SlideShare une entreprise Scribd logo
1  sur  39
January, 2017
American Backflow Prevention
Association Presentation:
Backflow Installation and Design
Presented by
Randy Holland
Environmental Quality Consultant
New professional liability risk for engineers
Best Practices: Containment Backflow Preventer Placement
The entire water system design community is struggling with new
professional liability risk involving the location of containment backflow
preventer systems. This is not because of a new design practice, but
because of new information about the old practices.
In the past 2 years important organizations and noted industry leaders have
added new warnings with much stronger language that not only change
recognized best practices, but actually challenge the fitness and safety of
older placement methods altogether.
Best Practices: Containment Backflow Preventer Placement
It seems very clear that we will not get
rid of the problem of placement by
ignoring the containment advocates.
Advanced Metering Infrastructure
(AMI) systems are revealing that more
backflow is occurring at the meter
than was previously believed. Its far
more likely that aggressive
containment rules will increase rather
than decrease.
The risks are finally being revealed.
Best Practices: Containment Backflow Preventer Placement
And with this new risk realization comes a new Interested Party. The insurance
company. Because of this very public commentary from experts, they now have
new weapons for damage recovery.
Water utilities are seeking more containment
backflow protection than ever before.
Consider:
“…. The return of any water to the public
water system after the water has been used
for any purpose on the customer’s premises
or within the customer’s piping system is unacceptable
and opposed by AWWA.…”
- preamble to EPA’s Cross Connection Control Manual
Best Practices: Containment Backflow Preventer Placement
More containment systems are being specified as
RPZ, regardless of hazard threshold, than ever
before.
Consider:
Best Practices: Containment Backflow Preventer Placement
Why?
• Older low hazard-use buildings with lead in every plumbing
joint cannot be considered low-hazard forever.
• As buildings turn over tenants, they are often transitioned from
low to high hazard uses. Management and enforcement of
retrofits is an extraordinary burden
• Bad/ignorant actors changing plumbing systems without
permits or oversight..
Best Practices: Containment Backflow Preventer Placement
Consider:
For containment, AWWA, ASPE, & the legal
community recognize “outside aboveground” as
best practice.
1. Why outside?
2. Why not a vault?
3. Momentum: What is driving the change to
better solutions?
Today We’ll Cover:
Best Practices: Containment Backflow Preventer Placement
1. RPZs are an
indoor flood
hazard
“Before an RPZ is located, consideration should be
given to both how much water will be discharged,
and where it will drain. Consideration must be
given to the drain system to assure the drainage
system can handle the load. If a drain is not
capable of accepting the flow, other choices as to
the location of the valve, such as outside in a
heated enclosure, should be made.”
-2006 ASPE Plumbing
Engineering Design Handbook, vol 2, p 70
Best Practices: Containment Backflow Preventer Placement
Why Outside? Indoor Flood Risk.
Best Practices: Containment Backflow Preventer Placement
Why Outside? Indoor Flood Risk.
Flow Stop
The most important thing a designer must
understand is the worst case scenario. What can
happen. What describes the ‘perfect storm?
We all know that with an RPZ, when water
demand stops the water between the valves
often evacuates into the relief valve. Some
(many) think that that event defines the limit of
what water can ever flow into a drain.
Not so.
Loss of pressure
#2 valve
blocked
Consider a flow-stop situation, one that
might naturally occur at the end of the day.
If you look closely, you can see that a small
pebble has lodged in the #2 check valve.
Now let’s say there’s a fire around the
corner that causes back siphon at this point
in the system.
Because the # 2 check valve is not closing,
all the water that has been delivered to the
building will continue to flow out the relief
valve until the private lines are cleared. If
this is a four story building, that’s a lot of
water!
Best Practices: Containment Backflow Preventer Placement
Why Outside? Indoor Flood Risk.
#1 valve
Failure
Normal
delivery
pressure
Now consider a failure of the #1 check
valve. Under normal operating conditions,
this failure would go unnoticed. After all,
water is being called for by the user
through the opening of taps. The water
flows in undeterred.
But with this imbalance in the system,
changes in demand tend to rock the
remaining valves open and closed
sporadically.
Demand
Best Practices: Containment Backflow Preventer Placement
Why Outside? Indoor Flood Risk.
#1 valve
Failure
Blockage
relief
valve
Demand
Normal
delivery
pressure
This creates the conditions for the “perfect
storm” scenario. The imbalance created by
the # 1 failure makes the relief valve more
prone to opening momentarily, allowing
debris to block the closure of that valve.
Under such conditions, a constant flow of
delivered water will begin to flow directly
out the relief valve. This reduces water
pressure for the user, but delivery will
continue.
Best Practices: Containment Backflow Preventer Placement
Why Outside? Indoor Flood Risk.
No
demand
Normal
delivery
pressure
The real damage begins when the user
stops using water such as at the end of a
work day.
With the relief valve blocked open and the
# 1 valve inoperative, all the water that the
purveyor can provide will flow unabated
out the relief valve wherever it might be,
and continue until the water source is
interrupted.
This is the scenario that must be avoided:
the perfect storm.
Best Practices: Containment Backflow Preventer Placement
Why Outside? Indoor Flood Risk.
This picture was tweeted last summer by a
Nashville backflow tester. He was called to
a multi-story office building on a Sunday to
inspect a “malfunctioning backflow
preventer”. By the time he completed his
service of the assembly, a small pebble was
all he recovered from the 8” RPZ in the
background.
Best Practices: Containment Backflow Preventer Placement
Why Outside? Indoor Flood Risk.
This was the scene
when he arrived.
By the way, the RPZ was
working perfectly
before and after the
call, behaving precisely
as it was designed to.
Best Practices: Containment Backflow Preventer Placement
Why Outside? Indoor Flood Risk.
Best Practices: Containment Backflow Preventer Placement
Why Outside? Indoor Flood Risk.
This flood occurred in a hospital mechanical room causing over $1M in damage.
You are looking at 2 sides of one wall. On the left, we see that the sudden water
flow and volume moved the wall into the next room (right photo), which happened to
be a telephone and low-voltage wiring room.
Best Practices: Containment Backflow Preventer Placement
Why Outside? Indoor Flood Risk.
The insurer sought recovery from all the risk holders including the engineer, architect,
contractor, subcontractor, and even the most recent recorded tester; While the details
of who paid what were not made public, we do know that the property insurer was
made whole by one or more of the listed defendants.
So if an RPZ is designed to dump water,
then drain capacity is the issue. The
chart on the right is from the
manufacturer of the BPA seen in the
previous flood photos. It illustrates the
anticipated flow rate from the relief valve
at various pipe sizes and at various
pressures. Note that the assembly
shown will flow 375 GPM at 85 PSI. A 4”
drain pipe with a 1% fall rate evacuates
clean water at a maximum rate of 93
GPM. If that device is flowing at 375
GPM and your clearing 93, then you are
flooding at a rate of 282 GPM.
Best Practices: Containment Backflow Preventer Placement
Why Outside? Indoor Flood Risk.
This is an article published June
2013 in the Chicago chapter of the
American Society of Plumbing
Engineers written by David DeBord,
a former president of that
organization, and current Education
chair of the national ASPE.
Best Practices: Containment Backflow Preventer Placement
Why Outside? Indoor Flood Risk.
He uses the Manufacturer’s data
and he actually does the math in the
article and offers FLOOD rates or
219 GPM for 2 1/2 and 3”; and flood
rate of 482 GPM for 4” and above.
Backflow Failure
Why Outside? Indoor Flood Risk.
Watch this video
showing a check
valve failure and
the resulting flood
water flow.
Premise Isolation: Best Practices & Standard Details
Charlotte: 32.000 SF
Columbus: 36.000 SF
Suffolk Cty: 33.333 SF
Arlington: 32.000 SF
Average: 33.325 SF
Why Outside? Increase revenue and property value.
Consider the average square footage required
for just a 3-inch indoor in-line backflow
