IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE)
e-ISSN: 2278-1676,p-ISSN: 2320-3331, Volume 6, Issue 5 (Jul. - Aug. 2013), PP 68-73
www.iosrjournals.org
www.iosrjournals.org 68 | Page
Modeling of Ferro-resonance on the VT of GIS substation
S.M.Hassan.Hosseini1
, Y. Toghani Holari2
, S.M.Hosseini.Bafghi3
1, 2, 3
(Department of Electrical Engineering, Islamic Azad University South Tehran Branch, Tehran, IRAN)
Abstract : The main subject of the essay is study of ferroresonance in the voltage transformers at 400kV GIS
substation. Ferroresonance has destructive effects such as, undulations of high voltages, warming of
transformers, increasing of heat, temperature increasing and damaging voltage transformers, high noise due to
evolution due to magnet and bad working of protective instruments. So we have to apply limitations on system
parameters to avoid such an undesirable phenomenon like this. In this paper ferroresonance phenomenon on
VTs of real GIS substation (karon 4 power plant had been studied. With regarding high risk of ferroresonance
due to studied substation conditions, damping circuit (FDSD, ZD) had been designed with help of EMTP-RV
and the results are presented in two conditions of being without damping and by using of damping in the circuit.
The results show damping circuit is successful in obviation of these dangerous oscillations.
Keywords: Gas Insulated Substation (GIS), Voltage Transformers (VT), Ferroresonance, FDSD, ZD
I. INTRODUCTION
Regarding to the advantages of GIS substations in comparison with AIS (Air Insulated Substation) and
purposing that instruments such as current and voltage transformer , bypass disconnector switch, high voltage
conductor , grounding switchgear, breaker and etc. that are kept in boxes under pressure of SF6 gas , and
increasing usage of these substations toward the past and regarding to this point that urban and industries areas
with increasing load and insufficient area and needing high voltages are regarded , in last year's the use of GIS
substation have increased.[1]. In this paper we study the Karoon 4 power plant GIS substation that is a 400kV
substation with double bus bar and disconnector switch, this substation is fed by 4 single phase 100MW
transformers. The outputs of these transformers are connected to the 400kV network with 4 air lines. Despite the
advantages of this gas insulated substations, it has fundamental problems. One of the main ingredients of
destruction of the instruments in GIS substations is ferroresonance that influenced the insulation of network at
different point. Ferroresonance is one of the rare and destructive phenomena in power network that figured as a
nonlinear resonance that happen between the capacitor of the network and the nonlinear inductance of voltage
transformer at the saturation instant. The word of ferroresonance, that arrived to the books and papers from the
end of the second decade of 20th century , use for all the oscillation phenomena in electrical circuits that consist
of at least nonlinear self , capacitor , voltage source (generally sinusoidal). The effective elements in causing
resonance and ferroresonance in power systems are, harmonic, core saturating, changing inductance of wiring,
cutting of 1 or 2 phases of system, unsymmetrical load, inappropriate use of circuit breakers and fuses, using
cables with high capacitance. Ferroresonance has other destructive effects such as oscillation of high voltages,
intricacy in wave forms of voltage and current , warming of transformers , damaging voltage transformers (VT),
for example in Karoon 4 power plant 400kV GIS substation , loud noise due of evolution due to magnet ,
malfunction protective instruments. Numerous cases of ferroresonance in power system have been reported in
years. In last year's the number of ferroresonance because of the intricacy of system and operating modern
instrument has increased. [2], [3] outbreak of ferroresonanc has some signs like permanent over voltage with
vast amplitude as phase to phase or phase to ground, permanent over current with vast amplitude, shifting
voltage zero point, increasing temperature of voltage transformer, continual increasing of the noise altitude of
transformers and reactors, damaging electrical equipment's such as capacitor banks and CVT because of
increasing the thermal effect or breakage of dampers of the protective equipment's. Therefore some limitations
should be applied to parameters of systems to avoid occurrence of undesirable phenomena like these. [4], [5].
All of the studies have been simulated by EMTP-RV software.
II. Parallel Capacitor In H.V Circuit Breaker
Power capacitors have different usage in structure and mechanism of power circuit breaker especially
at high voltage levels. Like grading capacitors that have two breaking boxes in series. Voltage usually doesn’t
distribute equally on breaking boxes. To avoid making stress of high voltage and smoothing voltage on them,
capacitors parallel with contacts of circuit breaker that usually have capacity between 900 to 1600 pF for each
breaking box are used. Although by the development of technology usage of these capacitors have been reduced
but they are used in high voltages yet.[3],[6]. Some defects of these capacitors are increasing the risk of
Modeling of Ferro-resonance on the VT of GIS substation
www.iosrjournals.org 69 | Page
ferroresonance with nearby voltage transformers, increasing the weight, complexity of installation operation and
increasing leakage current.
III. Karoon 4 Case Study
The purpose of this paper is to study the ferroresonance on voltage transformers (VT) in Karoon 4
power plant GIS 400kv substation as an example of GIS substation with bus bar and long line that have been
effected by this phenomenon by increasing the voltage and damaging isolation and heating, destruction and
damaging of VT . These simulations are done by EMTP-RV Software and finally propose the practical method
to resist it. There conductive wires of A & C phase of damping reactor have been burnt by the high current at
secondary circuit because of the single phase with VT ferroresonance. One of the reasons of this phenomenon is
that the VT Company adequately doesn’t consider the capacity of the damping reactor to absorb the resonance
energy in VT in some cases of GIS switching conditions during first energizing at site. [7] Special
recommendation presented in this paper offer to avoiding over heating Beside VT of BUS 1 and 2 and damping
reactor until additional FDSD (Ferroresonance Detecting and Suppression Device) at site became adjusted. The
related circuit breaker (CB) for each 400kV GIS bay should be closed about 5 minutes after closing of both DS's
(disconnecting switches) during energization. Reversely, during power Outage one of both DS's should be
opened within 5 minutes after opening of the circuit breaker [3], [8]. On 19 & 24 November in 2010, VT of #1
bus was exposed to ferro-resonance 2 times during energizing (10min.) & de-energizing (2min.) by switching of
CB & DS of C03 bay that is shown is shown in Figure 1.
Fig1. Karoon4 400kV substation single line diagram state of energizing from first circuit output line of Karon3
and bus 1 and corresponding VT
On 20 & 21 November in 2010, VT of #2 bus were exposed to ferroresonance 2 times during
energizing (5min.) and de-energizing (2min.) by switching of CB & DS of C04 bay through #2 bus bar.
Fig2. Karoon4 400kV substation single line diagram state of energizing from second circuit output line of
Karoon3 and bus 2 and corresponding VT
Modeling of Ferro-resonance on the VT of GIS substation
www.iosrjournals.org 70 | Page
