14TH CANADIAN CONFERENCE ON BUILDING SCIENCE AND TECHNOLOGY
PRACTICAL ISSUES ASSOICATED WITH THE USE OF INFRARED
THERMOGRAPHY FOR DETECTION OF HEAT, AIR AND
MOISTURE DEFICIENCIES IN BUILDING ENVELOPES
G. B. McIntosh
ABSTRACT
Thermal infrared cameras have been used for more than 40 years in helping diagnose problems related to
heat, air or moisture deficiencies in buildings. But in the past 10 years significant advances have been made
in the performance, size, weight and cost reduction of cameras to the point where entry level cameras suitable
for some building investigations, are less than $3,000, and in coming years will be even less expensive.
This has led to the proliferation of its use as a building diagnostic tool. Unfortunately this has also led to
the misunderstanding of how this technology should be properly utilized, and the mis-belief that there is
such a thing as an “all-in-one” building diagnostic scan, and/or that an investigation can be performed any
time of day or year. Irrespective of how good the camera performance is, there are different minimum
environmental conditions and specific inspection methodologies required for the reliable detection of heat,
air and moisture problems for various types of construction. In addition, while thermography can be a very
useful qualitative tool, other methods and tools must be used for quantification of actual amounts of excessive
heat flow, air flow, or moisture content. This paper will discuss the limitations of utilizing thermal imaging
as a building diagnostic tool, the appropriate and separate methodologies that should be employed for heat,
air and moisture deficiencies, the various standards and protocols that should be followed, and the
complementary quantitative and verification tools that should be used in conjunction with thermography.
This paper will try to be as subjective as possible by referencing Canadian and International standards related
to building inspections using thermography. This includes historical, current and in-progress standards from
National Master Specifications of Canada, ASTM, RESNET and ISO.
INTRODUCTION
Thermography can and has been utilized in the discovery of otherwise undetectable heat, air and moisture
anomalies in buildings. Unfortunately, thermography only is applicable when these anomalies affect
detectable surface temperature patterns. It therefore requires suitable thermodynamic conditions sometimes
unique to the environment, materials, assembly, or operation of the building in order to discover an anomaly
related to a specific heat, air, or moisture deficiency. This creates limitations on the time, location, camera
detection capabilities, and operator expertise required for suitable, reliable and repeatable detection. This
paper will discuss practical considerations for detection of thermal anomalies in each of three categories.
For each topic we will discuss the limitations, challenges and requirements for the use of this building
diagnostic tool.
DETECTING THERMALANOMALIES RELATED TO CONDUCTIVE HEAT TRANSFER
Thermographic evaluations for conductive thermal anomalies (e.g.: insulation quantity, quality, deficiency,
thermal bypasses) may be conducted in heat loss (winter) or heat gain (summer) conditions so long as there
is a minimum steady state temperature difference maintained between the inside and outside of the structure.
Evaluation is based upon Fourier’s law of conduction: heat flux, Q = (k/L)·ΔT (Incropera, et al, 1996). Hence
any thermal anomaly detected as a surface temperature variance under constant steady state temperature
12 CCBST 2014 Proceedings Book_v10 A6 403-438_Layout 1 14-10-17 4:08 PM Page 429
4 3 0
14TH CANADIAN CONFERENCE ON BUILDING SCIENCE AND TECHNOLOGY
difference (ΔT) must be attributable to a variance in material conductivity (k) or thickness (L). ASTM
C1060, ISO 6781, and RESNET standards specify a minimum of 10º
C difference across the enclosure. The
Canadian National Master Specifications NMS 022713 requires a minimum difference of 15º
C, although
NMS standards are aimed more towards commercial and institutional buildings where buffer spaces (e.g.
ceiling plenums, vented rain-screens) and thicker more complex construction is common. All standards
require steady state conditions lasting at least 3 to 4 hours (longer in some standards under certain conditions)
to eliminate transient surface thermal patterns influenced by material thermal capacitance storing or releasing
energy. Most standards require the inspection be conducted from both interior and exterior perspectives,
although most note that an interior inspection will usually provide better, more stable information,
particularly in conventional construction where the insulation is typically placed closer to the interior than
the exterior surfaces. Irrespective of whether it is an inside or outside inspection, transient environmental
conditions, particularly those caused by solar loading and wind, may confuse actual insulation conductive
performance, and/or cause conductive deficiencies to go undetected.
Most standards refer to thermographic assessments as being qualitative in which different types of insulation
anomalies and construction deficiencies related to thermal conduction will exhibit unique surface temperature
patterns. Most standards refer to the use of a known thermal conductivity bypass (e.g. wood studs) as a
qualitative thermal performance reference. In conventional wood frame construction the wood studs will
exhibit a regular consistent pattern of lower performance relative to the insulation. In a normal insulated
wall, when an inside wall is viewed under heat loss conditions the studs will appear cooler than the insulation
(Photo 1a), while in summertime the polarity will be reversed and the studs will appear warmer than the
insulation (Photo1b).
Accurate quantitative heat transfer performance (conductance or equivalent R value) cannot be derived from
a thermal image and/or temperature values alone. If this is desired it should be done in accordance with
ASTM C1046 – 95 and ASTM C1155 – 95. The only part that thermography plays in ASTM C1046 is to
determine the placement of the heat flow devices and measurements. Since the total enclosure heat loss is
affected by the total surface area multiplied by the unit heat flux, then thermography can also be useful for
estimating the total area affected by either one localized conductive anomaly, or the sum of repetitive
anomalies. RESNET, however, is the only standard which suggests a quantitative approach of determining
12 CCBST 2014 Proceedings Book_v10 A6 403-438_Layout 1 14-10-17 4:08 PM Page 430
4 3 1
14TH CANADIAN CONFERENCE ON BUILDING SCIENCE AND TECHNOLOGY
approximate area affected. In addition to being a difficult and time-consuming practice however, a specific
threshold of surface temperature difference must be specified to define an “anomaly” to be included in the
area calculation.
Some thermographers approximate wall performance based upon the principle of Temperature Index (Mill,
P.A.D., 1979). This index is derived from dividing the drop in temperature from the inside surface (Tis)
minus the outside ambient (Toa) by the total drop in temperature from the inside ambient (Tia) minus the
outside ambient (Toa), i.e.: Temperature Index = (Tis-Toa) / (Tia-Toa). It is based upon the principle that in
steady state the unit heat flux transferred from the interior space to the inside wall should be equal to the
heat flux conducted through a unit wall area (assuming an infinite plane). Therefore, the ratio of temperatures
should be equal to the ratio of wall thermal resistance (L/k) value to the overall heat flow resistance inclusive
of the inside surface resistance. Temperature Index produces a graph with a variable range of possible wall
performance, since the actual field value for the inside surface resistance, (which ultimately determines Tis)
may vary significantly at the time of the inspection. While ASHRAE handbook of fundamentals Table 4
suggests a design resistance value for a vertical wall of 0.120 m2
·K/W (0.68 hr·ft2
·F/Btu), the actual field
value can vary significantly depending on air velocity, surface emissivity, orientation, and variance in the
air temperature and radiant environment. On a low emissivity wall, for instance, theASHRAE value changes
to 0.238 m2
·K/W (1.35 hr·ft2
·F/Btu). Or, if there is a 5 ft/sec air flow across the inside wall the design value
changes to 0.044 m2
·K/W (0.25 hr·ft2
·F/Btu). Another major assumption in the use of Temperature Index is
that the components of the wall are in steady state, i.e. no part of the wall is storing or releasing heat due to
the material’s heat capacitance or to a phase change (e.g.: moisture within the wall enclosure). An additional
error is created when there is three dimensional heat transfer taking place within the wall. This will occur
on or close to thermal bridging (e.g. wood or metal studs), when there is air movement within the wall, or
when there are highly diffusive materials within the wall. Due to this cumulative uncertainty, Temperature
Index is not an accurate or reliable method to predict an actual quantitative performance or for calculating
an accurate R value (Stainton, W.D. 1978). It is however, a reasonable method for classifying the thermal
performance of a light construction (e.g. wood frame, fibreglass insulated) wall. If the wall is in steady
state there can be a high confidence that the wall is in a performance category, (e.g.: very poor, poor,
acceptable, good) which could justify further investigation of an anomaly, such as heat flow measurement
or destructive testing respectively.
Qualitative pattern assessments imply that training and experience is required in order to identify deficiencies
from normal patterns, and all standards refer to training and experience requirements, although only the
RESNET and NMS standards specify ASNT SNT-TC-1A compliant Level 1 thermographers for the data
collection stage. NMS further requires anASNT compliant Level 2 for the assessment stage. ISO 6781/DIS-
3, a revision to the current ISO 6781 standard, is a new training and certification document which specifies
comprehensive training and experience requirements for detection of heat, air and moisture anomalies in
residential, commercial and institutional buildings.
All standards specify a minimum theoretical detectable difference (sensitivity) for an IR camera to be 0.1º
C
or 100mK (Noise Equivalent Temperature Difference or NETD). Attainment in the field of this number is
doubtful however, due to operator control and material emissive properties. Most standards also refer to the
minimum spatial detection capabilities for interior inspections of approximately 3 milliradians (the angle
subtended by an object 3mm in size at a 1m distance) specified as Instantaneous Field of View (IFOV).
NMS 022713 is the most rigorous by defining the minimum detectable object size as 150mm2
(approx
12.5x12.5mm) within minimum physical minimum Field of View requirements. For interior work this
approximates a minimum 160 x 120 pixel camera with a 20 to 30 degree lens used at a distance not exceeding
12 CCBST 2014 Proceedings Book_v10 A6 403-438_Layout 1 14-10-17 4:08 PM Page 431
4 3 2
14TH CANADIAN CONFERENCE ON BUILDING SCIENCE AND TECHNOLOGY
5m. RESNET has a similar spatial requirement, although somewhat relaxed in the minimum Field of View
requirement. For normal exterior work NMS requirements translate to a 320 x 240 pixel camera used at a
distance of up to about 20m, although it specifies that higher resolutions of lenses and/or pixel count may
be necessary to achieve the minimum 150mm2
resolution at longer stand-off distances. Unfortunately there
is a proliferation of low cost (under $500) thermal imagers which do not even come close to meeting these
specifications, yet are being utilized for thermographic assessments.
DETECTING THERMALANOMALIES RELATED TO AIR MOVEMENT
Unintentional air movement within, around, and through an enclosure may result is significant energy,
thermal comfort, moisture, durability and environmental issues. As shown in Table 1, air movement with
respect to a building enclosure can take 7 different types. (Mill, P.A.D. et al, 1982)
TABLE 1: TYPES OF ENCLOSURE AIR MOVEMENT AFFECTING SURFACE TEMPERATURE
Air movement types 1,2,4,6 and 7 will transfer heat via surface to air convection, while types 3 and 5 are
air leakage and have additional heat transfer associated with mass transfer (note: any latent heat related to
phase change during mass transport will be discussed next section). Under some environmental conditions
and certain types of wall assemblies the thermal patterns associated with types 2,4 and 6 can be
misinterpreted as either uncontrolled air leakage, or even at times missing insulation (when in fact adequate
insulation and/or an adequate enclosure air barrier is present).
The use of thermography to detect the effect of air leakage requires that there is both a pressure and
temperature difference between the inside and outside air. It does not detect the air directly, but rather the
heat transfer that the air movement has upon the surrounding surface. Investigations into air related thermal
anomalies may be conducted in heat loss (winter) or heat gain (summer) conditions as long as minimum
temperature and pressure differences exist across the enclosure. When air movement studies utilizing a
single pressure condition are conducted in conjunction with conductive insulation studies confusing and
ambiguous patterns can result, particularly from diffuse air movement through some types of porous
insulation. Definitive air movement testing relies on multiple pressure conditions, preferably both positive
pressure and negative pressure. Identification of air movement types 3, 4, 6 and 7 must be done by exterior
evaluation and positive pressure while identification of types 1, 2, 4 and 5 must be done by interior evaluation
and negative pressure.
Natural pressure differences across the enclosure are created by three means: stack effect; wind; and by
mechanical systems (e.g.: fans and combustion equipment). Unfortunately the thermographer is at the mercy
of the natural conditions creating the pressure differences at the time of the survey. This often leads to a
poor evaluation since parts of the building may be under positive pressure, others negative pressure, and
even others nominal pressure. To overcome this limitation the thermographer can pro-actively create a
pressure condition by one of two means: 1.) in smaller buildings utilize a blower door which can create
positive or negative air pressure differences within the entire structure or 2.) in larger or commercial buildings
adjust the inlet and exhaust fans and/or their dampers to vary pressure differential. A blower door has the
12 CCBST 2014 Proceedings Book_v10 A6 403-438_Layout 1 14-10-17 4:08 PM Page 432
4 3 3
14TH CANADIAN CONFERENCE ON BUILDING SCIENCE AND TECHNOLOGY
advantage of being able to characterize the air leakage curve for the building and provide a quantitative
estimation of the amount of air leakage under average and extreme conditions. For larger buildings where
blower door use is not possible, air leakage quantification will typically be limited to evaluation via tracer
