reducing information
 Technology's ever-
 increasing carbon
     footprint
             Tom Raftery

    Blog: cix.ie / tomrafteryit.net
    Podcast: www.podleaders.com

    Email: tom@tomrafteryit.net
CIX

• Cork Internet eXchange - CIX
 • First professional data centre outside
   Dublin
 • Opening Oct ’07
 • Not a sales pitch (unless your based in
   Cork!!!)
CIX.ie
CIX.ie
CIX.ie
CIX.ie
CIX.ie
Lingo
• Watts = Voltage x Amps
• 1000 Watts for 1 hour = 1kWh
• 1U = 1 rack unit = 44.45 mm (1.75 in) high
• 1U servers -> 1A = 220W or .22kW
• Blade Servers/SAN = 500W per 1 U
• A large server might take 1kW
• 40U rack could use 20kW of power
CIX Vision



• Carbon neutral data centre
 • Why?
 • How?
Why? Climate change
Why?


• DC running costs
 • Staffing - reasonable controllable
 • Connectivity - decreasing
 • Energy - increasing
Increasing Energy
    requirements

• Rack of equipment typically used
 • 1.5 kW 7 years ago
 • 4.5 kW 4 years ago and
 • 15 kW in 2006!
 • SL Avatar consumes 1.75 kWh p.a.!
Watts per $1000 server
        spend


  • Price to fill a rack has gone down
  • Power consumption has gone up
  • => Increasing Watts per $1000 of
    server spend
Watts per $1000
Carbon Neutrality



• How?
 • Using Pure Plant Oil (PPO) as an
   energy source
Background

• Data Centres:
 • Consume a lot of electricity
 • At roughly a constant rate
 • Have generating capacity at 2x
   requirements
 • Connected to grid through high
   voltage substations
Background

• Electricity Supply:
 • Cannot be stored
 • Seasonal & diurnal demands
 • ESB offers Max Demand (MD)
   discounts
 • Wind generates 0-30% of demand
   but is highly unstable
The Strategy
• Create a Data Centre power grid
• Powered by diesel generators burning
  PPO
• Grid generates power for ESB by day
  and pulls surplus power from ESB by
  night
• Give control of grid to ESB
• ESB can now buy more wind power
Requirements

• Political will
• Buy in from ESB
• Buy in from other DCs
• Buy in from farmers!
• Time!
In the meantime



• CIX are innovating to maximise
 • Energy efficiency and
 • Minimise carbon footprint
Optimal DC environment
DC Energy Flow
Innovations
• Utilise free cooling
• Dynamically maximise chilled water
  temperature
• Eliminate water mixing
• Minimise humidification
• Eliminate air mixing
• Utilise low resistance, slow speed air
  paths
Free Cooling

• Mean temp in Cork is 10.5˚C
• Optimum inlet temp for servers is
  21˚C
• Exhaust air from servers is 30˚C to
  40˚C
• Use ambient temp to cool the warm
  air and return water
Maximise Chilled Water
         Temp


  • Chillers have a fixed set point
  • CIX developed dynamic chiller
    control system
   • Maximises temp of chilled water
   • Reduces energy required to chill it
Eliminate Water Mixing

 • Fixed chiller set-point
   • If CRAHs get overly cold water
   • => mix with warm water -
     extremely wasteful
 • Dynamic set point eliminates water
   mixing
Minimise Humidification

  • Low temperature water CRAHs =>
    condensation
   • reduces the relative humidity
   • Steam (energy and cooling
     implications) required to humidify
  • Dynamic chiller set point => less
    condensation
Typical DC
Eliminate Air mixing


• Mixing hot and cold air - v wasteful
• Most DCs - hot aisle/cold aisle
  separation
• CIX - cold aisle containment - most
  energy efficient rack layout
Low Resistance, Slow
     Speed Air
 • Large unobstructed under-floor
   cavities
 • Large overhead spaces for return air
   flows
 • Fans require less energy to move air
 • Also, using thyristor controlled
   direct drive fans to reduce belt
   resistance losses
Server Supplied Heating



