Effect Of pollution on flashover voltage of pin insulators
(HIGH VOLTAGE PROJECT)
Electrical Engg.(Final Year)
Group no.- 6
Project Supervisor Group Members
Mr. Zafar Ahmad Akram Najfi (13EEB507)
Md. Sharique Ahmad (13EEB470)
MU Anas ( 13EEB055)
CONTENTS
๏‚ด Insulator and its Design Considerations
๏‚ด Types of Insulators
๏‚ด Causes of Insulation failure
๏‚ด Flashover Mechanism
๏‚ด Pollution Tests of Insulators
๏‚ด Sources of Insulator Contaminants
๏‚ด Methods to Measure Contamination
๏‚ด Methods to Prevent Flashover
๏‚ด Practical Work
๏‚ด References
What is an Insulator ?
Overhead line insulators are used to insulate line conductor from each other
and the supporting structure electrically.
DESIGN CONSIDERATIONS:
๏ƒ˜ High permittivity so that it can withstand high electrical stresses.
๏ƒ˜ High mechanical strength to bear the conductor load.
๏ƒ˜ High resistance to temperature changes.
๏ƒ˜ Insulator material should not be porous.
1
Types Of Insulators
Pin Type Insulators:-
It is earliest developed overhead insulator, but still popularly used in power network up to
33 KV system. It can be one part, two parts or three parts type.
Suspension Type Insulators:-
A numbers of insulators are connected in series to form a string and the line conductor is
carried by the bottom most insulator. Each insulator of a suspension string is called disc
insulator.
Fig 1. Pin Insulator and suspension
insulator
2
Strain Insulators:-
When there is a corner or sharp curve, the line is subjected to a greater tension. In
order to relieve the line of excessive tension, strain insulators are used.
Shackle Insulators:-
They are frequently used for low voltage distribution lines and can be used either in a
horizontal position or in vertical positions. They can be directly fixed to the pole or to the
cross arm.
Fig 2. Strain and shackle insulator 3
Causes Of Insulation Failure
๏‚ด The electrical breakdown of insulator can occur either by flashover or by
puncture.
๏‚ด In flashover an arc occur between the line conductor and the earth and the
discharge jump across the air gap following the shortest distance.
๏‚ด In case of flashover the insulator will continue to act in its proper capacity.
๏‚ด In case of puncture, discharge occurs from conductor to the pin through the
body of the insulator.
๏‚ด In case of puncture, the insulator is permanently destroyed due to excessive
heat.
4
Contamination Flashover
๏‚ด Contamination flashover occurs when insulators become coated with a wet
conducting film containing dissolved salts.
๏‚ด The wetting conditions responsible for flashover are fog, dew and drizzle which
form a conductive region on the insulator surface.
๏‚ด This results in a drop in surface resistivity, which enables current to conduct
through the insulators.
๏‚ด The surface layer is heated and causes an increase in the conductivity and
leakage current.
๏‚ด This heating results in a local drying of the surface layer and so called dry bands
occur.
5
๏‚ด Partial arc occurs across the dry bands on such contaminated insulators.
๏‚ด The partial discharges increase.
๏‚ด Finally the partial discharges are connected in series and a complete flashover
occurs unless corrective maintenance is done.
6Fig.3 Flashover of insulator
7
Fig.4 Flashover of insulator
Pollution Tests
Natural Pollution Test
๏ƒ˜ This method developed in Britain in 1936 before the development of artificial-
pollution test methods.
๏ƒ˜ It consists of energizing the outdoor insulators in a polluted area at its normal
service voltage for a long time and record its behaviour.
๏ƒ˜ The limitations of this method are:-
1) It takes long time.
2) Insensitive method.
3) The results are comparative.
8
Artificial Pollution Test
Salt Fog Method
๏ƒ˜ A simple and direct method for assessing the withstand characteristics of insulators
when surrounded by a saline atmosphere.
๏ƒ˜ A cleaned insulator is subjected to a salt water fog while it is energized at constant
voltage.
๏ƒ˜ The fog is produced by array of nozzles, on opposite sides of the insulator.
๏ƒ˜ A plain salt solution is used for the test with values usually from 2.5 to 226 kg/m3.
๏ƒ˜ The highest salinity(in kg/m3) at which at least three 1-hour tests out of four are
passed is called the withstand salinity and is regarded as the criterion of
performance.
9
Advantages Of Salt Fog Method
๏ƒ˜ The method itself is quite simple.
๏ƒ˜ Control of parameters like fog salinity, nozzle diameters, air pressure, flow
of solution, etc is very easy to achieve.
๏ƒ˜ The test results are repeatable and satisfactorily reproducible.
However, due to the poor representability of the salt-fog test, it is desirable to
modify the standard Salt-Fog test or to define a new pollution for coastal conditions.
10
Insulator Contaminants
Contaminants Sources of contaminants
Salt 1. Coastal areas/ Salt Industries
2. Highways with deposit of snow where salt is used to melt the snow.
Cement 1. Cement plant
2. Construction sites
3. Rocks quarries
Smog 1. Automobile emissions at highway crossing
2. Diesel engine emissions at railway crossing/yards
Fertilizers 1. Fertilizers plants
2. Frequent use of fertilizers in cultivated fields
Metallic 1. Mining handling processes
2. Mineral handling processes
Coal 1. Coal mining
2. Coal handling plants/ thermal plants
3. Coal burning/brick kilns areas
Volcanic ash Volcanic activity areas
Chemical Wide variety of chemical processes/process industries, oil refineries
11
Methods to Measure Contamination
There are two methods of measuring contamination:-
1). Equivalent salt deposit density Method
๏ƒ˜ The density of equivalent salt deposit density(ESDD) equals an amount of NaCl
which, dissolved in water, will change waterโ€™s conductivity to the level equal to the
solution of polluted deposits gathered from insulator surface.
๏ƒ˜ The severity of the pollution is characterized by the equivalent salt deposit density.
๏ƒ˜ ESDD is measured by periodically washing down the pollution from selected
insulators with distilled water and carefully collecting the water.
12
๏ƒ˜ The conductivity of the collected water is measured and equivalent amount of salts,
which produces the same conductivity, is calculated.
๏ƒ˜ The obtained mg value of salt is divided by the cleaned area of this insulator to
obtain the ESDD value.
๏ƒ˜ ๐‘ฌ๐‘บ๐‘ซ๐‘ซ = ๐ŸŽ. ๐Ÿ“๐Ÿ“ โˆ—
๐‘ฝ(
๐ˆ
๐Ÿ+๐ŸŽ.๐Ÿ ๐‘ปโˆ’๐Ÿ๐ŸŽ
