SlideShare a Scribd company logo
1 of 46
Download to read offline
891 Switchboard vs. 1558 Switchgear
“The Rest of the Story II-
While you where sleeping”
2
What happened since our last
discussion?????
• Selective coordination went on
steroids
• Arc Flash, Arc Resistant, and Arc
Fault overtook the NEC
• New UL ratings for everything and
nothing at the same time
• Mr. LEEDs is our new boss
3
TVSS SPD – Another UL? – 3rd
addition
The major differences are:
Change in terminology from Transient Voltage Surge
Suppressors to Surge Protective Devices
UL 1449 3rd Edition is now an American National
Standard (ANSI)
Addition of Nominal Discharge Current to ratings and
markings
Duty cycle test at nominal discharge current
Measured limiting voltage now performed at 6 kV/3 kA
4
TVSS 250 kA vs. 2 Billion kA
Based on available research, IEEE recommends
using the 20 kV, 10 kA combination wave as the
representative test for induced lightning surges
at service entrance locations. Above this amount,
the voltage will exceed BIL ratings causing
arcing in the conductors or distribution system.
In summary, low voltage wiring (<600V) is not
capable of conducting the lightning stroke
currents.
5
UL Retrofits
6
Bolted Fault Arcing Fault
Systems must be designed However, the majority of faults
for worst case conditions. will be arcing type.
Line-to-Line-to-Line Fault
7
What Can We Say About Arcing
Ground Fault Current Values?
8
Fault Reduction
9
“Arc Mitigation” – What about the
Standards?
1. UL recognizes switchgear tested in accordance with IEEE C37.20.7 as Arc Resistant
Switchgear.
2. No ANSI or UL standards cover the testing or manufacturing of arc sensing relays or
mitigation components.
10
ANSI C37.20.7
Type 1 - Arc resistant at front only
Type 2 - Arc resistant around the perimeter of the switchgear line-up
Appendix A
Type 1B or 2B - Arc resistant to type 1 or 2 with control door open.
Type 1C or 2C - Arc resistant to type 1or 2 plus between all adjacent
compartments (Meets all requirements of type and suffix B in addition to
the requirements of suffix C).
Type 1D - specifies Type 1 and applicable accessible sides
ARC Resistant Switchgear
11
Arc Resistant type 2C
You must have arc resistance
from compartment 7 to the
following compartments
within this vertical section:
4,6,8
Additionally you must have
arc resistance from this
compartment 7 to the
compartment 7 in the vertical
section to the right and left of
vertical structure shown.
In order to validate this you
must initiate an arcing current
in compartment 7, and have
burn indicators placed in
each of these adjacent
compartments. You must
pass all arc resistant test
criterion
4
1
2
3
5
6
8
7
=Arcing fault in
compartment 7
12
Remote Operation Solutions
13
Remote Operator
(In Operation)
(1)
(2)
(3)
(4)
14
Mr. LEEDs; Good, Better, Best
15
Electronic vs. Thermal magnetic
Top 3 reasons
16
SD=
0.5S
SD=
0.3S
SD=
0.3S
SD=
0.3S
M1
F1 F2 F3X
35kA fault current
Without ZSI = 0.5 S:
43.7 Cal/cm2
Greater than Cat. 4 PPE
DANGER!
With ZSI = 0.08 S:
7.0 Cal/cm2
FR Shirt & Pants
Cat. 2 PPE
Safety (Wired for)
Solution #1 – ZSI
Short time
GF
17
• ARMs features in white area of trip unit to separate
them from normal trip unit settings.
• Blue LED “Maintenance Mode”
• 2 Position Selector Switch:
• ON = Local ON
• O/I = OFF or External Control
• 5 Position Arc Flash Reduction Setting:
• From R5 (Max) …. To R1 (Min) Reduction
• Remote Indication:
• Power Relay Module Maintenance Mode Contact
• Communications
• Remote Enable:
• Switchgear Mounted Logic Level Selector Switch
• Switchgear Mounted Logic Level Ice Cube Relay
with Remote Mounted Control Switch
• Via Communications: Using Infa-Red Mint &
PDA, PowerNet, Modbus mMINT, & BIM
• Lock-out/Tag-out
5 levels of protection allow the operator to pre-
select the maximum arc flash reduction level
possible to avoid nuisance tripping during
maintenance operations
Safety
Solution #2 - ARMS
18
Switchgear and Switchboard
UL891=UL1558
NEMA vs. ANSI
And 3 (of many) reasons why
20
UL1558 Switchgear vs. UL891 Switchboard
Isolation is beautiful!
21
UL1558 Switchgear vs. UL891 Switchboard
