SPECIFICATION:
AlarmLineTM
LINEAR HEAT DETECTION SYSTEM
1. GENERAL SPECIFICATION
1.1 The contractor shall provide an AlarmLine Linear Heat Detector for early detection of
fire or overheat condition in protected areas or equipment. The AlarmLine Linear Heat
Detector shall consist of AlarmLine Sensor Cable and AlarmLine FACP (Fire Alarm
Control Panel) Interface Module. The sensor cable shall be an analog (integrating)
type linear heat detector. The alarm temperature shall be programmed in the FACP
Interface Module. The FACP Interface Module shall communicate alarm and trouble
conditions to the Fire Alarm Control Panel.
1.2 The AlarmLine Linear Heat Detector must be manufactured and/or supplied by: Kidde
Fire Systems, 400 Main Street, Ashland, MA 01721, U.S.A.,
1.3 The manufacturer shall warrant the AlarmLine Linear Heat Detector manufactured by it
for a period of eighteen (18) months from the date of shipment.
1.4 The system shall be supplied and installed by a factory authorized Kidde Fire Systems
distributor. The distributor shall be trained by the manufacturer to design, install, test
and maintain the AlarmLine Linear Heat Detector and shall be able to produce a
certificate stating such on request.
1.5 The factory authorized Kidde Fire Systems distributor shall confirm in writing that he
stocks a full complement of spare parts and offers 24-hour emergency service for all
equipment being furnished.
1.6 All materials and equipment used for this project shall be new and unused.
2. CODES/STANDARDS COMPLIANCE
2.1 The design, installation, testing and maintenance of the AlarmLine Linear Heat
Detector shall be in accordance to the following codes, standards and regulatory
bodies:
A. NFPA 70: National Electrical Code
B. NFPA 72: National Fire Alarm Code
C. Factory Mutual Approval Guide (latest edition).
D. Requirements of the local Authority Having Jurisdiction.
2.2 The AlarmLine Linear Heat Detector shall be Factory Mutual System (FM) approved.
2.3 The manufacturer of the AlarmLine Linear Heat Detector shall have a minimum of 15
years experience in the design, production and distribution of fire detection and fire
alarm systems.
SPECIFICATION:
AlarmLineTM
LINEAR HEAT DETECTION SYSTEM
2.4 The manufacturer of the Fire Alarm-Suppression system shall be certified to ISO 9001
for a minimum period of 5 years for the design, production and distribution of fire
detection and fire alarm systems.
3. SYSTEM DESCRIPTION
3.1 The Linear Heat Detector shall consist of an AlarmLine Sensor Cable and an
AlarmLine FACP Interface Module. The Sensor Cable shall be connected to the
AlarmLine FACP Interface Module that communicates through relays, alarm and
trouble conditions to the fire alarm control panel. The Sensor Cable alarm temperature
shall be field adjustable through the FACP Interface Module.
4. COMPONENTS – DESCRIPTION AND OPERATION
4.1 Linear Heat Detector Sensor Cable
A. The Linear Heat Detector Sensor Cable shall be an integrating or averaging type
detector cable that detects a localized hot spot or a low-level temperature increase
over its entire length. Fixed temperature sensor cable is not acceptable.
B. Changes in temperature shall produce a change in resistance between the Sensor
Cable conductors. This resistance change shall be monitored by the FACP Interface
Module to detect an alarm condition.
C. The Sensor Cable shall be capable of self-restoration when temperature drops below
its set point, provided it has not been heated above the temperature point of 257° F
(125° C).
D. The Sensor Cable shall consist of four 26AWG solid copper conductors each
insulated with a negative temperature coefficient material. The conductors shall be
twisted at a rate of approximately thirty turns per foot (90 per meter) to cancel out
potential high voltage inductance. The conductor insulation shall be color coded for
ease of installation. The sensor cable shall have an outer protective extrusion of
high temperature PVC material.
E. [OPTIONAL FOR -016 SENSOR] The sensor cable shall have an additional outer
extrusion of nylon as additional protection against harsh environments.
F. [OPTIONAL FOR -019 SENSOR] The sensor cable shall have an outer braid of
Phosphor Bronze to increase its tensile strength and for protection against abrasion.
G. The Sensor Cable shall be approved for installation in classified hazardous areas
when installed with an intrinsic safety barrier.
4.2 Linear Heat Detector FACP Interface Module
A. The FACP Interface Module shall monitor the resistance of the sensor cable for an
SPECIFICATION:
AlarmLineTM
LINEAR HEAT DETECTION SYSTEM
alarm condition.
B. The Sensor Cable alarm set point shall be set in the FACP Interface Module.
C. The FACP Interface Module shall be cable of monitoring up to 3,200 ft (1000 m) of
Sensor Cable.
D. The FACP Interface Module shall be capable of monitoring the sensor cable for both
open and short circuit conditions. Non-fire related short circuit conditions must not
cause a false alarm condition.
E. The FACP Interface Module shall interface to any 24VDC fire alarm control panel.
F. The FACP Interface Module shall consist of the following:
1. Alarm and trouble relay contacts to connect to the fire alarm control panel
detection input circuit.
2. Two (2) separate LED indicators for FIRE and FAULT.
3. Momentary test switch that tests alarm and trouble monitoring circuitry.
G. The FACP Interface Module shall be reset through the fire alarm control panel.
4.3 Intrinsic Safety Barrier
