Evolution in Electrical Maintenance & Safety
ProgrammeProgramme
How Connectivity Drives Operational Intelligence
FMM Seminar on Complying with the Electricity Supply (Ammendment) Act 2015 & Electricity Related Issues – May 10, 2016
Ch’ng Eng Yong, CEng MEI, CEM, CMVP, PEM
Power Solutions, EcoBuilding Business – Schneider Electric
1
2
What are we discussing today?
Evolution of electrical maintenance
How connectivity drives operational intelligence2
3
How connectivity drives operational intelligence
Closing thoughts
Evolution of Electrical Maintenance
Maintenance can avoid up to 77% of equipment breakdown
4%
1%1%
8%
7%
5%
5%
Causes of Contacts or
Environment
Overload
Electrical
disturbance
Faulty
insulation
Lightning
Shocks
Others
34%
17%
9%
9%
8%
Causes of
Equipment
Breakdown
Contacts or
faulty parts
Poor
workmanship
Faulty
equipment
Source: Hartford Steam Boiler Insurance and Schneider Electric
Humidity
Environment
Evolution of Electrical Maintenance
Maintenance can avoid up to 77% of equipment breakdown
4%
1%1%
8%
7%
5%
5%
Causes of Contacts or
Environment
Overload
Electrical
disturbance
Faulty
insulation
Lightning
Shocks
Others
34%
17%
9%
9%
8%
Causes of
Equipment
Breakdown
Contacts or
faulty parts
Poor
workmanship
Faulty
equipment
Source: Hartford Steam Boiler Insurance and Schneider Electric
Humidity
Environment
Evolution of Electrical Maintenance
Approaches to electrical equipment maintenance
Evolution of Electrical Maintenance
Real-time maintenance can avoid up to 94% of equipment breakdown
4%
1%1%
8%
7%
5%
5%
Causes of Contacts or
Environment
Overload
Electrical
disturbance
Faulty
insulation
Lightning
Shocks
Others
34%
17%
9%
9%
8%
Causes of
Equipment
Breakdown
Contacts or
faulty parts
Poor
workmanship
Faulty
equipment
Source: Hartford Steam Boiler Insurance and Schneider Electric
Humidity
Environment
Evolution of Electrical Maintenance
Real-time maintenance can avoid up to 94% of equipment breakdown
4%
1%1%
8%
7%
5%
5%
Causes of Contacts or
Environment
Overload
Electrical
disturbance
Faulty
insulation
34%
17%
9%
9%
8%
Causes of
Equipment
Breakdown
Contacts or
faulty parts
Poor
workmanship
Faulty
equipment
Source: Hartford Steam Boiler Insurance and Schneider Electric
Humidity
Environment
Evolution of Electrical Maintenance
Maintenance can avoid up to 77% of equipment breakdown
4%
1%1%
8%
7%
5%
5%
Causes of Contacts or
Environment
Overload
Electrical
disturbance
Faulty
insulation
Lightning
Shocks
Others
34%
17%
9%
9%
8%
Causes of
Equipment
Breakdown
Contacts or
faulty parts
Poor
workmanship
Faulty
equipment
Source: Hartford Steam Boiler Insurance and Schneider Electric
Humidity
Environment
Evolution of Electrical Maintenance
Maintenance can avoid up to 77% of equipment breakdown
4%
1%1%
8%
7%
5%
5%
Causes of Contacts or
Environment
Overload
Electrical
disturbance
Faulty
insulation
Lightning
Shocks
Others
34%
17%
9%
9%
8%
Causes of
Equipment
Breakdown
Contacts or
faulty parts
Poor
workmanship
Faulty
equipment
Source: Hartford Steam Boiler Insurance and Schneider Electric
Humidity
Environment
Predictive Monitoring
Detects issues before
Root Cause Analysis
Analyse electrical faultsDetects issues before
they become a problem & disturbances
Predictive Monitoring
Detects issues beforeDetects issues before
they become a problem
> LV Breaker aging
> Identifies predictive maintenance opportunities for
LV breakers
> Aging algorithm and wear parameters monitoring
based on environmental conditions and real time
Breaker Performance
based on environmental conditions and real time
load assessment
> Features predefined alarms for network abnormal
conditions tracking
> Prevent unwanted faults
> Scheduled maintenance operations
> UPS monthly auto-test report
> Check the battery health – predictive maintenance
opportunities identified
> UPS battery health
> Checks battery health in case of UPS without auto-
UPS Performance
> Checks battery health in case of UPS without auto-
test facilities
UPS monthly auto-test
UPS battery health
> Generator Test Report:
˃ Provide documented evidence of a regular and
consistent generator system testing process.
˃ Identify any generator problems that could prevent
a transfer to backup power.
Generator Performance
a transfer to backup power.
> Automated test process:
> Follow legislated test procedure
> Monitor genset and ATS status, check transfer
times
> Measure power quality and load levels
Emergency Power Supply System
> Measure power quality and load levels
> Finish test according to time requirement
> Ensures traceability through:
> Data is logged in the system, making it easy to
demonstrate standards compliance, and reduce
litigation risks
Root Cause Analysis
Analyze electrical faults
& disturbances
> Use multiple meter to determine general location
of the disturbance whether is upstream or
downstream
> If the meter is on the building main incomer, it
determines if the disturbance occurred within the
building or from the utility
Disturbance Detection Direction
building or from the utility
> A system of hardware and software that records
events with millisecond accuracy and puts them
in chronological order
> A historical timeline, with millisecond resolution
> Purpose:
Sequence of Event Recordings
> Purpose:
> Record initiating event
> Record resulting event sequence
> Help determine if controls and protections system
responded properly
> Allow to either fix it or mitigate its future effects
Evolution of Electrical Maintenance
Maintenance can avoid up to 77% of equipment breakdown
4%
1%1%
8%
7%
5%
5%
Causes of Contacts or
Environment
Overload
Electrical
disturbance
Faulty
insulation
Lightning
Shocks
Others
34%
17%
9%
9%
8%
Causes of
Equipment
Breakdown
Contacts or
faulty parts
Poor
workmanship
Faulty
equipment
Source: Hartford Steam Boiler Insurance and Schneider Electric
Humidity
Environment
Our technologies ensure that
everywhere, for everyone and at every moment.
Ch‘ng Eng Yong
+6012 – 2750 876
You‘ve got questions?
Contact
+6012 – 2750 876
eng-yong.chng@schneider-electric.com

