Power Usage Effectiveness
(PUE) Status & Directions


      Kathrin Winkler
      Director, The Green Grid
      VP, EMC Corporation
About The Green Grid

• A not-for-profit global consortium focused on driving
  energy efficiency in the computing ecosystem

• Developing meaningful and user-centric metrics to
  help IT and Facilities better manage their computing
  resources

• Developing and promoting standards, measurement
  methods, best practices and technologies that
  support these metrics

                                                          2
2                 Copyright © 2010, The Green Grid
Why Create Metrics?
       Awareness             Benchmarking                      Consistency
    • “If you can’t         • Continuous                     • Common
      measure it, you         improvement of                   Vocabulary
      can’t improve it”       operations
                                                             • Industry &
    • Finding the hot       • Comparing across                 Government
      spots                   the industry                     Collaboration

                            • Improvement                    • Better Efficiency
                              over time/
                              generation to
                              generation

                            • Validate claims



                                                                3
3                         Copyright © 2010, The Green Grid
Impact of IT Power Consumption
                                                            Computer Room Air
                                                            Conditioner power
            Server, network and storage                     consumption
            power consumption
                                                            23% - 54%
            38% - 63%

Battery Backup power
consumption
6% - 13%




                                                              Lighting power
                                                              consumption
                                                              1% - 2%

            Server Power Consumption Impacts Power
            throughout the Datacenter


4                        Copyright © 2010, The Green Grid
Data Center Power Efficiency Metrics:
    PUE and DCiE




                                                           Total Facility Power
      PUE = Power Usage Effectiveness =
                                                          IT Equipment Power

                    Data Center                 1    IT Equipment Power
     DCiE =                             =          =
              Infrastructure Efficiency        PUE    Total Facility Power

5                           Copyright © 2010, The Green Grid
PUE Refined
                                        Total Facility Power or Energy
              PUE =
                                       IT Equipment Power or Energy

                             Point of
                           Measurement


                           Frequency of
                           Measurement


                            Duration of
                           Measurement

6                                       Copyright © 2010, The Green (DCiE) Detailed Analysis (white paper #14) 60
    Sources: The Green Grid Metrics: Data Center Infrastructure EfficiencyGrid
             Usage and Public Reporting Guidelines for The Green Grid's Infrastructure Metrics PUE/DCiE (white paper #22)
PUE clarifications

    • PUEs of < 1.0 and DCiEs of > 1.0 are *not* allowed

    • These elements are always ≥ 0
       – Power consumed by IT equipment
       – Power lost in distribution
       – Power consumed by cooling equipment


    • PUE measures use within the data center, and does
      not include
       – Re-use of waste heat
       – Distributed power generation

7                      Copyright © 2010, The Green Grid
PUE Nomenclature
    Official PUE reports provide these information
      with subscripts appended to the metric

            PUEx,y              or               DCiEx,y

      x = Precision level of measurement (L1, L2, L3)
      y = Timeframe and collection frequency:
                       D    =     Daily
                      W     =     Weekly
                      M     =     Monthly
                       Y    =     Yearly
                       C    =     Continuously



8                   Copyright © 2010, The Green Grid
Reporting Precision
                            Level 1              Level 2           Level 3
                            (Basic)          (Intermediate)      (Advanced)

                                                              Server, Storage
IT Equipment Power
                             UPS                   PDU        device, Router,
Measurement From…
                                                              etc.

                                                Data Center
                                                input less
                                   Data Center
Total Facility Power   Data Center              shared HVAC
                                     input less
Measurement From…      input power              plus building
                                   shared HVAC
                                                lighting,
                                                security, etc.

Minimum                  Monthly/
                                                   Daily      Continuous
Measurement Interval     Weekly
9                      Copyright © 2010, The Green Grid
Example Reported Results
                      Single DCiE measurement (0.45) taken using a Level 1 meter
     0.45 DCiEL1,--   placement

                      Yearly average DCiE (0.51), using data points gathered monthly
     0.51 DCiEL1,YM   with a Level 1 meter placement


                      Monthly average PUE (1.6) using data points gathered weekly with
     1.6 PUEL1,MW     a Level 1 meter placement


                      Weekly average DCiE (0.43), using data points gathered daily with a
     0.43DCiEL1,WD    Level 1 meter placement


                      Weekly average PUE using data points gathered continuously with
     1.8 PUEL2,WC     a Level 2 meter placement.


                      Yearly average PUE (2.1) using continuous measurements with a
      2.1 PUEL3,YC    Level 3 meter placement.



10                         Copyright © 2010, The Green Grid
Classes of Measurement
ResultsClass      Description                                       Benefit to Reporting Organization

Unrecognized      A publicly reported result with no
                  claims of following TGG’s guidelines.
                  TGG will not comment on unrecognized
                  results.
     Reported     A publicly reported result by the                 Reporting organization can
                  reporting organization claiming they              use standard materials from
                  followed TGG’s measurement                        The Green Grid to explain
                  recommendations and nomenclature                  process and results to
                  guidelines. TGG will not comment on               audience.
                  Reported results.

     Registered   A publicly reported result, with key              Official registration of
                  report contextual data provided to TGG            reported result. Receipt of a
                  by the reporting organization to TGG’s            registration number from TGG.
                  data center performance database.                 Link to public report data from
                                                                    TGG’s website.
      Certified   A publicly reported result, with key              All benefits applicable to
                  additional data required for third-party          registered results, plus,
                  validation or certification of results,           consideration of reported
                  provided to TGG by the reporting                  results in future TGG award or
                  organization.                                     recognition programs.

