SUB-STATIONS
 The assembly of apparatus used to change
some characteristic(e.g. Voltage, a.c to d.c,
frequency, power factor etc) of electric supply is
called a sub-station
• It should be located at the centre of gravity
of load
• It should be easily operated and maintained
• It should provide safe and reliable
arrangement
• It should involve minimum capital cost
Sub-stations
Service
requirement
Constructional
features
 Transformer sub stations : these are used to change the voltage
levels of supply
 switching sub stations: they simply perfome switching operations
of power lines
 Power factor sub stations: they improve the power factor of the
system by using synchronous condensers
 Frequency sub stations: those sub stations which change supply
frequency
 Converting sub stations: those sub stations which change a.c.
power to d.c. power
 Industrial sub stations: those sub stations which supply power to
industries
Substations are classified as……..
Transformer substations are classified into 4 types these are……..
 step up substation: the generation voltage is stepped up to high
voltage
 Primary grid substation: here the voltage level is step down to 66kv
from 220kv for secondary transmission
 Secondary substation: the voltage level is further step down to 11kv
and these substations are generally outdoor type
 Distribution substation: the electric power from 11kv lines is
delivered to distribution substation. These are generally located near
consumer localities…
According to constructional features, the sub stations are classified as:
 Indoor sub station: these substations can be installed for voltages up to
11kv
 Outdoor sub station: for voltages beyond 66kv these type of sub stations
can be installed
 Underground sub stations: in thickly populated areas, the space available
is less so we install these type of substations
 Pole mounted substations: this is an outdoor substation with equipment
installed overhead on h-pole or 4 pole structure
It is a schematic view of pole mounted substation……
While designing a underground sub station the following points are to
be followed:
 the size of substation should be minimum
 There should be reasonable access for both equipment
 There should be provision for emergency lights and protection
against fire
 There should be good ventilation
 the transformers,switches,fuses should be air cooled to avoid
bringing oil into premises
 BUS BARS: various incoming and out going circuits are connected to
bus bars.busbars receive power from incoming circuits and deliver
power to out going circuits.
.
Electric substations are the part of power systems and used for
transferring power from generating points to load centres.some of
important components are…
 INSULATORS: insulators serve two purposes
1) they support conductors(busbars)
2) confine the current to the conductors
 most commonly used material for manufacture of
insulators is porcelain.
 ISOLATING SWITCHES: in sub stations it is often desired to
disconnect a part of system for general maintenance and repairs. this
is accomplished by an isolating switch or isolators.
 Circuit breaker: circuit breaker is used for switching
during normal and abnormal conditions. it is used to
interrupt short circuit currents .there are many types of
circuit breakers..
1) air blast circuit breaker.
2) oil circuit breaker
3) sf6 circuit breaker
 power transformers: these are used to step down or step up a.c.
voltages and to transfer electrical power from one voltage level to
another.
 Current transformers: current transformer in
essentially a step up transformer which steps down the
current to a known ratio.
 voltage transformer: it is essentially a step down transformer and
steps down the voltage to a known ratio.
 metering and indicating instruments: there are several metering and
indicating instruments installed in a sub station to maintain watch over the
circuit quantities.
 in addition to these there may be following equipment in a substation.
1) fuses
2) carrier current equipment
3) sub station auxiliary supplies
Single bus bar system…
GAS INSULATED SUBSTATION
Gas Insulated substations use
sulphur hexa fluoride(SF6) gas which
has superior dielectric properties.
Gas insulated substations are used
where there is space for providing
the substation is expensive in large
cities and towns
TYPES OF GAS INSULATED SUBSTATIONS
Gas insulated substations are classified according to
the type of configurations as………..
 isolated phase module
 3-phase common modules
 hybrid modules
Compact modules
Highly integrated systems
The individual circuit elements such as a pole of a circuit breaker, a single
pole isolator, one phase assembly of a current transformer etc..are
connected together forms an isolated phase GIS module.
In this type of module a three phase bay is assembled using the desired
number of three phase elements. This reduces the total number of
enclosures to one third.
It is the combination of isolated phase and three phase common
elements is used to achieve an optimal solution. Hybrid GIS technology
has gained popularity, specially in the medium and low voltage range
Compact GIS systems are essentially three phase common systems
in which the elements such as three phase circuit breaker, current
transformer etc…. Are placed
These are used in outdoor substations .highly integrated substations
are ready to install substations.
The high voltage conductor made up of
copper or aluminum is centrally placed in a
tabular metal enclosure. In isolated phase
GIS ,coaxial bus bar are common
The main parts of GIS are…….
 gas circuit
 seals and gaskets
 disconnectors
 earth switch
Circuit breaker
Current transformer
Plug in joints
Enclosure
Expansion joints
Gas circuit : gas circuit has to maintain the dual
purpose (i.e. arc interruption and insulation). Gas
circuit should maintain the pressure throughout its
life period so there should be no leakages
SEALS AND GASKETS : seals and gaskets are used to
capture the SF6 gas lekages.these are manufactured
with nitrile rubber and viton. These serves sealing
purpose
Disconnectors or isolators are used for electrical
isolation of circuit parts.
They are slow acting and operating at off load.
Disconnectors must be carefully designed and
tested to be able to break small charging current
without generating too higher over voltage.
Circuit breaker is a metal clad and uses SF6 gas for the
purpose of insulation and fault interruption. The circuit
breaker is directly connected to either current transformers or
isolators
fast earth switch: these are used to
protect the circuit connected current
transformer, voltage transformer
Maintenance earth switch: these are used
for grounding the high voltage conductors
during maintenance
PLUG IN JOINTS: these are designed in such a way that
they can carry rated full load current uninterruptedly
and can carry heavy transient currents types of plug in
joints are
Static joints
Quasi static joints
S.NO 145KV 170KV 245KV
1 Bay width
(m)
1.5 2.0 2.0
2 Bay depth 3.3 3.35 3.4
3 Bay height 3.2 3.4 3.4
4 Floor area
(sq.m)
4.95 6.7 6.8
5 Volume 15.84 22.78 23.12
6 Weight 3800 5000 5700
GIS have no risk for fire and explosion due
to leakage of oil.
They generate no noise and have no radio
interference.
The maintainence of GIS is free.
It offers solutions,
-Industrial areas where space and
pollution problems .
-Mountain areas where ice and snow
are major problems.
Gas insulations tend to be much more
expensive than air insulated installations
with the same ratings.
Care should be taken that no dust
particles enter into the live compartments
which results in flash over.
When fault occurs internally the
diagnosis of the fault and rectifying takes
very long time.
Sub stations-air insulated substations
Sub stations-air insulated substations

