Electronic Devices

                                                Floatless Relay (Example of Connection)
Electronic Devices



                                                 FLR501 A operation
                     Caution concerning electrode connection
                        ●Check carefully the terminal symbols and electrode lengths before                                     ●Use 0V to 100V terminal in the case of 100V AC power supply.
                         performing electrode circuit connection.                                                              ●Use 0V to 200V terminal in the case of 200V AC power supply.
                         E1 : upper limit, E2 : lower limit,
                         E3 : ground (be sure to ground E3)

                     Automatic water-supply operation
                                                              Power supply                                                             Operation
                                                circuit breaker
                                                Molded case




                                                                                                 Electronic        Power
                                                                                                                    relay
                                                                                                                                       ●The water-supply pump operates when water
                                                                                                   circuit           ×                  surface leaves E2. (The water level is raised)
                                                                                                                                       ●The pump stops when water surface reaches E1.
                                                                                                                                       ●When turning on the power while the water sur-
                                                                                                                                        face is within the control range (between E1 and
                                                                                                                                        E2), the pump will not operate until the water
                                                                                                                                        surface leaves E2.




                                                                                                                            Ground
                       Electromagnetic switch




                                                                                                                            Control
                                                                                                                            range


                                                                                        Water tank




                                                                                             Water supply source




                     Automatic water-discharge operation
                                                              Power supply                                                             Operation
                                                 circuit breaker
                                                 Molded case




                                                                                                 Electronic        Power
                                                                                                                    relay              ●The water-supply pump operates when water
                                                                                                   circuit           ×
                                                                                                                                        surface reaches E1. (The water level is lowered)
                                                                                                                                       ●The pump stops when water surface leaves E2.




                                                                                                                            Ground
                     Electromagnetic switch




                                                                                                                            Control
                                                                                                                             range
                                                                                           Water
                                                                                            tank




         202

  D_10-電子機器.p65                                                              Page 202                                                          06.7.26, 10:20 am   Adobe PageMaker 6.5J/PPC
Electronic Devices

                                   Floatless Relay (Example of Connection)




                                                                                                                                                                                               Electronic Devices
                                    FLR502 A operation
          Caution concerning electrode connection
             ●Check carefully the terminal symbols and electrode lengths before                                              ●Use 0V to 100V terminal in the case of 100V AC power supply.
              performing electrode circuit connection.                                                                       ●Use 0V to 200V terminal in the case of 200V AC power supply.
              E1 : upper limit, E2 : lower limit,
              E3 : ground (be sure to ground E3)
              E4 : abnormal low-water supply alarm, E'1 : recovery, E'2 : lower limit

          Automatic water-supply operation combined with pump idle prevention
                                                                                Electronic      Power                                Operation
                                                                                                 relay
                                                                                  circuit         ×1
                                              Power supply                      Electronic      Power                                Water tank
                                                                                                 relay
                                                                                  circuit                                            ●Water-supply pump operates when water surface
                            circuit breaker




                                                                                                  ×2
                             Molded case




                                                                                                                                      leaves E2. (Water level is raised)
                                                                                                                                     ●The pump stops when water reaches E1.
                                                                                                                                     ●When turning on the power while the water sur-
                                                                                                                                      face is within the control range (between E1 and
                                                                                                                                      E2), the pump will not operate until the water
                                                                                                                                      surface leaves E2.

                                                                                                                                     Water supply source
                                                              Alarm buzzer                                                           ●The pump stops and the alarm sounds when
                                                                                                                                      water surface leaves E'2.
          Electromagnetic switch




                                                                 Ground                                                              ●Normal water-supply operation resumes when
                                                                                                                                      water surface reaches E'1.
                                                                                                         Control                     ●Water-supply operation is performed normally
                                                                                                          range                       when the water surface of the water supply source
                                                                  Water tank
                                                                                                                                      is between E'1 and E'2 while the power is on.




                                                                         Water supply source




          Automatic water-supply operation combined with abnormal low-water supply alarm
                                                                                   Electronic     Power                              Operation
                                                                                                   relay
                                                                                     circuit         ×1
                                               Power supply                        Electronic     Power                              ●Water-supply pump operates when water surface
                                                                                                   relay
                                                                                     circuit                                          leaves E2. (Water level is raised)
                                   circuit breaker
                                    Molded case




                                                                                                     ×2
                                                                                                                                     ●The pump stops when water reaches E1.
                                                                                                                                     ●When turning on the power while the water sur-
                                                                                                                                      face is within the control range (between E1 and
                                                                                                                                      E2), the pump will not operate until the water
                                                                                                                                      surface leaves E2.
                                                                                                                                     ●The pumps stops and the alarm sounds when
                                                                                                                                      the water surface leaves E4 for some reason.


                                                                Alarm buzzer
          Electromagnetic switch




                                                                  Ground


                                                                                                                   Control
                                                                                                                    range

                                                                   Water tank                                        Low-water
                                                                                                                       supply




                                                                          Water supply source




                                                                                                                                                                                              203

D_10-電子機器.p65                                                 Page 203                                                                         06.7.26, 10:20 am   Adobe PageMaker 6.5J/PPC
Electronic Devices

                                               Floatless Relay (Example of Connection)
Electronic Devices



                                                FLR503 A operation
                                      Caution concerning electrode connection
                                              ●Check carefully the terminal symbols and electrode lengths before                                                      ●Use 0V to 100V terminal in the case of 100V AC power supply.
                                               performing electrode circuit connection.                                                                               ●Use 0V to 200V terminal in the case of 200V AC power supply.
                                               E1 : upper limit, E2 : lower limit,
                                               E3 : ground (be sure to ground E3)
                                               E4 : abnormal water increase alarm

                                      Automatic water-discharge operation combined with abnormal water increase alarm
                                                                                                                                    Electronic    Power                        Operation
                                                                                                                                                   relay
                                                                                                                                      circuit         ×1
                                                    Power supply                                                                                  Power                        ●Water-discharge pump operates when water sur-
                                                                                                                                    Electronic     relay
                                                                                                                                      circuit                                   face reaches E1. (Water level is lowered)
                                        circuit breaker




                                                                                                                                                      ×2
                                         Molded case




                                                                                                                                                                               ●The pump stops when water surface leaves E2.
                                                                                                                                                                               ●The pumps stops and the alarm sounds when
                                                                                                                                                                                the water surface reaches E4 for some reason.