)
๐‘จ
Where,
ฯƒ: is the layer conductivity at lab temperature(in mS)
V: volume for solution conductivity measurement at lab temperature (in ml)
T: temperature of the insulator surface
A: area of cleansed surface
13
2). Directional dust deposit gauge method
๏ƒ˜ This method was first chosen by research institute of electricity supply commission
(Eskom) in 1974 to examine insulator pollution.
๏ƒ˜ DDG includes four vertical split pipes and a pot below each pipe to gather pollution.
๏ƒ˜ The pipes are placed along the four geographical directions, north, south, east and
west.
๏ƒ˜ DDG pollution index, is the average of four conductivities (ยตS/cm) obtained from the
four direction for a thirty day month in 500 cc normalized washing water.
14
๏ƒ˜ Conductivity in north direction, ๐ˆ๐‘ต = ๐‘ช
๐‘ฝ
๐Ÿ“๐ŸŽ๐ŸŽ
๐Ÿ‘๐ŸŽ
๐‘ต
๏ƒ˜ Average conductivity = (๐œŽ๐‘+ ๐œŽ๐‘† + ๐œŽ๐ธ + ๐œŽ๐‘Š)/4
where :
๐œŽ๐‘, ๐œŽ๐‘†, ๐œŽ๐ธ, ๐œŽ๐‘Šare normalized conductivity in north, south, east and west
C= conductivity (ยตS/cm)
V= volume of distilled water (ml)
N= no. of days when the insulator
has been under investigation
15
Fig 4. Directional dust deposit gauge
Methods to Prevent Flashover
1).Periodic hand wiping
๏ƒ˜ Insulators can be prevented from flashover if the surface are kept clean by hand
wiping.
๏ƒ˜ This method is efficient but is also tedious, time consuming and expensive process
which requires equipment outage.
๏ƒ˜ Hand wiping is normally used on insulator where high pressure washing is either
impractical due to inaccessibility or ineffective due to hardness of surface deposit.
๏ƒ˜ Material such as wet or paraffin-soaked cloth, brushes, or similar cleaning material
may be needed for insulator with hard caked deposit.
16
2). Periodic washing either energized or de-energized
๏ƒ˜ De-energized cleaning of salty deposits is most effectively done by washing, but
hard industrial deposits can be removed by caustic soda solution or grit blasting.
๏ƒ˜ Grit blasting can be done by using the material such as crushed coconut oil shell,
which will not damage the glaze but will remove deposit such as compacted
cement dust.
๏ƒ˜ To avoid frequent outages, live washing is often preferred to clean un-energized
insulators.
๏ƒ˜ Manual jet washing is done from portable installations and automatically spray
washing from fixed nozzles around the insulators.
17
3).Periodic coating, either energized or de-energized with grease
compound
๏ƒ˜ Coating the insulator surface with a water repellent material such as silicon
grease which prevents formation of continuous water films.
๏ƒ˜ Coating insulators with grease compounds has been used satisfactorily as a
means of preventing contamination flashover for 20 years.
๏ƒ˜ This method is expensive and requires periodic maintenance of removing and
recoating, the frequency of such recoating, depending upon the degree of
contamination and the weather conditions.
๏ƒ˜ The grease can be applied to de-energized insulators by a number of methods
โ€” by hand using rubber gloves, pads or brushes, or by air spray equipment.
18
Practical Work
In order to investigate the influence of different contaminants and other factors on
performance of pin insulators, artificial pollution testing will be carried out in steps as
discussed below.
STEPS:-
1. We will choose 3 salts, NaCl, KCl, CaCl2 as contaminants for this experiment.
2. The surface of the specimen insulator is washed with detergent to remove
repellence.
3. Make solutions of three different concentrations of each salt of normality N, N/2,
N/4.
4. To see the variation of the flashover voltage with the normality of contaminants,
contamination will be carried out from one flange to the other flanges and
flashover voltages will be noted accordingly.
19
5. Temperature, pressure and humidity in the atmosphere at the time of testing is to
be noted to take into account the influence of weather condition.
6. Now taking NaCl of normality N, we will contaminate the upper flange (1) by
spraying the salt solution on it. The insulator is left in the sunlight to dry.
7. The flashover voltage (FOV) of the insulator is noted in this condition.
8. After washing the insulator again, the middle flange (2) is contaminated with the
same salt and same concentration and FOV is noted.
9. Repeat the same procedure for bottom flange (3).
10. After getting these three FOV values, now contaminate flanges in pair like upper-
middle (1-2), middle-bottom (2-3) , and bottom-upper (3-1) and note down their
flashover voltages respectively.
11. Now contaminate all the three flanges (1-2-3) simultaneously to get the 7th reading
of NaCl of concentration N. The readings of NaCl of normality N is thus completed.
20
12. Now we will take NaCl of N/2 concentration and repeat the steps numbered
from 6-11 and note down the FOV values to get second set of readings.
13. Third set of readings can be found out by taking NaCl (N/4 normality) and
following the same procedures as above.
14. After taking all these readings, the graph is to be plotted between FOV against
varying normality for NaCl and seven different sets of flange contamination
giving us 7 graphs for each salt.
15. Now, we will take KCl of concentrations N, N/2, N/4 one by one and follow, the
same procedures as was for NaCl (step 6-14). The same will be done with
CaCl2 .
16. The combined graph for the three salts of same concentration, say N, can be
plotted by keeping flashover voltage on Y-axis and flange position on X-axis.
Thus we will get three graphs for three different concentrations.
21
REFERENCES
๏‚ด B. Onyemaechi, M. J. Mbunwe, and M. Kingsley, "The Performance
Characteristics Of Low Voltage Insulator," IOSR Journal Of Electrical and
Electronics Engineering, vol. 7, no. 4, pp. 43โ€“47, Aug. 2013.
๏‚ด M. T. Gencoglu and M. Cebeci, "Investigation of pollution flashover on high
voltage insulators using artificial neural network," Expert Systems with
Applications: An International Journal, vol. 36, no. 4, pp. 7338โ€“7345, May 2009.
๏‚ด A. A. Khan and E. Husain, "Porcelain Insulator Performance under Different
Condition of Installation around Aligarh," International Journal of Electrical,
Computer, Energetic, Electronic and Communication Engineering, vol. 7, no. 7,
pp. 933โ€“937, 2013.
๏‚ด A. Husain, Electrical Power System, 5th ed. CBS Publishers & Distributors, 2010.
22