More Related Content

What's hot

PPt on 220 kV substation
PPt on 220 kV substationPPt on 220 kV substation
PPt on 220 kV substation
Ishank Ranjan
 
400kv sub-station-final-ppt-by-mohit
400kv sub-station-final-ppt-by-mohit400kv sub-station-final-ppt-by-mohit
400kv sub-station-final-ppt-by-mohit
Mohit Awasthi
 
Gas insulated substation
Gas insulated substationGas insulated substation
Gas insulated substation
sharique_64
 
Mcb, rccb, elcb
Mcb, rccb, elcbMcb, rccb, elcb
Mcb, rccb, elcb
Akash Patel
 

What's hot (20)

GIS 400kv substation
GIS  400kv substationGIS  400kv substation
GIS 400kv substation
 
PPt on 220 kV substation
PPt on 220 kV substationPPt on 220 kV substation
PPt on 220 kV substation
 
IEEE substation design
IEEE substation designIEEE substation design
IEEE substation design
 
400kv sub-station-final-ppt-by-mohit
400kv sub-station-final-ppt-by-mohit400kv sub-station-final-ppt-by-mohit
400kv sub-station-final-ppt-by-mohit
 
Presentation on 132/33 KVSubstation Training
Presentation on 132/33 KVSubstation Training Presentation on 132/33 KVSubstation Training
Presentation on 132/33 KVSubstation Training
 
Relays and its types - complete guide
Relays and its types - complete guideRelays and its types - complete guide
Relays and its types - complete guide
 
High voltage transmission
High voltage transmissionHigh voltage transmission
High voltage transmission
 
Gas insulated substation
Gas insulated substationGas insulated substation
Gas insulated substation
 
Mcb, rccb, elcb
Mcb, rccb, elcbMcb, rccb, elcb
Mcb, rccb, elcb
 
Substation Training presentation
Substation Training presentationSubstation Training presentation
Substation Training presentation
 
Transmission lines
Transmission linesTransmission lines
Transmission lines
 
Gis substation
Gis substationGis substation
Gis substation
 
substation 220 kv
substation 220 kv substation 220 kv
substation 220 kv
 
Electric power system
Electric power systemElectric power system
Electric power system
 
