How does the gas fire extinguishing system work and how to install it and use it? Where is it installed and why does it have to be installed? Whether the gas sparyed by fire fighting is harmful to human body and equipment? The gas fire extinguishing system should be installed in library, computer room, warehouse to protect equipment and property when fire occurs. But the gas sprayed is harmful for human body. So, there are two step to start gas extinguishing and 3 ways to start it. Shop fire alarm and fire fighting system at https://www.vedardsecurity.com
Fire alarm and fire automatically extinguishing system consists of various fire detectors include smoke detector, heat detector, manual call point, break glass and gas extinguishing system, gas release start button, gas release indicator. The gas release will be started by automatic mode, manual mode or mechanical mode according to on site situation. And it will be started after smoke detector triggers alarm and heat detector or manual call point triggers fire alarm. The gas fire extinguishing system can be connected with central fire alarm monitor panel installed in fire security room. After fire alarm triggers, the central fire alarm monitor will trigger alarm.
1. h e a t
Gas fire extinguishing control system is mainly
composed of gas fire extinguishing controller,
d e t e c t o r
h e a t d e t e c t o
到 固
heat detector
smoke detector
r
smoke detector
https://vedardsecurity.com https://www.vedard.com/forum
5. https://www.vedard.com/forum
e m e r g e n c y s t a r t
emergency start/stop button
/ s t o p b u t t o n
https://vedardsecurity.com
stop
p r e s s
s p r a y i
n g
break
emergency start/
stop button
6. F I R E
sound/light alarm
s o u n d / l i g h t a l a r m
https://vedardsecurity.com https://www.vedard.com/forum
7. e A S
gas spraying indicator light
gas spraying indicator light
https://vedardsecurity.com https://www.vedard.com/forum
气 体 保 护 区
D o n o t e n t e r 入
9. <
Manual alarm button can also be used in special cases
Manual alarm button
https://www.vedard.com/forum
P r e s s B u t t o n
按下报火警
fire
https://vedardsecurity.com
high
m
phone
些 -
r
高
10. 按 下 报 火 警
temperature
flame detector
电 话
火 警
manual button
smoke beam
https://www.vedard.com/forum
https://vedardsecurity.com
P r e s s B u t t o n
Or other types of fire detectors
11. https://www.vedard.com/forum
Gas extinguishing controller linkages control gas fire extinguishing
equipment,linkage control fan,Air valve fire valve,Ventilation and
linkage control gas fire extinguishing equipment And receive feedback signals
feedback
air conditioning,Automatic doors and Windows and other equipment.
controller
Ventilation
and air
conditioning
manual/
other equipment
auto
https://vedardsecurity.com
input/
output
m
smoke solenoid
detector
heat
detecto
r
start/ weightl
essness
alarm
gas indicator
stop
sound/
light
12. controller h e a t
s m o k e feedback
manual/
auto
sound/
light gas release
indicator
alarm
switch
equipment
heat
The gas extinguishing system shall be controlled by a dedicated gas extinguishing controller
detector
sound/
Weightle
ssness
feedback
device
light
controller
manual/
auto
w e i g h
t l e s s
n e s s
a l a r m
switch
. 品
https://www.vedard.com/forum
smoke
i
n
p
u
t
/
o
u
t
p
u
t
m
o
d
u
l
e
detector
Electromagnetic type drive
device
xtingui
There
are two
main
types of
gas
extinguish
ing
systems
fire alarm host
https://vedardsecurity.com
input/
output
Signal feedback
device
Ventilati
on and
air
condition
ing
solen
oid
valve
是 显
emergency
button
gas
release
indicator
emergency
Ventilation and air
conditioning
button
Gas
extinguish
ing
controller
with fire
detection
and alarm
function
Gas
extinguis
hing
controller
without
fire
detection
and
alarm
function
13. i n p u t /
o u t p u t
m o d u l e
https://www.vedard.com/forum
1.Gas fire extinguishing controller with fire detection and alarm function:
gas extinguishing
controller
This controller can be connected with fire detector and various linkage control modules, with automatic fire alarm and
gas fire control functions, can constitute an independent system. In case of fire, the gas fire extinguishing controller
receives the fire alarm signal from the fire detector or the manual alarm button and sends out the linkage control
smoke
emergenc
y start/
stop
detector
command to realize the gas fire extinguishing control function.
