7.MODBus and CANBus.pptx

MODBUS & CANBUS
PRESENTED TO:
ENGINEERING DEPTT. SEPL
PRESENTED BY:
ALI RAZA
MUHAMMAD FAIZAN SALEEM
Presentation # 7
1
CONTENTS
 Introduction of MODBUS
 Master Slave Configuration
 MODBUS RTU
 Data Storing
 MODBUS RTU Frame
 MODBUS TCP/IP
 CAN history
 Benefits of CAN
 Electrical States
 CAN Frame
 Application of CAN bus 2
OPEN SYSTEMS INTERCONNECTION (OSI)
MODEL
Conceptual and logical layout that defines network
communication used by systems open to
interconnection and communication with other
systems.
3
MODBUS INTRODUCTION
 Serial communication protocol developed by
Modicon published by Modicon in 1979 for use with
its PLCs
 MODBUS is an open protocol
 The protocol describes how information is received,
how queries are responded.
 In simple terms, it is a method used for transmitting
information over serial lines between electronic
devices.
4
MASTER SLAVE COMMUNICATION
 MODBUS provides master-slave communication
between intelligent devices
 Used to transmit signals from instrumentation and
control devices back to a main controller.
5
MODBUS TYPES
The three most common Modbus types used today
are as follows:
 Modbus RTU (based on serial communication like
RS485 and RS232)
 Modbus/TCP(Transmission Control Protocol)
(based on Ethernet communication)
 Modbus ASCII
6
MODBUS RTU
 Modbus RTU, data is coded in binary and requires
only one communication byte per data byte.
 Modbus RTU is the most widely used industrial
protocol
 This is ideal for use over RS232 or multi-drop
RS485 networks, at speeds from 1,200 to 115K
baud.
 The most common speeds are 9,600 and 19,200
baud.
7
DATA STORED IN MODBUS
Information is stored in the Slave device in four
different tables.
 Two tables store on/off discrete values (coils)
 Two store numerical values (registers).
 The coils and registers each have a read-only table
and read-write table.
 Each table has 9999 values
 Each coil or contact is 1 bit and assigned a data
address between 0000 and 270E.
 Each register is 1 word = 16 bits = 2 bytes and also
has data address between 0000 and270E. 8
DATA STORED IN MODBUS
 Each register is 1 word = 16 bits = 2 bytes and also
has data address between 0000 and270E.
9
MODBUS RTU FUNDAMENTALS
To enable communication with a slave device, the
master must send a message or query containing
following framing:-
 Device Address
 Function Code
 Data
 Error Check
10
Silence >= 3,5 characters
MODBUS FRAME STRUCTURE
DEVICE ADDRESS
Request: A master addresses a slave by placing
the slave address in the address field of the
massage.
Response: when the slave sends its response it
places its own address in the address field of the
massage.
 The Device Address is a number from 0 to 247.
 Messages sent to address 0 (broadcast messages)
can be accepted by all slaves
 The individual slave devices are assigned
addresses in the range of 1 to 247.
11
MODBUS FRAME STRUCTURE
FUNCTION CODE
The Function Code defines the command that the
slave device is to execute, such as read data, accept
data, report status, etc.
Function codes are 1 to 255. Some function codes
have sub-function codes
12
MODBUS FRAME STRUCTURE
DATA
Request: Data field contains the additional
information which the slave must use to take the
action defined by the functional code. This can
include the items like registers , addresses quantity of
the items to be handled.. etc
Response: If no error occurs , the data field
contains the data requested
Valid codes in the range of 0 to 255 decimals
13
MODBUS FRAME STRUCTURE
ERROR CHECK
CRC(Cyclic Redundancy check) : Error Check is a
16-bit numeric value representing the Cyclic
Redundancy Check (CRC).
 16-bit numeric value representing the Cyclic
Redundancy Check (CRC)
 The CRC is generated by the master and checked
by the receiving device.
 If the CRC values do not match, the device asks
for a retransmission of the message.
 In some systems, a parity check can also be
applied
14
MODBUS RTU FRAME STRUCTURE
15
MODBUS FRAME STRUCTURE
REQUEST
This command is requesting the ON/OFF status of
discrete coils # 20 to 56
from the slave device with address 17.
11 01 0013 0025 0E84
11: The Slave Address (11 hex = address17 )
01: The Function Code 1 (read Coil Status)
0013: The Data Address of the first coil to read.
( 0013 hex = 19 , + 1 offset = coil #20 )
0025: The total number of coils requested. (25 hex =
37, inputs 20 to 56 )
0E84: The CRC (cyclic redundancy check) for error
checking. 16
RESPONSE
11 01 05 CD6BB20E1B 45E6
11: The Slave Address (11 hex = address17 )
01: The Function Code 1 (read Coil Status)
05: The number of data bytes to follow (37 Coils / 8
