Transformers for Electric Arc-Melting Furnaces with Direct Voltage Regulation

In modern metallurgical and chemical industry there is an increasing need for electric arc-melting furnaces. Transformer is also one of the vital parts by which power is supplied to furnaces. Because of their technological aspects, Electric arcmelting furnaces, need special transformers different from usual distribution units. The main problem arises from the demand for relatively wide range of regulation on the low voltage side. In this article one of the many principles of voltage regulation is described, nomely, low voltage regulation by means of magnetic flux variations.

90 ELEKTROTEHNISKI VESTNIK 1982 - št. 2
Transformatorji za električne obločne peči
z direktno regulacijo napetosti
Jusuf Ikanovic, Ljubljana
UDK 621.314:669,041
Transformers for Electric Arc-Melting Furnaces with
Direct Voltage Regulation
In modern metallurgical and chemical industry there is an
increasing need for electric arc-melting furnaces. Transformer
is also one of the vital parts by which power is supplied to fur-
naces. Because of their technological aspects, Electric arc-
melting furnaces, need special transformers different from
usual distribution units. The main problem arises from the de-
mand for relatively wide range of regulation on the low volta-
ge side.
In this article one of the many principles of voltage
regulation is described, nomely, low voltage regulation by
means of magnetic flux variations.
V sodobni metalurški in kemični industriji naraščajo potre-
be po električnih obločnih pečeh. Sestavni del celotnega siste-
ma je tudi transformator, preko katerega se peč napaja. Obloč­
ne peči s svojimi specifičnimi tehnološkimi zahtevami nareku-
jejo izdelavo specialnih transformatorjev, ki se v marsičem
razlikujejo od običajnih distribucijskih enot. Poglavitni
problemi pri vseh teh enotah izvirajo iz zahteve po razmeroma
širokem območju regulacije na nizkonapetostni strani
transformatorja. Članek obravnava problematiko enega od
več možnih načinov regulacije napetosti, tj. regulacijo sekun-
darne napetosti s spreminjanjem magnetnega pretoka.
Uvod
Transformatorji za električne obločne peči ima-
jo naslednje značilnosti in posebnosti:
a) nizke sekundarne napetosti (do nekaj 100 V)
in v odvisnosti od moči izredno velike sekundarne
toke;
b) široko območje regulacije sekundarne nape-
tosti;
c) v večini primerov se napetost regulira pod
obremenitvijo;
d) zaradi pogostih kratkih stikov v peči je
transformator podvržen velikim elektrodinamič-
nim silam; ·
e) v transformatorju se pojavljajo prenapetosti,
ki so posledica posebnih karakteristik bremena;
f) naravno hlajenje ni več primerno in ·se že
manjše enote hladijo s prisilnim obtokom, veči­
noma vode in olja.
Zaradi preobširnosti nakazane problematike se
bomo omejili samo na probleme, ki izhajajo iz
prvih treh točk, to so problemi regulacije sekun-
darne napetosti. V svetu je· uveljavljenih več
možnih načinov regulacije. Izbira načina je odvis-
na predvsem od moči transformatorja in pa od
zahtev po območju in načinu regulacije sekundar-
ne napetosti. Pri vsem tem moramo hkrati iskati
najbolj gospodarno varianto, ki bo zahtevala naj-
manj vgrajenega materiala. Za transformatorje do
10 MVA nazivne moči je najprimernejša t.i. di-
rektna regulacija napetosti, oziroma regulacija
·napetosti s spreminjanjem magnetnega pretoka.
Pod tem imenom jo pogosto zasledimo v tuji stro-
kovni literaturi, kar je nekako bliže fizikalnim do-
Uredništvo je prejelo članek 1982-02-10
gajanjem v transformatorju v procesu regulacije
sekundarne napetosti. Napišimo eno izmed osnov-
nih enačb transformatorja v praznem teku
u2 N2
NI
V principu napetost
transformatorja lahko
ali N1.
U2 na sekundarni strani
spreminjamo z U~> N2
Napetost U1 je napajalna - omrežna napetost
transformatorja in je v normalnem obratovanju ni
možno spreminjati. _
Najbolj logično bi bilo, če bi napetost U2 spre-
minjali na nizkonapetostni strani, spreminjajoč
število nizkonapetostnih ovojev N2, vendar tudi tu
obstajajo določeni, predvsem tehnološki problemi.
Število ovojev na nizkonapetostni strani je že pri
transformatorjih srednjih moči tako majhno, da bi
bila regulacija le-teh pregroba, pri transformator-
jih večjih moči pa sploh neizvedljiva. V posamez-
nih primerih je število ovojev N2 = 2 ali pa celo
N2 = 1 ovoj.
Regulacija napetosti U2 s pomočjo U1 in N2 je
sicer izvedljiva, vendar samo z uporabo dodatnega
regulacijskega transformatorja, kar pa bistveno
podraži celotno izvedbo.
Ostane nam še tretja možnost, to je regulacija
sekundarne napetosti u2 s pomočjo spreminjanja
števila ovojev N 1 .na primarni strani transfor-
matorja. Tako regulacijo imenujemo direktna
regulacija napetosti ali regulacija napetosti s spre-
minjanjem magnetnega pretoka.
1
U2 = k! 1G = k2 U0 v = k3 <f>
<P - magnetni pretok
k3 = 4,44/N2 - konstanta
Najpogosteje je v uporabi regulacijska shema, ki
jo kaže slika l. ·
VN GR FR
Sl. l. Osnovna ~hema regulacije napetosti
VN - Visokonapetostno navitje
GR - Grobo regulacijsko navitje
FR - Fino regulacijsko navitje
NN - Nizkonapetostno navitje
)
•
ELEKTROTEHNISKI VESTNIK 1982 - št. 2 91
V nadaljnjem bomo skušali ugotoviti, kako se
spreminjajo osnovni parametri transformatorja, če
reguliramo sekundarno napetost s spreminjanjem
magnetnega pretoka, in sicer:
l. tipska moč,
2. izgube v železu,
3. izgube v bakru in
4. kratkostična napetost.
l. Tipska moč
1.1. Predpostavimo, da želimo regulirati sekun-
darno napetost v mejah od u2min do u2maks maks
ob konstantnem sekundarnem toku / 2. Pri tem za
primarno stran veljajo naslednja razmerja:
Ut N2
Nt maks= -U N2 /!maks=~ / 2
2 min 1min
Ut N 2
Nl noin = u - N2 /!min = -N / 2
2maks !maks
Posamezne moči, za katere moramo dimenzioni-
rati sekundarno in primarano navitje, so:
p2 = u 2maks /2
P1 = P2 [ 1 + ~ ( J2::s-~2:::J]
Razmerje x U2maks 1. l · b-U- - predstav Ja re atiVno o -
2 min
močje regulacije sekundarne napetosti. V večini
primerov se vrednost x giblje med 1,5 in 3.
