SlideShare une entreprise Scribd logo
1  sur  61
CPD


Ground Source Heat Pumps
   Jason Cox – National Sales Manager
CPD

  ENER-G Group Overview
Products & Solutions
ENER-G Sustainable Technologies




               Heat pumps
Heat Pumps
 Design
 Supply
 Install
 Commission
 Maintenance
Technology Principles
Standard Rating Conditions


  GSHP – Brine 0C & Water @ 35/30C

  ASHP – Air @ 7C & Water @ 35/30C




                                     EN14511
ASHP Performance Curves



Heat Output kW




                 Entering Water Temperature   35°C
                                              50 °C
ASHP Performance Curves




 C.O.P.




              Entering Water Temperature   35 °C
                                           50 °C
Standard Rating Conditions


  GSHP – Brine 0C & Water @ 35/30C

  ASHP – Air @ 7C & Water @ 35/30C




                                     EN14511
GSHP Performance Curves



Heat Output kW




                 Entering Water Temperature   35 °C
                                              50 °C
GSHP Performance Curves



 C.O.P.




             Entering Water Temperature   35 °C
                                          50 °C
Ground Source Applications
Collector Options
•Borehole Installation
•Slinky / Horizontal
Installation
•Lake / Pond Loops
•Energy Pile Installations
Vertical & Horizontal Loops
Collectors & Chambers
Ground Loop Design
Design Data

•Peak loads
•Load profile
•Geology
•Available space
Assumptions
  Output                                  99kW
  Natural gas                             3.1pkWh
  Electricity                             11.46p kWh

  Running hours                           1250
  Electricity                             *0.524g/kWh
  Natural gas                             *0.183g/kWh


         Full load hours x Output (kW) = kWh divided by efficiency = Input
                    Input x Cost of energy = Annual running cost




                *http://www.bre.co.uk/filelibrary/SAP/2009/SAP-2009_9-90.pdf
Ground Source Heat Pumps

System              Capital Cost (£)     Annual Running Cost (£)       Carbon Output


GSHP                       98,000                  3,545                     16,211
                                                (RHI £5,375)



         1250 kWh x 99kW = 123,750kWh per annum divided by 4 C.O.P = 30,938kWh

                  30,938kWh x 11.46ppkWh = £3,545 Annual Running Cost

                       RHI @ 4.3pkWh for installation less than 99kW
Comparison Table (99kW)
System   Efficiency   Capital Cost (£)   Annual Running Cost      Carbon Output
           (COP)                                 (£)
Boiler      0.9           15,000                4,262                  25,162


ASHP       *2.2           60,000                6,446                  29,475


GSHP        4.0           98,000                3,545                  16,211
                                             (RHI £5,375)




              *http://www.energysavingtrust.org.uk/Media/node_1422/Getting-
              warmer-a-field-trial-of-heat-pumps-PDF
Longfield Academy case study

New-build high school combines ground source heat pumps and solar thermal technology for renewable heating and
cooling
 The project
 The construction of a new academy building for 1,150 students combines ground source heat
 pumps, with solar thermal technology to maximise renewable energy efficiency.

 The solution
 ENER-G has installed 35 boreholes and completed work on the plant room, to accommodate four
 ground source heat pumps with a combined capacity of 200kW. A total of 22 solar thermal panels
 have been installed, covering 44 square metres of the Academy’s flat roof.

 The benefits
 •It is expected to achieve a minimum ‘Very Good’ rating under BREEAM for schools, as a result of
 using renewable power sources, and extensive use of insulation to secure a thermal performance
 15% beyond current standards.
 •The installed renewable technologies will supply heating and hot water to the academy, together
 with passive under-floor cooling in the summer months. This is projected to reduce the Academy’s
 carbon dioxide emissions from its heating system by up to 40%.
Malvern Community Hospital case study

New hospital combines ground source heat pumps and a combined heat and power system to generate its own green
power.
 The project
 The new-build Malvern Community Hospital opened in autumn 2010 and provides both
 in-patient and out-patient services. ENER-G delivered a solution that was considered the most
 efficient means of meeting the building’s heating demands combining two low carbon
 technologies – a ground source heat pump system and a combined heat and power (CHP) unit.
 This is the first time that these technologies have been used in combination in the UK’s healthcare
 sector.

 The solution
 The ground source system comprises 25 boreholes and two heat pumps with combined capacities
 of 125kW for both heating and cooling. The ENER-G CHP system is a reciprocating gas engine
 rated at 33kW of electrical output generating 55kW of useful thermal output for the building and
 the          ground           loop         for        the         heat           pump.

 The benefits
 • The hospital has achieved BREEAM rating ‘Excellent’ and is projected to save on its energy bills
 and reduce its carbon emissions by 15 tonnes per annum.
 • A low maintenance option, with the ground source system having a lifetime in excess of 50
 years, and the heat pumps lasting up to 25 years.
 • With the presence of a CHP system at the same site the electricity generated by the CHP unit
 can be utilised to power the heat pump
Summary
  Feasibility

  Project Management

  In-house drilling rigs & teams

  In-house heat pump install team

  Single point responsibility
Thank You


www.energ.co.uk
CPD


Gas Absorption Heat Pumps
  Mark Wilson – National Product Manager
Contents

Gas Absorption Heat Pumps
- Absorption Technology
- Different types of GAHP
- Benefits
- Integration
Gas Absorption Heat Pumps

 Absorption Technology
 Different types of GAHP
 Benefits
 Integration
Development of Gas
Absorption Heat Pumps
Principle of compression
Principle of Compression Heat Pump
heat pump
Principle of gas absorption
heat pump
                              Expansion valve




           Low temperature
                 gas
                                                        Hot gas
                              Heat pump
                                                                           USEFUL
                                                                           EFFECT
                                                              Heating return


                  Very cold                     Cold liquid
                   liquid     Expansion valve
How does a GAHP work?
1.   Gas burner heats ammonia and water
     solution.