11                               Copyright © 2010, The Green Grid
Putting Metrics into Global Action




                               • PUE Reporting Tool
                               • PUE Estimator Tool
                               • Power Configuration Efficiency Tool

12               Copyright © 2010, The Green Grid
PUE Scalability Metric




13              Copyright © 2010, The Green Grid
Partial PUE Definition
     • PUE = Total Facility Power divided by the
       IT Equipment Power
     • This takes into account power use within a
       facility
     • Partial PUE is for power use within a
       boundary
     • So:
         pPUE = Total Power within a boundary divided
         by the IT Equipment Power within that
         boundary

14                  Copyright © 2010, The Green Grid
pPUE Example

       121 kW     Transformer                          Container
                       6 kW
         115 kW                                   UPS       5 kW
                       100 kW
                                                                   95 kW

                                                    IT Equipment
                       15 kW

                      Chiller                                 30 tons
                                             Cooling




 • PUE = 121/95 = 1.27
 • pPUE of Container = 100/95 = 1.05
15                       Copyright © 2010, The Green Grid
  15
Energy Reuse Factor
                                                                        rejected
                                                     Non-DC
                                                     space
                                                                  H
                          Cool
                                                        G     Absorp
                                                              Chiller
                     A                    E
                                                                            I
      Utility
                                                              F
                                                    ICT
                B

                    UPS    C     PDU
                                                      D


                                                                  Data Center
      A+B                       A + B- F                          Boundary
PUE =                      ERF=
       D                           D
                    Both PUE & ERF valid metrics
16                        Copyright © 2010, The Green Grid
TGG Metrics

How efficient is my facility in                              Total Facility Power
  delivering power to IT                    PUE =           IT Equipment Power
        equipment?


 What % of facility power is                            IT Equipment Power
    delivered to my IT                     DCiE = Total Facility Power             x 100%
       equipment?



 How Much Work Can My IT                                       Useful Work
Equipment Do, In My Facility?              DCP=             Total Facility Power




                         Copyright © 2010, The Green Grid
Data Center Energy Productivity
 •     Data Center Energy Productivity (DCeP)




 •     First attempt to define useful work metric
 •     Very comprehensive, very accurate
 •     However, difficult to measure
 •     Some terms require user interpretation
     – eg., Ui(t,T) is the utility (value) of a transaction
     – Subjective, could be different for each organization


18                     Copyright © 2010, The Green Grid
Alternative Proposal - Proxies
     • Proxies indicate how much work is being
       done without measuring work directly
         Should be highly correlated to useful work
         Should be easier, cheaper, faster to collect


     • Proxies are often used where complex
       measures would be impractical
         eg., EPA Miles Per Gallon,
         marketing focus group,
         Dow Jones Industrial Average,
         or CNN Audience Reaction Meter



19                      Copyright © 2010, The Green Grid
Proxy Proposals
      1. DCeP-based Proxies
        • Simplified DCeP
        • Productivity Link
        • Sample workload
      2. Bits per kWH
      3. CPU-based proxies
        • SPECint_rate
        • SPECpower
        • CUPS
      4. OS images per Watt

20                 Copyright © 2010, The Green Grid
Proxy Shortcomings
In general, the proxy proposals:
• Aren’t meant for comparison between data centers
       Useful for tracking progress within a data center over time
       No guidelines for use and reporting, so wide variation
       possible

• Don’t address all data center devices equally
       Proposals tend to be server-centric
       Storage, networking, telephony, appliances, co-processors,
       etc

• Don’t consider the value of stored data
• Don’t account for interaction between devices
21                     Copyright © 2010, The Green Grid
Where to Next?

     • Proxies
        • Currently testing IT Productivity Proxies with the US
          National Labs
        • Using instrumented applications as a control
        • Starting with the Intel Energy Checker SDK as a basis for
          instrumenting applications within the Data Center Design
          Guide effort
        • Sharing results with other organizations globally




22                       Copyright © 2010, The Green Grid
Metric Harmonization
     Efforts
     • Global Metric Harmonization
         Ministry of Economy, Trade and Industry (METI)
         Green IT Promotional Council (GIPC)
         The U.S. Department of Energy (DOE)
         The U.S. Environmental Protection Agency (EPA)
         The European Union (EU)
         The Green Grid (TGG)

     • US Industry Consensus Session
         Environmental Protection Agency (EPA)
         Department of Energy (DOE)
         7x24 Exchange
         American Socienty of Heating, Refrigerating and Air-conditioning
         Engineers (ASHRAE)
         Silicon Valley Leadership Group (SVLG)
         The Green Grid (TGG)
         Uptime Institute
         United States Green Building Council (USGBC)
23                         Copyright © 2010, The Green Grid
Possible New PUE Variations
     • M&M WG has an approved AR to review
       and identify if we will proceed with any
       further possible variations of PUE
     • PUE Estimated
     • PUE Calculated
     • Design PUE
     • Design Day PUE
     • Virtual PUE
     • ….

24                  Copyright © 2010, The Green Grid
PUE Related Information
     Material Papers:
     • Current White
         1.   Describing Data Center Power Efficiency
         2.   PUE and DCiE Efficiency Metrics
         3.   DCiE Detailed Analysis
         4.   PUE Scalability
         5.   Usage and Public Reporting Guidelines
     •   Future Possible White Papers:
         1.   DCiE Detailed Analysis II
         2.   Partial PUE
         3.   Energy Re-use Factor & Re-use Energy Ratio
         4.   Possible new variations of PUE



25                        Copyright © 2010, The Green Grid
For More Information
• www.thegreengrid.org
  for whitepapers, training,
  and content

• For membership, please contact us:
  +1 503-619-0653 or
  admin@lists.thegreengrid.org

          Thank you to our members for your
        continued dedication and involvement in
              ICT energy efficiency efforts!
26                 Copyright © 2010, The Green Grid
Thank you!

