ETSE
Ms. Kinjal G. Shah, Assistant Professor
Electrical Engineering Department
CHAPTER-2
Arc phenomema
SWITCHGEARS : Definition
• Switchgear is a general term covering all equipment
used for :
- switching,
- protection,
- control and
- isolation in a power system.
• All equipment used for fault clearing is covered by the
term switchgear.
• Switchgears are used in Generation, Transmission and
Distribution Systems, whereas, Control Gears are used
in Consumer Circuits.
Necessity of Switchgears
• Switchgears are necessary at every switching
point in the power system because there are
several voltage levels and fault levels which has
to be controlled and protected by accessible
switching devices and for isolation, if the need
arises.
Principal Switchgears
• Principal Switchgears are the main
equipment concerned with the process of
switching and isolating circuits in a power
system.
Auxiliary Switchgears
• Auxiliary Switchgears are secondary or
subsidiary equipment which assist the main
switchgear equipment in the control,
measurement, protection and fault-
clearing process.
Examples of Principal Switchgears:
• SWITCHING DEVICES
(a) Circuit Breakers
(b) Isolators (Disconnector or Disconnecting Switch)
(c) Earthing Switches
(d) Load Switches (Ring Main Units)
(e) Contactors
Examples of Auxiliary Switchgears
• PROTECTION DEVICES
(i) Protection Relays
(j) Lightning Arresters
(k) Feeder Pillars
(l) Fuses.
• SENSING DEVICES Voltage
(m) Potential Transformers
(n) Current Transformers
Examples of Auxiliary Switchgears :
• CONTROL (COMPENSATION) DEVICES
(o) Series Inductive Reactors
(p) Shunt Inductive Reactors
(q) Series Capacitive Reactors
(r) Shunt Capacitive Reactors
• AUXILIARY POWER SUPPLY DEVICES
(s)Tripping Units (Battery Bank & Charger)
SWITCHGEAR : Gear for Switching
Switching Devices
-Circuit Breaker
- Isolators
- Switches
Control & Sensing
Devices
-CT, PT
- Reators
- Tripping Units
Decision Making
Devices
-Protective Relays
-Fuses
-Lightning Arrester
What is an Arc?
• During opening of current carrying contacts in a circuit
breaker the medium in between opening contacts
become highly ionized through which the interrupting
current gets low resistive path and continues to flow
through this path even the contacts are physically
separated.
• During the flowing of current from one contact to
other the path becomes so heated that it glows. This is
called arc.
Arc phenomena
• When a short-circuit occurs, a heavy current
flows through the contacts of the circuit breaker
before they are opened by the protective system.
• At the instant when the contacts begin to separate,
the contact area decreases rapidly and large fault
current causes increased current density and hence
risein temperature.
• The heat produced in the medium between contacts
(usually the medium is oil or air)is sufficient to ionise
the air or vapourise and ionise the oil.
• The ionised air or vapour acts as conductor and an arc
is struck between the contacts.
• The p.d. between the contacts is quite small and is just
sufficient to maintain the arc. The arc provides a low resistance
path and consequently the current in the circuit remains
uninterrupted so long as the arc persists.
• During the arcing period, the current flowing between the
contacts depends upon the arc resistance.
• The greater the arc resistance, the smaller the current that
flows between the contacts. The arc resistance depends upon
the following factors :
(i) Degree of ionisation — the arc resistance increases with the
decrease in the number of ionised particles between the contacts.
(ii) Length of the arc — the arc resistance increases with the length
of the arc i.e., separation of contacts
(iii) Cross-section of arc — the arc resistance increases with the
decrease in area of X-section of the arc.
Principles of Arc Extinction
• The methods of arc extinction, it is necessary to examine the factors
responsible for the maintenance of arc between the contacts. These
are :
(i) p.d. between the contacts
(ii) ionised particles between contacts
Taking these in turn,
(i) When the contacts have a small separation, the p.d. between them is
sufficient to maintain the arc. One way to extinguish the arc is to
separate the contacts to such a distance that p.d. becomes inadequate to
maintain the arc. However, this method is impracticable in high voltage
system where a separation of many metres may be required.
(ii) The ionised particles between the contacts tend to maintain the arc. If
the arc path is deionised , the arc extinction will be facilitated.
This may be achieved by cooling the arc or by bodily removing the ionised
particles from the space between the contacts
Methods of Arc Extinction
There are two methods of extinguishing the arc in circuit breakers.
1. High resistance method.
2. Low resistance or current zero method
1.High resistance method.
• In this method, arc resistance is made to increase with time so
that current is reduced to a value insufficient to maintain the
arc. Consequently, the current is interrupted or the arc is
extinguished.
• The principal disadvantage of this method is that enormous
energy is dissipated in the arc.
• Therefore, it is employed only in d.c. circuit breakers and low-
capacity a.c. circuit breakers.
The resistance of the arc may be increased by :
(i) Lengthening the arc.
The resistance of the arc is directly proportional to
its length. The length of the arc can be increased
by increasing the gap between contacts.
(ii) Cooling the arc.
Cooling helps in the deionisation of the medium
between the contacts. This increases the arc
resistance. Efficient cooling may be obtained by a
gas blast directed along the arc.
(iii) Reducing X-section of the arc.
If the area of X-section of the arc is reduced, the voltage
necessary to maintain the arc is increased. In other
words, the resistance of the arc path is increased. The
cross-section of the arc can be reduced by letting the arc
pass through a narrow opening or by having smaller area
of contacts.
(iv)Splitting the arc.
The resistance of the arc can be increased by splitting
the arc into a number of smaller arcs in series. Each one
of these arcs experiences the effect of lengthening and
cooling. The arc may be split by introducing some
conducting plates between the contacts.
2. Low resistnace method
• This method is employed for arc extinction in a.c.
circuits only. In this method, arc resistance is kept low
until current is zero where the arc extinguishes
naturally and is prevented from restriking inspite of
the rising voltage across the contacts.
• All modern high power a.c. circuit breakers employ
this method for arc extinction.
• In an a.c. system, current drops to zero after every
half-cycle. At every current zero, the arc extinguishes
for a brief moment. Now the medium between the
contacts contains ions and electrons so that it has
small dielectric strength and can be easily broken
down by the rising contact voltage known as restriking
voltage.
• If such a breakdown does occur, the arc will persist for
another halfcycle. If immediately after current zero,
the dielectric strength of the medium between
contacts is built up more rapidly than the voltage
across the contacts, the arc fails to restrike and the
current will be interrupted.
• The rapid increase of dielectric strength of the medium
near current zero can be achieved by :
(a) causing the ionised particles in the space between
contacts to recombine into neutral molecules.
(b) weeping the ionised particles away and replacing
them by un-ionised particles.
• The de-ionisation of the medium can be achieved by:
(i) lengthening of the gap.
• The dielectric strength of the medium is proportional
to the length of the gap between contacts. Therefore,
by opening the contacts rapidly, higher dielectric
strength of the medium can be achieved.
(ii) high pressure.
• If the pressure in the vicinity of the arc is increased, the density of the
particles constituting the discharge also increases. The increased
density of particles causes higher rate of de-ionisation and
consequently the dielectric strength of the medium between contacts
is increased.
(iii) cooling.
• Natural combination of ionised particles takes place more rapidly if
they are allowed to cool. Therefore, dielectric strength of the medium
between the contacts can be increased by cooling the arc.
(iv) blast effect.
• If the ionised particles between the contacts are swept away and
replaced by unionised particles, the dielectric strength of the medium
can be increased considerably. This may be achieved by a gas blast
directed along the discharge or by forcing oil into the contact space
Important Terms related to C.B.
(i)Arc Voltage.
It is the voltage that appears across the contacts
of the circuit breaker during the arcing period. As
soon as the contacts of the circuit breaker
separate, an arc is formed. The voltage that
appears across the contacts during arcing period is
called the arc voltage.
(ii) Restriking voltage.
It is the transient voltage that appears across the
contacts at or near current zero during arcing
period.
• At current zero, a high-frequency transient voltage appears
across the contacts and is caused by the rapid distribution
of energy between the magnetic and electric fields
associated with the plant and transmission lines of the
system. This transient voltage is known as restriking
voltage.
• The current interruption in the circuit depends upon this
voltage. If the restriking voltage rises more rapidly than the
dielectric strength of the medium between the contacts,