Contenu connexe

Tendances

Electrical Maintenance for Engineers and Technicians
Electrical Maintenance for Engineers and TechniciansElectrical Maintenance for Engineers and Technicians
Electrical Maintenance for Engineers and TechniciansLiving Online
 
Photovoltaic Training Course - Module 3.3 - Control system data management
Photovoltaic Training Course - Module 3.3 - Control system data managementPhotovoltaic Training Course - Module 3.3 - Control system data management
Photovoltaic Training Course - Module 3.3 - Control system data managementLeonardo ENERGY
 
Synchrophasor Timing Security
Synchrophasor Timing SecuritySynchrophasor Timing Security
Synchrophasor Timing SecurityTheAnfieldGroup
 
Vestas American Wind Training
Vestas American Wind TrainingVestas American Wind Training
Vestas American Wind TrainingPhillip Schwochow
 
Wind turbine condition monitoring sqi rev
Wind turbine condition monitoring sqi revWind turbine condition monitoring sqi rev
Wind turbine condition monitoring sqi revSpectra Quest Inc
 
5 reasons why it’s wrong to use HVAC control systems for smoke ventilation
5 reasons why it’s wrong to use HVAC control systems for smoke ventilation5 reasons why it’s wrong to use HVAC control systems for smoke ventilation
5 reasons why it’s wrong to use HVAC control systems for smoke ventilationColt UK
 
Hazardmon.com - Cloud-based hazard monitoring for conveying systems -Geaps pr...
Hazardmon.com - Cloud-based hazard monitoring for conveying systems -Geaps pr...Hazardmon.com - Cloud-based hazard monitoring for conveying systems -Geaps pr...
Hazardmon.com - Cloud-based hazard monitoring for conveying systems -Geaps pr...4B Braime Components
 