A. Intrinsic Safety Barriers must be used if the Sensor Cable is installed in the following
hazardous classification areas:
4. Class I, Division 1, Groups A, B, C, D
5. Class II, Division 1, Groups E, F, G
6. Class III, Division 1
4.4 Mounting Hardware and Accessories
A. The Sensor Cable shall be supported at a minimum of ten-foot intervals on straight
runs and more as conditions dictate at corners and transition points to provide
suitable strain relief. The Sensor cable shall be attached to supports that allow
minimal movement.
B. The Sensor Cable shall be installed with the following mounting hardware to insure
proper support and adequate distance away from metal surfaces. All mounting
hardware shall use a nylon cable clamp to fasten the Sensor Cable to the hardware.
7. Master Clamp
8. Flange Clip
9. Nylon Cable Tie
SPECIFICATION:
AlarmLineTM
LINEAR HEAT DETECTION SYSTEM
C. A Sensor Cable Heat Pad shall be used in critical areas where greater lengths of
Sensor Cable need to be concentrated into a compact area. The Heat Pad shall also
be used as a test point at the end of each Sensor Cable zone.
4.5 General Electrical Materials
A. All electrical enclosures, raceways, and conduits shall be provided and installed in
accordance with applicable codes and intended use, and shall contain only those
electrical circuits associated with the fire detection and control system. No circuit or
circuits that are unrelated to the fire detection and control system shall be routed
through the enclosures, raceways, and conduits dedicated to the fire detection and
control system.
B. All conductors shall be enclosed in rigid or thin walled, steel conduit unless open
wiring is permitted by the local electrical code.
C. Any conduit or raceway exposed to dampness or other similar conditions shall be
properly sealed and installed to prevent moisture entrapment. Provisions for draining
and drying shall be employed as required.
D. All wiring shall be of the proper size to conduct the circuit current, but shall not be
smaller than #18 AWG unless permitted by the local electrical code. Wire that has
scrapes, nicks, gouges, or crushed insulation shall not be used. The manufacturer’s
minimum wire-bending radii shall be observed in all enclosures, raceways, and
conduits. Aluminum wire shall not be used.
E. Splicing of circuits shall be kept to a minimum, and is only permitted in an electrical
box suitable for the purpose. Appropriate hardware shall be used to make the wire
splices. Wires that are spliced together shall have the same color insulation.
F. White colored wire shall be used exclusively for the identification of the neutral
conductor of an alternating-current circuit. Green colored wire shall be used
exclusively for the identification of the earth-ground conductor of an AC or DC circuit.
G. Appropriate color-coding shall be utilized for all other field wiring.
H. All electrical circuits shall be numerically tagged with suitable markings at each
terminal point. All circuits shall correspond with the installation drawings.
5. SUBMITTALS
5.1 The factory-authorized Kidde Fire Systems Distributor shall provide the following
drawings and documentation, acceptable to the local AHJ, for approval prior to starting
any work on the project:
SPECIFICATION:
AlarmLineTM
LINEAR HEAT DETECTION SYSTEM
A. Installation and Electrical layouts drawn to the scale depicting the locations and
mounting details of the all equipment
B. Details of Auxiliary functions required such as equipment shutdown, door holders,
etc.
C. The complete point-to-point conduit routing plan.
D. Internal Wiring Diagrams for the fire alarm control panel showing the power supply
requirements and all field wire terminations.
E. Calculations performed in accordance with the Manufacturers recommendations to
justify the capacities of all standby batteries used on the system.
F. A document detailing the sequence of system operations and outputs provided on
the receipt of individual system activation inputs.
5.2 The contractor shall submit a test plan that describes how the system shall be tested.
This shall include a step-by-step description of all tests and shall indicate type and
location of test apparatus to be used. Tests shall not be scheduled or conducted until
the engineer of record approves the test plan.
5.3 The contractor shall submit Ten (10) copies of shop drawings and product data sheets.
5.4 The contractor shall submit Five (5) copies of the AlarmLine Linear Heat Detector
Design, Installation, Operation and Maintenance Manual after complete installation.
6. SYSTEM INSTALLATION, COMMISSIONING AND MAINTENANCE
6.1 The contractor shall install the system in accordance with the manufacturer’s
installation, operation and maintenance manual.
6.2 The contractor shall be certified and trained by the manufacturer on design,
installation, operation and maintenance of the AlarmLine Linear Heat Detector. The
certification must be valid throughout the completion time period for the project.
6.3 The contractor shall record all equipment, tests and system configurations in a format
approved by the manufacturer and/or the local Authority Having Jurisdiction. A copy of
the commissioning results shall be provided to the end-user.
6.4 The AlarmLine Linear Heat Detector shall be maintained as recommended by the
manufacturer’s Design, Installation, Operation and Maintenance Manual, the relevant
NFPA Codes and the requirements of the local Authority Having Jurisdiction.
www.illinoisfire.com