For more information please go to
     www.thegreengrid.org




         Copyright © 2010, The Green Grid

More Related Content

What's hot

Restoration of Old Documents that Suffer from Degradation
Restoration of Old Documents that Suffer from DegradationRestoration of Old Documents that Suffer from Degradation
Restoration of Old Documents that Suffer from DegradationIRJET Journal
 
IRJET- A Hybrid Approach for Fire Safety Intensives Automatic Assistance ...
IRJET-  	  A Hybrid Approach for Fire Safety Intensives Automatic Assistance ...IRJET-  	  A Hybrid Approach for Fire Safety Intensives Automatic Assistance ...
IRJET- A Hybrid Approach for Fire Safety Intensives Automatic Assistance ...IRJET Journal
 
MULTI WAVELET BASED IMAGE COMPRESSION FOR TELE MEDICAL APPLICATION
MULTI WAVELET BASED IMAGE COMPRESSION FOR TELE MEDICAL APPLICATIONMULTI WAVELET BASED IMAGE COMPRESSION FOR TELE MEDICAL APPLICATION
MULTI WAVELET BASED IMAGE COMPRESSION FOR TELE MEDICAL APPLICATIONprj_publication
 
Dead node detection in teen protocol
Dead node detection in teen protocolDead node detection in teen protocol
Dead node detection in teen protocoleSAT Journals
 
Dead node detection in teen protocol survey
Dead node detection in teen protocol surveyDead node detection in teen protocol survey
Dead node detection in teen protocol surveyeSAT Publishing House
 
Coldset Case Study
Coldset Case StudyColdset Case Study
Coldset Case StudyTalyam
 
DESIGN AND IMPLEMENTATION OF A WIRELESS SENSOR AND ACTUATOR NETWORK FOR ENERG...
DESIGN AND IMPLEMENTATION OF A WIRELESS SENSOR AND ACTUATOR NETWORK FOR ENERG...DESIGN AND IMPLEMENTATION OF A WIRELESS SENSOR AND ACTUATOR NETWORK FOR ENERG...
DESIGN AND IMPLEMENTATION OF A WIRELESS SENSOR AND ACTUATOR NETWORK FOR ENERG...ijesajournal
 
Idc Ei Smart Buildings Maturity Model Webcast 4 3 12 Slides
Idc Ei Smart Buildings Maturity Model Webcast 4 3 12 SlidesIdc Ei Smart Buildings Maturity Model Webcast 4 3 12 Slides
Idc Ei Smart Buildings Maturity Model Webcast 4 3 12 SlidesCasey Talon
 
Energy-aware VM Allocation on An Opportunistic Cloud Infrastructure
Energy-aware VM Allocation on An Opportunistic Cloud InfrastructureEnergy-aware VM Allocation on An Opportunistic Cloud Infrastructure
Energy-aware VM Allocation on An Opportunistic Cloud InfrastructureMario Jose Villamizar Cano
 
The True Value of Grid Reliability
The True Value of Grid ReliabilityThe True Value of Grid Reliability
The True Value of Grid ReliabilityEchelon Corporation
 
IRJET- Enhancement of Image using Fuzzy Inference System for Remotely Sen...
IRJET-  	  Enhancement of Image using Fuzzy Inference System for Remotely Sen...IRJET-  	  Enhancement of Image using Fuzzy Inference System for Remotely Sen...
IRJET- Enhancement of Image using Fuzzy Inference System for Remotely Sen...IRJET Journal
 
Harvesting aware energy management for time-critical wireless sensor networks
Harvesting aware energy management for time-critical wireless sensor networksHarvesting aware energy management for time-critical wireless sensor networks
Harvesting aware energy management for time-critical wireless sensor networksIEEEFINALYEARPROJECTS
 
Hairong Qi V Swaminathan
Hairong Qi V SwaminathanHairong Qi V Swaminathan
Hairong Qi V SwaminathanFNian
 
Optimize your infrastructure for better efficiency - Branko Avramovski, Micro...
Optimize your infrastructure for better efficiency - Branko Avramovski, Micro...Optimize your infrastructure for better efficiency - Branko Avramovski, Micro...
Optimize your infrastructure for better efficiency - Branko Avramovski, Micro...Metamorphosis
 
View from an energy efficiency enabler: Beyond energy savings, Martin Kruska...
View from an energy efficiency enabler: Beyond energy savings, Martin Kruska...View from an energy efficiency enabler: Beyond energy savings, Martin Kruska...
View from an energy efficiency enabler: Beyond energy savings, Martin Kruska...EuropeanPaper
 
Practice Partner® Patient Records with Bright Note Technology™
Practice Partner® Patient Records with Bright Note Technology™Practice Partner® Patient Records with Bright Note Technology™
Practice Partner® Patient Records with Bright Note Technology™McKesson Physician Practice
 
IRJET - Energy Efficient Approach for Data Aggregation in IoT
IRJET -  	  Energy Efficient Approach for Data Aggregation in IoTIRJET -  	  Energy Efficient Approach for Data Aggregation in IoT
IRJET - Energy Efficient Approach for Data Aggregation in IoTIRJET Journal
 

What's hot (20)

Restoration of Old Documents that Suffer from Degradation
Restoration of Old Documents that Suffer from DegradationRestoration of Old Documents that Suffer from Degradation
Restoration of Old Documents that Suffer from Degradation
 
IRJET- A Hybrid Approach for Fire Safety Intensives Automatic Assistance ...
IRJET-  	  A Hybrid Approach for Fire Safety Intensives Automatic Assistance ...IRJET-  	  A Hybrid Approach for Fire Safety Intensives Automatic Assistance ...
IRJET- A Hybrid Approach for Fire Safety Intensives Automatic Assistance ...
 