2.   Ammonia gas enters condenser,
     condenses and releases heat.

3.   High pressure ammonia liquid converted
     into low pressure ammonia liquid.

4.   Ammonia liquid evaporates and draws in
     heat.

5.   Ammonia gas absorbs into ammonia
     water solution.

6.   Solution pump powers process.
How does a GAHP work?
1. Generator
Within the generator, the
low Nox gas-fired burner
heats the ammonia/water                            Expansion valve
solution via a heat
exchanger, increasing the                                 6
temperature and pressure.
                                                                 1
The strong ammonia
vapour travels to the
condenser (2) whilst the     Low temperature   5
weak ammonia solution is
circulated to the Absorber
                                   gas                   7

(5)                                                                         Hot gas
                                                    Heat pump



                                               4                 2
                                                                                   Heating return


                                   Very cold                         Cold liquid
                                    liquid         Expansion valve
                                                          3
How does a GAHP work?
2. Condenser
The high temperature,
high pressure ammonia
vapour releases its heat                          Expansion valve
into the heating system
in the condenser. The                                   6
vapour becomes a liquid
                                                                1
and travels to the
expansion valve (3) on
its way to the             Low temperature    5
evaporator (4)
                                 gas                    7

                                                   Heat pump                Hot gas




                                              4                 2
                                                                                  Heating return


                                  Very cold                         Cold liquid
                                   liquid         Expansion valve
                                                         3
How does a GAHP work?
3. Expansion valve
The high pressure
ammonia passes
through the expansion
valve where the                                 Expansion valve
pressure falls. The                                   6
ammonia now has a
reduced boiling point                                         1
and the liquid changes
back to a vapour. This
vapour passes on to      Low temperature    5

the Evaporator (4)             gas                    7

                                                 Heat pump                Hot gas




                                            4                 2
                                                                                Heating return


                                Very cold                         Cold liquid
                                 liquid         Expansion valve
                                                       3
How does a GAHP work?
4. Evaporator
A fan draws ambient air
through the evaporator.
The ambient air captured                           Expansion valve
by the ammonia vapour,
contains a high amount of                                6
free, renewable energy.
                                                                 1
The now heated, low
pressure vapour passes on
to the Absorber (5)         Low temperature    5

                                  gas                    7

                                                    Heat pump                Hot gas




                                               4                 2
                                                                                   Heating return


                                   Very cold                         Cold liquid
                                    liquid         Expansion valve
                                                          3
How does a GAHP work?
5. Absorber
In the absorber the weak
ammonia solution
recombines with the heated                            Expansion valve
vapour, changing its state
                                                            6
into a liquid. This releases
further heat to the heating                                         1
system. The now
recombined ammonia
solution is pumped (7) back    Low temperature    5
to the generator.                    gas                    7

                                                       Heat pump                Hot gas




                                                  4                 2
                                                                                      Heating return


                                      Very cold                         Cold liquid
                                       liquid         Expansion valve
                                                             3
How does a GAHP work?
6. Second expansion valve
This second valve controls the
flow of weak ammonia
between the Generator (1) and
                                                        Expansion valve
the Absorber (5)                                              6

                                                                      1


                                 Low temperature    5

                                       gas                    7

                                                         Heat pump                Hot gas




                                                    4                 2
                                                                                        Heating return


                                        Very cold                         Cold liquid
                                         liquid         Expansion valve
                                                               3
How does a GAHP work?
7. Heat pump
The pump moves the ammonia                           Expansion valve
solution from the Absorber (5)
back to the Generator (1) where                            6
the process starts again.
                                                                   1


                              Low temperature    5

                                    gas                    7

                                                      Heat pump                Hot gas




                                                 4                 2
                                                                                     Heating return


                                     Very cold                         Cold liquid
                                      liquid         Expansion valve
                                                            3
The Technology
• Water-ammonia sealed circuit : no
top-up, no drain, extremely simple
maintenance;
• Natural refrigerant : no CFC, HCFC,
HFC;
• One single moving component
(solution pump) : very high reliability;
• Exhaust flue gas water vapour
condensation: reduced energy losses
in the exhaust gas;
• Very low electrical consumption
1/10 of an equivalent electrical heat
pump.
Gas Absorption Heat Pumps
 Absorption Technology
 Different types of GAHP
 Benefits
 Integration
GAHP GS: Ground source
applications
• Nominal efficiency 170% by means of heat recovery from renewable source (ground)
• LT or HT versions (55 °C / 65 °C)
• Domestic Hot Water production up to 70°C
• Indoor installation
• Reduction in borehole quantity by up to 60%
• Cheaper civils costs against electric ground source
Ground Source applications
Collector Options
•Borehole Installation
•Slinky / Horizontal
Installation
•Lake / Pond Loops
•Energy Pile Installations
The Open University
The UK’s largest closed-loop ground source, gas absorption heat pump project,
providing low carbon heat and reducing energy consumption by up to 50%
The project
Building 12 is a 2,000m2 new-build development that forms part of the Walton Hall
Campus. The new building is targeting a BREEAM ‘Outstanding’ rating. It incorporates
natural ventilation, night time cooling, solar chimneys, automatic lighting controls, a green
roof, solar water heating and photovoltaic panels.

The solution
ENER-G drilled 13 boreholes to a depth of more than 100 metres to install a ground loop
system that feeds four gas absorption heat pumps, with a combined capacity of 140kW heat
output. This system supplies the building’s heating requirements and will achieve carbon
dioxide savings of approximately 45%, in comparison to a system heater via a condensing
boiler

The benefits
•Energy consumption reductions of up to 50%
•Exemption from the climate change levy
•Cost savings relating to the Carbon Reduction Commitment (CRC) energy efficiency scheme
and improved Building Energy Certificate ratings (EPC and DEC)
•Reduced regulatory costs as a result of low emissions, enabling points for BREEAM
assessment and compliance with Part L2A and Part L2B of the building regulations
GAHP A: Air source
applications
•Nominal efficiency 165% by means of heat recovery from renewable source (air)
• LT or HT versions (55 °C / 65 °C)
• Domestic Hot Water production up to 70°C
• Outdoor installation to free up plant room space
• Minimal drop off of output and efficiency in low ambient temperatures against electric heat pumps
GAHP A: Air source
GAHP AR: Alternate heating
and cooling
• Heating or cooling from the same unit
• 2-1 ratio of heating to cooling
• Efficiency in excess of 144%
• Outdoor installation to free up plant room
space
GAHP ACF & WS: Simultaneous
production of hot/cold water
• Heating to cooling ratio 2.5 to 1
• Efficiency in excess of 227%
• Indoor installation
• Very low electrical consumption
Gas Absorption Heat Pumps
 Absorption Technology
 Different types of GAHP
 Benefits
 Integration
Direct use of energy CO₂
savings


       h
       t
       t
       p
       :
       /
       /
       w
       w
       w
Direct use of energy CO₂
savings
• Gas produces 0.1836 kgCO₂ / kWh