bits per byte = 5 bytes)
CD: Coils 27 - 20 (1100 1101)
6B: Coils 35 - 28 (0110 1011)
B2: Coils 43 - 36 (1011 0010)
0E: Coils 51 - 44 (0000 1110)
1B: 3 space holders & Coils 56 - 52 (0001 1011)
45E6: The CRC (cyclic redundancy check).
17
MODBUS TCP/IP
 It is also a world-wide standard that serves as the
foundation for the World Wide Web. The primary
function of TCP is to ensure that all packets of data
are received correctly
 IP makes sure that messages are correctly
addressed and routed
 Modbus TCP/IP uses TCP/IP and Ethernet to carry
the data of the Modbus message structure between
devices
18
CONSTRUCTION OF A MODBUS TCP/IP
DATA PACKET
Modbus TCP/IP Application Data Unit (ADU) takes
the form of a 7 byte header and the protocol data unit
19
MODBUS TCP/IP
This is a Modbus variant used for communications
over TCP/IP networks, connecting over port 502.
It does not require a checksum calculation as lower
layers already provide checksum protection.
Modbus TCP/IP uses TCP and Ethernet 10 Mbit/s or
100 Mbits/s to carry the MODBUS messaging
structure
20
CAN HISTORY
 In 1985 Bosch originally developed CAN, a high-integrity
serial bus system for networking intelligent devices, to
replace automotive point-to-point wiring systems.
 As vehicle electronics became pervasive, complex wire
harnesses which were heavy, expensive and bulky were
replaced with CAN throughout the automotive industry.
 In 1993 CAN became the international standard known
as ISO 11898.
 Since 1994, several widely used higher-level protocols
have been standardized on top of CAN, such as
CanOpen and DeviceNet.
21
22
CAN OPEN SYSTEMS INTERCONNECT
(OSI) MODEL
BENEFITS OF CAN BUS
 Low-Cost, Lightweight Network
 Broadcast Communication
 Priority
 Error Capabilities
23
ELECTRICAL STATES
Recessive
 In the recessive state, no node (CAN device) drives
the bus. Since both ends of the long cable are
terminated (120ohm resistors across each end), the
voltage across the differential pair quickly falls to
zero.
Dominant
 In the dominant state, one end of the differential
pair, called CANL, is pulled low, while the other end,
CANH, is pulled high (generally 5V or 3.3V).
Naturally this overrides the recessive state, and this
the name. 24
EXPLANATION OF RECESSIVE AND DOMINANT
25
ELECTRICAL STATES
Bits on the bus
 Each bit has a certain time on the bus before the
next one’s turn. The bit rate can vary, but 1Mbit is
common (1µs per bit).
Idle
 When no nodes are transmitting, the bus is idle.
This is the recessive state.
 A transmission starts when a node asserts a
dominant state on the bus. The first bit is the SOF
(start of frame) bit.
26
CAN FRAME
 Everything in CAN is sent in a frame (or message).
This is essentially a packet. It consists of the
sender’s unique ID, some flags, some data, and a
CRC.
Standard (11-bit ID) frames
27
CAN FRAME
SOF bit
 The CAN DATA frame starts with the SOF – start of
frame – bit. This is analogous to the start bit in RS-
232 style asynchronous serial. It is the bit require to
transition from idle to non-idle. The SOF bit is a
logic 0 (dominant).
Identifier-
 The Standard CAN 11-bit identifier establishes the
priority of the message. The lower the binary value,
the higher its priority.
28
CAN FRAME
RTR (remote transmission request)
 is a single bit that indicates if this is a DATA frame
(0, dominant) or a REMOTE frame (1, recessive) .
IDE (Identifier Extension)
 A dominant single identifier extension (IDE) bit
means that a standard CAN identifier with no
extension is being transmitted.
29
CAN FRAME
r0
Reserved bit (for possible use by future standard
amendment).
DLC field (4 bits)
 The DLC – data length code – field indicates how
many bytes of data this frame will contain (0-8).
CRC(cyclic redundancy check) field (15 bits)
 This 15-bit CRC is used to check for any errors in
the received data.
30
CAN FRAME
ACK (Acknowledge)
 Every node receiving an accurate message
overwrites this recessive bit in the original message
with a dominate bit, indicating an error-free
message has been sent.
END of Frame (7 bits)
 The END of frame is simply a sequence of 7
recessive bits. This provides padding so that a
recently attached device can tell that the frame has
ended.
31
CAN FRAME
IFS
 This 7-bit interframe space (IFS) contains the time
required by the controller to move a correctly
received frame to its proper position in a message
buffer area.
32
VEHICLES BEFORE
CAN: EXPENSIVE,
BULKY POINT TO POINT
WIRING, WIRING
HARNESSES AND MANY
CONNECTORS.
VEHICLES AFTER
CAN: SYSTEMS OF
SYSTEMS WITH
MULTIPLE CAN
BUSSES, SIMPLIFIED
WIRING HARNESSES
AND MANY FEWER
CONNECTORS
Before
CAN
After CAN
33
1 sur 33

