UNIT-V FIRE SAFETY INSTALLATION

20CE7020E
BUILDING SERVICES
FIRE SAFETY
INSTALLATION
UNIT – 5
FIRE SAFETY INSTALLATION
Fire prevention and control systems - Fire alarms - Electrical alarm
circuits -Smoke extraction and ventilation -Gas extinguishers - Types of
detectors - Gas installation and components.
FIRE PREVENTION AND CONTROL SYSTEMS
• Stipulation of the various fire protection measures for building, to
minimise the loss of life & property and effects of fire on surrounding
area, are broadly based on following aspects/ philosophy.
Fire Tetrahedron
Extinguishing of fire
•Cooling – fire extinguishing by the application of water acts by removing heat from the
fuel faster than combustion generates it.
•Oxygen starving (பட்டினி) – application of carbon dioxides is intended primarily to
starve the fire of oxygen. Ex., putting fire blanket to cut off the oxygen
supply.
•Remove fuel source – a forest fire may be fought by starting smaller fires in advance of
the main blaze, to deprive it of fuel. Ex., physical removing fuel
•Interference of Chemical reaction – other gaseous fire suppression agents, such as halon
or HFC-225, interfere with the chemical reaction itself.
Fire hydrants systems
Rising Mians
(a) Dry riser (RED)
• Any floor is at a habitable height beyond 24 m and not exceeding 60 m above the ground level.
• For a building under purpose group of the fire code, having a habitable height exceeding 10 m but
not exceeding 60 m.
(b)Wet riser (Yellow)
• Any floor exceeding habitable height of 60 m above ground level
• Wet rising main zone heights exceeding 76 m may be permitted when a listed
pressure regulating device, which controls nozzle pressure under both flow and no flow
conditions is installed at each outlet in house rise buildings, the following requirements are
also applicable to wet risers:
• The maximum zone height shall not exceed 120 m
• The pressure regulating device is arranged to regulate pressure at the hose valve
outlet to a running pressure not exceeding 5.5 bar
• The pressure on the inlet side of the pressure regulating device does not exceed the
working pressure rating of the device
• All other pipe fitting and devices on the system are rated for not less than the
maximum system pressure.
UNIT-V    FIRE SAFETY INSTALLATION
UNIT-V    FIRE SAFETY INSTALLATION
Fire Safety precautions
• Don't overload outlets with multiple outlet cords or plugs. If
additional outlets are required, use an IS marked multi-outlet "power strip"
with its own built-in circuit breaker.
• Careless smoking, use of candles and incense, and unattended
cooking appliances remain major causes of fatal fires in residential
buildings. Use of fire crackers, hot work, and open fire is prohibited in all
buildings.
• Keep walkways, stairwells and exits free from obstructions at all
times.
• Report immediately if you observe/noticed damaged fire equipment
and other fire hazards to Campus security and Fire Safety wing.
• Do not open fire hydrant/hose reel water for unnecessarily use.
• Do not misuse of Fire Extinguisher.
UNIT-V    FIRE SAFETY INSTALLATION
Dry Pipe System
•Above the control valves, system is charged with compressed air/nitrogen instead of water
•Dry pipe valve held closed by air pressure
•Upon activation of sprinkler head, air is released and water flows into the pipe work
•For areas subjected to freezing temperatures.
Pre-Action System
• For areas where accidental discharge of water is unacceptable.
• Pipes filled with low pressure air.
• Heat/ smoke detector send signal to valve to release water to pipe work and sound alarm.
• When sprinkler burst, water is discharged.
• Prevent unwanted water flow when a pipe or sprinkler is accidently broken.
(d). Deluge System
• Pipes are usually empty, sprinkler are open
• Detectors activate control valve to allow water to flow
• Water is discharged simultaneously through all the open sprinklers in
the area.
•Thus, providing fast and total wetting of protected areas.
•For areas that required total coverage (extra high hazard area such as
aircraft hangers, power generating stations, and petrochemical facilities).
Fire protection equipment
 Automatic fire detection system
 Automatic sprinkler system
 Automatic release mechanism
 Automatic self-closing device
• Basement
 Boundary
 Cavity
 Ceiling
 Circulation space
.
•
Common Fire
Hazards
• Kitchen fire from unattended cooking, such as frying, boiling and simmering.
• Electrical systems that are overloaded, resulting in hot wiring or connections, or failed components.
• Combustible storage areas with insufficient protection.
• Combustibles near equipment that generates heat, flame, or sparks.
• Candles and other often flames
• Smoking (cigarettes, cigars, pipes, lighters, etc.).
• Equipment that generates heat and utilizes combustible materials.
• Flammable liquids and aerosols.
• Flammable solvent (and rags soaked with solvent) placed in enclosed trash cans.
• Fireplace chimneys not properly or regularly cleaned.
• Cooking appliances-stoves, ovens.
• Heating appliances-fireplaces, wood burning stoves, furnaces, boilers, portable heaters.
• Household appliances-clothes dryers, curling irons, hair dryers, refrigerators, freezers.
• Chimneys that concentrate creosote.
• Electrical wiring in poor condition.
• Leaking Batteries.
• Personal ignition sources-matches, lighters
• Electronic and electrical equipment
• Exterior cooking equipment-barbecue
