power Quality Using the Combination of Thyristor-Controlled Re...
Enhancement of Power Quality Using the Combination of Thyristor-Controlled Re...Enhancement of Power Quality Using the Combination of Thyristor-Controlled Re...
Enhancement of Power Quality Using the Combination of Thyristor-Controlled Re...
 
report of Improvement of the Electric Power Quality Using Series Active and S...
report of Improvement of the Electric Power Quality Using Series Active and S...report of Improvement of the Electric Power Quality Using Series Active and S...
report of Improvement of the Electric Power Quality Using Series Active and S...
 
IJCER (www.ijceronline.com) International Journal of computational Engineerin...
IJCER (www.ijceronline.com) International Journal of computational Engineerin...IJCER (www.ijceronline.com) International Journal of computational Engineerin...
IJCER (www.ijceronline.com) International Journal of computational Engineerin...
 
Application of Active Power Filter for Power Factor Correction of Nonlinear L...
Application of Active Power Filter for Power Factor Correction of Nonlinear L...Application of Active Power Filter for Power Factor Correction of Nonlinear L...
Application of Active Power Filter for Power Factor Correction of Nonlinear L...
 
Ag33180185
Ag33180185Ag33180185
Ag33180185
 
Volume 2-issue-6-1950-1954
Volume 2-issue-6-1950-1954Volume 2-issue-6-1950-1954
Volume 2-issue-6-1950-1954
 
Simulation and Design of SRF based Control Algorithm for Three Phase Shunt Ac...
Simulation and Design of SRF based Control Algorithm for Three Phase Shunt Ac...Simulation and Design of SRF based Control Algorithm for Three Phase Shunt Ac...
Simulation and Design of SRF based Control Algorithm for Three Phase Shunt Ac...
 
04 28 oct16 13501 27650-1-sm(edit))
04 28 oct16 13501 27650-1-sm(edit))04 28 oct16 13501 27650-1-sm(edit))
04 28 oct16 13501 27650-1-sm(edit))
 
A fault-tolerant photovoltaic integrated shunt active power filter with a 27-...
A fault-tolerant photovoltaic integrated shunt active power filter with a 27-...A fault-tolerant photovoltaic integrated shunt active power filter with a 27-...
A fault-tolerant photovoltaic integrated shunt active power filter with a 27-...
 
Application Of Shuntactive Power Filter Paper Presentation
Application Of Shuntactive Power Filter Paper PresentationApplication Of Shuntactive Power Filter Paper Presentation
Application Of Shuntactive Power Filter Paper Presentation
 

Viewers also liked

Adaptive Modified Minimally Switched Hysteresis Controlled Shunt Active Power...
Adaptive Modified Minimally Switched Hysteresis Controlled Shunt Active Power...Adaptive Modified Minimally Switched Hysteresis Controlled Shunt Active Power...
Adaptive Modified Minimally Switched Hysteresis Controlled Shunt Active Power...idescitation
 
A study of hysteresis band current control scheme for shunt active power filt...
A study of hysteresis band current control scheme for shunt active power filt...A study of hysteresis band current control scheme for shunt active power filt...
A study of hysteresis band current control scheme for shunt active power filt...Asoka Technologies
 
Analysis of Shunt APF (Active PowerFilter)
Analysis of Shunt APF (Active PowerFilter)Analysis of Shunt APF (Active PowerFilter)
Analysis of Shunt APF (Active PowerFilter)Rajesh Dunna
 
Shunt active power filter
Shunt active power filterShunt active power filter
Shunt active power filterRanganath
 
Performance enhancement of shunt active power filter with fuzzy and hysteresi...
Performance enhancement of shunt active power filter with fuzzy and hysteresi...Performance enhancement of shunt active power filter with fuzzy and hysteresi...
Performance enhancement of shunt active power filter with fuzzy and hysteresi...Asoka Technologies
 
Adaptive-Hysteresis-Based-SHAF-Using-PI-and-FLC-Controller-for-Current-Harmon...
Adaptive-Hysteresis-Based-SHAF-Using-PI-and-FLC-Controller-for-Current-Harmon...Adaptive-Hysteresis-Based-SHAF-Using-PI-and-FLC-Controller-for-Current-Harmon...
Adaptive-Hysteresis-Based-SHAF-Using-PI-and-FLC-Controller-for-Current-Harmon...Atul Sharma
 
Implementation of hysteresis current control for single phase grid connected ...
Implementation of hysteresis current control for single phase grid connected ...Implementation of hysteresis current control for single phase grid connected ...
Implementation of hysteresis current control for single phase grid connected ...Asoka Technologies
 
ACTIVE vs PASSIVE HARMONICS FILTERS
ACTIVE vs PASSIVE HARMONICS FILTERSACTIVE vs PASSIVE HARMONICS FILTERS
ACTIVE vs PASSIVE HARMONICS FILTERSJ A Simon
 
Performance Analysis of Three-phase Four-wire Shunt Active Power Filter
Performance Analysis  of  Three-phase  Four-wire Shunt Active  Power  Filter Performance Analysis  of  Three-phase  Four-wire Shunt Active  Power  Filter
Performance Analysis of Three-phase Four-wire Shunt Active Power Filter ST. MARTIN'S ENGINEERING COLLEGE
 
Harmonics and mitigation techniques
Harmonics and mitigation techniquesHarmonics and mitigation techniques
Harmonics and mitigation techniquesrifat maryum
 
Active_Power_Filter
Active_Power_FilterActive_Power_Filter
Active_Power_Filteremredurna
 
Active Power Filter
Active Power FilterActive Power Filter
Active Power FilterJawad Iqbal
 
Harmonics in power system
Harmonics in power systemHarmonics in power system
Harmonics in power systemMinh Anh Nguyen
 
Design Of Hybrid Series Active Filters for Harmonic Reduction in Single Phase...
Design Of Hybrid Series Active Filters for Harmonic Reduction in Single Phase...Design Of Hybrid Series Active Filters for Harmonic Reduction in Single Phase...
Design Of Hybrid Series Active Filters for Harmonic Reduction in Single Phase...IJMER
 
A Novel Approach of Harmonic Reduction with Transformer Connected 3-Phase Mul...
A Novel Approach of Harmonic Reduction with Transformer Connected 3-Phase Mul...A Novel Approach of Harmonic Reduction with Transformer Connected 3-Phase Mul...
A Novel Approach of Harmonic Reduction with Transformer Connected 3-Phase Mul...IJMER
 

Viewers also liked (20)

Adaptive Modified Minimally Switched Hysteresis Controlled Shunt Active Power...
Adaptive Modified Minimally Switched Hysteresis Controlled Shunt Active Power...Adaptive Modified Minimally Switched Hysteresis Controlled Shunt Active Power...
Adaptive Modified Minimally Switched Hysteresis Controlled Shunt Active Power...
 
A study of hysteresis band current control scheme for shunt active power filt...
A study of hysteresis band current control scheme for shunt active power filt...A study of hysteresis band current control scheme for shunt active power filt...
A study of hysteresis band current control scheme for shunt active power filt...
 
65 113-121
65 113-12165 113-121
65 113-121
 
Analysis of Shunt APF (Active PowerFilter)
Analysis of Shunt APF (Active PowerFilter)Analysis of Shunt APF (Active PowerFilter)
Analysis of Shunt APF (Active PowerFilter)
 
Shunt active power filter
Shunt active power filterShunt active power filter
Shunt active power filter
 
Exp passive filter (9)
Exp passive filter (9)Exp passive filter (9)
Exp passive filter (9)
 
Performance enhancement of shunt active power filter with fuzzy and hysteresi...
Performance enhancement of shunt active power filter with fuzzy and hysteresi...Performance enhancement of shunt active power filter with fuzzy and hysteresi...
Performance enhancement of shunt active power filter with fuzzy and hysteresi...
 
Adaptive-Hysteresis-Based-SHAF-Using-PI-and-FLC-Controller-for-Current-Harmon...
Adaptive-Hysteresis-Based-SHAF-Using-PI-and-FLC-Controller-for-Current-Harmon...Adaptive-Hysteresis-Based-SHAF-Using-PI-and-FLC-Controller-for-Current-Harmon...
Adaptive-Hysteresis-Based-SHAF-Using-PI-and-FLC-Controller-for-Current-Harmon...
 
Exp passive filter (4)
Exp passive filter (4)Exp passive filter (4)
Exp passive filter (4)
 
Implementation of hysteresis current control for single phase grid connected ...
Implementation of hysteresis current control for single phase grid connected ...Implementation of hysteresis current control for single phase grid connected ...
Implementation of hysteresis current control for single phase grid connected ...
 