Air pollution monitoring system
Air pollution monitoring systemAir pollution monitoring system
Air pollution monitoring systemSuraksha Sanghavi
 
NTHP1015 Foresight ENA Casestudy Brochure FA01_no bleed-single pages (5)
NTHP1015 Foresight ENA Casestudy Brochure FA01_no bleed-single pages (5)NTHP1015 Foresight ENA Casestudy Brochure FA01_no bleed-single pages (5)
NTHP1015 Foresight ENA Casestudy Brochure FA01_no bleed-single pages (5)Aleksandar Klisaric
 
Geo therm ltd brochure
Geo therm ltd   brochureGeo therm ltd   brochure
Geo therm ltd brochureTony Dale
 
Embedding Realtime Multilevel Gas Leakage Control System
Embedding Realtime Multilevel Gas Leakage Control SystemEmbedding Realtime Multilevel Gas Leakage Control System
Embedding Realtime Multilevel Gas Leakage Control SystemIRJET Journal
 
IoT Based Industrial Sewage Water Purity Indicator
IoT Based Industrial Sewage Water Purity IndicatorIoT Based Industrial Sewage Water Purity Indicator
IoT Based Industrial Sewage Water Purity IndicatorIRJET Journal
 
Eagle eye
Eagle eyeEagle eye
Eagle eyemitdfw
 
Power quality management case study
Power quality management  case studyPower quality management  case study
Power quality management case studyMinka Grdesic
 

Tendances (19)

Electrical maintenance
Electrical maintenanceElectrical maintenance
Electrical maintenance
 
Electrical Maintenance for Engineers and Technicians
Electrical Maintenance for Engineers and TechniciansElectrical Maintenance for Engineers and Technicians
Electrical Maintenance for Engineers and Technicians
 
Eicr brochure page
Eicr brochure pageEicr brochure page
Eicr brochure page
 
Photovoltaic Training Course - Module 3.3 - Control system data management
Photovoltaic Training Course - Module 3.3 - Control system data managementPhotovoltaic Training Course - Module 3.3 - Control system data management
Photovoltaic Training Course - Module 3.3 - Control system data management
 
Synchrophasor Timing Security
Synchrophasor Timing SecuritySynchrophasor Timing Security
Synchrophasor Timing Security
 
Vestas American Wind Training
Vestas American Wind TrainingVestas American Wind Training
Vestas American Wind Training
 
Wind turbine condition monitoring sqi rev
Wind turbine condition monitoring sqi revWind turbine condition monitoring sqi rev
Wind turbine condition monitoring sqi rev
 
5 reasons why it’s wrong to use HVAC control systems for smoke ventilation
5 reasons why it’s wrong to use HVAC control systems for smoke ventilation5 reasons why it’s wrong to use HVAC control systems for smoke ventilation
5 reasons why it’s wrong to use HVAC control systems for smoke ventilation
 
Hazardmon.com - Cloud-based hazard monitoring for conveying systems -Geaps pr...
Hazardmon.com - Cloud-based hazard monitoring for conveying systems -Geaps pr...Hazardmon.com - Cloud-based hazard monitoring for conveying systems -Geaps pr...
Hazardmon.com - Cloud-based hazard monitoring for conveying systems -Geaps pr...
 
Air pollution monitoring system
Air pollution monitoring systemAir pollution monitoring system
Air pollution monitoring system
 
NTHP1015 Foresight ENA Casestudy Brochure FA01_no bleed-single pages (5)
NTHP1015 Foresight ENA Casestudy Brochure FA01_no bleed-single pages (5)NTHP1015 Foresight ENA Casestudy Brochure FA01_no bleed-single pages (5)
NTHP1015 Foresight ENA Casestudy Brochure FA01_no bleed-single pages (5)
 
Geo therm ltd brochure
Geo therm ltd   brochureGeo therm ltd   brochure
Geo therm ltd brochure
 