FIRE ALARM
Fire alarm systems generally use visual and audio signalization to warn the
occupants of the building. Some fire alarm systems may also disable elevators,
which under most circumstances, are unsafe to use during a fire.
Fire Alarm Control Panels
(a) Function of control panel
• It is the brain of the fire detection and alarm system
• Responsible for monitoring the various alarm input devices such
as manual and automatic detection components
• Activates alarm output devices such as horns bells warning lights
emergency telephone diallers and building controls
(b) Design
• Control panels may range from simple units with a single input
and output zone, to complex computer driven systems that monitor
several buildings over an entire campus.
Types of arrangements
• Conventional (Older technology)
• Addressable (Newer technology)
Conventional Systems
(a) Conventional
• Point wired – have a dedicated writing back to the signal processing
• One or more circuits are routed through the protected space of the building.
• Along each circuit, one or more detection devices are placed
(b) Factors for selection & placement
• Depends on need for automatic or manual initiation
• Ambient temperature & environment conditions
• Anticipated type of fire
• Desired speed of response
(c) Fire occurrence situation
• One or more detectors will operate
• Action will close the circuit which the fire control panel recognizes as an emergency condition
• Panel will then activate one or more signalling alarm circuits to sound building alarm and
summon emergency help
• Panel may also send the signal to another alarm panel so that it can be monitored from a
remote point.
(d) Fault monitoring
• To help ensure that the system is functioning properly
these systems monitor the condition of each circuit by sending a
small current through the wires.
• Should a fault occur, such as due to a wiring break this
current cannot proceed and is registered as a trouble condition
• The indication is a need for service somewhere along the
respective circuit
Addressable systems
(a) Addressable systems
• State of the art in fire detection and alarm technology
• Monitors and controls the capabilities of each alarm initiating and signalling device through
microprocessor and systems software
• Major differences involve the way in which each device is monitored
• Each initiating device (automatic detector, manual station, sprinkler water flow switches) is given a
specific identification or address
• This address is correspondingly programmed into the control panels memory with information such
as the type of device its location and specific response details such as which alarm devices are to be
activated.
(b) Operations
•The control panels microprocessors send a constant interrogation signal over each circuit
•Each initiating devices is contracted to inquires its status (normal or emergency)
•This activates monitoring process occurs in rapid succession providing system updates every 5 to 10
seconds
•Therefore, instead of merely showing a fault along a wire they will indicate the location of the
problem
•This permits faster diagnosis of the trouble and allows a quicker repair and return to normal.
ELECTRICAL ALARM CIRCUITS
Fire Alarm Control Panels
(a) Function of control panel
• Control panel is the brain of the fire detection and alarm system
• Responsible for monitoring the various alarm input devices such
as manual and automatic detection components
• Activates alarm output devices such as horns bells warning lights
emergency telephone diallers and building controls
(b) Design
• Control panels may range from simple units with a single input
and output zone, to complex computer driven systems that monitor
several buildings over an entire campus.
FIRE PREVENTION IN VENTILATING SYSTEMS
Closed Alarm Circuit
PRESSURISATION OF ESCAPE ROUTES
UNIT-V    FIRE SAFETY INSTALLATION
UNIT-V    FIRE SAFETY INSTALLATION
SMOKE EXTRACTOR AND FIRE VENTILATOR
• Number and area of ventilators - estimates are based on providing a smoke-
free layer about 3 m above floor level.
Smoke Reservoir
UNIT-V    FIRE SAFETY INSTALLATION
GAS EXTINGUISHING SYSTEMS – HALON & HALON
SUBSTITUTES
UNIT-V    FIRE SAFETY INSTALLATION
PORTABLE FIRE EXTINGUISHERS (ACID BASED)
• A portable fire extinguisher must contain the type of fire extinguishing agent suitable
for the fire it is required to extinguish. It must also be clearly identifiable by colour
coding for its intended purpose.
Portable fire Extinguishers
Extinguishing agent Extinguisher colour Application
Water Red
Carbonaceous fires,
paper, wood, etc.,
Foam Red with cream band
Ditto and flammable
liquids, oils, fats, etc.,
Carbon dioxide Red with black band
Electrical fires a
flammable liquid
Dry chemicals Red with blue band All fires
UNIT-V    FIRE SAFETY INSTALLATION
Striking type soda – acid
water portable fire
extinguisher
Inversion type soda-and acid water portable fire extinguisher
PORTABLE FIRE EXTINGUISHERS (CHEMICAL BASED)
TYPES OF DETECTORS Ionisation smoke detector
Light Scattering Smoke Detector
Fusible Alloy Heat Detector
Bi-metal Coil Heat Detector
LIGHT OBSCURING AND LASER BEAM DETECTORS
Light Obscuring Detector
LIGHT OBSCURING AND LASER BEAM DETECTORS
Laser Beam Detector
Components of an Infra-red detector
Infra-red Detector for large and small areas
Ultra-violet detector
GAS INSTALLATION
Typical House Installation
Use condensate receiver
1 sur 51