gas depletion method.
ASTM E1186-03, RESNET and NMS 022713 standards do not agree on the pressures and temperatures
differences across the enclosure required for reliable thermographic detection of air leakage. It varies from
a difference of 1.7ºC @ 10 Pa (RESNET) to 5ºC @ 10 to 50 Pa (ASTM) to the most stringent requirements
of NMS which requires a minimum of 20ºC difference when pressures are between 5 to 10 Pa and 10ºC
minimum when pressures are between 10 to 25Pa.
The NMS standard describes an ideal two-step procedure for qualitative air leakage evaluation of larger
commercial buildings. The building is first placed under entire positive pressure and the outside surfaces
are inspected. Once all surfaces have been mapped, then the building systems are reversed and the building
is placed under negative pressure. After waiting a sufficient period of time, typically at least 2 hours, the
surfaces are re-scanned to see if the pattern has changed. If it has, it is likely due to air leakage. In order to
resolve the small areas of air leakage it is often necessary to use a narrow angle lense, map the exterior
surface with a set of images, and then assemble them into one large image. In winter, air exfiltration will
create warm patterns on the exterior surface. In general, the more diffuse the leakage, the larger the affected
area and the less dramatic the exterior thermal patterns. The more direct the leakage and size of hole, the
smaller and hotter the pattern will be.
The extreme sensitivity of modern cameras (e.g. better than 50 mK) can be such that even a relatively tight
building may appear to be extremely leaky when tested under large delta temperatures and pressures.
Therefore thermography should not be used to estimate the amount of air leakage (e.g. air changes per hour
or effective leakage area). If the surface temperature approaches the air temperature on the opposite side of
the wall, however, it is often indicative of a direct air leakage pathway (as opposed to diffuse pathways). If
this is an isolated case of a small hole, in extreme conditions of pressure difference and temperature the
resultant direct air leakage may cause damage (e.g. an interior pipe could freeze) yet a blower door test
could indicate a relatively tight building. Thermography could identify this, even under non-extreme test
12 CCBST 2014 Proceedings Book_v10 A6 403-438_Layout 1 14-10-17 4:08 PM Page 433
4 3 4
14TH CANADIAN CONFERENCE ON BUILDING SCIENCE AND TECHNOLOGY
conditions, because the surface temperature on the negative pressure side would be only slightly different
than the air temperature on the positive side.
Camera performance requirements specified by all Standards for air leakage detection are identical to those
for detection of conductive anomalies, with the NMS specifications being the most detailed and rigorous.
(refer to the previous section on conduction for camera specifications)
DETECTING THERMALANOMALIES RELATED TO MOISTURE
Water, may be detected thermodynamically for three reasons: when a material contains water it can affect
the thermal conductivity (k); when a material contains water it can alter the volumetric heat capacity (α·cp
); or when water changes state latent heat is absorbed (evaporation, melting) or released (condensation,
freezing). Many thermographers, however, believe that the only mechanism for detection of moisture is
evaporation. Under the right conditions, free air evaporative cooling on a surface can indeed be very
thermodynamic, and easily detected with a modern infrared camera: 1 droplet of water (e.g. of a mass of
0.45gms (0.001 lbs) can theoretically extract approximately 1.05kJ (1 Btu) from the surroundings in order
to provide the latent heat required for evaporation. After a flood in a building, the restoration industry will
usually attempt to dry the interior by significantly lowering the vapor pressure (relative humidity) and using
IR has brought with it the concept of water ‘always appearing cool’. The dramatic surface temperature
depression easily detectable during high vapour pressure difference, however, has led a very wrong general
assumption by building investigators for passive moisture detection. Relying on water detection through
the natural drying process only, will result both in false negatives (non-detection of moisture) and false
positives (the thermal anomaly is not moisture). Even near-surface moisture can go undetected if the vapour
pressure (RH) is too high in the free air condition adjacent to the surface. An infrared camera does not
directly detect evaporation: rather it may detect a surface temperature depression due to the rate of
evaporation which is determined by the vapor pressure difference between the saturated condition of the
material and the free air space adjacent to it as well as the vapour retarders present in between. If the free
air condition is warm and dry (low RH) it may create a high rate of cooling. Conversely, if the free air
condition is cool and/or humid (high RH) it could easily go undetected because the evaporative cooling rate
will be very low. In fact if condensation is occurring within a wall behind a vapour barrier then latent heat
will be released and surface warming may occur and completely be ignored or misinterpreted as a non-
moisture condition by an unsuspecting and untrained inspector.
Detection of interstitial water within a wall or roof assembly is much more complex than the process of
water evaporating from an exterior or interior surface exposed to free air. Many wall and roof systems
have unintentionally created two or more vapour retardant barriers which inhibits the drying process. This
raises the vapour pressure within the assembly, and inhibits evaporative cooling as a means of detection.
Ironically this situation creates enclosure issues which the investigator is often tasked with finding. In this
case, the thermographer must rely on a steady state conductivity change between wet and dry material; a
heat capacity change between wet and dry material (under transient state); or the special thermal and moisture
conditions required for one of the four phase changes.
Thermographic cameras are extremely sensitive, often able to detect differences less than 0.05ºC (50mK).
But while this may create a clearer, more defined pattern when the thermal conditions are right, it is not a
viable substitute for moisture detection under poor thermodynamic conditions, and/or when moisture is
buried deep within an enclosure. High sensitivity cameras used under less than ideal conditions can lead to
a large number of false positives, and/or lengthy field time for verification using other methods. False
12 CCBST 2014 Proceedings Book_v10 A6 403-438_Layout 1 14-10-17 4:08 PM Page 434
4 3 5
14TH CANADIAN CONFERENCE ON BUILDING SCIENCE AND TECHNOLOGY
negatives lead to credibility issues of both the inspector and the thermographic industry as well as the
possibilities of litigation, particularly when mold or other damage associated with the moister is present but
not detected.
Since moisture detection is not covered in much detail by any standard, a general assumption could be that
the requirements for camera performance are at least equal to those for detection of conductive anomalies.
The current consensus in the industry however, is that moisture detection necessitates a higher level of
thermal sensitivity. Most manufacturers have accommodated this by producing “building” model of IR
cameras with an NETD of at least 0.08ºC (80mK) or better. It is likely that any future standards developed
for moisture detection will require at least this level of sensitivity. Spatial requirements are likely to remain
the same as for conductive anomaly detection. The NMS standard is the only specification which itemizes
certain conditions for the detection of moisture. The standard requires a minimum 20ºC (temperature) and
25Pa (pressure) difference from the inside to the outside and 30ºC difference when the pressure difference
is less than 10Pa.
The Special Case of Low Slope Roof Moisture Detection
Both ASTM C1153-10 and NMS 022716 standards detail the conditions necessary for detection of moisture
trapped in conventional low slope built-up roofing systems. Interstitial moisture is detected using the
capacitive method of detection by observing the outside roof surface under transient conditions. Ideal
conditions are a warm sunny day with low wind, and no moisture on the roof surface. Inspection takes place
1 to 2 hours after the direct sunlight has left the roof surface and is conducted into the night. Potential wet
areas are identified as warm areas that have retained the solar heat gained during the day. Both standards
also permit investigations to be performed using the conductive method of inspection under steady state
heat loss conditions with a minimum differential of 10ºC (ASTM) or 15ºC (NMS) across the enclosure. In
all cases, and with both standards, the thermographer must be aware of inside conditions, fixtures and
appliances and no standing water should be present on the roof surface.
CONCLUSIONS
Thermography can play a significant role as a non destructive and rapid screening tool to identify potential
heat, air, and moisture related anomalies in large and small buildings, but only if the thermodynamic
12 CCBST 2014 Proceedings Book_v10 A6 403-438_Layout 1 14-10-17 4:08 PM Page 435
4 3 6
14TH CANADIAN CONFERENCE ON BUILDING SCIENCE AND TECHNOLOGY
conditions are right. Thermographic results alone cannot quantify excessive heat flow, air flow, or moisture
content. The primary use for thermography should as a qualitative investigative tool, identifying potential
areas for further investigation, validation and quantification by other means. Any quantitative thermographic
analysis should be limited to that of temperature measurement and/or potential percentage area affected.
Thermographic investigations should be limited to those environmental conditions, procedures, and methods
specified and recommended by various standards established by recognized independent bodies. Standards
for utilizing thermography for conductive and air leakage studies are well established and should be adhered
to. These are summarized in Table 1. But, because of a lack of current standards for moisture detection, it
should be done carefully and with a specific methodology for detection (conduction, capacitance or phase
change) appropriate for the materials, assembly and environmental conditions. This is summarized in Table
2. Home inspectors, for example, could apply a thermal camera in a limited scope for free-air detection of
water related anomalies, so long as they have a specific Standard of Practice detailing the method and
conditions necessary for doing so and a means (e.g. a moisture detector) for immediate field confirmation
of the suspected anomaly.
IR cameras suitable for building investigations are now inexpensive, lightweight and easy to use. There are,
however, cameras available which do not even come close to meeting the requirements of the current well
established standards for detection of heat, air and/or moisture anomalies. One should ensure that before a
camera is purchased, or a contract for services engaged, that a camera and thermographer meet the minimum
requirements of the appropriate standard for the task.
All standards emphasize the importance of training and certification related to not just the camera and
infrared detection principles, but more importantly knowledge of building construction, performance, and
sound building science principles. The proliferation of readily available low cost cameras used by
unqualified persons unaware of the underlying thermodynamic principles, appropriate methods, and
limitations could jeopardize the legitimate value of thermography as a valuable tool for the building
diagnostic industry.
12 CCBST 2014 Proceedings Book_v10 A6 403-438_Layout 1 14-10-17 4:08 PM Page 436
4 3 7
14TH CANADIAN CONFERENCE ON BUILDING SCIENCE AND TECHNOLOGY
12 CCBST 2014 Proceedings Book_v10 A6 403-438_Layout 1 14-10-17 4:08 PM Page 437
4 3 8
14TH CANADIAN CONFERENCE ON BUILDING SCIENCE AND TECHNOLOGY
REFERENCES
Incropera, F.P, Dewitt, D.P. Fundamentals of Heat and Mass Transfer, Fourth Edition, 1996, John Wiley
and Sons, ISBN 0-471-30460-3, Pages 4-5.
ASTM C1060-90. “Standard Practice for Thermographic Inspection of Insulation Installations in
Envelope Cavities of Frame Buildings”, ASTM International, www.astm.org
ISO 6781 Thermal Insulation - Qualitative Detection of Thermal Irregularities in Building Envelopes -
Infrared Method, International Standards Organization, www.iso.org
RESNET Revised Interim Guidelines for Thermographic Inspections of Buildings, 2012,
http://www.resnet.us/board/Results_of_Electronic_Ballot_of_RESNET_Board_on_Adopting_IR_Interim_
Guidelines.pdf
NMS 022713 Thermographic Assessment - Building Envelope, 2007, National Master Specifications of
Canada, www.tpsgc-pwgsc.gc.ca
ASNT Recommended Practice No. SNT-TC-1A: Personnel Qualification and Certification in
Nondestructive Testing 2011, American Society for Non-Destructive Testing, www.asnt.org
ISO/DIS 6781-3 Performance of buildings - Detection of heat, air and moisture irregularities in
buildings by infrared methods - Part 3: Qualifications of Equipment Operators, Data Analysts and Report
Writers, 2013, International Standards Organization, www.iso.org
ASTM Standard C1046 - 95 Standard Practice for In-Situ Measurement of Heat Flux and Temperature on
Building Envelope Components, 2007, ASTM International, www.astm.org
ASTM Standard C1155 – 95 Standard Practice for Determining Thermal Resistance of Building Envelope
Components from the In-Situ Data, 2007 ASTM International, www.astm.org
DeWitt, D.P, and Nutter, Gene D. Theory & Practice of Radiation Thermometry. Chapter 20: “The
application of thermography for industrial and building energy management”; McIntosh, G.B. and Mill,
P.A.D. Pages 1076 -1081, Wiley Interscience, New York City, 1988. ISBN 0-471-61018-6
Mill, P.A.D. “Thermographic Diagnosis of Building Envelope Deficiencies, Fathers of Confederation
Center, Report Series No. 28”, Public Works Canada, 1979, ISBN 0-662-50335-X, Pgs 34 to 37.
ASHRAE, Handbook of Fundamentals, Chapter 25, Table 1, vertical surface, still air, emissivity=0.9,
horizontal heat flow, 2001, The American Society of Heating, Refrigeration, and Air Conditioning
Engineers,
Stainton, W.D., Quantitative Interpretation of Building Thermograms, Proceedings 4th
Biennial Infrared
Information Exchange, 1978, AGA Corporation, Pine Brook , NJ,
Mill, P.A.D, Kaplan, A.G. , A Generic Methodology for Thermographic Diagnosis of Building Enclosures,
Report Series No. 30, Public Works Canada, 1982, ISBN 0-662-521-55-2, Pgs 8 to 9.
ASTM Standard E1186–03, Standard Practices for Air Leakage Site Detection in Building Envelopes and
Air Barrier Systems, 2009, International, www.astm.org
ASTM C1153-10 Standard Practice for Location of Wet Insulation in Roofing Systems Using Infrared
Imaging,2010, www.astm.org
NMS 022616, Thermographic Assessment - Roof, 2007, National Master Specifications of Canada
12 CCBST 2014 Proceedings Book_v10 A6 403-438_Layout 1 14-10-17 4:08 PM Page 438