Recommandé

Controller Area Network(CAN) par
Controller Area Network(CAN)Controller Area Network(CAN)
Controller Area Network(CAN)Ashutosh Bhardwaj
5.9K vues21 diapositives
Project_intership par
Project_intershipProject_intership
Project_intershipWajiha Muzaffar Ali
79 vues5 diapositives
Project_intership par
Project_intershipProject_intership
Project_intershipWajiha Muzaffar Ali
249 vues5 diapositives
Can bus par
Can busCan bus
Can busRucha Pupala
660 vues94 diapositives
Controller area network par
Controller area networkController area network
Controller area networkDivi1597
95 vues17 diapositives
IJSTEV2I12120 par
IJSTEV2I12120IJSTEV2I12120
IJSTEV2I12120manju147147
51 vues7 diapositives

Contenu connexe

Similaire à 7.MODBus and CANBus.pptx

Hands On Data Communications, Networking and TCP/IP Troubleshooting par
Hands On Data Communications, Networking and TCP/IP TroubleshootingHands On Data Communications, Networking and TCP/IP Troubleshooting
Hands On Data Communications, Networking and TCP/IP TroubleshootingLiving Online
715 vues21 diapositives
Zigbee 802-15-4 par
Zigbee 802-15-4Zigbee 802-15-4
Zigbee 802-15-4SHUBHAM MORGAONKAR
2.8K vues55 diapositives
UNIT 2b.pptx par
UNIT 2b.pptxUNIT 2b.pptx
UNIT 2b.pptxDharmendra212860
6 vues6 diapositives
Networking Technologies02.pptx par
Networking Technologies02.pptxNetworking Technologies02.pptx
Networking Technologies02.pptxANISHTP
3 vues53 diapositives
Ethernet Compliance Testing at Toradex par
Ethernet Compliance Testing at ToradexEthernet Compliance Testing at Toradex
Ethernet Compliance Testing at ToradexToradex
192 vues28 diapositives
Chapter 3 esy par
Chapter 3 esy Chapter 3 esy
Chapter 3 esy Yogesh Mashalkar
1.5K vues48 diapositives