Joulex & Junos Space SDK: Customer Success Story
Joulex & Junos Space SDK: Customer Success StoryJoulex & Junos Space SDK: Customer Success Story
Joulex & Junos Space SDK: Customer Success Story
 
MULTI WAVELET BASED IMAGE COMPRESSION FOR TELE MEDICAL APPLICATION
MULTI WAVELET BASED IMAGE COMPRESSION FOR TELE MEDICAL APPLICATIONMULTI WAVELET BASED IMAGE COMPRESSION FOR TELE MEDICAL APPLICATION
MULTI WAVELET BASED IMAGE COMPRESSION FOR TELE MEDICAL APPLICATION
 
Dead node detection in teen protocol
Dead node detection in teen protocolDead node detection in teen protocol
Dead node detection in teen protocol
 
Dead node detection in teen protocol survey
Dead node detection in teen protocol surveyDead node detection in teen protocol survey
Dead node detection in teen protocol survey
 
Coldset Case Study
Coldset Case StudyColdset Case Study
Coldset Case Study
 
DESIGN AND IMPLEMENTATION OF A WIRELESS SENSOR AND ACTUATOR NETWORK FOR ENERG...
DESIGN AND IMPLEMENTATION OF A WIRELESS SENSOR AND ACTUATOR NETWORK FOR ENERG...DESIGN AND IMPLEMENTATION OF A WIRELESS SENSOR AND ACTUATOR NETWORK FOR ENERG...
DESIGN AND IMPLEMENTATION OF A WIRELESS SENSOR AND ACTUATOR NETWORK FOR ENERG...
 
Idc Ei Smart Buildings Maturity Model Webcast 4 3 12 Slides
Idc Ei Smart Buildings Maturity Model Webcast 4 3 12 SlidesIdc Ei Smart Buildings Maturity Model Webcast 4 3 12 Slides
Idc Ei Smart Buildings Maturity Model Webcast 4 3 12 Slides
 
Energy-aware VM Allocation on An Opportunistic Cloud Infrastructure
Energy-aware VM Allocation on An Opportunistic Cloud InfrastructureEnergy-aware VM Allocation on An Opportunistic Cloud Infrastructure
Energy-aware VM Allocation on An Opportunistic Cloud Infrastructure
 
The True Value of Grid Reliability
The True Value of Grid ReliabilityThe True Value of Grid Reliability
The True Value of Grid Reliability
 
IRJET- Enhancement of Image using Fuzzy Inference System for Remotely Sen...
IRJET-  	  Enhancement of Image using Fuzzy Inference System for Remotely Sen...IRJET-  	  Enhancement of Image using Fuzzy Inference System for Remotely Sen...
IRJET- Enhancement of Image using Fuzzy Inference System for Remotely Sen...
 
Harvesting aware energy management for time-critical wireless sensor networks
Harvesting aware energy management for time-critical wireless sensor networksHarvesting aware energy management for time-critical wireless sensor networks
Harvesting aware energy management for time-critical wireless sensor networks
 
Hairong Qi V Swaminathan
Hairong Qi V SwaminathanHairong Qi V Swaminathan
Hairong Qi V Swaminathan
 
Optimize your infrastructure for better efficiency - Branko Avramovski, Micro...
Optimize your infrastructure for better efficiency - Branko Avramovski, Micro...Optimize your infrastructure for better efficiency - Branko Avramovski, Micro...
Optimize your infrastructure for better efficiency - Branko Avramovski, Micro...
 
View from an energy efficiency enabler: Beyond energy savings, Martin Kruska...
View from an energy efficiency enabler: Beyond energy savings, Martin Kruska...View from an energy efficiency enabler: Beyond energy savings, Martin Kruska...
View from an energy efficiency enabler: Beyond energy savings, Martin Kruska...
 
Embedded Service Oriented Monitoring for the Energy Aware Factory
Embedded Service Oriented Monitoring for the Energy Aware Factory Embedded Service Oriented Monitoring for the Energy Aware Factory
Embedded Service Oriented Monitoring for the Energy Aware Factory
 
Practice Partner® Patient Records with Bright Note Technology™
Practice Partner® Patient Records with Bright Note Technology™Practice Partner® Patient Records with Bright Note Technology™
Practice Partner® Patient Records with Bright Note Technology™
 
Content
ContentContent
Content
 
IRJET - Energy Efficient Approach for Data Aggregation in IoT
IRJET -  	  Energy Efficient Approach for Data Aggregation in IoTIRJET -  	  Energy Efficient Approach for Data Aggregation in IoT
IRJET - Energy Efficient Approach for Data Aggregation in IoT
 

Similar to Estado actual y proyecciones futuras de PUE/DCiE

PUE Reconsidered - AFCOM (MI), July 2009
PUE Reconsidered - AFCOM (MI), July 2009PUE Reconsidered - AFCOM (MI), July 2009
PUE Reconsidered - AFCOM (MI), July 2009Henry Hsu
 
Raritan Data Center Marketplace Pue
Raritan   Data Center Marketplace   PueRaritan   Data Center Marketplace   Pue
Raritan Data Center Marketplace Puewlambert_2001
 
Benchmark the Relative Performance of Your Data Center
Benchmark the Relative Performance of Your Data CenterBenchmark the Relative Performance of Your Data Center
Benchmark the Relative Performance of Your Data CenterAFCOM
 
Facility Optimization
Facility OptimizationFacility Optimization
Facility Optimizationcwoodson
 
Gfs crane dc measuring pu at multiple levels
Gfs crane dc measuring pu at multiple levelsGfs crane dc measuring pu at multiple levels
Gfs crane dc measuring pu at multiple levelsSwagata Mukherji
 
SunGard - Defining Sustainability Metrics (KpIs)
SunGard - Defining Sustainability Metrics (KpIs)SunGard - Defining Sustainability Metrics (KpIs)
SunGard - Defining Sustainability Metrics (KpIs)Harmeda
 
Data Center PUE Reconsidered
Data Center PUE Reconsidered Data Center PUE Reconsidered
Data Center PUE Reconsidered Raritan
 
Houston's Smart Grid: Transforming the Future of Electric Distribution & Ener...
Houston's Smart Grid: Transforming the Future of Electric Distribution & Ener...Houston's Smart Grid: Transforming the Future of Electric Distribution & Ener...
Houston's Smart Grid: Transforming the Future of Electric Distribution & Ener...aectnet
 
Koomeyondatacenterelectricityuse v24
Koomeyondatacenterelectricityuse v24Koomeyondatacenterelectricityuse v24
Koomeyondatacenterelectricityuse v24Jonathan Koomey
 