preventer. To the right, four representative
cities are represented. The average required
space is 33.325 SF.
Arlington, TX: 32 SF
Best Practices: Containment Backflow Preventer Placement
The space provided for an indoor BPA is routinely
inadequate as provided by the architect. That’s
because giving up space that would otherwise add
value is being allocated as non-revenue space. Non-
revenue space is the enemy of every development
project.
Assuming a discount rate of 9%, rent value of $30
per foot annually, and a 25 year life, the net
present value of that space to the property owner
is $12, 156.48.
NPV:
Landlord has lost this amount of value by
placing CBPA inside.
CONSIDER:
1. If space is recaptured for rental value, what will my alternative cost be?
2. Will placing the system outside cost more or less than $12,156.48?
3. If it’s less, then how much less? (I don’t like the look of a box outside.)
Why Outside? Increase revenue and property value.
Assuming a discount rate of 9%, rent value of $30 per
foot annually, and a 25 year life, the net present value
of that space to the property owner is $12, 156.48. Annual Rent Value
(based on Class A Office
@ $30/sf)
$999.75
25-year Cash Flows
(based on 2.5% inflation)
$34,149.22
Net Present Value
(based on 9% discount
rate)
$12,156.48
Average: 33.325 SF
Aboveground heated enclosure
for 3” BPA with heat.
Option A:
Use conventional model
e.i., Watts 957 NRS
Safe-T-Cover 300-AL-H
$3,266.00
72 X 38 X 22 = 60K CI
Why Outside? Increase revenue and property value.
Option B:
Use new ”n-type” model
e.i., Watts 957N NRS
Safe-T-Cover 200SN-AL-H
$1,120.00
46 X 38 X 19 = 33K CI
$1,000
$1,120
$1,800
$3,920
plus assembly
$3,266
$1,200
$1,800
$6,266
plus assembly
Irrational Costs, Irrational Risks!
Why Outside? Increase revenue and property value.
Indoor
CBPA
$12,156.48
plus assembly
“How much more value does my building have with the additional rent?”
ANSWER:
Irrational Costs, Irrational Risks!
Year Annual Rent*
1 $999.75
Property Value*
$10,289.09
5 $1,103.54 $11,357.23
10 $1,248.55 $12,849.67
15 $1,412.62 $14,538.22
20 $1,598.25 $16,448.66
25 $1,808.27 $18,610.15
* - Today’s dollars: Assumptions: Annual rent growth of 2.5%; 5% vacancy; 35% operating expenses;
capitalization rate of 6%.
Owner’s Property Value
Why Outside? Increase revenue and property value.
1. Why outside?
2. Why not a vault?
3. Momentum: What is driving the change to
better solutions?
Today We’ll Cover:
Best Practices: Containment Backflow Preventer Placement
Why not a vault? No RPZs in Vaults
Best Practices: Containment Backflow Preventer Placement
41 states have written code
that prohibits the installation
of RPZs below grade. And as
far as I know, where it
remains unwritten, it is
invariably enforced as an
unacceptable practice.
We’ve all seen the extraordinary measures
OSHA imposes to legally access vaults for
maintenance tasks. fresh air exchange
hoses, tents, extra men. The costs are
more and more prohibitive but frankly, the
risk of serious injury is real as well. But
beyond the cost of safety for onsite
workers, liability issues persist.
Why not a vault? Confined Space Hazards
Best Practices: Containment Backflow Preventer Placement
Why not a vault? Liability
Best Practices: Containment Backflow Preventer Placement
When a vault floods like this one, the
mandatory test cocks are submerged, and in
that event, a violation of the International
Plumbing has already occurred. Consider what
would typically make up that that water. Runoff
of lawn chemicals alone make this a clear and
present danger to the water supply. In fact, it
led the USC Foundation of Cross Connection &
Hydraulic Research in 2005 to change their
recommendation of even double check BFP
installation in vaults. “The foundation’s recommendation would be
to install the double check valve above grade.”
- USC-FCCHR “Crosstalk, Summer 2005
Why not a vault? Liability
Best Practices: Containment Backflow Preventer Placement
The foundation added stronger language in
2014.
“When a backflow preventer is installed below
grade, the vault or pit in which an assembly is
installed may fill up with water, The water in the
pit could create a cross-connection between the
water in the pit and the backflow preventer
through the test cocks. This may occur whether
the test cocks are opened or closed….”
- USC-FCCHR “Crosstalk, Summer 2014 .
Why not a vault? Changing Demands
Best Practices: Containment Backflow Preventer Placement
Buildings, through their normal life of changing
tenants over time, change uses with respect to
hazard levels, and hazard levels, or more
precisely, the named high-hazard threshold,
has become a moving target.
Around the corner from our Nashville office, I
snapped this picture. It sits in front of a
warehouse owned by an automotive dealer.
When they bought the property and erected
the building, they put a double-check BFP
down in that vault with the meter.
Why not a vault? Changing Demands
Best Practices: Containment Backflow Preventer Placement
A few years later, the city changed an
ordinance that redefined their particular use to
high-hazard. When they sought a permit to
upgrade the HVAC system, the city forced them
to change to an RPZ. So after constructing this
huge vault, they now leave it almost empty
with an RPZ in an enclosure perched on top of
it. They easily paid 3X the necessary cost
because they began with a “DC-only” solution.
Designers need to contemplate these latter-day
retrofits as they make design decisions.
Why not a vault? Legal Community Support
Best Practices: Containment Backflow Preventer Placement
Before his recent death, Indianapolis attorney Doug
Cregor was the nation’s leading litigator of Cross-
Connection Control cases.
Douglas Cregor, Esq.
“An outdoor, aboveground BFP installation may be the best
way to
1) reduce the owner’s exposure to damage caused by
flooding....and the corresponding water contamination
caused by a cross-connection
He was quoted in Plumbing Standards Magazine initially in
2009. I most recently saw it republished as part of a blog
post on the LinkedIn Group, “MEP Engineers & Managers”:
2) reduce the legal liability of the design engineers, the installers, and the certified testers
whose professional actions, in part, may have otherwise caused the flooding harm.
The water industry has a nationally accepted design criteria in ASSE’s Standard-1060 to
protect these installations. It’s a win-win-win ‘insurance policy’.”
1. Why outside?
2. Why not a vault?
3. Momentum: What is driving the change to
better solutions?
Today We’ll Cover:
Best Practices: Containment Backflow Preventer Placement
Best Practices: Containment Backflow Preventer Placement
This past fall at the Bi-Annual ASPE
National conference, one of the
learning workshops had this title.
The Board President of the Central
Texas ASPE, Chris Phillips, a
plumbing engineer at Jacobs in SAT
contacted me and asked me to
deliver the message.
TradeOrg.LeadershipWhereisthemomentum?
Best Practices: Containment Backflow Preventer Placement
Seattle, WA
Raleigh, NC
Charlotte, VA
Austin, TX
Nashville, TN
Albuquerque, NM
Long Island, NY
Denver, CO
Las Vegas, NV
Lynchburg, VA
Columbus, OH
Chicago. IL
Forth Worth, TX Roswell, GA
Longview, WA
Arlington, TX
Gwinnett City, GA
Chesapeake, VA
Olympia, WA
Kent, WA
Franklin, TN
Whereisthemomentum? MoreRPZs,moreoutdoors.
All these cities have made changes
whereby RPZ use has been
expanded either by lowering or
eliminating the hazard threshold
for use on domestic water lines in
the past 5 years. (These are the
cities we know of….)
Where is the momentum? Smaller solutions.
12’
6’8” 5’2”
5’4”
Best Practices: Containment Backflow Preventer Placement
Consider the required enclosure for the industry standard Watts 709 DCDA on the left. It is housed by our Model 1000-
AL. It’s 12 feet long and stands 6’8” tall. Compare it to the enclosure required for the Wilkins 450DA on the left. It is
housed in our Model 1000TLU880M. It’s 5’4” square and stands just 5’2” tall. These two options offer the same
plumbing solution and make a much smaller visual footprint.
Best Practices: Containment Backflow Preventer Placement
Where is the momentum? Adjustments for aesthetics.
AWWA has long resisted the practice
of placing the BPA near the building
because it increased the risk that
illegal taps might occur between the
meter and the BPA. But Arlington
noted that all their indoor RPZs were
already “living with that risk”. Enabling
the enclosure to reside close to the
building dramatically increases the
opportunity to screen it with
landscaping and thereby improve the
aesthetics of the grounds.
Arlington’sdecisiontoadddetailsbasedon:
1. Too much backflow detected through AMI
2. Isolation from the inspection process.
3. Non-conforming/Illegal changes after C of O
4. Subrogation risks
5. Local engineers’ survey