Fig3.Burnt Damping Reactor (ZD) of A-phase for #2 Bus VT
IV. Ferroresonance Detection Supervision Devise (Fdsd)
By regarding presented figures of this part such as fig 4 , a VT with conversion rate of 400/ to
110/ connected to a ferroresonace detector circuit is shown .[2].
Fig4. Information for adjusting FDSD
In continue internal circuit of detecting unit is connected to burden with value of 0.33 that is equivalent
of parallel branches. and also in figures 5 and 6, appearance of a FDSD and different part of operating lamp
A,B , Power Lamp , sensitivity Change , Test Switch , Optional Output Control in three phase and single phase
detector unit is shown.
Fig5 .picture of seeming figure of FDSD
Modeling of Ferro-resonance on the VT of GIS substation
www.iosrjournals.org 71 | Page
Fig6. Diagram of three phase FDSD connection
V. Ferroresonance Analysis With Fdsd+Zd
The conditions of standard analysis that can be used in done simulation are as below:
1. CB Capacitance=4,000pF/phase,
2. Unit Earth Capacitance for GIS=52.4pF/m
3. Internal Earth Capacitance of M.Tr: 13,366pF/phase
4. Internal Earth Capacitance of in Shunt Reactor: 3,382pf/phase
In above analysis, karoon 4 power plant GIS substation, that is a 400kV substation with double bus bar with
bypass disconnector switch, is studied and equivalent circuit of GIS substation, that consist of main parameters
like, source and resistance series with it, and CB that capacitor C1 is parallel with it, and as explained at section
3 above GIS circuit breaker had two 2000pF capacitor parallel with contacts of circuit breaker and equivalent
capacitance is 4000pf. The simulation is done on the basis of these values. Above simulated circuit consist of
equivalent capacitor of GIS substation in different studied conditions that are as a result of summation of
existing parameters which is studied in bellow waveforms. Also in this circuit, one VT with prime voltage of
400kV and secondary voltage of 105V is used for simulation and at last ZD and FDSD equivalent circuit for
damping probability of ferroresonance due to 4000pf capacitor parallel with CB are put .[7],[9].
Fig7-a- EMTP model for survey ferroresonance with FDSD+ZD
 if C1=4000 pF and C2=3820pF (for VT of bus 1)
Which capacitor (C2= (53.2+5.6+5.6+2+6.5)*52.4=3820).
0 0.5 1 1.5 2 2.5
-300
-200
-100
0
100
200
300
t (ms)
voltagev1(v)
Fig7-b- voltage waveform of VT secondary voltage in damping ferroresonance (V1)
Modeling of Ferro-resonance on the VT of GIS substation
www.iosrjournals.org 72 | Page
0 0.5 1 1.5 2 2.5
-4
-2
0
2
4
x 10
5
t (ms)
voltage(v)
Fig7-c- voltage waveform of VT primary
0 0.5 1 1.5 2 2.5
-100
-50
0
50
100
t (ms)
current(i)
Fig7-d- current waveform of VT primary
 if C1=4000 pf and C2= 7669pf ( for VT bus )
Which capacitor (C2= (53.2+5.6+7.05+7.2*9+2+7.2+6.5)*52.4 =7669)
0 0.5 1 1.5 2 2.5
-800
-600
-400
-200
0
200
400
600
800
t (ms)
voltagev1(v)
Fig8-a- VT secondary voltage waveform in presence of ferroresonance (V1)
0 0.5 1 1.5 2 2.5
-500
-400
-300
-200
-100
0
100
200
300
400
500
t (ms)
voltagev2(v)
Fig8-b- VT secondary voltage waveform in presence of ferroresonance (V2)
0 0.5 1 1.5 2 2.5
-4
-2
0
2
4
x 10
5
t (ms)
voltage(v)
Fig8-c- used voltage source waveform in simulated diagram with EMTP
Modeling of Ferro-resonance on the VT of GIS substation
www.iosrjournals.org 73 | Page
0 0.5 1 1.5 2 2.5
-400
-300
-200
-100
0
100
200
300
400
500
t (ms)
voltagev2(v)
Fig8-d- VT secondary voltage waveform in damping ferroresonance (V2)
The structure of gas switchers generally act like a capacitor (energized conductor-gas insulator-
grounded body). Also because of the mentioned reasons in high voltages, capacitors parallel with breaker
contacts are used. Capacitor parallel with breaker contacts are in series with GIS switcher capacitor, therefore
always there is a path for transmission of capacitor current, even when the breaker is in open state. This current
cause the voltage division between two capacitors and whatever the ratio of breaker parallel capacitor to GIS
capacitor is larger (lower impedance), voltage after circuit breaker and on the bus bar will be larger. GIS circuit
breaker existing in mentioned substation has two 2000pf capacitors parallel with breaker contact that the
equivalent capacitance will be 4000pf and can cause the ferroresonance on equipment's like VT. Different
producers of gas switchers use these capacitors to increase the operation of their circuit breakers. [8], [9]. One
effect of ferroresonance due to breaker parallel capacitor is heating and burning VT in Karoon 4 power plant
400kV GIS substation that is one of problems in such substation that their equipment are made by Hyundai
company and other several company.
VI. CONCLUSION
In this paper ferroresonance phenomenon on voltage measuring transformer in real 400kV GIS
substation (karon4 power plant) has been studied. After simulation, fig 7-b and 7-c show primary and secondary
voltage waveforms of VT and fig 7-d shows primary current of VT for bus number 1. Fig 8-a and 8-b show
secondary voltage waveform of VT in presence of ferroresonance for bus 1 and bus 2 in sequence. Fig 8-c
shows the source used in simulated diagram with EMTP and fig 8-d shows the secondary voltage waveform of
VT in damping ferroresonance for bus 2. The corresponding model has been presented and for different
conditions, simulation proved ferroresonance on VTs of bus 1 and bus 2. To eliminate this phenomenon,
ZD+FDSD damper circuit had been designed and added to model, results of simulation showed success
damping of these ferroresonance oscillations.
REFERENCES
[1] K. H. Tseng P.-Y. Cheng Department of Electrical Engineering, National Taipei University of Technology, No. 1, Sec. 3, Chung-
Hsiao E. Rd.,"Mitigating 161 kV electromagnetic potential transformers’ ferroresonance with damping reactors in gas-insulated
switchgear"Published in IET Generation, Transmission & Distribution Received on 27th June 2010.
[2] Hyundai Reports ”ferroresonance of VT ” Hyundai Heavy Industries Co., LTD ,Electro Electric System Div./Electro-Mechanical
Research Institute 2011.
[3] David A. N. Jacobson, Member IEEE "Examples of Ferroresonance in a High Voltage Power System "2003 IEEE.
[4] Q ing Liu, Yufeng Zhang “Influence of Switching Conditions on Very Fast Transient Over-voltage in500kV Gas Insulated Substation”
Department of Electrical and Control Engineering Of Xi’an University of Science and Technology, Xi’an, 710054, China.
[5] SaeedShahabi, ElectricalEngineering Department, Iran University of Science & Technology, Rasul EsmaeilniaShirvani, Islamic Azad
University of Saveh, Mohammad Purrezagholi, Babol University of Technology “Mitigating Ferroresonance in Coupling Capacitor
Voltage Transformers with Ferroresonance Suppressing Circuits"©2009 IEEE.
[6] H. Mohseni, J. Jadidian, A. A. Shayegani-Akmal, E. Hashemi, A. Naieny and E. Agheb "In-situ Insulation Test of 400 kV GIS", IEEE
Transactions on Dielectrics and ElectricalInsulation Vol. 15, No. 5; October 2008 .
[7] D. Shoup, Member, IEEE, J. Paserba, Fellow, IEEE, D. Sullivan, Member, IEEE P. Bolin, Senior Member, IEEE, R. Whiteside, Senior
Member, IEEE "ferroresonance Analysis of 500 kv Gas-Insulated substation "2011 IEEE.
[8] A. Abbasi, and A. Seifi, "Fast and perfect damping circuit for ferroresonance phenomena in coupling capacitor voltage transformers,"
Journal of Electric Power Components and Systems, Apr. 2009.
[9] W. Piasecki, M. Stosur, M. Florkowski, M. Fulczyk, B. Lewandowski"Mitigating Ferroresonance in HV inductive", Presented at the
International Conference on Power System Transients (IPST’09) in Kyoto, Japan on June 3-6, 2009.