                                                                                                     Alarm buzzer
                     Electromagnetic switch




                                                                                                                     Ground                                   Abnormal water
                                                                                                                                                              increase


                                                                                                                                                                    Control
                                                                                                                                                                    range
                                                                                                                          Water tank




                                                FLR505 A operation

                                      LCD and alarm
                                                                                                                               Electronic    Power                             Operation
                                                                                                                                              relay
                                                                                                                                 circuit         ×1
                                              Power supply
                                                                                                                               Electronic    Power                             ●The upper limit lamp lights and the alarm sounds
                                                                                                                                              relay
                                                                                                                                 circuit         ×2                             when the water surface reaches E1.
                     circuit breaker
                      Molded case




                                                                                                                                                                               ●The middle lamp flashes when the water surface
                                                                                                                                                                                is in the middle (between E1 and E2).
                                                                                                                                                                               ●The lower limit lamp lights and the alarm sounds
                                                                                                                                                                                when the water surface leaves E2.
                                                                                        Upper limit lamp


                                                                                                           Lower limit lamp
                                                          Alarm buzzer


                                                                         Middle lamp




                                                                                                                              Ground
                                                                                                                                                           Upper limit
                                                                                                                                                           alarm


                                                                                                                                                           Middle

                                                                                                                              Water tank                     Lower limit
                                                                                                                                                             alarm




         204

  D_10-電子機器.p65                                                                        Page 204                                                                                       06.7.26, 10:20 am   Adobe PageMaker 6.5J/PPC
Electronic Devices

             Floatless Relay (Example of Connection)




                                                                                                                                                                                                                              Electronic Devices
                FLR204 A operation
          Caution concerning electrode connection
           ●Check carefully the terminal symbols and electrode lengths before                                                        ●Use B-C terminals instead of A-C terminals in the case of water-discharge operation.
            performing electrode circuit connection.                                                                                 ●Use 0V to 100V terminal in the case of 100V AC power supply.
            E1 : full tank alarm, E2 : upper limit, E3 : lower limit, E4 : low-water supply alarm                                    ●Use 0V to 200V terminal in the case of 200V AC power supply.
            E5 : Ground (be sure to ground E5 terminal)

          Water-supply/water-discharge operation combined with full-tank/low-water supply alarm

                                                                                                                                     Power
                                                                                                                     Electronic       relay
                                                                                                                       circuit          ×1

                                                                                                                                     Power
                                                                                                                     Electronic       relay
                                                                                                                       circuit          ×2

                                                                                                                     Electronic      Power
                                                                                                                                      relay
                                                                                                                       circuit          ×3



                                                                Power supply
                                              circuit breaker
                                               Molded case




                                                                                   Alarm buzzer



                                                                                                    Full-tank lamp




                                                                                                                       supply lamp
                     Electromagnetic switch




                                                                                                                       Low-water




                                                                                                                                        Ground


                                                                                                                                                                                               Full-tank


                                                                                                                                                                                               Control
                                                                                                                                                                                               range


                                                                                                                                                                                               Low-water
                                                                                                                                         Water tank                                            supply
                                                                                           Water supply source




          Operation

          Water-supply operation
          ●Water-supply pump operates when water surface leaves E3. (Water level is raised)
          ●The pump stops when water surface reaches E2.
          ●When turning on the power while the water surface is between E2 and E3, the pump will not operate until the water
           surface leaves E3.
          ●Full-tank lamp lights and alarm sounds when water surface reaches E1 for some reason.
          ●Low-water supply lamp lights and alarm sounds when water surface leaves E4.

          Water-discharge operation
          ●Discharge pump operates when water surface reaches E2. (Water level is lowered)
          ●The pump stops when water surface leaves E3.
          ●Full-tank lamp lights and alarm sounds when water surface reaches E1 for some reason.
          ●Low-water supply lamp lights and alarm sounds when water surface leaves E4.




                                                                                                                                                                                                                             205

D_10-電子機器.p65                                                           Page 205                                                                             06.7.26, 10:20 am    Adobe PageMaker 6.5J/PPC
Electronic Devices

                       Floatless Relay (Example of Connection)
Electronic Devices



                        FLR206 A operation
                     Caution concerning electrode connection
                     ●Check carefully the terminal symbols and electrode lengths before                                                                                                                                          ●Use 0V to 100V terminal in the case of 100V AC power supply.
                      performing electrode circuit connection.                                                                                                                                                                   ●Use 0V to 200V terminal in the case of 200V AC power supply.
                      Water supply source E1: upper limit alarm, E2: lower limit alarm recovery,
                                          E3: lower limit alarm, E8: ground (be sure to ground E8 terminal)
                      Water tank          E4: full-tank alarm, E5: upper limit, E6: lower limit,
                                          E7: low-water supply alarm, E8: ground (be sure to ground E8 terminal)

                     Automatic water-supply operation with water-level display for water supply source
                     and water tank as well as pump idle prevention

                                                                                                                                                                                                                                 Power
                                                                                                                                                                                  Electronic                                      relay
                                                                                                                                                                                    circuit                                         ×1

                                                                                                                                                                                                                                 Power
                                                                                                                                                                                  Electronic                                      relay
                                                                                                                                                                                    circuit                                         ×2


                                                                                                                                                                                                                                 Power
                                                                                                                                                                                  Electronic                                      relay
                                                                                                                                                                                    circuit                                         ×3

                                                                                                                                                                                                                                 Power
                                                                                                                                                                                  Electronic                                      relay
                                                                                                                                                                                    circuit                                         ×4

                                                                                                                                                                                                                                 Power
                                                                                                                                                                                  Electronic                                      relay
                                                                                                                                                                                    circuit                                         ×5




                                                                       Power supply
                                                         circuit breaker
                                                          Molded case




                                                                                                                                                                                    Water tank low alarm
                                                                                         Water tank low lamp

                                                                                                               Water supply source



                                                                                                                                     Water tank full lamp




                                                                                                                                                                                                           Water supply source
                                                                                                                                                            Water supply source




                                                                                                                                                                                                                                  Water supply source



                                                                                                                                                                                                                                                        Water supply source
                                                                                                                                                                                                            lower limit alarm




                                                                                                                                                                                                                                                         upper limit alarm
                                                                                                                 lower limit lamp




                                                                                                                                                             upper limit lamp




                                                                                                                                                                                                                                       full alarm




                                                                                                                                                                                                                                                                                              Ground
                                Electromagnetic switch




                                                                                                                                                                                                                                                                                           Full-tank


                                                                                                                                                                                                                                                                                            Control
                                                                                                                                                                                                                                                                                            range



                                                                                                                                                                                  Water tank                                                                                              Low-water supply



                                                                                                                                                                                                                                                                                           Upper limit

                                                                                                                                                     Water supply source




                                                                                                                                                                                                                                                                                            Lower limit



         206

  D_10-電子機器.p65                                                               Page 206                                                                                                                                                                                        06.7.26, 10:20 am   Adobe PageMaker 6.5J/PPC
Electronic Devices

            Floatless Relay (Example of Connection)




                                                                                                                                    Electronic Devices
          Operation

          Water supply source
          ●Lower limit lamp lights, alarm sounds and pump stops when water surface leaves E3.
          ●Lower limit lamp and alarm turn off and pump can be prepared for operation when water surface reaches E2.
          ●Upper limit lamp lights and alarm sounds when water surface reaches E1.

          Water tank
          ●Low-water supply lamp lights and alarm sounds when water surface leaves E7.
          ●Low-water supply lamp and alarm turn off when water surface reaches E7.
          ●Water-supply operates when water surface leaves E6. (Water level is raised)
          ●The pump stops when water surface reaches E5.
          ●Full tank lamp turns on and alarm sounds when water surface reaches E4 for some reason.