ACTIVE vs PASSIVE HARMONICS FILTERS
ACTIVE vs PASSIVE HARMONICS FILTERSACTIVE vs PASSIVE HARMONICS FILTERS
ACTIVE vs PASSIVE HARMONICS FILTERS
 
THREE PHASE INVERTER FED BLDC MOTOR DRIVE
THREE PHASE INVERTER FED BLDC MOTOR DRIVETHREE PHASE INVERTER FED BLDC MOTOR DRIVE
THREE PHASE INVERTER FED BLDC MOTOR DRIVE
 
Performance Analysis of Three-phase Four-wire Shunt Active Power Filter
Performance Analysis  of  Three-phase  Four-wire Shunt Active  Power  Filter Performance Analysis  of  Three-phase  Four-wire Shunt Active  Power  Filter
Performance Analysis of Three-phase Four-wire Shunt Active Power Filter
 
Harmonics and mitigation techniques
Harmonics and mitigation techniquesHarmonics and mitigation techniques
Harmonics and mitigation techniques
 
Active_Power_Filter
Active_Power_FilterActive_Power_Filter
Active_Power_Filter
 
Active Power Filter
Active Power FilterActive Power Filter
Active Power Filter
 
Harmonics in power system
Harmonics in power systemHarmonics in power system
Harmonics in power system
 
Design Of Hybrid Series Active Filters for Harmonic Reduction in Single Phase...
Design Of Hybrid Series Active Filters for Harmonic Reduction in Single Phase...Design Of Hybrid Series Active Filters for Harmonic Reduction in Single Phase...
Design Of Hybrid Series Active Filters for Harmonic Reduction in Single Phase...
 
A Novel Approach of Harmonic Reduction with Transformer Connected 3-Phase Mul...
A Novel Approach of Harmonic Reduction with Transformer Connected 3-Phase Mul...A Novel Approach of Harmonic Reduction with Transformer Connected 3-Phase Mul...
A Novel Approach of Harmonic Reduction with Transformer Connected 3-Phase Mul...
 
Build Features, Not Apps
Build Features, Not AppsBuild Features, Not Apps
Build Features, Not Apps
 

Similar to Shunt active power filters based on diode clamped multilevel inverter and hysteresis band current controller

Mitigation of the Harmonics under Reactive Power Compensation by SHPF-TCR Usi...
Mitigation of the Harmonics under Reactive Power Compensation by SHPF-TCR Usi...Mitigation of the Harmonics under Reactive Power Compensation by SHPF-TCR Usi...
Mitigation of the Harmonics under Reactive Power Compensation by SHPF-TCR Usi...IJERA Editor
 
Comparative of Conventional and Intelligence Controller based Hybrid Generati...
Comparative of Conventional and Intelligence Controller based Hybrid Generati...Comparative of Conventional and Intelligence Controller based Hybrid Generati...
Comparative of Conventional and Intelligence Controller based Hybrid Generati...IJERD Editor
 
Power System Harmonic Compensation Using Shunt Active Power Filter
Power System Harmonic Compensation Using Shunt Active Power FilterPower System Harmonic Compensation Using Shunt Active Power Filter
Power System Harmonic Compensation Using Shunt Active Power FilterIJERA Editor
 
Pll based shunt active harmonic filter to compensate multiple non linear loads
Pll based shunt active harmonic filter to compensate multiple non linear loadsPll based shunt active harmonic filter to compensate multiple non linear loads
Pll based shunt active harmonic filter to compensate multiple non linear loadsIAEME Publication
 
Volume 2-issue-6-1950-1954
Volume 2-issue-6-1950-1954Volume 2-issue-6-1950-1954
Volume 2-issue-6-1950-1954Editor IJARCET
 
Power-Quality-Improvement-Using-PI-and-Fuzzy-Logic-Controllers-Based-Shunt-Ac...
Power-Quality-Improvement-Using-PI-and-Fuzzy-Logic-Controllers-Based-Shunt-Ac...Power-Quality-Improvement-Using-PI-and-Fuzzy-Logic-Controllers-Based-Shunt-Ac...
Power-Quality-Improvement-Using-PI-and-Fuzzy-Logic-Controllers-Based-Shunt-Ac...Atul Sharma
 
Design of shunt hybrid active power filter for compensating harmonic currents...
Design of shunt hybrid active power filter for compensating harmonic currents...Design of shunt hybrid active power filter for compensating harmonic currents...
Design of shunt hybrid active power filter for compensating harmonic currents...TELKOMNIKA JOURNAL
 
HYBRID ACTIVE POWER FILTER FOR EFFECTIVE COMPENSATION WITH CONTROL SCHEME
HYBRID ACTIVE POWER FILTER FOR EFFECTIVE COMPENSATION WITH CONTROL SCHEMEHYBRID ACTIVE POWER FILTER FOR EFFECTIVE COMPENSATION WITH CONTROL SCHEME
HYBRID ACTIVE POWER FILTER FOR EFFECTIVE COMPENSATION WITH CONTROL SCHEMEBlossoms Anjali
 
Power system harmonic reduction using shunt active filter
Power system harmonic reduction using shunt active filterPower system harmonic reduction using shunt active filter
Power system harmonic reduction using shunt active filtereSAT Publishing House
 
NOVEL CONTROL STRATEGIES FOR DISTRIBUTED ACTIVE FILTER
NOVEL CONTROL STRATEGIES FOR DISTRIBUTED ACTIVE FILTER NOVEL CONTROL STRATEGIES FOR DISTRIBUTED ACTIVE FILTER
NOVEL CONTROL STRATEGIES FOR DISTRIBUTED ACTIVE FILTER elelijjournal
 
International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)IJERD Editor
 
Modeling & Analysis of Shunt Active Power Filter Using IRP Theory Fed to Indu...
Modeling & Analysis of Shunt Active Power Filter Using IRP Theory Fed to Indu...Modeling & Analysis of Shunt Active Power Filter Using IRP Theory Fed to Indu...
Modeling & Analysis of Shunt Active Power Filter Using IRP Theory Fed to Indu...IJERA Editor
 
The Shunt Active Power Filter to Compensate Reactive Power and Harmonics with...
The Shunt Active Power Filter to Compensate Reactive Power and Harmonics with...The Shunt Active Power Filter to Compensate Reactive Power and Harmonics with...
The Shunt Active Power Filter to Compensate Reactive Power and Harmonics with...ijtsrd
 
Harmonic Compensation for Non Linear Load Using PWM Based Active Filter
Harmonic Compensation for Non Linear Load Using PWM Based Active FilterHarmonic Compensation for Non Linear Load Using PWM Based Active Filter
Harmonic Compensation for Non Linear Load Using PWM Based Active Filteridescitation
 
IRJET- Harmonic Mitigation for Power Quality Improvement using Active Power F...
IRJET- Harmonic Mitigation for Power Quality Improvement using Active Power F...IRJET- Harmonic Mitigation for Power Quality Improvement using Active Power F...
IRJET- Harmonic Mitigation for Power Quality Improvement using Active Power F...IRJET Journal
 

Similar to Shunt active power filters based on diode clamped multilevel inverter and hysteresis band current controller (20)

Mitigation of the Harmonics under Reactive Power Compensation by SHPF-TCR Usi...
Mitigation of the Harmonics under Reactive Power Compensation by SHPF-TCR Usi...Mitigation of the Harmonics under Reactive Power Compensation by SHPF-TCR Usi...
Mitigation of the Harmonics under Reactive Power Compensation by SHPF-TCR Usi...
 
Comparative of Conventional and Intelligence Controller based Hybrid Generati...
Comparative of Conventional and Intelligence Controller based Hybrid Generati...Comparative of Conventional and Intelligence Controller based Hybrid Generati...
Comparative of Conventional and Intelligence Controller based Hybrid Generati...
 
Prateek PPT.pptx
Prateek  PPT.pptxPrateek  PPT.pptx
Prateek PPT.pptx
 
Power System Harmonic Compensation Using Shunt Active Power Filter
Power System Harmonic Compensation Using Shunt Active Power FilterPower System Harmonic Compensation Using Shunt Active Power Filter
Power System Harmonic Compensation Using Shunt Active Power Filter
 
Pll based shunt active harmonic filter to compensate multiple non linear loads
Pll based shunt active harmonic filter to compensate multiple non linear loadsPll based shunt active harmonic filter to compensate multiple non linear loads
Pll based shunt active harmonic filter to compensate multiple non linear loads
 
Volume 2-issue-6-1950-1954
Volume 2-issue-6-1950-1954Volume 2-issue-6-1950-1954
Volume 2-issue-6-1950-1954
 
B011140509
B011140509B011140509
B011140509
 
Power-Quality-Improvement-Using-PI-and-Fuzzy-Logic-Controllers-Based-Shunt-Ac...
Power-Quality-Improvement-Using-PI-and-Fuzzy-Logic-Controllers-Based-Shunt-Ac...Power-Quality-Improvement-Using-PI-and-Fuzzy-Logic-Controllers-Based-Shunt-Ac...
Power-Quality-Improvement-Using-PI-and-Fuzzy-Logic-Controllers-Based-Shunt-Ac...
 