Contenu connexe

Tendances

Automatic phase changer
Automatic phase changerAutomatic phase changer
Automatic phase changer
viv3ksharma
 
Ppt of ehv ac transmission
Ppt of ehv ac transmissionPpt of ehv ac transmission
Ppt of ehv ac transmission
Sumit Kumar
 

Tendances (20)

Performance Analysis of Actual Step and Mesh Voltage of Substation Grounding ...
Performance Analysis of Actual Step and Mesh Voltage of Substation Grounding ...Performance Analysis of Actual Step and Mesh Voltage of Substation Grounding ...
Performance Analysis of Actual Step and Mesh Voltage of Substation Grounding ...
 
EHV AC
EHV ACEHV AC
EHV AC
 
HEMT
HEMTHEMT
HEMT
 
Earthing
EarthingEarthing
Earthing
 
Substation grounding grid design using Alternative Transients Program-ATP and...
Substation grounding grid design using Alternative Transients Program-ATP and...Substation grounding grid design using Alternative Transients Program-ATP and...
Substation grounding grid design using Alternative Transients Program-ATP and...
 
Power capacity of transmission lines
Power capacity of transmission linesPower capacity of transmission lines
Power capacity of transmission lines
 
Superjunction concept@nitc
Superjunction concept@nitcSuperjunction concept@nitc
Superjunction concept@nitc
 
Electric power grid
Electric power gridElectric power grid
Electric power grid
 
Line upgrade
Line upgradeLine upgrade
Line upgrade
 
Neutral grounding project seminar
Neutral grounding project seminarNeutral grounding project seminar
Neutral grounding project seminar
 
High electron mobility transistor
High electron mobility transistorHigh electron mobility transistor
High electron mobility transistor
 
Production and distribution of electricity
Production and distribution of electricityProduction and distribution of electricity
Production and distribution of electricity
 
State of the art GAN on Silicon - the grail of power electronics
State of the art   GAN on Silicon  - the grail of power electronicsState of the art   GAN on Silicon  - the grail of power electronics
State of the art GAN on Silicon - the grail of power electronics
 
PresenWide Bandgap Semiconductor Materials for Improved Performance Microwave...
PresenWide Bandgap Semiconductor Materials for Improved Performance Microwave...PresenWide Bandgap Semiconductor Materials for Improved Performance Microwave...
PresenWide Bandgap Semiconductor Materials for Improved Performance Microwave...
 
