SlideShare a Scribd company logo
1 of 45
Download to read offline
1
CE 412: Introduction to Structural Dynamics and
Earthquake Engineering
MODULE 10
(Applications of UBC-97, seismic provisions)
2
TABLE 16-L -VERTICAL STRUCTURAL IRREGULARITIES
3
TABLE16-M -PLAN STRUCTURAL IRREGULARITIES
1629.5.1 General. Each structure shall be designated as being structurally regular or
irregular in accordance with Sections 1629.5.2 and 1629.5.3.
1629.5.2 Regular structures. Regular structures have no significant physical
discontinuities in plan or vertical configuration or in their lateral-force-resisting systems
such as the irregular features described in Section 1629.5.3.
1629.5.3 Irregular structures.
1. Irregular structures have significant physical discontinuities in configuration or in their
lateral-force-resisting systems. Irregular features include, but are not limited to, those
described inTables 16-L and 16-M. All structures in Seismic Zone 1 and Occupancy
Categories 4 and 5 in Seismic Zone 2 need to be evaluated only for vertical
irregularities ofType 5 (Table 16-L) and horizontal irregularities of Type 1 (Table 16-M).
1629.5 Configuration Requirements.
1629.5.3 Irregular structures (contd).
2. Structures having any of the features listed inTable 16-L shall be designated as if
having a vertical irregularity.
EXCEPTION:Where no story drift ratio under design lateral forces is greater than 1.3 times the
story drift ratio of the story above, the structure may be deemed to not have the structural
irregularities ofType 1 or 2 inTable 16-L.The story drift ratio for the top two stories need not be
considered.The story drifts for this determination may be calculated neglecting torsional effects.
3. Structures having any of the features listed inTable 16-M shall be designated as having
a plan irregularity.
1629.5 Configuration Requirements.
1629.8.1 General. Any structure may be, and certain structures defined below shall
be, designed using the dynamic lateral-force procedures of Section 1631.
1629.8.2 Simplified static. The simplified static lateral-force procedure set forth in
Section 1630.2.3 may be used for the following structures of Occupancy Category 4
or 5:
1. Buildings of any occupancy (including single-family dwellings) not more than three
stories in height excluding basements, that use light-frame construction.
2. Other buildings not more than two stories in height excluding basements
1629.8 Selection of Lateral-force Procedure.
1629.8.3 Static.The static lateral force procedure of Section 1630 may be used for
the following structures:
1.All structures, regular or irregular, in Seismic Zone 1 and in Occupancy Categories 4
and 5 in Seismic Zone 2.
2. Regular structures under 240 feet (73 152 mm) in height with lateral force
resistance provided by systems listed in Table 16-N, except where Section 1629.8.4,
Item 4, applies.
3. Irregular structures not more than five stories or 65 feet (19 812 mm) in height.
4. Structures having a flexible upper portion supported on a rigid lower portion
where both portions of the structure considered separately can be classified as being
regular, the average story stiffness of the lower portion is at least 10 times the average
story stiffness of the upper portion and the period of the entire structure is not
greater than 1.1 times the period of the upper portion considered as a separate
structure fixed at the base.
1629.8 Selection of Lateral-force Procedure.
1629.8.4 Dynamic.The dynamic lateral-force procedure of Section 1631 shall be
used for all other structures, including the following:
1. Structures 240 feet (73,152 mm) or more in height, except as permitted by Section
1629.8.3, Item 1.
2. Structures having a stiffness, weight or geometric vertical irregularity ofType 1, 2 or
3, as defined in Table 16-L, or structures having irregular features not described in
Table 16-L or 16-M, except as permitted by Section 1630.4.2.
3. Structures over five stories or 65 feet (19,812 mm) in height in Seismic Zones 3 and
4 not having the same structural system throughout their height except as permitted
by Section 1630.4.2.
4. Structures, regular or irregular, located on Soil Profile Type SF,that have a period
greater than 0.7 second.The analysis shall include the effects of the soils at the site
and shall conform to Section 1631.2, Item 4.
1629.8 Selection of Lateral-force Procedure.
1629.9.1 Discontinuity. Structures with a discontinuity in capacity, vertical irregularity