Moč, za katero moramo dimenzionirati transfor-
mator, imenujemo podobno kot pri avtotransfor-
matorjih tipska moč.
ptip = ~ p2 [ 2 + ~ (x-~) ] (1,1)
Relativno območje regulacije x in tipska moč
Ptip v grobem karakterizirata vsak oblačni
transformator.
Primer: Vzemimo enofazni transformator, ki mu
na sekundarni strani želimo regulirati napetost od
u2 = 200 - 600 v, pri konstantnem sekundarnem
toku / 2 = 30 kA.
x = 3
P2 = Pn = 18MVA
P1 = 18 [ 1 + ~ ( 3 - ~) J
9 __~!!_ = 30 MVA3
1,6 7
7
18 - = 42 MVA3
Iz tega izhaja, da moramo projektirati transfor-
mator za približno 70 % večjo moč, kot je njegova
nazivna moč. V primerjavi s podobnim neregulacij-
skim bo obločni _...transformator za isto moč večji,
težji in s tem tudi dražji.
1.2. Do se_daj smo obravnavali primer regulacije
napetosti U2 pri konstantnem toku / 2. Sodobnejši
PIP", It/Itn• lilzn
f,O
0,9
0,8
0,7
0,6
0,5
/
1602
/
~·vr--
./ '"'y 1'--r-.......
Ut=konst
1
Sl. 2. Potek tokov in moči
lt,P
-·-.... Iz
Uz
metalurški in kemični procesi pa zahtevajo od
transformatorja široko območje regulacije napeto-
sti u2 in v določenem ciklu spreminjanje sekun-
darnega toka / 2 ter ohranjeno ali pa reducirano
moč. Najpogostejši delovni proces obločne peči,
s tem pa tudi transformatorja, poteka po diagramu
na sl. 2.
Tipska moč je v tem primeru enaka
1 ( U2maks)
Ptip = 2 ltmaks U1 x + /2maks U2n-----u;;-
= ~ pn (x+ U~::ks) (1,2)
Dejanska tipska moč je še nekoliko večja, kot je
po enačbah 1,1 in 1,2 določeno, to pa zaradi regula-
cijskih navitij, ki jih je potrebno še dodatno izoli-
rati. To povečanje tipske moči je pogosto potrebno
upoštevati, zlasti pri transformatorjih z višjo stop-
njo izolacije.
2. Izgube v železu
Tipske izgube v železu so definirane pri maksi-
malni ovojni napetosti, to je pri največji napetosti
na sekundarni strani transformatorja. Gostota
magnetnega pretoka se spreminja sorazmerno z
ovojno napetostjo
B B Uov u2
Bmaks Btip uovmaks U2maks'
izgube v železu pa še v odvisnosti od magnetnih
lastnosti uporabljene železne pločevine ter od kon-
strukcije jedra transformatorja. Nelinearnost po-
teka izgub bomo upoštevali z dodatnim faktorjem
c
P Fe = ~ = C' ___!!____ = C ____!!__!__
PFetip PFemaks Bmaks u 2maks
Na sliki 3 je narisan potek izgub v železu pri
Bmaks- 1,735 T za magnetno pločevino M 5.
Če krivulje magnetenja ne poznamo, zadošča za
bolj grobe izračune, če izgube v železu določimo
po poenostavljeni enačbi
:::ip ~ (B~aksy ~ ( U~:aksy
92 ELEKTROTEHNIŠKI VESTNIK 1982 - št. 2
uk;uktip• ~e/~etip • PcuiPcutip
1,3
~
1,1 ~
~
!'----.
V'~ '~
/
~e-
9
-...-- ~ /r-...
O,
""'
'X
/ ~"-........_
Pcu-
/ ~
Pcu2
....___
uk-
-.x
-------- ./' ~
0,7
0,5
' Pcu1 v 1-' _./
"~ :::::::-v -- Pcu1
f-
--Pcu2
0,3
U2
0,1
U2n U2maks
Sl. 3. Potek karakterističnih veličin
3. Izgube v bakru
Izgube v bakru se bodo spreminjale po celotnem
območju regulacije od u2 min do u 2 makS> v odvisno-
sti od / 2 in števila vklopljenih ovojev N1• Zaradi
enostavnosti izračuna predpostavimo, da imajo vsi
ovoji reguliranega navitja enak prerez ter da so
izgube v primarnem in sekundarnem navitju
' enake. V praksi je to v večini primerov približno
izpolnjeno. Izgube v bakru pri sekundarni napeto-
sti u 2 = u 2 n so maksimalne in jih imenujemo tip-
ske izgube:
p cu U2n = P culip
1
P cutipl = P cutip2 = 2 p cutip
Tipske izgube v bakru so približno enake izgu-
bam podobnega distribucijskega transformatorja,
katerega nazivna moč je enaka tipski moči oblač­
nega transformatorja, določeni po enačbi 1,1 in 1,2.