Directional over current relay
Directional over current relayDirectional over current relay
Directional over current relay
 
Switchyard
SwitchyardSwitchyard
Switchyard
 
Report on industrial summer training on 220 kv substation
Report  on industrial summer training on 220 kv substationReport  on industrial summer training on 220 kv substation
Report on industrial summer training on 220 kv substation
 
33kv substation
33kv substation33kv substation
33kv substation
 
Types Of Substations
Types Of SubstationsTypes Of Substations
Types Of Substations
 
Gas insulated substation
Gas insulated substationGas insulated substation
Gas insulated substation
 

Similar to Sub stations-air insulated substations

Gssherap 110901224655-phpapp02
Gssherap 110901224655-phpapp02Gssherap 110901224655-phpapp02
Gssherap 110901224655-phpapp02
Mohit Kothari
 
Gssherap 110901224655-phpapp0
Gssherap 110901224655-phpapp0Gssherap 110901224655-phpapp0
Gssherap 110901224655-phpapp0
Mohit Kothari
 
Gssherap 110901224655-phpapp02
Gssherap 110901224655-phpapp02Gssherap 110901224655-phpapp02
Gssherap 110901224655-phpapp02
Mohit Kothari
 

Similar to Sub stations-air insulated substations (20)

132 KV Grid Station Intern ship training report
132 KV Grid Station Intern ship training report132 KV Grid Station Intern ship training report
132 KV Grid Station Intern ship training report
 
the substation components study
the substation components study the substation components study
the substation components study
 
Design of substation
Design of substationDesign of substation
Design of substation
 
Substation
SubstationSubstation
Substation
 
Substation_fundamental.pptx
Substation_fundamental.pptxSubstation_fundamental.pptx
Substation_fundamental.pptx
 
G1-Distri-Transformer.pptx
G1-Distri-Transformer.pptxG1-Distri-Transformer.pptx
G1-Distri-Transformer.pptx
 
REPORT ON 33/11KV SUBSTATION
REPORT ON 33/11KV SUBSTATION REPORT ON 33/11KV SUBSTATION
REPORT ON 33/11KV SUBSTATION
 
ALBA MANUFACTURING OF TRANSFORMERS.pptx
ALBA MANUFACTURING OF TRANSFORMERS.pptxALBA MANUFACTURING OF TRANSFORMERS.pptx
ALBA MANUFACTURING OF TRANSFORMERS.pptx
 
Report on 220kv substation at Jassure
Report on 220kv substation at JassureReport on 220kv substation at Jassure
Report on 220kv substation at Jassure
 
Tuhas chapter 6,distribution substitution
Tuhas chapter 6,distribution substitutionTuhas chapter 6,distribution substitution
Tuhas chapter 6,distribution substitution
 
Gssherap 110901224655-phpapp02
Gssherap 110901224655-phpapp02Gssherap 110901224655-phpapp02
Gssherap 110901224655-phpapp02
 
Gssherap 110901224655-phpapp0
Gssherap 110901224655-phpapp0Gssherap 110901224655-phpapp0
Gssherap 110901224655-phpapp0
 
Gssherap 110901224655-phpapp02
Gssherap 110901224655-phpapp02Gssherap 110901224655-phpapp02
Gssherap 110901224655-phpapp02
 
Trans distn.ppt
Trans distn.pptTrans distn.ppt
Trans distn.ppt
 
TD unit 5-1.ppt
TD unit 5-1.pptTD unit 5-1.ppt
TD unit 5-1.ppt
 
Load Distribution
Load DistributionLoad Distribution
Load Distribution
 
rough.pptx
rough.pptxrough.pptx
rough.pptx
 
66%20Industrial%20Visit%20Report.docx
66%20Industrial%20Visit%20Report.docx66%20Industrial%20Visit%20Report.docx
66%20Industrial%20Visit%20Report.docx
 
Busduct___Busbar.pptx
Busduct___Busbar.pptxBusduct___Busbar.pptx
Busduct___Busbar.pptx
 
Heavy maintenance
Heavy maintenanceHeavy maintenance
Heavy maintenance
 

Recently uploaded

Activity 01 - Artificial Culture (1).pdf
Activity 01 - Artificial Culture (1).pdfActivity 01 - Artificial Culture (1).pdf
Activity 01 - Artificial Culture (1).pdf
ciinovamais
 