                                                                                                                                   207

D_10-電子機器.p65                Page 207                                               06.7.26, 10:20 am   Adobe PageMaker 6.5J/PPC
Electronic Devices

                                        Floatless Relay (Example of Connection)
Electronic Devices



                                              51F-G B Operation
                     Caution concerning electrode connection
                     ●Check carefully the terminal symbols and electrode lengths before                                ●Use 0V to 100V terminal in the case of 100V AC power supply.
                      performing electrode circuit connection.                                                         ●Use 0V to 200V terminal in the case of 200V AC power supply.
                      E1 : upper limit, E2 : lower limit,
                      E3 : ground (be sure to ground E3 terminal)

                     Automatic water-supply operation
                                                         Power supply                                                          Operation
                                              circuit breaker
                                              Molded case




                                                                                                          Power
                                                                                            Electronic     relay               ●Water-supply pump operates when water surface
                                                                                              circuit       × 
                                                                                                                                leaves E2. (Water level is raised)
                                                                                                                               ●The pump stops when water reaches E1.
                                                                                                                               ●When turning on the power while the water sur-
                                                                                                                                face is within the control range (between E1 and
                                                                                                                                E2), the pump will continue to operate until wa-
                                                                                                                                ter surface reaches E1.
                     Electromagnetic switch




                                                                                                                   Ground



                                                                                                                   Control
                                                                                                                   range


                                                                                   Water tank




                                                                                        Water supply source




                     Automatic water-supply operation
                                                         Power supply                                                          Operation
                                          circuit breaker
                                          Molded case




                                                                                            Electronic    Power
                                                                                                           relay               ●Water-discharge pump operates when water sur-
                                                                                              circuit       ×
                                                                                                                                face reaches E1. (Water level is lowered)
                                                                                                                               ●The pump stops when water surface leaves E2.
                     Electromagnetic switch




                                                                                                                   Ground



                                                                                                                   Control
                                                                                                                   range


                                                                                   Water tank




         208

  D_10-電子機器.p65                                                         Page 208                                                      06.7.26, 10:20 am   Adobe PageMaker 6.5J/PPC
Electronic Devices

                              Floatless Relay (Example of Connection)




                                                                                                                                                                                                Electronic Devices
                                     51F-G1 B operation
          Caution concerning electrode connection
           ●Check carefully the terminal symbols and electrode lengths before                                               ●Use 0V to 100V terminal in the case of 100V AC power supply.
            performing electrode circuit connection.                                                                        ●Use 0V to 200V terminal in the case of 200V AC power supply.
            E1 : upper limit, E2 : lower limit,
            E3 : ground (be sure to ground E3 terminal)
            E4 : abnormal low-water supply alarm, E'1 : recovery, E2' : lower limit

          Automatic water-supply operation combined with pump idle prevention
                                                                                           Power
                                                                                                                                        Operation
                                                                           Electronic       relay
                                                                             circuit         ×1
                                      Power supply                         Electronic      Power                                        Water tank
                                                                                            relay
                                                                                                                                        ●Water-supply pump operates when water surface
                          circuit breaker




                                                                             circuit         ×2
                          Molded case




                                                                                                                                         leaves E2. (Water level is raised)
                                                                                                                                        ●The pump stops when water surface reaches E1.

                                                                                                                                        Water supply source
                                                                                                                                        ●The pump stops and alarm sounds when water
                                                                                                                                         surface leaves E'2.
                                                                                                                                        ●Normal water-supply operation resumes when
                                                                                                                                         water surface reaches E'1.
                                                     Alarm buzzer                                                                       ●Press the push-button to start pump in the case
          Electromagnetic switch




                                                                                                                                         water surface of water supply source does not
                                                                                                                          Push button    reach E'1 during start or after recovering from
                                                       Ground
                                                                                                                            switch       power failure.
                                                                                                    Control range




                                                                                                                                        ●Do not press the push-button in the case low-
                                                                                                                                         water supply alarm sounds and the pump stops
                                                                                                                                         during normal operation.
                                                         Water tank




                                                                  Water supply source




          Automatic water-supply operation combined with abnormal low-water supply alarm
                                                                                        Power
                                                                                                                                        Operation
                                                                        Electronic
                                                                                         relay
                                                                          circuit         ×1

                                      Power supply                      Electronic      Power                                           ●Water-supply pump operates when water surface
                                                                                         relay
                                                                          circuit         ×2                                             leaves E2. (Water level is raised)
                        circuit breaker
                        Molded case




                                                                                                                                        ●The pump stops when water surface reaches E1.
                                                                                                                                        ●The pump stops and alarm sounds when water
                                                                                                                                         surface leaves E4 for some reason.
                                                                                                                                        ●Press the push-button to start pump in the case
                                                                                                                                         water surface of water supply source does not
                                                                                                                                         reach E4 during start or after recovering from
                                                                                                                                         power failure.
                                                                                                                                        ●To stop the pump by releasing the push-button
                                                     Alarm buzzer                                                                        switch, press and hold the push-button switch
                                                                                                                                         until water surface reaches E4.
            Electromagnetic switch




                                                                                                                    Push button
                                                      Ground                                                          switch

                                                                                                    Control
                                                                                                    range
                                                                                                       Low-water supply
                                                        Water tank




                                                                Water supply source




                                                                                                                                                                                               209

D_10-電子機器.p65                                        Page 209                                                                                   06.7.26, 10:20 am   Adobe PageMaker 6.5J/PPC
Electronic Devices

                                         Floatless Relay (Example of Connection)
Electronic Devices



                                              51F-G2 B operation
                     Caution concerning electrode connection
                      ●Check carefully the terminal symbols and electrode lengths before                                                                                     ●Use 0V to 100V terminal in the case of 100V AC power supply.
                       performing electrode circuit connection.                                                                                                              ●Use 0V to 200V terminal in the case of 200V AC power supply.
                       E1 : upper limit, E2 : lower limit,
                       E3 : ground (be sure to ground E3 terminal)
                       E4 : abnormal water increase alarm

                     Automatic water-discharge operation combined with abnormal water increase alarm
                                                                                                                                          Electronic       Power                      Operation
                                                                                                                                                            relay
                                                                                                                                            circuit          ×1
                                               Power supply                                                                               Electronic       Power                      ●Water-discharge pump operates when water sur-
                                                                                                                                                            relay
                                   circuit breaker




                                                                                                                                            circuit          ×2                        face reaches E1. (Water level is lowered)
                                   Molded case




                                                                                                                                                                                      ●The pump stocks when water surface leaves E2.
                                                                                                                                                                                      ●Alarm sounds when water surface reaches E4
                                                                                                                                                                                       for some reason.




                                                                                                                            Alarm buzzer
                     Electromagnetic switch




                                                                                                          Ground                                                     Abnormal
                                                                                                                                                                     water increase


                                                                                                                                                                          Control
                                                                                                                                                                           range
                                                                                                                        Water tank




                                              51F-I B operation

                     LCD and alarm
                                                                                                                               Electronic              Power                          Operation
                                                                                                                                                        relay
                                                                                                                                 circuit                 ×1

                                         Power supply                                                                          Electronic              Power                          ●Upper limit lamp lights and alarm sounds when
                                                                                                                                                        relay
                                                                                                                                 circuit                 ×2                            water surface reaches E1.
                      circuit breaker
                      Molded case




                                                                                                                                                                                      ●Middle lamp lights when water surface is in the
                                                                                                                                                                                       middle (between E1 and E2).
                                                                                                                                                                                      ●Lower limit lamp lights and alarm sounds when
                                                                                                                                                                                       water surface leaves E2.
                                                                                      Upper limit lamp


                                                                                                         Lower limit lamp
                                                     Alarm buzzer




                                                                                                                                 Ground
                                                                    Middle lamp




                                                                                                                                                                    Upper limit
                                                                                                                                                                    alarm