Type 5 as defined inTable 16-L, shall not be over two stories or 30 feet (9,144 mm) in
height where the weak story has a calculated strength of less than 65 percent of the
story above.
EXCEPTION:Where the weak story is capable of resisting a total lateral seismic force of Ωo
times the design force prescribed in Section 1630.Where Ωo = Seismic Force Amplification Factor,
which is required to account for structural overstrength and set forth inTable 16-N.
1629.9.2 Undefined structural systems. For undefined structural systems not
listed inTable 16-N, the coefficient R shall be substantiated by approved cyclic test data
and analyses.
1629.9.3 Irregular features. All structures having irregular features described in
Table 16-L or 16-M shall be designed to meet the additional requirements of those
sections referenced in the tables.
1629.9 System Limitations.
10
11
Vertical irregularity Type 1
12
This type of irregularity can also be determined by comparing values of lateral story
displacements or drift ratios due to the prescribed lateral forces.
This deformation comparison may even be more effective than the stiffness
comparison because the shape of the first mode shape is often closely approximated
by the structure displacements due to the specified triangular load pattern. Floor level
displacements and corresponding story drift ratios are directly available from
computer programs.
To compare displacements rather than stiffness, it is necessary to use the reciprocal of
the limiting percentage ratios of 70 and 80 percent as they apply to story stiffness, or
reverse their applicability to the story or
stories above.
Vertical irregularity Type 1
13
Vertical irregularity Type 1
14
Vertical irregularity Type 1
15
Vertical irregularity Type 1
16
In the example above, only the first story was checked for possible soft
story vertical irregularity. In practice, all stories must be checked, unless a
dynamic analysis is performed. It is often convenient to create a table as
shown below to facilitate this exercise.
Vertical irregularity Type 1
17
Vertical irregularity Type 3
18
Vertical irregularity Type 3
19
Vertical irregularity Type 3
20
Vertical irregularity Type 5
21
Vertical irregularity Type 5
22
Vertical irregularity Type 5
Plan Structural Irregularities
23
Type-I:Torsional irregularity - to be considered when diaphragms are not flexible .
Torsional irregularity shall be considered to exist when the maximum story drift, computed
including accidental torsion, at one end of the structure transverse to an axis is more than 1.2
times the average of the story drifts of the
two ends of the structure
24
Reference sections:1633.1, 1633.2.9, Item 6
Plan irregularity Type 1
25
Plan irregularity Type 1
26
Plan irregularity Type 1
Plan irregularity Type 1: further comments
Plan irregularity Type 1: further comments
29
Type-III: Diaphragm discontinuity
Diaphragms with abrupt discontinuities or variations in stiffness, including those having cutout
or open areas greater than 50 percent of the gross enclosed area of the diaphragm, or changes
in effective diaphragm stiffness of more than 50 percent from one story to the next.
Plan irregularity Type 3
Causes of Dynamic Loading
30
31
Plan irregularity Type 3 Reference sections:1633.2.9, Item 6 and 7
Plan irregularity Type 3
Plan irregularity Type 3
35
Plan irregularity Type 5
Reference sections:1633.1
1630.1.3 P-∆ effects
The resulting member forces and moments and the story drifts induced by P-∆ effects shall
be considered in the evaluation of overall structural frame stability and shall be evaluated
using the forces producing the displacements of ∆s.
P- ∆ need not be considered when the ratio of secondary moment to primary moment
does not exceed 0.10; the ratio may be evaluated for any story as the product of the total
dead, floor live and snow load, as required in Section 1612, above the story times the
seismic drift in that story divided by the product of the seismic shear in that story times
the height of that story.
In Seismic Zones 3 and 4, P- ∆ need not be considered when the story drift ratio does not
exceed 0.02/R.
P- vs P-∆ effect
h1=20 ft
1 P-∆ criteria for the building
2 Check the first story for P-∆ requirements
2 Check the first story for P-∆ requirements
Determine the following:
1. Maximum inelastic response displacements. §1630.9.1
2. Compare story drifts with the limit value. §1630.10.2
∆M =0.7R∆s=5.95∆s
14.52-11.36= 3.16
2. Compare story drifts with the limit value. §1630.10.2