• Electricity from the grid produces 0.5246 kgCO₂ /kWh



                       http://www.carbontrust.com/media/18223/ctl153_conversion_factors.pdf*
Direct use of energy CO₂
savings
• Utilized electricity from the grid produces 3* times the CO₂ of
  natural gas
• Electric HP Seasonal COP 2.25**
• GAHP Seasonal GUE 1.4
 Therefore a gas absorption heat pump produces 46 % less
               CO₂/kWh than a air source heat pump.
• If we use an example of 60 hours per week 6 months of the
  year…..
                                            http://www.carbontrust.com/media/18223/ctl153_conversion_factors.pdf*
              **http://www.energysavingtrust.org.uk/Media/node_1422/Getting-warmer-a-field-trial-of-heat-pumps-PDF
Direct use of energy CO₂
savings
Example: GAHP-A Air Source Heat Pump (36.2kW)
(Running 60 hours per week / 6 months per year)

Robur Gas Heat Pump
= 1560 (hrs) x 25.7 (kW gas) x 0.1836 (kgCO2/kWh gas)
= 7.3 Tonnes of CO2 per year

Electric Air Source Heat Pump (seasonal COP of 2.25)
= 1560 (hrs) x 16 (kW electricity) x 0.5246 (kgCO2/kWh elec)
= 13 Tonnes of CO2 per year

                                        To put that into perspective……..
1 year’s CO₂ difference would fill the Olympic swimming pool at the
                       2012 games 12 times!
Also take into account…

                       No use/leakage of F-Gases
A typical 37kW air to air electric heat pump contains about 14kg of R410a gas.

If the leakage from the system is for example 10% of the charge per year
                                      *(estimates put the Global Annual leakage rates of refrigerants at 27.8% !!)

This is equivalent to 2.5 Tonnes of CO2 per year



                        Another 5 swimming pools worth!
                           * Institute of refrigeration report 2008 (New high pressure Low GWP refrigerant blends)
Annual running costs
         Example : GAHP-A Air Source Heat Pump (36.2kW)
          (Running 60 hours per week / 6 months per year)
Robur Gas Heat Pump            Condensing Boiler                 Electric Air Source
(seasonal efficiency of      (seasonal efficiency of            Heat Pump (seasonal
       140%)                         90%)                           COP of 2.25)
 = [1560(hrs) x 0.75(LF) x   = [1560(hrs) x 0.75(LF) x         = [1560(hrs) x 0.75(LF) x
36.2(kW) x 3.1(p/kWh)] /     36.2(kW) x 3.1(p/kWh)] /         36.2(kW) x 11.46(p/kWh)] /
          1.40                         0.90                              2.25
   = £ 938 per year            = £ 1,459 per year                  = £ 2,157 per year

   Saving £500 over a condensing boiler or £1200 over an Electric Heat
                                 Pump
                                                                  Note: gas and electricity prices from SAP 2009
                                                     http://www.bre.co.uk/filelibrary/SAP/2009/SAP-2009_9-90.pdf
Annual running costs

   There are significant running cost
   savings to be achieved by using a
   Gas Absorption Heat Pump.
GSHP GAHP Covering Base Load
                                    Covering Base Load
                    140
                    130
                    120
Heating Load [kW]




                    110
                    100
                     90
                                                          Boiler
                     80
                     70
                     60
                     50
                                                          Boiler
                     40
                     30
                     20                                   GAHP
                     10
                      0
                          October   November   December   January   Febtuary   March   April
                                                           Month
Gas Absorption Heat Pumps
 Absorption Technology
 Different types of GAHP
 Benefits
 Integration
Integration of other heat
sources
Thank You


www.energ.co.uk

Contenu connexe

Tendances

Introduction to heat pumps
Introduction to heat pumpsIntroduction to heat pumps
Introduction to heat pumpsLeonardo ENERGY
 
Presentation on Heat pump and its Function.
Presentation on Heat pump and its Function.Presentation on Heat pump and its Function.
Presentation on Heat pump and its Function.Monjur Ayon
 
Unit 4 cogeneration
Unit 4 cogenerationUnit 4 cogeneration
Unit 4 cogenerationprakash0712
 
Heat engines for 10th standard new syllabus
Heat engines  for 10th standard new syllabusHeat engines  for 10th standard new syllabus
Heat engines for 10th standard new syllabusSwasthik Udupa
 
Cooling applications of solar system ppt
Cooling applications of solar system pptCooling applications of solar system ppt
Cooling applications of solar system pptvikramdangi
 
Water Efficiency in Thermal power Plant
Water Efficiency in Thermal power PlantWater Efficiency in Thermal power Plant
Water Efficiency in Thermal power PlantAtanu Maity
 
Thermal Efficiency of Buildings - Stefan Huber - Paul Heat Recovery Scotland
Thermal Efficiency of Buildings - Stefan Huber - Paul Heat Recovery ScotlandThermal Efficiency of Buildings - Stefan Huber - Paul Heat Recovery Scotland
Thermal Efficiency of Buildings - Stefan Huber - Paul Heat Recovery ScotlandEuro Energy Services
 
Air Source Heat Pumps - Thomas Dickson - Glow Worm
Air Source Heat Pumps - Thomas Dickson - Glow WormAir Source Heat Pumps - Thomas Dickson - Glow Worm
Air Source Heat Pumps - Thomas Dickson - Glow WormEuro Energy Services
 
Feedwater heater control: Level
Feedwater heater control: LevelFeedwater heater control: Level
Feedwater heater control: LevelShari Worthington
 
Waste Heat Recovery Project
Waste Heat Recovery ProjectWaste Heat Recovery Project
Waste Heat Recovery ProjectSUMIT JINDAL
 
SOLAR COOLING
SOLAR COOLINGSOLAR COOLING
SOLAR COOLINGVitess
 
Building Energy 2014: PV and Heat Pumps by Fortunat Mueller
Building Energy 2014: PV and Heat Pumps by Fortunat MuellerBuilding Energy 2014: PV and Heat Pumps by Fortunat Mueller
Building Energy 2014: PV and Heat Pumps by Fortunat Muellerfortunatmueller
 