Design of shunt hybrid active power filter for compensating harmonic currents...
Design of shunt hybrid active power filter for compensating harmonic currents...Design of shunt hybrid active power filter for compensating harmonic currents...
Design of shunt hybrid active power filter for compensating harmonic currents...
 
HYBRID ACTIVE POWER FILTER FOR EFFECTIVE COMPENSATION WITH CONTROL SCHEME
HYBRID ACTIVE POWER FILTER FOR EFFECTIVE COMPENSATION WITH CONTROL SCHEMEHYBRID ACTIVE POWER FILTER FOR EFFECTIVE COMPENSATION WITH CONTROL SCHEME
HYBRID ACTIVE POWER FILTER FOR EFFECTIVE COMPENSATION WITH CONTROL SCHEME
 
Power system harmonic reduction using shunt active filter
Power system harmonic reduction using shunt active filterPower system harmonic reduction using shunt active filter
Power system harmonic reduction using shunt active filter
 
NOVEL CONTROL STRATEGIES FOR DISTRIBUTED ACTIVE FILTER
NOVEL CONTROL STRATEGIES FOR DISTRIBUTED ACTIVE FILTER NOVEL CONTROL STRATEGIES FOR DISTRIBUTED ACTIVE FILTER
NOVEL CONTROL STRATEGIES FOR DISTRIBUTED ACTIVE FILTER
 
Ae4301167171
Ae4301167171Ae4301167171
Ae4301167171
 
International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)
 
Modeling & Analysis of Shunt Active Power Filter Using IRP Theory Fed to Indu...
Modeling & Analysis of Shunt Active Power Filter Using IRP Theory Fed to Indu...Modeling & Analysis of Shunt Active Power Filter Using IRP Theory Fed to Indu...
Modeling & Analysis of Shunt Active Power Filter Using IRP Theory Fed to Indu...
 
The Shunt Active Power Filter to Compensate Reactive Power and Harmonics with...
The Shunt Active Power Filter to Compensate Reactive Power and Harmonics with...The Shunt Active Power Filter to Compensate Reactive Power and Harmonics with...
The Shunt Active Power Filter to Compensate Reactive Power and Harmonics with...
 
Harmonic Compensation for Non Linear Load Using PWM Based Active Filter
Harmonic Compensation for Non Linear Load Using PWM Based Active FilterHarmonic Compensation for Non Linear Load Using PWM Based Active Filter
Harmonic Compensation for Non Linear Load Using PWM Based Active Filter
 
IRJET- Harmonic Mitigation for Power Quality Improvement using Active Power F...
IRJET- Harmonic Mitigation for Power Quality Improvement using Active Power F...IRJET- Harmonic Mitigation for Power Quality Improvement using Active Power F...
IRJET- Harmonic Mitigation for Power Quality Improvement using Active Power F...
 
[IJET V2I2P30] Authors: AnkurGheewala, Jay Chanawala,Nikhil Jadav,Modi Rishit...
[IJET V2I2P30] Authors: AnkurGheewala, Jay Chanawala,Nikhil Jadav,Modi Rishit...[IJET V2I2P30] Authors: AnkurGheewala, Jay Chanawala,Nikhil Jadav,Modi Rishit...
[IJET V2I2P30] Authors: AnkurGheewala, Jay Chanawala,Nikhil Jadav,Modi Rishit...
 
A011140104
A011140104A011140104
A011140104
 

More from Alexander Decker

Abnormalities of hormones and inflammatory cytokines in women affected with p...
Abnormalities of hormones and inflammatory cytokines in women affected with p...Abnormalities of hormones and inflammatory cytokines in women affected with p...
Abnormalities of hormones and inflammatory cytokines in women affected with p...Alexander Decker
 
A validation of the adverse childhood experiences scale in
A validation of the adverse childhood experiences scale inA validation of the adverse childhood experiences scale in
A validation of the adverse childhood experiences scale inAlexander Decker
 
A usability evaluation framework for b2 c e commerce websites
A usability evaluation framework for b2 c e commerce websitesA usability evaluation framework for b2 c e commerce websites
A usability evaluation framework for b2 c e commerce websitesAlexander Decker
 
A universal model for managing the marketing executives in nigerian banks
A universal model for managing the marketing executives in nigerian banksA universal model for managing the marketing executives in nigerian banks
A universal model for managing the marketing executives in nigerian banksAlexander Decker
 
A unique common fixed point theorems in generalized d
A unique common fixed point theorems in generalized dA unique common fixed point theorems in generalized d
A unique common fixed point theorems in generalized dAlexander Decker
 
A trends of salmonella and antibiotic resistance
A trends of salmonella and antibiotic resistanceA trends of salmonella and antibiotic resistance
A trends of salmonella and antibiotic resistanceAlexander Decker
 
A transformational generative approach towards understanding al-istifham
A transformational  generative approach towards understanding al-istifhamA transformational  generative approach towards understanding al-istifham
A transformational generative approach towards understanding al-istifhamAlexander Decker
 
A time series analysis of the determinants of savings in namibia
A time series analysis of the determinants of savings in namibiaA time series analysis of the determinants of savings in namibia
A time series analysis of the determinants of savings in namibiaAlexander Decker
 
A therapy for physical and mental fitness of school children
A therapy for physical and mental fitness of school childrenA therapy for physical and mental fitness of school children
A therapy for physical and mental fitness of school childrenAlexander Decker
 
A theory of efficiency for managing the marketing executives in nigerian banks
A theory of efficiency for managing the marketing executives in nigerian banksA theory of efficiency for managing the marketing executives in nigerian banks
A theory of efficiency for managing the marketing executives in nigerian banksAlexander Decker
 
A systematic evaluation of link budget for
A systematic evaluation of link budget forA systematic evaluation of link budget for
A systematic evaluation of link budget forAlexander Decker
 
A synthetic review of contraceptive supplies in punjab
A synthetic review of contraceptive supplies in punjabA synthetic review of contraceptive supplies in punjab
A synthetic review of contraceptive supplies in punjabAlexander Decker
 
A synthesis of taylor’s and fayol’s management approaches for managing market...
A synthesis of taylor’s and fayol’s management approaches for managing market...A synthesis of taylor’s and fayol’s management approaches for managing market...
A synthesis of taylor’s and fayol’s management approaches for managing market...Alexander Decker
 
A survey paper on sequence pattern mining with incremental
A survey paper on sequence pattern mining with incrementalA survey paper on sequence pattern mining with incremental
A survey paper on sequence pattern mining with incrementalAlexander Decker
 
A survey on live virtual machine migrations and its techniques
A survey on live virtual machine migrations and its techniquesA survey on live virtual machine migrations and its techniques
A survey on live virtual machine migrations and its techniquesAlexander Decker
 
A survey on data mining and analysis in hadoop and mongo db
A survey on data mining and analysis in hadoop and mongo dbA survey on data mining and analysis in hadoop and mongo db
A survey on data mining and analysis in hadoop and mongo dbAlexander Decker
 
A survey on challenges to the media cloud
A survey on challenges to the media cloudA survey on challenges to the media cloud
A survey on challenges to the media cloudAlexander Decker
 
A survey of provenance leveraged
A survey of provenance leveragedA survey of provenance leveraged
A survey of provenance leveragedAlexander Decker
 
A survey of private equity investments in kenya
A survey of private equity investments in kenyaA survey of private equity investments in kenya
A survey of private equity investments in kenyaAlexander Decker
 
A study to measures the financial health of
A study to measures the financial health ofA study to measures the financial health of
A study to measures the financial health ofAlexander Decker
 

More from Alexander Decker (20)

Abnormalities of hormones and inflammatory cytokines in women affected with p...
Abnormalities of hormones and inflammatory cytokines in women affected with p...Abnormalities of hormones and inflammatory cytokines in women affected with p...
Abnormalities of hormones and inflammatory cytokines in women affected with p...
 