 • Dimplex heat exchange unit
  • Servers heat the CIX offices
  • Servers heat water for CIX
Power


• 10kv low impedence looped
  connection to the national grid
• Using GE Super ECO UPS’s
  offering >98% efficiency
Power
                                                                 Normal mode
                                              Bypass
                                                                     Static bypass
                                              supply
•Normal mode
• The output voltage is newly generated,                  Rectifier            Inverter
    independently from the input voltage                 AC                                         Load
                                                                              DC
                                              Rectifie
    Heat losses are present in rectifier and
•                                                r                                   AC
                                                               DC
    inverter 
                                supply


                                                                Battery bank
•Super Eco Mode
• Load is supplied via the bypass                              Super Eco Mode
• UPS rectifier keeps the battery charged
                                              Bypass
• UPS inverter switched o                                          Static bypass
                                              supply
    (no heat losses)
                                                         Rectifier            Inverter    Transf.
                                                         AC                                         Load
                                                                              DC
                                              Rectifie
                                                 r                                   AC
                                                               DC
                                              supply


                                                                Battery bank
Typical DC
End Result

               Standard DC   CIX
                  33%         12%
    Chiller
                   3%         1%
 Humidifier
                   9%          4%
    CRAC
                  30%         80%
IT Equipment
                   5%        0.01%
     PDU
                  18%         2%
     UPS
                   1%         1%
   Lighting
                   1%          1%
 Switch Gear
Conclusion

• Carbon neutrality
 • many stakeholders
 • Political will
 • time to roll out
• Extreme energy efficiency
 • Being built-in!
References

•   Uptime Institute - www.upsite.com

•   APC - www.apc.com

•   GE - www.ge.com

•   CIX Energy Efficiency White Paper - www.cix.ie/air-
    conditioning-efficiency-at-the-cix-data-centre

•   Second Life Avatar Power consumption -
    www.roughtype.com/archives/2006/12/
    avatars_consume.php
Thanks

       Tom Raftery

 Blog: www.tomrafteryit.net
Podcast: www.podleaders.com

Email: tom@tomrafteryit.net

More Related Content

Similar to Reducing Information Technologies ever-increasing carbon footprint

Intelligent battery charger
Intelligent battery chargerIntelligent battery charger
Intelligent battery charger
slmnsvn
 

Similar to Reducing Information Technologies ever-increasing carbon footprint (20)

Reducing a data center's carbon footprint
Reducing a data center's carbon footprintReducing a data center's carbon footprint
Reducing a data center's carbon footprint
 
Day 3: Power Supply Quality in Buildings
Day 3: Power Supply Quality in Buildings Day 3: Power Supply Quality in Buildings
Day 3: Power Supply Quality in Buildings
 
Online classes pe dc-dc converter
Online classes pe dc-dc converterOnline classes pe dc-dc converter
Online classes pe dc-dc converter
 
Project presentation - battery charger 24V/33A
Project presentation - battery charger 24V/33AProject presentation - battery charger 24V/33A
Project presentation - battery charger 24V/33A
 
Pavegen
PavegenPavegen
Pavegen
 
DIODE APPLICATIONS .pdf
DIODE APPLICATIONS .pdfDIODE APPLICATIONS .pdf
DIODE APPLICATIONS .pdf
 
lecture 10 - electrical machines - dc to dc converters 1.pptx
lecture 10 - electrical machines - dc to dc converters 1.pptxlecture 10 - electrical machines - dc to dc converters 1.pptx
lecture 10 - electrical machines - dc to dc converters 1.pptx
 
Battery Charger Manufacturer - RS Power Systems
Battery Charger Manufacturer - RS Power SystemsBattery Charger Manufacturer - RS Power Systems
Battery Charger Manufacturer - RS Power Systems
 
power factor and power factor correction schneider EMERSON EDUARDO RODRIGUES
power factor and power factor correction schneider EMERSON EDUARDO RODRIGUESpower factor and power factor correction schneider EMERSON EDUARDO RODRIGUES
power factor and power factor correction schneider EMERSON EDUARDO RODRIGUES
 