More Related Content

What's hot

13. r stud - rdh 10935-000 - r-stud astm c177 laboratory testing report - 170213
13. r stud - rdh 10935-000 - r-stud astm c177 laboratory testing report - 17021313. r stud - rdh 10935-000 - r-stud astm c177 laboratory testing report - 170213
13. r stud - rdh 10935-000 - r-stud astm c177 laboratory testing report - 170213J. Patrick Lucas
 
Design and Analysis of Fin-X Technology
Design and Analysis of Fin-X Technology Design and Analysis of Fin-X Technology
Design and Analysis of Fin-X Technology Nitish Sharma
 
Chap5 space heat load calculations
Chap5 space heat load  calculationsChap5 space heat load  calculations
Chap5 space heat load calculationsCharlton Inao
 
Gifford,Hoffie_ConvCalibrHeatFluxGages
Gifford,Hoffie_ConvCalibrHeatFluxGagesGifford,Hoffie_ConvCalibrHeatFluxGages
Gifford,Hoffie_ConvCalibrHeatFluxGagesAndreas F. Hoffie
 
IRJET - Numerical Analysis on Laminar Flow Forced Convection on a Channel wi...
 IRJET - Numerical Analysis on Laminar Flow Forced Convection on a Channel wi... IRJET - Numerical Analysis on Laminar Flow Forced Convection on a Channel wi...
IRJET - Numerical Analysis on Laminar Flow Forced Convection on a Channel wi...IRJET Journal
 
Investigation of Different Types of Cement Material on Thermal Properties of ...
Investigation of Different Types of Cement Material on Thermal Properties of ...Investigation of Different Types of Cement Material on Thermal Properties of ...
Investigation of Different Types of Cement Material on Thermal Properties of ...IJERA Editor
 
Analysis of Coiled-Tube Heat Exchangers to Improve Heat Transfer Rate With Sp...
Analysis of Coiled-Tube Heat Exchangers to Improve Heat Transfer Rate With Sp...Analysis of Coiled-Tube Heat Exchangers to Improve Heat Transfer Rate With Sp...
Analysis of Coiled-Tube Heat Exchangers to Improve Heat Transfer Rate With Sp...IJMER
 
STUDY OF HEAT TRANSFER ON BROKEN ARC ROUGHNESS ELEMENTS ON THE ABSORBER PLATE...
STUDY OF HEAT TRANSFER ON BROKEN ARC ROUGHNESS ELEMENTS ON THE ABSORBER PLATE...STUDY OF HEAT TRANSFER ON BROKEN ARC ROUGHNESS ELEMENTS ON THE ABSORBER PLATE...
STUDY OF HEAT TRANSFER ON BROKEN ARC ROUGHNESS ELEMENTS ON THE ABSORBER PLATE...IAEME Publication
 
IRJET- Natural Convection Heat Transfer from Horizontal Rectangular Fin Array...
IRJET- Natural Convection Heat Transfer from Horizontal Rectangular Fin Array...IRJET- Natural Convection Heat Transfer from Horizontal Rectangular Fin Array...
IRJET- Natural Convection Heat Transfer from Horizontal Rectangular Fin Array...IRJET Journal
 
Climatology Applied To Architecture: An Experimental Investigation about Inte...
Climatology Applied To Architecture: An Experimental Investigation about Inte...Climatology Applied To Architecture: An Experimental Investigation about Inte...
Climatology Applied To Architecture: An Experimental Investigation about Inte...IJERA Editor
 
GEF Thermal Tech Paper Final 040501
GEF Thermal Tech Paper Final 040501GEF Thermal Tech Paper Final 040501
GEF Thermal Tech Paper Final 040501Martin Peltz
 
Experimental Investigation of Heat Transfer through Rectangular and Trapezoid...
Experimental Investigation of Heat Transfer through Rectangular and Trapezoid...Experimental Investigation of Heat Transfer through Rectangular and Trapezoid...
Experimental Investigation of Heat Transfer through Rectangular and Trapezoid...IRJET Journal
 