Similaire à 7.MODBus and CANBus.pptx(20)

Hands On Data Communications, Networking and TCP/IP Troubleshooting par Living Online
Hands On Data Communications, Networking and TCP/IP TroubleshootingHands On Data Communications, Networking and TCP/IP Troubleshooting
Hands On Data Communications, Networking and TCP/IP Troubleshooting
Living Online715 vues
Networking Technologies02.pptx par ANISHTP
Networking Technologies02.pptxNetworking Technologies02.pptx
Networking Technologies02.pptx
ANISHTP3 vues
Ethernet Compliance Testing at Toradex par Toradex
Ethernet Compliance Testing at ToradexEthernet Compliance Testing at Toradex
Ethernet Compliance Testing at Toradex
Toradex 192 vues
IEEE Paper A SystemC AMS Model of an I2C Bus Controller par Dweapons Art
IEEE Paper A SystemC AMS Model  of an I2C Bus ControllerIEEE Paper A SystemC AMS Model  of an I2C Bus Controller
IEEE Paper A SystemC AMS Model of an I2C Bus Controller
Dweapons Art2.1K vues
Serial Port Device Driver par Emblogic
Serial Port Device DriverSerial Port Device Driver
Serial Port Device Driver
Emblogic2.5K vues
Can network development using arm cortex m3 par Ankur Rastogi
Can network development using arm cortex m3Can network development using arm cortex m3
Can network development using arm cortex m3
Ankur Rastogi122 vues
Can network development using arm cortex m3 par Ankur Rastogi
Can network development using arm cortex m3Can network development using arm cortex m3
Can network development using arm cortex m3
Ankur Rastogi42 vues
underground cable fault location using aruino,gsm&gps par Mohd Sohail
underground cable fault location using aruino,gsm&gps underground cable fault location using aruino,gsm&gps
underground cable fault location using aruino,gsm&gps
Mohd Sohail17.7K vues
GSM BASED PREPAID ENERGY METER BILLING VIA SMS par SRINIVAS REDDY
GSM BASED PREPAID ENERGY METER BILLING VIA SMSGSM BASED PREPAID ENERGY METER BILLING VIA SMS
GSM BASED PREPAID ENERGY METER BILLING VIA SMS
SRINIVAS REDDY51.6K vues

Dernier

Final Year Presentation par
Final Year PresentationFinal Year Presentation
Final Year PresentationComsat Universal Islamabad Wah Campus
7 vues29 diapositives
CHEMICAL KINETICS.pdf par
CHEMICAL KINETICS.pdfCHEMICAL KINETICS.pdf
CHEMICAL KINETICS.pdfAguedaGutirrez
12 vues337 diapositives
SNMPx par
SNMPxSNMPx
SNMPxAmatullahbutt
17 vues12 diapositives
MK__Cert.pdf par
MK__Cert.pdfMK__Cert.pdf
MK__Cert.pdfHassan Khan
10 vues1 diapositive
NEW SUPPLIERS SUPPLIES (copie).pdf par
NEW SUPPLIERS SUPPLIES (copie).pdfNEW SUPPLIERS SUPPLIES (copie).pdf
NEW SUPPLIERS SUPPLIES (copie).pdfgeorgesradjou
15 vues30 diapositives
What is Unit Testing par
What is Unit TestingWhat is Unit Testing
What is Unit TestingSadaaki Emura
23 vues25 diapositives

Dernier(20)