https://vedardsecurity.com
s o u n d /
l i g h t
manual/
auto
Ventilation and
air conditioning
Electrom
agnetic
type drive
device
switch
a l a r m
heat
The gas fire extinguishing controller with fire detection and alarm function can be connected to fire detectors and various linkage control modules
detector
gas release
Signal feedback
device
indicator
Weightle
ssness
feedback
device
14. emergency
start /stop
gas release
The gas fire extinguishing controller without fire detection and alarm function has only a single gas fire control function.
indicator
button
s o u n d /
l i g h t
a l a l a r m
Signal feedback
device
Electrom
agnetic
type drive
device
https://www.vedard.com/forum
heat
detector
fire alarm controller
smoke
Weightle
ssness
feedback
device
detector
manual/
auto
switch
Ventilation and
air conditioning
input/
output
module
https://vedardsecurity.com
2. Gas fire extinguishing controller without fire detection and alarm function:
This controller has only a single gas fire control function and must be used in conjunction with the fire alarm controller. The fire
detector is connected to the fire alarm controller. When a fire occurs, the fire alarm controller will receive the fire alarm signal from the
fire detector or manual alarm button and issue instructions to the gas fire extinguishing controller. Then the gas fire extinguishing
gas fire extinguishing
controller
controller will linkage control related components to realize the gas fire extinguishing control function.
G
15. heat detector
smoke detector
https://www.vedard.com/forum
温 感
温 感 温 感
Selection of fire detectors
https://vedardsecurity.com
运 感
Fire detectors with high sensitivity should be selected in the protection area to alarm
and extinguish fire as early as possible.
Fire detectors with high sensitivity should be
For other types of fire detectors that only
output switching signals, the alarm loop can
selected in the protection area to alarm and
extinguish fire as early as possible.
Two different types of fire detectors should be
used in the protected area, usually smoke
fire detectors and heat fire detectors. Special
places can also use other types of fire
detectors or manual alarm buttons. All kinds
of detectors should be calculated according
to the specification requirements of the
protection area, cross layout.
be connected through the relay module.
16. 按 下 报 火 警
T e m p e r a t u r e manual
button
s e n s i n g c a b l e
P r e s s B u t t o n
U l t r a v i o l e t f i r e
Special places can also use other types of fire detectors or manual alarm button, cross
layout
d e t e c t o r
Fire detectors with high sensitivity should be selected in the protection area to alarm and extinguish fire as
https://vedardsecurity.com https://www.vedard.com/forum
火 讨
I n f r a r e d f i r e
early as possible.
Two different types of fire detectors should be used in the protection area, usually smoke detector and
heat detector. Other types of fire detectors or manual alarm buttons can also be used in special places.
The protection area of all kinds of detectors should be calculated according to the specifications and
arranged in a cross way.For other types of fire detectors that only output switching signals, the alarm
loop can be connected through the relay module.
d e t e c t o r
19. https://vedardsecurity.com
烟 感
尽气体保护区
放 气 物
https://www.vedard.com/forum
G A S
温感
The fire extinguishing agent spray indicator light signal should be kept in the protected area after
ventilation, and manually shut down
The upper part of the outlet of the protection zone shall be set with the exhaust indicator light. The gas
extinguishing controller shall start the exhaust indicator light after receiving the feedback signal of the
signal feedback device to warn personnel not to enter.
温 感
咽感
20. 温 感
https://www.vedard.com/forum
烟 感
因 感
https://vedardsecurity.com
The pipe network gas extinguishing system has three starting modes: automatic control, manual control and
mechanical emergency operation.
m
温 感
温感
Start mode of gas fire extinguishing
The pipe network gas extinguishing system has three starting modes: automatic control, manual control
and mechanical emergency operation.