Glede na potek moči in tokov v diagramu sl. 2 se
izgube v bakru ne spreminjajo zvezno po vsem
območju regulacije. Pri U2 = U2 n je točka, skozi
katero krivulja izgub kot funkcija sekundarne
napetosti ne poteka zvezno. Zato moramo obrav-
navati posamezna območja ločeno.
a) območje: U 2 min < U2 < U 2n
V tem območju so izgube v nizkonapetostnem
navitju konstantne
1
P cu 2 = 2 p cutip
Z znižanjem sekundarne napetosti primarni tok
pada, število vklopljenih ovojev primarnega
navitja pa se povečuje:
p = U 2n (!__)2
P cutip
cul u2 pn 2
Skupne izgube v bakru se spreminjajo po enačbi:
- - = = - - - + 1 (3,1)P cu P cul + P cu 2 1 [ U2n ( P)2
]
p cutip p cu tip 2 u2 pn
b) območje: U2 n < U2 < U2maks
Zvišanjem sekundarne napetosti se izgube v niz-
konapetostnem in visokonapetostnem navitju
manjšajo: 1 ( )2pcu2 = 2 pcutip r;;2
n
1 ( U2n)
pcul = 2 pcutip u2
Skupne izgube v bakru se spreminjajo po enačbi
Pcu = Pcui + Pcu2 = ~ [ (U2n)
2
+ U2n]
Pcu tip Pcu tip 2 U2 U2
= ..!._ U2n [ U2n + 1] (3,2)
2 u2 U2
Te enačbe nam omogočajo tudi nasprotno pot,
to je izračun tipskih izgub, če poznamo izgube pri
u2makS> u2min ali pa pri katerikoli drugi sekundarni
napetosti. Izračun izgub v bakru po enačbah 3.1 in
3.2 daje dovolj točne rezultate za praktično upo-
rabo. Odstopki nastopajo tam, kjer gre za večje
razlike med izgubami v primarnem in sekundar-
nem navitju, ter tam, kjer gre za višje primarne
napetosti in je potrebno regulacijski del navitij
močneje izolirati.
,
4. Kratkostična napetost
Kratkostično napetost pri transformatorju dolo-
čata induktivna in ohmska komponenta. Nas zani-
ma predvsem induktivna komponenta, ki za
transformatorje večjih moči predstavlja glavni del
kratkostične napetosti. Izhajamo iz osnovnega raz-
merja, ki določa kratkostično napetost v procentih
U0 = ~n 100 ;:;;;: UK [%)
Po krajšem izvajanju [2] je:
UK ;:;;;: un = 39,6 . 10- 3 ~b osr Or [% )
u ov2
kjer posamezne označbe pomenijo:
P, - moč transformatorja na steber [kVA]
u0 v - ovojna napetost [V1 ov] b
b dolžina silnic razsipanega polja b = ~ [mm]
O,r - srednji obseg silnic razsipanega polja [mm]
or - reducirana zračna reža [mm]
K - faktor Rogowskega
Z regulacijo sekundarne napetosti se bo spremi-
njala tudi kratkostična napetost. Predpostavimo,
da je kratkostična napetost pri sekundarni nape-
tosti U2 = U2 n in moči P = P" enaka tipski. Pri
poljubni drugi napetosti in drugi moči pa je:
UK P (Uov tip )
2
Osr Or (4, 1)
UKtip = Pn --:u;;:;- osrtip ortip
Za izračun kratkostične napetosti po enačbi 4.1
bi morali predpostaviti, da se O,r in Onki določata
geometrijske razsežnbsti navitij, ne spreminjata
z regulacijo napetosti.
V večini primerov pa to ni izpolnjeno, posebno
tam, kjer gre za večja območja regulacije in je
regulacijski del navitja potrebno sestaviti iz več
ELEKTROTEHNISKI VESTNIK 1982- št. 2 93
delnih navitij. V nekaterih primerih regulacijski
del predstavlja 3/4 glavnega primarnega navitja.
Z različno medsebojno lego posameznih navitij
je možno geometrijsko oblikovati razsipano polje
in tako vplivati na velikost kratkostične napetosti.
V odvisnosti od tega, kako veliko kratkostično
napetost želimo imeti, se bomo odločili za določeno
razporeditev navitij. Najpogosteje so posamezna
navitja razporejena po sliki 4.
Iz tega sledi, da izračun kratkostičnih napetosti
pri spremenljivi geometriji navitij s poenostavlje-
nimi enačbami ni dovolj točen, v posameznih pri-
merih pa sploh ni možen. Tedaj jo določamo z me-
todo delnih izračunov amper-ovojev vsake posa-
mezne tuljavice
U ""'U - s 2 It 'p [ a 'a- k - 0,124 ~b m1 - d It+
uov 3
+ mi2 d'I d!d + ( mi2 + mi m2 + m22)
+ m22 dt d1/' + ... +
kjer je:
a "_l_t d "+
3 It
m- relativno razmerje primarnih ovojev:
. NI'
mi=-
NI
NI'+ NI"
m2=
NI
Nnl = N1 - število ovojev delnih tuljavic primar-
nega navitja
Izračun kratkostičnih napetosti je na ta način
izredno natančen, vendar zamuden in obsežen,
zato je priporočljivo uporabljati računalniške
sisteme, ki bistveno skrajšajo potek izračuna. Na
podlagi tako izračunanih amper-ovojev vsake
delne tuljavice je možno za vsako obratovalno
točko od u2 maks do u2 min narisati porazdelitev razsi-
panega polja v oknu transformatorja. Na sliki 5 je
~~- /
l:""i'" ~ r--
d1d
iHt -': i
dtt(r1) /
dt2d < .J
dlt .--:
~
~ N' N" N(n)
% N2
/: 1 1 1
.,W1,~ :roIJi2 02ta1t 1 a1t _ a11
01t
1604
Sl. 4. Geometrična razporeditev navitij
1605
1,0
0,9
0,5
0.4
0,3
0,2
0,1
NN
0,0 +-___._____.J.__ ___L_J____L_J___ _L__ _}____.;,:.
Sl. 5. Potek razsipanega polja
d1n - notranji premer in
d2 , - zunanji premer navitij
narisana porazdelitev razsipanega polja pri regu-
laciji sekundarne napetosti po sliki 1 in pri
razporeditvi navitij po sliki 4. Izbrane so tri karak-
teristične napetosti u2min> u2n in u2maks·
Vsi diagrami in slike se nanašajo na primer oblač­
nega transformatorja, izdelanega v naši tovarni za
tovarno dušika v Rušah.