the arc will persist for another half-cycle. On the other
hand, if the dielectric strength of the medium builds up
more rapidly than the restriking voltage, the arc fails to
restrike and the current will be interrupted.
(iii) Recovery voltage.
It is the normal frequency (50 Hz) r.m.s. voltage that
appears across the contacts of the circuit breaker after
final arc extinction. It is approximately equal to the
system voltage.
Classification of Circuit Breakers
(i) Oil circuit breakers -- which employ some
insulating oil (e.g., transformer oil) for arc
extinction.
(ii) Air-blast circuit breakers-- in which high
pressure air-blast is used for extinguishing the arc.
(iii) Sulphur hexafluroide circuit breakers-- in
which sulphur hexafluoride (SF6 ) gas is used for
arc extinction.
(iv) Vacuum circuit breakers -- in which vacuum is
used for arc extinction.
Oil C.B.
• In such circuit breakers, some insulating oil (e.g.,
transformer oil) is used as an arc quenching medium.
• The contacts are opened under oil and an arc is struck
between them. The heat of the arc evaporates the
surrounding oil and dissociates it into a substantial
volume of gaseous hydrogen at high pressure.
• The hydrogen gas occupies a volume about one thousand
times that of the oil decomposed.
• The oil is, therefore, pushed away from the arc and an
expanding hydrogen gas bubble surrounds the arc region
and adjacent portions of the contacts.
Oil C.B.
Oil C.B.
• The arc extinction is facilitated mainly by two
processes.
• Firstly, the hydrogen gas has high heat conductivity
and cools the arc, thus aiding the de-ionisation of the
medium between the contacts.
• Secondly, the gas sets up turbulence in the oil and
forces it into the space between contacts, thus
eliminating the arcing products from the arc path.
• The result is that arc is extinguished and circuit
current interrupted.
Advantages of oil arc quenching medium
(i) It absorbs the arc energy to decompose the oil into
gases which have excellent cooling
properties.
(ii) It acts as an insulator and permits smaller clearance
between live conductors and earthed
components.
(iii) The surrounding oil presents cooling surface in close
proximity to the arc.
(i) It is inflammable and there is a risk of a fire.
(ii) It may form an explosive mixture with air
(iii) The arcing products (e.g., carbon) remain in
the oil and its quality deteriorates with successive
operations. This necessitates periodic checking
and replacement of oil.
Disadvantages of oil arc quenching medium
Types of oil C.B.
(i) Bulk oil circuit breakers which use a large quantity of
oil.
• The oil has to serve two purposes.
(i) it extinguishes the arc during opening of contacts and
(ii) it insulates the currentconducting parts from one
another and from the earthed tank.
Such circuit breakers may be classified into :
(a) Plain break oil circuit breakers (b) Arc control oil
circuit breakers.
(ii) Low oil circuit breakers which use minimum amount
of oil. In such circuit breakers, oil is
used only for arc extinction; the current conducting parts
are insulated by air or porcelain or
organic insulating material.
Air-Blast Circuit Breakers
• These breakers employ a high pressure air-blast as an
arc quenching medium.
• The contacts are opened in a flow of air-blast
established by the opening of blast valve.
• The air-blast cools the arc and sweeps away the arcing
products to the atmosphere.
• This rapidly increases the dielectric strength of the
medium between contacts and prevents from re-
establishing the arc.
• Consequently, the arc is extinguished and flow of
current is interrupted.
Advantages
(i) The risk of fire is eliminated.
(ii) The arcing products are completely removed by the blast
whereas the oil deteriorates with successive operations; the
expense of regular oil replacement is avoided.
(iii) The growth of dielectric strength is so rapid that final contact
gap needed for arc extinction is very small. This reduces the size of
the device.
(iv) The arcing time is very small due to the rapid build up of
dielectric strength between contacts. Therefore, the arc energy is
only a fraction of that in oil circuit breakers, thus resulting in less
burning of contacts.
(v) Due to lesser arc energy, air-blast circuit breakers are very
suitable for conditions where frequent operation is required.
(vi) The energy supplied for arc extinction is obtained from high
Disadvantages
(i) The air has relatively inferior arc extinguishing properties.
(ii) The air-blast circuit breakers are very sensitive to the variations
in the rate of rise of restriking voltage.
(iii) Considerable maintenance is required for the compressor plant
which supplies the air-blast.
• Application
The air blast circuit breakers are finding wide applications in high
voltage installations. Majority of the circuit breakers for voltages
beyond 110 kV are of this type.
Types of Air-Blast Circuit Breakers
• Depending upon the direction of air-blast in relation to
the arc, air-blast circuit breakers are classified into
(i) Axial-blast type
(ii) Cross-blast type
(iii) Radial-blast type
Sulphur Hexaflouride (SF6) Circuit Breakers
• In such circuit breakers, sulphur hexa flouride (SF6) gas is used
as the arc quenching medium.
• The SF6 is an electro-negative gas and has a strong tendency to
absorb free electrons.
• The contacts of the breaker are opened in a high pressure flow
of SF6 gas and an arc is struck between them.
• The conducting free electrons in the arc are rapidly captured by
the gas to form relatively immobile negative ions.
• This loss of conducting electrons in the arc quickly builds up
enough insulation strength to extinguish the arc.
• The SF6 circuit breakers have been found to be very effective
for high power and high voltage service.
Construction
• Fig. shows the parts of a typical SF6 circuit breaker. It consists of fixed
and moving contacts enclosed in a chamber (called arc interruption chamber)
containing SF6 gas.
• This chamber is connected to SF6 gas reservior.
• When the contacts of breaker are opened, the valve mechanism permits a
high pressure SF6 gas from the reservoir to flow towards the arc
interruption chamber.
• The fixed contact is a hollow cylindrical current carrying contact fitted with
an arc horn. The moving contact is also a hollow cylinder with rectangular
holes in the sides to permit the SF6 gas to let out through these holes after
flowing along and across the arc.
• The tips of fixed contact, moving contact and arcing horn are coated with
copper-tungsten arc resistant material.
Construction
Working
• In the closed position of the breaker, the contacts remain surrounded
by SF6 gas at a pressure of about 2·8 kg/cm2.
• When the breaker operates, the moving contact is pulled apart and an
arc is struck between the contacts.
• The movement of the moving contact is synchronised with the opening
of a valve which permits SF6 gas at 14 kg/cm2 pressure from the
reservoir to the arc interruption chamber.
• The high pressure flow of SF6 rapidly absorbs the free electrons in the
arc path to form immobile negative ions which are ineffective as
charge carriers.
• The result is that the medium between the contacts quickly builds up
high dielectric strength and causes the extinction of the arc.
• After the breaker operation (i.e., after arc extinction), the valve is
closed by the action of a set of springs.
Advantages
(i) Due to the superior arc quenching property of SF6, such circuit breakers have
very short arcing time.
(ii) Since the dielectric strength of SF6 gas is 2 to 3 times that of air, such breakers
can interrupt much larger currents.
(iii) The SF6 circuit breaker gives noiselss operation due to its closed gas circuit and
no exhaust to atmosphere unlike the air blast circuit breaker.
(iv) The closed gas enclosure keeps the interior dry so that there is no moisture
problem.
(v) There is no risk of fire in such breakers because SF6 gas is non-inflammable.
(vi) There are no carbon deposits so that tracking and insulation problems are
eliminated.
(vii) The SF6 breakers have low maintenance cost, light foundation requirements
and minimum auxiliary equipment.
(viii) Since SF6 breakers are totally enclosed and sealed from atmosphere, they are
particularly suitable where explosion hazard exists e.g., coal mines.
Disadvantages and Application
(i) SF6 breakers are costly due to the high cost of SF6.
(ii) Since SF6 gas has to be reconditioned after every operation
of the breaker, additional equipment is required for this
purpose.
Applications. A typical SF6 circuit breaker consists of
interrupter units each capable of dealing with currents upto 60
kA and voltages in the range of 50—80 kV. A number of units
are connected in series according to the system voltage. SF6
circuit breakers have been developed for voltages 115 kV to
230 kV, power ratings 10 MVA to 20 MVA and interrupting
time less than 3 cycles.
Vacuum Circuit Breakers (VCB)
• In such breakers, vacuum (degree of vacuum being in the
range from 10−7 to 10−5 torr) is used as the arc quenching
medium.
• Since vacuum offers the highest insulating strength, it has
far superior arc quenching properties than any other
medium.
• For example, when contacts of a breaker are opened in
vacuum, the interruption occurs at first current zero with
dielectric strength between the contacts building up at a
rate thousands of times higher than that obtained with
other circuit breakers.
• The production of arc in a vacuum circuit breaker and
its extinction can be explained as follows : When the
contacts of the breaker are opened in vacuum (10−7 to
