Harmonics mitigation and solutions
Schneider Electric 2
I. Introduction
II. Harmonics mitigation
solution
III.Case study
lV.Conclusion
Summary
Schneider Electric 3
I. Introduction
II. Harmonic mitigation solution
III.Case study
lV.Conclusion
Schneider Electric 4
I. Introduction
●The quality of electrical power is determined by the voltage
● High-quality voltage is the best guarantee for continuous operation of
equipment
The voltage signal must be perfect
at the source...
... because distortion may occur at the
end of the line
Line impedance
Type of installation
Length of cables
Internal impedance of
equipment...
The harmonic current
from the load
Type of load
Power supply
technology
Schneider Electric 5
I. Introduction
II. Harmonic mitigation solution
III.Case study
lV.Conclusion
Schneider Electric 6
-1.5
-1
-0.5
0
0.5
1
1.5
=
-1.5
-1
-0.5
0
0.5
1
1.5
+
-1.5
-1
-0.5
0
0.5
1
1.5
Signal with harmonics Fundamental H1 Harmonics H2 to Hn
H1 = 50Hz Hn = n x 50Hz
THD (U or I) % = 100 x
II. What is a harmonic waveform?
●Harmonic waveform is a distortion of the normal
Sinewave
●It is characterized by its distortion level
● For voltage (THD U - Total Harmonic Voltage
Distortion)
● For current (THD I - Total Harmonic Current
Distortion)
Schneider Electric 7
●Waveform examples and harmonic
spectrum
● Three- phase loads
Variable speed drive
Lifts…
● Single-phase loads
● Computers
● Phones
● Lighting ...
II. Current distortion
H11 H13 H17 H19 H21 H23
0
50
100
H1 H5 H7
Danger
H7 H9 H11 H13 H15
0
50
H1 H3 H5
Danger
H17
100
Schneider Electric 8
II. The effects of harmonics
●Voltage distortion:
● Excessive temperature rise in motors
● Electrical noises
● Sensitive electronic equipment malfunction
●Increase in the apparent power and over-sizing of sources (UPS,
Genset, etc.), capacitors, cables...
● Derating of electrical equipment or over-sizing
● Accelerated ageing of equipment
●Flow of current in the neutral conductor and consequently in the
PEN:
● Excessive temperature rise in transformer
● Tripping of circuit breakers
Schneider Electric 9
II. The effects of harmonics
M M M
Final distribution
enclosure
feeder S1 feeder S2 feeder S3
Secondary
switchboard
Main LV
Switchboard (MLVS)
feeder MS1 feeder MS2 feeder MSn
LV
Increased THDU
Increased RMS current
Non-linear current
circulating in the cables
●Voltage distortion: influence of THDI on the THDU
Schneider Electric 10
> Linear load without harmonics:
• Cos phi = Power factor = P/S
> Non-linear load :
• DPF = Displacement Power Factor - P1/S1 ( 50 Hz
fundamental current only)
• True Power factor = P/ST
> S = apparent powerP (W)
Q (var)φ
S (VA)
ST (VA)
D harmonic
P2 + Q2S =
P2 + Q2 + D2S =
II. The effects of harmonics
●Increase in the apparent power and over-sizing of
sources
Schneider Electric 11
-6
-4
-2
0
2
0 90 180 270 360 450
Phase 1
Phase 2
Phase 3
3rd Harmonic, phase 1
3rd Harmonic, phase 2
3rd Harmonic, phase 3
Total 3rd Harmonic
●Flow of current in the neutral conductor
● The H3 harmonic currents and multiples flow in the neutral
conductor.
● The cross-sectional area of the neutral conductor must be increased
(1.7 times that of the phases for switch-mode power supplies).
I3,I9,I15
II. The effects of harmonics
Schneider Electric 12
Normal or replacement
sources
Over-sizing of sources,
cables, etc.
Transformers with
different couplings
Tuned
filters
Anti-harm.
reactors
&
series filters
LD
y
Y
y
p1 = p2 p1 = p2
h5 h7
F
- The harmonics are not
eliminated.
- Very costly
2 Limits h3 and multiples.
D
d y
3 4
5 6
1
D
yn
h3 h9
2
h7 (6-pulse bridge)
5
6
Attenuates harmonics
at the tuning frequency.
Decreases THD(i).
1
3 4and attenuate h5 and
II. Harmonics mitigation solutions
●Electromechanical solutions
●Active filters
Schneider Electric 13
LoadMains
Filter
No capacitors
No power electronics
No batteries
No micro controllers
Unmatched reliability, same as that of a dry transformer
II. Passive filter: architecture & design
●3-phase + neutral filter
●Composed of only two elements
● 1 serial three-phase inductance
● 1 parallel three-phase inductance
Ph
N
Lo
Zo
Schneider Electric 14
input
output
●At A Glance:
● Zero sequence harmonic filter
● Reduces neutral currents in
commercial & industrial buildings
● Balancing of 3-phase currents
● 12-280 kVA (expandable)
● 3-phase low voltage applications
●Customer benefits
● Simple and highly reliable design
● Reduction of neutral currents by 10:1
● Compliance with harmonic standards
● Capacity upgrade by parallel
connection
● Operational savings
● Easy integration into power
distribution cabinets (Chassis Format)
● Easy sizing and installer friendly
II. Cleanwave: solution for neutral currents
Schneider Electric 15
II. Sizing cleanwave
●CleanWave is designed for the most demanding situations
● H3 harmonics and multiple: THDI up to 80%
● Neutral current = 1.8 times phase current
●Very easy sizing
Max power or max. Iphase
of the load
Selection of the filter of
immediately higher
power or current
25 kVA load
Selection of the
30 kVA CleanWave
Schneider Electric 16
II. Unbalanced load tests
Balanced Without Ph3 Without Ph2 & 3
I1 in
In in
I1 out
In out
I1 in
In in
I1 out
In out
I1 in
In in
I1 out
In out
I1: 150A
I2: 149A
I3: 151A
In: 21A
I1: 126A
I2: 126A
I3: 127A
In: 242A
I1: 126A
I2: 126A
I3: 0A
In: 201A
I1: 112A
I2: 122A
I3: 65A
In: 25A
I1: 107A
I2: 46A
I3: 46A
In: 25A
I1: 154A
I2: 0A
I3: 0A
In: 150A
Input:
In = 21 A
Output:
In = 242 A
Input:
In = 25 A
Output:
In = 201 A
Input:
In = 25 A
Output:
In = 150 A
1mv=1 A 1mv=1 A1mv=1 A
Schneider Electric 17
I source I load
Power
source
Non-linear
load
Active
harmonic
conditioner
I conditioner
● The active harmonic conditioner generates the harmonic currents
required by non-linear loads. These currents are opposite in phase with
respect to the current supplied by the source.
● The A.H.C is sized only for harmonic currents
● The current consumed by the load is therefore:
I load = I source + I conditioner
II. Active harmonic conditioner: architecture &
design
Schneider Electric 18
34
The
harmonics are
eliminated
upstream and
apparent
power is
reduced
Active
conditioner
supplies the
required
harmonics to
the load
2
CTs analyze the
harmonics
required by the
load
=
-2
-1,5
-1
-0,5
0
0,5
1
1,5
2
I. sinusoidal
-2
-1,5
-1
-0,5
0
0,5
1
1,5
2
I. load
+
I. conditioner
-2
-1
-0,5
0
0,5
1
2
1,5
Equipment is the
source of
harmonics
1
II. Reducing upstream harmonic pollution
Schneider Electric 19
II. Sinewave standard solution: 20-480A of
harmonic compensation
● SineWave includes everything for a simple and functional basic solution:
- EMC filter to comply with EN55011 level A and IEC 1000-4
- 7-language user interface
- Diagnostic and maintenance menu
- Basic indications by 3 LEDs
- Relay contacts for remote indications
- Terminal blocks for power and sensor connections
- Wide choice of current transformers: split or closed
Schneider Electric 20
● Input
• Voltage : 400 V , - 20% , + 15%
• Phases : 3-phase with or without neutral. Compatible
Operation with single phase and unbalanced load
• Frequency : 50 Hz or 60 Hz, +/- 8% auto-sensing
● Compensation characteristics
• Harmonics covered : H 2 to H 25
• Type of compensation : Harmonics - cos phi - mixed (Hn + cos)
• Compensation mode : Overall or selective (specific harmonics)
• Attenuation ratio : >10 at full load ( THDI)
• Cos phi correction : Up to 1
• THDU reduction : According to the installation parameters, THDU
reduction will be determinated by the SITE AUDIT
• Response time : < 40 ms in overall current compensation mode
• Overload : Automatic current limitation
II. Sinewave features
Schneider Electric 21
-2
-1,5
-1
-0.5
0
0.5
1
1,5
2
-2
-1,5
-1
-0.5
0
0.5
1
2
1,5
I phase = 48 A
THDI = 81%
I neutral = 42 A
S = 10.6 kVA
Power factor = 0.77
Cos phi 1 = 0.99
Mains current without
active conditioner
Mains current with
active conditioner
I phase = 38A (-21%)
THDI (reduced by a factor of 24) = 3.4%
I neutral = 2.6 A
S = 8.4 kVA
Power factor = 1
Cos phi 1 = 1
II. Example: Variable Speed Drive load
Schneider Electric 22
THDI = 92.6%
PF = 0.73
2.9%
1.0
Reduction of 27% in the line RMS current
Harmonic current without SineWave Harmonic current with SineWave
0
20
40
60
80
100
120
H1
H3
H5
H7
H9
H11
H13
H15
H17
H19
H21
0
20
40
60
80
100
120
H1
H3
H5
H7
H9
H11
H13
H15
H17
H19
H21
Test Results of a 60 A Active Conditioner
II. Example: Variable Speed Drive load
Schneider Electric 23
● Robust design suitable for heavy industrial
applications
● IP54 protection enclosure is standard
● Full EMC compliance with 89/336EEC,
conforms to IEC/EN 60439-1, EN61000-6-4
class A, EN61000-6-2 standards
● Current output ratings of 50 A, 100 A or 300
A
● Can be paralleled up to 10 units in any rating
combination
● Ultra fast response time (1/2 cycle)
● Cancel harmonic up to 50th order
● ABS Certified for Marine applications
II. Accusine solution
Schneider Electric 24
● Input
• Voltage : 208-480V, - 10% , + 10%; auto sensing
• Phases : 3-phase, 3-wire with or without neutral.
Compatible Operation with single phase
and unbalanced load
• Frequency : 50 Hz or 60 Hz, +/- 5% auto-sensing
● Compensation characteristics
• Harmonics covered : H 2 to H 50 (no filtering on neutral conductor)
• Type of compensation : Harmonics - cos phi - mixed (Hn +
cos)
• Compensation mode : overall
• Attenuation ratio : 10:1 overall
• Cos phi correction : Up to unity; can also inject lagging
VARS
• THDU reduction : Guaranteed compliance with
IEEE519; UK G5/4 or
IEC 61000-2-3
• Response time : < 10 ms
• Overload : Automatic current limitation
II. Accusine features
Schneider Electric 25
●Safe and reliable AC electrical distribution systems
● Overloading and overheating of the neutral conductor cancelled
● Nuisance tripping of protection circuit breakers avoided
●Improved power quality
● Reduction of the THD(V)
● Cancellation of the voltage potential on the neutral conductor
●Increased lifetime of AC distribution system equipment
●Over-sizing cables, transformers and other AC distribution equipment
avoided
●Compliance of installations with harmonic standards ensured
●Improved power factor
●Lower energy expenses/bills
II. Customer benefits / active power solutions
Schneider Electric 26
I. Introduction
II. Harmonic mitigation solution
III.Case study
lV.Conclusion
Schneider Electric 27
●Oil platform in the North Sea with
turbine / diesel generators feeding 6 KV
network
● Mechanical resonance on the platform
when pump VFDs operated above 49 Hz
due to generator loading
● Each 1 Hz increment in pump speed
equals $6k/day incremental revenue per
pump (2003 prices)
●2 x 600 KW VFDs at 380V
● 300A AHF for each VFD
● Operating in harmonic + power factor
correction mode
● Increased pump speed by 1 Hz
III. Accusine application case study
Schneider Electric 28
Voltage waveform - AHF OFF
Voltage waveform - AHF ON
●THD(V) reduced from
12.6% to 6.0%
●Note high voltage
notching & distortion on
generator fed network
Current waveform - AHF OFF
Current waveform - AHF ON
●THD(I) reduced from
31.8% to 7.2%
●PF from 80.3% to
95.2%
III. Accusine application case study
Schneider Electric 29
I. Introduction
II. Harmonic mitigation solution
III.Case study
lV.Conclusion
Schneider Electric 30
lV. Conclusion
●Power quality issues are well worth some consideration,
●Even more so for Oil & Gas processes where the availability and quality
of Power is quite critical,
●Correct identification of the root causes of the problem is essential to
choosing and implementing the best solution right from the start => Talk
to the experts.
Schneider Electric 31
●Schneider Electric is your Power Quality expert
●We offer a variety of solutions and products to help identify and correct
power quality problems
●Investing in power quality will improve both your operations and profits
The 3 main messages

