In power system, real power and reactive
power is controlled by the voltage and phase
angle difference between the sending end
and receiving end respectively. Impedance of
the transmission line can also be used to
control real and reactive power. Flexible AC
Transmission Systems (FACTS) are used to
improve the power transfer capability of
transmission line.
THYRISTOR CONTROL REACTOR
THYRISTOR SWITCHED CAPACITOR
STATIC VAR COMPENSATOR
THYRISTOR SWITCHED SERIESCOMPENSATOR
STATIC COMPENSATOR
SELF COMMUTATED COMPENSATOR
UNIFIED POWER FLOW CONTROLLER
INCREASE THE CAPABILITY OF LOADING OF
LINES TO THEIR THERMAL CAPABILITES
INCREASE THE SYSTEM SECURITY THROUGH
RISING THEIR TRANSIENT STABILITY LIMIT
CONTROL OF POWER FLOW AS ORDERED
REDUCE REACTIVE POWER FLOW
Static synchronous compensator, is a
regulating device used on ac
current electricity transmission networks. It is
based on a power electronics voltage-source
converter and can act as either a source or
sink of reactive AC power to an electricity
network. If connected to a source of power it
can also provide active AC power It is a
member of the FACTS family of devices.
Components mainly
used are :
Coupling Transformer
Voltage source
converter
Capacitor bank
STATCOM controller
HARMONIC COMPENSATION IS NOT ACHIEVED
PRESENCE OF FOUR PI CONTROLLERS MAKES
THE SYSTEM SLOW IN RESPONSE
IT ALSO REDUSES THE STABILITY
CONTINUOUS AND DYNAMIC VOLTAGECONTROL
HIGH EFFICIENCY
HIGH DYNAMIC VERY FAST RESPONSE TIME
SINGLE PHASE CONTROL FOR UNBALANCED LOADS
REACTIVE POWER COMPENSATION
The static synchronous compensator (STATCOM) is
increasingly popular in power system application.
In general, power factor and stability of the utility
system can be improved by STATCOM.
Statcom is able to provide rated current under
reduced voltage condition
Voltage support and control
Voltage fluctuation and flicker mitigation
Unsymmetrical load balancing
Power factor correction
Active harmonics cancellation
Improve transient stability of the power
system
The STATCOM has the ability to provide more
capacitive reactive power during faults, or when the
system voltage drops abnormally, compared to
ordinary static var compensator. This is because
the maximum capacitive reactive power generated
by a STATCOM decreases linearly with system
voltage, while that of the SVC is proportional to the
square of the voltage. Also, the STATCOM has a
faster response as it has no time delay associated
with thyristor firing.
Ultra dynamic response (<10ms)
No steps
Ind. + cap. Capabilities
Low harmonics no filters required
Cheaper than SVC below §50MVAR
Future work can involve multilevel STATACOM
to reduce harmonics in the system.Also more
practical sophisticated method may be
proposed to adress the minimization of
STATCOM capacity.
STATCOM can be implemented with Predictive
Controller.