                                                                                                                                                                    Middle

                                                                                                                            Water tank
                                                                                                                                                                      Lower limit
                                                                                                                                                                      alarm




         210

  D_10-電子機器.p65                                                                   Page 210                                                                                                   06.7.26, 10:20 am   Adobe PageMaker 6.5J/PPC
Electronic Devices

                             Floatless Relay (Example of Connection)




                                                                                                                                                                                            Electronic Devices
                                   FLRP301 (Compact Plug-In) A operation

          Automatic standard water-supply or water-discharge operation
                                     Power supply                                                                  Operation
                         circuit breaker
                         Molded case




                                                                                                                   Water-supply operation
                                                                                                                   ●Water-supply pump operates when water surface
                                                                      Control
                                                                      circuit                                       leaves E2. (Water level is raised)
                                                                                                                   ●The pump stops when water surface reaches E1.
                                                                                                                   ●When turning on the power while the water sur-
                                                                                                                    face is between E1 and E2, the pump will not
                                                                  Water     Water                                   operate until the water surface leaves E2.
                                                                  discharge supply
          Electromagnetic switch




                                                                                                          Ground   Water-discharge operation
                                                                                                                   ●Water-discharge pump operates when water sur-
                                                                                                                    face reaches E1. (Water level is lowered)
                                                                                                         Control
                                                                                                                   ●The pump stops when water surface leaves E2.
                                                                                                          range
                                                                                                                   Operation display                  Water-discharge opera-
                                                                   Water tank                                                                         tion
                                                                                                                   Water-supply operation
                                                                                                                     LED     Pump       Tank            LED       Pump        Tank
                                                                                                                                      Supplying        Yellow     OFF        Normal
                                                                          Water supply                              Yellow     ON
                                                                                                                                       water                                 Discharging
                                                                          source                                                                        Red        ON
                                                                                                                     Red      OFF      Normal                                   water



              ※ For water-discharge operation, connect wire connected to
                                    terminal 1 to terminal 11.


          Automatic water-supply operation combined with pump idle prevention
                                                                                                                   Operation

                                     Power supply                                                                  Water tank
                        circuit breaker




                                                                                                                   ●Water-supply pump operates when water surface
                        Molded case




                                                                                                                    leaves E2. (Water level is raised)
                                                                     Control                   Control
                                                                     circuit                   circuit             ●The pump stops when water surface reaches E1.
                                                                                                                   ●When turning on the power while the water sur-
                                                                                                                    face is within the control range (between E1 and
                                                                                                                    E2), the pump will not operate until the water
                                                                                                                    surface leaves E2.
                                                                                         Alarm buzzer
                                                                                                                   Water supply source
           Electromagnetic switch




                                                                                                                   ●The pump stops and alarm sounds when water
                                                                 Ground
                                                                                                                    surface leaves E'2.
                                                                                                                   ●Normal water-supply operation resumes when
                                                                                                         Control    water surface reaches E'1.
                                                                                                         range
                                                                                                                   Operation display
                                                                  Water tank
                                                                                                                                                              Water
                                                                                                                    P1LED    P2LED      Pump        Tank      supply      Alarm buzzer
                                                                                                                                                              source
                                                                                                                    Yellow   Yellow      OFF      Decrease Insufficient       ON
                                                                          Water supply source                       Yellow    Red        OFF      Normal Insufficient         ON
                                                                                                                                                   Supplying
                                                                                                                     Red     Yellow      ON        water     Normal          OFF

                                                                                                                     Red       Red       OFF       Normal Normal             OFF




                                                                                                                                                                                           211

D_10-電子機器.p65                                              Page 211                                                          06.7.26, 10:20 am    Adobe PageMaker 6.5J/PPC
Electronic Devices

                                      Floatless Relay (Example of Connection)
Electronic Devices



                                         51F-GPN (Compact Plug-In) B operation

                     Automatic standard water-supply or water-discharge operation
                                                Power supply                                                            Operation
                                 circuit breaker
                                 Molded case




                                                                                                                        Water-supply operation
                                                                                                                        ●Water-supply pump operates when water surface leaves
                                                                                 Control
                                                                                 circuit                                 E2. (Water level is raised)
                                                                                                                        ●The pump stops when water surface reaches E1.
                                                                                                                        ●The pump operates when the power is turned on while
                                                                                                                         water surface is within the control range (between E1
                                                                           Water     Water                               and E2). The pump will not stop until water surface
                                                                           discharge supply                              reaches E1.
                     Electromagnetic switch




                                                                                                              Ground
                                                                                                                        Water-discharge operation
                                                                                                                        ●Water-discharge pump operates when water surface
                                                                                                              Control
                                                                                                                         reaches E1. (Water level is lowered)
                                                                                                              range     ●The pump stops when water surface leaves E2.

                                                                               Water tank                               Operation display
                                                                                                                        Water-supply operation                Water-discharge operation
                                                                                                                          LED     Pump        Tank              LED        Pump     Tank
                                                                                       Water supply source                                  Supplying          Yellow      OFF     Normal
                                                                                                                         Yellow     ON       water
                                                                                                                                                                                   Discharging
                                                                                                                          Red       OFF      Normal             Red           ON      water


                       ※ For water-discharge operation, connect wire connected to
                                              terminal 1 to terminal 11.


                                                           (long)     (short)              (middle)                                   (long)      (short)            (middle)


                                                                                                     Bottom
                                                                                                                                                                              Bottom
                                                                                       Red           view                                                        Red
                                                                                                                                                                              view
                                                                                            Yellow                                                                   Yellow

                                                                                   Electronic                                                                 Electronic
                                                                                   circuit                                                                    circuit




                                                                        Yellow                                                                     Yellow
                                                                                   Red                                                                        Red
                                                                     Water                    Water                                            Water                  Water
                                                                     supply                   discharge                                        supply                 discharge



                                                      FLRP301 internal connection diagram                                         51F-GPN internal connection diagram




         212

  D_10-電子機器.p65                                                     Page 212                                                              06.7.26, 10:20 am     Adobe PageMaker 6.5J/PPC

More Related Content

What's hot

Generator protection
Generator protectionGenerator protection
Generator protection
Keshar Rawal
 
Technical slides tia_portal_v15_en
Technical slides tia_portal_v15_enTechnical slides tia_portal_v15_en
Technical slides tia_portal_v15_en
Deepak kumar
 
Ladder logic tutorial
Ladder logic tutorialLadder logic tutorial
Ladder logic tutorial
das1964
 

What's hot (20)

Generator protection
Generator protectionGenerator protection
Generator protection
 
ABB Life Expectancy Analysis Program Diagnostics
ABB Life Expectancy Analysis Program DiagnosticsABB Life Expectancy Analysis Program Diagnostics
ABB Life Expectancy Analysis Program Diagnostics
 
An inside view of thermal power stations and DDCMIS in power plants
An inside view of thermal power stations and DDCMIS in power plantsAn inside view of thermal power stations and DDCMIS in power plants
An inside view of thermal power stations and DDCMIS in power plants
 
AUTOMATIC TURBINE RUNUP SYSTEM
AUTOMATIC TURBINE RUNUP SYSTEMAUTOMATIC TURBINE RUNUP SYSTEM
AUTOMATIC TURBINE RUNUP SYSTEM
 