21. The fire extinguishing device of the prefabricated gas fire extinguishing system is set in the protection zone, and personnel must be
evacuated in case of fire. Therefore, the prefabricated gas fire extinguishing system (fire extinguishing system without pipe network
) has only two starting modes: automatic control and manual control
https://vedardsecurity.com https://www.vedard.com/forum
The fire extinguishing device of the prefabricated gas fire extinguishing system is set in the protection zone. In case of fire,
personnel must evacuate.
22. 磐
https://www.vedard.com/forum
https://vedardsecurity.com
In the state of automatic control, there are generally two ways to
control gas fire extinguishing:
A: B:
Smoke and heat
compound alarm
linkage
two separate fire alarms
linkage
In the state of automatic control, there are generally two ways to control gas fire extinguishing:
23. 因感
温感
温 感
烟 感
温 感
Method A: smoke and heat compound alarm linkage
This is the most commonly used control method. In the gas fire protection area, smoke fire detectors and heat fire detectors are generally arranged.
24. 因感
区 3 区
警告
温感
烟 感
温 感
温感
Method A: smoke and heat compound alarm linkage
When one detector gives an alarm, the sound and light fire alarm in the protection area is activated. When a different type of fire detector gives an alarm, the fire
information is confirmed.
25. 温感
实
温感
烟感
因感
害
温感
Start the fire sound and light alarm outside the protection zone, and send out the linkage control signal at the same time. After a delay of 0 to 30s, send out the
fire extinguishing start command and start the fire extinguishing device.
26. IG541
start line
G 5 4 1
https://www.vedard.com/forum
https://vedardsecurity.com
Start the fire sound and light alarm outside the protection zone, and send out the linkage control signal at the same
time. After a delay of 0 to 30s, send out the fire extinguishing start command and start the fire extinguishing device.
27. 红外火灾探测器 手动报警按钮
https://vedardsecurity.com
按 下 报 火 警
P g 密 s u t t o
紫外火灾探测器 感温电缆
https://www.vedard.com/forum
火
In some special places, other types of fire detectors may be required, and manual alarm buttons may also
be arranged. At this time, different detectors can be classified and linked by referring to the above smoke
heat compound.
In some special places, other types of fire detectors may be required, and manual alarm buttons may also be
deployed.
28. 火灾探测器(感烟)
手动报警按钮
In some special cases, the alarm signal of two separate fire detectors may also confirm the fire alarm
按 下 报 火 警
P r e s s B u t t o n
火 警 请
火灾探测器(感温)
https://www.vedard.com/forum
https://vedardsecurity.com
Method B: Linkage of two independent fire
alarm signals
In some special cases, it may be confirmed
by the alarm signals of two separate fire
detectors, or by the alarm signals of one fire
detector and one manual alarm button. When
the first fire alarm signal is issued, start the
fire audible and visual alarm in the protection
area; when the other fire alarm signal is
issued, confirm the fire alarm information,
start the fire audible and visual alarm outside
the protection area, and issue the linkage
control signal at the same time. After a delay
of 0 to 30s, the fire extinguishing start
command will be issued to start the fire
extinguishing device.
29. 发出联动控制
信号 , 联 动 关
闭电动门、窗、
防火门、空调、
风机等
发出灭火启动指令
启动放气指示灯
延时30秒(可调)
https://vedardsecurity.com
启动气体灭火装置
气体灭火控制器
When the first fire alarm signal is issued, activate the fire audible and visual alarm in the protection area. When another fire
alarm signal is issued, confirm the fire information.
接收反馈信号
气体灭火控 确认火警
发出联动控制信号
https://www.vedard.com/forum
fire
First alarm signal received
The gas fire controller reported the fire Activate the fire alarm in the
protection zone
Second alarm signal received
Gas fire controller confirms fire alarm and
sends out linkage control signal
Activate the fire alarm outside
the protection zone
Emergency
start button
Send out linkage control
signal, linkage close electric
door, window, fire door, air
conditioner, fan, etc
Delay 30 seconds (adjustable)
Fire extinguishing command issued
Activate the gas extinguishing device
The gas extinguishing controller receives the
feedback signal
Activate the gas
release indicator
30. 紧急停止按钮
紧急启动按钮
No matter the system is in automatic control state or manual control state, the manual control of gas fire extinguishing is always effective.