HEAT TRANSFER CO EFFICIENT VS HEAT FLOW RATE BY FORCED CONVECTION
HEAT TRANSFER CO EFFICIENT VS HEAT FLOW RATE BY FORCED CONVECTIONHEAT TRANSFER CO EFFICIENT VS HEAT FLOW RATE BY FORCED CONVECTION
HEAT TRANSFER CO EFFICIENT VS HEAT FLOW RATE BY FORCED CONVECTIONTajammul Kamal
 
New Methods to Spatially Extend Thermal Response Test Assessments
New Methods to Spatially Extend Thermal Response Test AssessmentsNew Methods to Spatially Extend Thermal Response Test Assessments
New Methods to Spatially Extend Thermal Response Test AssessmentsJasmin Raymond
 
Optimizing ground heat exchanger length with GeoperformX pipe
Optimizing ground heat exchanger length with  GeoperformX pipeOptimizing ground heat exchanger length with  GeoperformX pipe
Optimizing ground heat exchanger length with GeoperformX pipeJasmin Raymond
 
Cfd and conjugate heat transfer analysis of heat sinks with different fin geo...
Cfd and conjugate heat transfer analysis of heat sinks with different fin geo...Cfd and conjugate heat transfer analysis of heat sinks with different fin geo...
Cfd and conjugate heat transfer analysis of heat sinks with different fin geo...eSAT Journals
 
Insights from field experiments to conduct thermal response tests with heatin...
Insights from field experiments to conduct thermal response tests with heatin...Insights from field experiments to conduct thermal response tests with heatin...
Insights from field experiments to conduct thermal response tests with heatin...Jasmin Raymond
 

What's hot (20)

13. r stud - rdh 10935-000 - r-stud astm c177 laboratory testing report - 170213
13. r stud - rdh 10935-000 - r-stud astm c177 laboratory testing report - 17021313. r stud - rdh 10935-000 - r-stud astm c177 laboratory testing report - 170213
13. r stud - rdh 10935-000 - r-stud astm c177 laboratory testing report - 170213
 
I0412075080
I0412075080I0412075080
I0412075080
 
Ijmet 10 01_122
Ijmet 10 01_122Ijmet 10 01_122
Ijmet 10 01_122
 
Design and Analysis of Fin-X Technology
Design and Analysis of Fin-X Technology Design and Analysis of Fin-X Technology
Design and Analysis of Fin-X Technology
 
Chap5 space heat load calculations
Chap5 space heat load  calculationsChap5 space heat load  calculations
Chap5 space heat load calculations
 
Gifford,Hoffie_ConvCalibrHeatFluxGages
Gifford,Hoffie_ConvCalibrHeatFluxGagesGifford,Hoffie_ConvCalibrHeatFluxGages
Gifford,Hoffie_ConvCalibrHeatFluxGages
 
IRJET - Numerical Analysis on Laminar Flow Forced Convection on a Channel wi...
 IRJET - Numerical Analysis on Laminar Flow Forced Convection on a Channel wi... IRJET - Numerical Analysis on Laminar Flow Forced Convection on a Channel wi...
IRJET - Numerical Analysis on Laminar Flow Forced Convection on a Channel wi...
 
Investigation of Different Types of Cement Material on Thermal Properties of ...
Investigation of Different Types of Cement Material on Thermal Properties of ...Investigation of Different Types of Cement Material on Thermal Properties of ...
Investigation of Different Types of Cement Material on Thermal Properties of ...
 
Analysis of Coiled-Tube Heat Exchangers to Improve Heat Transfer Rate With Sp...
Analysis of Coiled-Tube Heat Exchangers to Improve Heat Transfer Rate With Sp...Analysis of Coiled-Tube Heat Exchangers to Improve Heat Transfer Rate With Sp...
Analysis of Coiled-Tube Heat Exchangers to Improve Heat Transfer Rate With Sp...
 
STUDY OF HEAT TRANSFER ON BROKEN ARC ROUGHNESS ELEMENTS ON THE ABSORBER PLATE...
STUDY OF HEAT TRANSFER ON BROKEN ARC ROUGHNESS ELEMENTS ON THE ABSORBER PLATE...STUDY OF HEAT TRANSFER ON BROKEN ARC ROUGHNESS ELEMENTS ON THE ABSORBER PLATE...
STUDY OF HEAT TRANSFER ON BROKEN ARC ROUGHNESS ELEMENTS ON THE ABSORBER PLATE...
 
IRJET- Natural Convection Heat Transfer from Horizontal Rectangular Fin Array...
IRJET- Natural Convection Heat Transfer from Horizontal Rectangular Fin Array...IRJET- Natural Convection Heat Transfer from Horizontal Rectangular Fin Array...
IRJET- Natural Convection Heat Transfer from Horizontal Rectangular Fin Array...
 
Climatology Applied To Architecture: An Experimental Investigation about Inte...
Climatology Applied To Architecture: An Experimental Investigation about Inte...Climatology Applied To Architecture: An Experimental Investigation about Inte...
Climatology Applied To Architecture: An Experimental Investigation about Inte...
 
GEF Thermal Tech Paper Final 040501
GEF Thermal Tech Paper Final 040501GEF Thermal Tech Paper Final 040501
GEF Thermal Tech Paper Final 040501
 
Experimental Investigation of Heat Transfer through Rectangular and Trapezoid...
Experimental Investigation of Heat Transfer through Rectangular and Trapezoid...Experimental Investigation of Heat Transfer through Rectangular and Trapezoid...
Experimental Investigation of Heat Transfer through Rectangular and Trapezoid...
 
HEAT TRANSFER CO EFFICIENT VS HEAT FLOW RATE BY FORCED CONVECTION
HEAT TRANSFER CO EFFICIENT VS HEAT FLOW RATE BY FORCED CONVECTIONHEAT TRANSFER CO EFFICIENT VS HEAT FLOW RATE BY FORCED CONVECTION
HEAT TRANSFER CO EFFICIENT VS HEAT FLOW RATE BY FORCED CONVECTION
 
New Methods to Spatially Extend Thermal Response Test Assessments
New Methods to Spatially Extend Thermal Response Test AssessmentsNew Methods to Spatially Extend Thermal Response Test Assessments
New Methods to Spatially Extend Thermal Response Test Assessments
 
Optimizing ground heat exchanger length with GeoperformX pipe
Optimizing ground heat exchanger length with  GeoperformX pipeOptimizing ground heat exchanger length with  GeoperformX pipe
Optimizing ground heat exchanger length with GeoperformX pipe
 
Cfd and conjugate heat transfer analysis of heat sinks with different fin geo...
Cfd and conjugate heat transfer analysis of heat sinks with different fin geo...Cfd and conjugate heat transfer analysis of heat sinks with different fin geo...
Cfd and conjugate heat transfer analysis of heat sinks with different fin geo...
 
Ld35191119013
Ld35191119013Ld35191119013
Ld35191119013
 
Insights from field experiments to conduct thermal response tests with heatin...
Insights from field experiments to conduct thermal response tests with heatin...Insights from field experiments to conduct thermal response tests with heatin...
Insights from field experiments to conduct thermal response tests with heatin...
 

Similar to Detecting Thermal Anomalies in Building Envelopes Using Infrared Thermography

Vishwakarma-MicroEng2015
Vishwakarma-MicroEng2015Vishwakarma-MicroEng2015
Vishwakarma-MicroEng2015Chirag Waghela
 
IRJET- Thermal Analysis on Solar Air Heater Duct
IRJET- Thermal Analysis on Solar Air Heater DuctIRJET- Thermal Analysis on Solar Air Heater Duct
IRJET- Thermal Analysis on Solar Air Heater DuctIRJET Journal
 
Tagliatela College of EngineeringEASC1112 – Methods of Engineeri.docx
Tagliatela College of EngineeringEASC1112 – Methods of Engineeri.docxTagliatela College of EngineeringEASC1112 – Methods of Engineeri.docx
Tagliatela College of EngineeringEASC1112 – Methods of Engineeri.docxssuserf9c51d
 
Thermal Interface Materials (TIMs): Conudction, Convection, Resistance
Thermal Interface Materials (TIMs): Conudction, Convection, ResistanceThermal Interface Materials (TIMs): Conudction, Convection, Resistance
Thermal Interface Materials (TIMs): Conudction, Convection, ResistanceDomestic PCB Fabrication
 
Thermal simulation report
Thermal simulation reportThermal simulation report
Thermal simulation reportDion Marsh
 
A Study on Stochastic Thermal Characterization of Electronic Packages
A Study on Stochastic Thermal Characterization of Electronic PackagesA Study on Stochastic Thermal Characterization of Electronic Packages
A Study on Stochastic Thermal Characterization of Electronic PackagesIJERA Editor
 
Combining Infrared Thermography and Numerical Analysis for Evaluating Thermal...
Combining Infrared Thermography and Numerical Analysis for Evaluating Thermal...Combining Infrared Thermography and Numerical Analysis for Evaluating Thermal...
Combining Infrared Thermography and Numerical Analysis for Evaluating Thermal...IJERA Editor
 
DSC- Basics PPT.ppt
DSC- Basics PPT.pptDSC- Basics PPT.ppt
DSC- Basics PPT.pptDHAYALK1
 
IRJET- Design and Fabrication of Thermo Acoustic Refrigerator
IRJET- Design and Fabrication of Thermo Acoustic RefrigeratorIRJET- Design and Fabrication of Thermo Acoustic Refrigerator
IRJET- Design and Fabrication of Thermo Acoustic RefrigeratorIRJET Journal
 
CFD Simulation of Thermo Acoustic Cooling
CFD Simulation of Thermo Acoustic CoolingCFD Simulation of Thermo Acoustic Cooling
CFD Simulation of Thermo Acoustic CoolingIRJEETJournal
 
DESIGN AND FABRICATION OF THERMO ACOUSTIC REFRIGERATOR
DESIGN AND FABRICATION OF THERMO ACOUSTIC REFRIGERATORDESIGN AND FABRICATION OF THERMO ACOUSTIC REFRIGERATOR
DESIGN AND FABRICATION OF THERMO ACOUSTIC REFRIGERATORP singh
 
Analytical Thermal Circuit Fastwarm Cathodes
Analytical Thermal Circuit Fastwarm CathodesAnalytical Thermal Circuit Fastwarm Cathodes
Analytical Thermal Circuit Fastwarm CathodesTMD Technologies Limited
 