More Related Content

What's hot

What's hot (20)

Dynamics of structures 5th edition chopra solutions manual
Dynamics of structures 5th edition chopra solutions manualDynamics of structures 5th edition chopra solutions manual
Dynamics of structures 5th edition chopra solutions manual
 
Structural anaysis and design of g + 5 storey building using bentley stadd pr...
Structural anaysis and design of g + 5 storey building using bentley stadd pr...Structural anaysis and design of g + 5 storey building using bentley stadd pr...
Structural anaysis and design of g + 5 storey building using bentley stadd pr...
 
Uni and bi axial column and design
Uni and bi axial column and design Uni and bi axial column and design
Uni and bi axial column and design
 
Design calculations of raft foundation
Design calculations of raft foundationDesign calculations of raft foundation
Design calculations of raft foundation
 
Structural engineering ii
Structural engineering iiStructural engineering ii
Structural engineering ii
 
Column Interaction Diagram construction
Column Interaction Diagram constructionColumn Interaction Diagram construction
Column Interaction Diagram construction
 
NSCP 2010 , Volume 1
NSCP 2010 , Volume 1NSCP 2010 , Volume 1
NSCP 2010 , Volume 1
 
Design of compression members
Design of compression membersDesign of compression members
Design of compression members
 
Raft foundations _design_and_analysis_with_a_practical_approach
Raft foundations _design_and_analysis_with_a_practical_approachRaft foundations _design_and_analysis_with_a_practical_approach
Raft foundations _design_and_analysis_with_a_practical_approach
 
ETABS Modelling
ETABS ModellingETABS Modelling
ETABS Modelling
 
Chapter 6-influence lines for statically determinate structures
Chapter 6-influence lines for statically  determinate structuresChapter 6-influence lines for statically  determinate structures
Chapter 6-influence lines for statically determinate structures
 
Design Procedure of Singly,Doubly & T-Beam(As Per ACI code)
Design Procedure of Singly,Doubly & T-Beam(As Per ACI code)Design Procedure of Singly,Doubly & T-Beam(As Per ACI code)
Design Procedure of Singly,Doubly & T-Beam(As Per ACI code)
 
Seismic Design Of Structures Project
Seismic Design Of Structures ProjectSeismic Design Of Structures Project
Seismic Design Of Structures Project
 
Seismic Analysis
Seismic AnalysisSeismic Analysis
Seismic Analysis
 
Lec.2 statically determinate structures & statically indeterminate struct...
Lec.2 statically determinate structures & statically indeterminate struct...Lec.2 statically determinate structures & statically indeterminate struct...
Lec.2 statically determinate structures & statically indeterminate struct...
 
TUNED LIQUID DAMPER
TUNED LIQUID DAMPERTUNED LIQUID DAMPER
TUNED LIQUID DAMPER
 
ANALYSIS AND DESIGN OF MULTI STOREY (G+5) COMMERCIAL BUILDING BY STAAD PRO AN...
ANALYSIS AND DESIGN OF MULTI STOREY (G+5) COMMERCIAL BUILDING BY STAAD PRO AN...ANALYSIS AND DESIGN OF MULTI STOREY (G+5) COMMERCIAL BUILDING BY STAAD PRO AN...
ANALYSIS AND DESIGN OF MULTI STOREY (G+5) COMMERCIAL BUILDING BY STAAD PRO AN...
 
