The document provides information on commissioning a control valve positioner for a power plant project. It includes specifications for the positioner, diagrams of how it controls air flow to open and close the valve, instructions for calibrating it by connecting a 4-20mA source and using a communicator to perform auto or manual calibration, and descriptions of its manual operation, limit switches, and alarms.
1. Qurayyah CCPP ProjectQurayyah CCPP Project
Fail Free Commissioning
Control Valve(Fisher HC6010)
EPC) Commissioning Management Team
2. Page index
1. POSITIONER SPECIFICATION
2. POSITIONER AND ACTUATOR AIR FLOW2. POSITIONER AND ACTUATOR AIR FLOW
3. POSITIONER ATTACHMENT
4 SIGNAL LINE CONNECTION4. SIGNAL LINE CONNECTION
5. CALIBRATION PROCEDURE
6. MANUAL OPERATION
7.CONTROL VALVE LIMIT SWITCHES
8.ALARM AND STATUS
1
3. 1. Positioner Specification
Electrical Specification
l dPower Supply 11 ‐30Vdc
Communication Hart protocol
Minimum Operating Current 3.5mA without microprocessor
Maximum Voltage 30Vdc
Analog Input Signal 4 ‐ 20mA
Positioner Specification
Linearity ±0.5% of output span
Air Consumption 1.4 bar (20 psi )
Maximum Air Supply 10 bar (145 psi)
2
4. 2. Positioner And Actuator Air Flow (1/2)
Flow diagram on how the actuator moves closing and opening position in digitalg g p g p g
and analog mode.
3
5. 2. Positioner And Actuator Air Flow (2/2)
positioner
actuator
positioner
4
6. 3. Positioner Attachment (1/2 )
Fieldvue DVC6010 Digital Valve Controller Mounted on
Sliding-Stem Actuators with up to 2 inches Travel
5
7. 3. Positioner Attachment (2/2)
• Air to Open Actuator
1. Insert the alignment pin in the hole marked A
2. The feedback arm rotates counterclockwise, from A to B as air pressure to
the casing or lower cylinder increases.g y
• Air to Close Actuator
1. Insert the alignment pin in the hole marked B
2. The feedback arm rotates clockwise from B to A as air pressure to the
casing or upper cylinder increases
6
casing or upper cylinder increases.
9. 5. Calibration Procedure (1/3)
.
• Connect 4 – 20mA source to the instrument
• Connect Hart Communicator and power ON
Auto Calibration
• Select to Auto travel calibration, the control
valve start to stroke from 0% to 100% open
automatically.
• Wait until the calibration is completed• Wait until the calibration is completed.
Manual Calibration
• Select To Manual calibration, its allows you
to determine 0% to 100% calibration point.
4 – 20mA
Source
• Refer to Hart Communicator for some
adjustment for tuning and travel calibration.
Hart Communicator
8
12. 6. Manual Operation
• Handwheel
• Handwheel lock
• Position travel indicator
• Rotate the handwheel lock Anti-clockwise to operate
the handwheelthe handwheel
•Start to rotate the handwheel lock to desire direction
• Clockwise for closing
• Anti clockwise for opening
• If the handwheel reach the maximum turn, you can
h k th iti i t l i di t if it i f ll lcheck the position in travel indicator if it is fully close
or fully open.
11
13. 7. Control Valve Limit Switch
• Limit switch for “open position” when control
valve is in fully open the contact is close forvalve is in fully open, the contact is close for
fully open feedback.
• Limit switch for “close position“ when control
valve is in fully close the contact is open forvalve is in fully close, the contact is open for
fully close feedback.