Isolation is beautiful!
22
Comparison of Standards
Endurance UL 1066 and UL 489 (continued)
* Maintenance of contacts is allowed under UL 1066
M-13
Required Nos. of Operations *
Electrical Mechanical
- - - -
- - - -
2,800 9,700
2,800 9,700
- - - -
800 3,200
- - - -
250 400
Pick-up and Time
Elements Tested:
• Long Time Delay
• Instantaneous
• Short Time Delay
1320 V
Must be able to carry Current
Provides for inspection,
cleaning, adjusting, lubricating
and tightening
O at 635V, 3-phase
FRAME SIZE
100 A
150 A and 225 A
600 A
800 A
801 A - 2500 A
1600 A or 2000 A
2501 A - 6000 A
3000 A, 4000 A or 5000 A
Short Circuit Current Test
Post-Test Trip Device Calibration
Post-Test AC Dielectric Withstand
V
Post-Test Condition of Circuit Bkr.
Maintenance
1240 - 2200 V
May not be able to CLOSE again
Internal servicing not permitted
O (2 - 60 min) - CO
One Pick-up and Time
200% Trip out at 25ºC
Required Nos. of Operations *
Electrical Mechanical
6,000 4,000
4,000 4,000
1,000 5,000
500 3,000
500 2,000
- - - -
400 1,100
400 1,100
UL 1066
Sequence III
UL 489
Sequence Y
Test Requirements
Switchgear and Switchboard
Number 1 difference
Short time
rating
NEMA vs. ANSI
24
Molded Case Circuit Breakers
• Tested in accordance with UL489
• Open Air Test - Rated @ 80%
• Over Toggle Mechanism
• Sealed Case - Not Maintainable
• Applied in Switchboards/Panelboards
Insulated Case Circuit Breakers
• Tested in accordance with UL489
• Open Air Test - Rated @ 80% or 100%
• 2-Step Stored Energy Mechanism
• Sealed Case - Not Fully Maintainable
• Applied As Mains in Switchboards/MCC’s
Power Circuit Breakers
• Tested in accordance with ANSI C37
• Tested in the Enclosure - Rated @ 100%
• 2-Step Stored Energy Mechanism
• Open Access - Fully Maintainable
• Applied in Metal-Enclosed Drawout Swgr.
UL489 versus ANSI C37
25
Selective Coordination
27
True or False
100% Selectively Coordinating a system makes it
more RELIABLE.
TRUE FALSE
28
True or False
100% Selectively Coordinating a system makes it
SAFER.
TRUE FALSE
29
What devices are required to
Selectively Coordinate?U TIL ITY A
M A I N A
M SG -A
M S G -TI E
U TI LITY B
M A IN B
M S G -B
A TS -EQ N O RM A T S-C R N O RM A T S- L S N O R MC H IL LE R F D R
G EN # 1 M A I N
G E N S W G R
A T S- EQ E M E R A TS -C R EM E R A TS -L S E M E R
G E N # 1
G E N # 2 M A I N
G E N # 2
EN
A T S- EQ
EN
A TS -C R
EN
A TS -L S
C B L-A T S EQ N C BL -A T S C R N C BL -A TS L S N C BL -0 00 5 C B L-0 0 06 C BL- 00 0 7
C B L -E Q 4 80 V P N L C BL -C R 4 8 0V PN L C BL -LS 4 80 V P N L
E Q 4 80 V P N L
EQ X F M R P R I
C B L -E Q X F M R P R I
S
P
E Q X F M R
C B L -E Q 2 08 V P N L
EQ 2 0 8V P N L M A IN
E Q 2 08 V P N L
EQ 2 0 8V B R A N CH
C R 4 8 0V PN L
C R X FM R P R I
C BL -C R X F M R P R I
S
P
C R X FM R
C BL -C R 2 0 8V PN L
C R 20 8 V P N L M AIN
C R 2 0 8V PN L
C R 20 8 V BR A N C H
L S 4 80 V P N L
L S X FM R P R I
C BL -LS X F M R PR I
S
P
L S X F M R
C BL -LS 2 08 V P N L
L S 2 0 8V PN L M A IN
L S 2 08 V P N L
L S 2 0 8V BR A N C H
C H ILL E R
C BL- C H ILLE R
D IS T R P N L FD R
C BL- D IST R P N L
D IS T R P N L
4 80 V LT G P N L F D R
C BL - 48 0V LT G P N L
48 0 V LT G P N L
LT G BR A N C H
4 80 V LR G S T
1. Load side of any
Emergency System ATS
2. Emergency
source to the
line side ATS
3. Normal
source to the
line side of the
ATS???
30
U TIL ITY A
M A I N A
M SG -A
M S G -TI E
U TI LITY B
M A IN B
M S G -B
A TS -EQ N O RM A T S-C R N O RM A T S- L S N O R MC H IL LE R F D R
G EN # 1 M A I N
G E N S W G R
A T S- EQ E M E R A TS -C R EM E R A TS -L S E M E R
G E N # 1
G E N # 2 M A I N
G E N # 2
EN
A T S- EQ
EN
A TS -C R
EN
A TS -L S
C B L-A T S EQ N C BL -A T S C R N C BL -A TS L S N C BL -0 00 5 C B L-0 0 06 C BL- 00 0 7
C B L -E Q 4 80 V P N L C BL -C R 4 8 0V PN L C BL -LS 4 80 V P N L
E Q 4 80 V P N L
EQ X F M R P R I
C B L -E Q X F M R P R I
S
P
E Q X F M R
C B L -E Q 2 08 V P N L
EQ 2 0 8V P N L M A IN
E Q 2 08 V P N L
EQ 2 0 8V B R A N CH
C R 4 8 0V PN L
C R X FM R P R I
C BL -C R X F M R P R I
S
P
C R X FM R
C BL -C R 2 0 8V PN L
C R 20 8 V P N L M AIN
C R 2 0 8V PN L
C R 20 8 V BR A N C H
L S 4 80 V P N L