Recommandé

Fire detection and alarm system par
Fire detection and alarm systemFire detection and alarm system
Fire detection and alarm systemsakshisankpal
538 vues27 diapositives
Fire detection and alarm system par
Fire detection and alarm systemFire detection and alarm system
Fire detection and alarm systemsakshisankpal
105 vues27 diapositives
FDA-Fire detection and alarm system par
FDA-Fire detection and alarm systemFDA-Fire detection and alarm system
FDA-Fire detection and alarm systemFathimaNasi
2.4K vues32 diapositives
Fire detectionand alarm systems 090512042400-phpapp01(1) par
Fire detectionand alarm systems 090512042400-phpapp01(1)Fire detectionand alarm systems 090512042400-phpapp01(1)
Fire detectionand alarm systems 090512042400-phpapp01(1)Mohammed Ullah
2K vues38 diapositives
Fire safety par
Fire safety Fire safety
Fire safety Annapurna Sakhardande
132 vues42 diapositives
BS2 group assignment par
BS2 group assignment BS2 group assignment
BS2 group assignment jk tan
138 vues61 diapositives

Contenu connexe

Similaire à UNIT-V FIRE SAFETY INSTALLATION

Fire safety par
Fire safety Fire safety
Fire safety Somu Acharjee
373 vues27 diapositives
Fire and Gas Detection System : Part 3_Technical Features, Locating Detectors... par
Fire and Gas Detection System : Part 3_Technical Features, Locating Detectors...Fire and Gas Detection System : Part 3_Technical Features, Locating Detectors...
Fire and Gas Detection System : Part 3_Technical Features, Locating Detectors...Gan Chun Chet
49 vues16 diapositives
fire fighting System par
fire fighting Systemfire fighting System
fire fighting Systemamitchaurashiya
216 vues20 diapositives
Firefighting & HVAC.pdf par
Firefighting & HVAC.pdfFirefighting & HVAC.pdf
Firefighting & HVAC.pdfMohamedElsayed167434
102 vues28 diapositives
Bs ii-presentation par
Bs ii-presentationBs ii-presentation
Bs ii-presentationLee Chun Yee
366 vues75 diapositives
FIRE DETECTION & ALARM SYSTEMS.pdf par
FIRE DETECTION & ALARM SYSTEMS.pdfFIRE DETECTION & ALARM SYSTEMS.pdf
FIRE DETECTION & ALARM SYSTEMS.pdfRiyaVerma238431
80 vues30 diapositives

Similaire à UNIT-V FIRE SAFETY INSTALLATION(20)

Fire and Gas Detection System : Part 3_Technical Features, Locating Detectors... par Gan Chun Chet
Fire and Gas Detection System : Part 3_Technical Features, Locating Detectors...Fire and Gas Detection System : Part 3_Technical Features, Locating Detectors...
Fire and Gas Detection System : Part 3_Technical Features, Locating Detectors...
Gan Chun Chet49 vues
Building Electronics (Fire Detection and Alarm System and CCTV) par Jed Concepcion
Building Electronics (Fire Detection and Alarm System and CCTV)Building Electronics (Fire Detection and Alarm System and CCTV)
Building Electronics (Fire Detection and Alarm System and CCTV)
Jed Concepcion565 vues
Fire safety in hospitals par Komal Gupta
Fire safety in hospitalsFire safety in hospitals
Fire safety in hospitals
Komal Gupta13.1K vues
FIRE PREVENTION & FIRE FIGHTING EQUIPMENT-N PPT.pptx par NeerajTiwari965955
FIRE PREVENTION & FIRE FIGHTING EQUIPMENT-N PPT.pptxFIRE PREVENTION & FIRE FIGHTING EQUIPMENT-N PPT.pptx
FIRE PREVENTION & FIRE FIGHTING EQUIPMENT-N PPT.pptx
Fire Alarm ... Design, Components, Applications par Mohamed Gamal
Fire Alarm ... Design, Components, ApplicationsFire Alarm ... Design, Components, Applications
Fire Alarm ... Design, Components, Applications
Mohamed Gamal77 vues
BUILDING SERVICE GROUP ASSIGNMENT par XinYee Khoo
BUILDING SERVICE GROUP ASSIGNMENTBUILDING SERVICE GROUP ASSIGNMENT
BUILDING SERVICE GROUP ASSIGNMENT
XinYee Khoo4.4K vues
Fire Fighting and Solution for Globus Shopping Mall (bandra) par Esa Shaikh
Fire Fighting and Solution for Globus Shopping  Mall (bandra)Fire Fighting and Solution for Globus Shopping  Mall (bandra)
Fire Fighting and Solution for Globus Shopping Mall (bandra)
Esa Shaikh13.4K vues
fire detection and alarm system par singh1515
fire detection and alarm systemfire detection and alarm system
fire detection and alarm system
singh1515144.1K vues
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf par nipunwijewardhana
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdfcdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
Intro to basic fire alarm technology par Arman Nasar
Intro to basic fire alarm technologyIntro to basic fire alarm technology
Intro to basic fire alarm technology
Arman Nasar18.2K vues