More Related Content

What's hot

Study of solid lubrication with MoS2 coating
Study of solid lubrication with MoS2 coatingStudy of solid lubrication with MoS2 coating
Study of solid lubrication with MoS2 coating
Saransh Gupta
ย 
Detailed Description of Process Flow
Detailed Description of Process FlowDetailed Description of Process Flow
Detailed Description of Process Flow
George Epstein
ย 
Design, Construction and Test of Corrosion
Design, Construction and Test of CorrosionDesign, Construction and Test of Corrosion
Design, Construction and Test of Corrosion
Amir Reza James Oskui
ย 
Thin film fabrication using thermal evaporation
Thin film fabrication using thermal evaporationThin film fabrication using thermal evaporation
Thin film fabrication using thermal evaporation
Udhayasuriyan V
ย 
MSE PhD lecture. Adv. Mater. Synthesis. Thin Films. Oct 23, 2014.
MSE PhD lecture. Adv. Mater. Synthesis. Thin Films. Oct 23, 2014.MSE PhD lecture. Adv. Mater. Synthesis. Thin Films. Oct 23, 2014.
MSE PhD lecture. Adv. Mater. Synthesis. Thin Films. Oct 23, 2014.
Toru Hara
ย 
Chapter 4 corrosion testin
Chapter 4 corrosion testinChapter 4 corrosion testin
Chapter 4 corrosion testin
Nima_s70
ย 
Direct Engineering Thin Film Presentation
Direct Engineering Thin Film PresentationDirect Engineering Thin Film Presentation
Direct Engineering Thin Film Presentation
Davis Hemenway
ย 

What's hot (20)