Motor.ppt
Motor.pptMotor.ppt
Motor.ppt
 
Steam Turbine Alignment
Steam Turbine AlignmentSteam Turbine Alignment
Steam Turbine Alignment
 
Different types of Transformers used in Generating Station
Different types of Transformers used in Generating StationDifferent types of Transformers used in Generating Station
Different types of Transformers used in Generating Station
 
Technical slides tia_portal_v15_en
Technical slides tia_portal_v15_enTechnical slides tia_portal_v15_en
Technical slides tia_portal_v15_en
 
Assembly and Disassembly Procedure of Screw type Compressor
Assembly and Disassembly Procedure of Screw type Compressor Assembly and Disassembly Procedure of Screw type Compressor
Assembly and Disassembly Procedure of Screw type Compressor
 
Electrical drives
Electrical drivesElectrical drives
Electrical drives
 
Plc (programming)
Plc (programming)Plc (programming)
Plc (programming)
 
PPT of PLC and SCADA
PPT of PLC and SCADAPPT of PLC and SCADA
PPT of PLC and SCADA
 
Vacuum Circuit Breaker (VCB) Working and Applications | Uses Of VCB
Vacuum Circuit Breaker (VCB) Working and Applications | Uses Of VCB Vacuum Circuit Breaker (VCB) Working and Applications | Uses Of VCB
Vacuum Circuit Breaker (VCB) Working and Applications | Uses Of VCB
 
Dol and star delta
Dol and star deltaDol and star delta
Dol and star delta
 
X12 constellation
X12 constellationX12 constellation
X12 constellation
 
Linear Induction Motor
Linear Induction MotorLinear Induction Motor
Linear Induction Motor
 
Thermal Power Plant Simulator Operations Training
Thermal Power Plant Simulator Operations TrainingThermal Power Plant Simulator Operations Training
Thermal Power Plant Simulator Operations Training
 
Turbine governing system an overview
Turbine governing system an overviewTurbine governing system an overview
Turbine governing system an overview
 
Alimentação da injeção eletrônica e seus defeitos
Alimentação da injeção eletrônica e seus defeitosAlimentação da injeção eletrônica e seus defeitos
Alimentação da injeção eletrônica e seus defeitos
 
Ladder logic tutorial
Ladder logic tutorialLadder logic tutorial
Ladder logic tutorial
 

Viewers also liked

Presentation plumbing
Presentation plumbingPresentation plumbing
Presentation plumbing
Liguidliguid
 

Viewers also liked (8)

61 f floatless level controller datasheet
61 f floatless level controller datasheet61 f floatless level controller datasheet
61 f floatless level controller datasheet
 
Solar for the home installation and maintenance-20161
Solar for the home installation and maintenance-20161Solar for the home installation and maintenance-20161
Solar for the home installation and maintenance-20161
 
Electrical installation guide 2013
Electrical installation guide 2013 Electrical installation guide 2013
Electrical installation guide 2013
 
Presentation on Over-/under-voltage protection of electrical appliance
Presentation on Over-/under-voltage protection of electrical appliancePresentation on Over-/under-voltage protection of electrical appliance
Presentation on Over-/under-voltage protection of electrical appliance
 
plumbing
plumbingplumbing
plumbing
 
Fire Pump Motor Starting
Fire Pump Motor StartingFire Pump Motor Starting
Fire Pump Motor Starting
 
Presentation plumbing
Presentation plumbingPresentation plumbing
Presentation plumbing
 
OVER VOLTAGE UNDER VOLTAGE TRIPPING MECHANISM
OVER VOLTAGE UNDER VOLTAGE TRIPPING MECHANISMOVER VOLTAGE UNDER VOLTAGE TRIPPING MECHANISM
OVER VOLTAGE UNDER VOLTAGE TRIPPING MECHANISM
 

More from Eko Kiswanto

Ulsab final report
Ulsab final reportUlsab final report
Ulsab final report
Eko Kiswanto
 
Ulsab engineer report complete
Ulsab engineer report completeUlsab engineer report complete
Ulsab engineer report complete
Eko Kiswanto
 
Faw whizol cp preview s
Faw whizol cp preview sFaw whizol cp preview s
Faw whizol cp preview s
Eko Kiswanto
 
Fa whizol poster_a2
Fa whizol poster_a2Fa whizol poster_a2
Fa whizol poster_a2
Eko Kiswanto
 
Whizol flyer quick
Whizol flyer quickWhizol flyer quick
Whizol flyer quick
Eko Kiswanto
 
Whizol product cat 03 14
Whizol product cat 03 14Whizol product cat 03 14
Whizol product cat 03 14
Eko Kiswanto
 
7 langkah selamat dari gempa bumi di rumah
7 langkah selamat dari gempa bumi di rumah7 langkah selamat dari gempa bumi di rumah
7 langkah selamat dari gempa bumi di rumah
Eko Kiswanto
 

More from Eko Kiswanto (20)

Af3 instruction manual-cm specialist
Af3 instruction manual-cm specialistAf3 instruction manual-cm specialist
Af3 instruction manual-cm specialist
 
Mesin Diesel Toyota tipe 2 KD FTV 14
Mesin Diesel Toyota tipe  2 KD FTV 14Mesin Diesel Toyota tipe  2 KD FTV 14
Mesin Diesel Toyota tipe 2 KD FTV 14
 
Kijang Innova-bensin-vvt-i 1 TR FE
Kijang Innova-bensin-vvt-i 1 TR FEKijang Innova-bensin-vvt-i 1 TR FE
Kijang Innova-bensin-vvt-i 1 TR FE
 
Pengukuran listrik
Pengukuran listrikPengukuran listrik
Pengukuran listrik
 
Teknisi k3 listrik
Teknisi k3 listrik Teknisi k3 listrik
Teknisi k3 listrik
 
Material science & eng 2014
Material science  & eng 2014Material science  & eng 2014
Material science & eng 2014
 
Agya ayla part number catalog
Agya ayla part number catalogAgya ayla part number catalog
Agya ayla part number catalog
 
Avanza xenia part number catalog
Avanza xenia part number catalogAvanza xenia part number catalog
Avanza xenia part number catalog
 
Rush terios part number catalog
Rush terios part number catalogRush terios part number catalog
Rush terios part number catalog
 
Material science & eng 2011
Material science  & eng 2011Material science  & eng 2011
Material science & eng 2011
 
Material science & eng 2012
Material science  & eng 2012Material science  & eng 2012
Material science & eng 2012
 
Ulsab final report
Ulsab final reportUlsab final report
Ulsab final report
 
Ulsab engineer report complete
Ulsab engineer report completeUlsab engineer report complete
Ulsab engineer report complete
 
Wika pressure & temperature handbook
Wika pressure & temperature handbookWika pressure & temperature handbook
Wika pressure & temperature handbook
 
Faw whizol cp preview s
Faw whizol cp preview sFaw whizol cp preview s
Faw whizol cp preview s
 
Fa whizol poster_a2
Fa whizol poster_a2Fa whizol poster_a2
Fa whizol poster_a2
 
Whizol flyer quick
Whizol flyer quickWhizol flyer quick
Whizol flyer quick
 
Whizol product cat 03 14
Whizol product cat 03 14Whizol product cat 03 14
Whizol product cat 03 14
 
Geomagz201409
Geomagz201409Geomagz201409
Geomagz201409
 
7 langkah selamat dari gempa bumi di rumah
7 langkah selamat dari gempa bumi di rumah7 langkah selamat dari gempa bumi di rumah
7 langkah selamat dari gempa bumi di rumah
 