Sklep
Opisani način regulacije sekundarne napetosti
obločnih transformatorjev v večini primerov ustre-
za zahtevam sodobne metalurške in kemične pro-
izvodnje. Ekonomičnost izvedbe in enostavna kon-
strukcija sta glavni značilnosti direktne regulacije
sekundarne napetosti. V celotnem sistemu ne po-
trebujemo dodatnega transformatorja. .Iz tehno-
loškega in gospodarnega vidika je njuna uporaba
še opravičljiva do približno 10 MVA nazivne moči
transformatorja. Za večje moči je v svetu uveljav-
ljena izvedba z dodatnim regulacijskim transfor-
matorjem, ali pa t. i. dodajalna (booster) regulacija.
Literatura
[1] F. Coppadoro:- La regolazione della tensione dei tran-
sformatori per 1' alimentazione dei forni eletrici, »L'elettro-
tecnica«, nI vol. LI-1964.
[2] P. M. Tihomirov: Raščet transformatorov, izd. 3-e,
»Energija«, Moskva 1968.
[3] G. Schemel: Lichtbogenofen-Transformatoren fur die
neuen Ofenreihen AM und AL, Brown Boveri Mitteilungen,
Baden 1979.
[4) C. T. Bradburn: Determining furnace transformer
losses, Allis-Chalmers Electrical Review, third quarter,
p. 26-29, 1961.
Avtorjev naslov: Jusuf Ikanovič, dipl. ing.,
»ENERGOINVEST« - Sarajevo, DO To-
varna transformatorjev, 61231 Ljubljana-
Črnuče

Recommandé

Improvement of the Filling Factor in Windings of Power Transformers par
Improvement of the Filling Factor in Windings of Power TransformersImprovement of the Filling Factor in Windings of Power Transformers
Improvement of the Filling Factor in Windings of Power TransformersJuso Ikanovic
349 vues7 diapositives
Močnostni transformatorji za prenovo Dravskih hidroelektrarn par
Močnostni transformatorji za prenovo Dravskih hidroelektrarnMočnostni transformatorji za prenovo Dravskih hidroelektrarn
Močnostni transformatorji za prenovo Dravskih hidroelektrarnJuso Ikanovic
223 vues5 diapositives
Booster Transformer Equivalent Circuit par
Booster Transformer Equivalent CircuitBooster Transformer Equivalent Circuit
Booster Transformer Equivalent CircuitJuso Ikanovic
250 vues6 diapositives
POWER TRANSFORMER WINDINGS WITHOUT PAPER INSULATION par
POWER TRANSFORMER WINDINGS WITHOUT PAPER INSULATIONPOWER TRANSFORMER WINDINGS WITHOUT PAPER INSULATION
POWER TRANSFORMER WINDINGS WITHOUT PAPER INSULATIONJuso Ikanovic
288 vues8 diapositives
Transformer Repair Workshop Report [EEE] par
Transformer Repair Workshop Report [EEE] Transformer Repair Workshop Report [EEE]
Transformer Repair Workshop Report [EEE] Nik Sharma
19.5K vues38 diapositives
Areva "Manufacturing of transformer, uses & it’s accessories" par
Areva "Manufacturing of transformer, uses & it’s accessories"Areva "Manufacturing of transformer, uses & it’s accessories"
Areva "Manufacturing of transformer, uses & it’s accessories"Harshit Srivastava
6.3K vues24 diapositives

Contenu connexe

Plus de Juso Ikanovic

DVOHODNO VIJACNO NAVITJE S PRAVOKOTNO ZICO Z UCINKI TRANSPONIRANEGA VODNIKA par
DVOHODNO VIJACNO NAVITJE S PRAVOKOTNO ZICO Z UCINKI TRANSPONIRANEGA VODNIKADVOHODNO VIJACNO NAVITJE S PRAVOKOTNO ZICO Z UCINKI TRANSPONIRANEGA VODNIKA
DVOHODNO VIJACNO NAVITJE S PRAVOKOTNO ZICO Z UCINKI TRANSPONIRANEGA VODNIKAJuso Ikanovic
269 vues12 diapositives
Problems in Design and Construction of High Power Transformers for Electric А... par
Problems in Design and Construction of High Power Transformers for Electric А...Problems in Design and Construction of High Power Transformers for Electric А...
Problems in Design and Construction of High Power Transformers for Electric А...Juso Ikanovic
290 vues4 diapositives
Converter Transformers manufactured to the Slovenian Railways par
Converter Transformers manufactured to the Slovenian RailwaysConverter Transformers manufactured to the Slovenian Railways
Converter Transformers manufactured to the Slovenian RailwaysJuso Ikanovic
532 vues4 diapositives
NOVOSTI V RAZVOJU NAVITIJ ENERGETSKIH TRANSFORMATORJEV Z LAK IZOLACIJO par
NOVOSTI V RAZVOJU NAVITIJ ENERGETSKIH TRANSFORMATORJEV Z LAK IZOLACIJONOVOSTI V RAZVOJU NAVITIJ ENERGETSKIH TRANSFORMATORJEV Z LAK IZOLACIJO
NOVOSTI V RAZVOJU NAVITIJ ENERGETSKIH TRANSFORMATORJEV Z LAK IZOLACIJOJuso Ikanovic
312 vues24 diapositives
BOOSTER REGULACIJA NAPONA NA NISKONAPONSKOJ SТRANI ENERGEТSКIН TRANSFORМATORA par
BOOSTER REGULACIJA NAPONA NA NISKONAPONSKOJ SТRANI ENERGEТSКIН TRANSFORМATORABOOSTER REGULACIJA NAPONA NA NISKONAPONSKOJ SТRANI ENERGEТSКIН TRANSFORМATORA
BOOSTER REGULACIJA NAPONA NA NISKONAPONSKOJ SТRANI ENERGEТSКIН TRANSFORМATORAJuso Ikanovic
191 vues10 diapositives
EKSPERIMENTALNI REZULTATI MJERENJA ODZIVA NAMOTAJA TRANSFORMATORA PRI OSCILAT... par
EKSPERIMENTALNI REZULTATI MJERENJA ODZIVA NAMOTAJA TRANSFORMATORA PRI OSCILAT...EKSPERIMENTALNI REZULTATI MJERENJA ODZIVA NAMOTAJA TRANSFORMATORA PRI OSCILAT...