The basics of sentences session 3pptx.pptx
The basics of sentences session 3pptx.pptxThe basics of sentences session 3pptx.pptx
The basics of sentences session 3pptx.pptx
heathfieldcps1
 
Jual Obat Aborsi Hongkong ( Asli No.1 ) 085657271886 Obat Penggugur Kandungan...
Jual Obat Aborsi Hongkong ( Asli No.1 ) 085657271886 Obat Penggugur Kandungan...Jual Obat Aborsi Hongkong ( Asli No.1 ) 085657271886 Obat Penggugur Kandungan...
Jual Obat Aborsi Hongkong ( Asli No.1 ) 085657271886 Obat Penggugur Kandungan...
ZurliaSoop
 
1029 - Danh muc Sach Giao Khoa 10 . pdf
1029 -  Danh muc Sach Giao Khoa 10 . pdf1029 -  Danh muc Sach Giao Khoa 10 . pdf
1029 - Danh muc Sach Giao Khoa 10 . pdf
QucHHunhnh
 
Spellings Wk 3 English CAPS CARES Please Practise
Spellings Wk 3 English CAPS CARES Please PractiseSpellings Wk 3 English CAPS CARES Please Practise
Spellings Wk 3 English CAPS CARES Please Practise
AnaAcapella
 

Recently uploaded (20)

Python Notes for mca i year students osmania university.docx
Python Notes for mca i year students osmania university.docxPython Notes for mca i year students osmania university.docx
Python Notes for mca i year students osmania university.docx
 
Activity 01 - Artificial Culture (1).pdf
Activity 01 - Artificial Culture (1).pdfActivity 01 - Artificial Culture (1).pdf
Activity 01 - Artificial Culture (1).pdf
 
The basics of sentences session 3pptx.pptx
The basics of sentences session 3pptx.pptxThe basics of sentences session 3pptx.pptx
The basics of sentences session 3pptx.pptx
 
Key note speaker Neum_Admir Softic_ENG.pdf
Key note speaker Neum_Admir Softic_ENG.pdfKey note speaker Neum_Admir Softic_ENG.pdf
Key note speaker Neum_Admir Softic_ENG.pdf
 
Introduction to Nonprofit Accounting: The Basics
Introduction to Nonprofit Accounting: The BasicsIntroduction to Nonprofit Accounting: The Basics
Introduction to Nonprofit Accounting: The Basics
 
General Principles of Intellectual Property: Concepts of Intellectual Proper...
General Principles of Intellectual Property: Concepts of Intellectual  Proper...General Principles of Intellectual Property: Concepts of Intellectual  Proper...
General Principles of Intellectual Property: Concepts of Intellectual Proper...
 
Jual Obat Aborsi Hongkong ( Asli No.1 ) 085657271886 Obat Penggugur Kandungan...
Jual Obat Aborsi Hongkong ( Asli No.1 ) 085657271886 Obat Penggugur Kandungan...Jual Obat Aborsi Hongkong ( Asli No.1 ) 085657271886 Obat Penggugur Kandungan...
Jual Obat Aborsi Hongkong ( Asli No.1 ) 085657271886 Obat Penggugur Kandungan...
 
Mixin Classes in Odoo 17 How to Extend Models Using Mixin Classes
Mixin Classes in Odoo 17  How to Extend Models Using Mixin ClassesMixin Classes in Odoo 17  How to Extend Models Using Mixin Classes
Mixin Classes in Odoo 17 How to Extend Models Using Mixin Classes
 
Sociology 101 Demonstration of Learning Exhibit
Sociology 101 Demonstration of Learning ExhibitSociology 101 Demonstration of Learning Exhibit
Sociology 101 Demonstration of Learning Exhibit
 
Spatium Project Simulation student brief
Spatium Project Simulation student briefSpatium Project Simulation student brief
Spatium Project Simulation student brief
 
1029 - Danh muc Sach Giao Khoa 10 . pdf
1029 -  Danh muc Sach Giao Khoa 10 . pdf1029 -  Danh muc Sach Giao Khoa 10 . pdf
1029 - Danh muc Sach Giao Khoa 10 . pdf
 
Spellings Wk 3 English CAPS CARES Please Practise
Spellings Wk 3 English CAPS CARES Please PractiseSpellings Wk 3 English CAPS CARES Please Practise
Spellings Wk 3 English CAPS CARES Please Practise
 
Explore beautiful and ugly buildings. Mathematics helps us create beautiful d...
Explore beautiful and ugly buildings. Mathematics helps us create beautiful d...Explore beautiful and ugly buildings. Mathematics helps us create beautiful d...
Explore beautiful and ugly buildings. Mathematics helps us create beautiful d...
 