10−5 torr), an arc is produced between the contacts by
the ionisation of metal vapours of contacts.
• However, the arc is quickly extinguished because the
metallic vapours, electrons and ions produced during
arc rapidly condense on the surfaces of the circuit
breaker contacts, resulting in quick recovery of
dielectric strength.
Vacuum Circuit Breakers (VCB)
Advantages
(i) They are compact, reliable and have longer life.
(ii) There are no fire hazards.
(iii) There is no generation of gas during and after operation.
(iv) They can interrupt any fault current. The outstanding feature of
a VCB is that it can break any heavy fault current perfectly just
before the contacts reach the definite open position.
(v) They require little maintenance and are quiet in operation.
(vi) They can successfully withstand lightning surges.
(vii) They have low arc energy.
(viii) They have low inertia and hence require smaller power for
control mechanism.
Applications
• For a country like India, where distances are quite
large and accessibility to remote areas difficult, the
installation of such outdoor, maintenance free circuit
breakers should prove a definite advantage.
• Vacuum circuit breakers are being employed for
outdoor applications ranging from 22 kV to 66 kV.
Even with limited rating of say 60 to 100 MVA, they
are suitable for a majority of applications in rural
areas.
MCB(Miniature Circuit Breaker)
. A miniature circuit breaker is an electromagnetic device that carries a
complete molded insulating material. The primary function of this
device is to switch the circuit. This means to automatically open the
circuit (which has been connected to it) when the current passing
through the circuit goes beyond a set value or limit. The device can be
manually switched ON or OFF just like normal switches whenever
necessary.
MCB(Miniature Circuit Breaker)
1. Actuator lever- used to manually trip and reset
the circuit breaker. Also indicates the status of
the circuit breaker (On or Off/tripped). Most
breakers are designed so they can still trip even if
the lever is held or locked in the "on" position.
This is sometimes referred to as "free trip" or
"positive trip" operation.
2. Actuator mechanism - forces the contacts
together or apart
3. Contacts - allow current when touching and
break the current when moved apart
MCB(Miniature Circuit Breaker)
.
4. Terminals
5. Bimetallic strip - separates contacts in response to smaller, longer-term
over currents
6. Calibration screw- allows the manufacturer to precisely adjust the trip
current of the device after assembly
7. Solenoid - separates contacts rapidly in response to high over currents
8. Arc divider/extinguisher
.
ELCB (Earth leakage circuit Breaker)
. An ECLB is one kind of safety device used for
installing an electrical device with high earth
impedance to avoid shock. These devices
identify small stray voltages of the electrical
device on the metal enclosures and intrude the
circuit if a dangerous voltage is identified. The
main purpose of Earth leakage circuit breaker
(ECLB) is to stop damage to humans & animals
due to electric shock.
Faults in Power System
Weather Condition
Equipment Failure
Human Error
Smoke of fire
Miscellaneous
Electrical Faults
Types of Electrical Fault
Fuse
• A fuse is a short piece of wire or thin strip which melts when excessive
current flows through it for sufficient time.
• It is inserted in series with the circuit to be protected. Under normal
operating conditions, the fuse element it at a temperature below its
melting point. Therefore, it carries the normal load current without
overheating.
• However, when a short circuit or overload occurs, the current through
the fuse element increases beyond its rated capacity.
• This raises the temperature and the fuse element melts (or blows out),
disconnecting the circuit protected by it.
• In this way, a fuse protects the machines and equipment from damage
due to excessive currents.
• It is worthwhile to note that a fuse performs both detection and
interruption functions.
How does fuse work?
• A fuse contains a thin wire, which melts if
the current is too high.This breaks the circuit
and so electricity is unable to flow through
the appliance.
• The appliance stops working and any danger
has been averted thin wire Fuses act as an
early warning system, preventing appliances
from being damaged by surges in electricity
and warning owners of faults.
• Symbol for a fuse
Types of Fuse
Selection of fuse
The factors to be considered when selecting a fuse are as follows:
1. Current Rating
The current rating specifies the nominal amperage value of the fuse,
given by the manufacturer as the level of current that the fuse can carry
under normal working condition.
A fuse, which is designed according to an IEC standard, can continuously
operate at 100% of rated current of the fuse. Fuses are temperature-
sensitive devices and the projected life of a fuse can be shortened
drastically when loaded to 100% of its nominal value.
In order to prolong the life of the fuse, the circuit designer should ensure
that the load on the fuse does not exceed the nominal rating listed by the
manufacturer. So a fuse with a current rating of 10A would not be
recommended for operation at more than 7.5A in a 25°C ambient
temperature.
2. Breaking Capaciy
• The breaking capacity is the maximum current which the fuse can
safely break or interrupt at rated voltage.
• When selecting a fuse, one should verify that the breaking capacity of
the fuse is sufficient for circuit operation.
• The interrupting rating must be equal to or greater than the short-
circuit current.
• When a fault or short circuit condition arises, the instantaneous
current passing through the fuse can be several times greater than its
current rating.
• If this current is beyond the level that the fuse can bear, the device
may explode or rupture, causing additional damage. Hence, for safe
operation, it is imperative that the fuse selected is able to withstand
the largest short-circuit current possible and can clear the circuit
safely.
3. Ambient Temperature
• The ambient temperature is a measure of the temperature of the air
immediately surrounding the fuse. Since the fuse is enclosed in a
panel mounted fuse-holder, or placed near other heat dissipating
components, like resistors, the ambient temperature is usually much
higher than the surrounding room temperature.
• The current carrying capacity of a fuse varies as the ambient
temperature changes. Operating the fuse at high ambient
temperatures can potentially shorten its life. On the other hand,
lower ambient temperatures can lead to longer fuse life.
The fuse also becomes hotter as the operating current becomes equal
to or greater than the breaking capacity. Experiments have shown that a
fuse will continue to work indefinitely, as long as the load does not
exceed 75% of the nominal current rating.
4. Fuse Types and Time-current Characteristics
• Fuses can be of different types based on the speed at which
they can blow. It is helpful to define fuses using time-
current curves, since fuses with the same current rating can
be represented by considerably different time-current
curves.
• Fast-acting fuses will melt rapidly and sever the connection
immediately when subjected to high current levels.
• This characteristic becomes important in applications
where speed is critical, such as in variable speed drives.
Fast-acting fuses are used for distribution feeders and
branch circuits.
5. Nominal Melting I2t Rating
• The fuse's nominal melting I2t rating must also meet the startup pulse
requirements. Nominal melting I2t is a measure of the energy required to
melt the fusing element and is expressed as "Ampere Squared Seconds"
(A2Sec). There two parts to a fuse's "reaction time".
• The time it takes for the fuse element to melt (also known as the melting
time, Tm).
• The time it takes for the electrical arc to settle (also known as the arcing
time, Ta).
• The total time it takes to open the fault is known as the total clearing time.
Tc = Tm + Ta
• The circuit designer should select a fuse whose I2t rating is greater than the
energy of the inrush current pulse. This ensures that the fuse will not cause a
nuisance opening during transient conditions.
• In order to achieve reliable system operation, it is a good design practice to
select a fuse such that the energy of the current pulse is not more than 20%
of the nominal melting I2t rating of the fuse.
6. Maximum Fault Current
• The Interrupting Rating of a fuse must meet or exceed the Maximum
Fault Current of the circuit.
7. Voltage Rating
• A fuse can safely interrupt its rated short circuit current as long as the
voltage is less than or equal to its rated voltage.
Advantages
• Fuse is cheapest type of protection in an electrical circuit
• Fuse needs zero maintenance
• Operation of fuse is simple and no complexity is involved
• Fuse has the ability to interrupt enormous short circuit current
without producing noise, flame, gas or smoke
• The operation time of fuse can be made much smaller than
operation of circuit breaker. It is the primary protection device
against short circuits
• It affords current limiting effect under short-circuit conditions
• Fuse inverse time current characteristic has the ability to use for
over-load protection
Disadvantages
• During short circuit or overload once fuse blows off
replacing of fuse takes time. During this period the
circuit lost power
• When fuses are connected in series it is difficult to
discriminate the fuse unless the fuse has significant
size difference
www.paruluniversity.ac.in