Study of solid lubrication with MoS2 coating
Study of solid lubrication with MoS2 coatingStudy of solid lubrication with MoS2 coating
Study of solid lubrication with MoS2 coating
ย 
Thin film and thick film resistor
Thin film and thick film resistorThin film and thick film resistor
Thin film and thick film resistor
ย 
Micro ftir3 end-recalls and shutdowns
Micro ftir3 end-recalls and shutdownsMicro ftir3 end-recalls and shutdowns
Micro ftir3 end-recalls and shutdowns
ย 
Thin films
Thin films Thin films
Thin films
ย 
Detailed Description of Process Flow
Detailed Description of Process FlowDetailed Description of Process Flow
Detailed Description of Process Flow
ย 
Rosa alejandra lukaszew a review of the thin film techniques potentially ap...
Rosa alejandra lukaszew   a review of the thin film techniques potentially ap...Rosa alejandra lukaszew   a review of the thin film techniques potentially ap...
Rosa alejandra lukaszew a review of the thin film techniques potentially ap...
ย 
Ceramic Epoxy brochure
Ceramic Epoxy brochureCeramic Epoxy brochure
Ceramic Epoxy brochure
ย 
Design, Construction and Test of Corrosion
Design, Construction and Test of CorrosionDesign, Construction and Test of Corrosion
Design, Construction and Test of Corrosion
ย 
Thin film fabrication using thermal evaporation
Thin film fabrication using thermal evaporationThin film fabrication using thermal evaporation
Thin film fabrication using thermal evaporation
ย 
MSE PhD lecture. Adv. Mater. Synthesis. Thin Films. Oct 23, 2014.
MSE PhD lecture. Adv. Mater. Synthesis. Thin Films. Oct 23, 2014.MSE PhD lecture. Adv. Mater. Synthesis. Thin Films. Oct 23, 2014.
MSE PhD lecture. Adv. Mater. Synthesis. Thin Films. Oct 23, 2014.
ย 
L1 ndt versus mechanical testing &; overview of liquid penetrant test
L1 ndt versus mechanical testing &; overview of liquid penetrant testL1 ndt versus mechanical testing &; overview of liquid penetrant test
L1 ndt versus mechanical testing &; overview of liquid penetrant test
ย 
Valve Comparison Table
Valve Comparison TableValve Comparison Table
Valve Comparison Table
ย 
Chapter 4 corrosion testin
Chapter 4 corrosion testinChapter 4 corrosion testin
Chapter 4 corrosion testin
ย 
Direct Engineering Thin Film Presentation
Direct Engineering Thin Film PresentationDirect Engineering Thin Film Presentation
Direct Engineering Thin Film Presentation
ย 
Ic technology-pattern transfer and etching
Ic technology-pattern transfer and etchingIc technology-pattern transfer and etching
Ic technology-pattern transfer and etching
ย 
Apps of thin films
Apps of thin filmsApps of thin films
Apps of thin films
ย 
Failure of composites
Failure of compositesFailure of composites
Failure of composites
ย 
PLS 2014: Vent to Prevent: How pressure equalization prevents premature failu...
PLS 2014: Vent to Prevent: How pressure equalization prevents premature failu...PLS 2014: Vent to Prevent: How pressure equalization prevents premature failu...
PLS 2014: Vent to Prevent: How pressure equalization prevents premature failu...
ย 
Thin films
Thin filmsThin films
Thin films
ย 
wet etching
wet etchingwet etching
wet etching
ย 

Similar to Effect of pollution on fov (2)

Air pollution control
Air pollution controlAir pollution control
Air pollution control
ECRD IN
ย 
Chemical analysis of insulator SEISCON 2011
Chemical analysis of insulator SEISCON 2011Chemical analysis of insulator SEISCON 2011
Chemical analysis of insulator SEISCON 2011
Md Farman
ย 
Final project Document 26.11.2007
Final project Document 26.11.2007Final project Document 26.11.2007
Final project Document 26.11.2007
Kwandiwe Noah
ย 
REMOVAL OF CHROMIUM FROM WASTEWATER USING MEMBRANE SEPARATION
REMOVAL OF CHROMIUM FROM WASTEWATER USING MEMBRANE SEPARATIONREMOVAL OF CHROMIUM FROM WASTEWATER USING MEMBRANE SEPARATION
REMOVAL OF CHROMIUM FROM WASTEWATER USING MEMBRANE SEPARATION
Pratiksha Patil
ย 

Similar to Effect of pollution on fov (2) (20)