A validation of the adverse childhood experiences scale in
A validation of the adverse childhood experiences scale inA validation of the adverse childhood experiences scale in
A validation of the adverse childhood experiences scale in
 
A usability evaluation framework for b2 c e commerce websites
A usability evaluation framework for b2 c e commerce websitesA usability evaluation framework for b2 c e commerce websites
A usability evaluation framework for b2 c e commerce websites
 
A universal model for managing the marketing executives in nigerian banks
A universal model for managing the marketing executives in nigerian banksA universal model for managing the marketing executives in nigerian banks
A universal model for managing the marketing executives in nigerian banks
 
A unique common fixed point theorems in generalized d
A unique common fixed point theorems in generalized dA unique common fixed point theorems in generalized d
A unique common fixed point theorems in generalized d
 
A trends of salmonella and antibiotic resistance
A trends of salmonella and antibiotic resistanceA trends of salmonella and antibiotic resistance
A trends of salmonella and antibiotic resistance
 
A transformational generative approach towards understanding al-istifham
A transformational  generative approach towards understanding al-istifhamA transformational  generative approach towards understanding al-istifham
A transformational generative approach towards understanding al-istifham
 
A time series analysis of the determinants of savings in namibia
A time series analysis of the determinants of savings in namibiaA time series analysis of the determinants of savings in namibia
A time series analysis of the determinants of savings in namibia
 
A therapy for physical and mental fitness of school children
A therapy for physical and mental fitness of school childrenA therapy for physical and mental fitness of school children
A therapy for physical and mental fitness of school children
 
A theory of efficiency for managing the marketing executives in nigerian banks
A theory of efficiency for managing the marketing executives in nigerian banksA theory of efficiency for managing the marketing executives in nigerian banks
A theory of efficiency for managing the marketing executives in nigerian banks
 
A systematic evaluation of link budget for
A systematic evaluation of link budget forA systematic evaluation of link budget for
A systematic evaluation of link budget for
 
A synthetic review of contraceptive supplies in punjab
A synthetic review of contraceptive supplies in punjabA synthetic review of contraceptive supplies in punjab
A synthetic review of contraceptive supplies in punjab
 
A synthesis of taylor’s and fayol’s management approaches for managing market...
A synthesis of taylor’s and fayol’s management approaches for managing market...A synthesis of taylor’s and fayol’s management approaches for managing market...
A synthesis of taylor’s and fayol’s management approaches for managing market...
 
A survey paper on sequence pattern mining with incremental
A survey paper on sequence pattern mining with incrementalA survey paper on sequence pattern mining with incremental
A survey paper on sequence pattern mining with incremental
 
A survey on live virtual machine migrations and its techniques
A survey on live virtual machine migrations and its techniquesA survey on live virtual machine migrations and its techniques
A survey on live virtual machine migrations and its techniques
 
A survey on data mining and analysis in hadoop and mongo db
A survey on data mining and analysis in hadoop and mongo dbA survey on data mining and analysis in hadoop and mongo db
A survey on data mining and analysis in hadoop and mongo db
 
A survey on challenges to the media cloud
A survey on challenges to the media cloudA survey on challenges to the media cloud
A survey on challenges to the media cloud
 
A survey of provenance leveraged
A survey of provenance leveragedA survey of provenance leveraged
A survey of provenance leveraged
 
A survey of private equity investments in kenya
A survey of private equity investments in kenyaA survey of private equity investments in kenya
A survey of private equity investments in kenya
 
A study to measures the financial health of
A study to measures the financial health ofA study to measures the financial health of
A study to measures the financial health of
 

Recently uploaded

Sales & Marketing Alignment: How to Synergize for Success
Sales & Marketing Alignment: How to Synergize for SuccessSales & Marketing Alignment: How to Synergize for Success
Sales & Marketing Alignment: How to Synergize for SuccessAggregage
 
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...lizamodels9
 
A DAY IN THE LIFE OF A SALESMAN / WOMAN
A DAY IN THE LIFE OF A  SALESMAN / WOMANA DAY IN THE LIFE OF A  SALESMAN / WOMAN
A DAY IN THE LIFE OF A SALESMAN / WOMANIlamathiKannappan
 
Ensure the security of your HCL environment by applying the Zero Trust princi...
Ensure the security of your HCL environment by applying the Zero Trust princi...Ensure the security of your HCL environment by applying the Zero Trust princi...
Ensure the security of your HCL environment by applying the Zero Trust princi...Roland Driesen
 
Insurers' journeys to build a mastery in the IoT usage
Insurers' journeys to build a mastery in the IoT usageInsurers' journeys to build a mastery in the IoT usage
Insurers' journeys to build a mastery in the IoT usageMatteo Carbone
 
BEST ✨ Call Girls In Indirapuram Ghaziabad ✔️ 9871031762 ✔️ Escorts Service...
BEST ✨ Call Girls In  Indirapuram Ghaziabad  ✔️ 9871031762 ✔️ Escorts Service...BEST ✨ Call Girls In  Indirapuram Ghaziabad  ✔️ 9871031762 ✔️ Escorts Service...
BEST ✨ Call Girls In Indirapuram Ghaziabad ✔️ 9871031762 ✔️ Escorts Service...noida100girls
 
Keppel Ltd. 1Q 2024 Business Update Presentation Slides
Keppel Ltd. 1Q 2024 Business Update  Presentation SlidesKeppel Ltd. 1Q 2024 Business Update  Presentation Slides
Keppel Ltd. 1Q 2024 Business Update Presentation SlidesKeppelCorporation
 
Grateful 7 speech thanking everyone that has helped.pdf
Grateful 7 speech thanking everyone that has helped.pdfGrateful 7 speech thanking everyone that has helped.pdf
Grateful 7 speech thanking everyone that has helped.pdfPaul Menig
 
GD Birla and his contribution in management
GD Birla and his contribution in managementGD Birla and his contribution in management
GD Birla and his contribution in managementchhavia330
 
HONOR Veterans Event Keynote by Michael Hawkins
HONOR Veterans Event Keynote by Michael HawkinsHONOR Veterans Event Keynote by Michael Hawkins
HONOR Veterans Event Keynote by Michael HawkinsMichael W. Hawkins
 
Best Basmati Rice Manufacturers in India
Best Basmati Rice Manufacturers in IndiaBest Basmati Rice Manufacturers in India
Best Basmati Rice Manufacturers in IndiaShree Krishna Exports
 
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service AvailableCall Girls Pune Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service AvailableDipal Arora
 
Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999
Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999
Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999Tina Ji
 
Yaroslav Rozhankivskyy: Три складові і три передумови максимальної продуктивн...
Yaroslav Rozhankivskyy: Три складові і три передумови максимальної продуктивн...Yaroslav Rozhankivskyy: Три складові і три передумови максимальної продуктивн...
Yaroslav Rozhankivskyy: Три складові і три передумови максимальної продуктивн...Lviv Startup Club
 
Call Girls In Panjim North Goa 9971646499 Genuine Service
Call Girls In Panjim North Goa 9971646499 Genuine ServiceCall Girls In Panjim North Goa 9971646499 Genuine Service
Call Girls In Panjim North Goa 9971646499 Genuine Serviceritikaroy0888
 
Monthly Social Media Update April 2024 pptx.pptx
Monthly Social Media Update April 2024 pptx.pptxMonthly Social Media Update April 2024 pptx.pptx
Monthly Social Media Update April 2024 pptx.pptxAndy Lambert
 
Regression analysis: Simple Linear Regression Multiple Linear Regression
Regression analysis:  Simple Linear Regression Multiple Linear RegressionRegression analysis:  Simple Linear Regression Multiple Linear Regression
Regression analysis: Simple Linear Regression Multiple Linear RegressionRavindra Nath Shukla
 
Tech Startup Growth Hacking 101 - Basics on Growth Marketing
Tech Startup Growth Hacking 101  - Basics on Growth MarketingTech Startup Growth Hacking 101  - Basics on Growth Marketing
Tech Startup Growth Hacking 101 - Basics on Growth MarketingShawn Pang
 
Creating Low-Code Loan Applications using the Trisotech Mortgage Feature Set
Creating Low-Code Loan Applications using the Trisotech Mortgage Feature SetCreating Low-Code Loan Applications using the Trisotech Mortgage Feature Set
Creating Low-Code Loan Applications using the Trisotech Mortgage Feature SetDenis Gagné
 

Recently uploaded (20)

Sales & Marketing Alignment: How to Synergize for Success
Sales & Marketing Alignment: How to Synergize for SuccessSales & Marketing Alignment: How to Synergize for Success
Sales & Marketing Alignment: How to Synergize for Success
 
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
 
VVVIP Call Girls In Greater Kailash ➡️ Delhi ➡️ 9999965857 🚀 No Advance 24HRS...
VVVIP Call Girls In Greater Kailash ➡️ Delhi ➡️ 9999965857 🚀 No Advance 24HRS...VVVIP Call Girls In Greater Kailash ➡️ Delhi ➡️ 9999965857 🚀 No Advance 24HRS...
VVVIP Call Girls In Greater Kailash ➡️ Delhi ➡️ 9999965857 🚀 No Advance 24HRS...
 