Plus de karthi keyan

UNIT IV REFRIGERATION PRINCIPLES ... par
UNIT IV	REFRIGERATION PRINCIPLES                                             ...UNIT IV	REFRIGERATION PRINCIPLES                                             ...
UNIT IV REFRIGERATION PRINCIPLES ...karthi keyan
65 vues44 diapositives
UNIT III PRINCIPLES OF ILLUMINATION par
UNIT III	PRINCIPLES OF ILLUMINATION	UNIT III	PRINCIPLES OF ILLUMINATION
UNIT III PRINCIPLES OF ILLUMINATION karthi keyan
50 vues36 diapositives
UNII II ELECTRICAL SYSTEMS IN BUILDINGS par
UNII II		ELECTRICAL SYSTEMS IN BUILDINGS	UNII II		ELECTRICAL SYSTEMS IN BUILDINGS
UNII II ELECTRICAL SYSTEMS IN BUILDINGS karthi keyan
99 vues59 diapositives
UNIT 1 MACHINERIES par
UNIT 1       	MACHINERIES             UNIT 1       	MACHINERIES
UNIT 1 MACHINERIES karthi keyan
62 vues44 diapositives
UNIT-1--STEADY STRESSES AND VARIABLE STRESSES IN MACHINE MEMBERS.pptx par
UNIT-1--STEADY STRESSES AND VARIABLE STRESSES IN MACHINE MEMBERS.pptxUNIT-1--STEADY STRESSES AND VARIABLE STRESSES IN MACHINE MEMBERS.pptx
UNIT-1--STEADY STRESSES AND VARIABLE STRESSES IN MACHINE MEMBERS.pptxkarthi keyan
20 vues89 diapositives
UNIT-4-ENERGY STORING ELEMENTS AND ENGINE COMPONENTS.pptx par
UNIT-4-ENERGY STORING ELEMENTS AND ENGINE COMPONENTS.pptxUNIT-4-ENERGY STORING ELEMENTS AND ENGINE COMPONENTS.pptx
UNIT-4-ENERGY STORING ELEMENTS AND ENGINE COMPONENTS.pptxkarthi keyan
26 vues98 diapositives

Plus de karthi keyan(20)