E047031040
E047031040E047031040
E047031040
ย 
F047041048
F047041048F047041048
F047041048
ย 
The Performance Characteristics of Low Voltage Insulators in a Polluted Envir...
The Performance Characteristics of Low Voltage Insulators in a Polluted Envir...The Performance Characteristics of Low Voltage Insulators in a Polluted Envir...
The Performance Characteristics of Low Voltage Insulators in a Polluted Envir...
ย 
Performance of 400 kv line insulators under pollution.
Performance of 400 kv line insulators under pollution.Performance of 400 kv line insulators under pollution.
Performance of 400 kv line insulators under pollution.
ย 
Air pollution control
Air pollution controlAir pollution control
Air pollution control
ย 
Air pollution control
Air pollution controlAir pollution control
Air pollution control
ย 
Air pollution control
Air pollution controlAir pollution control
Air pollution control
ย 
IRJET- A Proposed Design of Semi Automatic Cleaning System for High Power...
IRJET-  	  A Proposed Design of Semi Automatic Cleaning System for High Power...IRJET-  	  A Proposed Design of Semi Automatic Cleaning System for High Power...
IRJET- A Proposed Design of Semi Automatic Cleaning System for High Power...
ย 
Testing
TestingTesting
Testing
ย 
Chemical analysis of insulator SEISCON 2011
Chemical analysis of insulator SEISCON 2011Chemical analysis of insulator SEISCON 2011
Chemical analysis of insulator SEISCON 2011
ย 
Final project Document 26.11.2007
Final project Document 26.11.2007Final project Document 26.11.2007
Final project Document 26.11.2007
ย 
IRJET- Enhancement Performance of Polymer High Voltage Insulators using Nano-...
IRJET- Enhancement Performance of Polymer High Voltage Insulators using Nano-...IRJET- Enhancement Performance of Polymer High Voltage Insulators using Nano-...
IRJET- Enhancement Performance of Polymer High Voltage Insulators using Nano-...
ย 
Ge3510911102
Ge3510911102Ge3510911102
Ge3510911102
ย 
Behaviour of ZnO surge arrester in pollution
Behaviour of ZnO surge arrester in pollutionBehaviour of ZnO surge arrester in pollution
Behaviour of ZnO surge arrester in pollution
ย 
Renewable Energy in Water Desalination: Route of Technology, Vulnerabilities ...
Renewable Energy in Water Desalination: Route of Technology, Vulnerabilities ...Renewable Energy in Water Desalination: Route of Technology, Vulnerabilities ...
Renewable Energy in Water Desalination: Route of Technology, Vulnerabilities ...
ย 
INSULATOR FAILURE AND PROTECTION.pptx
INSULATOR FAILURE AND PROTECTION.pptxINSULATOR FAILURE AND PROTECTION.pptx
INSULATOR FAILURE AND PROTECTION.pptx
ย 
Air sampling
Air samplingAir sampling
Air sampling
ย 
Surface Engineering_Unit 1.pptx
Surface Engineering_Unit 1.pptxSurface Engineering_Unit 1.pptx
Surface Engineering_Unit 1.pptx
ย 
REMOVAL OF CHROMIUM FROM WASTEWATER USING MEMBRANE SEPARATION
REMOVAL OF CHROMIUM FROM WASTEWATER USING MEMBRANE SEPARATIONREMOVAL OF CHROMIUM FROM WASTEWATER USING MEMBRANE SEPARATION
REMOVAL OF CHROMIUM FROM WASTEWATER USING MEMBRANE SEPARATION
ย 
Earthing details of Electrical Substation
Earthing details of Electrical SubstationEarthing details of Electrical Substation
Earthing details of Electrical Substation
ย 

Recently uploaded

Call Girls in Netaji Nagar, Delhi ๐Ÿ’ฏ Call Us ๐Ÿ”9953056974 ๐Ÿ” Escort Service
Call Girls in Netaji Nagar, Delhi ๐Ÿ’ฏ Call Us ๐Ÿ”9953056974 ๐Ÿ” Escort ServiceCall Girls in Netaji Nagar, Delhi ๐Ÿ’ฏ Call Us ๐Ÿ”9953056974 ๐Ÿ” Escort Service
Call Girls in Netaji Nagar, Delhi ๐Ÿ’ฏ Call Us ๐Ÿ”9953056974 ๐Ÿ” Escort Service
9953056974 Low Rate Call Girls In Saket, Delhi NCR
ย 
Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power Play
Epec Engineered Technologies
ย 
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
dharasingh5698
ย 
Top Rated Call Girls In chittoor ๐Ÿ“ฑ {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor ๐Ÿ“ฑ {7001035870} VIP Escorts chittoorTop Rated Call Girls In chittoor ๐Ÿ“ฑ {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor ๐Ÿ“ฑ {7001035870} VIP Escorts chittoor
dharasingh5698
ย 
Call Girls in Ramesh Nagar Delhi ๐Ÿ’ฏ Call Us ๐Ÿ”9953056974 ๐Ÿ” Escort Service
Call Girls in Ramesh Nagar Delhi ๐Ÿ’ฏ Call Us ๐Ÿ”9953056974 ๐Ÿ” Escort ServiceCall Girls in Ramesh Nagar Delhi ๐Ÿ’ฏ Call Us ๐Ÿ”9953056974 ๐Ÿ” Escort Service
Call Girls in Ramesh Nagar Delhi ๐Ÿ’ฏ Call Us ๐Ÿ”9953056974 ๐Ÿ” Escort Service
9953056974 Low Rate Call Girls In Saket, Delhi NCR
ย 

Recently uploaded (20)