NEW SUPPLIERS SUPPLIES (copie).pdf par georgesradjou
NEW SUPPLIERS SUPPLIES (copie).pdfNEW SUPPLIERS SUPPLIES (copie).pdf
NEW SUPPLIERS SUPPLIES (copie).pdf
georgesradjou15 vues
Investigation of Physicochemical Changes of Soft Clay around Deep Geopolymer ... par AltinKaradagli
Investigation of Physicochemical Changes of Soft Clay around Deep Geopolymer ...Investigation of Physicochemical Changes of Soft Clay around Deep Geopolymer ...
Investigation of Physicochemical Changes of Soft Clay around Deep Geopolymer ...
SUMIT SQL PROJECT SUPERSTORE 1.pptx par Sumit Jadhav
SUMIT SQL PROJECT SUPERSTORE 1.pptxSUMIT SQL PROJECT SUPERSTORE 1.pptx
SUMIT SQL PROJECT SUPERSTORE 1.pptx
Sumit Jadhav 13 vues
Control Systems Feedback.pdf par LGGaming5
Control Systems Feedback.pdfControl Systems Feedback.pdf
Control Systems Feedback.pdf
LGGaming56 vues
fakenews_DBDA_Mar23.pptx par deepmitra8
fakenews_DBDA_Mar23.pptxfakenews_DBDA_Mar23.pptx
fakenews_DBDA_Mar23.pptx
deepmitra814 vues
Machine Element II Course outline.pdf par odatadese1
Machine Element II Course outline.pdfMachine Element II Course outline.pdf
Machine Element II Course outline.pdf
odatadese19 vues
Advances in micro milling: From tool fabrication to process outcomes par Shivendra Nandan
Advances in micro milling: From tool fabrication to process outcomesAdvances in micro milling: From tool fabrication to process outcomes
Advances in micro milling: From tool fabrication to process outcomes
GDSC Mikroskil Members Onboarding 2023.pdf par gdscmikroskil
GDSC Mikroskil Members Onboarding 2023.pdfGDSC Mikroskil Members Onboarding 2023.pdf
GDSC Mikroskil Members Onboarding 2023.pdf
gdscmikroskil51 vues
2023Dec ASU Wang NETR Group Research Focus and Facility Overview.pptx par lwang78
2023Dec ASU Wang NETR Group Research Focus and Facility Overview.pptx2023Dec ASU Wang NETR Group Research Focus and Facility Overview.pptx
2023Dec ASU Wang NETR Group Research Focus and Facility Overview.pptx
lwang7853 vues