More Related Content

Similar to arc phenomena and c.b.

Switchgear and protection engineering Lecture 03.pptx
Switchgear and protection engineering Lecture 03.pptxSwitchgear and protection engineering Lecture 03.pptx
Switchgear and protection engineering Lecture 03.pptxLoitaFredy
 
Circuit breakers
Circuit breakersCircuit breakers
Circuit breakersali raza
 
ARC PHENOMENON (Power Protection System).pptx
ARC PHENOMENON (Power Protection System).pptxARC PHENOMENON (Power Protection System).pptx
ARC PHENOMENON (Power Protection System).pptxBadhonBiswas3
 
3.1 Overhead Line Insulators,Underground Cables (1).pptx
3.1 Overhead Line Insulators,Underground Cables (1).pptx3.1 Overhead Line Insulators,Underground Cables (1).pptx
3.1 Overhead Line Insulators,Underground Cables (1).pptxBalaMurugan992669
 
Circuit breaker(encrypted)
Circuit breaker(encrypted)Circuit breaker(encrypted)
Circuit breaker(encrypted)Rohini Haridas
 
1502957341lectrure_3_KUET [Autosaved] [Autosaved].pptx
1502957341lectrure_3_KUET [Autosaved] [Autosaved].pptx1502957341lectrure_3_KUET [Autosaved] [Autosaved].pptx
1502957341lectrure_3_KUET [Autosaved] [Autosaved].pptxTajmun1
 
SGPD(MOD-4).pdf...................................................
SGPD(MOD-4).pdf...................................................SGPD(MOD-4).pdf...................................................
SGPD(MOD-4).pdf...................................................MANOJ KHARADE
 
SGPD(MOD-4).pdfsgp .....................
SGPD(MOD-4).pdfsgp .....................SGPD(MOD-4).pdfsgp .....................
SGPD(MOD-4).pdfsgp .....................MANOJ KHARADE
 
Circuit breaker
Circuit breakerCircuit breaker
Circuit breakerdipak doud
 
Lab # 03 Workshop Practice.pptx
Lab # 03 Workshop Practice.pptxLab # 03 Workshop Practice.pptx
Lab # 03 Workshop Practice.pptxTALHA RIAZ PERSOTA
 
Circuit breaker
Circuit breakerCircuit breaker
Circuit breakerdipak doud
 

Similar to arc phenomena and c.b. (20)

UNIT IV Circuit Breaker.pptx
UNIT IV Circuit Breaker.pptxUNIT IV Circuit Breaker.pptx
UNIT IV Circuit Breaker.pptx
 