Manual control of gas fire extinguishing
31. https://vedardsecurity.com
洒
喷
温 感
因
感
按 下
烟 感
紧急启/停按钮
温 感
温 感
https://www.vedard.com/forum
停止
Manual control is controlled by the emergency start-stop button, which must be installed at the exit of the protection zone. There is also
an emergency start-stop button on the control panel of the gas extinguishing controller.
The manual control is controlled by the emergency start-stop button. The exit of the protection zone must be installed with the
emergency start-stop button (the installation height is 1.5m from the ground). There is also an emergency start-stop button on the
control panel of the gas extinguishing controller.
32. ・ 喷 酒 自 动
启动映酒
别
到
量
请
1 区
・速时
启动控制
手动
・延时
https://www.vedard.com/forum
自动
唤 酒
・焙动唯酒
启动控制
现场启动
现场停止
现场度动 现场启动
现场启动
现场停止
自动 隙 西
紧急启动 紧急停止
现场停止
4 区
3 区
现场停止
紧急启动紧急停止 紧急启动紧急停止
延时
启动唤活
动
启动唯酒
启动控制
警 告
2 区
手动
手动
手动 延 时
玖 西
启动控制
紧急启动紧急停止
https://vedardsecurity.com
Manual control is controlled by the emergency start-stop button, which must be installed at the exit of the protection zone. There is also
an emergency start-stop button on the control panel of the gas extinguishing controller.
Manual control is controlled by emergency start-stop button. Emergency start-stop button must be installed at the exit of the
protection zone (installation height is 1.5m from the ground). Emergency start-stop button must also be installed on the control panel
of the gas extinguishing controller.
33. ・ 延 时 ・ 手 动
・ 喷 活 ・ 自 动
・ 启 动 唤 清
・ 启 动 控 制
・ 现 场 启 动
・现场停止
启 停
声 光
紧急启动紧急停止
2 区
https://vedardsecurity.com https://www.vedard.com/forum
There is emergency start button and an emergency stop button.
There is an emergency start button and an emergency stop button.
34. 紧急停止
・ 延 时 ・ 手 动
・ 项 活 ・ 自 动
・ 启 动 蚀 酒
・ 启 动 控 制
・ 现 场 启 动
・现场停止
After pressing the emergency start button, the gas fire extinguishing controller will issue a linkage control signal. After a delay of 0 to 30s, the fire extinguishing
start command will be issued to start the fire extinguishing device.
2 区
声光
https://www.vedard.com/forum
https://vedardsecurity.com
启 停
After pressing the emergency start button, the gas fire extinguishing controller will issue a linkage control signal. After a delay of 0 to
30s, the fire extinguishing start command will be issued to start the fire extinguishing device.
35. https://www.vedard.com/forum
https://vedardsecurity.com
The emergency stop button has the highest priority. Press the emergency stop button to stop the fire extinguishing process (including the delay stage of 0 to 30
seconds). Also, please note that the fire extinguishing start command is irreversible and the emergency stop button is only effective before the fire
extinguishing start command is issued.
Press emergency
stop
36. https://vedardsecurity.com https://www.vedard.com/forum
The emergency stop button has the highest priority. Press the emergency stop button to stop the fire
extinguishing process (including the delay stage of 0 to 30 seconds). Also, please note that the fire
extinguishing start command is irreversible and the emergency stop button is only effective before the fire
extinguishing start command is issued.
The linkage control signal of gas fire extinguishing shall include the following contents:
Turn off the air supply (exhaust) fan and air supply (exhaust) valve in the protected area;
Stop the ventilation and air conditioning system and close the electric fire valve located in the protected area.
The linkage control starts the opening closure device of the protection area, including closing the door and
window of the protection area;
When the automatic control starting mode is adopted, a controllable delay injection of no more than 30s
should be provided according to the need of safe evacuation of personnel from the protected area. For the
protection area where no one is working, it can be set to spray without delay.
37. M e c h a n i c a l e m e r g e n c y o p e r a t i o n f o r g a s f i r e e x t i n g u i s h i n g
https://www.vedard.com/forum
https://vedardsecurity.com
F 建
Mechanical emergency operation refers to the manual operation of the electromagnetic drive device that drives the gas cylinder set to extinguish the fire.