L S X FM R P R I
C BL -LS X F M R PR I
S
P
L S X F M R
C BL -LS 2 08 V P N L
L S 2 0 8V PN L M A IN
L S 2 08 V P N L
L S 2 0 8V BR A N C H
C H ILL E R
C BL- C H ILLE R
D IS T R P N L FD R
C BL- D IST R P N L
D IS T R P N L
4 80 V LT G P N L F D R
C BL - 48 0V LT G P N L
48 0 V LT G P N L
LT G BR A N C H
4 80 V LR G S T
What devices are required to
Selectively Coordinate?
3. Normal
source to the
line side of the
ATS???
Is this Zone important
for continuity of service?
This bus sees an unnecessary
outage. ATS transfers into a fault.
Gen feeds a fault. Normal ATS
breaker must be reset for ATS to
transfer back
31
2010 CEC
32
Why .1 seconds?
“Operating records show that the majority of electric faults originate
as phase-to-ground failures.” IEEE std. 141-1993, page 187. (Red
book)
“It should be recognized, however, that actual short circuits often
involve arcing, and variable arc impedance can reduce low-voltage
short-circuit current magnitudes appreciably.” IEEE std. 141-1993,
page 113. (Red book)
Looking at TCC’s, fault currents that cause operation of OCPD’s in
the sub 6 cycle range have been found to be rare occurrences for
systems that have already been safely energized.
33
Selective Coordination
Discussion – Protective Devices
34
35
Ground Faults on low-voltage
systems
“Arcing faults are the more destructive type of
fault because the arc limits the fault current.”
“Selectivity can be typically achieved only by
including more than one level of ground fault
relays.”
IEEE std. 142-2001, page 626. (Buff book)
36
How GFP Effects Coordination
From NEC 517-17: (a) Feeders“ Where GFP is
provided for operation of the service
disconnecting means ----an additional step of
GFP shall be provided in the next level of feeder
disconnecting means downstream toward the
load.”
This is a healthcare requirement.
37
More from NEC 517-17
(b) Selectivity. “ GFP for operation of the service feeder
disconnecting means shall be fully selective such that the
feeder device and not the service device shall open on
ground faults on the load side of the feeder device. A six
cycle minimum separation between the service and
feeder GF tripping bands shall be provided.”
Why 6 cycles? (OCPD opening time).
Note: only GFP is referenced here.
38
Specific Application Circuit Breakers
Motor Starting
Motor Circuit Protectors
Motor Starting Considerations
National Electrical Code 430-52
Maximum instantaneous setting 13x FLA
First peak may be 17-18x FLA or higher
on energy efficient motors
HMCP size 0-4 transient inrush trip suppressor
- Sustain high inrush for first cycle
- Provide sensitive, adjustable short-circuit protection
Specific Application Circuit Breakers
HMCP
Motor Circuit
Protectors
Adjustable Trip Settings
Multiples of continuous
current rating
Field adjustable
Close coordination
with motor
characteristics
41
42
Thermal Magnetic
Overload Protection (Thermal)
Short-Circuit Protection (Magnetic)
43
Know your fault current!
44
Bolted Fault Arcing Fault
Systems must be designed However, the majority of faults
for worst case conditions. will be arcing type.
Line-to-Line-to-Line Fault
45
Why .1 seconds?
“Operating records show that the majority of electric faults originate
as phase-to-ground failures.” IEEE std. 141-1993, page 187. (Red
book)
“It should be recognized, however, that actual short circuits often
involve arcing, and variable arc impedance can reduce low-voltage
short-circuit current magnitudes appreciably.” IEEE std. 141-1993,
page 113. (Red book)
Looking at TCC’s, fault currents that cause operation of OCPD’s in
the sub 6 cycle range have been found to be rare occurrences for
systems that have already been safely energized.
46
Does .1 Seconds make Sense -
Types and Frequencies of Faults
“Operating records show that the majority of electric
faults originate as phase-to-ground failures.” IEEE std.
141-1993, page 187. (Red book)
“It should be recognized, however, that actual short
circuits often involve arcing, and variable arc impedance
can reduce low-voltage short-circuit current magnitudes
appreciably.” IEEE std. 141-1993, page 113. (Red book)