More Related Content

What's hot

Electrical grounding and earthing systems
Electrical grounding and earthing systemsElectrical grounding and earthing systems
Electrical grounding and earthing systems
Biswajit Pratihari
 
Fault Level Calculation
Fault Level CalculationFault Level Calculation
Fault Level Calculation
Dinesh Sarda
 

What's hot (20)

Power System Restoration Guide
Power System Restoration Guide  Power System Restoration Guide
Power System Restoration Guide
 
Power quality ppt
Power quality pptPower quality ppt
Power quality ppt
 
Switchyard
SwitchyardSwitchyard
Switchyard
 
Testing of circuit breakers
Testing of circuit breakersTesting of circuit breakers
Testing of circuit breakers
 
Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1
 
1. power system losses introduction
1. power system losses introduction1. power system losses introduction
1. power system losses introduction
 
Electrical grounding and earthing systems
Electrical grounding and earthing systemsElectrical grounding and earthing systems
Electrical grounding and earthing systems
 
Cloud computing for smart grid applications
Cloud computing for smart grid applicationsCloud computing for smart grid applications
Cloud computing for smart grid applications
 
Inplant training about 110kv/11kv substation
Inplant training about 110kv/11kv substationInplant training about 110kv/11kv substation
Inplant training about 110kv/11kv substation
 
Fault Level Calculation
Fault Level CalculationFault Level Calculation
Fault Level Calculation
 
Overload capacity of power transformers
Overload capacity of power transformersOverload capacity of power transformers
Overload capacity of power transformers
 
basics of busbar and lbb protection
basics of busbar and lbb protection basics of busbar and lbb protection
basics of busbar and lbb protection
 
Smart grid
Smart  gridSmart  grid
Smart grid
 
Minimizing losses in power distribution system
Minimizing losses in power distribution systemMinimizing losses in power distribution system
Minimizing losses in power distribution system
 
Economic dispatch
Economic dispatch  Economic dispatch
Economic dispatch
 
Cable Sizing Calculations
Cable Sizing CalculationsCable Sizing Calculations
Cable Sizing Calculations
 
Electrical energy meter
Electrical energy meterElectrical energy meter
Electrical energy meter
 
Protection and Switchgear
Protection and SwitchgearProtection and Switchgear
Protection and Switchgear
 
CT and VT.pptx
CT and VT.pptxCT and VT.pptx
CT and VT.pptx
 
Net metering ppt
Net metering pptNet metering ppt
Net metering ppt
 

Viewers also liked

Harmonics in power system
Harmonics in power systemHarmonics in power system
Harmonics in power system
Minh Anh Nguyen
 
harmonic distortion ppt
harmonic distortion pptharmonic distortion ppt
harmonic distortion ppt
Aditi Tiwari
 
Harmonic mitigating transformer
Harmonic mitigating transformerHarmonic mitigating transformer
Harmonic mitigating transformer
Biswajit Pratihari
 
power quality conditioners
power quality conditionerspower quality conditioners
power quality conditioners
mamodiya
 

Viewers also liked (20)

Hormonics impact and_mitigation
Hormonics impact and_mitigationHormonics impact and_mitigation
Hormonics impact and_mitigation
 
Ps harmonics
Ps harmonicsPs harmonics
Ps harmonics
 
Harmonics: Causes and Effects
Harmonics: Causes and EffectsHarmonics: Causes and Effects
Harmonics: Causes and Effects
 
Harmonics in power system
Harmonics in power systemHarmonics in power system
Harmonics in power system
 