Recently uploaded

Artificial Intelligence: Facts and Myths
Artificial Intelligence: Facts and MythsArtificial Intelligence: Facts and Myths
Artificial Intelligence: Facts and Myths
Joaquim Jorge
 
CNv6 Instructor Chapter 6 Quality of Service
CNv6 Instructor Chapter 6 Quality of ServiceCNv6 Instructor Chapter 6 Quality of Service
CNv6 Instructor Chapter 6 Quality of Service
giselly40
 

Recently uploaded (20)

Artificial Intelligence: Facts and Myths
Artificial Intelligence: Facts and MythsArtificial Intelligence: Facts and Myths
Artificial Intelligence: Facts and Myths
 
Workshop - Best of Both Worlds_ Combine KG and Vector search for enhanced R...
Workshop - Best of Both Worlds_ Combine  KG and Vector search for  enhanced R...Workshop - Best of Both Worlds_ Combine  KG and Vector search for  enhanced R...
Workshop - Best of Both Worlds_ Combine KG and Vector search for enhanced R...
 
04-2024-HHUG-Sales-and-Marketing-Alignment.pptx
04-2024-HHUG-Sales-and-Marketing-Alignment.pptx04-2024-HHUG-Sales-and-Marketing-Alignment.pptx
04-2024-HHUG-Sales-and-Marketing-Alignment.pptx
 
GenCyber Cyber Security Day Presentation
GenCyber Cyber Security Day PresentationGenCyber Cyber Security Day Presentation
GenCyber Cyber Security Day Presentation
 
Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024
Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024
Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024
 
Boost PC performance: How more available memory can improve productivity
Boost PC performance: How more available memory can improve productivityBoost PC performance: How more available memory can improve productivity
Boost PC performance: How more available memory can improve productivity
 
2024: Domino Containers - The Next Step. News from the Domino Container commu...
2024: Domino Containers - The Next Step. News from the Domino Container commu...2024: Domino Containers - The Next Step. News from the Domino Container commu...
2024: Domino Containers - The Next Step. News from the Domino Container commu...
 
The 7 Things I Know About Cyber Security After 25 Years | April 2024
The 7 Things I Know About Cyber Security After 25 Years | April 2024The 7 Things I Know About Cyber Security After 25 Years | April 2024
The 7 Things I Know About Cyber Security After 25 Years | April 2024
 
From Event to Action: Accelerate Your Decision Making with Real-Time Automation
From Event to Action: Accelerate Your Decision Making with Real-Time AutomationFrom Event to Action: Accelerate Your Decision Making with Real-Time Automation
From Event to Action: Accelerate Your Decision Making with Real-Time Automation
 
CNv6 Instructor Chapter 6 Quality of Service
CNv6 Instructor Chapter 6 Quality of ServiceCNv6 Instructor Chapter 6 Quality of Service
CNv6 Instructor Chapter 6 Quality of Service
 
Tata AIG General Insurance Company - Insurer Innovation Award 2024
Tata AIG General Insurance Company - Insurer Innovation Award 2024Tata AIG General Insurance Company - Insurer Innovation Award 2024
Tata AIG General Insurance Company - Insurer Innovation Award 2024
 
08448380779 Call Girls In Friends Colony Women Seeking Men
08448380779 Call Girls In Friends Colony Women Seeking Men08448380779 Call Girls In Friends Colony Women Seeking Men
08448380779 Call Girls In Friends Colony Women Seeking Men
 
Factors to Consider When Choosing Accounts Payable Services Providers.pptx
Factors to Consider When Choosing Accounts Payable Services Providers.pptxFactors to Consider When Choosing Accounts Payable Services Providers.pptx
Factors to Consider When Choosing Accounts Payable Services Providers.pptx
 
[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdf[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdf
 
Scaling API-first – The story of a global engineering organization
Scaling API-first – The story of a global engineering organizationScaling API-first – The story of a global engineering organization
Scaling API-first – The story of a global engineering organization
 
Breaking the Kubernetes Kill Chain: Host Path Mount
Breaking the Kubernetes Kill Chain: Host Path MountBreaking the Kubernetes Kill Chain: Host Path Mount
Breaking the Kubernetes Kill Chain: Host Path Mount
 
Advantages of Hiring UIUX Design Service Providers for Your Business
Advantages of Hiring UIUX Design Service Providers for Your BusinessAdvantages of Hiring UIUX Design Service Providers for Your Business
Advantages of Hiring UIUX Design Service Providers for Your Business
 
A Call to Action for Generative AI in 2024
A Call to Action for Generative AI in 2024A Call to Action for Generative AI in 2024
A Call to Action for Generative AI in 2024
 
Exploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone ProcessorsExploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone Processors
 
08448380779 Call Girls In Civil Lines Women Seeking Men
08448380779 Call Girls In Civil Lines Women Seeking Men08448380779 Call Girls In Civil Lines Women Seeking Men
08448380779 Call Girls In Civil Lines Women Seeking Men
 