Cooling and heating load calculations tide load4z
Cooling and heating load calculations tide load4zCooling and heating load calculations tide load4z
Cooling and heating load calculations tide load4zTin Arboladura
 
Experimental and computational investigation of low cost standing wave thermo...
Experimental and computational investigation of low cost standing wave thermo...Experimental and computational investigation of low cost standing wave thermo...
Experimental and computational investigation of low cost standing wave thermo...IAEME Publication
 
Experimental and computational investigation of low cost standing wave thermo...
Experimental and computational investigation of low cost standing wave thermo...Experimental and computational investigation of low cost standing wave thermo...
Experimental and computational investigation of low cost standing wave thermo...IAEME Publication
 

Similar to Detecting Thermal Anomalies in Building Envelopes Using Infrared Thermography (20)

Ht 7
Ht 7Ht 7
Ht 7
 
Vishwakarma-MicroEng2015
Vishwakarma-MicroEng2015Vishwakarma-MicroEng2015
Vishwakarma-MicroEng2015
 
4 p.vijaya
4 p.vijaya4 p.vijaya
4 p.vijaya
 
IRJET- Thermal Analysis on Solar Air Heater Duct
IRJET- Thermal Analysis on Solar Air Heater DuctIRJET- Thermal Analysis on Solar Air Heater Duct
IRJET- Thermal Analysis on Solar Air Heater Duct
 
Tagliatela College of EngineeringEASC1112 – Methods of Engineeri.docx
Tagliatela College of EngineeringEASC1112 – Methods of Engineeri.docxTagliatela College of EngineeringEASC1112 – Methods of Engineeri.docx
Tagliatela College of EngineeringEASC1112 – Methods of Engineeri.docx
 
Thermal Interface Materials (TIMs): Conudction, Convection, Resistance
Thermal Interface Materials (TIMs): Conudction, Convection, ResistanceThermal Interface Materials (TIMs): Conudction, Convection, Resistance
Thermal Interface Materials (TIMs): Conudction, Convection, Resistance
 
Thermal simulation report
Thermal simulation reportThermal simulation report
Thermal simulation report
 
A Study on Stochastic Thermal Characterization of Electronic Packages
A Study on Stochastic Thermal Characterization of Electronic PackagesA Study on Stochastic Thermal Characterization of Electronic Packages
A Study on Stochastic Thermal Characterization of Electronic Packages
 
Combining Infrared Thermography and Numerical Analysis for Evaluating Thermal...
Combining Infrared Thermography and Numerical Analysis for Evaluating Thermal...Combining Infrared Thermography and Numerical Analysis for Evaluating Thermal...
Combining Infrared Thermography and Numerical Analysis for Evaluating Thermal...
 
DSC- Basics PPT.ppt
DSC- Basics PPT.pptDSC- Basics PPT.ppt
DSC- Basics PPT.ppt
 
IRJET- Design and Fabrication of Thermo Acoustic Refrigerator
IRJET- Design and Fabrication of Thermo Acoustic RefrigeratorIRJET- Design and Fabrication of Thermo Acoustic Refrigerator
IRJET- Design and Fabrication of Thermo Acoustic Refrigerator
 
CFD Simulation of Thermo Acoustic Cooling
CFD Simulation of Thermo Acoustic CoolingCFD Simulation of Thermo Acoustic Cooling
CFD Simulation of Thermo Acoustic Cooling
 
DESIGN AND FABRICATION OF THERMO ACOUSTIC REFRIGERATOR
DESIGN AND FABRICATION OF THERMO ACOUSTIC REFRIGERATORDESIGN AND FABRICATION OF THERMO ACOUSTIC REFRIGERATOR
DESIGN AND FABRICATION OF THERMO ACOUSTIC REFRIGERATOR
 
Analytical Thermal Circuit Fastwarm Cathodes
Analytical Thermal Circuit Fastwarm CathodesAnalytical Thermal Circuit Fastwarm Cathodes
Analytical Thermal Circuit Fastwarm Cathodes
 
Cooling and heating load calculations tide load4z
Cooling and heating load calculations tide load4zCooling and heating load calculations tide load4z
Cooling and heating load calculations tide load4z
 
Experimental and computational investigation of low cost standing wave thermo...
Experimental and computational investigation of low cost standing wave thermo...Experimental and computational investigation of low cost standing wave thermo...
Experimental and computational investigation of low cost standing wave thermo...
 
Experimental and computational investigation of low cost standing wave thermo...
Experimental and computational investigation of low cost standing wave thermo...Experimental and computational investigation of low cost standing wave thermo...
Experimental and computational investigation of low cost standing wave thermo...
 
Ceiling Radiant Cooling Panels as a Viable Distributed Parallel Sensible Co...
Ceiling Radiant Cooling Panels as a  Viable Distributed Parallel Sensible  Co...Ceiling Radiant Cooling Panels as a  Viable Distributed Parallel Sensible  Co...
Ceiling Radiant Cooling Panels as a Viable Distributed Parallel Sensible Co...
 
Differential Thermal Analysis & Differential Scanning Calorimetry
Differential Thermal Analysis & Differential Scanning CalorimetryDifferential Thermal Analysis & Differential Scanning Calorimetry
Differential Thermal Analysis & Differential Scanning Calorimetry
 
A Pitched Roof with Forced Ventilation to Limit Solar Gains_Crimson Publishers
A Pitched Roof with Forced Ventilation to Limit Solar Gains_Crimson PublishersA Pitched Roof with Forced Ventilation to Limit Solar Gains_Crimson Publishers
A Pitched Roof with Forced Ventilation to Limit Solar Gains_Crimson Publishers
 

More from John Kingsley

Get yourself trained or Certified for IEC 62443 and other trainings.pdf
Get yourself trained or Certified for IEC 62443 and other trainings.pdfGet yourself trained or Certified for IEC 62443 and other trainings.pdf
Get yourself trained or Certified for IEC 62443 and other trainings.pdfJohn Kingsley
 
MODIFICATION OF EXISTING FACILITIES FOR 20% ETHANOL BLENDING
MODIFICATION OF EXISTING FACILITIES FOR 20% ETHANOL BLENDINGMODIFICATION OF EXISTING FACILITIES FOR 20% ETHANOL BLENDING
MODIFICATION OF EXISTING FACILITIES FOR 20% ETHANOL BLENDINGJohn Kingsley
 
Reliability, availability, maintainability (RAM) study, on reciprocating comp...
Reliability, availability, maintainability (RAM) study, on reciprocating comp...Reliability, availability, maintainability (RAM) study, on reciprocating comp...
Reliability, availability, maintainability (RAM) study, on reciprocating comp...John Kingsley
 
Introduction to oil and gas exploration and processing
Introduction to oil and gas exploration and processingIntroduction to oil and gas exploration and processing
Introduction to oil and gas exploration and processingJohn Kingsley
 
iFluids Engineering Introduction
iFluids Engineering IntroductioniFluids Engineering Introduction
iFluids Engineering IntroductionJohn Kingsley
 
iFluids Engineering Brochure
iFluids Engineering BrochureiFluids Engineering Brochure
iFluids Engineering BrochureJohn Kingsley
 
iFluids Engienering Capability Presentation
iFluids Engienering Capability PresentationiFluids Engienering Capability Presentation
iFluids Engienering Capability PresentationJohn Kingsley
 
Hazop Training - Intermediate Level Course iFluids
Hazop Training  -  Intermediate Level Course iFluidsHazop Training  -  Intermediate Level Course iFluids
Hazop Training - Intermediate Level Course iFluidsJohn Kingsley
 
Introduction to PSM Online Interactive Training
Introduction to PSM Online Interactive TrainingIntroduction to PSM Online Interactive Training
Introduction to PSM Online Interactive TrainingJohn Kingsley
 
Sil assessment Risk Graph and LOPA Training iFluids
Sil assessment Risk Graph and LOPA Training iFluidsSil assessment Risk Graph and LOPA Training iFluids
Sil assessment Risk Graph and LOPA Training iFluidsJohn Kingsley
 
Hazop Fundamentals Online Training iFluids
Hazop Fundamentals Online Training iFluidsHazop Fundamentals Online Training iFluids
Hazop Fundamentals Online Training iFluidsJohn Kingsley
 
John kingsley OT ICS SCADA Cyber security consultant
John kingsley OT ICS SCADA Cyber security consultantJohn kingsley OT ICS SCADA Cyber security consultant
John kingsley OT ICS SCADA Cyber security consultantJohn Kingsley
 
iFluids Lean Six Sigma Case Study oil & gas
iFluids Lean Six Sigma Case Study oil & gasiFluids Lean Six Sigma Case Study oil & gas
iFluids Lean Six Sigma Case Study oil & gasJohn Kingsley
 
iFluids Behaviour based safety services and training
iFluids Behaviour based safety services and trainingiFluids Behaviour based safety services and training
iFluids Behaviour based safety services and trainingJohn Kingsley
 
iFluids Tank Inspection services
iFluids Tank Inspection servicesiFluids Tank Inspection services
iFluids Tank Inspection servicesJohn Kingsley
 
iFluids Cybersecurity Seminar CIC Qatar 2018 Agenda
iFluids Cybersecurity Seminar  CIC Qatar 2018 AgendaiFluids Cybersecurity Seminar  CIC Qatar 2018 Agenda
iFluids Cybersecurity Seminar CIC Qatar 2018 AgendaJohn Kingsley
 
How to write a plant operating manual
How to write a plant operating manualHow to write a plant operating manual
How to write a plant operating manualJohn Kingsley
 
Case study of dcs upgrade how to reduce stress during execution
Case study of dcs upgrade how to reduce stress during executionCase study of dcs upgrade how to reduce stress during execution
Case study of dcs upgrade how to reduce stress during executionJohn Kingsley
 
Hydrocarbon leak detection in tank farms
Hydrocarbon leak detection in tank farmsHydrocarbon leak detection in tank farms
Hydrocarbon leak detection in tank farmsJohn Kingsley
 
Guide to specifying visual signals
Guide to specifying visual signalsGuide to specifying visual signals
Guide to specifying visual signalsJohn Kingsley
 

More from John Kingsley (20)

Get yourself trained or Certified for IEC 62443 and other trainings.pdf
Get yourself trained or Certified for IEC 62443 and other trainings.pdfGet yourself trained or Certified for IEC 62443 and other trainings.pdf
Get yourself trained or Certified for IEC 62443 and other trainings.pdf
 
MODIFICATION OF EXISTING FACILITIES FOR 20% ETHANOL BLENDING
MODIFICATION OF EXISTING FACILITIES FOR 20% ETHANOL BLENDINGMODIFICATION OF EXISTING FACILITIES FOR 20% ETHANOL BLENDING
MODIFICATION OF EXISTING FACILITIES FOR 20% ETHANOL BLENDING
 
Reliability, availability, maintainability (RAM) study, on reciprocating comp...
Reliability, availability, maintainability (RAM) study, on reciprocating comp...Reliability, availability, maintainability (RAM) study, on reciprocating comp...
Reliability, availability, maintainability (RAM) study, on reciprocating comp...
 