Contenu connexe

Dernier

Main Memory Management in Operating System
Main Memory Management in Operating SystemMain Memory Management in Operating System
Main Memory Management in Operating SystemRashmi Bhat
 
multiple access in wireless communication
multiple access in wireless communicationmultiple access in wireless communication
multiple access in wireless communicationpanditadesh123
 
National Level Hackathon Participation Certificate.pdf
National Level Hackathon Participation Certificate.pdfNational Level Hackathon Participation Certificate.pdf
National Level Hackathon Participation Certificate.pdfRajuKanojiya4
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...VICTOR MAESTRE RAMIREZ
 
Arduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.pptArduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.pptSAURABHKUMAR892774
 
Energy Awareness training ppt for manufacturing process.pptx
Energy Awareness training ppt for manufacturing process.pptxEnergy Awareness training ppt for manufacturing process.pptx
Energy Awareness training ppt for manufacturing process.pptxsiddharthjain2303
 
Katarzyna Lipka-Sidor - BIM School Course
Katarzyna Lipka-Sidor - BIM School CourseKatarzyna Lipka-Sidor - BIM School Course
Katarzyna Lipka-Sidor - BIM School Coursebim.edu.pl
 
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdfCCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdfAsst.prof M.Gokilavani
 
"Exploring the Essential Functions and Design Considerations of Spillways in ...
"Exploring the Essential Functions and Design Considerations of Spillways in ..."Exploring the Essential Functions and Design Considerations of Spillways in ...
"Exploring the Essential Functions and Design Considerations of Spillways in ...Erbil Polytechnic University
 
US Department of Education FAFSA Week of Action
US Department of Education FAFSA Week of ActionUS Department of Education FAFSA Week of Action
US Department of Education FAFSA Week of ActionMebane Rash
 
Input Output Management in Operating System
Input Output Management in Operating SystemInput Output Management in Operating System
Input Output Management in Operating SystemRashmi Bhat
 
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)Dr SOUNDIRARAJ N
 
Instrumentation, measurement and control of bio process parameters ( Temperat...
Instrumentation, measurement and control of bio process parameters ( Temperat...Instrumentation, measurement and control of bio process parameters ( Temperat...
Instrumentation, measurement and control of bio process parameters ( Temperat...121011101441
 
Autonomous emergency braking system (aeb) ppt.ppt
Autonomous emergency braking system (aeb) ppt.pptAutonomous emergency braking system (aeb) ppt.ppt
Autonomous emergency braking system (aeb) ppt.pptbibisarnayak0
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionDr.Costas Sachpazis
 
Ch10-Global Supply Chain - Cadena de Suministro.pdf
Ch10-Global Supply Chain - Cadena de Suministro.pdfCh10-Global Supply Chain - Cadena de Suministro.pdf
Ch10-Global Supply Chain - Cadena de Suministro.pdfChristianCDAM
 
Engineering Drawing section of solid
Engineering Drawing     section of solidEngineering Drawing     section of solid
Engineering Drawing section of solidnamansinghjarodiya
 
Research Methodology for Engineering pdf
Research Methodology for Engineering pdfResearch Methodology for Engineering pdf
Research Methodology for Engineering pdfCaalaaAbdulkerim
 
Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AIabhishek36461
 
11. Properties of Liquid Fuels in Energy Engineering.pdf
11. Properties of Liquid Fuels in Energy Engineering.pdf11. Properties of Liquid Fuels in Energy Engineering.pdf
11. Properties of Liquid Fuels in Energy Engineering.pdfHafizMudaserAhmad
 

Dernier (20)

Main Memory Management in Operating System
Main Memory Management in Operating SystemMain Memory Management in Operating System
Main Memory Management in Operating System
 
multiple access in wireless communication
multiple access in wireless communicationmultiple access in wireless communication
multiple access in wireless communication
 
National Level Hackathon Participation Certificate.pdf
National Level Hackathon Participation Certificate.pdfNational Level Hackathon Participation Certificate.pdf
National Level Hackathon Participation Certificate.pdf
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...
 
Arduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.pptArduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.ppt
 
Energy Awareness training ppt for manufacturing process.pptx
Energy Awareness training ppt for manufacturing process.pptxEnergy Awareness training ppt for manufacturing process.pptx
Energy Awareness training ppt for manufacturing process.pptx
 
Katarzyna Lipka-Sidor - BIM School Course
Katarzyna Lipka-Sidor - BIM School CourseKatarzyna Lipka-Sidor - BIM School Course
Katarzyna Lipka-Sidor - BIM School Course
 
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdfCCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
 
"Exploring the Essential Functions and Design Considerations of Spillways in ...
"Exploring the Essential Functions and Design Considerations of Spillways in ..."Exploring the Essential Functions and Design Considerations of Spillways in ...
"Exploring the Essential Functions and Design Considerations of Spillways in ...
 
US Department of Education FAFSA Week of Action
US Department of Education FAFSA Week of ActionUS Department of Education FAFSA Week of Action
US Department of Education FAFSA Week of Action
 
Input Output Management in Operating System
Input Output Management in Operating SystemInput Output Management in Operating System
Input Output Management in Operating System
 
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
 
Instrumentation, measurement and control of bio process parameters ( Temperat...
Instrumentation, measurement and control of bio process parameters ( Temperat...Instrumentation, measurement and control of bio process parameters ( Temperat...
Instrumentation, measurement and control of bio process parameters ( Temperat...
 
Autonomous emergency braking system (aeb) ppt.ppt
Autonomous emergency braking system (aeb) ppt.pptAutonomous emergency braking system (aeb) ppt.ppt
Autonomous emergency braking system (aeb) ppt.ppt
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
 
Ch10-Global Supply Chain - Cadena de Suministro.pdf
Ch10-Global Supply Chain - Cadena de Suministro.pdfCh10-Global Supply Chain - Cadena de Suministro.pdf
Ch10-Global Supply Chain - Cadena de Suministro.pdf
 
Engineering Drawing section of solid
Engineering Drawing     section of solidEngineering Drawing     section of solid
Engineering Drawing section of solid
 
Research Methodology for Engineering pdf
Research Methodology for Engineering pdfResearch Methodology for Engineering pdf
Research Methodology for Engineering pdf
 
Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AI
 
11. Properties of Liquid Fuels in Energy Engineering.pdf
11. Properties of Liquid Fuels in Energy Engineering.pdf11. Properties of Liquid Fuels in Energy Engineering.pdf
11. Properties of Liquid Fuels in Energy Engineering.pdf
 

En vedette

How Race, Age and Gender Shape Attitudes Towards Mental Health
How Race, Age and Gender Shape Attitudes Towards Mental HealthHow Race, Age and Gender Shape Attitudes Towards Mental Health
How Race, Age and Gender Shape Attitudes Towards Mental HealthThinkNow
 
AI Trends in Creative Operations 2024 by Artwork Flow.pdf
AI Trends in Creative Operations 2024 by Artwork Flow.pdfAI Trends in Creative Operations 2024 by Artwork Flow.pdf
AI Trends in Creative Operations 2024 by Artwork Flow.pdfmarketingartwork
 
PEPSICO Presentation to CAGNY Conference Feb 2024
PEPSICO Presentation to CAGNY Conference Feb 2024PEPSICO Presentation to CAGNY Conference Feb 2024
PEPSICO Presentation to CAGNY Conference Feb 2024Neil Kimberley
 
Content Methodology: A Best Practices Report (Webinar)
Content Methodology: A Best Practices Report (Webinar)Content Methodology: A Best Practices Report (Webinar)
Content Methodology: A Best Practices Report (Webinar)contently
 
How to Prepare For a Successful Job Search for 2024
How to Prepare For a Successful Job Search for 2024How to Prepare For a Successful Job Search for 2024
How to Prepare For a Successful Job Search for 2024Albert Qian
 
Social Media Marketing Trends 2024 // The Global Indie Insights
Social Media Marketing Trends 2024 // The Global Indie InsightsSocial Media Marketing Trends 2024 // The Global Indie Insights
Social Media Marketing Trends 2024 // The Global Indie InsightsKurio // The Social Media Age(ncy)
 
Trends In Paid Search: Navigating The Digital Landscape In 2024
Trends In Paid Search: Navigating The Digital Landscape In 2024Trends In Paid Search: Navigating The Digital Landscape In 2024
Trends In Paid Search: Navigating The Digital Landscape In 2024Search Engine Journal
 
5 Public speaking tips from TED - Visualized summary
5 Public speaking tips from TED - Visualized summary5 Public speaking tips from TED - Visualized summary
5 Public speaking tips from TED - Visualized summarySpeakerHub
 
ChatGPT and the Future of Work - Clark Boyd
ChatGPT and the Future of Work - Clark Boyd ChatGPT and the Future of Work - Clark Boyd
ChatGPT and the Future of Work - Clark Boyd Clark Boyd
 
Getting into the tech field. what next
Getting into the tech field. what next Getting into the tech field. what next
Getting into the tech field. what next Tessa Mero
 