Contenu connexe

Tendances

Fire alarm 2_a_initiation basics
Fire alarm 2_a_initiation basicsFire alarm 2_a_initiation basics
Fire alarm 2_a_initiation basicsgrantlerc
 
Honeywell is2535-spec-sheet
Honeywell is2535-spec-sheetHoneywell is2535-spec-sheet
Honeywell is2535-spec-sheetAlarm Grid
 
Fire alarm 3-e-public_emergency_alarm_reporting_systems
Fire alarm 3-e-public_emergency_alarm_reporting_systemsFire alarm 3-e-public_emergency_alarm_reporting_systems
Fire alarm 3-e-public_emergency_alarm_reporting_systemsgrantlerc
 
Access control basics-9
Access control basics-9Access control basics-9
Access control basics-9grantlerc
 
Fibaro Smoke Sensor presentation
Fibaro Smoke Sensor presentationFibaro Smoke Sensor presentation
Fibaro Smoke Sensor presentationDomotica daVinci
 
Fire basics 1-3-functions_to_docs_08
Fire basics 1-3-functions_to_docs_08Fire basics 1-3-functions_to_docs_08
Fire basics 1-3-functions_to_docs_08grantlerc
 
Pepperl + Fuchs' Emerson Global User Exchange highlights!
Pepperl + Fuchs' Emerson Global User Exchange highlights!Pepperl + Fuchs' Emerson Global User Exchange highlights!
Pepperl + Fuchs' Emerson Global User Exchange highlights!Kristen_Barbour_PF
 
Fluke Industrial Private Limited, Mumbai, Electronic Test Tools
Fluke Industrial Private Limited, Mumbai, Electronic Test ToolsFluke Industrial Private Limited, Mumbai, Electronic Test Tools
Fluke Industrial Private Limited, Mumbai, Electronic Test ToolsIndiaMART InterMESH Limited
 
Fire alarm 3-b-protected_premises_fire_alarm_system
Fire alarm 3-b-protected_premises_fire_alarm_systemFire alarm 3-b-protected_premises_fire_alarm_system
Fire alarm 3-b-protected_premises_fire_alarm_systemgrantlerc
 
Fire Safety Devices , Fire detection systems
Fire Safety Devices , Fire detection systems Fire Safety Devices , Fire detection systems
Fire Safety Devices , Fire detection systems Soumya Sharma
 
Pepperl+Fuchs 2011 Emerson Global Users Exchange fieldbus presentation
Pepperl+Fuchs  2011 Emerson Global Users Exchange fieldbus presentationPepperl+Fuchs  2011 Emerson Global Users Exchange fieldbus presentation
Pepperl+Fuchs 2011 Emerson Global Users Exchange fieldbus presentationKristen_Barbour_PF
 