Chapter 3-analysis of statically determinate trusses
Chapter 3-analysis of statically determinate trussesChapter 3-analysis of statically determinate trusses
Chapter 3-analysis of statically determinate trusses
 
Response Spectrum
Response SpectrumResponse Spectrum
Response Spectrum
 
Examples on total consolidation
Examples on total  consolidationExamples on total  consolidation
Examples on total consolidation
 

Similar to Module 10, Spring 2020.pdf

Seismic response of rc frame structure with soft storey
Seismic response of rc frame structure with soft storeySeismic response of rc frame structure with soft storey
Seismic response of rc frame structure with soft storey
eSAT Publishing House
 
AS 4678—2002www.standards.com.au © Standards Australia .docx
AS 4678—2002www.standards.com.au © Standards Australia .docxAS 4678—2002www.standards.com.au © Standards Australia .docx
AS 4678—2002www.standards.com.au © Standards Australia .docx
rossskuddershamus
 

Similar to Module 10, Spring 2020.pdf (20)

Street Light Automatic Intensity Controller
Street Light Automatic Intensity ControllerStreet Light Automatic Intensity Controller
Street Light Automatic Intensity Controller
 
Comparison of performance of lateral load resisting systems in multi storey f...
Comparison of performance of lateral load resisting systems in multi storey f...Comparison of performance of lateral load resisting systems in multi storey f...
Comparison of performance of lateral load resisting systems in multi storey f...
 
Effect of Planar Solid Shear Wall - Frame Arrangement on the Deformation Beha...
Effect of Planar Solid Shear Wall - Frame Arrangement on the Deformation Beha...Effect of Planar Solid Shear Wall - Frame Arrangement on the Deformation Beha...
Effect of Planar Solid Shear Wall - Frame Arrangement on the Deformation Beha...
 
N0121398105
N0121398105N0121398105
N0121398105
 
Influence of Combine Vertical Irregularities in the Response of Earthquake Re...
Influence of Combine Vertical Irregularities in the Response of Earthquake Re...Influence of Combine Vertical Irregularities in the Response of Earthquake Re...
Influence of Combine Vertical Irregularities in the Response of Earthquake Re...
 
seismic ubc -97
seismic ubc -97seismic ubc -97
seismic ubc -97
 
G section15
G section15G section15
G section15
 
IRJET- Comparison of Incremental Dynamic Analysis Curve with Pushover Curve
IRJET- Comparison of Incremental Dynamic Analysis Curve with Pushover CurveIRJET- Comparison of Incremental Dynamic Analysis Curve with Pushover Curve
IRJET- Comparison of Incremental Dynamic Analysis Curve with Pushover Curve
 
IRJET - Seismic Analysis of Different Shape of RC Building by using the Visco...
IRJET - Seismic Analysis of Different Shape of RC Building by using the Visco...IRJET - Seismic Analysis of Different Shape of RC Building by using the Visco...
IRJET - Seismic Analysis of Different Shape of RC Building by using the Visco...
 
D012211830
D012211830D012211830
D012211830
 
Seismic Analysis of Multi-Storeyed Building Having Vertical Irregularities us...
Seismic Analysis of Multi-Storeyed Building Having Vertical Irregularities us...Seismic Analysis of Multi-Storeyed Building Having Vertical Irregularities us...
Seismic Analysis of Multi-Storeyed Building Having Vertical Irregularities us...
 
IRJET- Collapse Analysis of Irregular Flat Slab Structure at different Seismi...
IRJET- Collapse Analysis of Irregular Flat Slab Structure at different Seismi...IRJET- Collapse Analysis of Irregular Flat Slab Structure at different Seismi...
IRJET- Collapse Analysis of Irregular Flat Slab Structure at different Seismi...
 
Progressive Collapse Analysis of RC Framed Structures
Progressive Collapse Analysis of RC Framed StructuresProgressive Collapse Analysis of RC Framed Structures
Progressive Collapse Analysis of RC Framed Structures
 
Summary of CHAPTER 6 (ACI318-14M) Structural Analysis
Summary of CHAPTER 6 (ACI318-14M) Structural AnalysisSummary of CHAPTER 6 (ACI318-14M) Structural Analysis
Summary of CHAPTER 6 (ACI318-14M) Structural Analysis
 
IRJET- Progressive Collapse Resistance of Flat Slab Building
IRJET- Progressive Collapse Resistance of Flat Slab BuildingIRJET- Progressive Collapse Resistance of Flat Slab Building
IRJET- Progressive Collapse Resistance of Flat Slab Building
 
IRJET- Comparative Analysis on Seismic Behaviour of Regular and Verticall...
IRJET-  	  Comparative Analysis on Seismic Behaviour of Regular and Verticall...IRJET-  	  Comparative Analysis on Seismic Behaviour of Regular and Verticall...
IRJET- Comparative Analysis on Seismic Behaviour of Regular and Verticall...
 