Chapter 4 - AC-DC Conversion.pdf
Chapter 4 - AC-DC Conversion.pdfChapter 4 - AC-DC Conversion.pdf
Chapter 4 - AC-DC Conversion.pdf
 
capacitors
capacitorscapacitors
capacitors
 
2011 ced capacitors
2011 ced capacitors2011 ced capacitors
2011 ced capacitors
 
Product: Power Factor & Harmonics: StacoSine: Technical
Product: Power Factor & Harmonics: StacoSine: TechnicalProduct: Power Factor & Harmonics: StacoSine: Technical
Product: Power Factor & Harmonics: StacoSine: Technical
 
Dc Principal
Dc PrincipalDc Principal
Dc Principal
 
Webinar: Desmistificando projetos de fontes chaveadas
Webinar: Desmistificando projetos de fontes chaveadasWebinar: Desmistificando projetos de fontes chaveadas
Webinar: Desmistificando projetos de fontes chaveadas
 
Intelligent battery charger
Intelligent battery chargerIntelligent battery charger
Intelligent battery charger
 
PE4MSc_Ch1_SC_devices.pptx
PE4MSc_Ch1_SC_devices.pptxPE4MSc_Ch1_SC_devices.pptx
PE4MSc_Ch1_SC_devices.pptx
 
Amplifiers
AmplifiersAmplifiers
Amplifiers
 
Diode bridge rectifier_ppt
Diode bridge rectifier_pptDiode bridge rectifier_ppt
Diode bridge rectifier_ppt
 
Ripple factor
Ripple factorRipple factor
Ripple factor
 

More from Tom Raftery

More from Tom Raftery (20)

The future of digital - a 10 year vision
The future of digital - a 10 year visionThe future of digital - a 10 year vision
The future of digital - a 10 year vision
 
Sap Leonardo - what is it, and why would I want one?
Sap Leonardo - what is it, and why would I want one?Sap Leonardo - what is it, and why would I want one?
Sap Leonardo - what is it, and why would I want one?
 
New Business Models for utilities
New Business Models for utilitiesNew Business Models for utilities
New Business Models for utilities
 
The impact of the Internet of Things (IoT) on telcos, datacenter, and utilities
The impact of the Internet of Things (IoT) on telcos, datacenter, and utilitiesThe impact of the Internet of Things (IoT) on telcos, datacenter, and utilities
The impact of the Internet of Things (IoT) on telcos, datacenter, and utilities
 
The future of IT should be Green
The future of IT should be GreenThe future of IT should be Green
The future of IT should be Green
 
The Internet of Things and Energy - ThingMonk 2015
The Internet of Things and Energy - ThingMonk 2015The Internet of Things and Energy - ThingMonk 2015
The Internet of Things and Energy - ThingMonk 2015
 
Internet of Things (IoT) and energy keynote at Tesla World
Internet of Things (IoT) and energy keynote at Tesla WorldInternet of Things (IoT) and energy keynote at Tesla World
Internet of Things (IoT) and energy keynote at Tesla World
 
Internet of Things and Energy at SAP for Utilities
Internet of Things and Energy at SAP for UtilitiesInternet of Things and Energy at SAP for Utilities
Internet of Things and Energy at SAP for Utilities
 
The convergence of the Internet of Things and Energy
The convergence of the Internet of Things and EnergyThe convergence of the Internet of Things and Energy
The convergence of the Internet of Things and Energy
 
IoT and Energy
IoT and EnergyIoT and Energy
IoT and Energy
 
People as sensors - mining social media for meaningful information
People as sensors - mining social media for meaningful informationPeople as sensors - mining social media for meaningful information
People as sensors - mining social media for meaningful information
 
Can Social Media make Utilities sexy again?
Can Social Media make Utilities sexy again?Can Social Media make Utilities sexy again?
Can Social Media make Utilities sexy again?
 