Embedding Realtime Multilevel Gas Leakage Control System
Embedding Realtime Multilevel Gas Leakage Control SystemEmbedding Realtime Multilevel Gas Leakage Control System
Embedding Realtime Multilevel Gas Leakage Control System
 
Rigel 377
Rigel 377Rigel 377
Rigel 377
 
Rigel 288
Rigel 288Rigel 288
Rigel 288
 
IoT Based Industrial Sewage Water Purity Indicator
IoT Based Industrial Sewage Water Purity IndicatorIoT Based Industrial Sewage Water Purity Indicator
IoT Based Industrial Sewage Water Purity Indicator
 
Eagle eye
Eagle eyeEagle eye
Eagle eye
 
Power quality management case study
Power quality management  case studyPower quality management  case study
Power quality management case study
 
Poster Swagata Das
Poster Swagata DasPoster Swagata Das
Poster Swagata Das
 

En vedette

Electrical maintenance in Hazardous area
Electrical maintenance in Hazardous area Electrical maintenance in Hazardous area
Electrical maintenance in Hazardous area BHAGWAN PRASAD
 
T.L.E. GRADE 7 LESSONS
T.L.E. GRADE 7 LESSONST.L.E. GRADE 7 LESSONS
T.L.E. GRADE 7 LESSONSDayleen Hijosa
 
High Voltage Safety Operating Procedures for Engineers and Technicians
High Voltage Safety Operating Procedures for Engineers and TechniciansHigh Voltage Safety Operating Procedures for Engineers and Technicians
High Voltage Safety Operating Procedures for Engineers and TechniciansLiving Online
 
Electrical Risk Management
Electrical Risk ManagementElectrical Risk Management
Electrical Risk Managementguest81e1c7
 
Electrical Safety Joliet Distribution Center
Electrical Safety Joliet Distribution CenterElectrical Safety Joliet Distribution Center
Electrical Safety Joliet Distribution Centertrevor_heller
 
Lockout Tagout
Lockout TagoutLockout Tagout
Lockout Tagoutvtsiri
 
Wastewater treatment( general introduction )
Wastewater treatment( general introduction )Wastewater treatment( general introduction )
Wastewater treatment( general introduction )Anudeep Nema
 
Wastewater treatment
Wastewater treatmentWastewater treatment
Wastewater treatmentGhassan Hadi
 
Preventive Maintenance Strategies for Power Distribution Systems- Charles Alvis
Preventive Maintenance Strategies for Power Distribution Systems- Charles AlvisPreventive Maintenance Strategies for Power Distribution Systems- Charles Alvis
Preventive Maintenance Strategies for Power Distribution Systems- Charles AlvisSchneider Electric
 
Electrical maintenance fundamentals
Electrical maintenance fundamentalsElectrical maintenance fundamentals
Electrical maintenance fundamentalsJames Shearer
 
Troubleshooting, Maintenance and Protection of AC Electrical Motors and Drives
Troubleshooting, Maintenance and Protection of AC Electrical Motors and DrivesTroubleshooting, Maintenance and Protection of AC Electrical Motors and Drives
Troubleshooting, Maintenance and Protection of AC Electrical Motors and DrivesLiving Online
 
Electrical maintenance-1
Electrical maintenance-1Electrical maintenance-1
Electrical maintenance-1Vijay Raskar
 
Electrical Safety
Electrical  Safety Electrical  Safety
Electrical Safety Reliance
 
Water treatment plant of environmental engineering
Water treatment plant of environmental engineeringWater treatment plant of environmental engineering
Water treatment plant of environmental engineeringSehrish Mehmood
 
Electrical Safety by Industrial Safety Institute
Electrical Safety by Industrial Safety InstituteElectrical Safety by Industrial Safety Institute
Electrical Safety by Industrial Safety InstituteAtlantic Training, LLC.
 
presentation on substation layout and BUS bar arrangement.
presentation on substation layout and BUS bar arrangement.presentation on substation layout and BUS bar arrangement.
presentation on substation layout and BUS bar arrangement.Hemendra Kumar Rajput
 