Fire alarm basics 1-5
Fire alarm basics 1-5Fire alarm basics 1-5
Fire alarm basics 1-5grantlerc
 
Brosur Gossen Metrawatt LINAX PQ5000 MOBILE
Brosur Gossen Metrawatt LINAX PQ5000 MOBILEBrosur Gossen Metrawatt LINAX PQ5000 MOBILE
Brosur Gossen Metrawatt LINAX PQ5000 MOBILEPT. Siwali Swantika
 
California Firecodes
California FirecodesCalifornia Firecodes
California Firecodesmalcolmfd
 
Fire basics 1-4-risers_thru_power_supplies_08
Fire basics 1-4-risers_thru_power_supplies_08Fire basics 1-4-risers_thru_power_supplies_08
Fire basics 1-4-risers_thru_power_supplies_08grantlerc
 

Tendances (20)

Panel
PanelPanel
Panel
 
Back to Basics
Back to BasicsBack to Basics
Back to Basics
 
SMART WIRELESS SENSOR
SMART WIRELESS SENSORSMART WIRELESS SENSOR
SMART WIRELESS SENSOR
 
Fire alarm 2_a_initiation basics
Fire alarm 2_a_initiation basicsFire alarm 2_a_initiation basics
Fire alarm 2_a_initiation basics
 
Honeywell is2535-spec-sheet
Honeywell is2535-spec-sheetHoneywell is2535-spec-sheet
Honeywell is2535-spec-sheet
 
Fire alarm 3-e-public_emergency_alarm_reporting_systems
Fire alarm 3-e-public_emergency_alarm_reporting_systemsFire alarm 3-e-public_emergency_alarm_reporting_systems
Fire alarm 3-e-public_emergency_alarm_reporting_systems
 
Access control basics-9
Access control basics-9Access control basics-9
Access control basics-9
 
Fibaro Smoke Sensor presentation
Fibaro Smoke Sensor presentationFibaro Smoke Sensor presentation
Fibaro Smoke Sensor presentation
 
Fire basics 1-3-functions_to_docs_08
Fire basics 1-3-functions_to_docs_08Fire basics 1-3-functions_to_docs_08
Fire basics 1-3-functions_to_docs_08
 
Fixed Gas Detectors Crowcon
Fixed Gas Detectors CrowconFixed Gas Detectors Crowcon
Fixed Gas Detectors Crowcon
 
Pepperl + Fuchs' Emerson Global User Exchange highlights!
Pepperl + Fuchs' Emerson Global User Exchange highlights!Pepperl + Fuchs' Emerson Global User Exchange highlights!
Pepperl + Fuchs' Emerson Global User Exchange highlights!
 
Fluke Industrial Private Limited, Mumbai, Electronic Test Tools
Fluke Industrial Private Limited, Mumbai, Electronic Test ToolsFluke Industrial Private Limited, Mumbai, Electronic Test Tools
Fluke Industrial Private Limited, Mumbai, Electronic Test Tools
 
Fire alarm 3-b-protected_premises_fire_alarm_system
Fire alarm 3-b-protected_premises_fire_alarm_systemFire alarm 3-b-protected_premises_fire_alarm_system
Fire alarm 3-b-protected_premises_fire_alarm_system
 
Fire Safety Devices , Fire detection systems
Fire Safety Devices , Fire detection systems Fire Safety Devices , Fire detection systems
Fire Safety Devices , Fire detection systems
 
Pepperl+Fuchs 2011 Emerson Global Users Exchange fieldbus presentation
Pepperl+Fuchs  2011 Emerson Global Users Exchange fieldbus presentationPepperl+Fuchs  2011 Emerson Global Users Exchange fieldbus presentation
Pepperl+Fuchs 2011 Emerson Global Users Exchange fieldbus presentation
 
Fire alarm basics 1-5
Fire alarm basics 1-5Fire alarm basics 1-5
Fire alarm basics 1-5
 