Introduction to oil and gas exploration and processing
Introduction to oil and gas exploration and processingIntroduction to oil and gas exploration and processing
Introduction to oil and gas exploration and processing
 
iFluids Engineering Introduction
iFluids Engineering IntroductioniFluids Engineering Introduction
iFluids Engineering Introduction
 
iFluids Engineering Brochure
iFluids Engineering BrochureiFluids Engineering Brochure
iFluids Engineering Brochure
 
iFluids Engienering Capability Presentation
iFluids Engienering Capability PresentationiFluids Engienering Capability Presentation
iFluids Engienering Capability Presentation
 
Hazop Training - Intermediate Level Course iFluids
Hazop Training  -  Intermediate Level Course iFluidsHazop Training  -  Intermediate Level Course iFluids
Hazop Training - Intermediate Level Course iFluids
 
Introduction to PSM Online Interactive Training
Introduction to PSM Online Interactive TrainingIntroduction to PSM Online Interactive Training
Introduction to PSM Online Interactive Training
 
Sil assessment Risk Graph and LOPA Training iFluids
Sil assessment Risk Graph and LOPA Training iFluidsSil assessment Risk Graph and LOPA Training iFluids
Sil assessment Risk Graph and LOPA Training iFluids
 
Hazop Fundamentals Online Training iFluids
Hazop Fundamentals Online Training iFluidsHazop Fundamentals Online Training iFluids
Hazop Fundamentals Online Training iFluids
 
John kingsley OT ICS SCADA Cyber security consultant
John kingsley OT ICS SCADA Cyber security consultantJohn kingsley OT ICS SCADA Cyber security consultant
John kingsley OT ICS SCADA Cyber security consultant
 
iFluids Lean Six Sigma Case Study oil & gas
iFluids Lean Six Sigma Case Study oil & gasiFluids Lean Six Sigma Case Study oil & gas
iFluids Lean Six Sigma Case Study oil & gas
 
iFluids Behaviour based safety services and training
iFluids Behaviour based safety services and trainingiFluids Behaviour based safety services and training
iFluids Behaviour based safety services and training
 
iFluids Tank Inspection services
iFluids Tank Inspection servicesiFluids Tank Inspection services
iFluids Tank Inspection services
 
iFluids Cybersecurity Seminar CIC Qatar 2018 Agenda
iFluids Cybersecurity Seminar  CIC Qatar 2018 AgendaiFluids Cybersecurity Seminar  CIC Qatar 2018 Agenda
iFluids Cybersecurity Seminar CIC Qatar 2018 Agenda
 
How to write a plant operating manual
How to write a plant operating manualHow to write a plant operating manual
How to write a plant operating manual
 
Case study of dcs upgrade how to reduce stress during execution
Case study of dcs upgrade how to reduce stress during executionCase study of dcs upgrade how to reduce stress during execution
Case study of dcs upgrade how to reduce stress during execution
 
Hydrocarbon leak detection in tank farms
Hydrocarbon leak detection in tank farmsHydrocarbon leak detection in tank farms
Hydrocarbon leak detection in tank farms
 
Guide to specifying visual signals
Guide to specifying visual signalsGuide to specifying visual signals
Guide to specifying visual signals
 

Recently uploaded

Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...ranjana rawat
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...roncy bisnoi
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSISrknatarajan
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college projectTonystark477637
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Call Girls in Nagpur High Profile
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performancesivaprakash250
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordAsst.prof M.Gokilavani
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Dr.Costas Sachpazis
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduitsrknatarajan
 

Recently uploaded (20)

Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSIS
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college project
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduits
 