7.MODBus and CANBus.pptx

  • 1. MODBUS & CANBUS PRESENTED TO: ENGINEERING DEPTT. SEPL PRESENTED BY: ALI RAZA MUHAMMAD FAIZAN SALEEM Presentation # 7 1
  • 2. CONTENTS  Introduction of MODBUS  Master Slave Configuration  MODBUS RTU  Data Storing  MODBUS RTU Frame  MODBUS TCP/IP  CAN history  Benefits of CAN  Electrical States  CAN Frame  Application of CAN bus 2
  • 3. OPEN SYSTEMS INTERCONNECTION (OSI) MODEL Conceptual and logical layout that defines network communication used by systems open to interconnection and communication with other systems. 3
  • 4. MODBUS INTRODUCTION  Serial communication protocol developed by Modicon published by Modicon in 1979 for use with its PLCs  MODBUS is an open protocol  The protocol describes how information is received, how queries are responded.  In simple terms, it is a method used for transmitting information over serial lines between electronic devices. 4
  • 5. MASTER SLAVE COMMUNICATION  MODBUS provides master-slave communication between intelligent devices  Used to transmit signals from instrumentation and control devices back to a main controller. 5
  • 6. MODBUS TYPES The three most common Modbus types used today are as follows:  Modbus RTU (based on serial communication like RS485 and RS232)  Modbus/TCP(Transmission Control Protocol) (based on Ethernet communication)  Modbus ASCII 6
  • 7. MODBUS RTU  Modbus RTU, data is coded in binary and requires only one communication byte per data byte.  Modbus RTU is the most widely used industrial protocol  This is ideal for use over RS232 or multi-drop RS485 networks, at speeds from 1,200 to 115K baud.  The most common speeds are 9,600 and 19,200 baud. 7
  • 8. DATA STORED IN MODBUS Information is stored in the Slave device in four different tables.  Two tables store on/off discrete values (coils)  Two store numerical values (registers).  The coils and registers each have a read-only table and read-write table.  Each table has 9999 values  Each coil or contact is 1 bit and assigned a data address between 0000 and 270E.  Each register is 1 word = 16 bits = 2 bytes and also has data address between 0000 and270E. 8
  • 9. DATA STORED IN MODBUS  Each register is 1 word = 16 bits = 2 bytes and also has data address between 0000 and270E. 9
  • 10. MODBUS RTU FUNDAMENTALS To enable communication with a slave device, the master must send a message or query containing following framing:-  Device Address  Function Code  Data  Error Check 10 Silence >= 3,5 characters
  • 11. MODBUS FRAME STRUCTURE DEVICE ADDRESS Request: A master addresses a slave by placing the slave address in the address field of the massage. Response: when the slave sends its response it places its own address in the address field of the massage.  The Device Address is a number from 0 to 247.  Messages sent to address 0 (broadcast messages) can be accepted by all slaves  The individual slave devices are assigned addresses in the range of 1 to 247. 11
  • 12. MODBUS FRAME STRUCTURE FUNCTION CODE The Function Code defines the command that the slave device is to execute, such as read data, accept data, report status, etc. Function codes are 1 to 255. Some function codes have sub-function codes 12
  • 13. MODBUS FRAME STRUCTURE DATA Request: Data field contains the additional information which the slave must use to take the action defined by the functional code. This can include the items like registers , addresses quantity of the items to be handled.. etc Response: If no error occurs , the data field contains the data requested Valid codes in the range of 0 to 255 decimals 13
  • 14. MODBUS FRAME STRUCTURE ERROR CHECK CRC(Cyclic Redundancy check) : Error Check is a 16-bit numeric value representing the Cyclic Redundancy Check (CRC).  16-bit numeric value representing the Cyclic Redundancy Check (CRC)  The CRC is generated by the master and checked by the receiving device.  If the CRC values do not match, the device asks for a retransmission of the message.  In some systems, a parity check can also be applied 14
  • 15. MODBUS RTU FRAME STRUCTURE 15
  • 16. MODBUS FRAME STRUCTURE REQUEST This command is requesting the ON/OFF status of discrete coils # 20 to 56 from the slave device with address 17. 11 01 0013 0025 0E84 11: The Slave Address (11 hex = address17 ) 01: The Function Code 1 (read Coil Status) 0013: The Data Address of the first coil to read. ( 0013 hex = 19 , + 1 offset = coil #20 ) 0025: The total number of coils requested. (25 hex = 37, inputs 20 to 56 ) 0E84: The CRC (cyclic redundancy check) for error checking. 16