Ppt4 london - michael rudgyard ( concurrent thinking ) driving efficiencie...
Ppt4   london -  michael rudgyard ( concurrent thinking ) driving efficiencie...Ppt4   london -  michael rudgyard ( concurrent thinking ) driving efficiencie...
Ppt4 london - michael rudgyard ( concurrent thinking ) driving efficiencie...JISC's Green ICT Programme
 
Av power consumption trial executive summary v1 0
Av power consumption trial executive summary v1 0Av power consumption trial executive summary v1 0
Av power consumption trial executive summary v1 0Anatol Alizar
 
Bringing Enterprise IT into the 21st Century: A Management and Sustainabilit...
Bringing Enterprise IT into the 21st Century:  A Management and Sustainabilit...Bringing Enterprise IT into the 21st Century:  A Management and Sustainabilit...
Bringing Enterprise IT into the 21st Century: A Management and Sustainabilit...Jonathan Koomey
 
Industrial Mains Power Monitoring and Alert System Over LAN Network
Industrial Mains Power Monitoring and Alert System Over LAN NetworkIndustrial Mains Power Monitoring and Alert System Over LAN Network
Industrial Mains Power Monitoring and Alert System Over LAN NetworkIRJET Journal
 
The Data Center in Real Time: Monitoring Tools Overview & Demo
The Data Center in Real Time: Monitoring Tools Overview & DemoThe Data Center in Real Time: Monitoring Tools Overview & Demo
The Data Center in Real Time: Monitoring Tools Overview & Demo42U Data Center Solutions
 
Co c dc-best practices
Co c dc-best practicesCo c dc-best practices
Co c dc-best practicesavdsouza
 
Strategies for Re-Using Data Center Heat Energy and Their Impact on PUE (Both...
Strategies for Re-Using Data Center Heat Energy and Their Impact on PUE (Both...Strategies for Re-Using Data Center Heat Energy and Their Impact on PUE (Both...
Strategies for Re-Using Data Center Heat Energy and Their Impact on PUE (Both...Upsite Technologies
 
IRJET- The Next Generation Green Data Center:Multi-Facetapproach to Reduc...
IRJET-  	  The Next Generation Green Data Center:Multi-Facetapproach to Reduc...IRJET-  	  The Next Generation Green Data Center:Multi-Facetapproach to Reduc...
IRJET- The Next Generation Green Data Center:Multi-Facetapproach to Reduc...IRJET Journal
 
BLOG-POST_HOW STAKEHOLDERS VIEW PUE
BLOG-POST_HOW STAKEHOLDERS VIEW PUEBLOG-POST_HOW STAKEHOLDERS VIEW PUE
BLOG-POST_HOW STAKEHOLDERS VIEW PUEDaniel Bodenski
 
Trends in HPC Power Metrics and where to from here Ramkumar Nagappan Intel Final
Trends in HPC Power Metrics and where to from here Ramkumar Nagappan Intel FinalTrends in HPC Power Metrics and where to from here Ramkumar Nagappan Intel Final
Trends in HPC Power Metrics and where to from here Ramkumar Nagappan Intel FinalRamkumar Nagappan
 

Similar to Estado actual y proyecciones futuras de PUE/DCiE (20)

PUE Reconsidered - AFCOM (MI), July 2009
PUE Reconsidered - AFCOM (MI), July 2009PUE Reconsidered - AFCOM (MI), July 2009
PUE Reconsidered - AFCOM (MI), July 2009
 
Raritan Data Center Marketplace Pue
Raritan   Data Center Marketplace   PueRaritan   Data Center Marketplace   Pue
Raritan Data Center Marketplace Pue
 
Benchmark the Relative Performance of Your Data Center
Benchmark the Relative Performance of Your Data CenterBenchmark the Relative Performance of Your Data Center
Benchmark the Relative Performance of Your Data Center
 
Facility Optimization
Facility OptimizationFacility Optimization
Facility Optimization
 
Gfs crane dc measuring pu at multiple levels
Gfs crane dc measuring pu at multiple levelsGfs crane dc measuring pu at multiple levels
Gfs crane dc measuring pu at multiple levels
 
SunGard - Defining Sustainability Metrics (KpIs)
SunGard - Defining Sustainability Metrics (KpIs)SunGard - Defining Sustainability Metrics (KpIs)
SunGard - Defining Sustainability Metrics (KpIs)
 
Data Center PUE Reconsidered
Data Center PUE Reconsidered Data Center PUE Reconsidered
Data Center PUE Reconsidered
 
Houston's Smart Grid: Transforming the Future of Electric Distribution & Ener...
Houston's Smart Grid: Transforming the Future of Electric Distribution & Ener...Houston's Smart Grid: Transforming the Future of Electric Distribution & Ener...
Houston's Smart Grid: Transforming the Future of Electric Distribution & Ener...
 
Koomeyondatacenterelectricityuse v24
Koomeyondatacenterelectricityuse v24Koomeyondatacenterelectricityuse v24
Koomeyondatacenterelectricityuse v24
 
Ppt4 london - michael rudgyard ( concurrent thinking ) driving efficiencie...
Ppt4   london -  michael rudgyard ( concurrent thinking ) driving efficiencie...Ppt4   london -  michael rudgyard ( concurrent thinking ) driving efficiencie...
Ppt4 london - michael rudgyard ( concurrent thinking ) driving efficiencie...
 
Av power consumption trial executive summary v1 0
Av power consumption trial executive summary v1 0Av power consumption trial executive summary v1 0
Av power consumption trial executive summary v1 0
 
Bringing Enterprise IT into the 21st Century: A Management and Sustainabilit...
Bringing Enterprise IT into the 21st Century:  A Management and Sustainabilit...Bringing Enterprise IT into the 21st Century:  A Management and Sustainabilit...
Bringing Enterprise IT into the 21st Century: A Management and Sustainabilit...
 