Can we hack open source cloud platforms to help reduce emissions? cloudstack ...
Can we hack open source cloud platforms to help reduce emissions? cloudstack ...Can we hack open source cloud platforms to help reduce emissions? cloudstack ...
Can we hack open source cloud platforms to help reduce emissions? cloudstack ...
 
Can social make utilities sexy again?
Can social make utilities sexy again?Can social make utilities sexy again?
Can social make utilities sexy again?
 
The new power of the customer voice - social media's place in business
The new power of the customer voice - social media's place in businessThe new power of the customer voice - social media's place in business
The new power of the customer voice - social media's place in business
 
Can we hack open source #cloud platforms to help reduce emissions?
Can we hack open source #cloud platforms to help reduce emissions?Can we hack open source #cloud platforms to help reduce emissions?
Can we hack open source #cloud platforms to help reduce emissions?
 
Cloud Computing's Green potential
Cloud Computing's Green potentialCloud Computing's Green potential
Cloud Computing's Green potential
 
Potent Social Media strategies for Utility companies
Potent Social Media strategies for Utility companiesPotent Social Media strategies for Utility companies
Potent Social Media strategies for Utility companies
 
Energy 2.0 at Visualizar11
Energy 2.0 at Visualizar11Energy 2.0 at Visualizar11
Energy 2.0 at Visualizar11
 
Cloud Computing's Green Credentials
Cloud Computing's Green CredentialsCloud Computing's Green Credentials
Cloud Computing's Green Credentials
 

Recently uploaded

Cloud Frontiers: A Deep Dive into Serverless Spatial Data and FME
Cloud Frontiers:  A Deep Dive into Serverless Spatial Data and FMECloud Frontiers:  A Deep Dive into Serverless Spatial Data and FME
Cloud Frontiers: A Deep Dive into Serverless Spatial Data and FME
Safe Software
 

Recently uploaded (20)

Apidays New York 2024 - The value of a flexible API Management solution for O...
Apidays New York 2024 - The value of a flexible API Management solution for O...Apidays New York 2024 - The value of a flexible API Management solution for O...
Apidays New York 2024 - The value of a flexible API Management solution for O...
 
Apidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, Adobe
Apidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, AdobeApidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, Adobe
Apidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, Adobe
 
AXA XL - Insurer Innovation Award Americas 2024
AXA XL - Insurer Innovation Award Americas 2024AXA XL - Insurer Innovation Award Americas 2024
AXA XL - Insurer Innovation Award Americas 2024
 
ICT role in 21st century education and its challenges
ICT role in 21st century education and its challengesICT role in 21st century education and its challenges
ICT role in 21st century education and its challenges
 
Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024
 
ProductAnonymous-April2024-WinProductDiscovery-MelissaKlemke
ProductAnonymous-April2024-WinProductDiscovery-MelissaKlemkeProductAnonymous-April2024-WinProductDiscovery-MelissaKlemke
ProductAnonymous-April2024-WinProductDiscovery-MelissaKlemke
 
Exploring Multimodal Embeddings with Milvus
Exploring Multimodal Embeddings with MilvusExploring Multimodal Embeddings with Milvus
Exploring Multimodal Embeddings with Milvus
 
How to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected WorkerHow to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected Worker
 
Strategize a Smooth Tenant-to-tenant Migration and Copilot Takeoff
Strategize a Smooth Tenant-to-tenant Migration and Copilot TakeoffStrategize a Smooth Tenant-to-tenant Migration and Copilot Takeoff
Strategize a Smooth Tenant-to-tenant Migration and Copilot Takeoff
 
Biography Of Angeliki Cooney | Senior Vice President Life Sciences | Albany, ...
Biography Of Angeliki Cooney | Senior Vice President Life Sciences | Albany, ...Biography Of Angeliki Cooney | Senior Vice President Life Sciences | Albany, ...
Biography Of Angeliki Cooney | Senior Vice President Life Sciences | Albany, ...
 