Vertx v100 ds_en
Vertx v100 ds_enVertx v100 ds_en
Vertx v100 ds_en
 
Brosur Gossen Metrawatt LINAX PQ5000 MOBILE
Brosur Gossen Metrawatt LINAX PQ5000 MOBILEBrosur Gossen Metrawatt LINAX PQ5000 MOBILE
Brosur Gossen Metrawatt LINAX PQ5000 MOBILE
 
California Firecodes
California FirecodesCalifornia Firecodes
California Firecodes
 
Fire basics 1-4-risers_thru_power_supplies_08
Fire basics 1-4-risers_thru_power_supplies_08Fire basics 1-4-risers_thru_power_supplies_08
Fire basics 1-4-risers_thru_power_supplies_08
 

Similaire à Linear heat detection_spec

Access control basics-7
Access control basics-7Access control basics-7
Access control basics-7grantlerc
 
Water Detection System for Air Conditional&Mechanical Ventilation Installation
Water Detection System for Air Conditional&Mechanical Ventilation InstallationWater Detection System for Air Conditional&Mechanical Ventilation Installation
Water Detection System for Air Conditional&Mechanical Ventilation InstallationJohnny Tsai
 
Method Statement for Fire Alarm System Installation.docx
Method Statement for Fire Alarm System Installation.docxMethod Statement for Fire Alarm System Installation.docx
Method Statement for Fire Alarm System Installation.docxWaheebAlkubati2
 
Defender smokehalt - V automatic overhead coiling fabric smoke curtain
Defender smokehalt - V automatic overhead coiling fabric smoke curtainDefender smokehalt - V automatic overhead coiling fabric smoke curtain
Defender smokehalt - V automatic overhead coiling fabric smoke curtainlyndaflintof
 
Electrical layout of
Electrical layout ofElectrical layout of
Electrical layout ofBhakti Stm
 
Technical specification for 3.ph 4 wire stw 12 02-11
Technical specification for 3.ph 4 wire stw 12 02-11Technical specification for 3.ph 4 wire stw 12 02-11
Technical specification for 3.ph 4 wire stw 12 02-11laxman prasad
 
Fire alarm checklist
Fire alarm checklistFire alarm checklist
Fire alarm checklistirhabsyam
 
Internal cabling guidelines
Internal cabling guidelinesInternal cabling guidelines
Internal cabling guidelinestraoman
 
Specification for electrical automation and instrumentation 02
Specification for electrical automation and instrumentation  02Specification for electrical automation and instrumentation  02
Specification for electrical automation and instrumentation 02Sajeewa Lakmal
 
Manual osciloscopio GDS-800
Manual osciloscopio GDS-800Manual osciloscopio GDS-800
Manual osciloscopio GDS-800Armando Uribe Jr
 
Schneider electric tc indoor
Schneider electric tc indoorSchneider electric tc indoor
Schneider electric tc indoorRosmer Ocando
 
260573 SYSTEM STUDIES.pdf
260573 SYSTEM STUDIES.pdf260573 SYSTEM STUDIES.pdf
260573 SYSTEM STUDIES.pdfssuser0c23d5
 
I zone manual SenseTek-nl
I zone manual SenseTek-nlI zone manual SenseTek-nl
I zone manual SenseTek-nlHans Bronkhorst
 
Edwards Signaling E-FSA250R Installation Manual
Edwards Signaling E-FSA250R Installation ManualEdwards Signaling E-FSA250R Installation Manual
Edwards Signaling E-FSA250R Installation ManualJMAC Supply
 
Edwards Signaling E-FSA64RD Installation Manual
Edwards Signaling E-FSA64RD Installation ManualEdwards Signaling E-FSA64RD Installation Manual
Edwards Signaling E-FSA64RD Installation ManualJMAC Supply
 
5 is 1554_2_pvc cables hd
5 is 1554_2_pvc cables hd5 is 1554_2_pvc cables hd
5 is 1554_2_pvc cables hdSamsher Singh
 

Similaire à Linear heat detection_spec (20)

Access control basics-7
Access control basics-7Access control basics-7
Access control basics-7
 
Alarmline digital manual
Alarmline digital manualAlarmline digital manual
Alarmline digital manual
 
Water Detection System for Air Conditional&Mechanical Ventilation Installation
Water Detection System for Air Conditional&Mechanical Ventilation InstallationWater Detection System for Air Conditional&Mechanical Ventilation Installation
Water Detection System for Air Conditional&Mechanical Ventilation Installation
 