UNIT IV REFRIGERATION PRINCIPLES ... par karthi keyan
UNIT IV	REFRIGERATION PRINCIPLES                                             ...UNIT IV	REFRIGERATION PRINCIPLES                                             ...
UNIT IV REFRIGERATION PRINCIPLES ...
karthi keyan65 vues
UNIT III PRINCIPLES OF ILLUMINATION par karthi keyan
UNIT III	PRINCIPLES OF ILLUMINATION	UNIT III	PRINCIPLES OF ILLUMINATION
UNIT III PRINCIPLES OF ILLUMINATION
karthi keyan50 vues
UNII II ELECTRICAL SYSTEMS IN BUILDINGS par karthi keyan
UNII II		ELECTRICAL SYSTEMS IN BUILDINGS	UNII II		ELECTRICAL SYSTEMS IN BUILDINGS
UNII II ELECTRICAL SYSTEMS IN BUILDINGS
karthi keyan99 vues
UNIT-1--STEADY STRESSES AND VARIABLE STRESSES IN MACHINE MEMBERS.pptx par karthi keyan
UNIT-1--STEADY STRESSES AND VARIABLE STRESSES IN MACHINE MEMBERS.pptxUNIT-1--STEADY STRESSES AND VARIABLE STRESSES IN MACHINE MEMBERS.pptx
UNIT-1--STEADY STRESSES AND VARIABLE STRESSES IN MACHINE MEMBERS.pptx
karthi keyan20 vues
UNIT-4-ENERGY STORING ELEMENTS AND ENGINE COMPONENTS.pptx par karthi keyan
UNIT-4-ENERGY STORING ELEMENTS AND ENGINE COMPONENTS.pptxUNIT-4-ENERGY STORING ELEMENTS AND ENGINE COMPONENTS.pptx
UNIT-4-ENERGY STORING ELEMENTS AND ENGINE COMPONENTS.pptx
karthi keyan26 vues
UNIT-2-SHAFTS AND COUPLINGS.pptx par karthi keyan
UNIT-2-SHAFTS AND COUPLINGS.pptxUNIT-2-SHAFTS AND COUPLINGS.pptx
UNIT-2-SHAFTS AND COUPLINGS.pptx
karthi keyan21 vues
UNIT-5-BEARINGS AND ENGINE COMPONENTS.pptx par karthi keyan
UNIT-5-BEARINGS AND ENGINE COMPONENTS.pptxUNIT-5-BEARINGS AND ENGINE COMPONENTS.pptx
UNIT-5-BEARINGS AND ENGINE COMPONENTS.pptx
karthi keyan13 vues
UNIT-3-TEMPORARY AND PERMANENT JOINTS.pptx par karthi keyan
UNIT-3-TEMPORARY AND PERMANENT JOINTS.pptxUNIT-3-TEMPORARY AND PERMANENT JOINTS.pptx
UNIT-3-TEMPORARY AND PERMANENT JOINTS.pptx
karthi keyan12 vues
UNIT-1-BASICS OF MECHANISMS.ppt par karthi keyan
UNIT-1-BASICS OF MECHANISMS.pptUNIT-1-BASICS OF MECHANISMS.ppt
UNIT-1-BASICS OF MECHANISMS.ppt
karthi keyan23 vues
UNIT-5 - FRICTION IN MACHINE ELEMENTS.pptx par karthi keyan
UNIT-5 - FRICTION IN MACHINE ELEMENTS.pptxUNIT-5 - FRICTION IN MACHINE ELEMENTS.pptx
UNIT-5 - FRICTION IN MACHINE ELEMENTS.pptx
karthi keyan21 vues
UNIT-2 -KINEMATICS OF LINKAGE MECHANISM.pptx par karthi keyan
UNIT-2 -KINEMATICS OF LINKAGE MECHANISM.pptxUNIT-2 -KINEMATICS OF LINKAGE MECHANISM.pptx
UNIT-2 -KINEMATICS OF LINKAGE MECHANISM.pptx
karthi keyan26 vues
UNIT-4 - GEARS AND GEAR TRAINS.pptx par karthi keyan
UNIT-4 - GEARS AND GEAR TRAINS.pptxUNIT-4 - GEARS AND GEAR TRAINS.pptx
UNIT-4 - GEARS AND GEAR TRAINS.pptx
karthi keyan4 vues
UNIT -3 -KINEMATICS OF CAM MECHANISMS.ppt par karthi keyan
UNIT -3 -KINEMATICS OF CAM MECHANISMS.pptUNIT -3 -KINEMATICS OF CAM MECHANISMS.ppt
UNIT -3 -KINEMATICS OF CAM MECHANISMS.ppt
karthi keyan32 vues
UNIT V ALTERNATIVE ENERGY SOURCES par karthi keyan
UNIT V ALTERNATIVE ENERGY SOURCES UNIT V ALTERNATIVE ENERGY SOURCES
UNIT V ALTERNATIVE ENERGY SOURCES
karthi keyan75 vues
UNIT IV STEERING, BRAKES AND SUSPENSION SYSTEMS par karthi keyan
UNIT IV    STEERING, BRAKES AND SUSPENSION SYSTEMS	UNIT IV    STEERING, BRAKES AND SUSPENSION SYSTEMS
UNIT IV STEERING, BRAKES AND SUSPENSION SYSTEMS
karthi keyan179 vues
UNIT III TRANSMISSION SYSTEMS par karthi keyan
UNIT III TRANSMISSION SYSTEMSUNIT III TRANSMISSION SYSTEMS
UNIT III TRANSMISSION SYSTEMS
karthi keyan64 vues
UNIT II ENGINE AUXILIARY SYSTEMS par karthi keyan
UNIT II ENGINE AUXILIARY SYSTEMS UNIT II ENGINE AUXILIARY SYSTEMS
UNIT II ENGINE AUXILIARY SYSTEMS
karthi keyan329 vues
Unit 1--VEHICLE STRUCTURE AND ENGINES par karthi keyan
Unit 1--VEHICLE STRUCTURE AND ENGINESUnit 1--VEHICLE STRUCTURE AND ENGINES
Unit 1--VEHICLE STRUCTURE AND ENGINES
karthi keyan161 vues
UCM - Unit 5 recent trends in non-traditional machining processes par karthi keyan
UCM - Unit 5   recent trends in non-traditional machining processesUCM - Unit 5   recent trends in non-traditional machining processes
UCM - Unit 5 recent trends in non-traditional machining processes
karthi keyan384 vues