Neutral grounding
Neutral groundingNeutral grounding
Neutral grounding
 
Automatic phase changer
Automatic phase changerAutomatic phase changer
Automatic phase changer
 
Earthing of epg
Earthing  of epg Earthing  of epg
Earthing of epg
 
Ppt of ehv ac transmission
Ppt of ehv ac transmissionPpt of ehv ac transmission
Ppt of ehv ac transmission
 
Distribution system 2
Distribution system  2Distribution system  2
Distribution system 2
 
Power quality surveys
Power quality surveys  Power quality surveys
Power quality surveys
 

En vedette

EPiServer 7.5 Commerce
EPiServer 7.5 CommerceEPiServer 7.5 Commerce
EPiServer 7.5 Commerce
Beth McEnery
 
Zinc Sulfate As a Growth Disruptor for Spodoptera littoralis With Reference t...
Zinc Sulfate As a Growth Disruptor for Spodoptera littoralis With Reference t...Zinc Sulfate As a Growth Disruptor for Spodoptera littoralis With Reference t...
Zinc Sulfate As a Growth Disruptor for Spodoptera littoralis With Reference t...
IOSR Journals
 

En vedette (20)

Ferro-resonance due to interruption of magnetizing currents of a cable fed tr...
Ferro-resonance due to interruption of magnetizing currents of a cable fed tr...Ferro-resonance due to interruption of magnetizing currents of a cable fed tr...
Ferro-resonance due to interruption of magnetizing currents of a cable fed tr...
 
Transformer Failures and Case Studies
Transformer Failures and Case StudiesTransformer Failures and Case Studies
Transformer Failures and Case Studies
 
EPiServer 7.5 Commerce
EPiServer 7.5 CommerceEPiServer 7.5 Commerce
EPiServer 7.5 Commerce
 
A Modular Approach To Intrusion Detection in Homogenous Wireless Network
A Modular Approach To Intrusion Detection in Homogenous Wireless NetworkA Modular Approach To Intrusion Detection in Homogenous Wireless Network
A Modular Approach To Intrusion Detection in Homogenous Wireless Network
 
I0355561
I0355561I0355561
I0355561
 
Area-Efficient VLSI Implementation for Parallel Linear-Phase FIR Digital Filt...
Area-Efficient VLSI Implementation for Parallel Linear-Phase FIR Digital Filt...Area-Efficient VLSI Implementation for Parallel Linear-Phase FIR Digital Filt...
Area-Efficient VLSI Implementation for Parallel Linear-Phase FIR Digital Filt...
 
Modeling Of Carbon Deposit From Methane Gas On Zeolite Y Catalyst Activity In...
Modeling Of Carbon Deposit From Methane Gas On Zeolite Y Catalyst Activity In...Modeling Of Carbon Deposit From Methane Gas On Zeolite Y Catalyst Activity In...
Modeling Of Carbon Deposit From Methane Gas On Zeolite Y Catalyst Activity In...
 
Effect of Switching angle on Magnetizing flux and Inrush current of a Transfo...
Effect of Switching angle on Magnetizing flux and Inrush current of a Transfo...Effect of Switching angle on Magnetizing flux and Inrush current of a Transfo...
Effect of Switching angle on Magnetizing flux and Inrush current of a Transfo...
 
Zinc Sulfate As a Growth Disruptor for Spodoptera littoralis With Reference t...
Zinc Sulfate As a Growth Disruptor for Spodoptera littoralis With Reference t...Zinc Sulfate As a Growth Disruptor for Spodoptera littoralis With Reference t...
Zinc Sulfate As a Growth Disruptor for Spodoptera littoralis With Reference t...
 
Comparison Study of Lossless Data Compression Algorithms for Text Data
Comparison Study of Lossless Data Compression Algorithms for Text DataComparison Study of Lossless Data Compression Algorithms for Text Data
Comparison Study of Lossless Data Compression Algorithms for Text Data
 
Growth Performance of Rats Maintained On Citrullus colocynthis Seed Coat-base...
Growth Performance of Rats Maintained On Citrullus colocynthis Seed Coat-base...Growth Performance of Rats Maintained On Citrullus colocynthis Seed Coat-base...
Growth Performance of Rats Maintained On Citrullus colocynthis Seed Coat-base...
 
Творческое чтение и развитие одарённости
Творческое чтение и развитие одарённостиТворческое чтение и развитие одарённости
Творческое чтение и развитие одарённости
 
H1 n1.q&a
H1 n1.q&aH1 n1.q&a
H1 n1.q&a
 
Performance Analysis of CSI Based PV system During LL and TPG faults
Performance Analysis of CSI Based PV system During LL and TPG faultsPerformance Analysis of CSI Based PV system During LL and TPG faults
Performance Analysis of CSI Based PV system During LL and TPG faults
 
Performance evaluation of Hard and Soft Wimax by using PGP and PKM protocols ...
Performance evaluation of Hard and Soft Wimax by using PGP and PKM protocols ...Performance evaluation of Hard and Soft Wimax by using PGP and PKM protocols ...
Performance evaluation of Hard and Soft Wimax by using PGP and PKM protocols ...
 