To Improve Thermal Efficiency of 27mw Coal Fired Power Plant
To Improve Thermal Efficiency of 27mw Coal Fired Power PlantTo Improve Thermal Efficiency of 27mw Coal Fired Power Plant
To Improve Thermal Efficiency of 27mw Coal Fired Power PlantIJMER
 
Waste Heat Recovery Devices by Varun Pratap Singh
Waste Heat Recovery Devices by Varun Pratap SinghWaste Heat Recovery Devices by Varun Pratap Singh
Waste Heat Recovery Devices by Varun Pratap SinghVarun Pratap Singh
 
Boilers Classifications and Cost per kWh
Boilers Classifications and Cost per kWh Boilers Classifications and Cost per kWh
Boilers Classifications and Cost per kWh salehkhan
 

Tendances (20)

Heat pumps
Heat pumpsHeat pumps
Heat pumps
 
Heat Pump
Heat PumpHeat Pump
Heat Pump
 
Introduction to heat pumps
Introduction to heat pumpsIntroduction to heat pumps
Introduction to heat pumps
 
Presentation on Heat pump and its Function.
Presentation on Heat pump and its Function.Presentation on Heat pump and its Function.
Presentation on Heat pump and its Function.
 
Air source heat pumps
Air source heat pumpsAir source heat pumps
Air source heat pumps
 
Heat Engine
Heat EngineHeat Engine
Heat Engine
 
Unit 4 cogeneration
Unit 4 cogenerationUnit 4 cogeneration
Unit 4 cogeneration
 
Heat engines for 10th standard new syllabus
Heat engines  for 10th standard new syllabusHeat engines  for 10th standard new syllabus
Heat engines for 10th standard new syllabus
 
Cooling applications of solar system ppt
Cooling applications of solar system pptCooling applications of solar system ppt
Cooling applications of solar system ppt
 
Water Efficiency in Thermal power Plant
Water Efficiency in Thermal power PlantWater Efficiency in Thermal power Plant
Water Efficiency in Thermal power Plant
 
Thermal Efficiency of Buildings - Stefan Huber - Paul Heat Recovery Scotland
Thermal Efficiency of Buildings - Stefan Huber - Paul Heat Recovery ScotlandThermal Efficiency of Buildings - Stefan Huber - Paul Heat Recovery Scotland
Thermal Efficiency of Buildings - Stefan Huber - Paul Heat Recovery Scotland
 
Air Source Heat Pumps - Thomas Dickson - Glow Worm
Air Source Heat Pumps - Thomas Dickson - Glow WormAir Source Heat Pumps - Thomas Dickson - Glow Worm
Air Source Heat Pumps - Thomas Dickson - Glow Worm
 
Feedwater heater control: Level
Feedwater heater control: LevelFeedwater heater control: Level
Feedwater heater control: Level
 
Waste Heat Recovery Project
Waste Heat Recovery ProjectWaste Heat Recovery Project
Waste Heat Recovery Project
 
SOLAR COOLING
SOLAR COOLINGSOLAR COOLING
SOLAR COOLING
 
Building Energy 2014: PV and Heat Pumps by Fortunat Mueller
Building Energy 2014: PV and Heat Pumps by Fortunat MuellerBuilding Energy 2014: PV and Heat Pumps by Fortunat Mueller
Building Energy 2014: PV and Heat Pumps by Fortunat Mueller
 
To Improve Thermal Efficiency of 27mw Coal Fired Power Plant
To Improve Thermal Efficiency of 27mw Coal Fired Power PlantTo Improve Thermal Efficiency of 27mw Coal Fired Power Plant
To Improve Thermal Efficiency of 27mw Coal Fired Power Plant
 
Waste Heat Recovery Devices by Varun Pratap Singh
Waste Heat Recovery Devices by Varun Pratap SinghWaste Heat Recovery Devices by Varun Pratap Singh
Waste Heat Recovery Devices by Varun Pratap Singh
 
Inci Gen
Inci GenInci Gen
Inci Gen
 
Boilers Classifications and Cost per kWh
Boilers Classifications and Cost per kWh Boilers Classifications and Cost per kWh
Boilers Classifications and Cost per kWh
 

Similaire à ENER-G Heat pump technology CPD

Heat Pumps.pptx
Heat Pumps.pptxHeat Pumps.pptx
Heat Pumps.pptxWilade
 
Thermal power plant
Thermal power plantThermal power plant
Thermal power plantRabi Kumar
 
Water to Water Heat Recovery
Water to Water Heat RecoveryWater to Water Heat Recovery
Water to Water Heat RecoveryIllinois ASHRAE
 
Experience of air to water heat pumps
Experience of air to water heat pumpsExperience of air to water heat pumps
Experience of air to water heat pumpsNick Grant
 
Simple Vapor Absorption Refrigeration System
Simple Vapor Absorption Refrigeration SystemSimple Vapor Absorption Refrigeration System
Simple Vapor Absorption Refrigeration SystemIan Louise Celestino
 
EDI SY SEM 2 - Mid Sem Review ppt.pptx
EDI SY SEM 2 - Mid Sem Review ppt.pptxEDI SY SEM 2 - Mid Sem Review ppt.pptx
EDI SY SEM 2 - Mid Sem Review ppt.pptxKhaireSushom
 
Academic project report
Academic project reportAcademic project report
Academic project reportravi wankhede
 
Supercritical steam generators
Supercritical steam generatorsSupercritical steam generators
Supercritical steam generatorsAshutosh Katti
 
Thermal power plant Khedr, Hisar, Haryana
Thermal power plant Khedr, Hisar, HaryanaThermal power plant Khedr, Hisar, Haryana
Thermal power plant Khedr, Hisar, HaryanaEesha Gupta
 
Experimental Investigation of a Household Refrigerator Using Evaporative-Cool...
Experimental Investigation of a Household Refrigerator Using Evaporative-Cool...Experimental Investigation of a Household Refrigerator Using Evaporative-Cool...
Experimental Investigation of a Household Refrigerator Using Evaporative-Cool...inventy
 
Kota super thermal power plant,kstps ppt,RTU
Kota super thermal power plant,kstps ppt,RTUKota super thermal power plant,kstps ppt,RTU
Kota super thermal power plant,kstps ppt,RTUManohar Nagar
 
Thermal Energy Generation in Sri Lanka
Thermal Energy Generation in Sri LankaThermal Energy Generation in Sri Lanka
Thermal Energy Generation in Sri LankaHeshan Rajapaksha
 