Google's Just Not That Into You: Understanding Core Updates & Search Intent
Google's Just Not That Into You: Understanding Core Updates & Search IntentGoogle's Just Not That Into You: Understanding Core Updates & Search Intent
Google's Just Not That Into You: Understanding Core Updates & Search IntentLily Ray
 
Time Management & Productivity - Best Practices
Time Management & Productivity -  Best PracticesTime Management & Productivity -  Best Practices
Time Management & Productivity - Best PracticesVit Horky
 
The six step guide to practical project management
The six step guide to practical project managementThe six step guide to practical project management
The six step guide to practical project managementMindGenius
 
Beginners Guide to TikTok for Search - Rachel Pearson - We are Tilt __ Bright...
Beginners Guide to TikTok for Search - Rachel Pearson - We are Tilt __ Bright...Beginners Guide to TikTok for Search - Rachel Pearson - We are Tilt __ Bright...
Beginners Guide to TikTok for Search - Rachel Pearson - We are Tilt __ Bright...RachelPearson36
 
Unlocking the Power of ChatGPT and AI in Testing - A Real-World Look, present...
Unlocking the Power of ChatGPT and AI in Testing - A Real-World Look, present...Unlocking the Power of ChatGPT and AI in Testing - A Real-World Look, present...
Unlocking the Power of ChatGPT and AI in Testing - A Real-World Look, present...Applitools
 
12 Ways to Increase Your Influence at Work
12 Ways to Increase Your Influence at Work12 Ways to Increase Your Influence at Work
12 Ways to Increase Your Influence at WorkGetSmarter
 

En vedette (20)

How Race, Age and Gender Shape Attitudes Towards Mental Health
How Race, Age and Gender Shape Attitudes Towards Mental HealthHow Race, Age and Gender Shape Attitudes Towards Mental Health
How Race, Age and Gender Shape Attitudes Towards Mental Health
 
AI Trends in Creative Operations 2024 by Artwork Flow.pdf
AI Trends in Creative Operations 2024 by Artwork Flow.pdfAI Trends in Creative Operations 2024 by Artwork Flow.pdf
AI Trends in Creative Operations 2024 by Artwork Flow.pdf
 
Skeleton Culture Code
Skeleton Culture CodeSkeleton Culture Code
Skeleton Culture Code
 
PEPSICO Presentation to CAGNY Conference Feb 2024
PEPSICO Presentation to CAGNY Conference Feb 2024PEPSICO Presentation to CAGNY Conference Feb 2024
PEPSICO Presentation to CAGNY Conference Feb 2024
 
Content Methodology: A Best Practices Report (Webinar)
Content Methodology: A Best Practices Report (Webinar)Content Methodology: A Best Practices Report (Webinar)
Content Methodology: A Best Practices Report (Webinar)
 
How to Prepare For a Successful Job Search for 2024
How to Prepare For a Successful Job Search for 2024How to Prepare For a Successful Job Search for 2024
How to Prepare For a Successful Job Search for 2024
 
Social Media Marketing Trends 2024 // The Global Indie Insights
Social Media Marketing Trends 2024 // The Global Indie InsightsSocial Media Marketing Trends 2024 // The Global Indie Insights
Social Media Marketing Trends 2024 // The Global Indie Insights
 
Trends In Paid Search: Navigating The Digital Landscape In 2024
Trends In Paid Search: Navigating The Digital Landscape In 2024Trends In Paid Search: Navigating The Digital Landscape In 2024
Trends In Paid Search: Navigating The Digital Landscape In 2024
 
5 Public speaking tips from TED - Visualized summary
5 Public speaking tips from TED - Visualized summary5 Public speaking tips from TED - Visualized summary
5 Public speaking tips from TED - Visualized summary
 
ChatGPT and the Future of Work - Clark Boyd
ChatGPT and the Future of Work - Clark Boyd ChatGPT and the Future of Work - Clark Boyd
ChatGPT and the Future of Work - Clark Boyd
 
Getting into the tech field. what next
Getting into the tech field. what next Getting into the tech field. what next
Getting into the tech field. what next
 
Google's Just Not That Into You: Understanding Core Updates & Search Intent
Google's Just Not That Into You: Understanding Core Updates & Search IntentGoogle's Just Not That Into You: Understanding Core Updates & Search Intent
Google's Just Not That Into You: Understanding Core Updates & Search Intent
 
How to have difficult conversations
How to have difficult conversations How to have difficult conversations
How to have difficult conversations
 
Introduction to Data Science
Introduction to Data ScienceIntroduction to Data Science
Introduction to Data Science
 
Time Management & Productivity - Best Practices
Time Management & Productivity -  Best PracticesTime Management & Productivity -  Best Practices
Time Management & Productivity - Best Practices
 
The six step guide to practical project management
The six step guide to practical project managementThe six step guide to practical project management
The six step guide to practical project management
 
Beginners Guide to TikTok for Search - Rachel Pearson - We are Tilt __ Bright...
Beginners Guide to TikTok for Search - Rachel Pearson - We are Tilt __ Bright...Beginners Guide to TikTok for Search - Rachel Pearson - We are Tilt __ Bright...
Beginners Guide to TikTok for Search - Rachel Pearson - We are Tilt __ Bright...
 
Unlocking the Power of ChatGPT and AI in Testing - A Real-World Look, present...
Unlocking the Power of ChatGPT and AI in Testing - A Real-World Look, present...Unlocking the Power of ChatGPT and AI in Testing - A Real-World Look, present...
Unlocking the Power of ChatGPT and AI in Testing - A Real-World Look, present...
 
12 Ways to Increase Your Influence at Work
12 Ways to Increase Your Influence at Work12 Ways to Increase Your Influence at Work
12 Ways to Increase Your Influence at Work
 
ChatGPT webinar slides
ChatGPT webinar slidesChatGPT webinar slides
ChatGPT webinar slides
 