Harmonics
HarmonicsHarmonics
Harmonics
 
Harmonics and mitigation techniques
Harmonics and mitigation techniquesHarmonics and mitigation techniques
Harmonics and mitigation techniques
 
Harmonics
HarmonicsHarmonics
Harmonics
 
harmonic distortion ppt
harmonic distortion pptharmonic distortion ppt
harmonic distortion ppt
 
POWER HARMONICS- SOURCES, ISSUES AND MITIGATION
POWER HARMONICS- SOURCES, ISSUES AND MITIGATIONPOWER HARMONICS- SOURCES, ISSUES AND MITIGATION
POWER HARMONICS- SOURCES, ISSUES AND MITIGATION
 
Power Quality
Power QualityPower Quality
Power Quality
 
Harmonic mitigating transformer
Harmonic mitigating transformerHarmonic mitigating transformer
Harmonic mitigating transformer
 
Harmonics: Causes, Effects and Minimization
Harmonics: Causes, Effects and MinimizationHarmonics: Causes, Effects and Minimization
Harmonics: Causes, Effects and Minimization
 
Harmonics
HarmonicsHarmonics
Harmonics
 
Harmonics In Transformer pdf
Harmonics In Transformer  pdfHarmonics In Transformer  pdf
Harmonics In Transformer pdf
 
Product: Power Factor & Harmonics: StacoSine: MGE filter presentation
Product: Power Factor & Harmonics: StacoSine: MGE filter presentationProduct: Power Factor & Harmonics: StacoSine: MGE filter presentation
Product: Power Factor & Harmonics: StacoSine: MGE filter presentation
 
Vivek harmonics
Vivek harmonicsVivek harmonics
Vivek harmonics
 
power quality conditioners
power quality conditionerspower quality conditioners
power quality conditioners
 
Transformer Harmonics
Transformer HarmonicsTransformer Harmonics
Transformer Harmonics
 
Introduction to Power Quality
Introduction to Power QualityIntroduction to Power Quality
Introduction to Power Quality
 
Active filters
Active filtersActive filters
Active filters
 

Similar to Harmonics mitigation solutions

Maximise Efficiency & Reliability - Maintain ‘healthy’ electrical network wit...
Maximise Efficiency & Reliability - Maintain ‘healthy’ electrical network wit...Maximise Efficiency & Reliability - Maintain ‘healthy’ electrical network wit...
Maximise Efficiency & Reliability - Maintain ‘healthy’ electrical network wit...
Eng Yong CH'NG, CEng MEI, CEM, CMVP, PEM
 
Advanced motion controls b30a40ac
Advanced motion controls b30a40acAdvanced motion controls b30a40ac
Advanced motion controls b30a40ac
Electromate
 
Advanced motion controls b100a40ac
Advanced motion controls b100a40acAdvanced motion controls b100a40ac
Advanced motion controls b100a40ac
Electromate
 
Advanced motion controls b60a40ac
Advanced motion controls b60a40acAdvanced motion controls b60a40ac
Advanced motion controls b60a40ac
Electromate
 
Advanced motion controls b100a20
Advanced motion controls b100a20Advanced motion controls b100a20
Advanced motion controls b100a20
Electromate
 
Advanced motion controls b100a40
Advanced motion controls b100a40Advanced motion controls b100a40
Advanced motion controls b100a40
Electromate
 
Ac Power Problems And Measurement Sreevidhya@Students
Ac Power Problems And Measurement Sreevidhya@StudentsAc Power Problems And Measurement Sreevidhya@Students
Ac Power Problems And Measurement Sreevidhya@Students
B Bhargav Reddy
 
Advanced motion controls be25a20
Advanced motion controls be25a20Advanced motion controls be25a20
Advanced motion controls be25a20
Electromate
 
Advanced motion controls be40a20
Advanced motion controls be40a20Advanced motion controls be40a20
Advanced motion controls be40a20
Electromate
 
Advanced motions control 16a20ac
Advanced motions control 16a20acAdvanced motions control 16a20ac
Advanced motions control 16a20ac
Electromate
 
Advanced motion controls b40a40ac
Advanced motion controls b40a40acAdvanced motion controls b40a40ac
Advanced motion controls b40a40ac
Electromate
 

Similar to Harmonics mitigation solutions (20)

Maximise Efficiency & Reliability - Maintain ‘healthy’ electrical network wit...
Maximise Efficiency & Reliability - Maintain ‘healthy’ electrical network wit...Maximise Efficiency & Reliability - Maintain ‘healthy’ electrical network wit...
Maximise Efficiency & Reliability - Maintain ‘healthy’ electrical network wit...
 
Advanced motion controls b30a40ac
Advanced motion controls b30a40acAdvanced motion controls b30a40ac
Advanced motion controls b30a40ac
 
Advanced motion controls b100a40ac
Advanced motion controls b100a40acAdvanced motion controls b100a40ac
Advanced motion controls b100a40ac
 
Advanced motion controls b40a40
Advanced motion controls b40a40Advanced motion controls b40a40
Advanced motion controls b40a40
 
Advanced motion controls b30a40
Advanced motion controls b30a40Advanced motion controls b30a40
Advanced motion controls b30a40
 
Advanced motion controls b60a40ac
Advanced motion controls b60a40acAdvanced motion controls b60a40ac
Advanced motion controls b60a40ac
 
Webinar Slides: Measurements and Analysis for Switched-mode Power Designs
Webinar Slides: Measurements and Analysis for Switched-mode Power DesignsWebinar Slides: Measurements and Analysis for Switched-mode Power Designs
Webinar Slides: Measurements and Analysis for Switched-mode Power Designs
 