Cogenration plant, where generated steam is utilized to generate power as wel...
Cogenration plant, where generated steam is utilized to generate power as wel...Cogenration plant, where generated steam is utilized to generate power as wel...
Cogenration plant, where generated steam is utilized to generate power as wel...SujeetSalunkhe
 
Thermal Power Plant - Full Detail About Plant and Parts (Also Contain Animate...
Thermal Power Plant - Full Detail About Plant and Parts (Also Contain Animate...Thermal Power Plant - Full Detail About Plant and Parts (Also Contain Animate...
Thermal Power Plant - Full Detail About Plant and Parts (Also Contain Animate...Shubham Thakur
 

Similaire à ENER-G Heat pump technology CPD (20)

Chapter 10 lecture
Chapter 10 lectureChapter 10 lecture
Chapter 10 lecture
 
Heat Pumps.pptx
Heat Pumps.pptxHeat Pumps.pptx
Heat Pumps.pptx
 
Thermal power plant
Thermal power plantThermal power plant
Thermal power plant
 
Water to Water Heat Recovery
Water to Water Heat RecoveryWater to Water Heat Recovery
Water to Water Heat Recovery
 
Pptx
PptxPptx
Pptx
 
Lecture 7-9
Lecture 7-9Lecture 7-9
Lecture 7-9
 
Experience of air to water heat pumps
Experience of air to water heat pumpsExperience of air to water heat pumps
Experience of air to water heat pumps
 
Simple Vapor Absorption Refrigeration System
Simple Vapor Absorption Refrigeration SystemSimple Vapor Absorption Refrigeration System
Simple Vapor Absorption Refrigeration System
 
report final
report finalreport final
report final
 
EDI SY SEM 2 - Mid Sem Review ppt.pptx
EDI SY SEM 2 - Mid Sem Review ppt.pptxEDI SY SEM 2 - Mid Sem Review ppt.pptx
EDI SY SEM 2 - Mid Sem Review ppt.pptx
 
Academic project report
Academic project reportAcademic project report
Academic project report
 
Supercritical steam generators
Supercritical steam generatorsSupercritical steam generators
Supercritical steam generators
 
Thermal power plant Khedr, Hisar, Haryana
Thermal power plant Khedr, Hisar, HaryanaThermal power plant Khedr, Hisar, Haryana
Thermal power plant Khedr, Hisar, Haryana
 
Vapor absorption system
Vapor absorption system Vapor absorption system
Vapor absorption system
 
Experimental Investigation of a Household Refrigerator Using Evaporative-Cool...
Experimental Investigation of a Household Refrigerator Using Evaporative-Cool...Experimental Investigation of a Household Refrigerator Using Evaporative-Cool...
Experimental Investigation of a Household Refrigerator Using Evaporative-Cool...
 
Kota super thermal power plant,kstps ppt,RTU
Kota super thermal power plant,kstps ppt,RTUKota super thermal power plant,kstps ppt,RTU
Kota super thermal power plant,kstps ppt,RTU
 
Thermal Energy Generation in Sri Lanka
Thermal Energy Generation in Sri LankaThermal Energy Generation in Sri Lanka
Thermal Energy Generation in Sri Lanka
 
Power cycles
Power cyclesPower cycles
Power cycles
 
Cogenration plant, where generated steam is utilized to generate power as wel...
Cogenration plant, where generated steam is utilized to generate power as wel...Cogenration plant, where generated steam is utilized to generate power as wel...
Cogenration plant, where generated steam is utilized to generate power as wel...
 
Thermal Power Plant - Full Detail About Plant and Parts (Also Contain Animate...
Thermal Power Plant - Full Detail About Plant and Parts (Also Contain Animate...Thermal Power Plant - Full Detail About Plant and Parts (Also Contain Animate...
Thermal Power Plant - Full Detail About Plant and Parts (Also Contain Animate...
 

Dernier

Sports & Fitness Value Added Course FY..
Sports & Fitness Value Added Course FY..Sports & Fitness Value Added Course FY..
Sports & Fitness Value Added Course FY..Disha Kariya
 
SOCIAL AND HISTORICAL CONTEXT - LFTVD.pptx
SOCIAL AND HISTORICAL CONTEXT - LFTVD.pptxSOCIAL AND HISTORICAL CONTEXT - LFTVD.pptx
SOCIAL AND HISTORICAL CONTEXT - LFTVD.pptxiammrhaywood
 
The basics of sentences session 2pptx copy.pptx
The basics of sentences session 2pptx copy.pptxThe basics of sentences session 2pptx copy.pptx
The basics of sentences session 2pptx copy.pptxheathfieldcps1
 
Disha NEET Physics Guide for classes 11 and 12.pdf
Disha NEET Physics Guide for classes 11 and 12.pdfDisha NEET Physics Guide for classes 11 and 12.pdf
Disha NEET Physics Guide for classes 11 and 12.pdfchloefrazer622
 
9548086042 for call girls in Indira Nagar with room service
9548086042  for call girls in Indira Nagar  with room service9548086042  for call girls in Indira Nagar  with room service
9548086042 for call girls in Indira Nagar with room servicediscovermytutordmt
 
Beyond the EU: DORA and NIS 2 Directive's Global Impact
Beyond the EU: DORA and NIS 2 Directive's Global ImpactBeyond the EU: DORA and NIS 2 Directive's Global Impact
Beyond the EU: DORA and NIS 2 Directive's Global ImpactPECB
 
Class 11th Physics NEET formula sheet pdf
Class 11th Physics NEET formula sheet pdfClass 11th Physics NEET formula sheet pdf
Class 11th Physics NEET formula sheet pdfAyushMahapatra5
 
Grant Readiness 101 TechSoup and Remy Consulting
Grant Readiness 101 TechSoup and Remy ConsultingGrant Readiness 101 TechSoup and Remy Consulting
Grant Readiness 101 TechSoup and Remy ConsultingTechSoup
 
General AI for Medical Educators April 2024
General AI for Medical Educators April 2024General AI for Medical Educators April 2024
General AI for Medical Educators April 2024Janet Corral
 
Paris 2024 Olympic Geographies - an activity
Paris 2024 Olympic Geographies - an activityParis 2024 Olympic Geographies - an activity
Paris 2024 Olympic Geographies - an activityGeoBlogs
 