Strategies for Landing an Oracle DBA Job as a Fresher
Strategies for Landing an Oracle DBA Job as a FresherStrategies for Landing an Oracle DBA Job as a Fresher
Strategies for Landing an Oracle DBA Job as a Fresher
 
[BuildWithAI] Introduction to Gemini.pdf
[BuildWithAI] Introduction to Gemini.pdf[BuildWithAI] Introduction to Gemini.pdf
[BuildWithAI] Introduction to Gemini.pdf
 
Rising Above_ Dubai Floods and the Fortitude of Dubai International Airport.pdf
Rising Above_ Dubai Floods and the Fortitude of Dubai International Airport.pdfRising Above_ Dubai Floods and the Fortitude of Dubai International Airport.pdf
Rising Above_ Dubai Floods and the Fortitude of Dubai International Airport.pdf
 
TrustArc Webinar - Unlock the Power of AI-Driven Data Discovery
TrustArc Webinar - Unlock the Power of AI-Driven Data DiscoveryTrustArc Webinar - Unlock the Power of AI-Driven Data Discovery
TrustArc Webinar - Unlock the Power of AI-Driven Data Discovery
 
Corporate and higher education May webinar.pptx
Corporate and higher education May webinar.pptxCorporate and higher education May webinar.pptx
Corporate and higher education May webinar.pptx
 
Apidays New York 2024 - Accelerating FinTech Innovation by Vasa Krishnan, Fin...
Apidays New York 2024 - Accelerating FinTech Innovation by Vasa Krishnan, Fin...Apidays New York 2024 - Accelerating FinTech Innovation by Vasa Krishnan, Fin...
Apidays New York 2024 - Accelerating FinTech Innovation by Vasa Krishnan, Fin...
 
Cloud Frontiers: A Deep Dive into Serverless Spatial Data and FME
Cloud Frontiers:  A Deep Dive into Serverless Spatial Data and FMECloud Frontiers:  A Deep Dive into Serverless Spatial Data and FME
Cloud Frontiers: A Deep Dive into Serverless Spatial Data and FME
 
MS Copilot expands with MS Graph connectors
MS Copilot expands with MS Graph connectorsMS Copilot expands with MS Graph connectors
MS Copilot expands with MS Graph connectors
 
Boost Fertility New Invention Ups Success Rates.pdf
Boost Fertility New Invention Ups Success Rates.pdfBoost Fertility New Invention Ups Success Rates.pdf
Boost Fertility New Invention Ups Success Rates.pdf
 
Exploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone ProcessorsExploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone Processors
 