EMI Surge Protection Circuit Analysis
EMI Surge Protection Circuit AnalysisEMI Surge Protection Circuit Analysis
EMI Surge Protection Circuit Analysis
 
Advanced motion controls b100a20
Advanced motion controls b100a20Advanced motion controls b100a20
Advanced motion controls b100a20
 
AD654 DataSheet - (ic-component.com)
AD654 DataSheet - (ic-component.com)AD654 DataSheet - (ic-component.com)
AD654 DataSheet - (ic-component.com)
 
LTC1540 Ultra-Low Power Comparator
LTC1540 Ultra-Low Power ComparatorLTC1540 Ultra-Low Power Comparator
LTC1540 Ultra-Low Power Comparator
 
Advanced motion controls b100a40
Advanced motion controls b100a40Advanced motion controls b100a40
Advanced motion controls b100a40
 
RF Module Design - [Chapter 6] Power Amplifier
RF Module Design - [Chapter 6]  Power AmplifierRF Module Design - [Chapter 6]  Power Amplifier
RF Module Design - [Chapter 6] Power Amplifier
 
Ac Power Problems And Measurement Sreevidhya@Students
Ac Power Problems And Measurement Sreevidhya@StudentsAc Power Problems And Measurement Sreevidhya@Students
Ac Power Problems And Measurement Sreevidhya@Students
 
Advanced motion controls be25a20
Advanced motion controls be25a20Advanced motion controls be25a20
Advanced motion controls be25a20
 
Advanced motion controls 25a20
Advanced motion controls 25a20Advanced motion controls 25a20
Advanced motion controls 25a20
 
Advanced motion controls 50a20
Advanced motion controls 50a20Advanced motion controls 50a20
Advanced motion controls 50a20
 
Advanced motion controls be40a20
Advanced motion controls be40a20Advanced motion controls be40a20
Advanced motion controls be40a20
 
Advanced motions control 16a20ac
Advanced motions control 16a20acAdvanced motions control 16a20ac
Advanced motions control 16a20ac
 
Advanced motion controls b40a40ac
Advanced motion controls b40a40acAdvanced motion controls b40a40ac
Advanced motion controls b40a40ac
 

More from Fahad Shaikh (13)

Renewable energy sources
Renewable energy sourcesRenewable energy sources
Renewable energy sources
 
Reproduction (life of cycle)
Reproduction (life of cycle)Reproduction (life of cycle)
Reproduction (life of cycle)
 
Propogation of light
Propogation of lightPropogation of light
Propogation of light
 
What is nfc (4)
What is nfc (4)What is nfc (4)
What is nfc (4)
 
Magnetic levitation(5)
Magnetic levitation(5)Magnetic levitation(5)
Magnetic levitation(5)
 
Hts cable (6)
Hts cable (6)Hts cable (6)
Hts cable (6)
 
Gps mobile based human position (2)
Gps mobile based human position (2)Gps mobile based human position (2)
Gps mobile based human position (2)
 
What is nfc (3)
What is nfc  (3)What is nfc  (3)
What is nfc (3)
 
Harmonics
HarmonicsHarmonics
Harmonics
 
Gil
GilGil
Gil
 
Structure of an atom new
Structure of an atom newStructure of an atom new
Structure of an atom new
 
Industrial health and safety seminar
Industrial health and safety seminarIndustrial health and safety seminar
Industrial health and safety seminar
 
Hydro p-s
Hydro p-sHydro p-s
Hydro p-s
 

Recently uploaded

Recently uploaded (20)

Mehran University Newsletter Vol-X, Issue-I, 2024
Mehran University Newsletter Vol-X, Issue-I, 2024Mehran University Newsletter Vol-X, Issue-I, 2024
Mehran University Newsletter Vol-X, Issue-I, 2024
 
Unit 3 Emotional Intelligence and Spiritual Intelligence.pdf
Unit 3 Emotional Intelligence and Spiritual Intelligence.pdfUnit 3 Emotional Intelligence and Spiritual Intelligence.pdf
Unit 3 Emotional Intelligence and Spiritual Intelligence.pdf
 
Sociology 101 Demonstration of Learning Exhibit
Sociology 101 Demonstration of Learning ExhibitSociology 101 Demonstration of Learning Exhibit
Sociology 101 Demonstration of Learning Exhibit
 
Python Notes for mca i year students osmania university.docx
Python Notes for mca i year students osmania university.docxPython Notes for mca i year students osmania university.docx
Python Notes for mca i year students osmania university.docx
 
COMMUNICATING NEGATIVE NEWS - APPROACHES .pptx
COMMUNICATING NEGATIVE NEWS - APPROACHES .pptxCOMMUNICATING NEGATIVE NEWS - APPROACHES .pptx
COMMUNICATING NEGATIVE NEWS - APPROACHES .pptx
 
Graduate Outcomes Presentation Slides - English
Graduate Outcomes Presentation Slides - EnglishGraduate Outcomes Presentation Slides - English
Graduate Outcomes Presentation Slides - English
 
SOC 101 Demonstration of Learning Presentation
SOC 101 Demonstration of Learning PresentationSOC 101 Demonstration of Learning Presentation
SOC 101 Demonstration of Learning Presentation
 
Key note speaker Neum_Admir Softic_ENG.pdf
Key note speaker Neum_Admir Softic_ENG.pdfKey note speaker Neum_Admir Softic_ENG.pdf
Key note speaker Neum_Admir Softic_ENG.pdf
 
Kodo Millet PPT made by Ghanshyam bairwa college of Agriculture kumher bhara...
Kodo Millet  PPT made by Ghanshyam bairwa college of Agriculture kumher bhara...Kodo Millet  PPT made by Ghanshyam bairwa college of Agriculture kumher bhara...
Kodo Millet PPT made by Ghanshyam bairwa college of Agriculture kumher bhara...
 