Kasuga flr floatless relay

  • 1. Electronic Devices Floatless Relay (Example of Connection) Electronic Devices FLR501 A operation Caution concerning electrode connection ●Check carefully the terminal symbols and electrode lengths before ●Use 0V to 100V terminal in the case of 100V AC power supply. performing electrode circuit connection. ●Use 0V to 200V terminal in the case of 200V AC power supply. E1 : upper limit, E2 : lower limit, E3 : ground (be sure to ground E3) Automatic water-supply operation Power supply Operation circuit breaker Molded case Electronic Power relay ●The water-supply pump operates when water circuit × surface leaves E2. (The water level is raised) ●The pump stops when water surface reaches E1. ●When turning on the power while the water sur- face is within the control range (between E1 and E2), the pump will not operate until the water surface leaves E2. Ground Electromagnetic switch Control range Water tank Water supply source Automatic water-discharge operation Power supply Operation circuit breaker Molded case Electronic Power relay ●The water-supply pump operates when water circuit × surface reaches E1. (The water level is lowered) ●The pump stops when water surface leaves E2. Ground Electromagnetic switch Control range Water tank 202 D_10-電子機器.p65 Page 202 06.7.26, 10:20 am Adobe PageMaker 6.5J/PPC
  • 2. Electronic Devices Floatless Relay (Example of Connection) Electronic Devices FLR502 A operation Caution concerning electrode connection ●Check carefully the terminal symbols and electrode lengths before ●Use 0V to 100V terminal in the case of 100V AC power supply. performing electrode circuit connection. ●Use 0V to 200V terminal in the case of 200V AC power supply. E1 : upper limit, E2 : lower limit, E3 : ground (be sure to ground E3) E4 : abnormal low-water supply alarm, E'1 : recovery, E'2 : lower limit Automatic water-supply operation combined with pump idle prevention Electronic Power Operation relay circuit ×1 Power supply Electronic Power Water tank relay circuit ●Water-supply pump operates when water surface circuit breaker ×2 Molded case leaves E2. (Water level is raised) ●The pump stops when water reaches E1. ●When turning on the power while the water sur- face is within the control range (between E1 and E2), the pump will not operate until the water surface leaves E2. Water supply source Alarm buzzer ●The pump stops and the alarm sounds when water surface leaves E'2. Electromagnetic switch Ground ●Normal water-supply operation resumes when water surface reaches E'1. Control ●Water-supply operation is performed normally range when the water surface of the water supply source Water tank is between E'1 and E'2 while the power is on. Water supply source Automatic water-supply operation combined with abnormal low-water supply alarm Electronic Power Operation relay circuit ×1 Power supply Electronic Power ●Water-supply pump operates when water surface relay circuit leaves E2. (Water level is raised) circuit breaker Molded case ×2 ●The pump stops when water reaches E1. ●When turning on the power while the water sur- face is within the control range (between E1 and E2), the pump will not operate until the water surface leaves E2. ●The pumps stops and the alarm sounds when the water surface leaves E4 for some reason. Alarm buzzer Electromagnetic switch Ground Control range Water tank Low-water supply Water supply source 203 D_10-電子機器.p65 Page 203 06.7.26, 10:20 am Adobe PageMaker 6.5J/PPC
  • 3. Electronic Devices Floatless Relay (Example of Connection) Electronic Devices FLR503 A operation Caution concerning electrode connection ●Check carefully the terminal symbols and electrode lengths before ●Use 0V to 100V terminal in the case of 100V AC power supply. performing electrode circuit connection. ●Use 0V to 200V terminal in the case of 200V AC power supply. E1 : upper limit, E2 : lower limit, E3 : ground (be sure to ground E3) E4 : abnormal water increase alarm Automatic water-discharge operation combined with abnormal water increase alarm Electronic Power Operation relay circuit ×1 Power supply Power ●Water-discharge pump operates when water sur- Electronic relay circuit face reaches E1. (Water level is lowered) circuit breaker ×2 Molded case ●The pump stops when water surface leaves E2. ●The pumps stops and the alarm sounds when the water surface reaches E4 for some reason. Alarm buzzer Electromagnetic switch Ground Abnormal water increase Control range Water tank FLR505 A operation LCD and alarm Electronic Power Operation relay circuit ×1 Power supply Electronic Power ●The upper limit lamp lights and the alarm sounds relay circuit ×2 when the water surface reaches E1. circuit breaker Molded case ●The middle lamp flashes when the water surface is in the middle (between E1 and E2). ●The lower limit lamp lights and the alarm sounds when the water surface leaves E2. Upper limit lamp Lower limit lamp Alarm buzzer Middle lamp Ground Upper limit alarm Middle Water tank Lower limit alarm 204 D_10-電子機器.p65 Page 204 06.7.26, 10:20 am Adobe PageMaker 6.5J/PPC
  • 4. Electronic Devices Floatless Relay (Example of Connection) Electronic Devices FLR204 A operation Caution concerning electrode connection ●Check carefully the terminal symbols and electrode lengths before ●Use B-C terminals instead of A-C terminals in the case of water-discharge operation. performing electrode circuit connection. ●Use 0V to 100V terminal in the case of 100V AC power supply. E1 : full tank alarm, E2 : upper limit, E3 : lower limit, E4 : low-water supply alarm ●Use 0V to 200V terminal in the case of 200V AC power supply. E5 : Ground (be sure to ground E5 terminal) Water-supply/water-discharge operation combined with full-tank/low-water supply alarm Power Electronic relay circuit ×1 Power Electronic relay circuit ×2 Electronic Power relay circuit ×3 Power supply circuit breaker Molded case Alarm buzzer Full-tank lamp supply lamp Electromagnetic switch Low-water Ground Full-tank Control range Low-water Water tank supply Water supply source Operation Water-supply operation ●Water-supply pump operates when water surface leaves E3. (Water level is raised) ●The pump stops when water surface reaches E2. ●When turning on the power while the water surface is between E2 and E3, the pump will not operate until the water surface leaves E3. ●Full-tank lamp lights and alarm sounds when water surface reaches E1 for some reason. ●Low-water supply lamp lights and alarm sounds when water surface leaves E4. Water-discharge operation ●Discharge pump operates when water surface reaches E2. (Water level is lowered) ●The pump stops when water surface leaves E3. ●Full-tank lamp lights and alarm sounds when water surface reaches E1 for some reason. ●Low-water supply lamp lights and alarm sounds when water surface leaves E4. 205 D_10-電子機器.p65 Page 205 06.7.26, 10:20 am Adobe PageMaker 6.5J/PPC
  • 5. Electronic Devices Floatless Relay (Example of Connection) Electronic Devices FLR206 A operation Caution concerning electrode connection ●Check carefully the terminal symbols and electrode lengths before ●Use 0V to 100V terminal in the case of 100V AC power supply. performing electrode circuit connection. ●Use 0V to 200V terminal in the case of 200V AC power supply. Water supply source E1: upper limit alarm, E2: lower limit alarm recovery, E3: lower limit alarm, E8: ground (be sure to ground E8 terminal) Water tank E4: full-tank alarm, E5: upper limit, E6: lower limit, E7: low-water supply alarm, E8: ground (be sure to ground E8 terminal) Automatic water-supply operation with water-level display for water supply source and water tank as well as pump idle prevention Power Electronic relay circuit ×1 Power Electronic relay circuit ×2 Power Electronic relay circuit ×3 Power Electronic relay circuit ×4 Power Electronic relay circuit ×5 Power supply circuit breaker Molded case Water tank low alarm Water tank low lamp Water supply source Water tank full lamp Water supply source Water supply source Water supply source Water supply source lower limit alarm upper limit alarm lower limit lamp upper limit lamp full alarm Ground Electromagnetic switch Full-tank Control range Water tank Low-water supply Upper limit Water supply source Lower limit 206 D_10-電子機器.p65 Page 206 06.7.26, 10:20 am Adobe PageMaker 6.5J/PPC
  • 6. Electronic Devices Floatless Relay (Example of Connection) Electronic Devices Operation Water supply source ●Lower limit lamp lights, alarm sounds and pump stops when water surface leaves E3. ●Lower limit lamp and alarm turn off and pump can be prepared for operation when water surface reaches E2. ●Upper limit lamp lights and alarm sounds when water surface reaches E1. Water tank ●Low-water supply lamp lights and alarm sounds when water surface leaves E7. ●Low-water supply lamp and alarm turn off when water surface reaches E7. ●Water-supply operates when water surface leaves E6. (Water level is raised) ●The pump stops when water surface reaches E5. ●Full tank lamp turns on and alarm sounds when water surface reaches E4 for some reason. 207 D_10-電子機器.p65 Page 207 06.7.26, 10:20 am Adobe PageMaker 6.5J/PPC