PUE Reconsidered
PUE ReconsideredPUE Reconsidered
PUE Reconsidered
 
Industrial Mains Power Monitoring and Alert System Over LAN Network
Industrial Mains Power Monitoring and Alert System Over LAN NetworkIndustrial Mains Power Monitoring and Alert System Over LAN Network
Industrial Mains Power Monitoring and Alert System Over LAN Network
 
The Data Center in Real Time: Monitoring Tools Overview & Demo
The Data Center in Real Time: Monitoring Tools Overview & DemoThe Data Center in Real Time: Monitoring Tools Overview & Demo
The Data Center in Real Time: Monitoring Tools Overview & Demo
 
Co c dc-best practices
Co c dc-best practicesCo c dc-best practices
Co c dc-best practices
 
Strategies for Re-Using Data Center Heat Energy and Their Impact on PUE (Both...
Strategies for Re-Using Data Center Heat Energy and Their Impact on PUE (Both...Strategies for Re-Using Data Center Heat Energy and Their Impact on PUE (Both...
Strategies for Re-Using Data Center Heat Energy and Their Impact on PUE (Both...
 
IRJET- The Next Generation Green Data Center:Multi-Facetapproach to Reduc...
IRJET-  	  The Next Generation Green Data Center:Multi-Facetapproach to Reduc...IRJET-  	  The Next Generation Green Data Center:Multi-Facetapproach to Reduc...
IRJET- The Next Generation Green Data Center:Multi-Facetapproach to Reduc...
 
BLOG-POST_HOW STAKEHOLDERS VIEW PUE
BLOG-POST_HOW STAKEHOLDERS VIEW PUEBLOG-POST_HOW STAKEHOLDERS VIEW PUE
BLOG-POST_HOW STAKEHOLDERS VIEW PUE
 
Trends in HPC Power Metrics and where to from here Ramkumar Nagappan Intel Final
Trends in HPC Power Metrics and where to from here Ramkumar Nagappan Intel FinalTrends in HPC Power Metrics and where to from here Ramkumar Nagappan Intel Final
Trends in HPC Power Metrics and where to from here Ramkumar Nagappan Intel Final
 

More from Data Center Consultores

Tiers (Un vistazo a los Tiers, Mitos y concepciones erróneas)
Tiers (Un vistazo a los Tiers, Mitos y concepciones erróneas)Tiers (Un vistazo a los Tiers, Mitos y concepciones erróneas)
Tiers (Un vistazo a los Tiers, Mitos y concepciones erróneas)Data Center Consultores
 
Proyección del Uptime Institute hacia Latinoamérica
Proyección del Uptime Institute hacia LatinoaméricaProyección del Uptime Institute hacia Latinoamérica
Proyección del Uptime Institute hacia LatinoaméricaData Center Consultores
 
Nueva generación de enfriamiento en Data Centers: Smart Aisle
Nueva generación de enfriamiento en Data Centers: Smart AisleNueva generación de enfriamiento en Data Centers: Smart Aisle
Nueva generación de enfriamiento en Data Centers: Smart AisleData Center Consultores
 
Cómo proteger su activo más importante: la Información
Cómo proteger su activo más importante: la InformaciónCómo proteger su activo más importante: la Información
Cómo proteger su activo más importante: la InformaciónData Center Consultores
 
Estrategias para ahorro de energía en applicaciones de misión crítica de IT
Estrategias para ahorro de energía en applicaciones de misión crítica de ITEstrategias para ahorro de energía en applicaciones de misión crítica de IT
Estrategias para ahorro de energía en applicaciones de misión crítica de ITData Center Consultores
 
Claves para el diseño conceptual de Centro de Datos
Claves para el diseño conceptual de Centro de DatosClaves para el diseño conceptual de Centro de Datos
Claves para el diseño conceptual de Centro de DatosData Center Consultores
 
Sistemas de Seguridad para Centros de Datos de Alta Disponibilidad
Sistemas de Seguridad para Centros de Datos de Alta DisponibilidadSistemas de Seguridad para Centros de Datos de Alta Disponibilidad
Sistemas de Seguridad para Centros de Datos de Alta DisponibilidadData Center Consultores
 
Nuevo estándar para diseño de data center ANSI/BICSI-002
Nuevo estándar para diseño de data center ANSI/BICSI-002Nuevo estándar para diseño de data center ANSI/BICSI-002
Nuevo estándar para diseño de data center ANSI/BICSI-002Data Center Consultores
 
Una visión a las tendencias y nuevas tenologías en Centros de Datos
Una visión a las tendencias y nuevas tenologías en Centros de DatosUna visión a las tendencias y nuevas tenologías en Centros de Datos
Una visión a las tendencias y nuevas tenologías en Centros de DatosData Center Consultores
 

More from Data Center Consultores (16)

Tiers (Un vistazo a los Tiers, Mitos y concepciones erróneas)
Tiers (Un vistazo a los Tiers, Mitos y concepciones erróneas)Tiers (Un vistazo a los Tiers, Mitos y concepciones erróneas)
Tiers (Un vistazo a los Tiers, Mitos y concepciones erróneas)
 
Proyección del Uptime Institute hacia Latinoamérica
Proyección del Uptime Institute hacia LatinoaméricaProyección del Uptime Institute hacia Latinoamérica
Proyección del Uptime Institute hacia Latinoamérica
 
Virtualización para la Eficiencia
Virtualización para la EficienciaVirtualización para la Eficiencia
Virtualización para la Eficiencia
 
Diseñando el Data Center del Futuro
Diseñando el Data Center del FuturoDiseñando el Data Center del Futuro
Diseñando el Data Center del Futuro
 
Nueva generación de enfriamiento en Data Centers: Smart Aisle
Nueva generación de enfriamiento en Data Centers: Smart AisleNueva generación de enfriamiento en Data Centers: Smart Aisle
Nueva generación de enfriamiento en Data Centers: Smart Aisle
 
Cómo proteger su activo más importante: la Información
Cómo proteger su activo más importante: la InformaciónCómo proteger su activo más importante: la Información
Cómo proteger su activo más importante: la Información
 