Fostering Friendships - Enhancing Social Bonds in the Classroom
Fostering Friendships - Enhancing Social Bonds  in the ClassroomFostering Friendships - Enhancing Social Bonds  in the Classroom
Fostering Friendships - Enhancing Social Bonds in the Classroom
 
Beyond_Borders_Understanding_Anime_and_Manga_Fandom_A_Comprehensive_Audience_...
Beyond_Borders_Understanding_Anime_and_Manga_Fandom_A_Comprehensive_Audience_...Beyond_Borders_Understanding_Anime_and_Manga_Fandom_A_Comprehensive_Audience_...
Beyond_Borders_Understanding_Anime_and_Manga_Fandom_A_Comprehensive_Audience_...
 
On_Translating_a_Tamil_Poem_by_A_K_Ramanujan.pptx
On_Translating_a_Tamil_Poem_by_A_K_Ramanujan.pptxOn_Translating_a_Tamil_Poem_by_A_K_Ramanujan.pptx
On_Translating_a_Tamil_Poem_by_A_K_Ramanujan.pptx
 
On National Teacher Day, meet the 2024-25 Kenan Fellows
On National Teacher Day, meet the 2024-25 Kenan FellowsOn National Teacher Day, meet the 2024-25 Kenan Fellows
On National Teacher Day, meet the 2024-25 Kenan Fellows
 
80 ĐỀ THI THỬ TUYỂN SINH TIẾNG ANH VÀO 10 SỞ GD – ĐT THÀNH PHỐ HỒ CHÍ MINH NĂ...
80 ĐỀ THI THỬ TUYỂN SINH TIẾNG ANH VÀO 10 SỞ GD – ĐT THÀNH PHỐ HỒ CHÍ MINH NĂ...80 ĐỀ THI THỬ TUYỂN SINH TIẾNG ANH VÀO 10 SỞ GD – ĐT THÀNH PHỐ HỒ CHÍ MINH NĂ...
80 ĐỀ THI THỬ TUYỂN SINH TIẾNG ANH VÀO 10 SỞ GD – ĐT THÀNH PHỐ HỒ CHÍ MINH NĂ...
 
Wellbeing inclusion and digital dystopias.pptx
Wellbeing inclusion and digital dystopias.pptxWellbeing inclusion and digital dystopias.pptx
Wellbeing inclusion and digital dystopias.pptx
 
How to setup Pycharm environment for Odoo 17.pptx
How to setup Pycharm environment for Odoo 17.pptxHow to setup Pycharm environment for Odoo 17.pptx
How to setup Pycharm environment for Odoo 17.pptx
 
ICT role in 21st century education and it's challenges.
ICT role in 21st century education and it's challenges.ICT role in 21st century education and it's challenges.
ICT role in 21st century education and it's challenges.
 
2024-NATIONAL-LEARNING-CAMP-AND-OTHER.pptx
2024-NATIONAL-LEARNING-CAMP-AND-OTHER.pptx2024-NATIONAL-LEARNING-CAMP-AND-OTHER.pptx
2024-NATIONAL-LEARNING-CAMP-AND-OTHER.pptx
 
NO1 Top Black Magic Specialist In Lahore Black magic In Pakistan Kala Ilam Ex...
NO1 Top Black Magic Specialist In Lahore Black magic In Pakistan Kala Ilam Ex...NO1 Top Black Magic Specialist In Lahore Black magic In Pakistan Kala Ilam Ex...
NO1 Top Black Magic Specialist In Lahore Black magic In Pakistan Kala Ilam Ex...
 
Towards a code of practice for AI in AT.pptx
Towards a code of practice for AI in AT.pptxTowards a code of practice for AI in AT.pptx
Towards a code of practice for AI in AT.pptx
 