Switchgear and protection engineering Lecture 03.pptx
Switchgear and protection engineering Lecture 03.pptxSwitchgear and protection engineering Lecture 03.pptx
Switchgear and protection engineering Lecture 03.pptx
 
Circuit breaker
Circuit breakerCircuit breaker
Circuit breaker
 
Circuit breakers
Circuit breakersCircuit breakers
Circuit breakers
 
Circuit Breakers
Circuit BreakersCircuit Breakers
Circuit Breakers
 
ARC PHENOMENON (Power Protection System).pptx
ARC PHENOMENON (Power Protection System).pptxARC PHENOMENON (Power Protection System).pptx
ARC PHENOMENON (Power Protection System).pptx
 
Lightening Arrester.pptx
Lightening Arrester.pptxLightening Arrester.pptx
Lightening Arrester.pptx
 
3.1 Overhead Line Insulators,Underground Cables (1).pptx
3.1 Overhead Line Insulators,Underground Cables (1).pptx3.1 Overhead Line Insulators,Underground Cables (1).pptx
3.1 Overhead Line Insulators,Underground Cables (1).pptx
 
Mod5part1
Mod5part1Mod5part1
Mod5part1
 
Circuit breaker(encrypted)
Circuit breaker(encrypted)Circuit breaker(encrypted)
Circuit breaker(encrypted)
 
1502957341lectrure_3_KUET [Autosaved] [Autosaved].pptx
1502957341lectrure_3_KUET [Autosaved] [Autosaved].pptx1502957341lectrure_3_KUET [Autosaved] [Autosaved].pptx
1502957341lectrure_3_KUET [Autosaved] [Autosaved].pptx
 
SGPD(MOD-4).pdf...................................................
SGPD(MOD-4).pdf...................................................SGPD(MOD-4).pdf...................................................
SGPD(MOD-4).pdf...................................................
 
SGPD(MOD-4).pdfsgp .....................
SGPD(MOD-4).pdfsgp .....................SGPD(MOD-4).pdfsgp .....................
SGPD(MOD-4).pdfsgp .....................
 
Circuit breaker
Circuit breakerCircuit breaker
Circuit breaker
 
Lab # 03 Workshop Practice.pptx
Lab # 03 Workshop Practice.pptxLab # 03 Workshop Practice.pptx
Lab # 03 Workshop Practice.pptx
 
Surge arrester
Surge arresterSurge arrester
Surge arrester
 
Lightning arresters
Lightning arrestersLightning arresters
Lightning arresters
 
Air Circuit breaker
Air Circuit breakerAir Circuit breaker
Air Circuit breaker
 
air type circuit breaker
air type circuit breakerair type circuit breaker
air type circuit breaker
 
Circuit breaker
Circuit breakerCircuit breaker
Circuit breaker
 

Recently uploaded

The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlysanyuktamishra911
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINESIVASHANKAR N
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdfankushspencer015
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Dr.Costas Sachpazis
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performancesivaprakash250
 
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsRussian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...Call Girls in Nagpur High Profile
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordAsst.prof M.Gokilavani
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSSIVASHANKAR N
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...Call Girls in Nagpur High Profile
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfKamal Acharya
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingrknatarajan
 

Recently uploaded (20)

The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsRussian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
 

arc phenomena and c.b.