царскосельский лицей а.с.пушкина
царскосельский лицей а.с.пушкинацарскосельский лицей а.с.пушкина
царскосельский лицей а.с.пушкина
 
Luminescence of Cesium Thiocyanate (CsSCN) doped with Eu2+ (CsSCN:Eu2+)
Luminescence of Cesium Thiocyanate (CsSCN) doped with Eu2+ (CsSCN:Eu2+)Luminescence of Cesium Thiocyanate (CsSCN) doped with Eu2+ (CsSCN:Eu2+)
Luminescence of Cesium Thiocyanate (CsSCN) doped with Eu2+ (CsSCN:Eu2+)
 
H0345259
H0345259H0345259
H0345259
 
The Wind Powered Generator
The Wind Powered GeneratorThe Wind Powered Generator
The Wind Powered Generator
 
Capacitive voltage and current induction phenomena in GIS substation
Capacitive voltage and current induction phenomena in GIS substationCapacitive voltage and current induction phenomena in GIS substation
Capacitive voltage and current induction phenomena in GIS substation
 

Similaire à Modeling of Ferro-resonance on the VT of GIS substation

Simulation and Results of Static Var Compensator for Electric Arc Furnace No ...
Simulation and Results of Static Var Compensator for Electric Arc Furnace No ...Simulation and Results of Static Var Compensator for Electric Arc Furnace No ...
Simulation and Results of Static Var Compensator for Electric Arc Furnace No ...
ijtsrd
 
Harmonic Mitigation in Distribution System by using Passive Filters
Harmonic Mitigation in Distribution System by using Passive FiltersHarmonic Mitigation in Distribution System by using Passive Filters
Harmonic Mitigation in Distribution System by using Passive Filters
ijtsrd
 
Modeling and analysis of transformer
Modeling and analysis of transformerModeling and analysis of transformer
Modeling and analysis of transformer
IJARIIT
 

Similaire à Modeling of Ferro-resonance on the VT of GIS substation (20)

Simulation and Results of Static Var Compensator for Electric Arc Furnace No ...
Simulation and Results of Static Var Compensator for Electric Arc Furnace No ...Simulation and Results of Static Var Compensator for Electric Arc Furnace No ...
Simulation and Results of Static Var Compensator for Electric Arc Furnace No ...
 
Fea of pcb multilayer stack up high voltage planar transformer for aerospace...
Fea of  pcb multilayer stack up high voltage planar transformer for aerospace...Fea of  pcb multilayer stack up high voltage planar transformer for aerospace...
Fea of pcb multilayer stack up high voltage planar transformer for aerospace...
 
Design and Simulation of Permanent Magnet Linear Generator for Wave Energy Po...
Design and Simulation of Permanent Magnet Linear Generator for Wave Energy Po...Design and Simulation of Permanent Magnet Linear Generator for Wave Energy Po...
Design and Simulation of Permanent Magnet Linear Generator for Wave Energy Po...
 
electrical system
electrical system electrical system
electrical system
 
C0212014018
C0212014018C0212014018
C0212014018
 
Harmonic Mitigation in Distribution System by using Passive Filters
Harmonic Mitigation in Distribution System by using Passive FiltersHarmonic Mitigation in Distribution System by using Passive Filters
Harmonic Mitigation in Distribution System by using Passive Filters
 
Voltage Profile Improvement using Switched Capacitors: Case of Single Wire Ea...
Voltage Profile Improvement using Switched Capacitors: Case of Single Wire Ea...Voltage Profile Improvement using Switched Capacitors: Case of Single Wire Ea...
Voltage Profile Improvement using Switched Capacitors: Case of Single Wire Ea...
 
Ferroresonance Conditions in Wind Parks
Ferroresonance Conditions in Wind Parks Ferroresonance Conditions in Wind Parks
Ferroresonance Conditions in Wind Parks
 
overvoltage in distribution network
overvoltage in distribution networkovervoltage in distribution network
overvoltage in distribution network
 
Modeling and analysis of power transformers under ferroresonance phenomenon
Modeling and analysis of power transformers under ferroresonance phenomenonModeling and analysis of power transformers under ferroresonance phenomenon
Modeling and analysis of power transformers under ferroresonance phenomenon
 
Techno economic study of series current limiting reactor and its impact in th...
Techno economic study of series current limiting reactor and its impact in th...Techno economic study of series current limiting reactor and its impact in th...
Techno economic study of series current limiting reactor and its impact in th...
 
Transients Caused by Switching of 420 kV Three-Phase Variable Shunt Reactor
Transients Caused by Switching of 420 kV Three-Phase Variable Shunt ReactorTransients Caused by Switching of 420 kV Three-Phase Variable Shunt Reactor
Transients Caused by Switching of 420 kV Three-Phase Variable Shunt Reactor
 
Simulation and Partial Discharge Measurement in 400kv Typical GIS Substation
Simulation and Partial Discharge Measurement in 400kv Typical GIS SubstationSimulation and Partial Discharge Measurement in 400kv Typical GIS Substation
Simulation and Partial Discharge Measurement in 400kv Typical GIS Substation
 
A Study of Thermal Behaviour of HTS Devices at Alternating Current
A Study of Thermal Behaviour of HTS Devices at Alternating Current A Study of Thermal Behaviour of HTS Devices at Alternating Current
A Study of Thermal Behaviour of HTS Devices at Alternating Current
 
Analsis of very fast transient over voltages in gas insulated substations
Analsis of very fast transient over voltages in gas insulated substationsAnalsis of very fast transient over voltages in gas insulated substations
Analsis of very fast transient over voltages in gas insulated substations
 
Analsis of very fast transient over voltages in gas insulated substations
Analsis of very fast transient over voltages in gas insulated substationsAnalsis of very fast transient over voltages in gas insulated substations
Analsis of very fast transient over voltages in gas insulated substations
 
Frequency response analysis for transformer tap changer damage detection
Frequency response analysis for transformer tap changer damage detectionFrequency response analysis for transformer tap changer damage detection
Frequency response analysis for transformer tap changer damage detection
 
Inrush current reduction in three phase power transformer by using prefluxing...
Inrush current reduction in three phase power transformer by using prefluxing...Inrush current reduction in three phase power transformer by using prefluxing...
Inrush current reduction in three phase power transformer by using prefluxing...
 