Seismic response of rc frame structure with soft storey
Seismic response of rc frame structure with soft storeySeismic response of rc frame structure with soft storey
Seismic response of rc frame structure with soft storey
 
Skills m08 e_portalframes_singlestoreybuildings
Skills m08 e_portalframes_singlestoreybuildingsSkills m08 e_portalframes_singlestoreybuildings
Skills m08 e_portalframes_singlestoreybuildings
 
PROGRESSIVE COLLAPSE ANALYSIS OF REINFORCED CONCRETE STRUCTURES WITH FLAT SLA...
PROGRESSIVE COLLAPSE ANALYSIS OF REINFORCED CONCRETE STRUCTURES WITH FLAT SLA...PROGRESSIVE COLLAPSE ANALYSIS OF REINFORCED CONCRETE STRUCTURES WITH FLAT SLA...
PROGRESSIVE COLLAPSE ANALYSIS OF REINFORCED CONCRETE STRUCTURES WITH FLAT SLA...
 
AS 4678—2002www.standards.com.au © Standards Australia .docx
AS 4678—2002www.standards.com.au © Standards Australia .docxAS 4678—2002www.standards.com.au © Standards Australia .docx
AS 4678—2002www.standards.com.au © Standards Australia .docx
 

More from Mohammad Javed (15)

Module 14 [Compatibility Mode].pdf
Module 14 [Compatibility Mode].pdfModule 14 [Compatibility Mode].pdf
Module 14 [Compatibility Mode].pdf
 
Module 9, Spring 2020.pdf
Module 9, Spring 2020.pdfModule 9, Spring 2020.pdf
Module 9, Spring 2020.pdf
 
Module 8, Spring 2020.pdf
Module 8, Spring 2020.pdfModule 8, Spring 2020.pdf
Module 8, Spring 2020.pdf
 
Module 7, Spring 2020.pdf
Module  7, Spring 2020.pdfModule  7, Spring 2020.pdf
Module 7, Spring 2020.pdf
 
Module 6, Spring 2020.pdf
Module  6, Spring 2020.pdfModule  6, Spring 2020.pdf
Module 6, Spring 2020.pdf
 
Module 5, Spring 2020.pdf
Module 5, Spring 2020.pdfModule 5, Spring 2020.pdf
Module 5, Spring 2020.pdf
 
Module 4_spring 2020.pdf
Module 4_spring 2020.pdfModule 4_spring 2020.pdf
Module 4_spring 2020.pdf
 
Module 3_ Spring 2020.pdf
Module 3_ Spring 2020.pdfModule 3_ Spring 2020.pdf
Module 3_ Spring 2020.pdf
 
Module 2_spring 2020.pdf
Module 2_spring 2020.pdfModule 2_spring 2020.pdf
Module 2_spring 2020.pdf
 
Module 1_Spring 2020.pdf
Module 1_Spring 2020.pdfModule 1_Spring 2020.pdf
Module 1_Spring 2020.pdf
 
Module 4
Module 4Module 4
Module 4
 
Module 5
Module 5Module 5
Module 5
 
Module 8
Module 8 Module 8
Module 8
 
Module 7
Module 7 Module 7
Module 7
 
Module 6 updated
Module 6 updatedModule 6 updated
Module 6 updated
 

Recently uploaded

AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
ankushspencer015
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Christo Ananth
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
dharasingh5698
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college project
Tonystark477637
 
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Dr.Costas Sachpazis
 

Recently uploaded (20)

(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
 
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELLPVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdf
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
Vivazz, Mieres Social Housing Design Spain
Vivazz, Mieres Social Housing Design SpainVivazz, Mieres Social Housing Design Spain
Vivazz, Mieres Social Housing Design Spain
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - V
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college project
 