Wastewater treatment
Wastewater treatmentWastewater treatment
Wastewater treatmentRanjan Das
 
water treatment slides
water treatment slideswater treatment slides
water treatment slidesAnand Keshri
 

En vedette (20)

Electrical maintenance in Hazardous area
Electrical maintenance in Hazardous area Electrical maintenance in Hazardous area
Electrical maintenance in Hazardous area
 
T.L.E. GRADE 7 LESSONS
T.L.E. GRADE 7 LESSONST.L.E. GRADE 7 LESSONS
T.L.E. GRADE 7 LESSONS
 
High Voltage Safety Operating Procedures for Engineers and Technicians
High Voltage Safety Operating Procedures for Engineers and TechniciansHigh Voltage Safety Operating Procedures for Engineers and Technicians
High Voltage Safety Operating Procedures for Engineers and Technicians
 
Electrical Risk Management
Electrical Risk ManagementElectrical Risk Management
Electrical Risk Management
 
Electrical Safety Joliet Distribution Center
Electrical Safety Joliet Distribution CenterElectrical Safety Joliet Distribution Center
Electrical Safety Joliet Distribution Center
 
Lockout Tagout
Lockout TagoutLockout Tagout
Lockout Tagout
 
Wastewater treatment( general introduction )
Wastewater treatment( general introduction )Wastewater treatment( general introduction )
Wastewater treatment( general introduction )
 
Wastewater treatment
Wastewater treatmentWastewater treatment
Wastewater treatment
 
Preventive Maintenance Strategies for Power Distribution Systems- Charles Alvis
Preventive Maintenance Strategies for Power Distribution Systems- Charles AlvisPreventive Maintenance Strategies for Power Distribution Systems- Charles Alvis
Preventive Maintenance Strategies for Power Distribution Systems- Charles Alvis
 
Electrical safety new
Electrical safety newElectrical safety new
Electrical safety new
 
Electrical maintenance fundamentals
Electrical maintenance fundamentalsElectrical maintenance fundamentals
Electrical maintenance fundamentals
 
Troubleshooting, Maintenance and Protection of AC Electrical Motors and Drives
Troubleshooting, Maintenance and Protection of AC Electrical Motors and DrivesTroubleshooting, Maintenance and Protection of AC Electrical Motors and Drives
Troubleshooting, Maintenance and Protection of AC Electrical Motors and Drives
 
Electrical maintenance-1
Electrical maintenance-1Electrical maintenance-1
Electrical maintenance-1
 
Electrical Safety
Electrical  Safety Electrical  Safety
Electrical Safety
 
Water treatment plant of environmental engineering
Water treatment plant of environmental engineeringWater treatment plant of environmental engineering
Water treatment plant of environmental engineering
 
Electrical safety
Electrical safetyElectrical safety
Electrical safety
 
Electrical Safety by Industrial Safety Institute
Electrical Safety by Industrial Safety InstituteElectrical Safety by Industrial Safety Institute
Electrical Safety by Industrial Safety Institute
 
presentation on substation layout and BUS bar arrangement.
presentation on substation layout and BUS bar arrangement.presentation on substation layout and BUS bar arrangement.
presentation on substation layout and BUS bar arrangement.
 
Wastewater treatment
Wastewater treatmentWastewater treatment
Wastewater treatment
 
water treatment slides
water treatment slideswater treatment slides
water treatment slides
 

Similaire à Evolution in Electrical Maintenance & Safety Programme - How Connectivity Drives Operational Intelligence

Health Monitoring of Industrial and Electrical Equipment
Health Monitoring of Industrial and Electrical EquipmentHealth Monitoring of Industrial and Electrical Equipment
Health Monitoring of Industrial and Electrical EquipmentMAJAHARUL IMAM
 
Nidec asi service infrared termography
Nidec asi service infrared termographyNidec asi service infrared termography
Nidec asi service infrared termographyNidec Corporation
 
Functional safety by FMEA/FTA
Functional safety by FMEA/FTAFunctional safety by FMEA/FTA
Functional safety by FMEA/FTAmehmor
 