Advanced Views - Calendar View in Odoo 17
Advanced Views - Calendar View in Odoo 17Advanced Views - Calendar View in Odoo 17
Advanced Views - Calendar View in Odoo 17Celine George
 
Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...
Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...
Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...Krashi Coaching
 
BAG TECHNIQUE Bag technique-a tool making use of public health bag through wh...
BAG TECHNIQUE Bag technique-a tool making use of public health bag through wh...BAG TECHNIQUE Bag technique-a tool making use of public health bag through wh...
BAG TECHNIQUE Bag technique-a tool making use of public health bag through wh...Sapna Thakur
 
microwave assisted reaction. General introduction
microwave assisted reaction. General introductionmicrowave assisted reaction. General introduction
microwave assisted reaction. General introductionMaksud Ahmed
 
Q4-W6-Restating Informational Text Grade 3
Q4-W6-Restating Informational Text Grade 3Q4-W6-Restating Informational Text Grade 3
Q4-W6-Restating Informational Text Grade 3JemimahLaneBuaron
 
Unit-IV- Pharma. Marketing Channels.pptx
Unit-IV- Pharma. Marketing Channels.pptxUnit-IV- Pharma. Marketing Channels.pptx
Unit-IV- Pharma. Marketing Channels.pptxVishalSingh1417
 
Nutritional Needs Presentation - HLTH 104
Nutritional Needs Presentation - HLTH 104Nutritional Needs Presentation - HLTH 104
Nutritional Needs Presentation - HLTH 104misteraugie
 
IGNOU MSCCFT and PGDCFT Exam Question Pattern: MCFT003 Counselling and Family...
IGNOU MSCCFT and PGDCFT Exam Question Pattern: MCFT003 Counselling and Family...IGNOU MSCCFT and PGDCFT Exam Question Pattern: MCFT003 Counselling and Family...
IGNOU MSCCFT and PGDCFT Exam Question Pattern: MCFT003 Counselling and Family...PsychoTech Services
 

Dernier (20)

Sports & Fitness Value Added Course FY..
Sports & Fitness Value Added Course FY..Sports & Fitness Value Added Course FY..
Sports & Fitness Value Added Course FY..
 
SOCIAL AND HISTORICAL CONTEXT - LFTVD.pptx
SOCIAL AND HISTORICAL CONTEXT - LFTVD.pptxSOCIAL AND HISTORICAL CONTEXT - LFTVD.pptx
SOCIAL AND HISTORICAL CONTEXT - LFTVD.pptx
 
INDIA QUIZ 2024 RLAC DELHI UNIVERSITY.pptx
INDIA QUIZ 2024 RLAC DELHI UNIVERSITY.pptxINDIA QUIZ 2024 RLAC DELHI UNIVERSITY.pptx
INDIA QUIZ 2024 RLAC DELHI UNIVERSITY.pptx
 
The basics of sentences session 2pptx copy.pptx
The basics of sentences session 2pptx copy.pptxThe basics of sentences session 2pptx copy.pptx
The basics of sentences session 2pptx copy.pptx
 
Disha NEET Physics Guide for classes 11 and 12.pdf
Disha NEET Physics Guide for classes 11 and 12.pdfDisha NEET Physics Guide for classes 11 and 12.pdf
Disha NEET Physics Guide for classes 11 and 12.pdf
 
9548086042 for call girls in Indira Nagar with room service
9548086042  for call girls in Indira Nagar  with room service9548086042  for call girls in Indira Nagar  with room service
9548086042 for call girls in Indira Nagar with room service
 
Beyond the EU: DORA and NIS 2 Directive's Global Impact
Beyond the EU: DORA and NIS 2 Directive's Global ImpactBeyond the EU: DORA and NIS 2 Directive's Global Impact
Beyond the EU: DORA and NIS 2 Directive's Global Impact
 
Mattingly "AI & Prompt Design: The Basics of Prompt Design"
Mattingly "AI & Prompt Design: The Basics of Prompt Design"Mattingly "AI & Prompt Design: The Basics of Prompt Design"
Mattingly "AI & Prompt Design: The Basics of Prompt Design"
 
Class 11th Physics NEET formula sheet pdf
Class 11th Physics NEET formula sheet pdfClass 11th Physics NEET formula sheet pdf
Class 11th Physics NEET formula sheet pdf
 
Grant Readiness 101 TechSoup and Remy Consulting
Grant Readiness 101 TechSoup and Remy ConsultingGrant Readiness 101 TechSoup and Remy Consulting
Grant Readiness 101 TechSoup and Remy Consulting
 
General AI for Medical Educators April 2024
General AI for Medical Educators April 2024General AI for Medical Educators April 2024
General AI for Medical Educators April 2024
 
Paris 2024 Olympic Geographies - an activity
Paris 2024 Olympic Geographies - an activityParis 2024 Olympic Geographies - an activity
Paris 2024 Olympic Geographies - an activity
 
Advanced Views - Calendar View in Odoo 17
Advanced Views - Calendar View in Odoo 17Advanced Views - Calendar View in Odoo 17
Advanced Views - Calendar View in Odoo 17
 
Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...
Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...
Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...
 
BAG TECHNIQUE Bag technique-a tool making use of public health bag through wh...
BAG TECHNIQUE Bag technique-a tool making use of public health bag through wh...BAG TECHNIQUE Bag technique-a tool making use of public health bag through wh...
BAG TECHNIQUE Bag technique-a tool making use of public health bag through wh...
 
microwave assisted reaction. General introduction
microwave assisted reaction. General introductionmicrowave assisted reaction. General introduction
microwave assisted reaction. General introduction
 
Q4-W6-Restating Informational Text Grade 3
Q4-W6-Restating Informational Text Grade 3Q4-W6-Restating Informational Text Grade 3
Q4-W6-Restating Informational Text Grade 3
 
Unit-IV- Pharma. Marketing Channels.pptx
Unit-IV- Pharma. Marketing Channels.pptxUnit-IV- Pharma. Marketing Channels.pptx
Unit-IV- Pharma. Marketing Channels.pptx
 
Nutritional Needs Presentation - HLTH 104
Nutritional Needs Presentation - HLTH 104Nutritional Needs Presentation - HLTH 104
Nutritional Needs Presentation - HLTH 104
 
IGNOU MSCCFT and PGDCFT Exam Question Pattern: MCFT003 Counselling and Family...
IGNOU MSCCFT and PGDCFT Exam Question Pattern: MCFT003 Counselling and Family...IGNOU MSCCFT and PGDCFT Exam Question Pattern: MCFT003 Counselling and Family...
IGNOU MSCCFT and PGDCFT Exam Question Pattern: MCFT003 Counselling and Family...
 