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 
NFPA 5000 2024 standard .
NFPA 5000 2024 standard                                  .NFPA 5000 2024 standard                                  .
NFPA 5000 2024 standard .
 
chapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringchapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineering
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.ppt
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)
 

Module 10, Spring 2020.pdf

  • 1. 1 CE 412: Introduction to Structural Dynamics and Earthquake Engineering MODULE 10 (Applications of UBC-97, seismic provisions)
  • 2. 2 TABLE 16-L -VERTICAL STRUCTURAL IRREGULARITIES
  • 4. 1629.5.1 General. Each structure shall be designated as being structurally regular or irregular in accordance with Sections 1629.5.2 and 1629.5.3. 1629.5.2 Regular structures. Regular structures have no significant physical discontinuities in plan or vertical configuration or in their lateral-force-resisting systems such as the irregular features described in Section 1629.5.3. 1629.5.3 Irregular structures. 1. Irregular structures have significant physical discontinuities in configuration or in their lateral-force-resisting systems. Irregular features include, but are not limited to, those described inTables 16-L and 16-M. All structures in Seismic Zone 1 and Occupancy Categories 4 and 5 in Seismic Zone 2 need to be evaluated only for vertical irregularities ofType 5 (Table 16-L) and horizontal irregularities of Type 1 (Table 16-M). 1629.5 Configuration Requirements.
  • 5. 1629.5.3 Irregular structures (contd). 2. Structures having any of the features listed inTable 16-L shall be designated as if having a vertical irregularity. EXCEPTION:Where no story drift ratio under design lateral forces is greater than 1.3 times the story drift ratio of the story above, the structure may be deemed to not have the structural irregularities ofType 1 or 2 inTable 16-L.The story drift ratio for the top two stories need not be considered.The story drifts for this determination may be calculated neglecting torsional effects. 3. Structures having any of the features listed inTable 16-M shall be designated as having a plan irregularity. 1629.5 Configuration Requirements.
  • 6. 1629.8.1 General. Any structure may be, and certain structures defined below shall be, designed using the dynamic lateral-force procedures of Section 1631. 1629.8.2 Simplified static. The simplified static lateral-force procedure set forth in Section 1630.2.3 may be used for the following structures of Occupancy Category 4 or 5: 1. Buildings of any occupancy (including single-family dwellings) not more than three stories in height excluding basements, that use light-frame construction. 2. Other buildings not more than two stories in height excluding basements 1629.8 Selection of Lateral-force Procedure.
  • 7. 1629.8.3 Static.The static lateral force procedure of Section 1630 may be used for the following structures: 1.All structures, regular or irregular, in Seismic Zone 1 and in Occupancy Categories 4 and 5 in Seismic Zone 2. 2. Regular structures under 240 feet (73 152 mm) in height with lateral force resistance provided by systems listed in Table 16-N, except where Section 1629.8.4, Item 4, applies. 3. Irregular structures not more than five stories or 65 feet (19 812 mm) in height. 4. Structures having a flexible upper portion supported on a rigid lower portion where both portions of the structure considered separately can be classified as being regular, the average story stiffness of the lower portion is at least 10 times the average story stiffness of the upper portion and the period of the entire structure is not greater than 1.1 times the period of the upper portion considered as a separate structure fixed at the base. 1629.8 Selection of Lateral-force Procedure.
  • 8. 1629.8.4 Dynamic.The dynamic lateral-force procedure of Section 1631 shall be used for all other structures, including the following: 1. Structures 240 feet (73,152 mm) or more in height, except as permitted by Section 1629.8.3, Item 1. 2. Structures having a stiffness, weight or geometric vertical irregularity ofType 1, 2 or 3, as defined in Table 16-L, or structures having irregular features not described in Table 16-L or 16-M, except as permitted by Section 1630.4.2. 3. Structures over five stories or 65 feet (19,812 mm) in height in Seismic Zones 3 and 4 not having the same structural system throughout their height except as permitted by Section 1630.4.2. 4. Structures, regular or irregular, located on Soil Profile Type SF,that have a period greater than 0.7 second.The analysis shall include the effects of the soils at the site and shall conform to Section 1631.2, Item 4. 1629.8 Selection of Lateral-force Procedure.