More Related Content

What's hot

Testing and Condition Monitoring of Substation Equipments
Testing and Condition Monitoring of Substation EquipmentsTesting and Condition Monitoring of Substation Equipments
Testing and Condition Monitoring of Substation EquipmentsSumeet Ratnawat
 
220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance220 KV Substation Operation & Maintenance
220 KV Substation Operation & MaintenanceHimansu Pradhan
 
Generator protection calculations settings
Generator protection calculations settingsGenerator protection calculations settings
Generator protection calculations settingsmichaeljmack
 
Testing,maintenance&protection
Testing,maintenance&protectionTesting,maintenance&protection
Testing,maintenance&protectionRakesh Joshi
 
15 years of experience stator ground fault protection
15 years of experience stator ground fault protection15 years of experience stator ground fault protection
15 years of experience stator ground fault protectionmichaeljmack
 
High voltage testing of electrical transformer
High voltage testing of electrical transformerHigh voltage testing of electrical transformer
High voltage testing of electrical transformerPraveenKumar5880
 
Transformer testing
Transformer testingTransformer testing
Transformer testingajayknows
 
400/220 kV SCADA controlled gis based TRANSMISSION SUBSTATION
400/220 kV SCADA controlled gis based TRANSMISSION SUBSTATION400/220 kV SCADA controlled gis based TRANSMISSION SUBSTATION
400/220 kV SCADA controlled gis based TRANSMISSION SUBSTATIONPower System Operation
 
Cable sizing to withstand short-circuit current - Example
Cable sizing to withstand short-circuit current - ExampleCable sizing to withstand short-circuit current - Example
Cable sizing to withstand short-circuit current - ExampleLeonardo ENERGY
 
Power System Protection course - Part I
Power System Protection course - Part IPower System Protection course - Part I
Power System Protection course - Part ISlides Hub
 
04 ret670 test report
04 ret670 test report04 ret670 test report
04 ret670 test reportniranjan131
 
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)Power System Operation
 
Power transformer testing and commissioning guidelines r
Power transformer testing and commissioning guidelines rPower transformer testing and commissioning guidelines r
Power transformer testing and commissioning guidelines rAshish Patel
 
Transformer Differential Protection Setting Calculations
Transformer Differential Protection Setting CalculationsTransformer Differential Protection Setting Calculations
Transformer Differential Protection Setting CalculationsPower System Operation
 
Switchgear - complete guide
Switchgear - complete guideSwitchgear - complete guide
Switchgear - complete guideSlides Hub
 

What's hot (20)

Testing and Condition Monitoring of Substation Equipments
Testing and Condition Monitoring of Substation EquipmentsTesting and Condition Monitoring of Substation Equipments
Testing and Condition Monitoring of Substation Equipments
 
Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentation
 
1.substation layouts
1.substation  layouts1.substation  layouts
1.substation layouts
 
220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance
 
Testing of Transformer (AREVA)
Testing of Transformer (AREVA)Testing of Transformer (AREVA)
Testing of Transformer (AREVA)
 
Generator protection calculations settings
Generator protection calculations settingsGenerator protection calculations settings
Generator protection calculations settings
 
BUSBAR PROTECTION
BUSBAR PROTECTIONBUSBAR PROTECTION
BUSBAR PROTECTION
 
Testing,maintenance&protection
Testing,maintenance&protectionTesting,maintenance&protection
Testing,maintenance&protection
 
15 years of experience stator ground fault protection
15 years of experience stator ground fault protection15 years of experience stator ground fault protection
15 years of experience stator ground fault protection
 
High voltage testing of electrical transformer
High voltage testing of electrical transformerHigh voltage testing of electrical transformer
High voltage testing of electrical transformer
 
Transformer testing
Transformer testingTransformer testing
Transformer testing
 
400/220 kV SCADA controlled gis based TRANSMISSION SUBSTATION
400/220 kV SCADA controlled gis based TRANSMISSION SUBSTATION400/220 kV SCADA controlled gis based TRANSMISSION SUBSTATION
400/220 kV SCADA controlled gis based TRANSMISSION SUBSTATION
 
Cable sizing to withstand short-circuit current - Example
Cable sizing to withstand short-circuit current - ExampleCable sizing to withstand short-circuit current - Example
Cable sizing to withstand short-circuit current - Example
 
What's short circuit level
What's short circuit levelWhat's short circuit level
What's short circuit level
 
Power System Protection course - Part I
Power System Protection course - Part IPower System Protection course - Part I
Power System Protection course - Part I
 
04 ret670 test report
04 ret670 test report04 ret670 test report
04 ret670 test report
 
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
 
Power transformer testing and commissioning guidelines r
Power transformer testing and commissioning guidelines rPower transformer testing and commissioning guidelines r
Power transformer testing and commissioning guidelines r
 
Transformer Differential Protection Setting Calculations
Transformer Differential Protection Setting CalculationsTransformer Differential Protection Setting Calculations
Transformer Differential Protection Setting Calculations
 
Switchgear - complete guide
Switchgear - complete guideSwitchgear - complete guide
Switchgear - complete guide
 

Similar to 891 Switchboard vs. 1558 Switchgear

Similar to 891 Switchboard vs. 1558 Switchgear (20)

Electrical
ElectricalElectrical
Electrical
 
PLANO ELECTRICO CAT GENSET 3500B Renr98450001
PLANO ELECTRICO CAT GENSET 3500B Renr98450001PLANO ELECTRICO CAT GENSET 3500B Renr98450001
PLANO ELECTRICO CAT GENSET 3500B Renr98450001
 
Wiring_Diagram_Book.pdf
Wiring_Diagram_Book.pdfWiring_Diagram_Book.pdf
Wiring_Diagram_Book.pdf
 
electro-pneumatics.pptx
electro-pneumatics.pptxelectro-pneumatics.pptx
electro-pneumatics.pptx
 
10 - Ac Power Regulators & Control Power Transformers - Fuji Electric
10 - Ac Power Regulators & Control Power Transformers - Fuji Electric10 - Ac Power Regulators & Control Power Transformers - Fuji Electric
10 - Ac Power Regulators & Control Power Transformers - Fuji Electric
 
INTERFACING.ppt
INTERFACING.pptINTERFACING.ppt
INTERFACING.ppt
 
Novatek Presentation
Novatek PresentationNovatek Presentation
Novatek Presentation
 
Solid state relay_catalog
Solid state relay_catalogSolid state relay_catalog
Solid state relay_catalog
 