Mechanical emergency operation refers
to the manual operation of the
electromagnetic drive device that drives
the gas cylinder set to extinguish the fire.
When the automatic and manual system
fails and the personnel in the protection
zone have been evacuated, you can pull
the safety pin of the electromagnetic
drive device of the drive gas cylinder
group in the corresponding protection
zone, and press the start button on the
upper part of the electromagnetic drive
device to start directly. In the absence of
manual failure of the gas drive bottle set
or electromagnetic drive device, you can
also manually open the selection valve,
and then manually open the container
valve of the extinguishing agent bottle
set to start the fire extinguishig.
38. ,
Pull the plug
The safety pin of the electromagnetic drive device of the drive gas cylinder group in the corresponding protection zone can be pulled open
39. M a n u a l l y o p e n s e l e c t o r v a l v e
You can also manually open the selection valve, and then manually open the valve of the extinguishing agent bottle group
container to start the fire extinguishing.
40. 启 停
https://www.vedard.com/forum
警告
The conversion between manual and automatic control can be done on gas fire extinguishing control host.
紧急启动紧急停止
https://vedardsecurity.com
2 区
・ 延 时 ・ 手 动
・ 喷 活 ・ 自 动
・ 启 动 喷 活
・ 启 动 控 制
・ 现 场 启 动
・ 现 场 停 止
声 光 区
Conversion between manual
control and automatic control
You can switch manual control
and automatic control on the gas
fire extinguishing control host
41. 烟 感
温
感
因 感
https://vedardsecurity.com https://www.vedard.com/forum
温 感
温 感
In some protected areas, manual and automatic control conversion devices should also be provided outside the protected areas.
Some protection areas [fire extinguishing design concentration or actual use
concentration is greater than the NOAEL concentration (NOAEL) protection areas and
the use of thermal sol prefabricated fire extinguishing system], there should also be a
manual and automatic control of the conversion device outside the protection area
(installation height is 1.5m from the ground center).
44. 声光报警器(外)
感探测春
桓式七氟两烷气体
灭火装置
急启动停止按钮
https://www.vedard.com/forum
气体灭火控制器
至
清
控
中
心
声光报警器(内)
感温探测器
防护区
放气指示灯
https://vedardsecurity.com
配
山
If there is more than one prefabricated fire extinguishing device in the same protection zone, it must be able to start at the same time, and
the time difference of its action response should not be greater than 2 seconds
If there is more than one prefabricated fire extinguishing device (fire extinguishing device without pipe
network) in the same protection zone, it must be able to start at the same time, and the time difference of
its action response should not be greater than 2 seconds.
45. https://vedardsecurity.com https://www.vedard.com/forum
Where there is a fire control room, the relevant information of the fire control system in each protection area shall be transmitted to the fire control room.
Where there is a fire control room, the
relevant information of the fire control system
in each protection area shall be transmitted
to the fire control room.
Information to be transmitted to the fire
control room includes:
Fire information, fire fighting action, manual
and automatic conversion and system
equipment failure information.
46. The gas extinguishing controller can be installed in the fire control room
https://www.vedard.com/forum
https://vedardsecurity.com
The setting position of the gas extinguishing controller
The gas fire extinguishing controller can be set in the fire control room (suitable for the protection area is not far
from the fire control room). For convenient operation, it can also be set up in the duty room of the floor in the
protection zone.
f i r e c o n t r o l r o o m F l o o r d u t y r o o m
47. 磐
For no duty room with pipe network fire extinguishing system,You can consider setting in the bottle storage room
For no duty room with pipe network fire extinguishing system,You can consider setting in the bottle storage room
protection area protection area
https://vedardsecurity.com https://www.vedard.com/forum
能
48. https://www.vedard.com/forum
https://vedardsecurity.com
得
For prefabricated fire extinguishing system without duty room,you can consider to set in an easy to operate position outside the protected area
For prefabricated fire extinguishing system without duty room,you can consider to set in an easy to operate position outside the protected area