Infraestructura TI en armonía
Infraestructura TI en armoníaInfraestructura TI en armonía
Infraestructura TI en armonía
 
Gamatronics Solutions for Data Centers
Gamatronics Solutions for Data CentersGamatronics Solutions for Data Centers
Gamatronics Solutions for Data Centers
 
Estrategias para ahorro de energía en applicaciones de misión crítica de IT
Estrategias para ahorro de energía en applicaciones de misión crítica de ITEstrategias para ahorro de energía en applicaciones de misión crítica de IT
Estrategias para ahorro de energía en applicaciones de misión crítica de IT
 
Claves para el diseño conceptual de Centro de Datos
Claves para el diseño conceptual de Centro de DatosClaves para el diseño conceptual de Centro de Datos
Claves para el diseño conceptual de Centro de Datos
 
Sistemas de Seguridad para Centros de Datos de Alta Disponibilidad
Sistemas de Seguridad para Centros de Datos de Alta DisponibilidadSistemas de Seguridad para Centros de Datos de Alta Disponibilidad
Sistemas de Seguridad para Centros de Datos de Alta Disponibilidad
 
Case Study Caso Thor
Case Study Caso ThorCase Study Caso Thor
Case Study Caso Thor
 
Data Center as a Service
Data Center as a ServiceData Center as a Service
Data Center as a Service
 
Nuevo estándar para diseño de data center ANSI/BICSI-002
Nuevo estándar para diseño de data center ANSI/BICSI-002Nuevo estándar para diseño de data center ANSI/BICSI-002
Nuevo estándar para diseño de data center ANSI/BICSI-002
 
Una visión a las tendencias y nuevas tenologías en Centros de Datos
Una visión a las tendencias y nuevas tenologías en Centros de DatosUna visión a las tendencias y nuevas tenologías en Centros de Datos
Una visión a las tendencias y nuevas tenologías en Centros de Datos
 