  • 1. ETSE Ms. Kinjal G. Shah, Assistant Professor Electrical Engineering Department
  • 3. SWITCHGEARS : Definition • Switchgear is a general term covering all equipment used for : - switching, - protection, - control and - isolation in a power system. • All equipment used for fault clearing is covered by the term switchgear. • Switchgears are used in Generation, Transmission and Distribution Systems, whereas, Control Gears are used in Consumer Circuits.
  • 4. Necessity of Switchgears • Switchgears are necessary at every switching point in the power system because there are several voltage levels and fault levels which has to be controlled and protected by accessible switching devices and for isolation, if the need arises.
  • 5. Principal Switchgears • Principal Switchgears are the main equipment concerned with the process of switching and isolating circuits in a power system.
  • 6. Auxiliary Switchgears • Auxiliary Switchgears are secondary or subsidiary equipment which assist the main switchgear equipment in the control, measurement, protection and fault- clearing process.
  • 7. Examples of Principal Switchgears: • SWITCHING DEVICES (a) Circuit Breakers (b) Isolators (Disconnector or Disconnecting Switch) (c) Earthing Switches (d) Load Switches (Ring Main Units) (e) Contactors
  • 8. Examples of Auxiliary Switchgears • PROTECTION DEVICES (i) Protection Relays (j) Lightning Arresters (k) Feeder Pillars (l) Fuses. • SENSING DEVICES Voltage (m) Potential Transformers (n) Current Transformers
  • 9. Examples of Auxiliary Switchgears : • CONTROL (COMPENSATION) DEVICES (o) Series Inductive Reactors (p) Shunt Inductive Reactors (q) Series Capacitive Reactors (r) Shunt Capacitive Reactors • AUXILIARY POWER SUPPLY DEVICES (s)Tripping Units (Battery Bank & Charger)
  • 10. SWITCHGEAR : Gear for Switching Switching Devices -Circuit Breaker - Isolators - Switches Control & Sensing Devices -CT, PT - Reators - Tripping Units Decision Making Devices -Protective Relays -Fuses -Lightning Arrester
  • 11. What is an Arc? • During opening of current carrying contacts in a circuit breaker the medium in between opening contacts become highly ionized through which the interrupting current gets low resistive path and continues to flow through this path even the contacts are physically separated. • During the flowing of current from one contact to other the path becomes so heated that it glows. This is called arc.
  • 12. Arc phenomena • When a short-circuit occurs, a heavy current flows through the contacts of the circuit breaker before they are opened by the protective system. • At the instant when the contacts begin to separate, the contact area decreases rapidly and large fault current causes increased current density and hence risein temperature. • The heat produced in the medium between contacts (usually the medium is oil or air)is sufficient to ionise the air or vapourise and ionise the oil. • The ionised air or vapour acts as conductor and an arc is struck between the contacts.
  • 13. • The p.d. between the contacts is quite small and is just sufficient to maintain the arc. The arc provides a low resistance path and consequently the current in the circuit remains uninterrupted so long as the arc persists. • During the arcing period, the current flowing between the contacts depends upon the arc resistance. • The greater the arc resistance, the smaller the current that flows between the contacts. The arc resistance depends upon the following factors : (i) Degree of ionisation — the arc resistance increases with the decrease in the number of ionised particles between the contacts. (ii) Length of the arc — the arc resistance increases with the length of the arc i.e., separation of contacts (iii) Cross-section of arc — the arc resistance increases with the decrease in area of X-section of the arc.
  • 14. Principles of Arc Extinction • The methods of arc extinction, it is necessary to examine the factors responsible for the maintenance of arc between the contacts. These are : (i) p.d. between the contacts (ii) ionised particles between contacts Taking these in turn, (i) When the contacts have a small separation, the p.d. between them is sufficient to maintain the arc. One way to extinguish the arc is to separate the contacts to such a distance that p.d. becomes inadequate to maintain the arc. However, this method is impracticable in high voltage system where a separation of many metres may be required. (ii) The ionised particles between the contacts tend to maintain the arc. If the arc path is deionised , the arc extinction will be facilitated. This may be achieved by cooling the arc or by bodily removing the ionised particles from the space between the contacts
  • 15. Methods of Arc Extinction There are two methods of extinguishing the arc in circuit breakers. 1. High resistance method. 2. Low resistance or current zero method 1.High resistance method. • In this method, arc resistance is made to increase with time so that current is reduced to a value insufficient to maintain the arc. Consequently, the current is interrupted or the arc is extinguished. • The principal disadvantage of this method is that enormous energy is dissipated in the arc. • Therefore, it is employed only in d.c. circuit breakers and low- capacity a.c. circuit breakers.
  • 16. The resistance of the arc may be increased by : (i) Lengthening the arc. The resistance of the arc is directly proportional to its length. The length of the arc can be increased by increasing the gap between contacts. (ii) Cooling the arc. Cooling helps in the deionisation of the medium between the contacts. This increases the arc resistance. Efficient cooling may be obtained by a gas blast directed along the arc.
  • 17. (iii) Reducing X-section of the arc. If the area of X-section of the arc is reduced, the voltage necessary to maintain the arc is increased. In other words, the resistance of the arc path is increased. The cross-section of the arc can be reduced by letting the arc pass through a narrow opening or by having smaller area of contacts. (iv)Splitting the arc. The resistance of the arc can be increased by splitting the arc into a number of smaller arcs in series. Each one of these arcs experiences the effect of lengthening and cooling. The arc may be split by introducing some conducting plates between the contacts.
  • 18. 2. Low resistnace method • This method is employed for arc extinction in a.c. circuits only. In this method, arc resistance is kept low until current is zero where the arc extinguishes naturally and is prevented from restriking inspite of the rising voltage across the contacts. • All modern high power a.c. circuit breakers employ this method for arc extinction.
  • 19. • In an a.c. system, current drops to zero after every half-cycle. At every current zero, the arc extinguishes for a brief moment. Now the medium between the contacts contains ions and electrons so that it has small dielectric strength and can be easily broken down by the rising contact voltage known as restriking voltage. • If such a breakdown does occur, the arc will persist for another halfcycle. If immediately after current zero, the dielectric strength of the medium between contacts is built up more rapidly than the voltage across the contacts, the arc fails to restrike and the current will be interrupted.
  • 20. • The rapid increase of dielectric strength of the medium near current zero can be achieved by : (a) causing the ionised particles in the space between contacts to recombine into neutral molecules. (b) weeping the ionised particles away and replacing them by un-ionised particles. • The de-ionisation of the medium can be achieved by: (i) lengthening of the gap. • The dielectric strength of the medium is proportional to the length of the gap between contacts. Therefore, by opening the contacts rapidly, higher dielectric strength of the medium can be achieved.
  • 21. (ii) high pressure. • If the pressure in the vicinity of the arc is increased, the density of the particles constituting the discharge also increases. The increased density of particles causes higher rate of de-ionisation and consequently the dielectric strength of the medium between contacts is increased. (iii) cooling. • Natural combination of ionised particles takes place more rapidly if they are allowed to cool. Therefore, dielectric strength of the medium between the contacts can be increased by cooling the arc. (iv) blast effect. • If the ionised particles between the contacts are swept away and replaced by unionised particles, the dielectric strength of the medium can be increased considerably. This may be achieved by a gas blast directed along the discharge or by forcing oil into the contact space
  • 22. Important Terms related to C.B. (i)Arc Voltage. It is the voltage that appears across the contacts of the circuit breaker during the arcing period. As soon as the contacts of the circuit breaker separate, an arc is formed. The voltage that appears across the contacts during arcing period is called the arc voltage. (ii) Restriking voltage. It is the transient voltage that appears across the contacts at or near current zero during arcing period.
  • 23. • At current zero, a high-frequency transient voltage appears across the contacts and is caused by the rapid distribution of energy between the magnetic and electric fields associated with the plant and transmission lines of the system. This transient voltage is known as restriking voltage. • The current interruption in the circuit depends upon this voltage. If the restriking voltage rises more rapidly than the dielectric strength of the medium between the contacts, the arc will persist for another half-cycle. On the other hand, if the dielectric strength of the medium builds up more rapidly than the restriking voltage, the arc fails to restrike and the current will be interrupted.
