1. ED34-862 Specifications
2. Specifications
Ceiling Mounted Cassette Corner Type
Model FXKQ25MAVE FXKQ32MAVE FXKQ40MAVE FXKQ63MAVE
kcal/h 2,500 3,200 4,000 6,300
∗1 Cooling Capacity (19.5°CWB) Btu/h 9,900 12,600 16,000 24,900
kW 2.9 3.7 4.7 7.3
∗2 Cooling Capacity (19.0°CWB) kW 2.8 3.6 4.5 7.1
Casing Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate 4
Dimensions: (H×W×D) mm 215×1,110×710 215×1,110×710 215×1,110×710 215×1,310×710
Coil (Cross Rows×Stages×Fin Pitch mm 2×11×1.75 2×11×1.75 2×11×1.75 3×11×1.75
Fin Coil) Face Area m² 0.180 0.180 0.180 0.226
Model 3D12H1AN1V1 3D12H1AN1V1 3D12H1AP1V1 4D12H1AJ1V1
Type Sirocco Fan Sirocco Fan Sirocco Fan Sirocco Fan
Motor Output × Number W 15×1 15×1 20×1 45×1
Fan of Units
m³/min 11/9 11/9 13/10 18/15
Air Flow Rate (H/L)
cfm 388/318 388/318 459/353 635/530
Drive Direct Drive Direct Drive Direct Drive Direct Drive
Temperature Control Microprocessor Thermostat Microprocessor Thermostat Microprocessor Thermostat Microprocessor Thermostat
for Cooling and Heating for Cooling and Heating for Cooling and Heating for Cooling and Heating
Sound Absorbing Thermal Insulation Material Polyethylene Foam Polyethylene Foam Polyethylene Foam Polyethylene Foam
Liquid Pipes mm φ6.4 (Flare Connection) φ6.4 (Flare Connection) φ6.4 (Flare Connection) φ9.5 (Flare Connection)
Piping Gas Pipes mm φ12.7 (Flare Connection) φ12.7 (Flare Connection) φ12.7 (Flare Connection) φ15.9 (Flare Connection)
Connections VP25 VP25 VP25 VP25
Drain Pipe mm
( External Dia. 25 )
Internal
Dia. 32
( External Dia. 25 )
Internal
Dia. 32
( External Dia. 25 )
Internal
Dia. 32
( External Dia. 25 )
Internal
Dia. 32
Machine Weight (Mass) kg 31 31 31 34
∗4 Sound Level (H/L) (220V) dBA 38/33 38/33 40/34 42/37
Safety Devices Fuse. Fuse. Fuse. Fuse.
Thermal Fuse for Fan Motor. Thermal Fuse for Fan Motor. Thermal Fuse for Fan Motor. Thermal Fuse for Fan Motor.
Refrigerant Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
Connectable Outdoor Units R-410A PA Series R-410A PA Series R-410A PA Series R-410A PA Series
Model BYK45FJW1 BYK45FJW1 BYK45FJW1 BYK71FJW1
Panel Color White (10Y9/0.5) White (10Y9/0.5) White (10Y9/0.5) White (10Y9/0.5)
Decoration
Panels Dimensions: (H×W×D) mm 70×1,240×800 70×1,240×800 70×1,240×800 70×1,440×800
(Option) Resin Net Resin Net Resin Net Resin Net
Air Filter (with Mold Resistant) (with Mold Resistant) (with Mold Resistant) (with Mold Resistant)
Weight kg 8.5 8.5 8.5 9.5
Operation Manual. Operation Manual. Operation Manual. Operation Manual.
Installation Manual. Paper Installation Manual. Paper Installation Manual. Paper Installation Manual. Paper
Pattern for Installation. Drain Pattern for Installation. Drain Pattern for Installation. Drain Pattern for Installation. Drain
Hose. Clamp Metal. Hose. Clamp Metal. Hose. Clamp Metal. Hose. Clamp Metal.
Standard Accessories Insulation for Fitting. Sealing Insulation for Fitting. Sealing Insulation for Fitting. Sealing Insulation for Fitting. Sealing
Pads. Clamps. Screws. Pads. Clamps. Screws. Pads. Clamps. Screws. Pads. Clamps. Screws.
Washers. Positioning Jig for Washers. Positioning Jig for Washers. Positioning Jig for Washers. Positioning Jig for
Installation. Insulation for Installation. Insulation for Installation. Insulation for Installation. Insulation for
Hanger Bracket. Air Outlet Hanger Bracket. Air Outlet Hanger Bracket. Air Outlet Hanger Bracket. Air Outlet
Blocking Pad. Blocking Pad. Blocking Pad. Blocking Pad.
Drawing No. C : 3D038813A
Note:
Conversion Formulae
∗1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
∗2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5 m, level difference : 0 m. kcal/h=kW×860
Btu/h=kW×3412
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. cfm=m³/min×35.3
∗4 Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1m downward. During actual operation, these values
are normally somewhat higher as a result of ambient conditions.
5 Refer to page 150 for Fan Motor Input.
Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.
FXKQ-MA 145