NDOKI VILLAGE
NDOKI VILLAGENDOKI VILLAGE
NDOKI VILLAGE
 
Method Statement for Fire Alarm System Installation.docx
Method Statement for Fire Alarm System Installation.docxMethod Statement for Fire Alarm System Installation.docx
Method Statement for Fire Alarm System Installation.docx
 
Defender smokehalt - V automatic overhead coiling fabric smoke curtain
Defender smokehalt - V automatic overhead coiling fabric smoke curtainDefender smokehalt - V automatic overhead coiling fabric smoke curtain
Defender smokehalt - V automatic overhead coiling fabric smoke curtain
 
Electrical layout of
Electrical layout ofElectrical layout of
Electrical layout of
 
11.docx
11.docx11.docx
11.docx
 
Technical specification for 3.ph 4 wire stw 12 02-11
Technical specification for 3.ph 4 wire stw 12 02-11Technical specification for 3.ph 4 wire stw 12 02-11
Technical specification for 3.ph 4 wire stw 12 02-11
 
Fire alarm checklist
Fire alarm checklistFire alarm checklist
Fire alarm checklist
 
Internal cabling guidelines
Internal cabling guidelinesInternal cabling guidelines
Internal cabling guidelines
 
Specification for electrical automation and instrumentation 02
Specification for electrical automation and instrumentation  02Specification for electrical automation and instrumentation  02
Specification for electrical automation and instrumentation 02
 
Manual osciloscopio GDS-800
Manual osciloscopio GDS-800Manual osciloscopio GDS-800
Manual osciloscopio GDS-800
 
Schneider electric tc indoor
Schneider electric tc indoorSchneider electric tc indoor
Schneider electric tc indoor
 
260573 SYSTEM STUDIES.pdf
260573 SYSTEM STUDIES.pdf260573 SYSTEM STUDIES.pdf
260573 SYSTEM STUDIES.pdf
 
BOQ _UN.pptx
BOQ _UN.pptxBOQ _UN.pptx
BOQ _UN.pptx
 
I zone manual SenseTek-nl
I zone manual SenseTek-nlI zone manual SenseTek-nl
I zone manual SenseTek-nl
 
Edwards Signaling E-FSA250R Installation Manual
Edwards Signaling E-FSA250R Installation ManualEdwards Signaling E-FSA250R Installation Manual
Edwards Signaling E-FSA250R Installation Manual
 
Edwards Signaling E-FSA64RD Installation Manual
Edwards Signaling E-FSA64RD Installation ManualEdwards Signaling E-FSA64RD Installation Manual
Edwards Signaling E-FSA64RD Installation Manual
 
5 is 1554_2_pvc cables hd
5 is 1554_2_pvc cables hd5 is 1554_2_pvc cables hd
5 is 1554_2_pvc cables hd
 