Containment Backflow Installation and Design

  • 1. January, 2017 American Backflow Prevention Association Presentation: Backflow Installation and Design Presented by Randy Holland Environmental Quality Consultant
  • 2. New professional liability risk for engineers Best Practices: Containment Backflow Preventer Placement The entire water system design community is struggling with new professional liability risk involving the location of containment backflow preventer systems. This is not because of a new design practice, but because of new information about the old practices. In the past 2 years important organizations and noted industry leaders have added new warnings with much stronger language that not only change recognized best practices, but actually challenge the fitness and safety of older placement methods altogether.
  • 3. Best Practices: Containment Backflow Preventer Placement It seems very clear that we will not get rid of the problem of placement by ignoring the containment advocates. Advanced Metering Infrastructure (AMI) systems are revealing that more backflow is occurring at the meter than was previously believed. Its far more likely that aggressive containment rules will increase rather than decrease. The risks are finally being revealed.
  • 4. Best Practices: Containment Backflow Preventer Placement And with this new risk realization comes a new Interested Party. The insurance company. Because of this very public commentary from experts, they now have new weapons for damage recovery.
  • 5. Water utilities are seeking more containment backflow protection than ever before. Consider: “…. The return of any water to the public water system after the water has been used for any purpose on the customer’s premises or within the customer’s piping system is unacceptable and opposed by AWWA.…” - preamble to EPA’s Cross Connection Control Manual Best Practices: Containment Backflow Preventer Placement
  • 6. More containment systems are being specified as RPZ, regardless of hazard threshold, than ever before. Consider: Best Practices: Containment Backflow Preventer Placement Why? • Older low hazard-use buildings with lead in every plumbing joint cannot be considered low-hazard forever. • As buildings turn over tenants, they are often transitioned from low to high hazard uses. Management and enforcement of retrofits is an extraordinary burden • Bad/ignorant actors changing plumbing systems without permits or oversight..
  • 7. Best Practices: Containment Backflow Preventer Placement Consider: For containment, AWWA, ASPE, & the legal community recognize “outside aboveground” as best practice.
  • 8. 1. Why outside? 2. Why not a vault? 3. Momentum: What is driving the change to better solutions? Today We’ll Cover: Best Practices: Containment Backflow Preventer Placement
  • 9. 1. RPZs are an indoor flood hazard “Before an RPZ is located, consideration should be given to both how much water will be discharged, and where it will drain. Consideration must be given to the drain system to assure the drainage system can handle the load. If a drain is not capable of accepting the flow, other choices as to the location of the valve, such as outside in a heated enclosure, should be made.” -2006 ASPE Plumbing Engineering Design Handbook, vol 2, p 70 Best Practices: Containment Backflow Preventer Placement Why Outside? Indoor Flood Risk.
  • 10. Best Practices: Containment Backflow Preventer Placement Why Outside? Indoor Flood Risk. Flow Stop The most important thing a designer must understand is the worst case scenario. What can happen. What describes the ‘perfect storm? We all know that with an RPZ, when water demand stops the water between the valves often evacuates into the relief valve. Some (many) think that that event defines the limit of what water can ever flow into a drain. Not so.
  • 11. Loss of pressure #2 valve blocked Consider a flow-stop situation, one that might naturally occur at the end of the day. If you look closely, you can see that a small pebble has lodged in the #2 check valve. Now let’s say there’s a fire around the corner that causes back siphon at this point in the system. Because the # 2 check valve is not closing, all the water that has been delivered to the building will continue to flow out the relief valve until the private lines are cleared. If this is a four story building, that’s a lot of water! Best Practices: Containment Backflow Preventer Placement Why Outside? Indoor Flood Risk.
  • 12. #1 valve Failure Normal delivery pressure Now consider a failure of the #1 check valve. Under normal operating conditions, this failure would go unnoticed. After all, water is being called for by the user through the opening of taps. The water flows in undeterred. But with this imbalance in the system, changes in demand tend to rock the remaining valves open and closed sporadically. Demand Best Practices: Containment Backflow Preventer Placement Why Outside? Indoor Flood Risk.
  • 13. #1 valve Failure Blockage relief valve Demand Normal delivery pressure This creates the conditions for the “perfect storm” scenario. The imbalance created by the # 1 failure makes the relief valve more prone to opening momentarily, allowing debris to block the closure of that valve. Under such conditions, a constant flow of delivered water will begin to flow directly out the relief valve. This reduces water pressure for the user, but delivery will continue. Best Practices: Containment Backflow Preventer Placement Why Outside? Indoor Flood Risk.
  • 14. No demand Normal delivery pressure The real damage begins when the user stops using water such as at the end of a work day. With the relief valve blocked open and the # 1 valve inoperative, all the water that the purveyor can provide will flow unabated out the relief valve wherever it might be, and continue until the water source is interrupted. This is the scenario that must be avoided: the perfect storm. Best Practices: Containment Backflow Preventer Placement Why Outside? Indoor Flood Risk.
  • 15. This picture was tweeted last summer by a Nashville backflow tester. He was called to a multi-story office building on a Sunday to inspect a “malfunctioning backflow preventer”. By the time he completed his service of the assembly, a small pebble was all he recovered from the 8” RPZ in the background. Best Practices: Containment Backflow Preventer Placement Why Outside? Indoor Flood Risk.
  • 16. This was the scene when he arrived. By the way, the RPZ was working perfectly before and after the call, behaving precisely as it was designed to. Best Practices: Containment Backflow Preventer Placement Why Outside? Indoor Flood Risk.
  • 17. Best Practices: Containment Backflow Preventer Placement Why Outside? Indoor Flood Risk. This flood occurred in a hospital mechanical room causing over $1M in damage. You are looking at 2 sides of one wall. On the left, we see that the sudden water flow and volume moved the wall into the next room (right photo), which happened to be a telephone and low-voltage wiring room.
  • 18. Best Practices: Containment Backflow Preventer Placement Why Outside? Indoor Flood Risk. The insurer sought recovery from all the risk holders including the engineer, architect, contractor, subcontractor, and even the most recent recorded tester; While the details of who paid what were not made public, we do know that the property insurer was made whole by one or more of the listed defendants.
  • 19. So if an RPZ is designed to dump water, then drain capacity is the issue. The chart on the right is from the manufacturer of the BPA seen in the previous flood photos. It illustrates the anticipated flow rate from the relief valve at various pipe sizes and at various pressures. Note that the assembly shown will flow 375 GPM at 85 PSI. A 4” drain pipe with a 1% fall rate evacuates clean water at a maximum rate of 93 GPM. If that device is flowing at 375 GPM and your clearing 93, then you are flooding at a rate of 282 GPM. Best Practices: Containment Backflow Preventer Placement Why Outside? Indoor Flood Risk.
  • 20. This is an article published June 2013 in the Chicago chapter of the American Society of Plumbing Engineers written by David DeBord, a former president of that organization, and current Education chair of the national ASPE. Best Practices: Containment Backflow Preventer Placement Why Outside? Indoor Flood Risk. He uses the Manufacturer’s data and he actually does the math in the article and offers FLOOD rates or 219 GPM for 2 1/2 and 3”; and flood rate of 482 GPM for 4” and above.
  • 21. Backflow Failure Why Outside? Indoor Flood Risk. Watch this video showing a check valve failure and the resulting flood water flow. Premise Isolation: Best Practices & Standard Details
  • 22. Charlotte: 32.000 SF Columbus: 36.000 SF Suffolk Cty: 33.333 SF Arlington: 32.000 SF Average: 33.325 SF Why Outside? Increase revenue and property value. Consider the average square footage required for just a 3-inch indoor in-line backflow preventer. To the right, four representative cities are represented. The average required space is 33.325 SF. Arlington, TX: 32 SF Best Practices: Containment Backflow Preventer Placement The space provided for an indoor BPA is routinely inadequate as provided by the architect. That’s because giving up space that would otherwise add value is being allocated as non-revenue space. Non- revenue space is the enemy of every development project. Assuming a discount rate of 9%, rent value of $30 per foot annually, and a 25 year life, the net present value of that space to the property owner is $12, 156.48.