Modeling and analysis of transformer
Modeling and analysis of transformerModeling and analysis of transformer
Modeling and analysis of transformer
 
Design of 230 kV Twin Bundle Double Circuit Overhead Transmission Line
Design of 230 kV Twin Bundle Double Circuit Overhead Transmission LineDesign of 230 kV Twin Bundle Double Circuit Overhead Transmission Line
Design of 230 kV Twin Bundle Double Circuit Overhead Transmission Line
 

Plus de IOSR Journals

Plus de IOSR Journals (20)

A011140104
A011140104A011140104
A011140104
 
M0111397100
M0111397100M0111397100
M0111397100
 
L011138596
L011138596L011138596
L011138596
 
K011138084
K011138084K011138084
K011138084
 
J011137479
J011137479J011137479
J011137479
 
I011136673
I011136673I011136673
I011136673
 
G011134454
G011134454G011134454
G011134454
 
H011135565
H011135565H011135565
H011135565
 
F011134043
F011134043F011134043
F011134043
 
E011133639
E011133639E011133639
E011133639
 
D011132635
D011132635D011132635
D011132635
 
C011131925
C011131925C011131925
C011131925
 
B011130918
B011130918B011130918
B011130918
 
A011130108
A011130108A011130108
A011130108
 
I011125160
I011125160I011125160
I011125160
 
H011124050
H011124050H011124050
H011124050
 
G011123539
G011123539G011123539
G011123539
 
F011123134
F011123134F011123134
F011123134
 
E011122530
E011122530E011122530
E011122530
 
D011121524
D011121524D011121524
D011121524
 

Dernier

Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
dharasingh5698
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Christo Ananth
 

Dernier (20)

Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELLPVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
 
Intze Overhead Water Tank Design by Working Stress - IS Method.pdf
Intze Overhead Water Tank  Design by Working Stress - IS Method.pdfIntze Overhead Water Tank  Design by Working Stress - IS Method.pdf
Intze Overhead Water Tank Design by Working Stress - IS Method.pdf
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdf
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
 
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leap
 
Call for Papers - International Journal of Intelligent Systems and Applicatio...
Call for Papers - International Journal of Intelligent Systems and Applicatio...Call for Papers - International Journal of Intelligent Systems and Applicatio...
Call for Papers - International Journal of Intelligent Systems and Applicatio...
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
Unit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfUnit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdf
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
 
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
 
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
 
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdf
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
 