Control & Isolation 5
Control & Isolation 5Control & Isolation 5
Control & Isolation 5
 
sharp_14mn10_ch_sn-000.pptx
sharp_14mn10_ch_sn-000.pptxsharp_14mn10_ch_sn-000.pptx
sharp_14mn10_ch_sn-000.pptx
 
330cl
 330cl 330cl
330cl
 
Training slides
Training slidesTraining slides
Training slides
 
Bender rc48 c
Bender rc48 cBender rc48 c
Bender rc48 c
 
Lm 741 datasheet
Lm 741 datasheetLm 741 datasheet
Lm 741 datasheet
 
Dec2001 contactor
Dec2001   contactorDec2001   contactor
Dec2001 contactor
 
01 - Contactor - Fuji Electric
 01 - Contactor - Fuji Electric 01 - Contactor - Fuji Electric
01 - Contactor - Fuji Electric
 
Probador de-flybacks
Probador de-flybacksProbador de-flybacks
Probador de-flybacks
 
Electrónica: Probador de LOPT/FBT Flyback
Electrónica: Probador de LOPT/FBT FlybackElectrónica: Probador de LOPT/FBT Flyback
Electrónica: Probador de LOPT/FBT Flyback
 
Conductive Level Switches From Nivelco
Conductive Level Switches From NivelcoConductive Level Switches From Nivelco
Conductive Level Switches From Nivelco
 
Cdvr service manual renr7941-00 _ sis - caterpillar
Cdvr   service manual   renr7941-00 _ sis - caterpillarCdvr   service manual   renr7941-00 _ sis - caterpillar
Cdvr service manual renr7941-00 _ sis - caterpillar
 

More from michaeljmack

Auburn, NY - 200 Years of History 1793-1993
Auburn, NY - 200 Years of History  1793-1993Auburn, NY - 200 Years of History  1793-1993
Auburn, NY - 200 Years of History 1793-1993michaeljmack
 
Auburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 YearbookAuburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 Yearbookmichaeljmack
 
Auburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 YearbookAuburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 Yearbookmichaeljmack
 
Diesel Particulate Filters Control Systems
Diesel Particulate Filters Control SystemsDiesel Particulate Filters Control Systems
Diesel Particulate Filters Control Systemsmichaeljmack
 
Understanding Arc Flash
Understanding Arc FlashUnderstanding Arc Flash
Understanding Arc Flashmichaeljmack
 
Siemens MV GIS Switchgear
Siemens MV GIS SwitchgearSiemens MV GIS Switchgear
Siemens MV GIS Switchgearmichaeljmack
 
Fundamentals of transformer inrush
Fundamentals of transformer inrushFundamentals of transformer inrush
Fundamentals of transformer inrushmichaeljmack
 
Building information modeling
Building information modelingBuilding information modeling
Building information modelingmichaeljmack
 
Emergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby SystemsEmergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby Systemsmichaeljmack
 
Lighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit SpacesLighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit Spacesmichaeljmack
 
COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708michaeljmack
 
Seismic Compliance of Electrical Distribution
Seismic Compliance of Electrical DistributionSeismic Compliance of Electrical Distribution
Seismic Compliance of Electrical Distributionmichaeljmack
 
Generator Set Transient Performance
Generator Set Transient PerformanceGenerator Set Transient Performance
Generator Set Transient Performancemichaeljmack
 
Modeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital SimulatorModeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital Simulatormichaeljmack
 
Facts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind PlantsFacts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind Plantsmichaeljmack
 
Power Plant Horror Stories
Power Plant Horror StoriesPower Plant Horror Stories
Power Plant Horror Storiesmichaeljmack
 
Blackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load SheddingBlackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load Sheddingmichaeljmack
 
Transformer Fundamentals
Transformer FundamentalsTransformer Fundamentals
Transformer Fundamentalsmichaeljmack
 

More from michaeljmack (20)

Auburn, NY - 200 Years of History 1793-1993
Auburn, NY - 200 Years of History  1793-1993Auburn, NY - 200 Years of History  1793-1993
Auburn, NY - 200 Years of History 1793-1993
 
Auburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 YearbookAuburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 Yearbook
 
Auburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 YearbookAuburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 Yearbook
 
Surge Protection
Surge ProtectionSurge Protection
Surge Protection
 
Diesel Particulate Filters Control Systems
Diesel Particulate Filters Control SystemsDiesel Particulate Filters Control Systems
Diesel Particulate Filters Control Systems
 
Understanding Arc Flash
Understanding Arc FlashUnderstanding Arc Flash
Understanding Arc Flash
 
Siemens MV GIS Switchgear
Siemens MV GIS SwitchgearSiemens MV GIS Switchgear
Siemens MV GIS Switchgear
 
Fundamentals of transformer inrush
Fundamentals of transformer inrushFundamentals of transformer inrush
Fundamentals of transformer inrush
 
Building information modeling
Building information modelingBuilding information modeling
Building information modeling
 
Emergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby SystemsEmergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby Systems
 
Lighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit SpacesLighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit Spaces
 
COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708
 
Seismic Compliance of Electrical Distribution
Seismic Compliance of Electrical DistributionSeismic Compliance of Electrical Distribution
Seismic Compliance of Electrical Distribution
 
Generator Set Transient Performance
Generator Set Transient PerformanceGenerator Set Transient Performance
Generator Set Transient Performance
 
Modeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital SimulatorModeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital Simulator
 
Facts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind PlantsFacts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind Plants
 
Power Plant Horror Stories
Power Plant Horror StoriesPower Plant Horror Stories
Power Plant Horror Stories
 
Blackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load SheddingBlackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load Shedding
 
Transformer Fundamentals
Transformer FundamentalsTransformer Fundamentals
Transformer Fundamentals
 
Arc Flash
Arc FlashArc Flash
Arc Flash
 

Recently uploaded

Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoão Esperancinha
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Dr.Costas Sachpazis
 
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxthe ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxhumanexperienceaaa
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSSIVASHANKAR N
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
 
(TARA) Talegaon Dabhade Call Girls Just Call 7001035870 [ Cash on Delivery ] ...
(TARA) Talegaon Dabhade Call Girls Just Call 7001035870 [ Cash on Delivery ] ...(TARA) Talegaon Dabhade Call Girls Just Call 7001035870 [ Cash on Delivery ] ...
(TARA) Talegaon Dabhade Call Girls Just Call 7001035870 [ Cash on Delivery ] ...ranjana rawat
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).pptssuser5c9d4b1
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝soniya singh
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxupamatechverse
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxupamatechverse
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 

Recently uploaded (20)

Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxthe ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 
(TARA) Talegaon Dabhade Call Girls Just Call 7001035870 [ Cash on Delivery ] ...
(TARA) Talegaon Dabhade Call Girls Just Call 7001035870 [ Cash on Delivery ] ...(TARA) Talegaon Dabhade Call Girls Just Call 7001035870 [ Cash on Delivery ] ...
(TARA) Talegaon Dabhade Call Girls Just Call 7001035870 [ Cash on Delivery ] ...
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 