  • 23. NPV: Landlord has lost this amount of value by placing CBPA inside. CONSIDER: 1. If space is recaptured for rental value, what will my alternative cost be? 2. Will placing the system outside cost more or less than $12,156.48? 3. If it’s less, then how much less? (I don’t like the look of a box outside.) Why Outside? Increase revenue and property value. Assuming a discount rate of 9%, rent value of $30 per foot annually, and a 25 year life, the net present value of that space to the property owner is $12, 156.48. Annual Rent Value (based on Class A Office @ $30/sf) $999.75 25-year Cash Flows (based on 2.5% inflation) $34,149.22 Net Present Value (based on 9% discount rate) $12,156.48 Average: 33.325 SF
  • 24. Aboveground heated enclosure for 3” BPA with heat. Option A: Use conventional model e.i., Watts 957 NRS Safe-T-Cover 300-AL-H $3,266.00 72 X 38 X 22 = 60K CI Why Outside? Increase revenue and property value. Option B: Use new ”n-type” model e.i., Watts 957N NRS Safe-T-Cover 200SN-AL-H $1,120.00 46 X 38 X 19 = 33K CI
  • 25. $1,000 $1,120 $1,800 $3,920 plus assembly $3,266 $1,200 $1,800 $6,266 plus assembly Irrational Costs, Irrational Risks! Why Outside? Increase revenue and property value. Indoor CBPA $12,156.48 plus assembly
  • 26. “How much more value does my building have with the additional rent?” ANSWER: Irrational Costs, Irrational Risks! Year Annual Rent* 1 $999.75 Property Value* $10,289.09 5 $1,103.54 $11,357.23 10 $1,248.55 $12,849.67 15 $1,412.62 $14,538.22 20 $1,598.25 $16,448.66 25 $1,808.27 $18,610.15 * - Today’s dollars: Assumptions: Annual rent growth of 2.5%; 5% vacancy; 35% operating expenses; capitalization rate of 6%. Owner’s Property Value Why Outside? Increase revenue and property value.
  • 27. 1. Why outside? 2. Why not a vault? 3. Momentum: What is driving the change to better solutions? Today We’ll Cover: Best Practices: Containment Backflow Preventer Placement
  • 28. Why not a vault? No RPZs in Vaults Best Practices: Containment Backflow Preventer Placement 41 states have written code that prohibits the installation of RPZs below grade. And as far as I know, where it remains unwritten, it is invariably enforced as an unacceptable practice.
  • 29. We’ve all seen the extraordinary measures OSHA imposes to legally access vaults for maintenance tasks. fresh air exchange hoses, tents, extra men. The costs are more and more prohibitive but frankly, the risk of serious injury is real as well. But beyond the cost of safety for onsite workers, liability issues persist. Why not a vault? Confined Space Hazards Best Practices: Containment Backflow Preventer Placement
  • 30. Why not a vault? Liability Best Practices: Containment Backflow Preventer Placement When a vault floods like this one, the mandatory test cocks are submerged, and in that event, a violation of the International Plumbing has already occurred. Consider what would typically make up that that water. Runoff of lawn chemicals alone make this a clear and present danger to the water supply. In fact, it led the USC Foundation of Cross Connection & Hydraulic Research in 2005 to change their recommendation of even double check BFP installation in vaults. “The foundation’s recommendation would be to install the double check valve above grade.” - USC-FCCHR “Crosstalk, Summer 2005
  • 31. Why not a vault? Liability Best Practices: Containment Backflow Preventer Placement The foundation added stronger language in 2014. “When a backflow preventer is installed below grade, the vault or pit in which an assembly is installed may fill up with water, The water in the pit could create a cross-connection between the water in the pit and the backflow preventer through the test cocks. This may occur whether the test cocks are opened or closed….” - USC-FCCHR “Crosstalk, Summer 2014 .
  • 32. Why not a vault? Changing Demands Best Practices: Containment Backflow Preventer Placement Buildings, through their normal life of changing tenants over time, change uses with respect to hazard levels, and hazard levels, or more precisely, the named high-hazard threshold, has become a moving target. Around the corner from our Nashville office, I snapped this picture. It sits in front of a warehouse owned by an automotive dealer. When they bought the property and erected the building, they put a double-check BFP down in that vault with the meter.
  • 33. Why not a vault? Changing Demands Best Practices: Containment Backflow Preventer Placement A few years later, the city changed an ordinance that redefined their particular use to high-hazard. When they sought a permit to upgrade the HVAC system, the city forced them to change to an RPZ. So after constructing this huge vault, they now leave it almost empty with an RPZ in an enclosure perched on top of it. They easily paid 3X the necessary cost because they began with a “DC-only” solution. Designers need to contemplate these latter-day retrofits as they make design decisions.
  • 34. Why not a vault? Legal Community Support Best Practices: Containment Backflow Preventer Placement Before his recent death, Indianapolis attorney Doug Cregor was the nation’s leading litigator of Cross- Connection Control cases. Douglas Cregor, Esq. “An outdoor, aboveground BFP installation may be the best way to 1) reduce the owner’s exposure to damage caused by flooding....and the corresponding water contamination caused by a cross-connection He was quoted in Plumbing Standards Magazine initially in 2009. I most recently saw it republished as part of a blog post on the LinkedIn Group, “MEP Engineers & Managers”: 2) reduce the legal liability of the design engineers, the installers, and the certified testers whose professional actions, in part, may have otherwise caused the flooding harm. The water industry has a nationally accepted design criteria in ASSE’s Standard-1060 to protect these installations. It’s a win-win-win ‘insurance policy’.”
  • 35. 1. Why outside? 2. Why not a vault? 3. Momentum: What is driving the change to better solutions? Today We’ll Cover: Best Practices: Containment Backflow Preventer Placement
  • 36. Best Practices: Containment Backflow Preventer Placement This past fall at the Bi-Annual ASPE National conference, one of the learning workshops had this title. The Board President of the Central Texas ASPE, Chris Phillips, a plumbing engineer at Jacobs in SAT contacted me and asked me to deliver the message. TradeOrg.LeadershipWhereisthemomentum?
  • 37. Best Practices: Containment Backflow Preventer Placement Seattle, WA Raleigh, NC Charlotte, VA Austin, TX Nashville, TN Albuquerque, NM Long Island, NY Denver, CO Las Vegas, NV Lynchburg, VA Columbus, OH Chicago. IL Forth Worth, TX Roswell, GA Longview, WA Arlington, TX Gwinnett City, GA Chesapeake, VA Olympia, WA Kent, WA Franklin, TN Whereisthemomentum? MoreRPZs,moreoutdoors. All these cities have made changes whereby RPZ use has been expanded either by lowering or eliminating the hazard threshold for use on domestic water lines in the past 5 years. (These are the cities we know of….)
  • 38. Where is the momentum? Smaller solutions. 12’ 6’8” 5’2” 5’4” Best Practices: Containment Backflow Preventer Placement Consider the required enclosure for the industry standard Watts 709 DCDA on the left. It is housed by our Model 1000- AL. It’s 12 feet long and stands 6’8” tall. Compare it to the enclosure required for the Wilkins 450DA on the left. It is housed in our Model 1000TLU880M. It’s 5’4” square and stands just 5’2” tall. These two options offer the same plumbing solution and make a much smaller visual footprint.
  • 39. Best Practices: Containment Backflow Preventer Placement Where is the momentum? Adjustments for aesthetics. AWWA has long resisted the practice of placing the BPA near the building because it increased the risk that illegal taps might occur between the meter and the BPA. But Arlington noted that all their indoor RPZs were already “living with that risk”. Enabling the enclosure to reside close to the building dramatically increases the opportunity to screen it with landscaping and thereby improve the aesthetics of the grounds. Arlington’sdecisiontoadddetailsbasedon: 1. Too much backflow detected through AMI 2. Isolation from the inspection process. 3. Non-conforming/Illegal changes after C of O 4. Subrogation risks 5. Local engineers’ survey
  • 40. 3. CivilengineersarereadytotakeonthetaskifSDsexist Take-Aways 1. 3”andlargerCBPAsshouldnotbeinstalledindoorsandMEPsare seekingtobeexcludedfromthetask a. Indoor flood risks b. Designing for sudden flood water flows exceeds expertise 4. Water/buildingauthoritiesarefeelingpressuretoaddaboveground standarddetailssothatcivilengineerscandothisworkandimprove thesafetybyadvocatingsaferplacement Best Practices: Containment Backflow Preventer Placement 2. CBPAs should not be installed in subterranean vaults a. Contamination risks b. Probability of subsequent aboveground retrofit
  • 41. Thank You! American Backflow Prevention Association Presentation: Backflow Installation and Design Best Practices: Containment Backflow Preventer Placement