DistribuTECH 2016: OMNETRIC next generation outage management
DistribuTECH 2016: OMNETRIC next generation outage managementDistribuTECH 2016: OMNETRIC next generation outage management
DistribuTECH 2016: OMNETRIC next generation outage managementOMNETRIC
 
Estimating Reliability of Power Factor Correction Circuits: A Comparative Study
Estimating Reliability of Power Factor Correction Circuits: A Comparative StudyEstimating Reliability of Power Factor Correction Circuits: A Comparative Study
Estimating Reliability of Power Factor Correction Circuits: A Comparative StudyIJERA Editor
 
Wind Exchange 2015 Report
Wind Exchange 2015 ReportWind Exchange 2015 Report
Wind Exchange 2015 ReportJoshua Chokera
 
SMC ETP System Power Transformer Maintenance
SMC ETP System Power Transformer MaintenanceSMC ETP System Power Transformer Maintenance
SMC ETP System Power Transformer MaintenanceErika Herbozo
 
Transformer Protection using PLC
Transformer Protection using PLCTransformer Protection using PLC
Transformer Protection using PLCSageer Ali Khan
 
IRJET - Overview of Smart Tower Technology for Transmission Lines
IRJET - 	  Overview of Smart Tower Technology for Transmission LinesIRJET - 	  Overview of Smart Tower Technology for Transmission Lines
IRJET - Overview of Smart Tower Technology for Transmission LinesIRJET Journal
 
Global Electrical Safety
Global Electrical SafetyGlobal Electrical Safety
Global Electrical Safetyguest81e1c7
 
IRJET - Transmission Line Fault Classification using DWT
IRJET -  	  Transmission Line Fault Classification using DWTIRJET -  	  Transmission Line Fault Classification using DWT
IRJET - Transmission Line Fault Classification using DWTIRJET Journal
 
Monitoring of Distribution Transformer Parameters Using Plc
Monitoring of Distribution Transformer Parameters Using PlcMonitoring of Distribution Transformer Parameters Using Plc
Monitoring of Distribution Transformer Parameters Using PlcIRJET Journal
 
Schneider Electric
Schneider ElectricSchneider Electric
Schneider ElectricFMA Summits
 
Tpl electrical safety230311
Tpl electrical safety230311Tpl electrical safety230311
Tpl electrical safety230311Essakki raj
 
Switchgear and Protection Engineering Lecture 01.pptx
Switchgear and Protection Engineering Lecture 01.pptxSwitchgear and Protection Engineering Lecture 01.pptx
Switchgear and Protection Engineering Lecture 01.pptxLoitaFredy
 

Similaire à Evolution in Electrical Maintenance & Safety Programme - How Connectivity Drives Operational Intelligence (20)

UST Power Quality Basics
UST Power Quality BasicsUST Power Quality Basics
UST Power Quality Basics
 
Health Monitoring of Industrial and Electrical Equipment
Health Monitoring of Industrial and Electrical EquipmentHealth Monitoring of Industrial and Electrical Equipment
Health Monitoring of Industrial and Electrical Equipment
 
Fmea
FmeaFmea
Fmea
 
Power quality analysis (2)
Power quality analysis (2)Power quality analysis (2)
Power quality analysis (2)
 
Nidec asi service infrared termography
Nidec asi service infrared termographyNidec asi service infrared termography
Nidec asi service infrared termography
 
Functional safety by FMEA/FTA
Functional safety by FMEA/FTAFunctional safety by FMEA/FTA
Functional safety by FMEA/FTA
 
DistribuTECH 2016: OMNETRIC next generation outage management
DistribuTECH 2016: OMNETRIC next generation outage managementDistribuTECH 2016: OMNETRIC next generation outage management
DistribuTECH 2016: OMNETRIC next generation outage management
 
file-9.pptx
file-9.pptxfile-9.pptx
file-9.pptx
 
Estimating Reliability of Power Factor Correction Circuits: A Comparative Study
Estimating Reliability of Power Factor Correction Circuits: A Comparative StudyEstimating Reliability of Power Factor Correction Circuits: A Comparative Study
Estimating Reliability of Power Factor Correction Circuits: A Comparative Study
 
file-9.pptx
file-9.pptxfile-9.pptx
file-9.pptx
 
Wind Exchange 2015 Report
Wind Exchange 2015 ReportWind Exchange 2015 Report
Wind Exchange 2015 Report
 