Minimum and Maximum Modes of microprocessor 8086
Minimum and Maximum Modes of microprocessor 8086Minimum and Maximum Modes of microprocessor 8086
Minimum and Maximum Modes of microprocessor 8086
ย 
Call Girls in Netaji Nagar, Delhi ๐Ÿ’ฏ Call Us ๐Ÿ”9953056974 ๐Ÿ” Escort Service
Call Girls in Netaji Nagar, Delhi ๐Ÿ’ฏ Call Us ๐Ÿ”9953056974 ๐Ÿ” Escort ServiceCall Girls in Netaji Nagar, Delhi ๐Ÿ’ฏ Call Us ๐Ÿ”9953056974 ๐Ÿ” Escort Service
Call Girls in Netaji Nagar, Delhi ๐Ÿ’ฏ Call Us ๐Ÿ”9953056974 ๐Ÿ” Escort Service
ย 
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
ย 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
ย 
Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power Play
ย 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - V
ย 
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
ย 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
ย 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torque
ย 
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
ย 
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
ย 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
ย 
Top Rated Call Girls In chittoor ๐Ÿ“ฑ {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor ๐Ÿ“ฑ {7001035870} VIP Escorts chittoorTop Rated Call Girls In chittoor ๐Ÿ“ฑ {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor ๐Ÿ“ฑ {7001035870} VIP Escorts chittoor
ย 
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
ย 
Unit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfUnit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdf
ย 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leap
ย 
Call Girls in Ramesh Nagar Delhi ๐Ÿ’ฏ Call Us ๐Ÿ”9953056974 ๐Ÿ” Escort Service
Call Girls in Ramesh Nagar Delhi ๐Ÿ’ฏ Call Us ๐Ÿ”9953056974 ๐Ÿ” Escort ServiceCall Girls in Ramesh Nagar Delhi ๐Ÿ’ฏ Call Us ๐Ÿ”9953056974 ๐Ÿ” Escort Service
Call Girls in Ramesh Nagar Delhi ๐Ÿ’ฏ Call Us ๐Ÿ”9953056974 ๐Ÿ” Escort Service
ย 
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
ย 
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
COST-EFFETIVE  and Energy Efficient BUILDINGS ptxCOST-EFFETIVE  and Energy Efficient BUILDINGS ptx
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
ย 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ย 

Effect of pollution on fov (2)