Linear heat detection_spec

  • 1. SPECIFICATION: AlarmLineTM LINEAR HEAT DETECTION SYSTEM 1. GENERAL SPECIFICATION 1.1 The contractor shall provide an AlarmLine Linear Heat Detector for early detection of fire or overheat condition in protected areas or equipment. The AlarmLine Linear Heat Detector shall consist of AlarmLine Sensor Cable and AlarmLine FACP (Fire Alarm Control Panel) Interface Module. The sensor cable shall be an analog (integrating) type linear heat detector. The alarm temperature shall be programmed in the FACP Interface Module. The FACP Interface Module shall communicate alarm and trouble conditions to the Fire Alarm Control Panel. 1.2 The AlarmLine Linear Heat Detector must be manufactured and/or supplied by: Kidde Fire Systems, 400 Main Street, Ashland, MA 01721, U.S.A., 1.3 The manufacturer shall warrant the AlarmLine Linear Heat Detector manufactured by it for a period of eighteen (18) months from the date of shipment. 1.4 The system shall be supplied and installed by a factory authorized Kidde Fire Systems distributor. The distributor shall be trained by the manufacturer to design, install, test and maintain the AlarmLine Linear Heat Detector and shall be able to produce a certificate stating such on request. 1.5 The factory authorized Kidde Fire Systems distributor shall confirm in writing that he stocks a full complement of spare parts and offers 24-hour emergency service for all equipment being furnished. 1.6 All materials and equipment used for this project shall be new and unused. 2. CODES/STANDARDS COMPLIANCE 2.1 The design, installation, testing and maintenance of the AlarmLine Linear Heat Detector shall be in accordance to the following codes, standards and regulatory bodies: A. NFPA 70: National Electrical Code B. NFPA 72: National Fire Alarm Code C. Factory Mutual Approval Guide (latest edition). D. Requirements of the local Authority Having Jurisdiction. 2.2 The AlarmLine Linear Heat Detector shall be Factory Mutual System (FM) approved. 2.3 The manufacturer of the AlarmLine Linear Heat Detector shall have a minimum of 15 years experience in the design, production and distribution of fire detection and fire alarm systems.
  • 2. SPECIFICATION: AlarmLineTM LINEAR HEAT DETECTION SYSTEM 2.4 The manufacturer of the Fire Alarm-Suppression system shall be certified to ISO 9001 for a minimum period of 5 years for the design, production and distribution of fire detection and fire alarm systems. 3. SYSTEM DESCRIPTION 3.1 The Linear Heat Detector shall consist of an AlarmLine Sensor Cable and an AlarmLine FACP Interface Module. The Sensor Cable shall be connected to the AlarmLine FACP Interface Module that communicates through relays, alarm and trouble conditions to the fire alarm control panel. The Sensor Cable alarm temperature shall be field adjustable through the FACP Interface Module. 4. COMPONENTS – DESCRIPTION AND OPERATION 4.1 Linear Heat Detector Sensor Cable A. The Linear Heat Detector Sensor Cable shall be an integrating or averaging type detector cable that detects a localized hot spot or a low-level temperature increase over its entire length. Fixed temperature sensor cable is not acceptable. B. Changes in temperature shall produce a change in resistance between the Sensor Cable conductors. This resistance change shall be monitored by the FACP Interface Module to detect an alarm condition. C. The Sensor Cable shall be capable of self-restoration when temperature drops below its set point, provided it has not been heated above the temperature point of 257° F (125° C). D. The Sensor Cable shall consist of four 26AWG solid copper conductors each insulated with a negative temperature coefficient material. The conductors shall be twisted at a rate of approximately thirty turns per foot (90 per meter) to cancel out potential high voltage inductance. The conductor insulation shall be color coded for ease of installation. The sensor cable shall have an outer protective extrusion of high temperature PVC material. E. [OPTIONAL FOR -016 SENSOR] The sensor cable shall have an additional outer extrusion of nylon as additional protection against harsh environments. F. [OPTIONAL FOR -019 SENSOR] The sensor cable shall have an outer braid of Phosphor Bronze to increase its tensile strength and for protection against abrasion. G. The Sensor Cable shall be approved for installation in classified hazardous areas when installed with an intrinsic safety barrier. 4.2 Linear Heat Detector FACP Interface Module A. The FACP Interface Module shall monitor the resistance of the sensor cable for an
  • 3. SPECIFICATION: AlarmLineTM LINEAR HEAT DETECTION SYSTEM alarm condition. B. The Sensor Cable alarm set point shall be set in the FACP Interface Module. C. The FACP Interface Module shall be cable of monitoring up to 3,200 ft (1000 m) of Sensor Cable. D. The FACP Interface Module shall be capable of monitoring the sensor cable for both open and short circuit conditions. Non-fire related short circuit conditions must not cause a false alarm condition. E. The FACP Interface Module shall interface to any 24VDC fire alarm control panel. F. The FACP Interface Module shall consist of the following: 1. Alarm and trouble relay contacts to connect to the fire alarm control panel detection input circuit. 2. Two (2) separate LED indicators for FIRE and FAULT. 3. Momentary test switch that tests alarm and trouble monitoring circuitry. G. The FACP Interface Module shall be reset through the fire alarm control panel. 