SMC ETP System Power Transformer Maintenance
SMC ETP System Power Transformer MaintenanceSMC ETP System Power Transformer Maintenance
SMC ETP System Power Transformer Maintenance
 
Transformer Protection using PLC
Transformer Protection using PLCTransformer Protection using PLC
Transformer Protection using PLC
 
IRJET - Overview of Smart Tower Technology for Transmission Lines
IRJET - 	  Overview of Smart Tower Technology for Transmission LinesIRJET - 	  Overview of Smart Tower Technology for Transmission Lines
IRJET - Overview of Smart Tower Technology for Transmission Lines
 
Global Electrical Safety
Global Electrical SafetyGlobal Electrical Safety
Global Electrical Safety
 
IRJET - Transmission Line Fault Classification using DWT
IRJET -  	  Transmission Line Fault Classification using DWTIRJET -  	  Transmission Line Fault Classification using DWT
IRJET - Transmission Line Fault Classification using DWT
 
Monitoring of Distribution Transformer Parameters Using Plc
Monitoring of Distribution Transformer Parameters Using PlcMonitoring of Distribution Transformer Parameters Using Plc
Monitoring of Distribution Transformer Parameters Using Plc
 
Schneider Electric
Schneider ElectricSchneider Electric
Schneider Electric
 
Tpl electrical safety230311
Tpl electrical safety230311Tpl electrical safety230311
Tpl electrical safety230311
 
Switchgear and Protection Engineering Lecture 01.pptx
Switchgear and Protection Engineering Lecture 01.pptxSwitchgear and Protection Engineering Lecture 01.pptx
Switchgear and Protection Engineering Lecture 01.pptx
 

Evolution in Electrical Maintenance & Safety Programme - How Connectivity Drives Operational Intelligence