891 Switchboard vs. 1558 Switchgear

  • 1. 891 Switchboard vs. 1558 Switchgear “The Rest of the Story II- While you where sleeping”
  • 2. 2 What happened since our last discussion????? • Selective coordination went on steroids • Arc Flash, Arc Resistant, and Arc Fault overtook the NEC • New UL ratings for everything and nothing at the same time • Mr. LEEDs is our new boss
  • 3. 3 TVSS SPD – Another UL? – 3rd addition The major differences are: Change in terminology from Transient Voltage Surge Suppressors to Surge Protective Devices UL 1449 3rd Edition is now an American National Standard (ANSI) Addition of Nominal Discharge Current to ratings and markings Duty cycle test at nominal discharge current Measured limiting voltage now performed at 6 kV/3 kA
  • 4. 4 TVSS 250 kA vs. 2 Billion kA Based on available research, IEEE recommends using the 20 kV, 10 kA combination wave as the representative test for induced lightning surges at service entrance locations. Above this amount, the voltage will exceed BIL ratings causing arcing in the conductors or distribution system. In summary, low voltage wiring (<600V) is not capable of conducting the lightning stroke currents.
  • 6. 6 Bolted Fault Arcing Fault Systems must be designed However, the majority of faults for worst case conditions. will be arcing type. Line-to-Line-to-Line Fault
  • 7. 7 What Can We Say About Arcing Ground Fault Current Values?
  • 9. 9 “Arc Mitigation” – What about the Standards? 1. UL recognizes switchgear tested in accordance with IEEE C37.20.7 as Arc Resistant Switchgear. 2. No ANSI or UL standards cover the testing or manufacturing of arc sensing relays or mitigation components.
  • 10. 10 ANSI C37.20.7 Type 1 - Arc resistant at front only Type 2 - Arc resistant around the perimeter of the switchgear line-up Appendix A Type 1B or 2B - Arc resistant to type 1 or 2 with control door open. Type 1C or 2C - Arc resistant to type 1or 2 plus between all adjacent compartments (Meets all requirements of type and suffix B in addition to the requirements of suffix C). Type 1D - specifies Type 1 and applicable accessible sides ARC Resistant Switchgear
  • 11. 11 Arc Resistant type 2C You must have arc resistance from compartment 7 to the following compartments within this vertical section: 4,6,8 Additionally you must have arc resistance from this compartment 7 to the compartment 7 in the vertical section to the right and left of vertical structure shown. In order to validate this you must initiate an arcing current in compartment 7, and have burn indicators placed in each of these adjacent compartments. You must pass all arc resistant test criterion 4 1 2 3 5 6 8 7 =Arcing fault in compartment 7
  • 14. 14 Mr. LEEDs; Good, Better, Best
  • 15. 15 Electronic vs. Thermal magnetic Top 3 reasons
  • 16. 16 SD= 0.5S SD= 0.3S SD= 0.3S SD= 0.3S M1 F1 F2 F3X 35kA fault current Without ZSI = 0.5 S: 43.7 Cal/cm2 Greater than Cat. 4 PPE DANGER! With ZSI = 0.08 S: 7.0 Cal/cm2 FR Shirt & Pants Cat. 2 PPE Safety (Wired for) Solution #1 – ZSI Short time GF
  • 17. 17 • ARMs features in white area of trip unit to separate them from normal trip unit settings. • Blue LED “Maintenance Mode” • 2 Position Selector Switch: • ON = Local ON • O/I = OFF or External Control • 5 Position Arc Flash Reduction Setting: • From R5 (Max) …. To R1 (Min) Reduction • Remote Indication: • Power Relay Module Maintenance Mode Contact • Communications • Remote Enable: • Switchgear Mounted Logic Level Selector Switch • Switchgear Mounted Logic Level Ice Cube Relay with Remote Mounted Control Switch • Via Communications: Using Infa-Red Mint & PDA, PowerNet, Modbus mMINT, & BIM • Lock-out/Tag-out 5 levels of protection allow the operator to pre- select the maximum arc flash reduction level possible to avoid nuisance tripping during maintenance operations Safety Solution #2 - ARMS
  • 18. 18
  • 19. Switchgear and Switchboard UL891=UL1558 NEMA vs. ANSI And 3 (of many) reasons why
  • 20. 20 UL1558 Switchgear vs. UL891 Switchboard Isolation is beautiful!
  • 21. 21 UL1558 Switchgear vs. UL891 Switchboard Isolation is beautiful!
  • 22. 22 Comparison of Standards Endurance UL 1066 and UL 489 (continued) * Maintenance of contacts is allowed under UL 1066 M-13 Required Nos. of Operations * Electrical Mechanical - - - - - - - - 2,800 9,700 2,800 9,700 - - - - 800 3,200 - - - - 250 400 Pick-up and Time Elements Tested: • Long Time Delay • Instantaneous • Short Time Delay 1320 V Must be able to carry Current Provides for inspection, cleaning, adjusting, lubricating and tightening O at 635V, 3-phase FRAME SIZE 100 A 150 A and 225 A 600 A 800 A 801 A - 2500 A 1600 A or 2000 A 2501 A - 6000 A 3000 A, 4000 A or 5000 A Short Circuit Current Test Post-Test Trip Device Calibration Post-Test AC Dielectric Withstand V Post-Test Condition of Circuit Bkr. Maintenance 1240 - 2200 V May not be able to CLOSE again Internal servicing not permitted O (2 - 60 min) - CO One Pick-up and Time 200% Trip out at 25ºC Required Nos. of Operations * Electrical Mechanical 6,000 4,000 4,000 4,000 1,000 5,000 500 3,000 500 2,000 - - - - 400 1,100 400 1,100 UL 1066 Sequence III UL 489 Sequence Y Test Requirements
  • 23. Switchgear and Switchboard Number 1 difference Short time rating NEMA vs. ANSI
  • 24. 24 Molded Case Circuit Breakers • Tested in accordance with UL489 • Open Air Test - Rated @ 80% • Over Toggle Mechanism • Sealed Case - Not Maintainable • Applied in Switchboards/Panelboards Insulated Case Circuit Breakers • Tested in accordance with UL489 • Open Air Test - Rated @ 80% or 100% • 2-Step Stored Energy Mechanism • Sealed Case - Not Fully Maintainable • Applied As Mains in Switchboards/MCC’s Power Circuit Breakers • Tested in accordance with ANSI C37 • Tested in the Enclosure - Rated @ 100% • 2-Step Stored Energy Mechanism • Open Access - Fully Maintainable • Applied in Metal-Enclosed Drawout Swgr. UL489 versus ANSI C37
  • 25. 25
  • 27. 27 True or False 100% Selectively Coordinating a system makes it more RELIABLE. TRUE FALSE
  • 28. 28 True or False 100% Selectively Coordinating a system makes it SAFER. TRUE FALSE