Modeling of Ferro-resonance on the VT of GIS substation

  • 1. IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-ISSN: 2278-1676,p-ISSN: 2320-3331, Volume 6, Issue 5 (Jul. - Aug. 2013), PP 68-73 www.iosrjournals.org www.iosrjournals.org 68 | Page Modeling of Ferro-resonance on the VT of GIS substation S.M.Hassan.Hosseini1 , Y. Toghani Holari2 , S.M.Hosseini.Bafghi3 1, 2, 3 (Department of Electrical Engineering, Islamic Azad University South Tehran Branch, Tehran, IRAN) Abstract : The main subject of the essay is study of ferroresonance in the voltage transformers at 400kV GIS substation. Ferroresonance has destructive effects such as, undulations of high voltages, warming of transformers, increasing of heat, temperature increasing and damaging voltage transformers, high noise due to evolution due to magnet and bad working of protective instruments. So we have to apply limitations on system parameters to avoid such an undesirable phenomenon like this. In this paper ferroresonance phenomenon on VTs of real GIS substation (karon 4 power plant had been studied. With regarding high risk of ferroresonance due to studied substation conditions, damping circuit (FDSD, ZD) had been designed with help of EMTP-RV and the results are presented in two conditions of being without damping and by using of damping in the circuit. The results show damping circuit is successful in obviation of these dangerous oscillations. Keywords: Gas Insulated Substation (GIS), Voltage Transformers (VT), Ferroresonance, FDSD, ZD I. INTRODUCTION Regarding to the advantages of GIS substations in comparison with AIS (Air Insulated Substation) and purposing that instruments such as current and voltage transformer , bypass disconnector switch, high voltage conductor , grounding switchgear, breaker and etc. that are kept in boxes under pressure of SF6 gas , and increasing usage of these substations toward the past and regarding to this point that urban and industries areas with increasing load and insufficient area and needing high voltages are regarded , in last year's the use of GIS substation have increased.[1]. In this paper we study the Karoon 4 power plant GIS substation that is a 400kV substation with double bus bar and disconnector switch, this substation is fed by 4 single phase 100MW transformers. The outputs of these transformers are connected to the 400kV network with 4 air lines. Despite the advantages of this gas insulated substations, it has fundamental problems. One of the main ingredients of destruction of the instruments in GIS substations is ferroresonance that influenced the insulation of network at different point. Ferroresonance is one of the rare and destructive phenomena in power network that figured as a nonlinear resonance that happen between the capacitor of the network and the nonlinear inductance of voltage transformer at the saturation instant. The word of ferroresonance, that arrived to the books and papers from the end of the second decade of 20th century , use for all the oscillation phenomena in electrical circuits that consist of at least nonlinear self , capacitor , voltage source (generally sinusoidal). The effective elements in causing resonance and ferroresonance in power systems are, harmonic, core saturating, changing inductance of wiring, cutting of 1 or 2 phases of system, unsymmetrical load, inappropriate use of circuit breakers and fuses, using cables with high capacitance. Ferroresonance has other destructive effects such as oscillation of high voltages, intricacy in wave forms of voltage and current , warming of transformers , damaging voltage transformers (VT), for example in Karoon 4 power plant 400kV GIS substation , loud noise due of evolution due to magnet , malfunction protective instruments. Numerous cases of ferroresonance in power system have been reported in years. In last year's the number of ferroresonance because of the intricacy of system and operating modern instrument has increased. [2], [3] outbreak of ferroresonanc has some signs like permanent over voltage with vast amplitude as phase to phase or phase to ground, permanent over current with vast amplitude, shifting voltage zero point, increasing temperature of voltage transformer, continual increasing of the noise altitude of transformers and reactors, damaging electrical equipment's such as capacitor banks and CVT because of increasing the thermal effect or breakage of dampers of the protective equipment's. Therefore some limitations should be applied to parameters of systems to avoid occurrence of undesirable phenomena like these. [4], [5]. All of the studies have been simulated by EMTP-RV software. II. Parallel Capacitor In H.V Circuit Breaker Power capacitors have different usage in structure and mechanism of power circuit breaker especially at high voltage levels. Like grading capacitors that have two breaking boxes in series. Voltage usually doesn’t distribute equally on breaking boxes. To avoid making stress of high voltage and smoothing voltage on them, capacitors parallel with contacts of circuit breaker that usually have capacity between 900 to 1600 pF for each breaking box are used. Although by the development of technology usage of these capacitors have been reduced but they are used in high voltages yet.[3],[6]. Some defects of these capacitors are increasing the risk of
  • 2. Modeling of Ferro-resonance on the VT of GIS substation www.iosrjournals.org 69 | Page ferroresonance with nearby voltage transformers, increasing the weight, complexity of installation operation and increasing leakage current. III. Karoon 4 Case Study The purpose of this paper is to study the ferroresonance on voltage transformers (VT) in Karoon 4 power plant GIS 400kv substation as an example of GIS substation with bus bar and long line that have been effected by this phenomenon by increasing the voltage and damaging isolation and heating, destruction and damaging of VT . These simulations are done by EMTP-RV Software and finally propose the practical method to resist it. There conductive wires of A & C phase of damping reactor have been burnt by the high current at secondary circuit because of the single phase with VT ferroresonance. One of the reasons of this phenomenon is that the VT Company adequately doesn’t consider the capacity of the damping reactor to absorb the resonance energy in VT in some cases of GIS switching conditions during first energizing at site. [7] Special recommendation presented in this paper offer to avoiding over heating Beside VT of BUS 1 and 2 and damping reactor until additional FDSD (Ferroresonance Detecting and Suppression Device) at site became adjusted. The related circuit breaker (CB) for each 400kV GIS bay should be closed about 5 minutes after closing of both DS's (disconnecting switches) during energization. Reversely, during power Outage one of both DS's should be opened within 5 minutes after opening of the circuit breaker [3], [8]. On 19 & 24 November in 2010, VT of #1 bus was exposed to ferro-resonance 2 times during energizing (10min.) & de-energizing (2min.) by switching of CB & DS of C03 bay that is shown is shown in Figure 1. Fig1. Karoon4 400kV substation single line diagram state of energizing from first circuit output line of Karon3 and bus 1 and corresponding VT On 20 & 21 November in 2010, VT of #2 bus were exposed to ferroresonance 2 times during energizing (5min.) and de-energizing (2min.) by switching of CB & DS of C04 bay through #2 bus bar. Fig2. Karoon4 400kV substation single line diagram state of energizing from second circuit output line of Karoon3 and bus 2 and corresponding VT