  • 1. Effect Of pollution on flashover voltage of pin insulators (HIGH VOLTAGE PROJECT) Electrical Engg.(Final Year) Group no.- 6 Project Supervisor Group Members Mr. Zafar Ahmad Akram Najfi (13EEB507) Md. Sharique Ahmad (13EEB470) MU Anas ( 13EEB055)
  • 2. CONTENTS ๏‚ด Insulator and its Design Considerations ๏‚ด Types of Insulators ๏‚ด Causes of Insulation failure ๏‚ด Flashover Mechanism ๏‚ด Pollution Tests of Insulators ๏‚ด Sources of Insulator Contaminants ๏‚ด Methods to Measure Contamination ๏‚ด Methods to Prevent Flashover ๏‚ด Practical Work ๏‚ด References
  • 3. What is an Insulator ? Overhead line insulators are used to insulate line conductor from each other and the supporting structure electrically. DESIGN CONSIDERATIONS: ๏ƒ˜ High permittivity so that it can withstand high electrical stresses. ๏ƒ˜ High mechanical strength to bear the conductor load. ๏ƒ˜ High resistance to temperature changes. ๏ƒ˜ Insulator material should not be porous. 1
  • 4. Types Of Insulators Pin Type Insulators:- It is earliest developed overhead insulator, but still popularly used in power network up to 33 KV system. It can be one part, two parts or three parts type. Suspension Type Insulators:- A numbers of insulators are connected in series to form a string and the line conductor is carried by the bottom most insulator. Each insulator of a suspension string is called disc insulator. Fig 1. Pin Insulator and suspension insulator 2
  • 5. Strain Insulators:- When there is a corner or sharp curve, the line is subjected to a greater tension. In order to relieve the line of excessive tension, strain insulators are used. Shackle Insulators:- They are frequently used for low voltage distribution lines and can be used either in a horizontal position or in vertical positions. They can be directly fixed to the pole or to the cross arm. Fig 2. Strain and shackle insulator 3
  • 6. Causes Of Insulation Failure ๏‚ด The electrical breakdown of insulator can occur either by flashover or by puncture. ๏‚ด In flashover an arc occur between the line conductor and the earth and the discharge jump across the air gap following the shortest distance. ๏‚ด In case of flashover the insulator will continue to act in its proper capacity. ๏‚ด In case of puncture, discharge occurs from conductor to the pin through the body of the insulator. ๏‚ด In case of puncture, the insulator is permanently destroyed due to excessive heat. 4
  • 7. Contamination Flashover ๏‚ด Contamination flashover occurs when insulators become coated with a wet conducting film containing dissolved salts. ๏‚ด The wetting conditions responsible for flashover are fog, dew and drizzle which form a conductive region on the insulator surface. ๏‚ด This results in a drop in surface resistivity, which enables current to conduct through the insulators. ๏‚ด The surface layer is heated and causes an increase in the conductivity and leakage current. ๏‚ด This heating results in a local drying of the surface layer and so called dry bands occur. 5
  • 8. ๏‚ด Partial arc occurs across the dry bands on such contaminated insulators. ๏‚ด The partial discharges increase. ๏‚ด Finally the partial discharges are connected in series and a complete flashover occurs unless corrective maintenance is done. 6Fig.3 Flashover of insulator
  • 10. Pollution Tests Natural Pollution Test ๏ƒ˜ This method developed in Britain in 1936 before the development of artificial- pollution test methods. ๏ƒ˜ It consists of energizing the outdoor insulators in a polluted area at its normal service voltage for a long time and record its behaviour. ๏ƒ˜ The limitations of this method are:- 1) It takes long time. 2) Insensitive method. 3) The results are comparative. 8
  • 11. Artificial Pollution Test Salt Fog Method ๏ƒ˜ A simple and direct method for assessing the withstand characteristics of insulators when surrounded by a saline atmosphere. ๏ƒ˜ A cleaned insulator is subjected to a salt water fog while it is energized at constant voltage. ๏ƒ˜ The fog is produced by array of nozzles, on opposite sides of the insulator. ๏ƒ˜ A plain salt solution is used for the test with values usually from 2.5 to 226 kg/m3. ๏ƒ˜ The highest salinity(in kg/m3) at which at least three 1-hour tests out of four are passed is called the withstand salinity and is regarded as the criterion of performance. 9
  • 12. Advantages Of Salt Fog Method ๏ƒ˜ The method itself is quite simple. ๏ƒ˜ Control of parameters like fog salinity, nozzle diameters, air pressure, flow of solution, etc is very easy to achieve. ๏ƒ˜ The test results are repeatable and satisfactorily reproducible. However, due to the poor representability of the salt-fog test, it is desirable to modify the standard Salt-Fog test or to define a new pollution for coastal conditions. 10
  • 13. Insulator Contaminants Contaminants Sources of contaminants Salt 1. Coastal areas/ Salt Industries 2. Highways with deposit of snow where salt is used to melt the snow. Cement 1. Cement plant 2. Construction sites 3. Rocks quarries Smog 1. Automobile emissions at highway crossing 2. Diesel engine emissions at railway crossing/yards Fertilizers 1. Fertilizers plants 2. Frequent use of fertilizers in cultivated fields Metallic 1. Mining handling processes 2. Mineral handling processes Coal 1. Coal mining 2. Coal handling plants/ thermal plants 3. Coal burning/brick kilns areas Volcanic ash Volcanic activity areas Chemical Wide variety of chemical processes/process industries, oil refineries 11
  • 14. Methods to Measure Contamination There are two methods of measuring contamination:- 1). Equivalent salt deposit density Method ๏ƒ˜ The density of equivalent salt deposit density(ESDD) equals an amount of NaCl which, dissolved in water, will change waterโ€™s conductivity to the level equal to the solution of polluted deposits gathered from insulator surface. ๏ƒ˜ The severity of the pollution is characterized by the equivalent salt deposit density. ๏ƒ˜ ESDD is measured by periodically washing down the pollution from selected insulators with distilled water and carefully collecting the water. 12
  • 15. ๏ƒ˜ The conductivity of the collected water is measured and equivalent amount of salts, which produces the same conductivity, is calculated. ๏ƒ˜ The obtained mg value of salt is divided by the cleaned area of this insulator to obtain the ESDD value. ๏ƒ˜ ๐‘ฌ๐‘บ๐‘ซ๐‘ซ = ๐ŸŽ. ๐Ÿ“๐Ÿ“ โˆ— ๐‘ฝ( ๐ˆ ๐Ÿ+๐ŸŽ.๐Ÿ ๐‘ปโˆ’๐Ÿ๐ŸŽ ) ๐‘จ Where, ฯƒ: is the layer conductivity at lab temperature(in mS) V: volume for solution conductivity measurement at lab temperature (in ml) T: temperature of the insulator surface A: area of cleansed surface 13