  • 1. Evolution in Electrical Maintenance & Safety ProgrammeProgramme How Connectivity Drives Operational Intelligence FMM Seminar on Complying with the Electricity Supply (Ammendment) Act 2015 & Electricity Related Issues – May 10, 2016 Ch’ng Eng Yong, CEng MEI, CEM, CMVP, PEM Power Solutions, EcoBuilding Business – Schneider Electric
  • 2. 1 2 What are we discussing today? Evolution of electrical maintenance How connectivity drives operational intelligence2 3 How connectivity drives operational intelligence Closing thoughts
  • 3. Evolution of Electrical Maintenance Maintenance can avoid up to 77% of equipment breakdown 4% 1%1% 8% 7% 5% 5% Causes of Contacts or Environment Overload Electrical disturbance Faulty insulation Lightning Shocks Others 34% 17% 9% 9% 8% Causes of Equipment Breakdown Contacts or faulty parts Poor workmanship Faulty equipment Source: Hartford Steam Boiler Insurance and Schneider Electric Humidity Environment
  • 4. Evolution of Electrical Maintenance Maintenance can avoid up to 77% of equipment breakdown 4% 1%1% 8% 7% 5% 5% Causes of Contacts or Environment Overload Electrical disturbance Faulty insulation Lightning Shocks Others 34% 17% 9% 9% 8% Causes of Equipment Breakdown Contacts or faulty parts Poor workmanship Faulty equipment Source: Hartford Steam Boiler Insurance and Schneider Electric Humidity Environment
  • 5. Evolution of Electrical Maintenance Approaches to electrical equipment maintenance
  • 6. Evolution of Electrical Maintenance Real-time maintenance can avoid up to 94% of equipment breakdown 4% 1%1% 8% 7% 5% 5% Causes of Contacts or Environment Overload Electrical disturbance Faulty insulation Lightning Shocks Others 34% 17% 9% 9% 8% Causes of Equipment Breakdown Contacts or faulty parts Poor workmanship Faulty equipment Source: Hartford Steam Boiler Insurance and Schneider Electric Humidity Environment
  • 7. Evolution of Electrical Maintenance Real-time maintenance can avoid up to 94% of equipment breakdown 4% 1%1% 8% 7% 5% 5% Causes of Contacts or Environment Overload Electrical disturbance Faulty insulation 34% 17% 9% 9% 8% Causes of Equipment Breakdown Contacts or faulty parts Poor workmanship Faulty equipment Source: Hartford Steam Boiler Insurance and Schneider Electric Humidity Environment
  • 8. Evolution of Electrical Maintenance Maintenance can avoid up to 77% of equipment breakdown 4% 1%1% 8% 7% 5% 5% Causes of Contacts or Environment Overload Electrical disturbance Faulty insulation Lightning Shocks Others 34% 17% 9% 9% 8% Causes of Equipment Breakdown Contacts or faulty parts Poor workmanship Faulty equipment Source: Hartford Steam Boiler Insurance and Schneider Electric Humidity Environment
  • 9. Evolution of Electrical Maintenance Maintenance can avoid up to 77% of equipment breakdown 4% 1%1% 8% 7% 5% 5% Causes of Contacts or Environment Overload Electrical disturbance Faulty insulation Lightning Shocks Others 34% 17% 9% 9% 8% Causes of Equipment Breakdown Contacts or faulty parts Poor workmanship Faulty equipment Source: Hartford Steam Boiler Insurance and Schneider Electric Humidity Environment
  • 10. Predictive Monitoring Detects issues before Root Cause Analysis Analyse electrical faultsDetects issues before they become a problem & disturbances
  • 11. Predictive Monitoring Detects issues beforeDetects issues before they become a problem
  • 12. > LV Breaker aging > Identifies predictive maintenance opportunities for LV breakers > Aging algorithm and wear parameters monitoring based on environmental conditions and real time Breaker Performance based on environmental conditions and real time load assessment > Features predefined alarms for network abnormal conditions tracking > Prevent unwanted faults > Scheduled maintenance operations
  • 13. > UPS monthly auto-test report > Check the battery health – predictive maintenance opportunities identified > UPS battery health > Checks battery health in case of UPS without auto- UPS Performance > Checks battery health in case of UPS without auto- test facilities UPS monthly auto-test UPS battery health
  • 14. > Generator Test Report: ˃ Provide documented evidence of a regular and consistent generator system testing process. ˃ Identify any generator problems that could prevent a transfer to backup power. Generator Performance a transfer to backup power.
  • 15. > Automated test process: > Follow legislated test procedure > Monitor genset and ATS status, check transfer times > Measure power quality and load levels Emergency Power Supply System > Measure power quality and load levels > Finish test according to time requirement > Ensures traceability through: > Data is logged in the system, making it easy to demonstrate standards compliance, and reduce litigation risks
  • 16. Root Cause Analysis Analyze electrical faults & disturbances
  • 17. > Use multiple meter to determine general location of the disturbance whether is upstream or downstream > If the meter is on the building main incomer, it determines if the disturbance occurred within the building or from the utility Disturbance Detection Direction building or from the utility
  • 18. > A system of hardware and software that records events with millisecond accuracy and puts them in chronological order > A historical timeline, with millisecond resolution > Purpose: Sequence of Event Recordings > Purpose: > Record initiating event > Record resulting event sequence > Help determine if controls and protections system responded properly > Allow to either fix it or mitigate its future effects
  • 19. Evolution of Electrical Maintenance Maintenance can avoid up to 77% of equipment breakdown 4% 1%1% 8% 7% 5% 5% Causes of Contacts or Environment Overload Electrical disturbance Faulty insulation Lightning Shocks Others 34% 17% 9% 9% 8% Causes of Equipment Breakdown Contacts or faulty parts Poor workmanship Faulty equipment Source: Hartford Steam Boiler Insurance and Schneider Electric Humidity Environment
  • 20. Our technologies ensure that everywhere, for everyone and at every moment.
  • 21. Ch‘ng Eng Yong +6012 – 2750 876 You‘ve got questions? Contact +6012 – 2750 876 eng-yong.chng@schneider-electric.com