Harmonics mitigation solutions

  • 2. Schneider Electric 2 I. Introduction II. Harmonics mitigation solution III.Case study lV.Conclusion Summary
  • 3. Schneider Electric 3 I. Introduction II. Harmonic mitigation solution III.Case study lV.Conclusion
  • 4. Schneider Electric 4 I. Introduction ●The quality of electrical power is determined by the voltage ● High-quality voltage is the best guarantee for continuous operation of equipment The voltage signal must be perfect at the source... ... because distortion may occur at the end of the line Line impedance Type of installation Length of cables Internal impedance of equipment... The harmonic current from the load Type of load Power supply technology
  • 5. Schneider Electric 5 I. Introduction II. Harmonic mitigation solution III.Case study lV.Conclusion
  • 6. Schneider Electric 6 -1.5 -1 -0.5 0 0.5 1 1.5 = -1.5 -1 -0.5 0 0.5 1 1.5 + -1.5 -1 -0.5 0 0.5 1 1.5 Signal with harmonics Fundamental H1 Harmonics H2 to Hn H1 = 50Hz Hn = n x 50Hz THD (U or I) % = 100 x II. What is a harmonic waveform? ●Harmonic waveform is a distortion of the normal Sinewave ●It is characterized by its distortion level ● For voltage (THD U - Total Harmonic Voltage Distortion) ● For current (THD I - Total Harmonic Current Distortion)
  • 7. Schneider Electric 7 ●Waveform examples and harmonic spectrum ● Three- phase loads Variable speed drive Lifts… ● Single-phase loads ● Computers ● Phones ● Lighting ... II. Current distortion H11 H13 H17 H19 H21 H23 0 50 100 H1 H5 H7 Danger H7 H9 H11 H13 H15 0 50 H1 H3 H5 Danger H17 100
  • 8. Schneider Electric 8 II. The effects of harmonics ●Voltage distortion: ● Excessive temperature rise in motors ● Electrical noises ● Sensitive electronic equipment malfunction ●Increase in the apparent power and over-sizing of sources (UPS, Genset, etc.), capacitors, cables... ● Derating of electrical equipment or over-sizing ● Accelerated ageing of equipment ●Flow of current in the neutral conductor and consequently in the PEN: ● Excessive temperature rise in transformer ● Tripping of circuit breakers
  • 9. Schneider Electric 9 II. The effects of harmonics M M M Final distribution enclosure feeder S1 feeder S2 feeder S3 Secondary switchboard Main LV Switchboard (MLVS) feeder MS1 feeder MS2 feeder MSn LV Increased THDU Increased RMS current Non-linear current circulating in the cables ●Voltage distortion: influence of THDI on the THDU
  • 10. Schneider Electric 10 > Linear load without harmonics: • Cos phi = Power factor = P/S > Non-linear load : • DPF = Displacement Power Factor - P1/S1 ( 50 Hz fundamental current only) • True Power factor = P/ST > S = apparent powerP (W) Q (var)φ S (VA) ST (VA) D harmonic P2 + Q2S = P2 + Q2 + D2S = II. The effects of harmonics ●Increase in the apparent power and over-sizing of sources
  • 11. Schneider Electric 11 -6 -4 -2 0 2 0 90 180 270 360 450 Phase 1 Phase 2 Phase 3 3rd Harmonic, phase 1 3rd Harmonic, phase 2 3rd Harmonic, phase 3 Total 3rd Harmonic ●Flow of current in the neutral conductor ● The H3 harmonic currents and multiples flow in the neutral conductor. ● The cross-sectional area of the neutral conductor must be increased (1.7 times that of the phases for switch-mode power supplies). I3,I9,I15 II. The effects of harmonics
  • 12. Schneider Electric 12 Normal or replacement sources Over-sizing of sources, cables, etc. Transformers with different couplings Tuned filters Anti-harm. reactors & series filters LD y Y y p1 = p2 p1 = p2 h5 h7 F - The harmonics are not eliminated. - Very costly 2 Limits h3 and multiples. D d y 3 4 5 6 1 D yn h3 h9 2 h7 (6-pulse bridge) 5 6 Attenuates harmonics at the tuning frequency. Decreases THD(i). 1 3 4and attenuate h5 and II. Harmonics mitigation solutions ●Electromechanical solutions ●Active filters
  • 13. Schneider Electric 13 LoadMains Filter No capacitors No power electronics No batteries No micro controllers Unmatched reliability, same as that of a dry transformer II. Passive filter: architecture & design ●3-phase + neutral filter ●Composed of only two elements ● 1 serial three-phase inductance ● 1 parallel three-phase inductance Ph N Lo Zo
  • 14. Schneider Electric 14 input output ●At A Glance: ● Zero sequence harmonic filter ● Reduces neutral currents in commercial & industrial buildings ● Balancing of 3-phase currents ● 12-280 kVA (expandable) ● 3-phase low voltage applications ●Customer benefits ● Simple and highly reliable design ● Reduction of neutral currents by 10:1 ● Compliance with harmonic standards ● Capacity upgrade by parallel connection ● Operational savings ● Easy integration into power distribution cabinets (Chassis Format) ● Easy sizing and installer friendly II. Cleanwave: solution for neutral currents
  • 15. Schneider Electric 15 II. Sizing cleanwave ●CleanWave is designed for the most demanding situations ● H3 harmonics and multiple: THDI up to 80% ● Neutral current = 1.8 times phase current ●Very easy sizing Max power or max. Iphase of the load Selection of the filter of immediately higher power or current 25 kVA load Selection of the 30 kVA CleanWave
  • 16. Schneider Electric 16 II. Unbalanced load tests Balanced Without Ph3 Without Ph2 & 3 I1 in In in I1 out In out I1 in In in I1 out In out I1 in In in I1 out In out I1: 150A I2: 149A I3: 151A In: 21A I1: 126A I2: 126A I3: 127A In: 242A I1: 126A I2: 126A I3: 0A In: 201A I1: 112A I2: 122A I3: 65A In: 25A I1: 107A I2: 46A I3: 46A In: 25A I1: 154A I2: 0A I3: 0A In: 150A Input: In = 21 A Output: In = 242 A Input: In = 25 A Output: In = 201 A Input: In = 25 A Output: In = 150 A 1mv=1 A 1mv=1 A1mv=1 A
  • 17. Schneider Electric 17 I source I load Power source Non-linear load Active harmonic conditioner I conditioner ● The active harmonic conditioner generates the harmonic currents required by non-linear loads. These currents are opposite in phase with respect to the current supplied by the source. ● The A.H.C is sized only for harmonic currents ● The current consumed by the load is therefore: I load = I source + I conditioner II. Active harmonic conditioner: architecture & design