  • 24. (iii) Recovery voltage. It is the normal frequency (50 Hz) r.m.s. voltage that appears across the contacts of the circuit breaker after final arc extinction. It is approximately equal to the system voltage.
  • 25. Classification of Circuit Breakers (i) Oil circuit breakers -- which employ some insulating oil (e.g., transformer oil) for arc extinction. (ii) Air-blast circuit breakers-- in which high pressure air-blast is used for extinguishing the arc. (iii) Sulphur hexafluroide circuit breakers-- in which sulphur hexafluoride (SF6 ) gas is used for arc extinction. (iv) Vacuum circuit breakers -- in which vacuum is used for arc extinction.
  • 26. Oil C.B. • In such circuit breakers, some insulating oil (e.g., transformer oil) is used as an arc quenching medium. • The contacts are opened under oil and an arc is struck between them. The heat of the arc evaporates the surrounding oil and dissociates it into a substantial volume of gaseous hydrogen at high pressure. • The hydrogen gas occupies a volume about one thousand times that of the oil decomposed. • The oil is, therefore, pushed away from the arc and an expanding hydrogen gas bubble surrounds the arc region and adjacent portions of the contacts.
  • 28. Oil C.B. • The arc extinction is facilitated mainly by two processes. • Firstly, the hydrogen gas has high heat conductivity and cools the arc, thus aiding the de-ionisation of the medium between the contacts. • Secondly, the gas sets up turbulence in the oil and forces it into the space between contacts, thus eliminating the arcing products from the arc path. • The result is that arc is extinguished and circuit current interrupted.
  • 29. Advantages of oil arc quenching medium (i) It absorbs the arc energy to decompose the oil into gases which have excellent cooling properties. (ii) It acts as an insulator and permits smaller clearance between live conductors and earthed components. (iii) The surrounding oil presents cooling surface in close proximity to the arc.
  • 30. (i) It is inflammable and there is a risk of a fire. (ii) It may form an explosive mixture with air (iii) The arcing products (e.g., carbon) remain in the oil and its quality deteriorates with successive operations. This necessitates periodic checking and replacement of oil. Disadvantages of oil arc quenching medium
  • 31. Types of oil C.B. (i) Bulk oil circuit breakers which use a large quantity of oil. • The oil has to serve two purposes. (i) it extinguishes the arc during opening of contacts and (ii) it insulates the currentconducting parts from one another and from the earthed tank. Such circuit breakers may be classified into : (a) Plain break oil circuit breakers (b) Arc control oil circuit breakers.
  • 32. (ii) Low oil circuit breakers which use minimum amount of oil. In such circuit breakers, oil is used only for arc extinction; the current conducting parts are insulated by air or porcelain or organic insulating material.
  • 33. Air-Blast Circuit Breakers • These breakers employ a high pressure air-blast as an arc quenching medium. • The contacts are opened in a flow of air-blast established by the opening of blast valve. • The air-blast cools the arc and sweeps away the arcing products to the atmosphere. • This rapidly increases the dielectric strength of the medium between contacts and prevents from re- establishing the arc. • Consequently, the arc is extinguished and flow of current is interrupted.
  • 34. Advantages (i) The risk of fire is eliminated. (ii) The arcing products are completely removed by the blast whereas the oil deteriorates with successive operations; the expense of regular oil replacement is avoided. (iii) The growth of dielectric strength is so rapid that final contact gap needed for arc extinction is very small. This reduces the size of the device. (iv) The arcing time is very small due to the rapid build up of dielectric strength between contacts. Therefore, the arc energy is only a fraction of that in oil circuit breakers, thus resulting in less burning of contacts. (v) Due to lesser arc energy, air-blast circuit breakers are very suitable for conditions where frequent operation is required. (vi) The energy supplied for arc extinction is obtained from high
  • 35. Disadvantages (i) The air has relatively inferior arc extinguishing properties. (ii) The air-blast circuit breakers are very sensitive to the variations in the rate of rise of restriking voltage. (iii) Considerable maintenance is required for the compressor plant which supplies the air-blast. • Application The air blast circuit breakers are finding wide applications in high voltage installations. Majority of the circuit breakers for voltages beyond 110 kV are of this type.
  • 36. Types of Air-Blast Circuit Breakers • Depending upon the direction of air-blast in relation to the arc, air-blast circuit breakers are classified into (i) Axial-blast type (ii) Cross-blast type (iii) Radial-blast type
  • 37. Sulphur Hexaflouride (SF6) Circuit Breakers • In such circuit breakers, sulphur hexa flouride (SF6) gas is used as the arc quenching medium. • The SF6 is an electro-negative gas and has a strong tendency to absorb free electrons. • The contacts of the breaker are opened in a high pressure flow of SF6 gas and an arc is struck between them. • The conducting free electrons in the arc are rapidly captured by the gas to form relatively immobile negative ions. • This loss of conducting electrons in the arc quickly builds up enough insulation strength to extinguish the arc. • The SF6 circuit breakers have been found to be very effective for high power and high voltage service.
  • 38. Construction • Fig. shows the parts of a typical SF6 circuit breaker. It consists of fixed and moving contacts enclosed in a chamber (called arc interruption chamber) containing SF6 gas. • This chamber is connected to SF6 gas reservior. • When the contacts of breaker are opened, the valve mechanism permits a high pressure SF6 gas from the reservoir to flow towards the arc interruption chamber. • The fixed contact is a hollow cylindrical current carrying contact fitted with an arc horn. The moving contact is also a hollow cylinder with rectangular holes in the sides to permit the SF6 gas to let out through these holes after flowing along and across the arc. • The tips of fixed contact, moving contact and arcing horn are coated with copper-tungsten arc resistant material.
  • 40. Working • In the closed position of the breaker, the contacts remain surrounded by SF6 gas at a pressure of about 2·8 kg/cm2. • When the breaker operates, the moving contact is pulled apart and an arc is struck between the contacts. • The movement of the moving contact is synchronised with the opening of a valve which permits SF6 gas at 14 kg/cm2 pressure from the reservoir to the arc interruption chamber. • The high pressure flow of SF6 rapidly absorbs the free electrons in the arc path to form immobile negative ions which are ineffective as charge carriers. • The result is that the medium between the contacts quickly builds up high dielectric strength and causes the extinction of the arc. • After the breaker operation (i.e., after arc extinction), the valve is closed by the action of a set of springs.
  • 41. Advantages (i) Due to the superior arc quenching property of SF6, such circuit breakers have very short arcing time. (ii) Since the dielectric strength of SF6 gas is 2 to 3 times that of air, such breakers can interrupt much larger currents. (iii) The SF6 circuit breaker gives noiselss operation due to its closed gas circuit and no exhaust to atmosphere unlike the air blast circuit breaker. (iv) The closed gas enclosure keeps the interior dry so that there is no moisture problem. (v) There is no risk of fire in such breakers because SF6 gas is non-inflammable. (vi) There are no carbon deposits so that tracking and insulation problems are eliminated. (vii) The SF6 breakers have low maintenance cost, light foundation requirements and minimum auxiliary equipment. (viii) Since SF6 breakers are totally enclosed and sealed from atmosphere, they are particularly suitable where explosion hazard exists e.g., coal mines.
  • 42. Disadvantages and Application (i) SF6 breakers are costly due to the high cost of SF6. (ii) Since SF6 gas has to be reconditioned after every operation of the breaker, additional equipment is required for this purpose. Applications. A typical SF6 circuit breaker consists of interrupter units each capable of dealing with currents upto 60 kA and voltages in the range of 50—80 kV. A number of units are connected in series according to the system voltage. SF6 circuit breakers have been developed for voltages 115 kV to 230 kV, power ratings 10 MVA to 20 MVA and interrupting time less than 3 cycles.
  • 43. Vacuum Circuit Breakers (VCB) • In such breakers, vacuum (degree of vacuum being in the range from 10−7 to 10−5 torr) is used as the arc quenching medium. • Since vacuum offers the highest insulating strength, it has far superior arc quenching properties than any other medium. • For example, when contacts of a breaker are opened in vacuum, the interruption occurs at first current zero with dielectric strength between the contacts building up at a rate thousands of times higher than that obtained with other circuit breakers.