4.3 Intrinsic Safety Barrier A. Intrinsic Safety Barriers must be used if the Sensor Cable is installed in the following hazardous classification areas: 4. Class I, Division 1, Groups A, B, C, D 5. Class II, Division 1, Groups E, F, G 6. Class III, Division 1 4.4 Mounting Hardware and Accessories A. The Sensor Cable shall be supported at a minimum of ten-foot intervals on straight runs and more as conditions dictate at corners and transition points to provide suitable strain relief. The Sensor cable shall be attached to supports that allow minimal movement. B. The Sensor Cable shall be installed with the following mounting hardware to insure proper support and adequate distance away from metal surfaces. All mounting hardware shall use a nylon cable clamp to fasten the Sensor Cable to the hardware. 7. Master Clamp 8. Flange Clip 9. Nylon Cable Tie
  • 4. SPECIFICATION: AlarmLineTM LINEAR HEAT DETECTION SYSTEM C. A Sensor Cable Heat Pad shall be used in critical areas where greater lengths of Sensor Cable need to be concentrated into a compact area. The Heat Pad shall also be used as a test point at the end of each Sensor Cable zone. 4.5 General Electrical Materials A. All electrical enclosures, raceways, and conduits shall be provided and installed in accordance with applicable codes and intended use, and shall contain only those electrical circuits associated with the fire detection and control system. No circuit or circuits that are unrelated to the fire detection and control system shall be routed through the enclosures, raceways, and conduits dedicated to the fire detection and control system. B. All conductors shall be enclosed in rigid or thin walled, steel conduit unless open wiring is permitted by the local electrical code. C. Any conduit or raceway exposed to dampness or other similar conditions shall be properly sealed and installed to prevent moisture entrapment. Provisions for draining and drying shall be employed as required. D. All wiring shall be of the proper size to conduct the circuit current, but shall not be smaller than #18 AWG unless permitted by the local electrical code. Wire that has scrapes, nicks, gouges, or crushed insulation shall not be used. The manufacturer’s minimum wire-bending radii shall be observed in all enclosures, raceways, and conduits. Aluminum wire shall not be used. E. Splicing of circuits shall be kept to a minimum, and is only permitted in an electrical box suitable for the purpose. Appropriate hardware shall be used to make the wire splices. Wires that are spliced together shall have the same color insulation. F. White colored wire shall be used exclusively for the identification of the neutral conductor of an alternating-current circuit. Green colored wire shall be used exclusively for the identification of the earth-ground conductor of an AC or DC circuit. G. Appropriate color-coding shall be utilized for all other field wiring. H. All electrical circuits shall be numerically tagged with suitable markings at each terminal point. All circuits shall correspond with the installation drawings. 5. SUBMITTALS 5.1 The factory-authorized Kidde Fire Systems Distributor shall provide the following drawings and documentation, acceptable to the local AHJ, for approval prior to starting any work on the project:
  • 5. SPECIFICATION: AlarmLineTM LINEAR HEAT DETECTION SYSTEM A. Installation and Electrical layouts drawn to the scale depicting the locations and mounting details of the all equipment B. Details of Auxiliary functions required such as equipment shutdown, door holders, etc. C. The complete point-to-point conduit routing plan. D. Internal Wiring Diagrams for the fire alarm control panel showing the power supply requirements and all field wire terminations. E. Calculations performed in accordance with the Manufacturers recommendations to justify the capacities of all standby batteries used on the system. F. A document detailing the sequence of system operations and outputs provided on the receipt of individual system activation inputs. 5.2 The contractor shall submit a test plan that describes how the system shall be tested. This shall include a step-by-step description of all tests and shall indicate type and location of test apparatus to be used. Tests shall not be scheduled or conducted until the engineer of record approves the test plan. 5.3 The contractor shall submit Ten (10) copies of shop drawings and product data sheets. 5.4 The contractor shall submit Five (5) copies of the AlarmLine Linear Heat Detector Design, Installation, Operation and Maintenance Manual after complete installation. 6. SYSTEM INSTALLATION, COMMISSIONING AND MAINTENANCE 6.1 The contractor shall install the system in accordance with the manufacturer’s installation, operation and maintenance manual. 6.2 The contractor shall be certified and trained by the manufacturer on design, installation, operation and maintenance of the AlarmLine Linear Heat Detector. The certification must be valid throughout the completion time period for the project. 6.3 The contractor shall record all equipment, tests and system configurations in a format approved by the manufacturer and/or the local Authority Having Jurisdiction. A copy of the commissioning results shall be provided to the end-user. 6.4 The AlarmLine Linear Heat Detector shall be maintained as recommended by the manufacturer’s Design, Installation, Operation and Maintenance Manual, the relevant NFPA Codes and the requirements of the local Authority Having Jurisdiction. www.illinoisfire.com