EKSPERIMENTALNI REZULTATI MJERENJA ODZIVA NAMOTAJA TRANSFORMATORA PRI OSCILAT...Juso Ikanovic
284 vues8 diapositives

Plus de Juso Ikanovic(11)

DVOHODNO VIJACNO NAVITJE S PRAVOKOTNO ZICO Z UCINKI TRANSPONIRANEGA VODNIKA par Juso Ikanovic
DVOHODNO VIJACNO NAVITJE S PRAVOKOTNO ZICO Z UCINKI TRANSPONIRANEGA VODNIKADVOHODNO VIJACNO NAVITJE S PRAVOKOTNO ZICO Z UCINKI TRANSPONIRANEGA VODNIKA
DVOHODNO VIJACNO NAVITJE S PRAVOKOTNO ZICO Z UCINKI TRANSPONIRANEGA VODNIKA
Juso Ikanovic269 vues
Problems in Design and Construction of High Power Transformers for Electric А... par Juso Ikanovic
Problems in Design and Construction of High Power Transformers for Electric А...Problems in Design and Construction of High Power Transformers for Electric А...
Problems in Design and Construction of High Power Transformers for Electric А...
Juso Ikanovic290 vues
Converter Transformers manufactured to the Slovenian Railways par Juso Ikanovic
Converter Transformers manufactured to the Slovenian RailwaysConverter Transformers manufactured to the Slovenian Railways
Converter Transformers manufactured to the Slovenian Railways
Juso Ikanovic532 vues
NOVOSTI V RAZVOJU NAVITIJ ENERGETSKIH TRANSFORMATORJEV Z LAK IZOLACIJO par Juso Ikanovic
NOVOSTI V RAZVOJU NAVITIJ ENERGETSKIH TRANSFORMATORJEV Z LAK IZOLACIJONOVOSTI V RAZVOJU NAVITIJ ENERGETSKIH TRANSFORMATORJEV Z LAK IZOLACIJO
NOVOSTI V RAZVOJU NAVITIJ ENERGETSKIH TRANSFORMATORJEV Z LAK IZOLACIJO
Juso Ikanovic312 vues
BOOSTER REGULACIJA NAPONA NA NISKONAPONSKOJ SТRANI ENERGEТSКIН TRANSFORМATORA par Juso Ikanovic
BOOSTER REGULACIJA NAPONA NA NISKONAPONSKOJ SТRANI ENERGEТSКIН TRANSFORМATORABOOSTER REGULACIJA NAPONA NA NISKONAPONSKOJ SТRANI ENERGEТSКIН TRANSFORМATORA
BOOSTER REGULACIJA NAPONA NA NISKONAPONSKOJ SТRANI ENERGEТSКIН TRANSFORМATORA
Juso Ikanovic191 vues
EKSPERIMENTALNI REZULTATI MJERENJA ODZIVA NAMOTAJA TRANSFORMATORA PRI OSCILAT... par Juso Ikanovic
EKSPERIMENTALNI REZULTATI MJERENJA ODZIVA NAMOTAJA TRANSFORMATORA PRI OSCILAT...EKSPERIMENTALNI REZULTATI MJERENJA ODZIVA NAMOTAJA TRANSFORMATORA PRI OSCILAT...
EKSPERIMENTALNI REZULTATI MJERENJA ODZIVA NAMOTAJA TRANSFORMATORA PRI OSCILAT...
Juso Ikanovic284 vues
REPARATION OF POWER TRANSFORMERS 150 MVA- 220 kV par Juso Ikanovic
REPARATION OF POWER TRANSFORMERS 150 MVA- 220 kVREPARATION OF POWER TRANSFORMERS 150 MVA- 220 kV
REPARATION OF POWER TRANSFORMERS 150 MVA- 220 kV
Juso Ikanovic184 vues
Semi - hybrid thermal insulation system par Juso Ikanovic
Semi - hybrid thermal insulation systemSemi - hybrid thermal insulation system
Semi - hybrid thermal insulation system
Juso Ikanovic195 vues
Power Transformer Windings without Paper Insulation par Juso Ikanovic
Power Transformer Windings without Paper Insulation Power Transformer Windings without Paper Insulation
Power Transformer Windings without Paper Insulation
Juso Ikanovic220 vues
CONVERTER TRANSFORMERS FOR REFURBISHMENT OF SLOVENIAN RAILWAYS par Juso Ikanovic
CONVERTER TRANSFORMERS FOR REFURBISHMENT OF SLOVENIAN RAILWAYSCONVERTER TRANSFORMERS FOR REFURBISHMENT OF SLOVENIAN RAILWAYS
CONVERTER TRANSFORMERS FOR REFURBISHMENT OF SLOVENIAN RAILWAYS
Juso Ikanovic425 vues
IMPACT OF OPTICAL FIBRE TEMPERATURE SENSORS ON DIELECTRIC WITHSTAND OF OIL CH... par Juso Ikanovic
IMPACT OF OPTICAL FIBRE TEMPERATURE SENSORS ON DIELECTRIC WITHSTAND OF OIL CH...IMPACT OF OPTICAL FIBRE TEMPERATURE SENSORS ON DIELECTRIC WITHSTAND OF OIL CH...
IMPACT OF OPTICAL FIBRE TEMPERATURE SENSORS ON DIELECTRIC WITHSTAND OF OIL CH...