ENER-G Heat pump technology CPD

  • 1. CPD Ground Source Heat Pumps Jason Cox – National Sales Manager
  • 2. CPD ENER-G Group Overview
  • 5. Heat Pumps  Design  Supply  Install  Commission  Maintenance
  • 7. Standard Rating Conditions GSHP – Brine 0C & Water @ 35/30C ASHP – Air @ 7C & Water @ 35/30C EN14511
  • 8. ASHP Performance Curves Heat Output kW Entering Water Temperature 35°C 50 °C
  • 9. ASHP Performance Curves C.O.P. Entering Water Temperature 35 °C 50 °C
  • 10. Standard Rating Conditions GSHP – Brine 0C & Water @ 35/30C ASHP – Air @ 7C & Water @ 35/30C EN14511
  • 11. GSHP Performance Curves Heat Output kW Entering Water Temperature 35 °C 50 °C
  • 12. GSHP Performance Curves C.O.P. Entering Water Temperature 35 °C 50 °C
  • 13. Ground Source Applications Collector Options •Borehole Installation •Slinky / Horizontal Installation •Lake / Pond Loops •Energy Pile Installations
  • 16. Ground Loop Design Design Data •Peak loads •Load profile •Geology •Available space
  • 17. Assumptions Output 99kW Natural gas 3.1pkWh Electricity 11.46p kWh Running hours 1250 Electricity *0.524g/kWh Natural gas *0.183g/kWh Full load hours x Output (kW) = kWh divided by efficiency = Input Input x Cost of energy = Annual running cost *http://www.bre.co.uk/filelibrary/SAP/2009/SAP-2009_9-90.pdf
  • 18. Ground Source Heat Pumps System Capital Cost (£) Annual Running Cost (£) Carbon Output GSHP 98,000 3,545 16,211 (RHI £5,375) 1250 kWh x 99kW = 123,750kWh per annum divided by 4 C.O.P = 30,938kWh 30,938kWh x 11.46ppkWh = £3,545 Annual Running Cost RHI @ 4.3pkWh for installation less than 99kW
  • 19. Comparison Table (99kW) System Efficiency Capital Cost (£) Annual Running Cost Carbon Output (COP) (£) Boiler 0.9 15,000 4,262 25,162 ASHP *2.2 60,000 6,446 29,475 GSHP 4.0 98,000 3,545 16,211 (RHI £5,375) *http://www.energysavingtrust.org.uk/Media/node_1422/Getting- warmer-a-field-trial-of-heat-pumps-PDF
  • 20. Longfield Academy case study New-build high school combines ground source heat pumps and solar thermal technology for renewable heating and cooling The project The construction of a new academy building for 1,150 students combines ground source heat pumps, with solar thermal technology to maximise renewable energy efficiency. The solution ENER-G has installed 35 boreholes and completed work on the plant room, to accommodate four ground source heat pumps with a combined capacity of 200kW. A total of 22 solar thermal panels have been installed, covering 44 square metres of the Academy’s flat roof. The benefits •It is expected to achieve a minimum ‘Very Good’ rating under BREEAM for schools, as a result of using renewable power sources, and extensive use of insulation to secure a thermal performance 15% beyond current standards. •The installed renewable technologies will supply heating and hot water to the academy, together with passive under-floor cooling in the summer months. This is projected to reduce the Academy’s carbon dioxide emissions from its heating system by up to 40%.
  • 21.
  • 22. Malvern Community Hospital case study New hospital combines ground source heat pumps and a combined heat and power system to generate its own green power. The project The new-build Malvern Community Hospital opened in autumn 2010 and provides both in-patient and out-patient services. ENER-G delivered a solution that was considered the most efficient means of meeting the building’s heating demands combining two low carbon technologies – a ground source heat pump system and a combined heat and power (CHP) unit. This is the first time that these technologies have been used in combination in the UK’s healthcare sector. The solution The ground source system comprises 25 boreholes and two heat pumps with combined capacities of 125kW for both heating and cooling. The ENER-G CHP system is a reciprocating gas engine rated at 33kW of electrical output generating 55kW of useful thermal output for the building and the ground loop for the heat pump. The benefits • The hospital has achieved BREEAM rating ‘Excellent’ and is projected to save on its energy bills and reduce its carbon emissions by 15 tonnes per annum. • A low maintenance option, with the ground source system having a lifetime in excess of 50 years, and the heat pumps lasting up to 25 years. • With the presence of a CHP system at the same site the electricity generated by the CHP unit can be utilised to power the heat pump
  • 23.
  • 24. Summary  Feasibility  Project Management  In-house drilling rigs & teams  In-house heat pump install team  Single point responsibility
  • 26. CPD Gas Absorption Heat Pumps Mark Wilson – National Product Manager
  • 27. Contents Gas Absorption Heat Pumps - Absorption Technology - Different types of GAHP - Benefits - Integration
  • 28. Gas Absorption Heat Pumps Absorption Technology Different types of GAHP Benefits Integration
  • 30. Principle of compression Principle of Compression Heat Pump heat pump
  • 31. Principle of gas absorption heat pump Expansion valve Low temperature gas Hot gas Heat pump USEFUL EFFECT Heating return Very cold Cold liquid liquid Expansion valve
  • 32. How does a GAHP work? 1. Gas burner heats ammonia and water solution. 2. Ammonia gas enters condenser, condenses and releases heat. 3. High pressure ammonia liquid converted into low pressure ammonia liquid. 4. Ammonia liquid evaporates and draws in heat. 5. Ammonia gas absorbs into ammonia water solution. 6. Solution pump powers process.
  • 33. How does a GAHP work? 1. Generator Within the generator, the low Nox gas-fired burner heats the ammonia/water Expansion valve solution via a heat exchanger, increasing the 6 temperature and pressure. 1 The strong ammonia vapour travels to the condenser (2) whilst the Low temperature 5 weak ammonia solution is circulated to the Absorber gas 7 (5) Hot gas Heat pump 4 2 Heating return Very cold Cold liquid liquid Expansion valve 3
  • 34. How does a GAHP work? 2. Condenser The high temperature, high pressure ammonia vapour releases its heat Expansion valve into the heating system in the condenser. The 6 vapour becomes a liquid 1 and travels to the expansion valve (3) on its way to the Low temperature 5 evaporator (4) gas 7 Heat pump Hot gas 4 2 Heating return Very cold Cold liquid liquid Expansion valve 3