Micro-Scholarship, What it is, How can it help me.pdf
Micro-Scholarship, What it is, How can it help me.pdfMicro-Scholarship, What it is, How can it help me.pdf
Micro-Scholarship, What it is, How can it help me.pdf
 
How to Give a Domain for a Field in Odoo 17
How to Give a Domain for a Field in Odoo 17How to Give a Domain for a Field in Odoo 17
How to Give a Domain for a Field in Odoo 17
 
Making communications land - Are they received and understood as intended? we...
Making communications land - Are they received and understood as intended? we...Making communications land - Are they received and understood as intended? we...
Making communications land - Are they received and understood as intended? we...
 
SKILL OF INTRODUCING THE LESSON MICRO SKILLS.pptx
SKILL OF INTRODUCING THE LESSON MICRO SKILLS.pptxSKILL OF INTRODUCING THE LESSON MICRO SKILLS.pptx
SKILL OF INTRODUCING THE LESSON MICRO SKILLS.pptx
 
Application orientated numerical on hev.ppt
Application orientated numerical on hev.pptApplication orientated numerical on hev.ppt
Application orientated numerical on hev.ppt
 
Single or Multiple melodic lines structure
Single or Multiple melodic lines structureSingle or Multiple melodic lines structure
Single or Multiple melodic lines structure
 
Kodo Millet PPT made by Ghanshyam bairwa college of Agriculture kumher bhara...
Kodo Millet  PPT made by Ghanshyam bairwa college of Agriculture kumher bhara...Kodo Millet  PPT made by Ghanshyam bairwa college of Agriculture kumher bhara...
Kodo Millet PPT made by Ghanshyam bairwa college of Agriculture kumher bhara...
 