Notes de l'éditeur

  1. The fact is, the entire Eng commty, at least those that engage in the design of water systems, are struggling w/ new professional liability risk involving the location of CNTMT Backflow preventer systems. not because of a new design practice, but because of new information about the old practices. There has been a slow trickle of warnings for years, * past two years: imp orgs and ind’ry leaders have added new warnings, much stronger language: not only change recognized best practices, but actually challenge the fitness and safety of older placement methods altogether.
  2. I told you I wouldn’t attempt to settle the Doctrine Question today. But I will say we are not going to get rid of the problem by dumping the system itself. More backflow is occurring at the meter than was previously believed
  3. And with this new risk realization comes a new Interested Party. The insurance company. Because of this very public commentary from experts, they now have new weapons for damage recovery.
  4. Consider these facts. [READ] Water utilities are seeking more containment backflow protection To answer the “why” question, one must first look to AWWAs statement in the preamble of the CCCM published by EPA: [READ] . The return of any water to the public water system after the water has been used for any purpose on the customer’s premises or within the customer’s piping system is unacceptable and opposed by AWWA *But new technologies like SCADA and AMI are revealing that there are far more BF events happening than we ever imagined. (Supervisory Control and Data Acquisition) back-siphon events that were not detected prior to these technologies; back pressure events sometimes caused by the SCADA systems themselves (pressure regulation, internal distribution pumps, etc. 40-year-old buildings with lead in every plumbing joint are no longer low hazards to the public water supply. The Bootleg Contingency: bad/ignorant actors Terrorism
  5. Consider these facts. [READ] Water utilities are seeking more containment backflow protection To answer the “why” question, one must first look to AWWAs statement in the preamble of the CCCM published by EPA: [READ] . The return of any water to the public water system after the water has been used for any purpose on the customer’s premises or within the customer’s piping system is unacceptable and opposed by AWWA *But new technologies like SCADA and AMI are revealing that there are far more BF events happening than we ever imagined. (Supervisory Control and Data Acquisition) back-siphon events that were not detected prior to these technologies; back pressure events sometimes caused by the SCADA systems themselves (pressure regulation, internal distribution pumps, etc. 40-year-old buildings with lead in every plumbing joint are no longer low hazards to the public water supply. The Bootleg Contingency: bad/ignorant actors Terrorism
  6. Number 3 For containment, AWWA, ASPE, & the legal community recognize “outside aboveground” as ‘best practice’.
  7. Today we’ll take a look at the questions designers and plans-review personnel are asking to determine proper application of containment backflow prevention Why outside? (OR asked another way, Why not inside?) I’ll show you the 2 critically important reasons why these systems are best placed outside. 2. Once that’s laid out, I’ll take you through the 5 reasons more and more water authorities are deciding that subterranean vault installation is too dangerous, too expensive, and too much of a risk burden to be allowed to continue. 3. Where is the momentum (and what does it tell us about the future) for containment BP systems? 4. Survey
  8. The first question is Why Outside? What’s wrong with inside? The number one reason has to do with RPZs because RPZs are an ever-present flood hazard. * Here’s what the American Society of Plumbing Engineers published in their Plumbing Engineering Design Handbook: [READ]
  9. The most important thing a designer must understand is the worst case scenario. What CAN happen. What describes The Perfect STORM? We all know that with an RPZ, when water demand stops, the water between the valves often evacuates into the relief valve. Some (many) think that that event defines the limit of what water can ever flow into a drain. Not so.
  10. Consider a flow-stop situation, one that might naturally occur at the end of the day. If you look closely, you can see that a small pebble has lodged in the #2 check valve. Now let’s say there’s a fire around the corner that causes back siphon at this point in the system. Because the # 2 check valve is not closing, all the water that has been delivered to the building will continue to flow out the relief valve until the private lines are cleared. If this is a four story building, that’s a lot of water.
  11. Failure of # 1. undetected in normal conditions.
  12. Faulire of #1 PLUS Relief valve blockage:
  13. * This picture was tweeted this summer by a Nashville backflow tester. (READ)
  14. Let’s look at a flood of a medical facility. You are looking at 2 sides of one wall. On the left, we see that the water volume from the release moved the wall into the next room, which happened to be a telephone and low-voltage wiring room. The insurer sought recovery from all the risk holders including the engineer, architect, contractor, subcontractor, and even the most recent recorded tester; and while the details of who paid what were not made public, we do know that the property insurer was made whole by one or more of the listed defendants.
  15. Let’s look at a flood of a medical facility. You are looking at 2 sides of one wall. On the left, we see that the water volume from the release moved the wall into the next room, which happened to be a telephone and low-voltage wiring room. The insurer sought recovery from all the risk holders including the engineer, architect, contractor, subcontractor, and even the most recent recorded tester; and while the details of who paid what were not made public, we do know that the property insurer was made whole by one or more of the listed defendants.
  16. So if these things are designed to dump water, then drain capacity is the issue. The chart on the left is from Wilkins. It’s the Relief Valve Discharge Rate chart of its top of the line, 375 RPZ. It illustrates the flow rate of that device in various sizes and at various pressures. Note that a 2 1/2 inch device will flow 375 GPM at 85 PSI. If you remember your fluid volume tables, you’ll recall that a 4” drain pipe with a 6 inch fall per 100 horizontal feet evacuates clean water at a rate of 93 GPM. If that device is flowing at 375 GPM and your clearing 93, then you are flooding at a rate of 282 GPM. The chart on the right is a Drain Requirements chart created by the city of Columbus, OH. It’s importance cannot be overstated. It reveals that unless you intend to utilize 8” drain pipes at a 6” per 100 horizontal feet fall-rate all the way to the sewer, you cannot justify anything larger inside than a 2” RPZ inside. * An article published this summer in the Chicago chapter of the American Society of Plumbing Engineers written by David DeBord, a former president of that organization, states all these facts better than I can. He uses the Manufacturer’s data supplied by the Watts Corporation and he uses a 65 PSI instead of my 85, but he actually does the math in the article and offers FLOOD rates or 219 GPM for 2 1/2 and 3”; and flood rate of 482 GPM for 4” and above. * He concludes that regarding indoor RPZs, : (READ)
  17. So if these things are designed to dump water, then drain capacity is the issue. The chart on the left is from Wilkins. It’s the Relief Valve Discharge Rate chart of its top of the line, 375 RPZ. It illustrates the flow rate of that device in various sizes and at various pressures. Note that a 2 1/2 inch device will flow 375 GPM at 85 PSI. If you remember your fluid volume tables, you’ll recall that a 4” drain pipe with a 6 inch fall per 100 horizontal feet evacuates clean water at a rate of 93 GPM. If that device is flowing at 375 GPM and your clearing 93, then you are flooding at a rate of 282 GPM. The chart on the right is a Drain Requirements chart created by the city of Columbus, OH. It’s importance cannot be overstated. It reveals that unless you intend to utilize 8” drain pipes at a 6” per 100 horizontal feet fall-rate all the way to the sewer, you cannot justify anything larger inside than a 2” RPZ inside. * An article published this summer in the Chicago chapter of the American Society of Plumbing Engineers written by David DeBord, a former president of that organization, states all these facts better than I can. He uses the Manufacturer’s data supplied by the Watts Corporation and he uses a 65 PSI instead of my 85, but he actually does the math in the article and offers FLOOD rates or 219 GPM for 2 1/2 and 3”; and flood rate of 482 GPM for 4” and above. * He concludes that regarding indoor RPZs, : (READ)
  18. Video showing a #1 check valve failure and debris in the relief valve holding it open. See this video now at https://www.youtube.com/watch?v=d7MjJuZQoYo
  19. the average floor area required for a conventional 3” backflow preventer is 33.325 SF.
  20. Cost of an enclosure, 2 options: Option 1: conventional, “in-line” assembly= $3,266 Option 2: N-type assembly=$1,100.
  21. Costs are $3,920 and $6,266 respectively.
  22. Today we’ll take a look at the questions designers and plans-review personnel are asking to determine proper application of containment backflow prevention Why outside? (OR asked another way, Why not inside?) I’ll show you the 2 critically important reasons why these systems are best placed outside. 2. Once that’s laid out, I’ll take you through the 5 reasons more and more water authorities are deciding that subterranean vault installation is too dangerous, too expensive, and too much of a risk burden to be allowed to continue. 3. Where is the momentum (and what does it tell us about the future) for containment BP systems? 4. Survey
  23. Why an aboveground enclosure? Why not a subterranean vault? Well, the first reason has to do with the RPZ. 41 states have written code that prohibits the installation of RPZs below grade. And as far as I know, where it remains unwritten, it is invariably enforced as an unacceptable practice.
  24. So let’s look at the considerations. Safety, Liability, and changing demands * We’ve all seen the extraordinary measures OSHA imposes to legally access vaults for maintenance tasks. fresh air exchange hoses, tents, extra men. The costs are more and more prohibitive but frankly, the risk of serious injury is real as well. * But beyond the cost of safety for onsite workers, liability issues persist. * When a vault floods like this one, the mandatory test cocks are submerged, and in that event, a violation of the International Plumbing has likely already occurred. The water may look clean, but consider what would typically make up the constituents of that water. Runoff of lawn chemicals alone make this a clear and present danger to the water supply. In fact, it led the USC Foundation of Cross Connection & Hydraulic Research in 2005 to change their recommendation of even double check BFP installation in vaults. * (READ) Finally, Changing demands. Engineers are obviously preoccupied with new construction. But buildings, through their normal life of changing tenants over time, change uses with respect to hazard levels, and hazard levels, or more precisely, the named high-hazard threshold, has become a moving target. Around the corner from our office in Nashville, I snapped this picture. It sits in front of a warehouse owned by an automotive dealer. When they bought the property and erected the building, they put a double-check BFP down in that vault with the meter. A few years later, the city changed an ordinance that redefined their particular use to high-hazard. When they sought a permit to upgrade the HVAC system, the city forced them to change to an RPZ. After constructing this huge vault, they now leave it almost empty with an RPZ in an enclosure perched on top of it. They paid three times for a single solution. Now this enclosure – This is what happens all too often when tenants or hazard thresholds change in areas where no guidelines or Standard Details exist.