A DAY IN THE LIFE OF A SALESMAN / WOMAN
A DAY IN THE LIFE OF A  SALESMAN / WOMANA DAY IN THE LIFE OF A  SALESMAN / WOMAN
A DAY IN THE LIFE OF A SALESMAN / WOMAN
 
Ensure the security of your HCL environment by applying the Zero Trust princi...
Ensure the security of your HCL environment by applying the Zero Trust princi...Ensure the security of your HCL environment by applying the Zero Trust princi...
Ensure the security of your HCL environment by applying the Zero Trust princi...
 
Insurers' journeys to build a mastery in the IoT usage
Insurers' journeys to build a mastery in the IoT usageInsurers' journeys to build a mastery in the IoT usage
Insurers' journeys to build a mastery in the IoT usage
 
BEST ✨ Call Girls In Indirapuram Ghaziabad ✔️ 9871031762 ✔️ Escorts Service...
BEST ✨ Call Girls In  Indirapuram Ghaziabad  ✔️ 9871031762 ✔️ Escorts Service...BEST ✨ Call Girls In  Indirapuram Ghaziabad  ✔️ 9871031762 ✔️ Escorts Service...
BEST ✨ Call Girls In Indirapuram Ghaziabad ✔️ 9871031762 ✔️ Escorts Service...
 
Keppel Ltd. 1Q 2024 Business Update Presentation Slides
Keppel Ltd. 1Q 2024 Business Update  Presentation SlidesKeppel Ltd. 1Q 2024 Business Update  Presentation Slides
Keppel Ltd. 1Q 2024 Business Update Presentation Slides
 
Grateful 7 speech thanking everyone that has helped.pdf
Grateful 7 speech thanking everyone that has helped.pdfGrateful 7 speech thanking everyone that has helped.pdf
Grateful 7 speech thanking everyone that has helped.pdf
 
GD Birla and his contribution in management
GD Birla and his contribution in managementGD Birla and his contribution in management
GD Birla and his contribution in management
 
HONOR Veterans Event Keynote by Michael Hawkins
HONOR Veterans Event Keynote by Michael HawkinsHONOR Veterans Event Keynote by Michael Hawkins
HONOR Veterans Event Keynote by Michael Hawkins
 
Best Basmati Rice Manufacturers in India
Best Basmati Rice Manufacturers in IndiaBest Basmati Rice Manufacturers in India
Best Basmati Rice Manufacturers in India
 
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service AvailableCall Girls Pune Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service Available
 
Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999
Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999
Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999
 
Yaroslav Rozhankivskyy: Три складові і три передумови максимальної продуктивн...
Yaroslav Rozhankivskyy: Три складові і три передумови максимальної продуктивн...Yaroslav Rozhankivskyy: Три складові і три передумови максимальної продуктивн...
Yaroslav Rozhankivskyy: Три складові і три передумови максимальної продуктивн...
 
Call Girls In Panjim North Goa 9971646499 Genuine Service
Call Girls In Panjim North Goa 9971646499 Genuine ServiceCall Girls In Panjim North Goa 9971646499 Genuine Service
Call Girls In Panjim North Goa 9971646499 Genuine Service
 
Monthly Social Media Update April 2024 pptx.pptx
Monthly Social Media Update April 2024 pptx.pptxMonthly Social Media Update April 2024 pptx.pptx
Monthly Social Media Update April 2024 pptx.pptx
 
Regression analysis: Simple Linear Regression Multiple Linear Regression
Regression analysis:  Simple Linear Regression Multiple Linear RegressionRegression analysis:  Simple Linear Regression Multiple Linear Regression
Regression analysis: Simple Linear Regression Multiple Linear Regression
 
Tech Startup Growth Hacking 101 - Basics on Growth Marketing
Tech Startup Growth Hacking 101  - Basics on Growth MarketingTech Startup Growth Hacking 101  - Basics on Growth Marketing
Tech Startup Growth Hacking 101 - Basics on Growth Marketing
 
Creating Low-Code Loan Applications using the Trisotech Mortgage Feature Set
Creating Low-Code Loan Applications using the Trisotech Mortgage Feature SetCreating Low-Code Loan Applications using the Trisotech Mortgage Feature Set
Creating Low-Code Loan Applications using the Trisotech Mortgage Feature Set
 

Shunt active power filters based on diode clamped multilevel inverter and hysteresis band current controller