  • 3. Modeling of Ferro-resonance on the VT of GIS substation www.iosrjournals.org 70 | Page Fig3.Burnt Damping Reactor (ZD) of A-phase for #2 Bus VT IV. Ferroresonance Detection Supervision Devise (Fdsd) By regarding presented figures of this part such as fig 4 , a VT with conversion rate of 400/ to 110/ connected to a ferroresonace detector circuit is shown .[2]. Fig4. Information for adjusting FDSD In continue internal circuit of detecting unit is connected to burden with value of 0.33 that is equivalent of parallel branches. and also in figures 5 and 6, appearance of a FDSD and different part of operating lamp A,B , Power Lamp , sensitivity Change , Test Switch , Optional Output Control in three phase and single phase detector unit is shown. Fig5 .picture of seeming figure of FDSD
  • 4. Modeling of Ferro-resonance on the VT of GIS substation www.iosrjournals.org 71 | Page Fig6. Diagram of three phase FDSD connection V. Ferroresonance Analysis With Fdsd+Zd The conditions of standard analysis that can be used in done simulation are as below: 1. CB Capacitance=4,000pF/phase, 2. Unit Earth Capacitance for GIS=52.4pF/m 3. Internal Earth Capacitance of M.Tr: 13,366pF/phase 4. Internal Earth Capacitance of in Shunt Reactor: 3,382pf/phase In above analysis, karoon 4 power plant GIS substation, that is a 400kV substation with double bus bar with bypass disconnector switch, is studied and equivalent circuit of GIS substation, that consist of main parameters like, source and resistance series with it, and CB that capacitor C1 is parallel with it, and as explained at section 3 above GIS circuit breaker had two 2000pF capacitor parallel with contacts of circuit breaker and equivalent capacitance is 4000pf. The simulation is done on the basis of these values. Above simulated circuit consist of equivalent capacitor of GIS substation in different studied conditions that are as a result of summation of existing parameters which is studied in bellow waveforms. Also in this circuit, one VT with prime voltage of 400kV and secondary voltage of 105V is used for simulation and at last ZD and FDSD equivalent circuit for damping probability of ferroresonance due to 4000pf capacitor parallel with CB are put .[7],[9]. Fig7-a- EMTP model for survey ferroresonance with FDSD+ZD  if C1=4000 pF and C2=3820pF (for VT of bus 1) Which capacitor (C2= (53.2+5.6+5.6+2+6.5)*52.4=3820). 0 0.5 1 1.5 2 2.5 -300 -200 -100 0 100 200 300 t (ms) voltagev1(v) Fig7-b- voltage waveform of VT secondary voltage in damping ferroresonance (V1)
  • 5. Modeling of Ferro-resonance on the VT of GIS substation www.iosrjournals.org 72 | Page 0 0.5 1 1.5 2 2.5 -4 -2 0 2 4 x 10 5 t (ms) voltage(v) Fig7-c- voltage waveform of VT primary 0 0.5 1 1.5 2 2.5 -100 -50 0 50 100 t (ms) current(i) Fig7-d- current waveform of VT primary  if C1=4000 pf and C2= 7669pf ( for VT bus ) Which capacitor (C2= (53.2+5.6+7.05+7.2*9+2+7.2+6.5)*52.4 =7669) 0 0.5 1 1.5 2 2.5 -800 -600 -400 -200 0 200 400 600 800 t (ms) voltagev1(v) Fig8-a- VT secondary voltage waveform in presence of ferroresonance (V1) 0 0.5 1 1.5 2 2.5 -500 -400 -300 -200 -100 0 100 200 300 400 500 t (ms) voltagev2(v) Fig8-b- VT secondary voltage waveform in presence of ferroresonance (V2) 0 0.5 1 1.5 2 2.5 -4 -2 0 2 4 x 10 5 t (ms) voltage(v) Fig8-c- used voltage source waveform in simulated diagram with EMTP
  • 6. Modeling of Ferro-resonance on the VT of GIS substation www.iosrjournals.org 73 | Page 0 0.5 1 1.5 2 2.5 -400 -300 -200 -100 0 100 200 300 400 500 t (ms) voltagev2(v) Fig8-d- VT secondary voltage waveform in damping ferroresonance (V2) The structure of gas switchers generally act like a capacitor (energized conductor-gas insulator- grounded body). Also because of the mentioned reasons in high voltages, capacitors parallel with breaker contacts are used. Capacitor parallel with breaker contacts are in series with GIS switcher capacitor, therefore always there is a path for transmission of capacitor current, even when the breaker is in open state. This current cause the voltage division between two capacitors and whatever the ratio of breaker parallel capacitor to GIS capacitor is larger (lower impedance), voltage after circuit breaker and on the bus bar will be larger. GIS circuit breaker existing in mentioned substation has two 2000pf capacitors parallel with breaker contact that the equivalent capacitance will be 4000pf and can cause the ferroresonance on equipment's like VT. Different producers of gas switchers use these capacitors to increase the operation of their circuit breakers. [8], [9]. One effect of ferroresonance due to breaker parallel capacitor is heating and burning VT in Karoon 4 power plant 400kV GIS substation that is one of problems in such substation that their equipment are made by Hyundai company and other several company. VI. CONCLUSION In this paper ferroresonance phenomenon on voltage measuring transformer in real 400kV GIS substation (karon4 power plant) has been studied. After simulation, fig 7-b and 7-c show primary and secondary voltage waveforms of VT and fig 7-d shows primary current of VT for bus number 1. Fig 8-a and 8-b show secondary voltage waveform of VT in presence of ferroresonance for bus 1 and bus 2 in sequence. Fig 8-c shows the source used in simulated diagram with EMTP and fig 8-d shows the secondary voltage waveform of VT in damping ferroresonance for bus 2. The corresponding model has been presented and for different conditions, simulation proved ferroresonance on VTs of bus 1 and bus 2. To eliminate this phenomenon, ZD+FDSD damper circuit had been designed and added to model, results of simulation showed success damping of these ferroresonance oscillations. REFERENCES [1] K. H. Tseng P.-Y. Cheng Department of Electrical Engineering, National Taipei University of Technology, No. 1, Sec. 3, Chung- Hsiao E. Rd.,"Mitigating 161 kV electromagnetic potential transformers’ ferroresonance with damping reactors in gas-insulated switchgear"Published in IET Generation, Transmission & Distribution Received on 27th June 2010. [2] Hyundai Reports ”ferroresonance of VT ” Hyundai Heavy Industries Co., LTD ,Electro Electric System Div./Electro-Mechanical Research Institute 2011. [3] David A. N. Jacobson, Member IEEE "Examples of Ferroresonance in a High Voltage Power System "2003 IEEE. [4] Q ing Liu, Yufeng Zhang “Influence of Switching Conditions on Very Fast Transient Over-voltage in500kV Gas Insulated Substation” Department of Electrical and Control Engineering Of Xi’an University of Science and Technology, Xi’an, 710054, China. [5] SaeedShahabi, ElectricalEngineering Department, Iran University of Science & Technology, Rasul EsmaeilniaShirvani, Islamic Azad University of Saveh, Mohammad Purrezagholi, Babol University of Technology “Mitigating Ferroresonance in Coupling Capacitor Voltage Transformers with Ferroresonance Suppressing Circuits"©2009 IEEE. [6] H. Mohseni, J. Jadidian, A. A. Shayegani-Akmal, E. Hashemi, A. Naieny and E. Agheb "In-situ Insulation Test of 400 kV GIS", IEEE Transactions on Dielectrics and ElectricalInsulation Vol. 15, No. 5; October 2008 . [7] D. Shoup, Member, IEEE, J. Paserba, Fellow, IEEE, D. Sullivan, Member, IEEE P. Bolin, Senior Member, IEEE, R. Whiteside, Senior Member, IEEE "ferroresonance Analysis of 500 kv Gas-Insulated substation "2011 IEEE. [8] A. Abbasi, and A. Seifi, "Fast and perfect damping circuit for ferroresonance phenomena in coupling capacitor voltage transformers," Journal of Electric Power Components and Systems, Apr. 2009. [9] W. Piasecki, M. Stosur, M. Florkowski, M. Fulczyk, B. Lewandowski"Mitigating Ferroresonance in HV inductive", Presented at the International Conference on Power System Transients (IPST’09) in Kyoto, Japan on June 3-6, 2009.