Detecting Thermal Anomalies in Building Envelopes Using Infrared Thermography

  • 1. 4 2 9 14TH CANADIAN CONFERENCE ON BUILDING SCIENCE AND TECHNOLOGY PRACTICAL ISSUES ASSOICATED WITH THE USE OF INFRARED THERMOGRAPHY FOR DETECTION OF HEAT, AIR AND MOISTURE DEFICIENCIES IN BUILDING ENVELOPES G. B. McIntosh ABSTRACT Thermal infrared cameras have been used for more than 40 years in helping diagnose problems related to heat, air or moisture deficiencies in buildings. But in the past 10 years significant advances have been made in the performance, size, weight and cost reduction of cameras to the point where entry level cameras suitable for some building investigations, are less than $3,000, and in coming years will be even less expensive. This has led to the proliferation of its use as a building diagnostic tool. Unfortunately this has also led to the misunderstanding of how this technology should be properly utilized, and the mis-belief that there is such a thing as an “all-in-one” building diagnostic scan, and/or that an investigation can be performed any time of day or year. Irrespective of how good the camera performance is, there are different minimum environmental conditions and specific inspection methodologies required for the reliable detection of heat, air and moisture problems for various types of construction. In addition, while thermography can be a very useful qualitative tool, other methods and tools must be used for quantification of actual amounts of excessive heat flow, air flow, or moisture content. This paper will discuss the limitations of utilizing thermal imaging as a building diagnostic tool, the appropriate and separate methodologies that should be employed for heat, air and moisture deficiencies, the various standards and protocols that should be followed, and the complementary quantitative and verification tools that should be used in conjunction with thermography. This paper will try to be as subjective as possible by referencing Canadian and International standards related to building inspections using thermography. This includes historical, current and in-progress standards from National Master Specifications of Canada, ASTM, RESNET and ISO. INTRODUCTION Thermography can and has been utilized in the discovery of otherwise undetectable heat, air and moisture anomalies in buildings. Unfortunately, thermography only is applicable when these anomalies affect detectable surface temperature patterns. It therefore requires suitable thermodynamic conditions sometimes unique to the environment, materials, assembly, or operation of the building in order to discover an anomaly related to a specific heat, air, or moisture deficiency. This creates limitations on the time, location, camera detection capabilities, and operator expertise required for suitable, reliable and repeatable detection. This paper will discuss practical considerations for detection of thermal anomalies in each of three categories. For each topic we will discuss the limitations, challenges and requirements for the use of this building diagnostic tool. DETECTING THERMALANOMALIES RELATED TO CONDUCTIVE HEAT TRANSFER Thermographic evaluations for conductive thermal anomalies (e.g.: insulation quantity, quality, deficiency, thermal bypasses) may be conducted in heat loss (winter) or heat gain (summer) conditions so long as there is a minimum steady state temperature difference maintained between the inside and outside of the structure. Evaluation is based upon Fourier’s law of conduction: heat flux, Q = (k/L)·ΔT (Incropera, et al, 1996). Hence any thermal anomaly detected as a surface temperature variance under constant steady state temperature 12 CCBST 2014 Proceedings Book_v10 A6 403-438_Layout 1 14-10-17 4:08 PM Page 429
  • 2. 4 3 0 14TH CANADIAN CONFERENCE ON BUILDING SCIENCE AND TECHNOLOGY difference (ΔT) must be attributable to a variance in material conductivity (k) or thickness (L). ASTM C1060, ISO 6781, and RESNET standards specify a minimum of 10º C difference across the enclosure. The Canadian National Master Specifications NMS 022713 requires a minimum difference of 15º C, although NMS standards are aimed more towards commercial and institutional buildings where buffer spaces (e.g. ceiling plenums, vented rain-screens) and thicker more complex construction is common. All standards require steady state conditions lasting at least 3 to 4 hours (longer in some standards under certain conditions) to eliminate transient surface thermal patterns influenced by material thermal capacitance storing or releasing energy. Most standards require the inspection be conducted from both interior and exterior perspectives, although most note that an interior inspection will usually provide better, more stable information, particularly in conventional construction where the insulation is typically placed closer to the interior than the exterior surfaces. Irrespective of whether it is an inside or outside inspection, transient environmental conditions, particularly those caused by solar loading and wind, may confuse actual insulation conductive performance, and/or cause conductive deficiencies to go undetected. Most standards refer to thermographic assessments as being qualitative in which different types of insulation anomalies and construction deficiencies related to thermal conduction will exhibit unique surface temperature patterns. Most standards refer to the use of a known thermal conductivity bypass (e.g. wood studs) as a qualitative thermal performance reference. In conventional wood frame construction the wood studs will exhibit a regular consistent pattern of lower performance relative to the insulation. In a normal insulated wall, when an inside wall is viewed under heat loss conditions the studs will appear cooler than the insulation (Photo 1a), while in summertime the polarity will be reversed and the studs will appear warmer than the insulation (Photo1b). Accurate quantitative heat transfer performance (conductance or equivalent R value) cannot be derived from a thermal image and/or temperature values alone. If this is desired it should be done in accordance with ASTM C1046 – 95 and ASTM C1155 – 95. The only part that thermography plays in ASTM C1046 is to determine the placement of the heat flow devices and measurements. Since the total enclosure heat loss is affected by the total surface area multiplied by the unit heat flux, then thermography can also be useful for estimating the total area affected by either one localized conductive anomaly, or the sum of repetitive anomalies. RESNET, however, is the only standard which suggests a quantitative approach of determining 12 CCBST 2014 Proceedings Book_v10 A6 403-438_Layout 1 14-10-17 4:08 PM Page 430
  • 3. 4 3 1 14TH CANADIAN CONFERENCE ON BUILDING SCIENCE AND TECHNOLOGY approximate area affected. In addition to being a difficult and time-consuming practice however, a specific threshold of surface temperature difference must be specified to define an “anomaly” to be included in the area calculation. Some thermographers approximate wall performance based upon the principle of Temperature Index (Mill, P.A.D., 1979). This index is derived from dividing the drop in temperature from the inside surface (Tis) minus the outside ambient (Toa) by the total drop in temperature from the inside ambient (Tia) minus the outside ambient (Toa), i.e.: Temperature Index = (Tis-Toa) / (Tia-Toa). It is based upon the principle that in steady state the unit heat flux transferred from the interior space to the inside wall should be equal to the heat flux conducted through a unit wall area (assuming an infinite plane). Therefore, the ratio of temperatures should be equal to the ratio of wall thermal resistance (L/k) value to the overall heat flow resistance inclusive of the inside surface resistance. Temperature Index produces a graph with a variable range of possible wall performance, since the actual field value for the inside surface resistance, (which ultimately determines Tis) may vary significantly at the time of the inspection. While ASHRAE handbook of fundamentals Table 4 suggests a design resistance value for a vertical wall of 0.120 m2 ·K/W (0.68 hr·ft2 ·F/Btu), the actual field value can vary significantly depending on air velocity, surface emissivity, orientation, and variance in the air temperature and radiant environment. On a low emissivity wall, for instance, theASHRAE value changes to 0.238 m2 ·K/W (1.35 hr·ft2 ·F/Btu). Or, if there is a 5 ft/sec air flow across the inside wall the design value changes to 0.044 m2 ·K/W (0.25 hr·ft2 ·F/Btu). Another major assumption in the use of Temperature Index is that the components of the wall are in steady state, i.e. no part of the wall is storing or releasing heat due to the material’s heat capacitance or to a phase change (e.g.: moisture within the wall enclosure). An additional error is created when there is three dimensional heat transfer taking place within the wall. This will occur on or close to thermal bridging (e.g. wood or metal studs), when there is air movement within the wall, or when there are highly diffusive materials within the wall. Due to this cumulative uncertainty, Temperature Index is not an accurate or reliable method to predict an actual quantitative performance or for calculating an accurate R value (Stainton, W.D. 1978). It is however, a reasonable method for classifying the thermal performance of a light construction (e.g. wood frame, fibreglass insulated) wall. If the wall is in steady state there can be a high confidence that the wall is in a performance category, (e.g.: very poor, poor, acceptable, good) which could justify further investigation of an anomaly, such as heat flow measurement or destructive testing respectively. Qualitative pattern assessments imply that training and experience is required in order to identify deficiencies from normal patterns, and all standards refer to training and experience requirements, although only the RESNET and NMS standards specify ASNT SNT-TC-1A compliant Level 1 thermographers for the data collection stage. NMS further requires anASNT compliant Level 2 for the assessment stage. ISO 6781/DIS- 3, a revision to the current ISO 6781 standard, is a new training and certification document which specifies comprehensive training and experience requirements for detection of heat, air and moisture anomalies in residential, commercial and institutional buildings. All standards specify a minimum theoretical detectable difference (sensitivity) for an IR camera to be 0.1º C or 100mK (Noise Equivalent Temperature Difference or NETD). Attainment in the field of this number is doubtful however, due to operator control and material emissive properties. Most standards also refer to the minimum spatial detection capabilities for interior inspections of approximately 3 milliradians (the angle subtended by an object 3mm in size at a 1m distance) specified as Instantaneous Field of View (IFOV). NMS 022713 is the most rigorous by defining the minimum detectable object size as 150mm2 (approx 12.5x12.5mm) within minimum physical minimum Field of View requirements. For interior work this approximates a minimum 160 x 120 pixel camera with a 20 to 30 degree lens used at a distance not exceeding 12 CCBST 2014 Proceedings Book_v10 A6 403-438_Layout 1 14-10-17 4:08 PM Page 431
  • 4. 4 3 2 14TH CANADIAN CONFERENCE ON BUILDING SCIENCE AND TECHNOLOGY 5m. RESNET has a similar spatial requirement, although somewhat relaxed in the minimum Field of View requirement. For normal exterior work NMS requirements translate to a 320 x 240 pixel camera used at a distance of up to about 20m, although it specifies that higher resolutions of lenses and/or pixel count may be necessary to achieve the minimum 150mm2 resolution at longer stand-off distances. Unfortunately there is a proliferation of low cost (under $500) thermal imagers which do not even come close to meeting these specifications, yet are being utilized for thermographic assessments. DETECTING THERMALANOMALIES RELATED TO AIR MOVEMENT Unintentional air movement within, around, and through an enclosure may result is significant energy, thermal comfort, moisture, durability and environmental issues. As shown in Table 1, air movement with respect to a building enclosure can take 7 different types. (Mill, P.A.D. et al, 1982) TABLE 1: TYPES OF ENCLOSURE AIR MOVEMENT AFFECTING SURFACE TEMPERATURE Air movement types 1,2,4,6 and 7 will transfer heat via surface to air convection, while types 3 and 5 are air leakage and have additional heat transfer associated with mass transfer (note: any latent heat related to phase change during mass transport will be discussed next section). Under some environmental conditions and certain types of wall assemblies the thermal patterns associated with types 2,4 and 6 can be misinterpreted as either uncontrolled air leakage, or even at times missing insulation (when in fact adequate insulation and/or an adequate enclosure air barrier is present). The use of thermography to detect the effect of air leakage requires that there is both a pressure and temperature difference between the inside and outside air. It does not detect the air directly, but rather the heat transfer that the air movement has upon the surrounding surface. Investigations into air related thermal anomalies may be conducted in heat loss (winter) or heat gain (summer) conditions as long as minimum temperature and pressure differences exist across the enclosure. When air movement studies utilizing a single pressure condition are conducted in conjunction with conductive insulation studies confusing and ambiguous patterns can result, particularly from diffuse air movement through some types of porous insulation. Definitive air movement testing relies on multiple pressure conditions, preferably both positive pressure and negative pressure. Identification of air movement types 3, 4, 6 and 7 must be done by exterior evaluation and positive pressure while identification of types 1, 2, 4 and 5 must be done by interior evaluation and negative pressure. Natural pressure differences across the enclosure are created by three means: stack effect; wind; and by mechanical systems (e.g.: fans and combustion equipment). Unfortunately the thermographer is at the mercy of the natural conditions creating the pressure differences at the time of the survey. This often leads to a poor evaluation since parts of the building may be under positive pressure, others negative pressure, and even others nominal pressure. To overcome this limitation the thermographer can pro-actively create a pressure condition by one of two means: 1.) in smaller buildings utilize a blower door which can create positive or negative air pressure differences within the entire structure or 2.) in larger or commercial buildings adjust the inlet and exhaust fans and/or their dampers to vary pressure differential. A blower door has the 12 CCBST 2014 Proceedings Book_v10 A6 403-438_Layout 1 14-10-17 4:08 PM Page 432