  • 1. Innovative Systems Design and Engineering ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol.4, No.14, 2013 www.iiste.org Shunt Active Power Filters Based On Diode Clamped Multilevel Inverter and Hysteresis Band Current Controller PROF. DR. EMİN TACER, Akram Qashou and Nezihe yildiran Bahçeşehir University Email: akram11_qashou@hotmail.com Abstract This work focused to design and implementing the three phase shunt Active Power Filter (SAPF) based in instantaneous reactive power theory which we used to generate the reference current and measure the power and reactive power and power factor and using Hysteresis Band Current Controller to obtain the gating signals for 11-steps diode clamped multilevel inverter (DCMLI). The proposed system represent two inverter Shunt Active filters is less total harmonic distortion (THD) and reduced semiconductor ratings compared with conventional inverter. The current drawn by the non- linear load and improve the source side power factor by compensate the reactive power. Also, the shunt Active Power Filter (SAPF) system response has been tested under steady state and transient conditions for real time current compensation harmonics. A study of its performance through simulation results will be investigated through MATLAB Simulink. Keywords: Shunt Active power filter (SHAPF), diode clamped Multilevel Inverter (DCMLI), Hysteresis band controller. 1.1 Introduction Most researchers studied shunt active power filters (APF) based on conventional two-level inverters with conventional controllers requiring a complex and a complicated mathematical model. In order to overcome this problem a hysteresis band controller based diode clamped multilevel inverter is used and extended to an 11- Step two inverters shunt active power filter. 1.2 Objectives (a)-Two inverter Shunt active power filter will be used in this thesis to decrease harmonics in current wave and compensate reactive power of non-linear loads. A control system based on hysteresis band controller with Shunt Active Power Filter (SAPF) is proposed to study the system results and performance. (b)-Three phase 11- Step Diode Clamped Multi-Level Inverter (DCMLI) proposed as a voltage source inverter instead of other inverters because specification of this type of lowest Total Harmonic Distortion (THD) and 11Step according to the cost condition. [Harmonics current generation will be used by Diode Clamped Multi-Level Inverter (DCMLI) with the same magnitude of the source current harmonic but in opposite phase]. The DCMLI output will be connected at the point of common coupling of the system in order to avoid or cancel the current source harmonics. (c)-Instantaneous reactive power theory based on proposed system, it will be employed to obtained the reference current of the DCMLI, the theory based on instantaneous values in three-phase power systems with or without neutral wire, and is valid for steady-state or transitory operations, in this theory instantaneous active current ( ip) and instantaneous reactive current (iq) of three phase system are calculated based on Clark transformation which applied to the voltage and current vectors. (d)-Hysteresis band controller will be used to optimize the switching pattern of diode clump inverter to compensate harmonic and reactive load currents. (e)-Analyze the obtained results and compare it with other published results. 1.3 Problem Statement The operation of non-linear loads in power system and applications almost creates harmonics currents and harmonics voltages especially in industrial systems. Therefore, the harmonic current and voltage exist at the same frequency where inductive and capacitive of industrial power system are equal, this situation reflected to the harmonic current and voltages and raise it and become much greater. 1
  • 2. Innovative Systems Design and Engineering ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol.4, No.14, 2013 www.iiste.org 1.4 Literature Review The power quality problem was as old as electrical system, but the interest in these problems starts from thirty years only. However, the use of active power filters has started only in the last twenty years. There are some of researches in this field in the last two decades are summarized as follows: A distributed active filter system (DAFS) was discussed by (Po-Tai Cheng and Zhung-Lin Lee.2004), to alleviate power systems harmonic distribution. Multiple active filter units of the DAFS are proposed to install on the same location or different locations within the power system. In order to reduce the power lines voltage harmonic distortion, the active filter units of the proposed DAFS cooperate without any communication among them. They reduce voltage harmonics by work like a harmonic conductance. A controller of each unit is programmed by droop relationship between the volt-ampere of the active filter unit and the harmonic conductance so multiple active filter units can share the workload of harmonic filtering. The volt-ampere rating of the active filter unit decides the slope of the relation in order to evenly distribute the workload according to the each unit rated capacity. The distributed deployment of active filter units also shows that they can effectively improve the power lines voltage THDs more than installing active filter in the radial system terminals. The converter absorbed a current rich in harmonics. This would disrupt the network and the consumers joined at the same node will influences. Several techniques used including active filtering and/or passive, to minimize the harmonics of side network. (M. T. Benchouia, M.E.H. Benbouzid, A.Golea, S.E.Zouzou, 2007), have discussed these techniques. Adaptive controller Referenced by The Fuzzy Model is used to minimize the converter harmonics of the side network, including the DC-link voltage and power factor control. The result shows the line current wave is approximately sinusoidal. They found that, the system has adequate dynamic response to load variation according to the rapid change of the line current results. Also they found that any external disturbance has not affected the reactive power. Also the study ends with the result that the increasing or decreasing of step load torque determines the sign of the Input real power peaks. Harmonic current-source load generates the harmonics and by using both of the shunt passive filter and shunt active filter this harmonics can be compensated. Passive filter is not recommended to use because the system impedance strongly determined the performance of passive filter and it may cause resonance problem, and so, the active filter is more attractive. If the harmonic of the voltage source load compensated by using shunt passive filters or shunt active filters, an over current problems may occurs due to the amplification of the load current. The active filter capacity may be the same or larger than that of the load. Hence, it is neither practical nor economical to use shunt active filter to compensate harmonic voltage source. The power factor improvement is the determinant of the capacity of passive filter; it may be overloaded in the harmonic voltage source application. When applying active filter with harmonic voltage source load, a series reactor must be placed on the load side. Another research discuss the design and simulation of Harmonic and power factor compensation of multiple non-linear loads of a single phase shunt active power filter by (Z.F. Hussien, N. Atan, I.Z Abidin,2003). Whereas the active filter is based on a full bridge single phase inverter. The system was modeled in Mat lab Simulink to consist of an AC controller as nonlinear loads connected to active filter to enhance the harmonic of the current injected by the load, and an uncontrolled rectifier. The differences between the proposed model and other models are as follows: - Topology is a Shunt Active Power Filter, current source for Ibrahim.A. Altawil, (2011), while it is a comparison between two techniques to reduce THD multilevel voltage source inverter using cascaded inverters with separated DC sources for Siriroj Sirisukprasert , (1999), and it is a shunt hybrid active power filter system, for current source inverter based induction furnace(CSI-IF) for Adnan Tan, (2011), but it is a Two inverter Shunt Active Power Filter Current source for the proposed model - Load is a nonlinear load with inductive load for Ibrahim.A. Altawil, (2011), while it is in each phase, a resistor and inductor are connected in series for Siriroj Sirisukprasert , (1999), and it is a Nonlinear (CSI-IF) for Adnan Tan, (2011), but it is a nonlinear load (rectifier load bridge, inductive and DC motor) for the proposed model. - Simulation model is a three phase nine steps diode clamped multi level inverter Ibrahim.A. Altawil, (2011), while it is three phase seven steps Multilevel voltage source inverter using cascaded inverters with separated DC sources using triangular-carrier method for Siriroj Sirisukprasert, (1999), and it is a Three phase three Step bridge inverter for Adnan Tan, (2011), but it is a three phase 11- Step diode clamped multi-level inverter for the proposed model. - Results are (THD=2.8%), (PF=0.95), (P=20kW), (Q=6kVAR) for Ibrahim.A. Altawil, (2011), while it is a line voltage THD = 12.3% (P=1.8KW), (PF= 0.92), (Q=2.5 KVRA) for Siriroj Sirisukprasert, (1999), and they are (THD=1.8- 3.2%), (PF=31. 5), (P=0.95), (Q=4kVAR) Adnan Tan, (2011), but they are (THD=1.8%), (PF=0.99), (P=10MW), (Q=0.3MVAR) for the proposed model. 2
  • 3. Innovative Systems Design and Engineering ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol.4, No.14, 2013 www.iiste.org 1.5 Power circuit topology Many non-linear loads are the cause of non-sinusoidal current drawn from electrical power supply. This current will produce voltage harmonics when passing through different kind of power system impedances. The connected sensitive equipment which attached to the same power system will affected by these harmonics, (Hussien, Atan, Abidin,2003). To reduce these harmonics, regularly, passive filters (LC filters) used, but other unnecessary effects may occur it may result in parallel resonances with the network impedance. Active power filters is proposed to use instead of the passive filter due to the harmful of resonance. Improve the power quality without the disadvanteges of passive filters is the main objective to use shunt active power filters. The Power Circuit Topology will be explained by the headings below. 1234- Two Inverter Shunt Active Filters (SAFS). Hysteresis PWM current controller. Generation of Reference current using p-q theories Diode-clamped multilevel inverter 1.5.1 Two Inverter Shunt Active Filters (SAFS) SAFs are attached to the distribution line shunt, and they compensate the harmonics by injecting compensating currents. The injected currents magnitude is equals to the disturbances in the system magnitude but opposite in phase. This eliminates the harmonics in the transmission system to restore the waveforms of source voltage and source current sinusoidal again. Depending upon the objective of the SAF, harmonic compensation yields real power oscillations elimination; power factor correction or reduction of current harmonics from the distribution system. Constant real power compensation can be provided by SAPF by compensating the oscillating active power (P) and reactive power (Q) of the load. Figure 5.1: Two parallel inverters Shunt Active Filters 1.5.2 Hysteresis PWM current controller The current controller of the hysteresis band for shunt active power filter can be approved for inverter switching pattern generation. The proposed current control methods has an assortment for the configurations of such active power filter, but in terms of immediate current controllability and straight forward the control method of hysteresis current has the biggest rate of implementation than other current control methods. Hysteresis band current controller has properties like sturdiness, fastest control, and tremendous dynamics with minimum hardware. (L. Hongda and K. Cao) The conventional hysteresis band current control scheme used for the control of active power filter line current is shown in figure three, composed of active a hysteresis around the reference line current (I*L) and actual line 3