Dernier

AWS A5.18 A5.18M-2021.pdf par
AWS A5.18 A5.18M-2021.pdfAWS A5.18 A5.18M-2021.pdf
AWS A5.18 A5.18M-2021.pdfThinhNguyen455948
7 vues48 diapositives
Plant Design Report-Oil Refinery.pdf par
Plant Design Report-Oil Refinery.pdfPlant Design Report-Oil Refinery.pdf
Plant Design Report-Oil Refinery.pdfSafeen Yaseen Ja'far
7 vues10 diapositives
Pitchbook Repowerlab.pdf par
Pitchbook Repowerlab.pdfPitchbook Repowerlab.pdf
Pitchbook Repowerlab.pdfVictoriaGaleano
6 vues12 diapositives
unit 1.pptx par
unit 1.pptxunit 1.pptx
unit 1.pptxrrbornarecm
5 vues53 diapositives
Design of machine elements-UNIT 3.pptx par
Design of machine elements-UNIT 3.pptxDesign of machine elements-UNIT 3.pptx
Design of machine elements-UNIT 3.pptxgopinathcreddy
37 vues31 diapositives
BCIC - Manufacturing Conclave - Technology-Driven Manufacturing for Growth par
BCIC - Manufacturing Conclave -  Technology-Driven Manufacturing for GrowthBCIC - Manufacturing Conclave -  Technology-Driven Manufacturing for Growth
BCIC - Manufacturing Conclave - Technology-Driven Manufacturing for GrowthInnomantra
15 vues4 diapositives

Dernier(20)

Design of machine elements-UNIT 3.pptx par gopinathcreddy
Design of machine elements-UNIT 3.pptxDesign of machine elements-UNIT 3.pptx
Design of machine elements-UNIT 3.pptx
gopinathcreddy37 vues
BCIC - Manufacturing Conclave - Technology-Driven Manufacturing for Growth par Innomantra
BCIC - Manufacturing Conclave -  Technology-Driven Manufacturing for GrowthBCIC - Manufacturing Conclave -  Technology-Driven Manufacturing for Growth
BCIC - Manufacturing Conclave - Technology-Driven Manufacturing for Growth
Innomantra 15 vues
REACTJS.pdf par ArthyR3
REACTJS.pdfREACTJS.pdf
REACTJS.pdf
ArthyR337 vues
Design of Structures and Foundations for Vibrating Machines, Arya-ONeill-Pinc... par csegroupvn
Design of Structures and Foundations for Vibrating Machines, Arya-ONeill-Pinc...Design of Structures and Foundations for Vibrating Machines, Arya-ONeill-Pinc...
Design of Structures and Foundations for Vibrating Machines, Arya-ONeill-Pinc...
csegroupvn8 vues
MongoDB.pdf par ArthyR3
MongoDB.pdfMongoDB.pdf
MongoDB.pdf
ArthyR349 vues
Créativité dans le design mécanique à l’aide de l’optimisation topologique par LIEGE CREATIVE
Créativité dans le design mécanique à l’aide de l’optimisation topologiqueCréativité dans le design mécanique à l’aide de l’optimisation topologique
Créativité dans le design mécanique à l’aide de l’optimisation topologique
Unlocking Research Visibility.pdf par KhatirNaima
Unlocking Research Visibility.pdfUnlocking Research Visibility.pdf
Unlocking Research Visibility.pdf
KhatirNaima10 vues
Design_Discover_Develop_Campaign.pptx par ShivanshSeth6
Design_Discover_Develop_Campaign.pptxDesign_Discover_Develop_Campaign.pptx
Design_Discover_Develop_Campaign.pptx
ShivanshSeth649 vues
Integrating Sustainable Development Goals (SDGs) in School Education par SheetalTank1
Integrating Sustainable Development Goals (SDGs) in School EducationIntegrating Sustainable Development Goals (SDGs) in School Education
Integrating Sustainable Development Goals (SDGs) in School Education
SheetalTank19 vues
ASSIGNMENTS ON FUZZY LOGIC IN TRAFFIC FLOW.pdf par AlhamduKure
ASSIGNMENTS ON FUZZY LOGIC IN TRAFFIC FLOW.pdfASSIGNMENTS ON FUZZY LOGIC IN TRAFFIC FLOW.pdf
ASSIGNMENTS ON FUZZY LOGIC IN TRAFFIC FLOW.pdf
AlhamduKure8 vues