  • 44. • The production of arc in a vacuum circuit breaker and its extinction can be explained as follows : When the contacts of the breaker are opened in vacuum (10−7 to 10−5 torr), an arc is produced between the contacts by the ionisation of metal vapours of contacts. • However, the arc is quickly extinguished because the metallic vapours, electrons and ions produced during arc rapidly condense on the surfaces of the circuit breaker contacts, resulting in quick recovery of dielectric strength. Vacuum Circuit Breakers (VCB)
  • 45.
  • 46. Advantages (i) They are compact, reliable and have longer life. (ii) There are no fire hazards. (iii) There is no generation of gas during and after operation. (iv) They can interrupt any fault current. The outstanding feature of a VCB is that it can break any heavy fault current perfectly just before the contacts reach the definite open position. (v) They require little maintenance and are quiet in operation. (vi) They can successfully withstand lightning surges. (vii) They have low arc energy. (viii) They have low inertia and hence require smaller power for control mechanism.
  • 47. Applications • For a country like India, where distances are quite large and accessibility to remote areas difficult, the installation of such outdoor, maintenance free circuit breakers should prove a definite advantage. • Vacuum circuit breakers are being employed for outdoor applications ranging from 22 kV to 66 kV. Even with limited rating of say 60 to 100 MVA, they are suitable for a majority of applications in rural areas.
  • 48. MCB(Miniature Circuit Breaker) . A miniature circuit breaker is an electromagnetic device that carries a complete molded insulating material. The primary function of this device is to switch the circuit. This means to automatically open the circuit (which has been connected to it) when the current passing through the circuit goes beyond a set value or limit. The device can be manually switched ON or OFF just like normal switches whenever necessary.
  • 49. MCB(Miniature Circuit Breaker) 1. Actuator lever- used to manually trip and reset the circuit breaker. Also indicates the status of the circuit breaker (On or Off/tripped). Most breakers are designed so they can still trip even if the lever is held or locked in the "on" position. This is sometimes referred to as "free trip" or "positive trip" operation. 2. Actuator mechanism - forces the contacts together or apart 3. Contacts - allow current when touching and break the current when moved apart
  • 50. MCB(Miniature Circuit Breaker) . 4. Terminals 5. Bimetallic strip - separates contacts in response to smaller, longer-term over currents 6. Calibration screw- allows the manufacturer to precisely adjust the trip current of the device after assembly 7. Solenoid - separates contacts rapidly in response to high over currents 8. Arc divider/extinguisher .
  • 51. ELCB (Earth leakage circuit Breaker) . An ECLB is one kind of safety device used for installing an electrical device with high earth impedance to avoid shock. These devices identify small stray voltages of the electrical device on the metal enclosures and intrude the circuit if a dangerous voltage is identified. The main purpose of Earth leakage circuit breaker (ECLB) is to stop damage to humans & animals due to electric shock.
  • 52. Faults in Power System
  • 60. Fuse • A fuse is a short piece of wire or thin strip which melts when excessive current flows through it for sufficient time. • It is inserted in series with the circuit to be protected. Under normal operating conditions, the fuse element it at a temperature below its melting point. Therefore, it carries the normal load current without overheating. • However, when a short circuit or overload occurs, the current through the fuse element increases beyond its rated capacity. • This raises the temperature and the fuse element melts (or blows out), disconnecting the circuit protected by it. • In this way, a fuse protects the machines and equipment from damage due to excessive currents. • It is worthwhile to note that a fuse performs both detection and interruption functions.
  • 61. How does fuse work? • A fuse contains a thin wire, which melts if the current is too high.This breaks the circuit and so electricity is unable to flow through the appliance. • The appliance stops working and any danger has been averted thin wire Fuses act as an early warning system, preventing appliances from being damaged by surges in electricity and warning owners of faults. • Symbol for a fuse
  • 63. Selection of fuse The factors to be considered when selecting a fuse are as follows: 1. Current Rating The current rating specifies the nominal amperage value of the fuse, given by the manufacturer as the level of current that the fuse can carry under normal working condition. A fuse, which is designed according to an IEC standard, can continuously operate at 100% of rated current of the fuse. Fuses are temperature- sensitive devices and the projected life of a fuse can be shortened drastically when loaded to 100% of its nominal value. In order to prolong the life of the fuse, the circuit designer should ensure that the load on the fuse does not exceed the nominal rating listed by the manufacturer. So a fuse with a current rating of 10A would not be recommended for operation at more than 7.5A in a 25°C ambient temperature.
  • 64. 2. Breaking Capaciy • The breaking capacity is the maximum current which the fuse can safely break or interrupt at rated voltage. • When selecting a fuse, one should verify that the breaking capacity of the fuse is sufficient for circuit operation. • The interrupting rating must be equal to or greater than the short- circuit current. • When a fault or short circuit condition arises, the instantaneous current passing through the fuse can be several times greater than its current rating. • If this current is beyond the level that the fuse can bear, the device may explode or rupture, causing additional damage. Hence, for safe operation, it is imperative that the fuse selected is able to withstand the largest short-circuit current possible and can clear the circuit safely.
  • 65. 3. Ambient Temperature • The ambient temperature is a measure of the temperature of the air immediately surrounding the fuse. Since the fuse is enclosed in a panel mounted fuse-holder, or placed near other heat dissipating components, like resistors, the ambient temperature is usually much higher than the surrounding room temperature. • The current carrying capacity of a fuse varies as the ambient temperature changes. Operating the fuse at high ambient temperatures can potentially shorten its life. On the other hand, lower ambient temperatures can lead to longer fuse life. The fuse also becomes hotter as the operating current becomes equal to or greater than the breaking capacity. Experiments have shown that a fuse will continue to work indefinitely, as long as the load does not exceed 75% of the nominal current rating.
  • 66. 4. Fuse Types and Time-current Characteristics • Fuses can be of different types based on the speed at which they can blow. It is helpful to define fuses using time- current curves, since fuses with the same current rating can be represented by considerably different time-current curves. • Fast-acting fuses will melt rapidly and sever the connection immediately when subjected to high current levels. • This characteristic becomes important in applications where speed is critical, such as in variable speed drives. Fast-acting fuses are used for distribution feeders and branch circuits.
  • 67. 5. Nominal Melting I2t Rating • The fuse's nominal melting I2t rating must also meet the startup pulse requirements. Nominal melting I2t is a measure of the energy required to melt the fusing element and is expressed as "Ampere Squared Seconds" (A2Sec). There two parts to a fuse's "reaction time". • The time it takes for the fuse element to melt (also known as the melting time, Tm). • The time it takes for the electrical arc to settle (also known as the arcing time, Ta). • The total time it takes to open the fault is known as the total clearing time. Tc = Tm + Ta • The circuit designer should select a fuse whose I2t rating is greater than the energy of the inrush current pulse. This ensures that the fuse will not cause a nuisance opening during transient conditions. • In order to achieve reliable system operation, it is a good design practice to select a fuse such that the energy of the current pulse is not more than 20% of the nominal melting I2t rating of the fuse.
  • 68. 6. Maximum Fault Current • The Interrupting Rating of a fuse must meet or exceed the Maximum Fault Current of the circuit. 7. Voltage Rating • A fuse can safely interrupt its rated short circuit current as long as the voltage is less than or equal to its rated voltage.
  • 69. Advantages • Fuse is cheapest type of protection in an electrical circuit • Fuse needs zero maintenance • Operation of fuse is simple and no complexity is involved • Fuse has the ability to interrupt enormous short circuit current without producing noise, flame, gas or smoke • The operation time of fuse can be made much smaller than operation of circuit breaker. It is the primary protection device against short circuits • It affords current limiting effect under short-circuit conditions • Fuse inverse time current characteristic has the ability to use for over-load protection
  • 70. Disadvantages • During short circuit or overload once fuse blows off replacing of fuse takes time. During this period the circuit lost power • When fuses are connected in series it is difficult to discriminate the fuse unless the fuse has significant size difference