  • 4. Innovative Systems Design and Engineering ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol.4, No.14, 2013 www.iiste.org current of the active power filter is referred to as (IL). The hysteresis band current controller decides the switching pattern of active power filter. The switching logic is formulated as follows: (S. Buso, S. Fasolo, L. Malesani, P. Mattavelli, July 2000). If IL < (I*L- HB) upper switch of the leg is OFF and lower switch of the leg is ON. If IL > (I*L + HB) upper switch of the leg is ON and lower switch of the leg is OFF. Figure 5.2: Conventional Hysteresis Band Current Controller Figure 5.3: Simulation of Hysteresis Band Current Controller 1.5.3 Generation of Reference current using p-q theories The three phase instantaneous reactive current (Iq) and instantaneous active current (Ip) are calculated by this theory based on instantaneous reactive power theory. The current and voltage vector is calculated according to the Clark transformation. The following equations illustrates the method to obtain the instantaneous values of currents and voltages in the (α, β) coordinates. (FERRACCI, 2001). (5.1) Where: 4
  • 5. Innovative Systems Design and Engineering ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol.4, No.14, 2013 www.iiste.org A: transformation matrix and obtained of (FERRACCI, 2001) .And given as: (5.2) The transformation can be used in case of that the voltages are balanced and sinusoidal, as a summary + + =0 (5.3) The instantaneous reactive and active power in the coordinates of α, β is given according to the coming formula: (FERRACCI, 2001) (5.4) (5.5) According to the α–β plane, the equation of the currents as a function of the instantaneous power is addressed in the following expression: This yields that: (5.8) (5.9) (5.10) Equations (5.4) and (5.5), expressed in terms of the AC components in addition to the DC components the values of p and q, which is: Where: the instantaneous power (p) DC component, and belongs to the conventional fundamental active current. : Is the instantaneous power (p) AC component and belongs to the harmonic currents caused by the instantaneous real power AC component. : Is the imaginary instantaneous power (q) DC component, and belongs to the reactive power generated by the voltages and currents fundamental components. : Is the instantaneous imaginary power (q) AC component, and belongs to the harmonic currents caused by the instantaneous reactive power ac component. The active power filter reference signal must have the values of , and for compensation of the reactive power (displacement power factor) and non-linear loads current harmonics. The following equations calculate the reference currents needed by the active power filters: (5.13) 5
  • 6. Innovative Systems Design and Engineering ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol.4, No.14, 2013 www.iiste.org The following matrix equation 5.14 presents the final compensating currents gathered with a, b, c reference frames zero sequence components: (5.14) Where the zero sequence current components = ( + + ). Start Input phase voltages Input load currents Voltages and Currents calculations (Vα Vβ V0) and (Iα Iβ I0) P, q Transformation theory units Input Vref and VDC Calculation PI Controller Correction Calculation Currents after filtering (Icα’, Icβ’) Phase Currents outputs Figure 5.4: Generation of Reference current using p-q theories End This block diagram (fig 5.4): chooses the instantaneous reactive power theory which we used to generate the reference current and measure the power and reactive power and power factor. First of all we transfer the phase voltage and load current from (a, b, c) reference frame to (0, α, β) reference frame, then we find the power and reactive power and power factor. 1.5.4 Diode-clamped multilevel inverter The shunt active power filter is operated as a controlled current source connected in parallel with the non-linear loads driven by PWM to inject current harmonics into the ac source. 11-steps diode clamped inverter is used in this work to generate compensation current (Z. F. Hussien. N. Atan, I. Z. Abidin, 2003) (F. Z. Peng, J-S Lai, 6
  • 7. Innovative Systems Design and Engineering ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol.4, No.14, 2013 www.iiste.org 1996).A diode clamped multilevel inverter (M-level) inverter typically consists of (M-1) capacitors on the dc bus and produces M-levels on the phase voltage. Also it contains 2*(M-1) switching devices and (M- 1)*(M-2) clamping diodes. The dc voltage applied to the capacitors terminals, C1, C2, C3, C4 and C5 and each capacitor has a voltage Vdc/5 and each devices voltage stress is limited to one capacitor voltage level through clamping diode. The numbering order of the switches is S1, S2, S3, S4, S5, S1*, S2*, S3*, S4* and S5*. Figure 5.5: Structure of three-phase, 11-Step of a diode-clamped inverter 1.6 Simulation and Results 1.6.1 OVERALL CIRCUIT DIAGRAM (SIMULATION MODEL): Fig 6.1 The overall diagram of the simulation circuit contains in the table 6.1 Table 6.1: system parameters Parameter Source Voltage Source frequency f Voltage phase angle Source resistance Source Inductance Load inductance Load Resistance Armature Dc Motor Load inductance Armature Dc Motor Load Resistance Field Dc Motor Load inductance Field Dc Motor Load Resistance Field of Dc Motor Value 11KVp-p 50 Hz 0.1 Ω 10 mH 1.5 mH 20 Ω 3H 2Ω 13 H 84Ω 400 V 7
  • 8. Innovative Systems Design and Engineering ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol.4, No.14, 2013 www.iiste.org Fig 6.1: Overall circuit diagram. This figure is show overall system which mainly consists of: 1. 2. 3. 4. 5. 6. AC voltage source. Nonlinear load. Two inverter Shunt active power filters (SAPF). Instantaneous reactive power model (IRPT). Gate signal (hysteresis band current control). Discrete time. Instantaneous reactive power theory is used in simulation to generate the reference of main system elements of current, power, reactive power and power factor which it is used in the current control of hysteresis band. The current control signals compared with actual current to produce the gating signal, figure 6.2 represent the instantaneous reactive power simulation. 8
  • 9. Innovative Systems Design and Engineering ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol.4, No.14, 2013 www.iiste.org Fig 6.2: Inside instantaneous reactive power simulation. Fast Fourier Transform (FFT) is suitable algorithms to discrete time sinusoidal signals founded in modern software such as Mat lab. FFT algorithm required in discrete Fourier transforms (DFT) computation as well as FFT inverse. FFT algorithms have varied type’s mentions as involving, number theory, group theory and also the arithmetic of simple complex-number. In MATLAB/Simulink, FFT algorithms used to explore the compensated source current. This tool is very simple and easy to use. The main reason of used FFT is to order of harmonics by analyses the source current in the system. Otherwise, FFT gives the proportion of harmonics magnitude with respect to fundamental magnitude. Many features can found in this tool it can compute the signal and make many operations such as Total Harmonic Distortion (THD). Figure 6.3 (c), 6.4 (b) and 6.5 (b) represents the current source fast Fourier transform (FFT) analysis without SHAPF (THD = 20.18%) which is connected with one inverter SHAPF (THD = 4.35%). also with connected two inverters SHAPF (THD = 2.05%) which shows further decries in THD when using two inverter SHAPF for medium distribution system 11Kv is less than 5% the harmonic limit imposed by IEEE-519 standard. By using the initial elements and parameter represented on figure 6.1, and the diode rectifier of three phase with impedance R =20 Ω, L= 1.5 mH as a load, the system simulated from t=0 s to t=0.4s. To be illustrated to only balance three phase load is considered, the three phase load current is very high distorted. Otherwise, figure 6.3 (a) represents the pre-compensation current source. Power Factor Before Filtering 1 0.8 pf 0.6 0.4 0.2 0 0 0.05 0.1 0.15 0.2 0.25 0.3 Time(S) Fig 6.3 (a): unfaltering Load current. Fig 6.3 (b): (APF) unless power factor (PF=0.77%). 9
  • 10. Innovative Systems Design and Engineering ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol.4, No.14, 2013 www.iiste.org Figure 6.3 (a) shows the highly distorted load current in the simulation. Fundamental (50Hz) , THD= 20.18% 18 Mag (% of Fundamental) 16 14 12 10 8 6 4 2 0 0 5 10 15 20 25 Harmonic order Fig 6.3 (c): (FFT) unless APF for source current. (THD =20.18%). Figure 6.3 (c) deepened on choose of the harmonic in the source current unless active power filters. The figure represents a high destroyed as we see. Furthermore, the total harmonic distortion is very high (20.18%) and the most appearance harmonic is in the fifth. Typically, by studying the steady state conditions, a small comparison must represented on thesis about the waveforms before and after load also between source currents with two and one inverters APF and study the effects on the harmonics In the transient state conditions, it was observed that when the load current before and after filtering is increased and becomes more sinusoidal from 0.1 to 0.2, resulting that the harmonics is decreased. But the harmonics are not the same in Steady state and Transient state. 6.3 CASE1: STEADY STATE CONDITION Two parallel inverters Shunt Active Power Filter (SHAPF) model is considered to a study state condition. Study state test is made to evaluate the response of the two parallel SHAPF inverters. on this thesis focused to design a simulation to study the behavior of distribution power system with one inverter shunt active power filter (SHAPF), and with two parallel inverter together without shunt active power filter (SHAPF) to ensure that the SHAPF is able to compensate the current harmonic which produced by non-linear load and compare the best way to choose solution. Figure 6.4 (a) represents the post-compensation current source with single inverter for particular phase A. This shows the current have a sinusoidal form. Otherwise, and the Total Harmonic Distortion (THD) by using one SHAPF inverter is illustrated in Figure 6.4(b) Fundamental (50Hz) , THD= 4.35% 100 90 80 Mag (% of Fundamental) 70 60 50 40 30 20 10 0 0 5 10 15 20 Harmonic order Fig 6.4 (a): Source current with filtering Fig 6.4 (b): (FFT) for source current with single and single inverter. inverter (THD =4.35%). 10 25