UNIT-V FIRE SAFETY INSTALLATION

  • 2. FIRE SAFETY INSTALLATION Fire prevention and control systems - Fire alarms - Electrical alarm circuits -Smoke extraction and ventilation -Gas extinguishers - Types of detectors - Gas installation and components.
  • 3. FIRE PREVENTION AND CONTROL SYSTEMS • Stipulation of the various fire protection measures for building, to minimise the loss of life & property and effects of fire on surrounding area, are broadly based on following aspects/ philosophy.
  • 5. Extinguishing of fire •Cooling – fire extinguishing by the application of water acts by removing heat from the fuel faster than combustion generates it. •Oxygen starving (பட்டினி) – application of carbon dioxides is intended primarily to starve the fire of oxygen. Ex., putting fire blanket to cut off the oxygen supply. •Remove fuel source – a forest fire may be fought by starting smaller fires in advance of the main blaze, to deprive it of fuel. Ex., physical removing fuel •Interference of Chemical reaction – other gaseous fire suppression agents, such as halon or HFC-225, interfere with the chemical reaction itself.
  • 7. Rising Mians (a) Dry riser (RED) • Any floor is at a habitable height beyond 24 m and not exceeding 60 m above the ground level. • For a building under purpose group of the fire code, having a habitable height exceeding 10 m but not exceeding 60 m. (b)Wet riser (Yellow) • Any floor exceeding habitable height of 60 m above ground level • Wet rising main zone heights exceeding 76 m may be permitted when a listed pressure regulating device, which controls nozzle pressure under both flow and no flow conditions is installed at each outlet in house rise buildings, the following requirements are also applicable to wet risers: • The maximum zone height shall not exceed 120 m • The pressure regulating device is arranged to regulate pressure at the hose valve outlet to a running pressure not exceeding 5.5 bar • The pressure on the inlet side of the pressure regulating device does not exceed the working pressure rating of the device • All other pipe fitting and devices on the system are rated for not less than the maximum system pressure.
  • 10. Fire Safety precautions • Don't overload outlets with multiple outlet cords or plugs. If additional outlets are required, use an IS marked multi-outlet "power strip" with its own built-in circuit breaker. • Careless smoking, use of candles and incense, and unattended cooking appliances remain major causes of fatal fires in residential buildings. Use of fire crackers, hot work, and open fire is prohibited in all buildings. • Keep walkways, stairwells and exits free from obstructions at all times. • Report immediately if you observe/noticed damaged fire equipment and other fire hazards to Campus security and Fire Safety wing. • Do not open fire hydrant/hose reel water for unnecessarily use. • Do not misuse of Fire Extinguisher.
  • 12. Dry Pipe System •Above the control valves, system is charged with compressed air/nitrogen instead of water •Dry pipe valve held closed by air pressure •Upon activation of sprinkler head, air is released and water flows into the pipe work •For areas subjected to freezing temperatures.
  • 13. Pre-Action System • For areas where accidental discharge of water is unacceptable. • Pipes filled with low pressure air. • Heat/ smoke detector send signal to valve to release water to pipe work and sound alarm. • When sprinkler burst, water is discharged. • Prevent unwanted water flow when a pipe or sprinkler is accidently broken.
  • 14. (d). Deluge System • Pipes are usually empty, sprinkler are open • Detectors activate control valve to allow water to flow • Water is discharged simultaneously through all the open sprinklers in the area. •Thus, providing fast and total wetting of protected areas. •For areas that required total coverage (extra high hazard area such as aircraft hangers, power generating stations, and petrochemical facilities).
  • 15. Fire protection equipment  Automatic fire detection system  Automatic sprinkler system  Automatic release mechanism  Automatic self-closing device • Basement  Boundary  Cavity  Ceiling  Circulation space . •
  • 16. Common Fire Hazards • Kitchen fire from unattended cooking, such as frying, boiling and simmering. • Electrical systems that are overloaded, resulting in hot wiring or connections, or failed components. • Combustible storage areas with insufficient protection. • Combustibles near equipment that generates heat, flame, or sparks. • Candles and other often flames • Smoking (cigarettes, cigars, pipes, lighters, etc.). • Equipment that generates heat and utilizes combustible materials. • Flammable liquids and aerosols. • Flammable solvent (and rags soaked with solvent) placed in enclosed trash cans. • Fireplace chimneys not properly or regularly cleaned. • Cooking appliances-stoves, ovens. • Heating appliances-fireplaces, wood burning stoves, furnaces, boilers, portable heaters. • Household appliances-clothes dryers, curling irons, hair dryers, refrigerators, freezers. • Chimneys that concentrate creosote. • Electrical wiring in poor condition. • Leaking Batteries. • Personal ignition sources-matches, lighters • Electronic and electrical equipment • Exterior cooking equipment-barbecue