Juso Ikanovic211 vues

Transformers for Electric Arc-Melting Furnaces with Direct Voltage Regulation

  • 1. 90 ELEKTROTEHNISKI VESTNIK 1982 - št. 2 Transformatorji za električne obločne peči z direktno regulacijo napetosti Jusuf Ikanovic, Ljubljana UDK 621.314:669,041 Transformers for Electric Arc-Melting Furnaces with Direct Voltage Regulation In modern metallurgical and chemical industry there is an increasing need for electric arc-melting furnaces. Transformer is also one of the vital parts by which power is supplied to fur- naces. Because of their technological aspects, Electric arc- melting furnaces, need special transformers different from usual distribution units. The main problem arises from the de- mand for relatively wide range of regulation on the low volta- ge side. In this article one of the many principles of voltage regulation is described, nomely, low voltage regulation by means of magnetic flux variations. V sodobni metalurški in kemični industriji naraščajo potre- be po električnih obločnih pečeh. Sestavni del celotnega siste- ma je tudi transformator, preko katerega se peč napaja. Obloč­ ne peči s svojimi specifičnimi tehnološkimi zahtevami nareku- jejo izdelavo specialnih transformatorjev, ki se v marsičem razlikujejo od običajnih distribucijskih enot. Poglavitni problemi pri vseh teh enotah izvirajo iz zahteve po razmeroma širokem območju regulacije na nizkonapetostni strani transformatorja. Članek obravnava problematiko enega od več možnih načinov regulacije napetosti, tj. regulacijo sekun- darne napetosti s spreminjanjem magnetnega pretoka. Uvod Transformatorji za električne obločne peči ima- jo naslednje značilnosti in posebnosti: a) nizke sekundarne napetosti (do nekaj 100 V) in v odvisnosti od moči izredno velike sekundarne toke; b) široko območje regulacije sekundarne nape- tosti; c) v večini primerov se napetost regulira pod obremenitvijo; d) zaradi pogostih kratkih stikov v peči je transformator podvržen velikim elektrodinamič- nim silam; · e) v transformatorju se pojavljajo prenapetosti, ki so posledica posebnih karakteristik bremena; f) naravno hlajenje ni več primerno in ·se že manjše enote hladijo s prisilnim obtokom, veči­ noma vode in olja. Zaradi preobširnosti nakazane problematike se bomo omejili samo na probleme, ki izhajajo iz prvih treh točk, to so problemi regulacije sekun- darne napetosti. V svetu je· uveljavljenih več možnih načinov regulacije. Izbira načina je odvis- na predvsem od moči transformatorja in pa od zahtev po območju in načinu regulacije sekundar- ne napetosti. Pri vsem tem moramo hkrati iskati najbolj gospodarno varianto, ki bo zahtevala naj- manj vgrajenega materiala. Za transformatorje do 10 MVA nazivne moči je najprimernejša t.i. di- rektna regulacija napetosti, oziroma regulacija ·napetosti s spreminjanjem magnetnega pretoka. Pod tem imenom jo pogosto zasledimo v tuji stro- kovni literaturi, kar je nekako bliže fizikalnim do- Uredništvo je prejelo članek 1982-02-10 gajanjem v transformatorju v procesu regulacije sekundarne napetosti. Napišimo eno izmed osnov- nih enačb transformatorja v praznem teku u2 N2 NI V principu napetost transformatorja lahko ali N1. U2 na sekundarni strani spreminjamo z U~> N2 Napetost U1 je napajalna - omrežna napetost transformatorja in je v normalnem obratovanju ni možno spreminjati. _ Najbolj logično bi bilo, če bi napetost U2 spre- minjali na nizkonapetostni strani, spreminjajoč število nizkonapetostnih ovojev N2, vendar tudi tu obstajajo določeni, predvsem tehnološki problemi. Število ovojev na nizkonapetostni strani je že pri transformatorjih srednjih moči tako majhno, da bi bila regulacija le-teh pregroba, pri transformator- jih večjih moči pa sploh neizvedljiva. V posamez- nih primerih je število ovojev N2 = 2 ali pa celo N2 = 1 ovoj. Regulacija napetosti U2 s pomočjo U1 in N2 je sicer izvedljiva, vendar samo z uporabo dodatnega regulacijskega transformatorja, kar pa bistveno podraži celotno izvedbo. Ostane nam še tretja možnost, to je regulacija sekundarne napetosti u2 s pomočjo spreminjanja števila ovojev N 1 .na primarni strani transfor- matorja. Tako regulacijo imenujemo direktna regulacija napetosti ali regulacija napetosti s spre- minjanjem magnetnega pretoka. 1 U2 = k! 1G = k2 U0 v = k3 <f> <P - magnetni pretok k3 = 4,44/N2 - konstanta Najpogosteje je v uporabi regulacijska shema, ki jo kaže slika l. · VN GR FR Sl. l. Osnovna ~hema regulacije napetosti VN - Visokonapetostno navitje GR - Grobo regulacijsko navitje FR - Fino regulacijsko navitje NN - Nizkonapetostno navitje