  • 29. 29 What devices are required to Selectively Coordinate?U TIL ITY A M A I N A M SG -A M S G -TI E U TI LITY B M A IN B M S G -B A TS -EQ N O RM A T S-C R N O RM A T S- L S N O R MC H IL LE R F D R G EN # 1 M A I N G E N S W G R A T S- EQ E M E R A TS -C R EM E R A TS -L S E M E R G E N # 1 G E N # 2 M A I N G E N # 2 EN A T S- EQ EN A TS -C R EN A TS -L S C B L-A T S EQ N C BL -A T S C R N C BL -A TS L S N C BL -0 00 5 C B L-0 0 06 C BL- 00 0 7 C B L -E Q 4 80 V P N L C BL -C R 4 8 0V PN L C BL -LS 4 80 V P N L E Q 4 80 V P N L EQ X F M R P R I C B L -E Q X F M R P R I S P E Q X F M R C B L -E Q 2 08 V P N L EQ 2 0 8V P N L M A IN E Q 2 08 V P N L EQ 2 0 8V B R A N CH C R 4 8 0V PN L C R X FM R P R I C BL -C R X F M R P R I S P C R X FM R C BL -C R 2 0 8V PN L C R 20 8 V P N L M AIN C R 2 0 8V PN L C R 20 8 V BR A N C H L S 4 80 V P N L L S X FM R P R I C BL -LS X F M R PR I S P L S X F M R C BL -LS 2 08 V P N L L S 2 0 8V PN L M A IN L S 2 08 V P N L L S 2 0 8V BR A N C H C H ILL E R C BL- C H ILLE R D IS T R P N L FD R C BL- D IST R P N L D IS T R P N L 4 80 V LT G P N L F D R C BL - 48 0V LT G P N L 48 0 V LT G P N L LT G BR A N C H 4 80 V LR G S T 1. Load side of any Emergency System ATS 2. Emergency source to the line side ATS 3. Normal source to the line side of the ATS???
  • 30. 30 U TIL ITY A M A I N A M SG -A M S G -TI E U TI LITY B M A IN B M S G -B A TS -EQ N O RM A T S-C R N O RM A T S- L S N O R MC H IL LE R F D R G EN # 1 M A I N G E N S W G R A T S- EQ E M E R A TS -C R EM E R A TS -L S E M E R G E N # 1 G E N # 2 M A I N G E N # 2 EN A T S- EQ EN A TS -C R EN A TS -L S C B L-A T S EQ N C BL -A T S C R N C BL -A TS L S N C BL -0 00 5 C B L-0 0 06 C BL- 00 0 7 C B L -E Q 4 80 V P N L C BL -C R 4 8 0V PN L C BL -LS 4 80 V P N L E Q 4 80 V P N L EQ X F M R P R I C B L -E Q X F M R P R I S P E Q X F M R C B L -E Q 2 08 V P N L EQ 2 0 8V P N L M A IN E Q 2 08 V P N L EQ 2 0 8V B R A N CH C R 4 8 0V PN L C R X FM R P R I C BL -C R X F M R P R I S P C R X FM R C BL -C R 2 0 8V PN L C R 20 8 V P N L M AIN C R 2 0 8V PN L C R 20 8 V BR A N C H L S 4 80 V P N L L S X FM R P R I C BL -LS X F M R PR I S P L S X F M R C BL -LS 2 08 V P N L L S 2 0 8V PN L M A IN L S 2 08 V P N L L S 2 0 8V BR A N C H C H ILL E R C BL- C H ILLE R D IS T R P N L FD R C BL- D IST R P N L D IS T R P N L 4 80 V LT G P N L F D R C BL - 48 0V LT G P N L 48 0 V LT G P N L LT G BR A N C H 4 80 V LR G S T What devices are required to Selectively Coordinate? 3. Normal source to the line side of the ATS??? Is this Zone important for continuity of service? This bus sees an unnecessary outage. ATS transfers into a fault. Gen feeds a fault. Normal ATS breaker must be reset for ATS to transfer back
  • 32. 32 Why .1 seconds? “Operating records show that the majority of electric faults originate as phase-to-ground failures.” IEEE std. 141-1993, page 187. (Red book) “It should be recognized, however, that actual short circuits often involve arcing, and variable arc impedance can reduce low-voltage short-circuit current magnitudes appreciably.” IEEE std. 141-1993, page 113. (Red book) Looking at TCC’s, fault currents that cause operation of OCPD’s in the sub 6 cycle range have been found to be rare occurrences for systems that have already been safely energized.
  • 34. 34
  • 35. 35 Ground Faults on low-voltage systems “Arcing faults are the more destructive type of fault because the arc limits the fault current.” “Selectivity can be typically achieved only by including more than one level of ground fault relays.” IEEE std. 142-2001, page 626. (Buff book)
  • 36. 36 How GFP Effects Coordination From NEC 517-17: (a) Feeders“ Where GFP is provided for operation of the service disconnecting means ----an additional step of GFP shall be provided in the next level of feeder disconnecting means downstream toward the load.” This is a healthcare requirement.
  • 37. 37 More from NEC 517-17 (b) Selectivity. “ GFP for operation of the service feeder disconnecting means shall be fully selective such that the feeder device and not the service device shall open on ground faults on the load side of the feeder device. A six cycle minimum separation between the service and feeder GF tripping bands shall be provided.” Why 6 cycles? (OCPD opening time). Note: only GFP is referenced here.
  • 38. 38
  • 39. Specific Application Circuit Breakers Motor Starting Motor Circuit Protectors Motor Starting Considerations National Electrical Code 430-52 Maximum instantaneous setting 13x FLA First peak may be 17-18x FLA or higher on energy efficient motors HMCP size 0-4 transient inrush trip suppressor - Sustain high inrush for first cycle - Provide sensitive, adjustable short-circuit protection
  • 40. Specific Application Circuit Breakers HMCP Motor Circuit Protectors Adjustable Trip Settings Multiples of continuous current rating Field adjustable Close coordination with motor characteristics
  • 41. 41
  • 42. 42 Thermal Magnetic Overload Protection (Thermal) Short-Circuit Protection (Magnetic)
  • 43. 43 Know your fault current!
  • 44. 44 Bolted Fault Arcing Fault Systems must be designed However, the majority of faults for worst case conditions. will be arcing type. Line-to-Line-to-Line Fault
  • 45. 45 Why .1 seconds? “Operating records show that the majority of electric faults originate as phase-to-ground failures.” IEEE std. 141-1993, page 187. (Red book) “It should be recognized, however, that actual short circuits often involve arcing, and variable arc impedance can reduce low-voltage short-circuit current magnitudes appreciably.” IEEE std. 141-1993, page 113. (Red book) Looking at TCC’s, fault currents that cause operation of OCPD’s in the sub 6 cycle range have been found to be rare occurrences for systems that have already been safely energized.
  • 46. 46 Does .1 Seconds make Sense - Types and Frequencies of Faults “Operating records show that the majority of electric faults originate as phase-to-ground failures.” IEEE std. 141-1993, page 187. (Red book) “It should be recognized, however, that actual short circuits often involve arcing, and variable arc impedance can reduce low-voltage short-circuit current magnitudes appreciably.” IEEE std. 141-1993, page 113. (Red book)