  • 7. Electronic Devices Floatless Relay (Example of Connection) Electronic Devices 51F-G B Operation Caution concerning electrode connection ●Check carefully the terminal symbols and electrode lengths before ●Use 0V to 100V terminal in the case of 100V AC power supply. performing electrode circuit connection. ●Use 0V to 200V terminal in the case of 200V AC power supply. E1 : upper limit, E2 : lower limit, E3 : ground (be sure to ground E3 terminal) Automatic water-supply operation Power supply Operation circuit breaker Molded case Power Electronic relay ●Water-supply pump operates when water surface circuit ×  leaves E2. (Water level is raised) ●The pump stops when water reaches E1. ●When turning on the power while the water sur- face is within the control range (between E1 and E2), the pump will continue to operate until wa- ter surface reaches E1. Electromagnetic switch Ground Control range Water tank Water supply source Automatic water-supply operation Power supply Operation circuit breaker Molded case Electronic Power relay ●Water-discharge pump operates when water sur- circuit × face reaches E1. (Water level is lowered) ●The pump stops when water surface leaves E2. Electromagnetic switch Ground Control range Water tank 208 D_10-電子機器.p65 Page 208 06.7.26, 10:20 am Adobe PageMaker 6.5J/PPC
  • 8. Electronic Devices Floatless Relay (Example of Connection) Electronic Devices 51F-G1 B operation Caution concerning electrode connection ●Check carefully the terminal symbols and electrode lengths before ●Use 0V to 100V terminal in the case of 100V AC power supply. performing electrode circuit connection. ●Use 0V to 200V terminal in the case of 200V AC power supply. E1 : upper limit, E2 : lower limit, E3 : ground (be sure to ground E3 terminal) E4 : abnormal low-water supply alarm, E'1 : recovery, E2' : lower limit Automatic water-supply operation combined with pump idle prevention Power Operation Electronic relay circuit ×1 Power supply Electronic Power Water tank relay ●Water-supply pump operates when water surface circuit breaker circuit ×2 Molded case leaves E2. (Water level is raised) ●The pump stops when water surface reaches E1. Water supply source ●The pump stops and alarm sounds when water surface leaves E'2. ●Normal water-supply operation resumes when water surface reaches E'1. Alarm buzzer ●Press the push-button to start pump in the case Electromagnetic switch water surface of water supply source does not Push button reach E'1 during start or after recovering from Ground switch power failure. Control range ●Do not press the push-button in the case low- water supply alarm sounds and the pump stops during normal operation. Water tank Water supply source Automatic water-supply operation combined with abnormal low-water supply alarm Power Operation Electronic relay circuit ×1 Power supply Electronic Power ●Water-supply pump operates when water surface relay circuit ×2 leaves E2. (Water level is raised) circuit breaker Molded case ●The pump stops when water surface reaches E1. ●The pump stops and alarm sounds when water surface leaves E4 for some reason. ●Press the push-button to start pump in the case water surface of water supply source does not reach E4 during start or after recovering from power failure. ●To stop the pump by releasing the push-button Alarm buzzer switch, press and hold the push-button switch until water surface reaches E4. Electromagnetic switch Push button Ground switch Control range Low-water supply Water tank Water supply source 209 D_10-電子機器.p65 Page 209 06.7.26, 10:20 am Adobe PageMaker 6.5J/PPC
  • 9. Electronic Devices Floatless Relay (Example of Connection) Electronic Devices 51F-G2 B operation Caution concerning electrode connection ●Check carefully the terminal symbols and electrode lengths before ●Use 0V to 100V terminal in the case of 100V AC power supply. performing electrode circuit connection. ●Use 0V to 200V terminal in the case of 200V AC power supply. E1 : upper limit, E2 : lower limit, E3 : ground (be sure to ground E3 terminal) E4 : abnormal water increase alarm Automatic water-discharge operation combined with abnormal water increase alarm Electronic Power Operation relay circuit ×1 Power supply Electronic Power ●Water-discharge pump operates when water sur- relay circuit breaker circuit ×2 face reaches E1. (Water level is lowered) Molded case ●The pump stocks when water surface leaves E2. ●Alarm sounds when water surface reaches E4 for some reason. Alarm buzzer Electromagnetic switch Ground Abnormal water increase Control range Water tank 51F-I B operation LCD and alarm Electronic Power Operation relay circuit ×1 Power supply Electronic Power ●Upper limit lamp lights and alarm sounds when relay circuit ×2 water surface reaches E1. circuit breaker Molded case ●Middle lamp lights when water surface is in the middle (between E1 and E2). ●Lower limit lamp lights and alarm sounds when water surface leaves E2. Upper limit lamp Lower limit lamp Alarm buzzer Ground Middle lamp Upper limit alarm Middle Water tank Lower limit alarm 210 D_10-電子機器.p65 Page 210 06.7.26, 10:20 am Adobe PageMaker 6.5J/PPC
  • 10. Electronic Devices Floatless Relay (Example of Connection) Electronic Devices FLRP301 (Compact Plug-In) A operation Automatic standard water-supply or water-discharge operation Power supply Operation circuit breaker Molded case Water-supply operation ●Water-supply pump operates when water surface Control circuit leaves E2. (Water level is raised) ●The pump stops when water surface reaches E1. ●When turning on the power while the water sur- face is between E1 and E2, the pump will not Water Water operate until the water surface leaves E2. discharge supply Electromagnetic switch Ground Water-discharge operation ●Water-discharge pump operates when water sur- face reaches E1. (Water level is lowered) Control ●The pump stops when water surface leaves E2. range Operation display Water-discharge opera- Water tank tion Water-supply operation LED Pump Tank LED Pump Tank Supplying Yellow OFF Normal Water supply Yellow ON water Discharging source Red ON Red OFF Normal water ※ For water-discharge operation, connect wire connected to terminal 1 to terminal 11. Automatic water-supply operation combined with pump idle prevention Operation Power supply Water tank circuit breaker ●Water-supply pump operates when water surface Molded case leaves E2. (Water level is raised) Control Control circuit circuit ●The pump stops when water surface reaches E1. ●When turning on the power while the water sur- face is within the control range (between E1 and E2), the pump will not operate until the water surface leaves E2. Alarm buzzer Water supply source Electromagnetic switch ●The pump stops and alarm sounds when water Ground surface leaves E'2. ●Normal water-supply operation resumes when Control water surface reaches E'1. range Operation display Water tank Water P1LED P2LED Pump Tank supply Alarm buzzer source Yellow Yellow OFF Decrease Insufficient ON Water supply source Yellow Red OFF Normal Insufficient ON Supplying Red Yellow ON water Normal OFF Red Red OFF Normal Normal OFF 211 D_10-電子機器.p65 Page 211 06.7.26, 10:20 am Adobe PageMaker 6.5J/PPC
  • 11. Electronic Devices Floatless Relay (Example of Connection) Electronic Devices 51F-GPN (Compact Plug-In) B operation Automatic standard water-supply or water-discharge operation Power supply Operation circuit breaker Molded case Water-supply operation ●Water-supply pump operates when water surface leaves Control circuit E2. (Water level is raised) ●The pump stops when water surface reaches E1. ●The pump operates when the power is turned on while water surface is within the control range (between E1 Water Water and E2). The pump will not stop until water surface discharge supply reaches E1. Electromagnetic switch Ground Water-discharge operation ●Water-discharge pump operates when water surface Control reaches E1. (Water level is lowered) range ●The pump stops when water surface leaves E2. Water tank Operation display Water-supply operation Water-discharge operation LED Pump Tank LED Pump Tank Water supply source Supplying Yellow OFF Normal Yellow ON water Discharging Red OFF Normal Red ON water ※ For water-discharge operation, connect wire connected to terminal 1 to terminal 11. (long) (short) (middle) (long) (short) (middle) Bottom Bottom Red view Red view Yellow Yellow Electronic Electronic circuit circuit Yellow Yellow Red Red Water Water Water Water supply discharge supply discharge FLRP301 internal connection diagram 51F-GPN internal connection diagram 212 D_10-電子機器.p65 Page 212 06.7.26, 10:20 am Adobe PageMaker 6.5J/PPC