  • 9. 1629.9.1 Discontinuity. Structures with a discontinuity in capacity, vertical irregularity Type 5 as defined inTable 16-L, shall not be over two stories or 30 feet (9,144 mm) in height where the weak story has a calculated strength of less than 65 percent of the story above. EXCEPTION:Where the weak story is capable of resisting a total lateral seismic force of Ωo times the design force prescribed in Section 1630.Where Ωo = Seismic Force Amplification Factor, which is required to account for structural overstrength and set forth inTable 16-N. 1629.9.2 Undefined structural systems. For undefined structural systems not listed inTable 16-N, the coefficient R shall be substantiated by approved cyclic test data and analyses. 1629.9.3 Irregular features. All structures having irregular features described in Table 16-L or 16-M shall be designed to meet the additional requirements of those sections referenced in the tables. 1629.9 System Limitations.
  • 10. 10
  • 12. 12 This type of irregularity can also be determined by comparing values of lateral story displacements or drift ratios due to the prescribed lateral forces. This deformation comparison may even be more effective than the stiffness comparison because the shape of the first mode shape is often closely approximated by the structure displacements due to the specified triangular load pattern. Floor level displacements and corresponding story drift ratios are directly available from computer programs. To compare displacements rather than stiffness, it is necessary to use the reciprocal of the limiting percentage ratios of 70 and 80 percent as they apply to story stiffness, or reverse their applicability to the story or stories above. Vertical irregularity Type 1
  • 16. 16 In the example above, only the first story was checked for possible soft story vertical irregularity. In practice, all stories must be checked, unless a dynamic analysis is performed. It is often convenient to create a table as shown below to facilitate this exercise. Vertical irregularity Type 1
  • 23. Plan Structural Irregularities 23 Type-I:Torsional irregularity - to be considered when diaphragms are not flexible . Torsional irregularity shall be considered to exist when the maximum story drift, computed including accidental torsion, at one end of the structure transverse to an axis is more than 1.2 times the average of the story drifts of the two ends of the structure
  • 24. 24 Reference sections:1633.1, 1633.2.9, Item 6 Plan irregularity Type 1
  • 27. Plan irregularity Type 1: further comments
  • 28. Plan irregularity Type 1: further comments
  • 29. 29 Type-III: Diaphragm discontinuity Diaphragms with abrupt discontinuities or variations in stiffness, including those having cutout or open areas greater than 50 percent of the gross enclosed area of the diaphragm, or changes in effective diaphragm stiffness of more than 50 percent from one story to the next. Plan irregularity Type 3
  • 30. Causes of Dynamic Loading 30
  • 31. 31 Plan irregularity Type 3 Reference sections:1633.2.9, Item 6 and 7
  • 34.
  • 35. 35 Plan irregularity Type 5 Reference sections:1633.1
  • 36. 1630.1.3 P-∆ effects The resulting member forces and moments and the story drifts induced by P-∆ effects shall be considered in the evaluation of overall structural frame stability and shall be evaluated using the forces producing the displacements of ∆s. P- ∆ need not be considered when the ratio of secondary moment to primary moment does not exceed 0.10; the ratio may be evaluated for any story as the product of the total dead, floor live and snow load, as required in Section 1612, above the story times the seismic drift in that story divided by the product of the seismic shear in that story times the height of that story. In Seismic Zones 3 and 4, P- ∆ need not be considered when the story drift ratio does not exceed 0.02/R.
  • 37. P- vs P-∆ effect
  • 39. 1 P-∆ criteria for the building
  • 40. 2 Check the first story for P-∆ requirements
  • 41. 2 Check the first story for P-∆ requirements
  • 43. 1. Maximum inelastic response displacements. §1630.9.1
  • 44. 2. Compare story drifts with the limit value. §1630.10.2
  • 45. ∆M =0.7R∆s=5.95∆s 14.52-11.36= 3.16 2. Compare story drifts with the limit value. §1630.10.2