Reducing Information Technologies ever-increasing carbon footprint

  • 1. reducing information Technology's ever- increasing carbon footprint Tom Raftery Blog: cix.ie / tomrafteryit.net Podcast: www.podleaders.com Email: tom@tomrafteryit.net
  • 2. CIX • Cork Internet eXchange - CIX • First professional data centre outside Dublin • Opening Oct ’07 • Not a sales pitch (unless your based in Cork!!!)
  • 8. Lingo • Watts = Voltage x Amps • 1000 Watts for 1 hour = 1kWh • 1U = 1 rack unit = 44.45 mm (1.75 in) high • 1U servers -> 1A = 220W or .22kW • Blade Servers/SAN = 500W per 1 U • A large server might take 1kW • 40U rack could use 20kW of power
  • 9. CIX Vision • Carbon neutral data centre • Why? • How?
  • 11. Why? • DC running costs • Staffing - reasonable controllable • Connectivity - decreasing • Energy - increasing
  • 12. Increasing Energy requirements • Rack of equipment typically used • 1.5 kW 7 years ago • 4.5 kW 4 years ago and • 15 kW in 2006! • SL Avatar consumes 1.75 kWh p.a.!
  • 13. Watts per $1000 server spend • Price to fill a rack has gone down • Power consumption has gone up • => Increasing Watts per $1000 of server spend
  • 15. Carbon Neutrality • How? • Using Pure Plant Oil (PPO) as an energy source
  • 16. Background • Data Centres: • Consume a lot of electricity • At roughly a constant rate • Have generating capacity at 2x requirements • Connected to grid through high voltage substations
  • 17. Background • Electricity Supply: • Cannot be stored • Seasonal & diurnal demands • ESB offers Max Demand (MD) discounts • Wind generates 0-30% of demand but is highly unstable
  • 18. The Strategy • Create a Data Centre power grid • Powered by diesel generators burning PPO • Grid generates power for ESB by day and pulls surplus power from ESB by night • Give control of grid to ESB • ESB can now buy more wind power
  • 19. Requirements • Political will • Buy in from ESB • Buy in from other DCs • Buy in from farmers! • Time!
  • 20. In the meantime • CIX are innovating to maximise • Energy efficiency and • Minimise carbon footprint
  • 23. Innovations • Utilise free cooling • Dynamically maximise chilled water temperature • Eliminate water mixing • Minimise humidification • Eliminate air mixing • Utilise low resistance, slow speed air paths
  • 24. Free Cooling • Mean temp in Cork is 10.5˚C • Optimum inlet temp for servers is 21˚C • Exhaust air from servers is 30˚C to 40˚C • Use ambient temp to cool the warm air and return water
  • 25. Maximise Chilled Water Temp • Chillers have a fixed set point • CIX developed dynamic chiller control system • Maximises temp of chilled water • Reduces energy required to chill it
  • 26. Eliminate Water Mixing • Fixed chiller set-point • If CRAHs get overly cold water • => mix with warm water - extremely wasteful • Dynamic set point eliminates water mixing
  • 27. Minimise Humidification • Low temperature water CRAHs => condensation • reduces the relative humidity • Steam (energy and cooling implications) required to humidify • Dynamic chiller set point => less condensation
  • 29. Eliminate Air mixing • Mixing hot and cold air - v wasteful • Most DCs - hot aisle/cold aisle separation • CIX - cold aisle containment - most energy efficient rack layout
  • 30. Low Resistance, Slow Speed Air • Large unobstructed under-floor cavities • Large overhead spaces for return air flows • Fans require less energy to move air • Also, using thyristor controlled direct drive fans to reduce belt resistance losses
  • 31. Server Supplied Heating • Dimplex heat exchange unit • Servers heat the CIX offices • Servers heat water for CIX
  • 32. Power • 10kv low impedence looped connection to the national grid • Using GE Super ECO UPS’s offering >98% efficiency
  • 33. Power Normal mode Bypass Static bypass supply •Normal mode • The output voltage is newly generated, Rectifier Inverter independently from the input voltage AC Load DC Rectifie Heat losses are present in rectifier and • r AC DC inverter supply Battery bank •Super Eco Mode • Load is supplied via the bypass Super Eco Mode • UPS rectifier keeps the battery charged Bypass • UPS inverter switched o Static bypass supply (no heat losses) Rectifier Inverter Transf. AC Load DC Rectifie r AC DC supply Battery bank
  • 35. End Result Standard DC CIX 33% 12% Chiller 3% 1% Humidifier 9% 4% CRAC 30% 80% IT Equipment 5% 0.01% PDU 18% 2% UPS 1% 1% Lighting 1% 1% Switch Gear
  • 36. Conclusion • Carbon neutrality • many stakeholders • Political will • time to roll out • Extreme energy efficiency • Being built-in!
  • 37. References • Uptime Institute - www.upsite.com • APC - www.apc.com • GE - www.ge.com • CIX Energy Efficiency White Paper - www.cix.ie/air- conditioning-efficiency-at-the-cix-data-centre • Second Life Avatar Power consumption - www.roughtype.com/archives/2006/12/ avatars_consume.php
  • 38. Thanks Tom Raftery Blog: www.tomrafteryit.net Podcast: www.podleaders.com Email: tom@tomrafteryit.net