  • 17. RESPONSE 11 01 05 CD6BB20E1B 45E6 11: The Slave Address (11 hex = address17 ) 01: The Function Code 1 (read Coil Status) 05: The number of data bytes to follow (37 Coils / 8 bits per byte = 5 bytes) CD: Coils 27 - 20 (1100 1101) 6B: Coils 35 - 28 (0110 1011) B2: Coils 43 - 36 (1011 0010) 0E: Coils 51 - 44 (0000 1110) 1B: 3 space holders & Coils 56 - 52 (0001 1011) 45E6: The CRC (cyclic redundancy check). 17
  • 18. MODBUS TCP/IP  It is also a world-wide standard that serves as the foundation for the World Wide Web. The primary function of TCP is to ensure that all packets of data are received correctly  IP makes sure that messages are correctly addressed and routed  Modbus TCP/IP uses TCP/IP and Ethernet to carry the data of the Modbus message structure between devices 18
  • 19. CONSTRUCTION OF A MODBUS TCP/IP DATA PACKET Modbus TCP/IP Application Data Unit (ADU) takes the form of a 7 byte header and the protocol data unit 19
  • 20. MODBUS TCP/IP This is a Modbus variant used for communications over TCP/IP networks, connecting over port 502. It does not require a checksum calculation as lower layers already provide checksum protection. Modbus TCP/IP uses TCP and Ethernet 10 Mbit/s or 100 Mbits/s to carry the MODBUS messaging structure 20
  • 21. CAN HISTORY  In 1985 Bosch originally developed CAN, a high-integrity serial bus system for networking intelligent devices, to replace automotive point-to-point wiring systems.  As vehicle electronics became pervasive, complex wire harnesses which were heavy, expensive and bulky were replaced with CAN throughout the automotive industry.  In 1993 CAN became the international standard known as ISO 11898.  Since 1994, several widely used higher-level protocols have been standardized on top of CAN, such as CanOpen and DeviceNet. 21
  • 22. 22 CAN OPEN SYSTEMS INTERCONNECT (OSI) MODEL
  • 23. BENEFITS OF CAN BUS  Low-Cost, Lightweight Network  Broadcast Communication  Priority  Error Capabilities 23
  • 24. ELECTRICAL STATES Recessive  In the recessive state, no node (CAN device) drives the bus. Since both ends of the long cable are terminated (120ohm resistors across each end), the voltage across the differential pair quickly falls to zero. Dominant  In the dominant state, one end of the differential pair, called CANL, is pulled low, while the other end, CANH, is pulled high (generally 5V or 3.3V). Naturally this overrides the recessive state, and this the name. 24
  • 25. EXPLANATION OF RECESSIVE AND DOMINANT 25
  • 26. ELECTRICAL STATES Bits on the bus  Each bit has a certain time on the bus before the next one’s turn. The bit rate can vary, but 1Mbit is common (1µs per bit). Idle  When no nodes are transmitting, the bus is idle. This is the recessive state.  A transmission starts when a node asserts a dominant state on the bus. The first bit is the SOF (start of frame) bit. 26
  • 27. CAN FRAME  Everything in CAN is sent in a frame (or message). This is essentially a packet. It consists of the sender’s unique ID, some flags, some data, and a CRC. Standard (11-bit ID) frames 27
  • 28. CAN FRAME SOF bit  The CAN DATA frame starts with the SOF – start of frame – bit. This is analogous to the start bit in RS- 232 style asynchronous serial. It is the bit require to transition from idle to non-idle. The SOF bit is a logic 0 (dominant). Identifier-  The Standard CAN 11-bit identifier establishes the priority of the message. The lower the binary value, the higher its priority. 28
  • 29. CAN FRAME RTR (remote transmission request)  is a single bit that indicates if this is a DATA frame (0, dominant) or a REMOTE frame (1, recessive) . IDE (Identifier Extension)  A dominant single identifier extension (IDE) bit means that a standard CAN identifier with no extension is being transmitted. 29
  • 30. CAN FRAME r0 Reserved bit (for possible use by future standard amendment). DLC field (4 bits)  The DLC – data length code – field indicates how many bytes of data this frame will contain (0-8). CRC(cyclic redundancy check) field (15 bits)  This 15-bit CRC is used to check for any errors in the received data. 30
  • 31. CAN FRAME ACK (Acknowledge)  Every node receiving an accurate message overwrites this recessive bit in the original message with a dominate bit, indicating an error-free message has been sent. END of Frame (7 bits)  The END of frame is simply a sequence of 7 recessive bits. This provides padding so that a recently attached device can tell that the frame has ended. 31
  • 32. CAN FRAME IFS  This 7-bit interframe space (IFS) contains the time required by the controller to move a correctly received frame to its proper position in a message buffer area. 32
  • 33. VEHICLES BEFORE CAN: EXPENSIVE, BULKY POINT TO POINT WIRING, WIRING HARNESSES AND MANY CONNECTORS. VEHICLES AFTER CAN: SYSTEMS OF SYSTEMS WITH MULTIPLE CAN BUSSES, SIMPLIFIED WIRING HARNESSES AND MANY FEWER CONNECTORS Before CAN After CAN 33