Sub stations-air insulated substations

  • 2.  The assembly of apparatus used to change some characteristic(e.g. Voltage, a.c to d.c, frequency, power factor etc) of electric supply is called a sub-station
  • 3. • It should be located at the centre of gravity of load • It should be easily operated and maintained • It should provide safe and reliable arrangement • It should involve minimum capital cost
  • 5.  Transformer sub stations : these are used to change the voltage levels of supply  switching sub stations: they simply perfome switching operations of power lines  Power factor sub stations: they improve the power factor of the system by using synchronous condensers  Frequency sub stations: those sub stations which change supply frequency  Converting sub stations: those sub stations which change a.c. power to d.c. power  Industrial sub stations: those sub stations which supply power to industries Substations are classified as……..
  • 6. Transformer substations are classified into 4 types these are……..  step up substation: the generation voltage is stepped up to high voltage  Primary grid substation: here the voltage level is step down to 66kv from 220kv for secondary transmission  Secondary substation: the voltage level is further step down to 11kv and these substations are generally outdoor type  Distribution substation: the electric power from 11kv lines is delivered to distribution substation. These are generally located near consumer localities…
  • 7. According to constructional features, the sub stations are classified as:  Indoor sub station: these substations can be installed for voltages up to 11kv  Outdoor sub station: for voltages beyond 66kv these type of sub stations can be installed  Underground sub stations: in thickly populated areas, the space available is less so we install these type of substations  Pole mounted substations: this is an outdoor substation with equipment installed overhead on h-pole or 4 pole structure
  • 8.
  • 9.
  • 10. It is a schematic view of pole mounted substation……
  • 11.
  • 12. While designing a underground sub station the following points are to be followed:  the size of substation should be minimum  There should be reasonable access for both equipment  There should be provision for emergency lights and protection against fire  There should be good ventilation  the transformers,switches,fuses should be air cooled to avoid bringing oil into premises
  • 13.
  • 14.
  • 15.
  • 16.
  • 17.  BUS BARS: various incoming and out going circuits are connected to bus bars.busbars receive power from incoming circuits and deliver power to out going circuits. . Electric substations are the part of power systems and used for transferring power from generating points to load centres.some of important components are…
  • 18.  INSULATORS: insulators serve two purposes 1) they support conductors(busbars) 2) confine the current to the conductors  most commonly used material for manufacture of insulators is porcelain.
  • 19.  ISOLATING SWITCHES: in sub stations it is often desired to disconnect a part of system for general maintenance and repairs. this is accomplished by an isolating switch or isolators.
  • 20.  Circuit breaker: circuit breaker is used for switching during normal and abnormal conditions. it is used to interrupt short circuit currents .there are many types of circuit breakers.. 1) air blast circuit breaker. 2) oil circuit breaker 3) sf6 circuit breaker
  • 21.  power transformers: these are used to step down or step up a.c. voltages and to transfer electrical power from one voltage level to another.
  • 22.  Current transformers: current transformer in essentially a step up transformer which steps down the current to a known ratio.
  • 23.  voltage transformer: it is essentially a step down transformer and steps down the voltage to a known ratio.
  • 24.  metering and indicating instruments: there are several metering and indicating instruments installed in a sub station to maintain watch over the circuit quantities.  in addition to these there may be following equipment in a substation. 1) fuses 2) carrier current equipment 3) sub station auxiliary supplies
  • 25. Single bus bar system…
  • 26.
  • 27.
  • 28.
  • 30. Gas Insulated substations use sulphur hexa fluoride(SF6) gas which has superior dielectric properties. Gas insulated substations are used where there is space for providing the substation is expensive in large cities and towns
  • 31. TYPES OF GAS INSULATED SUBSTATIONS Gas insulated substations are classified according to the type of configurations as………..  isolated phase module  3-phase common modules  hybrid modules Compact modules Highly integrated systems
  • 32. The individual circuit elements such as a pole of a circuit breaker, a single pole isolator, one phase assembly of a current transformer etc..are connected together forms an isolated phase GIS module.
  • 33. In this type of module a three phase bay is assembled using the desired number of three phase elements. This reduces the total number of enclosures to one third.
  • 34. It is the combination of isolated phase and three phase common elements is used to achieve an optimal solution. Hybrid GIS technology has gained popularity, specially in the medium and low voltage range
  • 35. Compact GIS systems are essentially three phase common systems in which the elements such as three phase circuit breaker, current transformer etc…. Are placed
  • 36. These are used in outdoor substations .highly integrated substations are ready to install substations.
  • 37.
  • 38. The high voltage conductor made up of copper or aluminum is centrally placed in a tabular metal enclosure. In isolated phase GIS ,coaxial bus bar are common
  • 39. The main parts of GIS are…….  gas circuit  seals and gaskets  disconnectors  earth switch Circuit breaker Current transformer Plug in joints Enclosure Expansion joints
  • 40.
  • 41. Gas circuit : gas circuit has to maintain the dual purpose (i.e. arc interruption and insulation). Gas circuit should maintain the pressure throughout its life period so there should be no leakages SEALS AND GASKETS : seals and gaskets are used to capture the SF6 gas lekages.these are manufactured with nitrile rubber and viton. These serves sealing purpose
  • 42. Disconnectors or isolators are used for electrical isolation of circuit parts. They are slow acting and operating at off load. Disconnectors must be carefully designed and tested to be able to break small charging current without generating too higher over voltage.
  • 43. Circuit breaker is a metal clad and uses SF6 gas for the purpose of insulation and fault interruption. The circuit breaker is directly connected to either current transformers or isolators
  • 44.
  • 45. fast earth switch: these are used to protect the circuit connected current transformer, voltage transformer Maintenance earth switch: these are used for grounding the high voltage conductors during maintenance
  • 46. PLUG IN JOINTS: these are designed in such a way that they can carry rated full load current uninterruptedly and can carry heavy transient currents types of plug in joints are Static joints Quasi static joints
  • 47. S.NO 145KV 170KV 245KV 1 Bay width (m) 1.5 2.0 2.0 2 Bay depth 3.3 3.35 3.4 3 Bay height 3.2 3.4 3.4 4 Floor area (sq.m) 4.95 6.7 6.8 5 Volume 15.84 22.78 23.12 6 Weight 3800 5000 5700
  • 48. GIS have no risk for fire and explosion due to leakage of oil. They generate no noise and have no radio interference. The maintainence of GIS is free. It offers solutions, -Industrial areas where space and pollution problems . -Mountain areas where ice and snow are major problems.
  • 49. Gas insulations tend to be much more expensive than air insulated installations with the same ratings. Care should be taken that no dust particles enter into the live compartments which results in flash over. When fault occurs internally the diagnosis of the fault and rectifying takes very long time.