  25. So let’s look at the considerations. Safety, Liability, and changing demands * We’ve all seen the extraordinary measures OSHA imposes to legally access vaults for maintenance tasks. fresh air exchange hoses, tents, extra men. The costs are more and more prohibitive but frankly, the risk of serious injury is real as well. * But beyond the cost of safety for onsite workers, liability issues persist. * When a vault floods like this one, the mandatory test cocks are submerged, and in that event, a violation of the International Plumbing has likely already occurred. The water may look clean, but consider what would typically make up the constituents of that water. Runoff of lawn chemicals alone make this a clear and present danger to the water supply. In fact, it led the USC Foundation of Cross Connection & Hydraulic Research in 2005 to change their recommendation of even double check BFP installation in vaults. * (READ) Finally, Changing demands. Engineers are obviously preoccupied with new construction. But buildings, through their normal life of changing tenants over time, change uses with respect to hazard levels, and hazard levels, or more precisely, the named high-hazard threshold, has become a moving target. Around the corner from our office in Nashville, I snapped this picture. It sits in front of a warehouse owned by an automotive dealer. When they bought the property and erected the building, they put a double-check BFP down in that vault with the meter. A few years later, the city changed an ordinance that redefined their particular use to high-hazard. When they sought a permit to upgrade the HVAC system, the city forced them to change to an RPZ. After constructing this huge vault, they now leave it almost empty with an RPZ in an enclosure perched on top of it. They paid three times for a single solution. Now this enclosure – This is what happens all too often when tenants or hazard thresholds change in areas where no guidelines or Standard Details exist.
  26. So let’s look at the considerations. Safety, Liability, and changing demands * We’ve all seen the extraordinary measures OSHA imposes to legally access vaults for maintenance tasks. fresh air exchange hoses, tents, extra men. The costs are more and more prohibitive but frankly, the risk of serious injury is real as well. * But beyond the cost of safety for onsite workers, liability issues persist. * When a vault floods like this one, the mandatory test cocks are submerged, and in that event, a violation of the International Plumbing has likely already occurred. The water may look clean, but consider what would typically make up the constituents of that water. Runoff of lawn chemicals alone make this a clear and present danger to the water supply. In fact, it led the USC Foundation of Cross Connection & Hydraulic Research in 2005 to change their recommendation of even double check BFP installation in vaults. * (READ) Finally, Changing demands. Engineers are obviously preoccupied with new construction. But buildings, through their normal life of changing tenants over time, change uses with respect to hazard levels, and hazard levels, or more precisely, the named high-hazard threshold, has become a moving target. Around the corner from our office in Nashville, I snapped this picture. It sits in front of a warehouse owned by an automotive dealer. When they bought the property and erected the building, they put a double-check BFP down in that vault with the meter. A few years later, the city changed an ordinance that redefined their particular use to high-hazard. When they sought a permit to upgrade the HVAC system, the city forced them to change to an RPZ. After constructing this huge vault, they now leave it almost empty with an RPZ in an enclosure perched on top of it. They paid three times for a single solution. Now this enclosure – This is what happens all too often when tenants or hazard thresholds change in areas where no guidelines or Standard Details exist.
  27. So let’s look at the considerations. Safety, Liability, and changing demands * We’ve all seen the extraordinary measures OSHA imposes to legally access vaults for maintenance tasks. fresh air exchange hoses, tents, extra men. The costs are more and more prohibitive but frankly, the risk of serious injury is real as well. * But beyond the cost of safety for onsite workers, liability issues persist. * When a vault floods like this one, the mandatory test cocks are submerged, and in that event, a violation of the International Plumbing has likely already occurred. The water may look clean, but consider what would typically make up the constituents of that water. Runoff of lawn chemicals alone make this a clear and present danger to the water supply. In fact, it led the USC Foundation of Cross Connection & Hydraulic Research in 2005 to change their recommendation of even double check BFP installation in vaults. * (READ) Finally, Changing demands. Engineers are obviously preoccupied with new construction. But buildings, through their normal life of changing tenants over time, change uses with respect to hazard levels, and hazard levels, or more precisely, the named high-hazard threshold, has become a moving target. Around the corner from our office in Nashville, I snapped this picture. It sits in front of a warehouse owned by an automotive dealer. When they bought the property and erected the building, they put a double-check BFP down in that vault with the meter. A few years later, the city changed an ordinance that redefined their particular use to high-hazard. When they sought a permit to upgrade the HVAC system, the city forced them to change to an RPZ. After constructing this huge vault, they now leave it almost empty with an RPZ in an enclosure perched on top of it. They paid three times for a single solution. Now this enclosure – This is what happens all too often when tenants or hazard thresholds change in areas where no guidelines or Standard Details exist.
  28. So let’s look at the considerations. Safety, Liability, and changing demands * We’ve all seen the extraordinary measures OSHA imposes to legally access vaults for maintenance tasks. fresh air exchange hoses, tents, extra men. The costs are more and more prohibitive but frankly, the risk of serious injury is real as well. * But beyond the cost of safety for onsite workers, liability issues persist. * When a vault floods like this one, the mandatory test cocks are submerged, and in that event, a violation of the International Plumbing has likely already occurred. The water may look clean, but consider what would typically make up the constituents of that water. Runoff of lawn chemicals alone make this a clear and present danger to the water supply. In fact, it led the USC Foundation of Cross Connection & Hydraulic Research in 2005 to change their recommendation of even double check BFP installation in vaults. * (READ) Finally, Changing demands. Engineers are obviously preoccupied with new construction. But buildings, through their normal life of changing tenants over time, change uses with respect to hazard levels, and hazard levels, or more precisely, the named high-hazard threshold, has become a moving target. Around the corner from our office in Nashville, I snapped this picture. It sits in front of a warehouse owned by an automotive dealer. When they bought the property and erected the building, they put a double-check BFP down in that vault with the meter. A few years later, the city changed an ordinance that redefined their particular use to high-hazard. When they sought a permit to upgrade the HVAC system, the city forced them to change to an RPZ. After constructing this huge vault, they now leave it almost empty with an RPZ in an enclosure perched on top of it. They paid three times for a single solution. Now this enclosure – This is what happens all too often when tenants or hazard thresholds change in areas where no guidelines or Standard Details exist.
  29. So let’s look at the considerations. Safety, Liability, and changing demands * We’ve all seen the extraordinary measures OSHA imposes to legally access vaults for maintenance tasks. fresh air exchange hoses, tents, extra men. The costs are more and more prohibitive but frankly, the risk of serious injury is real as well. * But beyond the cost of safety for onsite workers, liability issues persist. * When a vault floods like this one, the mandatory test cocks are submerged, and in that event, a violation of the International Plumbing has likely already occurred. The water may look clean, but consider what would typically make up the constituents of that water. Runoff of lawn chemicals alone make this a clear and present danger to the water supply. In fact, it led the USC Foundation of Cross Connection & Hydraulic Research in 2005 to change their recommendation of even double check BFP installation in vaults. * (READ) Finally, Changing demands. Engineers are obviously preoccupied with new construction. But buildings, through their normal life of changing tenants over time, change uses with respect to hazard levels, and hazard levels, or more precisely, the named high-hazard threshold, has become a moving target. Around the corner from our office in Nashville, I snapped this picture. It sits in front of a warehouse owned by an automotive dealer. When they bought the property and erected the building, they put a double-check BFP down in that vault with the meter. A few years later, the city changed an ordinance that redefined their particular use to high-hazard. When they sought a permit to upgrade the HVAC system, the city forced them to change to an RPZ. After constructing this huge vault, they now leave it almost empty with an RPZ in an enclosure perched on top of it. They paid three times for a single solution. Now this enclosure – This is what happens all too often when tenants or hazard thresholds change in areas where no guidelines or Standard Details exist.
  30. Today we’ll take a look at the questions designers and plans-review personnel are asking to determine proper application of containment backflow prevention Why outside? (OR asked another way, Why not inside?) I’ll show you the 2 critically important reasons why these systems are best placed outside. 2. Once that’s laid out, I’ll take you through the 5 reasons more and more water authorities are deciding that subterranean vault installation is too dangerous, too expensive, and too much of a risk burden to be allowed to continue. 3. Where is the momentum (and what does it tell us about the future) for containment BP systems? 4. Survey
  31. What is going on in the engineering community and with water jurisdictions that is driving change to get these installations into a safer environment? This past fall at the Bi-Annual ASPE National conference, one of the learning workshops had this title. The Board President of the Central Texas ASPE, Chris Phillips, a plumbing engineer at Jacobs in SAT contacted me and asked me to deliver the message.
  32. All these cities have made changes whereby RPZ use has been expanded either by lowering or eliminating the hazard threshold for use on domestic water lines in the past 5 years.
  33. Let’s look briefly at the new solutions emerging to deal with the need for less visual impact on property fronts that owners so desperately desire. * This is the industry standard Watts 709 DCDA. It is housed by our Model 1000-AL. It’s 12 feet long and stands 6’8” tall. * This is the Wilkins 450DA. It is housed in our Model 1000TLU880M. It’s 5’4” square and stands just 5’2” tall. same plumbing solution and make a much smaller visual footprint.
  34. So if you are a water authority contemplating an expanded use of aboveground enclosures, you are not alone. In fact, you’ve zeroed in on the central component to the nation’s emerging best practices and the proper application of containment backflow preventer systems. 1 Because of the Strong migration toward RPZs nationwide, proper application means more enclosures. 2 Because the High hazard threshold is changing or being eliminated all over the country, you’ll see more enclosures; 3 Because the owners and designer’s risk is lower with outdoor RPZs, you’ll see more enclosures; 4 Because of a growing list of available standard details for aboveground installations, you’ll see more enclosures; 5 Because it’s considered the best insurance policy against professional liability claims, you’ll see more enclosures.
  35. If you have any questions or comments, please email me at randy@safe-t-cover.com or phone me at 800-245-6333.