  • 2. ) • ELEKTROTEHNISKI VESTNIK 1982 - št. 2 91 V nadaljnjem bomo skušali ugotoviti, kako se spreminjajo osnovni parametri transformatorja, če reguliramo sekundarno napetost s spreminjanjem magnetnega pretoka, in sicer: l. tipska moč, 2. izgube v železu, 3. izgube v bakru in 4. kratkostična napetost. l. Tipska moč 1.1. Predpostavimo, da želimo regulirati sekun- darno napetost v mejah od u2min do u2maks maks ob konstantnem sekundarnem toku / 2. Pri tem za primarno stran veljajo naslednja razmerja: Ut N2 Nt maks= -U N2 /!maks=~ / 2 2 min 1min Ut N 2 Nl noin = u - N2 /!min = -N / 2 2maks !maks Posamezne moči, za katere moramo dimenzioni- rati sekundarno in primarano navitje, so: p2 = u 2maks /2 P1 = P2 [ 1 + ~ ( J2::s-~2:::J] Razmerje x U2maks 1. l · b-U- - predstav Ja re atiVno o - 2 min močje regulacije sekundarne napetosti. V večini primerov se vrednost x giblje med 1,5 in 3. Moč, za katero moramo dimenzionirati transfor- mator, imenujemo podobno kot pri avtotransfor- matorjih tipska moč. ptip = ~ p2 [ 2 + ~ (x-~) ] (1,1) Relativno območje regulacije x in tipska moč Ptip v grobem karakterizirata vsak oblačni transformator. Primer: Vzemimo enofazni transformator, ki mu na sekundarni strani želimo regulirati napetost od u2 = 200 - 600 v, pri konstantnem sekundarnem toku / 2 = 30 kA. x = 3 P2 = Pn = 18MVA P1 = 18 [ 1 + ~ ( 3 - ~) J 9 __~!!_ = 30 MVA3 1,6 7 7 18 - = 42 MVA3 Iz tega izhaja, da moramo projektirati transfor- mator za približno 70 % večjo moč, kot je njegova nazivna moč. V primerjavi s podobnim neregulacij- skim bo obločni _...transformator za isto moč večji, težji in s tem tudi dražji. 1.2. Do se_daj smo obravnavali primer regulacije napetosti U2 pri konstantnem toku / 2. Sodobnejši PIP", It/Itn• lilzn f,O 0,9 0,8 0,7 0,6 0,5 / 1602 / ~·vr-- ./ '"'y 1'--r-....... Ut=konst 1 Sl. 2. Potek tokov in moči lt,P -·-.... Iz Uz metalurški in kemični procesi pa zahtevajo od transformatorja široko območje regulacije napeto- sti u2 in v določenem ciklu spreminjanje sekun- darnega toka / 2 ter ohranjeno ali pa reducirano moč. Najpogostejši delovni proces obločne peči, s tem pa tudi transformatorja, poteka po diagramu na sl. 2. Tipska moč je v tem primeru enaka 1 ( U2maks) Ptip = 2 ltmaks U1 x + /2maks U2n-----u;;- = ~ pn (x+ U~::ks) (1,2) Dejanska tipska moč je še nekoliko večja, kot je po enačbah 1,1 in 1,2 določeno, to pa zaradi regula- cijskih navitij, ki jih je potrebno še dodatno izoli- rati. To povečanje tipske moči je pogosto potrebno upoštevati, zlasti pri transformatorjih z višjo stop- njo izolacije. 2. Izgube v železu Tipske izgube v železu so definirane pri maksi- malni ovojni napetosti, to je pri največji napetosti na sekundarni strani transformatorja. Gostota magnetnega pretoka se spreminja sorazmerno z ovojno napetostjo B B Uov u2 Bmaks Btip uovmaks U2maks' izgube v železu pa še v odvisnosti od magnetnih lastnosti uporabljene železne pločevine ter od kon- strukcije jedra transformatorja. Nelinearnost po- teka izgub bomo upoštevali z dodatnim faktorjem c P Fe = ~ = C' ___!!____ = C ____!!__!__ PFetip PFemaks Bmaks u 2maks Na sliki 3 je narisan potek izgub v železu pri Bmaks- 1,735 T za magnetno pločevino M 5. Če krivulje magnetenja ne poznamo, zadošča za bolj grobe izračune, če izgube v železu določimo po poenostavljeni enačbi :::ip ~ (B~aksy ~ ( U~:aksy
  • 3. 92 ELEKTROTEHNIŠKI VESTNIK 1982 - št. 2 uk;uktip• ~e/~etip • PcuiPcutip 1,3 ~ 1,1 ~ ~ !'----. V'~ '~ / ~e- 9 -...-- ~ /r-... O, ""' 'X / ~"-........_ Pcu- / ~ Pcu2 ....___ uk- -.x -------- ./' ~ 0,7 0,5 ' Pcu1 v 1-' _./ "~ :::::::-v -- Pcu1 f- --Pcu2 0,3 U2 0,1 U2n U2maks Sl. 3. Potek karakterističnih veličin 3. Izgube v bakru Izgube v bakru se bodo spreminjale po celotnem območju regulacije od u2 min do u 2 makS> v odvisno- sti od / 2 in števila vklopljenih ovojev N1• Zaradi enostavnosti izračuna predpostavimo, da imajo vsi ovoji reguliranega navitja enak prerez ter da so izgube v primarnem in sekundarnem navitju ' enake. V praksi je to v večini primerov približno izpolnjeno. Izgube v bakru pri sekundarni napeto- sti u 2 = u 2 n so maksimalne in jih imenujemo tip- ske izgube: p cu U2n = P culip 1 P cutipl = P cutip2 = 2 p cutip Tipske izgube v bakru so približno enake izgu- bam podobnega distribucijskega transformatorja, katerega nazivna moč je enaka tipski moči oblač­ nega transformatorja, določeni po enačbi 1,1 in 1,2. Glede na potek moči in tokov v diagramu sl. 2 se izgube v bakru ne spreminjajo zvezno po vsem območju regulacije. Pri U2 = U2 n je točka, skozi katero krivulja izgub kot funkcija sekundarne napetosti ne poteka zvezno. Zato moramo obrav- navati posamezna območja ločeno. a) območje: U 2 min < U2 < U 2n V tem območju so izgube v nizkonapetostnem navitju konstantne 1 P cu 2 = 2 p cutip Z znižanjem sekundarne napetosti primarni tok pada, število vklopljenih ovojev primarnega navitja pa se povečuje: p = U 2n (!