  • 16. 2). Directional dust deposit gauge method ๏ƒ˜ This method was first chosen by research institute of electricity supply commission (Eskom) in 1974 to examine insulator pollution. ๏ƒ˜ DDG includes four vertical split pipes and a pot below each pipe to gather pollution. ๏ƒ˜ The pipes are placed along the four geographical directions, north, south, east and west. ๏ƒ˜ DDG pollution index, is the average of four conductivities (ยตS/cm) obtained from the four direction for a thirty day month in 500 cc normalized washing water. 14
  • 17. ๏ƒ˜ Conductivity in north direction, ๐ˆ๐‘ต = ๐‘ช ๐‘ฝ ๐Ÿ“๐ŸŽ๐ŸŽ ๐Ÿ‘๐ŸŽ ๐‘ต ๏ƒ˜ Average conductivity = (๐œŽ๐‘+ ๐œŽ๐‘† + ๐œŽ๐ธ + ๐œŽ๐‘Š)/4 where : ๐œŽ๐‘, ๐œŽ๐‘†, ๐œŽ๐ธ, ๐œŽ๐‘Šare normalized conductivity in north, south, east and west C= conductivity (ยตS/cm) V= volume of distilled water (ml) N= no. of days when the insulator has been under investigation 15 Fig 4. Directional dust deposit gauge
  • 18. Methods to Prevent Flashover 1).Periodic hand wiping ๏ƒ˜ Insulators can be prevented from flashover if the surface are kept clean by hand wiping. ๏ƒ˜ This method is efficient but is also tedious, time consuming and expensive process which requires equipment outage. ๏ƒ˜ Hand wiping is normally used on insulator where high pressure washing is either impractical due to inaccessibility or ineffective due to hardness of surface deposit. ๏ƒ˜ Material such as wet or paraffin-soaked cloth, brushes, or similar cleaning material may be needed for insulator with hard caked deposit. 16
  • 19. 2). Periodic washing either energized or de-energized ๏ƒ˜ De-energized cleaning of salty deposits is most effectively done by washing, but hard industrial deposits can be removed by caustic soda solution or grit blasting. ๏ƒ˜ Grit blasting can be done by using the material such as crushed coconut oil shell, which will not damage the glaze but will remove deposit such as compacted cement dust. ๏ƒ˜ To avoid frequent outages, live washing is often preferred to clean un-energized insulators. ๏ƒ˜ Manual jet washing is done from portable installations and automatically spray washing from fixed nozzles around the insulators. 17
  • 20. 3).Periodic coating, either energized or de-energized with grease compound ๏ƒ˜ Coating the insulator surface with a water repellent material such as silicon grease which prevents formation of continuous water films. ๏ƒ˜ Coating insulators with grease compounds has been used satisfactorily as a means of preventing contamination flashover for 20 years. ๏ƒ˜ This method is expensive and requires periodic maintenance of removing and recoating, the frequency of such recoating, depending upon the degree of contamination and the weather conditions. ๏ƒ˜ The grease can be applied to de-energized insulators by a number of methods โ€” by hand using rubber gloves, pads or brushes, or by air spray equipment. 18
  • 21. Practical Work In order to investigate the influence of different contaminants and other factors on performance of pin insulators, artificial pollution testing will be carried out in steps as discussed below. STEPS:- 1. We will choose 3 salts, NaCl, KCl, CaCl2 as contaminants for this experiment. 2. The surface of the specimen insulator is washed with detergent to remove repellence. 3. Make solutions of three different concentrations of each salt of normality N, N/2, N/4. 4. To see the variation of the flashover voltage with the normality of contaminants, contamination will be carried out from one flange to the other flanges and flashover voltages will be noted accordingly. 19
  • 22. 5. Temperature, pressure and humidity in the atmosphere at the time of testing is to be noted to take into account the influence of weather condition. 6. Now taking NaCl of normality N, we will contaminate the upper flange (1) by spraying the salt solution on it. The insulator is left in the sunlight to dry. 7. The flashover voltage (FOV) of the insulator is noted in this condition. 8. After washing the insulator again, the middle flange (2) is contaminated with the same salt and same concentration and FOV is noted. 9. Repeat the same procedure for bottom flange (3). 10. After getting these three FOV values, now contaminate flanges in pair like upper- middle (1-2), middle-bottom (2-3) , and bottom-upper (3-1) and note down their flashover voltages respectively. 11. Now contaminate all the three flanges (1-2-3) simultaneously to get the 7th reading of NaCl of concentration N. The readings of NaCl of normality N is thus completed. 20
  • 23. 12. Now we will take NaCl of N/2 concentration and repeat the steps numbered from 6-11 and note down the FOV values to get second set of readings. 13. Third set of readings can be found out by taking NaCl (N/4 normality) and following the same procedures as above. 14. After taking all these readings, the graph is to be plotted between FOV against varying normality for NaCl and seven different sets of flange contamination giving us 7 graphs for each salt. 15. Now, we will take KCl of concentrations N, N/2, N/4 one by one and follow, the same procedures as was for NaCl (step 6-14). The same will be done with CaCl2 . 16. The combined graph for the three salts of same concentration, say N, can be plotted by keeping flashover voltage on Y-axis and flange position on X-axis. Thus we will get three graphs for three different concentrations. 21
  • 24. REFERENCES ๏‚ด B. Onyemaechi, M. J. Mbunwe, and M. Kingsley, "The Performance Characteristics Of Low Voltage Insulator," IOSR Journal Of Electrical and Electronics Engineering, vol. 7, no. 4, pp. 43โ€“47, Aug. 2013. ๏‚ด M. T. Gencoglu and M. Cebeci, "Investigation of pollution flashover on high voltage insulators using artificial neural network," Expert Systems with Applications: An International Journal, vol. 36, no. 4, pp. 7338โ€“7345, May 2009. ๏‚ด A. A. Khan and E. Husain, "Porcelain Insulator Performance under Different Condition of Installation around Aligarh," International Journal of Electrical, Computer, Energetic, Electronic and Communication Engineering, vol. 7, no. 7, pp. 933โ€“937, 2013. ๏‚ด A. Husain, Electrical Power System, 5th ed. CBS Publishers & Distributors, 2010. 22