  • 11. Innovative Systems Design and Engineering ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol.4, No.14, 2013 www.iiste.org Figure 8.10 deepened on the parameters of the harmonic from the source current after using single inverter active power filter which is become small. The total harmonic distortion around (4.35%) which is a small and the most appearance harmonic is around fifth. The particular phase current source after compensation with two inverters Shunt Active Power Filter (SHAPF) presented in Figure 8.11a to indicate that the current become more sinusoidal. Figure8.11b represents the three phase’s current and the THD by using two inverters Shunt Active Power Filter (SHAPF) is shown in figure 8.11.c. The results shows that when using two inverters is much better Fundamental (50Hz) , THD= 2.06% 100 90 80 Mag (% of Fundamental) 70 60 50 40 30 20 10 0 0 5 10 15 20 Harmonic order Fig 6.5 (a): Source current with filtering and Fig 6.5 (b): FFT for source current and two inverter two inverters. (THD =2.05 %). Figure 6.5 (b) consider to choose the harmonic of the source current after using two inverter active power filter which is become very small and the total harmonic distortion around (2.05%) and the most appearance harmonic is the are the fifth. Figure 6.7 (a) represents that that the power factor correction was achieved. power factor after filtering 1 0.8 Pf 0.6 0.4 0.2 0 0 0.05 0.1 0.15 0.2 0.25 0.3 Time(S) Fig 6.7 (a): Total PF with APF. Each figures 6.7 (b) and 6.7 (c) represents the steady state conations with and without APF, the active and reactive power at the diode rectifier load. 11 25
  • 12. Innovative Systems Design and Engineering ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol.4, No.14, 2013 www.iiste.org Fig 6.7 (b): Active power of the load. Fig 6.7 (c): Reactive power of the load. Fundamental (50Hz) , THD= 20.18% 18 Mag (% of Fundamental) 16 14 12 10 8 6 4 2 0 0 5 10 15 20 25 Harmonic order Fig 6.8 (a): Source current (FFT) unless APF with THD =20.18%. Fundamental (50Hz) , THD= 4.35% 100 90 80 Mag (% of Fundamental) 70 60 50 40 30 20 10 0 0 5 10 15 20 Harmonic order Fig 6.8 (b): (FFT) for source current cabled with single inverter (THD=4.35 %). 12 25
  • 13. Innovative Systems Design and Engineering ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol.4, No.14, 2013 www.iiste.org Fundamental (50Hz) , THD= 2.06% 100 90 80 Mag (% of Fundamental) 70 60 50 40 30 20 10 0 0 5 10 15 20 25 Harmonic order Fig 6.13 (c): (FFT) for source current with two inverter (THD =2.05%). Fig 6.8 (c): (FFT) for source current with two inverter 8.4 CASE 2 TRANSIENT STATE CONDITIONS: (THD =2.05%). In this condition of study, we consider to turn on both systems we can see that the effects on the transient system is grater then the steady state ( harmonics), one inverter SHAPF and two inverters SHAPF model are presented to a transient condition. The transient test is used to evaluate the response and waveforms of the shunt active power filter (SHAPF). This simulation is modeled under environment of MATLAB/ Simulink to ensure that the shunt active power filter (SHAPF) is able to recover from this transient condition without affecting on the stability of the overall system. To declare the idea the DC motor load is added in parallel during period of time and the transient behavior of the system was studied. The motor parameters summarized on table 6.1. The current waveform and the Total Harmonic Distortion (THD) shown in Figure 6.9 (a, b) respectively Fig.6.9 (a): transient condition with load current without filtering. 13
  • 14. Innovative Systems Design and Engineering ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol.4, No.14, 2013 www.iiste.org Fundamental (50Hz) , THD= 14.38% 20 Mag (% of Fundamental) 18 16 14 12 10 8 6 4 2 0 0 5 10 15 20 25 Harmonic order Fig 6.10 (b) : Source current (FFT) unless two inverters (THD =14.38%). Figure 6.10 (a) represents the current source for particular phase after compensation with one inverter SHAPF, we can mention and shows that the current is more sinusoidal and in this area the harmonic is decrease between 0.1 to 0.2, the THD by using two inverter SHAPF is shown in figure 6.10 (b). Fundamental (50Hz) = 2040 , THD= 3.22% 100 90 Mag (% of Fundamental) 80 70 60 50 40 30 20 10 0 0 5 10 15 20 25 Harmonic order Fig 6.10 (a): transient source current filter with APF. Fig 6.10 (b): (FFT) for source current by using single inverter (THD =3.22%). Figure 6.11 (a) represents the current source for a particular phase after compensation with two SHAPF inverters which is depicted, we can see that the current is enhanced to be more sinusoidal and in this area the harmonic is decrease between 0.1 to 0.2, the THD by using two inverters SHAPF is shown in figure 6.11 (b). Fig 6.11 (a): transient source current filter with two inverters. 14
  • 15. Innovative Systems Design and Engineering ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol.4, No.14, 2013 www.iiste.org Fundamental (50Hz) , THD= 1.80% 100 90 Mag (% of Fundamental) 80 70 60 50 40 30 20 10 0 0 5 10 15 20 25 Harmonic order Fig 6.11 (b): (FFT) for source current with two inverters (THD =1.80%). Fig 6.12 (a): Active power of the load. Fig 6.12 (b): Reactive power of the load. 15
  • 16. Innovative Systems Design and Engineering ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol.4, No.14, 2013 www.iiste.org Fig 6.13: Total power factor with (APF). Table 6.2: Summary results. without inverter SHAPF with one inverter SHAPF with two inverter SHAPF 20.18% 14.38% 10 10 10 4.35% 3.22% 2.05% 1.8% THD Steady state THD Transient state 0.77 0.95 0.99 power factor 16 0.85 P(MW) 0.35 0.32 Q(MVAR)
  • 17. Innovative Systems Design and Engineering ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol.4, No.14, 2013 www.iiste.org 1.7 CONCLUSIONS In recent years, most researchers studied a Shunt Active Power Filters (SAPF) based on conventional two-shunt inverter with conventional controllers that requires a complex and a complicated mathematical model. In order to overcome this problem in the literature a Hysteresis band controller based diode clamped multilevel inverter has been implemented and extended. In my thesis deal with implementing and design of three phase two inverters shunt Active Power Filter (APF), in distribution system 11KV to enhance the reactive power and so eliminate harmonics from a typical non-linear load, composed from (uncontrolled bridge rectifier with inductive load and DC motor). In this research, almost a unity power factor and sinusoidal current source is achieved. The current source total harmonic distortion (THD) after compensation by single inverter is 4.35% but by using two inverters it decreases to 2.05% which is agreed and less than the harmonic limit imposed by the IEEE-519 standard (3%), by using two parallel inverters with 11-Step diode clamped multi-level inverter the circuit is simulated by using MATLAB/ Simulink. REFERENCES - R. C. Dugan, M. F. McGranaghan, S. Santosa, and H. W. Beaty, “Electrical Power Systems Quality”, second edition, McGraw-Hill, 2002. C. Sankaran, “Power Quality, the Electric Power Engineering Series”, CRC PRESS, 2002. Philippe FERRACCI, “Power Quality, Cahier technique”, Cahiers Techniques Electric, 2001, – No. 199. Lund quist, Johan, Associated power technologies," Total harmonic distortion and effects in electrical power systems", 2001. Alexander Kusko, Marc Thompson, McGraw Hill P.C. Power Quality in Electrical Systems, 2007. Angelo Baggini. ‘Hand book of power quality’, John Wiley and Sons, Ltd. The Atrium, Southern Gate, Chichester, West Sussex PO19 8SQ, England. Francisco C. De La Rosa, Harmonics and Power Systems, The Electric Power Engineering Series, Taylor & Francis Group, 2006. J. David Irwin, Power electronics handbook, Auburn University, Series editor. Lander, Cyril W. (1993). “Rectifying Circuits". Power electronics (3rd ed. ed.). London: McGraw-Hill. ISBN 9780077077143. Z. F. Hussien. N. Atan, I. Z. Abidin, "Shunt active power filter for harmonic compensation of nonlinear loads", 0-7803-8208-0/03/$17.00©2003 IEEE. R. S. Herrera, P. Salmeron, "Instantaneous Reactive Power Theory: A Reference in Nonlinear Loads Compensation", IEEETRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 56, NO. 6, JUNE 2009. Guichum Huang, "The algorithm of a reference compensation current for Shunt Active Power Filters control”, 978-0-7695-4116-7/10 $26.00 © 2010 IEEE. L. Hongda and K. Cao,"Active power filter simulation based on instaneous reactive power theory and the PWM hysteresis control mode",978-1-4244-8161-3/11/$26.00©2011 IEEE. S. Buso, S. Fasolo, L. Malesani, P. Mattavelli, ''A dead beat adaptive hysteresis current control",IEEE Transactions on industry applications, Vol.36, no.4, pp1174-1180, July 2000. M. Kale, E. Ozdemir, "A novel adaptive hysteresis band current controller for shunt active power filter", 0-7803-7729-X/03/$17.00©2003 IEEE. F. Z. Peng, "Application Issues of active power filters", IEEE Industry applications magazineSeptember/October 1998, 1077-2618/98/$10.00 © 1998 IEEE. A.de. Almeida, L. Moreira, J. Delgado "Power quality problems and new solutions", Department of Electrical and Computer Engineering, University of Coimbra, Pó II, Coimbra (Portugal). lo H. Akagi, Y. Kanazawa, and A. Nabae, “Generalized theory of the instantaneous reactive power in three-phase circuits,” in Proc. IPEC, Tokyo, Japan, 1983, pp. 1375-1386. Modern power electronics and AC drives, Bimal K. Bose, Prentice hall PTR 2000, ISBN 0-13-0167436. 17
  • 18. This academic article was published by The International Institute for Science, Technology and Education (IISTE). The IISTE is a pioneer in the Open Access Publishing service based in the U.S. and Europe. The aim of the institute is Accelerating Global Knowledge Sharing. More information about the publisher can be found in the IISTE’s homepage: http://www.iiste.org CALL FOR JOURNAL PAPERS The IISTE is currently hosting more than 30 peer-reviewed academic journals and collaborating with academic institutions around the world. There’s no deadline for submission. Prospective authors of IISTE journals can find the submission instruction on the following page: http://www.iiste.org/journals/ The IISTE editorial team promises to the review and publish all the qualified submissions in a fast manner. All the journals articles are available online to the readers all over the world without financial, legal, or technical barriers other than those inseparable from gaining access to the internet itself. Printed version of the journals is also available upon request of readers and authors. MORE RESOURCES Book publication information: http://www.iiste.org/book/ Recent conferences: http://www.iiste.org/conference/ IISTE Knowledge Sharing Partners EBSCO, Index Copernicus, Ulrich's Periodicals Directory, JournalTOCS, PKP Open Archives Harvester, Bielefeld Academic Search Engine, Elektronische Zeitschriftenbibliothek EZB, Open J-Gate, OCLC WorldCat, Universe Digtial Library , NewJour, Google Scholar