__)2 P cutip cul u2 pn 2 Skupne izgube v bakru se spreminjajo po enačbi: - - = = - - - + 1 (3,1)P cu P cul + P cu 2 1 [ U2n ( P)2 ] p cutip p cu tip 2 u2 pn b) območje: U2 n < U2 < U2maks Zvišanjem sekundarne napetosti se izgube v niz- konapetostnem in visokonapetostnem navitju manjšajo: 1 ( )2pcu2 = 2 pcutip r;;2 n 1 ( U2n) pcul = 2 pcutip u2 Skupne izgube v bakru se spreminjajo po enačbi Pcu = Pcui + Pcu2 = ~ [ (U2n) 2 + U2n] Pcu tip Pcu tip 2 U2 U2 = ..!._ U2n [ U2n + 1] (3,2) 2 u2 U2 Te enačbe nam omogočajo tudi nasprotno pot, to je izračun tipskih izgub, če poznamo izgube pri u2makS> u2min ali pa pri katerikoli drugi sekundarni napetosti. Izračun izgub v bakru po enačbah 3.1 in 3.2 daje dovolj točne rezultate za praktično upo- rabo. Odstopki nastopajo tam, kjer gre za večje razlike med izgubami v primarnem in sekundar- nem navitju, ter tam, kjer gre za višje primarne napetosti in je potrebno regulacijski del navitij močneje izolirati. , 4. Kratkostična napetost Kratkostično napetost pri transformatorju dolo- čata induktivna in ohmska komponenta. Nas zani- ma predvsem induktivna komponenta, ki za transformatorje večjih moči predstavlja glavni del kratkostične napetosti. Izhajamo iz osnovnega raz- merja, ki določa kratkostično napetost v procentih U0 = ~n 100 ;:;;;: UK [%) Po krajšem izvajanju [2] je: UK ;:;;;: un = 39,6 . 10- 3 ~b osr Or [% ) u ov2 kjer posamezne označbe pomenijo: P, - moč transformatorja na steber [kVA] u0 v - ovojna napetost [V1 ov] b b dolžina silnic razsipanega polja b = ~ [mm] O,r - srednji obseg silnic razsipanega polja [mm] or - reducirana zračna reža [mm] K - faktor Rogowskega Z regulacijo sekundarne napetosti se bo spremi- njala tudi kratkostična napetost. Predpostavimo, da je kratkostična napetost pri sekundarni nape- tosti U2 = U2 n in moči P = P" enaka tipski. Pri poljubni drugi napetosti in drugi moči pa je: UK P (Uov tip ) 2 Osr Or (4, 1) UKtip = Pn --:u;;:;- osrtip ortip Za izračun kratkostične napetosti po enačbi 4.1 bi morali predpostaviti, da se O,r in Onki določata geometrijske razsežnbsti navitij, ne spreminjata z regulacijo napetosti. V večini primerov pa to ni izpolnjeno, posebno tam, kjer gre za večja območja regulacije in je regulacijski del navitja potrebno sestaviti iz več
  • 4. ELEKTROTEHNISKI VESTNIK 1982- št. 2 93 delnih navitij. V nekaterih primerih regulacijski del predstavlja 3/4 glavnega primarnega navitja. Z različno medsebojno lego posameznih navitij je možno geometrijsko oblikovati razsipano polje in tako vplivati na velikost kratkostične napetosti. V odvisnosti od tega, kako veliko kratkostično napetost želimo imeti, se bomo odločili za določeno razporeditev navitij. Najpogosteje so posamezna navitja razporejena po sliki 4. Iz tega sledi, da izračun kratkostičnih napetosti pri spremenljivi geometriji navitij s poenostavlje- nimi enačbami ni dovolj točen, v posameznih pri- merih pa sploh ni možen. Tedaj jo določamo z me- todo delnih izračunov amper-ovojev vsake posa- mezne tuljavice U ""'U - s 2 It 'p [ a 'a- k - 0,124 ~b m1 - d It+ uov 3 + mi2 d'I d!d + ( mi2 + mi m2 + m22) + m22 dt d1/' + ... + kjer je: a "_l_t d "+ 3 It m- relativno razmerje primarnih ovojev: . NI' mi=- NI NI'+ NI" m2= NI Nnl = N1 - število ovojev delnih tuljavic primar- nega navitja Izračun kratkostičnih napetosti je na ta način izredno natančen, vendar zamuden in obsežen, zato je priporočljivo uporabljati računalniške sisteme, ki bistveno skrajšajo potek izračuna. Na podlagi tako izračunanih amper-ovojev vsake delne tuljavice je možno za vsako obratovalno točko od u2 maks do u2 min narisati porazdelitev razsi- panega polja v oknu transformatorja. Na sliki 5 je ~~- / l:""i'" ~ r-- d1d iHt -': i dtt(r1) / dt2d < .J dlt .--: ~ ~ N' N" N(n) % N2 /: 1 1 1 .,W1,~ :roIJi2 02ta1t 1 a1t _ a11 01t 1604 Sl. 4. Geometrična razporeditev navitij 1605 1,0 0,9 0,5 0.4 0,3 0,2 0,1 NN 0,0 +-___._____.J.__ ___L_J____L_J___ _L__ _}____.;,:. Sl. 5. Potek razsipanega polja d1n - notranji premer in d2 , - zunanji premer navitij narisana porazdelitev razsipanega polja pri regu- laciji sekundarne napetosti po sliki 1 in pri razporeditvi navitij po sliki 4. Izbrane so tri karak- teristične napetosti u2min> u2n in u2maks· Vsi diagrami in slike se nanašajo na primer oblač­ nega transformatorja, izdelanega v naši tovarni za tovarno dušika v Rušah. Sklep Opisani način regulacije sekundarne napetosti obločnih transformatorjev v večini primerov ustre- za zahtevam sodobne metalurške in kemične pro- izvodnje. Ekonomičnost izvedbe in enostavna kon- strukcija sta glavni značilnosti direktne regulacije sekundarne napetosti. V celotnem sistemu ne po- trebujemo dodatnega transformatorja. .Iz tehno- loškega in gospodarnega vidika je njuna uporaba še opravičljiva do približno 10 MVA nazivne moči transformatorja. Za večje moči je v svetu uveljav- ljena izvedba z dodatnim regulacijskim transfor- matorjem, ali pa t. i. dodajalna (booster) regulacija. Literatura [1] F. Coppadoro:- La regolazione della tensione dei tran- sformatori per 1' alimentazione dei forni eletrici, »L'elettro- tecnica«, nI vol. LI-1964. [2] P. M. Tihomirov: Raščet transformatorov, izd. 3-e, »Energija«, Moskva 1968. [3] G. Schemel: Lichtbogenofen-Transformatoren fur die neuen Ofenreihen AM und AL, Brown Boveri Mitteilungen, Baden 1979. [4) C. T. Bradburn: Determining furnace transformer losses, Allis-Chalmers Electrical Review, third quarter, p. 26-29, 1961. Avtorjev naslov: Jusuf Ikanovič, dipl. ing., »ENERGOINVEST« - Sarajevo, DO To- varna transformatorjev, 61231 Ljubljana- Črnuče