  • 17. FIRE ALARM Fire alarm systems generally use visual and audio signalization to warn the occupants of the building. Some fire alarm systems may also disable elevators, which under most circumstances, are unsafe to use during a fire.
  • 18. Fire Alarm Control Panels (a) Function of control panel • It is the brain of the fire detection and alarm system • Responsible for monitoring the various alarm input devices such as manual and automatic detection components • Activates alarm output devices such as horns bells warning lights emergency telephone diallers and building controls (b) Design • Control panels may range from simple units with a single input and output zone, to complex computer driven systems that monitor several buildings over an entire campus.
  • 19. Types of arrangements • Conventional (Older technology) • Addressable (Newer technology)
  • 20. Conventional Systems (a) Conventional • Point wired – have a dedicated writing back to the signal processing • One or more circuits are routed through the protected space of the building. • Along each circuit, one or more detection devices are placed (b) Factors for selection & placement • Depends on need for automatic or manual initiation • Ambient temperature & environment conditions • Anticipated type of fire • Desired speed of response (c) Fire occurrence situation • One or more detectors will operate • Action will close the circuit which the fire control panel recognizes as an emergency condition • Panel will then activate one or more signalling alarm circuits to sound building alarm and summon emergency help • Panel may also send the signal to another alarm panel so that it can be monitored from a remote point.
  • 21. (d) Fault monitoring • To help ensure that the system is functioning properly these systems monitor the condition of each circuit by sending a small current through the wires. • Should a fault occur, such as due to a wiring break this current cannot proceed and is registered as a trouble condition • The indication is a need for service somewhere along the respective circuit
  • 22. Addressable systems (a) Addressable systems • State of the art in fire detection and alarm technology • Monitors and controls the capabilities of each alarm initiating and signalling device through microprocessor and systems software • Major differences involve the way in which each device is monitored • Each initiating device (automatic detector, manual station, sprinkler water flow switches) is given a specific identification or address • This address is correspondingly programmed into the control panels memory with information such as the type of device its location and specific response details such as which alarm devices are to be activated. (b) Operations •The control panels microprocessors send a constant interrogation signal over each circuit •Each initiating devices is contracted to inquires its status (normal or emergency) •This activates monitoring process occurs in rapid succession providing system updates every 5 to 10 seconds •Therefore, instead of merely showing a fault along a wire they will indicate the location of the problem •This permits faster diagnosis of the trouble and allows a quicker repair and return to normal.
  • 24. Fire Alarm Control Panels (a) Function of control panel • Control panel is the brain of the fire detection and alarm system • Responsible for monitoring the various alarm input devices such as manual and automatic detection components • Activates alarm output devices such as horns bells warning lights emergency telephone diallers and building controls (b) Design • Control panels may range from simple units with a single input and output zone, to complex computer driven systems that monitor several buildings over an entire campus.
  • 25. FIRE PREVENTION IN VENTILATING SYSTEMS
  • 30. SMOKE EXTRACTOR AND FIRE VENTILATOR • Number and area of ventilators - estimates are based on providing a smoke- free layer about 3 m above floor level.
  • 33. GAS EXTINGUISHING SYSTEMS – HALON & HALON SUBSTITUTES
  • 35. PORTABLE FIRE EXTINGUISHERS (ACID BASED) • A portable fire extinguisher must contain the type of fire extinguishing agent suitable for the fire it is required to extinguish. It must also be clearly identifiable by colour coding for its intended purpose.
  • 36. Portable fire Extinguishers Extinguishing agent Extinguisher colour Application Water Red Carbonaceous fires, paper, wood, etc., Foam Red with cream band Ditto and flammable liquids, oils, fats, etc., Carbon dioxide Red with black band Electrical fires a flammable liquid Dry chemicals Red with blue band All fires
  • 38. Striking type soda – acid water portable fire extinguisher
  • 39. Inversion type soda-and acid water portable fire extinguisher
  • 40. PORTABLE FIRE EXTINGUISHERS (CHEMICAL BASED)
  • 41. TYPES OF DETECTORS Ionisation smoke detector
  • 43. Fusible Alloy Heat Detector
  • 44. Bi-metal Coil Heat Detector
  • 45. LIGHT OBSCURING AND LASER BEAM DETECTORS Light Obscuring Detector
  • 46. LIGHT OBSCURING AND LASER BEAM DETECTORS Laser Beam Detector
  • 47. Components of an Infra-red detector
  • 48. Infra-red Detector for large and small areas