  • 5. 4 3 3 14TH CANADIAN CONFERENCE ON BUILDING SCIENCE AND TECHNOLOGY advantage of being able to characterize the air leakage curve for the building and provide a quantitative estimation of the amount of air leakage under average and extreme conditions. For larger buildings where blower door use is not possible, air leakage quantification will typically be limited to evaluation via tracer gas depletion method. ASTM E1186-03, RESNET and NMS 022713 standards do not agree on the pressures and temperatures differences across the enclosure required for reliable thermographic detection of air leakage. It varies from a difference of 1.7ºC @ 10 Pa (RESNET) to 5ºC @ 10 to 50 Pa (ASTM) to the most stringent requirements of NMS which requires a minimum of 20ºC difference when pressures are between 5 to 10 Pa and 10ºC minimum when pressures are between 10 to 25Pa. The NMS standard describes an ideal two-step procedure for qualitative air leakage evaluation of larger commercial buildings. The building is first placed under entire positive pressure and the outside surfaces are inspected. Once all surfaces have been mapped, then the building systems are reversed and the building is placed under negative pressure. After waiting a sufficient period of time, typically at least 2 hours, the surfaces are re-scanned to see if the pattern has changed. If it has, it is likely due to air leakage. In order to resolve the small areas of air leakage it is often necessary to use a narrow angle lense, map the exterior surface with a set of images, and then assemble them into one large image. In winter, air exfiltration will create warm patterns on the exterior surface. In general, the more diffuse the leakage, the larger the affected area and the less dramatic the exterior thermal patterns. The more direct the leakage and size of hole, the smaller and hotter the pattern will be. The extreme sensitivity of modern cameras (e.g. better than 50 mK) can be such that even a relatively tight building may appear to be extremely leaky when tested under large delta temperatures and pressures. Therefore thermography should not be used to estimate the amount of air leakage (e.g. air changes per hour or effective leakage area). If the surface temperature approaches the air temperature on the opposite side of the wall, however, it is often indicative of a direct air leakage pathway (as opposed to diffuse pathways). If this is an isolated case of a small hole, in extreme conditions of pressure difference and temperature the resultant direct air leakage may cause damage (e.g. an interior pipe could freeze) yet a blower door test could indicate a relatively tight building. Thermography could identify this, even under non-extreme test 12 CCBST 2014 Proceedings Book_v10 A6 403-438_Layout 1 14-10-17 4:08 PM Page 433
  • 6. 4 3 4 14TH CANADIAN CONFERENCE ON BUILDING SCIENCE AND TECHNOLOGY conditions, because the surface temperature on the negative pressure side would be only slightly different than the air temperature on the positive side. Camera performance requirements specified by all Standards for air leakage detection are identical to those for detection of conductive anomalies, with the NMS specifications being the most detailed and rigorous. (refer to the previous section on conduction for camera specifications) DETECTING THERMALANOMALIES RELATED TO MOISTURE Water, may be detected thermodynamically for three reasons: when a material contains water it can affect the thermal conductivity (k); when a material contains water it can alter the volumetric heat capacity (α·cp ); or when water changes state latent heat is absorbed (evaporation, melting) or released (condensation, freezing). Many thermographers, however, believe that the only mechanism for detection of moisture is evaporation. Under the right conditions, free air evaporative cooling on a surface can indeed be very thermodynamic, and easily detected with a modern infrared camera: 1 droplet of water (e.g. of a mass of 0.45gms (0.001 lbs) can theoretically extract approximately 1.05kJ (1 Btu) from the surroundings in order to provide the latent heat required for evaporation. After a flood in a building, the restoration industry will usually attempt to dry the interior by significantly lowering the vapor pressure (relative humidity) and using IR has brought with it the concept of water ‘always appearing cool’. The dramatic surface temperature depression easily detectable during high vapour pressure difference, however, has led a very wrong general assumption by building investigators for passive moisture detection. Relying on water detection through the natural drying process only, will result both in false negatives (non-detection of moisture) and false positives (the thermal anomaly is not moisture). Even near-surface moisture can go undetected if the vapour pressure (RH) is too high in the free air condition adjacent to the surface. An infrared camera does not directly detect evaporation: rather it may detect a surface temperature depression due to the rate of evaporation which is determined by the vapor pressure difference between the saturated condition of the material and the free air space adjacent to it as well as the vapour retarders present in between. If the free air condition is warm and dry (low RH) it may create a high rate of cooling. Conversely, if the free air condition is cool and/or humid (high RH) it could easily go undetected because the evaporative cooling rate will be very low. In fact if condensation is occurring within a wall behind a vapour barrier then latent heat will be released and surface warming may occur and completely be ignored or misinterpreted as a non- moisture condition by an unsuspecting and untrained inspector. Detection of interstitial water within a wall or roof assembly is much more complex than the process of water evaporating from an exterior or interior surface exposed to free air. Many wall and roof systems have unintentionally created two or more vapour retardant barriers which inhibits the drying process. This raises the vapour pressure within the assembly, and inhibits evaporative cooling as a means of detection. Ironically this situation creates enclosure issues which the investigator is often tasked with finding. In this case, the thermographer must rely on a steady state conductivity change between wet and dry material; a heat capacity change between wet and dry material (under transient state); or the special thermal and moisture conditions required for one of the four phase changes. Thermographic cameras are extremely sensitive, often able to detect differences less than 0.05ºC (50mK). But while this may create a clearer, more defined pattern when the thermal conditions are right, it is not a viable substitute for moisture detection under poor thermodynamic conditions, and/or when moisture is buried deep within an enclosure. High sensitivity cameras used under less than ideal conditions can lead to a large number of false positives, and/or lengthy field time for verification using other methods. False 12 CCBST 2014 Proceedings Book_v10 A6 403-438_Layout 1 14-10-17 4:08 PM Page 434
  • 7. 4 3 5 14TH CANADIAN CONFERENCE ON BUILDING SCIENCE AND TECHNOLOGY negatives lead to credibility issues of both the inspector and the thermographic industry as well as the possibilities of litigation, particularly when mold or other damage associated with the moister is present but not detected. Since moisture detection is not covered in much detail by any standard, a general assumption could be that the requirements for camera performance are at least equal to those for detection of conductive anomalies. The current consensus in the industry however, is that moisture detection necessitates a higher level of thermal sensitivity. Most manufacturers have accommodated this by producing “building” model of IR cameras with an NETD of at least 0.08ºC (80mK) or better. It is likely that any future standards developed for moisture detection will require at least this level of sensitivity. Spatial requirements are likely to remain the same as for conductive anomaly detection. The NMS standard is the only specification which itemizes certain conditions for the detection of moisture. The standard requires a minimum 20ºC (temperature) and 25Pa (pressure) difference from the inside to the outside and 30ºC difference when the pressure difference is less than 10Pa. The Special Case of Low Slope Roof Moisture Detection Both ASTM C1153-10 and NMS 022716 standards detail the conditions necessary for detection of moisture trapped in conventional low slope built-up roofing systems. Interstitial moisture is detected using the capacitive method of detection by observing the outside roof surface under transient conditions. Ideal conditions are a warm sunny day with low wind, and no moisture on the roof surface. Inspection takes place 1 to 2 hours after the direct sunlight has left the roof surface and is conducted into the night. Potential wet areas are identified as warm areas that have retained the solar heat gained during the day. Both standards also permit investigations to be performed using the conductive method of inspection under steady state heat loss conditions with a minimum differential of 10ºC (ASTM) or 15ºC (NMS) across the enclosure. In all cases, and with both standards, the thermographer must be aware of inside conditions, fixtures and appliances and no standing water should be present on the roof surface. CONCLUSIONS Thermography can play a significant role as a non destructive and rapid screening tool to identify potential heat, air, and moisture related anomalies in large and small buildings, but only if the thermodynamic 12 CCBST 2014 Proceedings Book_v10 A6 403-438_Layout 1 14-10-17 4:08 PM Page 435
  • 8. 4 3 6 14TH CANADIAN CONFERENCE ON BUILDING SCIENCE AND TECHNOLOGY conditions are right. Thermographic results alone cannot quantify excessive heat flow, air flow, or moisture content. The primary use for thermography should as a qualitative investigative tool, identifying potential areas for further investigation, validation and quantification by other means. Any quantitative thermographic analysis should be limited to that of temperature measurement and/or potential percentage area affected. Thermographic investigations should be limited to those environmental conditions, procedures, and methods specified and recommended by various standards established by recognized independent bodies. Standards for utilizing thermography for conductive and air leakage studies are well established and should be adhered to. These are summarized in Table 1. But, because of a lack of current standards for moisture detection, it should be done carefully and with a specific methodology for detection (conduction, capacitance or phase change) appropriate for the materials, assembly and environmental conditions. This is summarized in Table 2. Home inspectors, for example, could apply a thermal camera in a limited scope for free-air detection of water related anomalies, so long as they have a specific Standard of Practice detailing the method and conditions necessary for doing so and a means (e.g. a moisture detector) for immediate field confirmation of the suspected anomaly. IR cameras suitable for building investigations are now inexpensive, lightweight and easy to use. There are, however, cameras available which do not even come close to meeting the requirements of the current well established standards for detection of heat, air and/or moisture anomalies. One should ensure that before a camera is purchased, or a contract for services engaged, that a camera and thermographer meet the minimum requirements of the appropriate standard for the task. All standards emphasize the importance of training and certification related to not just the camera and infrared detection principles, but more importantly knowledge of building construction, performance, and sound building science principles. The proliferation of readily available low cost cameras used by unqualified persons unaware of the underlying thermodynamic principles, appropriate methods, and limitations could jeopardize the legitimate value of thermography as a valuable tool for the building diagnostic industry. 12 CCBST 2014 Proceedings Book_v10 A6 403-438_Layout 1 14-10-17 4:08 PM Page 436
  • 9. 4 3 7 14TH CANADIAN CONFERENCE ON BUILDING SCIENCE AND TECHNOLOGY 12 CCBST 2014 Proceedings Book_v10 A6 403-438_Layout 1 14-10-17 4:08 PM Page 437
  • 10. 4 3 8 14TH CANADIAN CONFERENCE ON BUILDING SCIENCE AND TECHNOLOGY REFERENCES Incropera, F.P, Dewitt, D.P. Fundamentals of Heat and Mass Transfer, Fourth Edition, 1996, John Wiley and Sons, ISBN 0-471-30460-3, Pages 4-5. ASTM C1060-90. “Standard Practice for Thermographic Inspection of Insulation Installations in Envelope Cavities of Frame Buildings”, ASTM International, www.astm.org ISO 6781 Thermal Insulation - Qualitative Detection of Thermal Irregularities in Building Envelopes - Infrared Method, International Standards Organization, www.iso.org RESNET Revised Interim Guidelines for Thermographic Inspections of Buildings, 2012, http://www.resnet.us/board/Results_of_Electronic_Ballot_of_RESNET_Board_on_Adopting_IR_Interim_ Guidelines.pdf NMS 022713 Thermographic Assessment - Building Envelope, 2007, National Master Specifications of Canada, www.tpsgc-pwgsc.gc.ca ASNT Recommended Practice No. SNT-TC-1A: Personnel Qualification and Certification in Nondestructive Testing 2011, American Society for Non-Destructive Testing, www.asnt.org ISO/DIS 6781-3 Performance of buildings - Detection of heat, air and moisture irregularities in buildings by infrared methods - Part 3: Qualifications of Equipment Operators, Data Analysts and Report Writers, 2013, International Standards Organization, www.iso.org ASTM Standard C1046 - 95 Standard Practice for In-Situ Measurement of Heat Flux and Temperature on Building Envelope Components, 2007, ASTM International, www.astm.org ASTM Standard C1155 – 95 Standard Practice for Determining Thermal Resistance of Building Envelope Components from the In-Situ Data, 2007 ASTM International, www.astm.org DeWitt, D.P, and Nutter, Gene D. Theory & Practice of Radiation Thermometry. Chapter 20: “The application of thermography for industrial and building energy management”; McIntosh, G.B. and Mill, P.A.D. Pages 1076 -1081, Wiley Interscience, New York City, 1988. ISBN 0-471-61018-6 Mill, P.A.D. “Thermographic Diagnosis of Building Envelope Deficiencies, Fathers of Confederation Center, Report Series No. 28”, Public Works Canada, 1979, ISBN 0-662-50335-X, Pgs 34 to 37. ASHRAE, Handbook of Fundamentals, Chapter 25, Table 1, vertical surface, still air, emissivity=0.9, horizontal heat flow, 2001, The American Society of Heating, Refrigeration, and Air Conditioning Engineers, Stainton, W.D., Quantitative Interpretation of Building Thermograms, Proceedings 4th Biennial Infrared Information Exchange, 1978, AGA Corporation, Pine Brook , NJ, Mill, P.A.D, Kaplan, A.G. , A Generic Methodology for Thermographic Diagnosis of Building Enclosures, Report Series No. 30, Public Works Canada, 1982, ISBN 0-662-521-55-2, Pgs 8 to 9. ASTM Standard E1186–03, Standard Practices for Air Leakage Site Detection in Building Envelopes and Air Barrier Systems, 2009, International, www.astm.org ASTM C1153-10 Standard Practice for Location of Wet Insulation in Roofing Systems Using Infrared Imaging,2010, www.astm.org NMS 022616, Thermographic Assessment - Roof, 2007, National Master Specifications of Canada 12 CCBST 2014 Proceedings Book_v10 A6 403-438_Layout 1 14-10-17 4:08 PM Page 438