Data Center Green
Data Center GreenData Center Green
Data Center Green
 

Estado actual y proyecciones futuras de PUE/DCiE

  • 1. Power Usage Effectiveness (PUE) Status & Directions Kathrin Winkler Director, The Green Grid VP, EMC Corporation
  • 2. About The Green Grid • A not-for-profit global consortium focused on driving energy efficiency in the computing ecosystem • Developing meaningful and user-centric metrics to help IT and Facilities better manage their computing resources • Developing and promoting standards, measurement methods, best practices and technologies that support these metrics 2 2 Copyright © 2010, The Green Grid
  • 3. Why Create Metrics? Awareness Benchmarking Consistency • “If you can’t • Continuous • Common measure it, you improvement of Vocabulary can’t improve it” operations • Industry & • Finding the hot • Comparing across Government spots the industry Collaboration • Improvement • Better Efficiency over time/ generation to generation • Validate claims 3 3 Copyright © 2010, The Green Grid
  • 4. Impact of IT Power Consumption Computer Room Air Conditioner power Server, network and storage consumption power consumption 23% - 54% 38% - 63% Battery Backup power consumption 6% - 13% Lighting power consumption 1% - 2% Server Power Consumption Impacts Power throughout the Datacenter 4 Copyright © 2010, The Green Grid
  • 5. Data Center Power Efficiency Metrics: PUE and DCiE Total Facility Power PUE = Power Usage Effectiveness = IT Equipment Power Data Center 1 IT Equipment Power DCiE = = = Infrastructure Efficiency PUE Total Facility Power 5 Copyright © 2010, The Green Grid
  • 6. PUE Refined Total Facility Power or Energy PUE = IT Equipment Power or Energy Point of Measurement Frequency of Measurement Duration of Measurement 6 Copyright © 2010, The Green (DCiE) Detailed Analysis (white paper #14) 60 Sources: The Green Grid Metrics: Data Center Infrastructure EfficiencyGrid Usage and Public Reporting Guidelines for The Green Grid's Infrastructure Metrics PUE/DCiE (white paper #22)
  • 7. PUE clarifications • PUEs of < 1.0 and DCiEs of > 1.0 are *not* allowed • These elements are always ≥ 0 – Power consumed by IT equipment – Power lost in distribution – Power consumed by cooling equipment • PUE measures use within the data center, and does not include – Re-use of waste heat – Distributed power generation 7 Copyright © 2010, The Green Grid
  • 8. PUE Nomenclature Official PUE reports provide these information with subscripts appended to the metric PUEx,y or DCiEx,y x = Precision level of measurement (L1, L2, L3) y = Timeframe and collection frequency: D = Daily W = Weekly M = Monthly Y = Yearly C = Continuously 8 Copyright © 2010, The Green Grid
  • 9. Reporting Precision Level 1 Level 2 Level 3 (Basic) (Intermediate) (Advanced) Server, Storage IT Equipment Power UPS PDU device, Router, Measurement From… etc. Data Center input less Data Center Total Facility Power Data Center shared HVAC input less Measurement From… input power plus building shared HVAC lighting, security, etc. Minimum Monthly/ Daily Continuous Measurement Interval Weekly 9 Copyright © 2010, The Green Grid
  • 10. Example Reported Results Single DCiE measurement (0.45) taken using a Level 1 meter 0.45 DCiEL1,-- placement Yearly average DCiE (0.51), using data points gathered monthly 0.51 DCiEL1,YM with a Level 1 meter placement Monthly average PUE (1.6) using data points gathered weekly with 1.6 PUEL1,MW a Level 1 meter placement Weekly average DCiE (0.43), using data points gathered daily with a 0.43DCiEL1,WD Level 1 meter placement Weekly average PUE using data points gathered continuously with 1.8 PUEL2,WC a Level 2 meter placement. Yearly average PUE (2.1) using continuous measurements with a 2.1 PUEL3,YC Level 3 meter placement. 10 Copyright © 2010, The Green Grid
  • 11. Classes of Measurement ResultsClass Description Benefit to Reporting Organization Unrecognized A publicly reported result with no claims of following TGG’s guidelines. TGG will not comment on unrecognized results. Reported A publicly reported result by the Reporting organization can reporting organization claiming they use standard materials from followed TGG’s measurement The Green Grid to explain recommendations and nomenclature process and results to guidelines. TGG will not comment on audience. Reported results. Registered A publicly reported result, with key Official registration of report contextual data provided to TGG reported result. Receipt of a by the reporting organization to TGG’s registration number from TGG. data center performance database. Link to public report data from TGG’s website. Certified A publicly reported result, with key All benefits applicable to additional data required for third-party registered results, plus, validation or certification of results, consideration of reported provided to TGG by the reporting results in future TGG award or organization. recognition programs. 11 Copyright © 2010, The Green Grid
  • 12. Putting Metrics into Global Action • PUE Reporting Tool • PUE Estimator Tool • Power Configuration Efficiency Tool 12 Copyright © 2010, The Green Grid
  • 13. PUE Scalability Metric 13 Copyright © 2010, The Green Grid
  • 14. Partial PUE Definition • PUE = Total Facility Power divided by the IT Equipment Power • This takes into account power use within a facility • Partial PUE is for power use within a boundary • So: pPUE = Total Power within a boundary divided by the IT Equipment Power within that boundary 14 Copyright © 2010, The Green Grid
  • 15. pPUE Example 121 kW Transformer Container 6 kW 115 kW UPS 5 kW 100 kW 95 kW IT Equipment 15 kW Chiller 30 tons Cooling • PUE = 121/95 = 1.27 • pPUE of Container = 100/95 = 1.05 15 Copyright © 2010, The Green Grid 15
  • 16. Energy Reuse Factor rejected Non-DC space H Cool G Absorp Chiller A E I Utility F ICT B UPS C PDU D Data Center A+B A + B- F Boundary PUE = ERF= D D Both PUE & ERF valid metrics 16 Copyright © 2010, The Green Grid
  • 17. TGG Metrics How efficient is my facility in Total Facility Power delivering power to IT PUE = IT Equipment Power equipment? What % of facility power is IT Equipment Power delivered to my IT DCiE = Total Facility Power x 100% equipment? How Much Work Can My IT Useful Work Equipment Do, In My Facility? DCP= Total Facility Power Copyright © 2010, The Green Grid
  • 18. Data Center Energy Productivity • Data Center Energy Productivity (DCeP) • First attempt to define useful work metric • Very comprehensive, very accurate • However, difficult to measure • Some terms require user interpretation – eg., Ui(t,T) is the utility (value) of a transaction – Subjective, could be different for each organization 18 Copyright © 2010, The Green Grid
  • 19. Alternative Proposal - Proxies • Proxies indicate how much work is being done without measuring work directly Should be highly correlated to useful work Should be easier, cheaper, faster to collect • Proxies are often used where complex measures would be impractical eg., EPA Miles Per Gallon, marketing focus group, Dow Jones Industrial Average, or CNN Audience Reaction Meter 19 Copyright © 2010, The Green Grid
  • 20. Proxy Proposals 1. DCeP-based Proxies • Simplified DCeP • Productivity Link • Sample workload 2. Bits per kWH 3. CPU-based proxies • SPECint_rate • SPECpower • CUPS 4. OS images per Watt 20 Copyright © 2010, The Green Grid
  • 21. Proxy Shortcomings In general, the proxy proposals: • Aren’t meant for comparison between data centers Useful for tracking progress within a data center over time No guidelines for use and reporting, so wide variation possible • Don’t address all data center devices equally Proposals tend to be server-centric Storage, networking, telephony, appliances, co-processors, etc • Don’t consider the value of stored data • Don’t account for interaction between devices 21 Copyright © 2010, The Green Grid
  • 22. Where to Next? • Proxies • Currently testing IT Productivity Proxies with the US National Labs • Using instrumented applications as a control • Starting with the Intel Energy Checker SDK as a basis for instrumenting applications within the Data Center Design Guide effort • Sharing results with other organizations globally 22 Copyright © 2010, The Green Grid
  • 23. Metric Harmonization Efforts • Global Metric Harmonization Ministry of Economy, Trade and Industry (METI) Green IT Promotional Council (GIPC) The U.S. Department of Energy (DOE) The U.S. Environmental Protection Agency (EPA) The European Union (EU) The Green Grid (TGG) • US Industry Consensus Session Environmental Protection Agency (EPA) Department of Energy (DOE) 7x24 Exchange American Socienty of Heating, Refrigerating and Air-conditioning Engineers (ASHRAE) Silicon Valley Leadership Group (SVLG) The Green Grid (TGG) Uptime Institute United States Green Building Council (USGBC) 23 Copyright © 2010, The Green Grid
  • 24. Possible New PUE Variations • M&M WG has an approved AR to review and identify if we will proceed with any further possible variations of PUE • PUE Estimated • PUE Calculated • Design PUE • Design Day PUE • Virtual PUE • …. 24 Copyright © 2010, The Green Grid
  • 25. PUE Related Information Material Papers: • Current White 1. Describing Data Center Power Efficiency 2. PUE and DCiE Efficiency Metrics 3. DCiE Detailed Analysis 4. PUE Scalability 5. Usage and Public Reporting Guidelines • Future Possible White Papers: 1. DCiE Detailed Analysis II 2. Partial PUE 3. Energy Re-use Factor & Re-use Energy Ratio 4. Possible new variations of PUE 25 Copyright © 2010, The Green Grid
  • 26. For More Information • www.thegreengrid.org for whitepapers, training, and content • For membership, please contact us: +1 503-619-0653 or admin@lists.thegreengrid.org Thank you to our members for your continued dedication and involvement in ICT energy efficiency efforts! 26 Copyright © 2010, The Green Grid
  • 27. Thank you! For more information please go to www.thegreengrid.org Copyright © 2010, The Green Grid