  • 18. Schneider Electric 18 34 The harmonics are eliminated upstream and apparent power is reduced Active conditioner supplies the required harmonics to the load 2 CTs analyze the harmonics required by the load = -2 -1,5 -1 -0,5 0 0,5 1 1,5 2 I. sinusoidal -2 -1,5 -1 -0,5 0 0,5 1 1,5 2 I. load + I. conditioner -2 -1 -0,5 0 0,5 1 2 1,5 Equipment is the source of harmonics 1 II. Reducing upstream harmonic pollution
  • 19. Schneider Electric 19 II. Sinewave standard solution: 20-480A of harmonic compensation ● SineWave includes everything for a simple and functional basic solution: - EMC filter to comply with EN55011 level A and IEC 1000-4 - 7-language user interface - Diagnostic and maintenance menu - Basic indications by 3 LEDs - Relay contacts for remote indications - Terminal blocks for power and sensor connections - Wide choice of current transformers: split or closed
  • 20. Schneider Electric 20 ● Input • Voltage : 400 V , - 20% , + 15% • Phases : 3-phase with or without neutral. Compatible Operation with single phase and unbalanced load • Frequency : 50 Hz or 60 Hz, +/- 8% auto-sensing ● Compensation characteristics • Harmonics covered : H 2 to H 25 • Type of compensation : Harmonics - cos phi - mixed (Hn + cos) • Compensation mode : Overall or selective (specific harmonics) • Attenuation ratio : >10 at full load ( THDI) • Cos phi correction : Up to 1 • THDU reduction : According to the installation parameters, THDU reduction will be determinated by the SITE AUDIT • Response time : < 40 ms in overall current compensation mode • Overload : Automatic current limitation II. Sinewave features
  • 21. Schneider Electric 21 -2 -1,5 -1 -0.5 0 0.5 1 1,5 2 -2 -1,5 -1 -0.5 0 0.5 1 2 1,5 I phase = 48 A THDI = 81% I neutral = 42 A S = 10.6 kVA Power factor = 0.77 Cos phi 1 = 0.99 Mains current without active conditioner Mains current with active conditioner I phase = 38A (-21%) THDI (reduced by a factor of 24) = 3.4% I neutral = 2.6 A S = 8.4 kVA Power factor = 1 Cos phi 1 = 1 II. Example: Variable Speed Drive load
  • 22. Schneider Electric 22 THDI = 92.6% PF = 0.73 2.9% 1.0 Reduction of 27% in the line RMS current Harmonic current without SineWave Harmonic current with SineWave 0 20 40 60 80 100 120 H1 H3 H5 H7 H9 H11 H13 H15 H17 H19 H21 0 20 40 60 80 100 120 H1 H3 H5 H7 H9 H11 H13 H15 H17 H19 H21 Test Results of a 60 A Active Conditioner II. Example: Variable Speed Drive load
  • 23. Schneider Electric 23 ● Robust design suitable for heavy industrial applications ● IP54 protection enclosure is standard ● Full EMC compliance with 89/336EEC, conforms to IEC/EN 60439-1, EN61000-6-4 class A, EN61000-6-2 standards ● Current output ratings of 50 A, 100 A or 300 A ● Can be paralleled up to 10 units in any rating combination ● Ultra fast response time (1/2 cycle) ● Cancel harmonic up to 50th order ● ABS Certified for Marine applications II. Accusine solution
  • 24. Schneider Electric 24 ● Input • Voltage : 208-480V, - 10% , + 10%; auto sensing • Phases : 3-phase, 3-wire with or without neutral. Compatible Operation with single phase and unbalanced load • Frequency : 50 Hz or 60 Hz, +/- 5% auto-sensing ● Compensation characteristics • Harmonics covered : H 2 to H 50 (no filtering on neutral conductor) • Type of compensation : Harmonics - cos phi - mixed (Hn + cos) • Compensation mode : overall • Attenuation ratio : 10:1 overall • Cos phi correction : Up to unity; can also inject lagging VARS • THDU reduction : Guaranteed compliance with IEEE519; UK G5/4 or IEC 61000-2-3 • Response time : < 10 ms • Overload : Automatic current limitation II. Accusine features
  • 25. Schneider Electric 25 ●Safe and reliable AC electrical distribution systems ● Overloading and overheating of the neutral conductor cancelled ● Nuisance tripping of protection circuit breakers avoided ●Improved power quality ● Reduction of the THD(V) ● Cancellation of the voltage potential on the neutral conductor ●Increased lifetime of AC distribution system equipment ●Over-sizing cables, transformers and other AC distribution equipment avoided ●Compliance of installations with harmonic standards ensured ●Improved power factor ●Lower energy expenses/bills II. Customer benefits / active power solutions
  • 26. Schneider Electric 26 I. Introduction II. Harmonic mitigation solution III.Case study lV.Conclusion
  • 27. Schneider Electric 27 ●Oil platform in the North Sea with turbine / diesel generators feeding 6 KV network ● Mechanical resonance on the platform when pump VFDs operated above 49 Hz due to generator loading ● Each 1 Hz increment in pump speed equals $6k/day incremental revenue per pump (2003 prices) ●2 x 600 KW VFDs at 380V ● 300A AHF for each VFD ● Operating in harmonic + power factor correction mode ● Increased pump speed by 1 Hz III. Accusine application case study
  • 28. Schneider Electric 28 Voltage waveform - AHF OFF Voltage waveform - AHF ON ●THD(V) reduced from 12.6% to 6.0% ●Note high voltage notching & distortion on generator fed network Current waveform - AHF OFF Current waveform - AHF ON ●THD(I) reduced from 31.8% to 7.2% ●PF from 80.3% to 95.2% III. Accusine application case study
  • 29. Schneider Electric 29 I. Introduction II. Harmonic mitigation solution III.Case study lV.Conclusion
  • 30. Schneider Electric 30 lV. Conclusion ●Power quality issues are well worth some consideration, ●Even more so for Oil & Gas processes where the availability and quality of Power is quite critical, ●Correct identification of the root causes of the problem is essential to choosing and implementing the best solution right from the start => Talk to the experts.
  • 31. Schneider Electric 31 ●Schneider Electric is your Power Quality expert ●We offer a variety of solutions and products to help identify and correct power quality problems ●Investing in power quality will improve both your operations and profits The 3 main messages