  • 35. How does a GAHP work? 3. Expansion valve The high pressure ammonia passes through the expansion valve where the Expansion valve pressure falls. The 6 ammonia now has a reduced boiling point 1 and the liquid changes back to a vapour. This vapour passes on to Low temperature 5 the Evaporator (4) gas 7 Heat pump Hot gas 4 2 Heating return Very cold Cold liquid liquid Expansion valve 3
  • 36. How does a GAHP work? 4. Evaporator A fan draws ambient air through the evaporator. The ambient air captured Expansion valve by the ammonia vapour, contains a high amount of 6 free, renewable energy. 1 The now heated, low pressure vapour passes on to the Absorber (5) Low temperature 5 gas 7 Heat pump Hot gas 4 2 Heating return Very cold Cold liquid liquid Expansion valve 3
  • 37. How does a GAHP work? 5. Absorber In the absorber the weak ammonia solution recombines with the heated Expansion valve vapour, changing its state 6 into a liquid. This releases further heat to the heating 1 system. The now recombined ammonia solution is pumped (7) back Low temperature 5 to the generator. gas 7 Heat pump Hot gas 4 2 Heating return Very cold Cold liquid liquid Expansion valve 3
  • 38. How does a GAHP work? 6. Second expansion valve This second valve controls the flow of weak ammonia between the Generator (1) and Expansion valve the Absorber (5) 6 1 Low temperature 5 gas 7 Heat pump Hot gas 4 2 Heating return Very cold Cold liquid liquid Expansion valve 3
  • 39. How does a GAHP work? 7. Heat pump The pump moves the ammonia Expansion valve solution from the Absorber (5) back to the Generator (1) where 6 the process starts again. 1 Low temperature 5 gas 7 Heat pump Hot gas 4 2 Heating return Very cold Cold liquid liquid Expansion valve 3
  • 40. The Technology • Water-ammonia sealed circuit : no top-up, no drain, extremely simple maintenance; • Natural refrigerant : no CFC, HCFC, HFC; • One single moving component (solution pump) : very high reliability; • Exhaust flue gas water vapour condensation: reduced energy losses in the exhaust gas; • Very low electrical consumption 1/10 of an equivalent electrical heat pump.
  • 41. Gas Absorption Heat Pumps Absorption Technology Different types of GAHP Benefits Integration
  • 42. GAHP GS: Ground source applications • Nominal efficiency 170% by means of heat recovery from renewable source (ground) • LT or HT versions (55 °C / 65 °C) • Domestic Hot Water production up to 70°C • Indoor installation • Reduction in borehole quantity by up to 60% • Cheaper civils costs against electric ground source
  • 43. Ground Source applications Collector Options •Borehole Installation •Slinky / Horizontal Installation •Lake / Pond Loops •Energy Pile Installations
  • 44. The Open University The UK’s largest closed-loop ground source, gas absorption heat pump project, providing low carbon heat and reducing energy consumption by up to 50% The project Building 12 is a 2,000m2 new-build development that forms part of the Walton Hall Campus. The new building is targeting a BREEAM ‘Outstanding’ rating. It incorporates natural ventilation, night time cooling, solar chimneys, automatic lighting controls, a green roof, solar water heating and photovoltaic panels. The solution ENER-G drilled 13 boreholes to a depth of more than 100 metres to install a ground loop system that feeds four gas absorption heat pumps, with a combined capacity of 140kW heat output. This system supplies the building’s heating requirements and will achieve carbon dioxide savings of approximately 45%, in comparison to a system heater via a condensing boiler The benefits •Energy consumption reductions of up to 50% •Exemption from the climate change levy •Cost savings relating to the Carbon Reduction Commitment (CRC) energy efficiency scheme and improved Building Energy Certificate ratings (EPC and DEC) •Reduced regulatory costs as a result of low emissions, enabling points for BREEAM assessment and compliance with Part L2A and Part L2B of the building regulations
  • 45. GAHP A: Air source applications •Nominal efficiency 165% by means of heat recovery from renewable source (air) • LT or HT versions (55 °C / 65 °C) • Domestic Hot Water production up to 70°C • Outdoor installation to free up plant room space • Minimal drop off of output and efficiency in low ambient temperatures against electric heat pumps
  • 46. GAHP A: Air source
  • 47. GAHP AR: Alternate heating and cooling • Heating or cooling from the same unit • 2-1 ratio of heating to cooling • Efficiency in excess of 144% • Outdoor installation to free up plant room space
  • 48. GAHP ACF & WS: Simultaneous production of hot/cold water • Heating to cooling ratio 2.5 to 1 • Efficiency in excess of 227% • Indoor installation • Very low electrical consumption
  • 49. Gas Absorption Heat Pumps Absorption Technology Different types of GAHP Benefits Integration
  • 50. Direct use of energy CO₂ savings h t t p : / / w w w
  • 51. Direct use of energy CO₂ savings • Gas produces 0.1836 kgCO₂ / kWh • Electricity from the grid produces 0.5246 kgCO₂ /kWh http://www.carbontrust.com/media/18223/ctl153_conversion_factors.pdf*
  • 52. Direct use of energy CO₂ savings • Utilized electricity from the grid produces 3* times the CO₂ of natural gas • Electric HP Seasonal COP 2.25** • GAHP Seasonal GUE 1.4 Therefore a gas absorption heat pump produces 46 % less CO₂/kWh than a air source heat pump. • If we use an example of 60 hours per week 6 months of the year….. http://www.carbontrust.com/media/18223/ctl153_conversion_factors.pdf* **http://www.energysavingtrust.org.uk/Media/node_1422/Getting-warmer-a-field-trial-of-heat-pumps-PDF
  • 53. Direct use of energy CO₂ savings Example: GAHP-A Air Source Heat Pump (36.2kW) (Running 60 hours per week / 6 months per year) Robur Gas Heat Pump = 1560 (hrs) x 25.7 (kW gas) x 0.1836 (kgCO2/kWh gas) = 7.3 Tonnes of CO2 per year Electric Air Source Heat Pump (seasonal COP of 2.25) = 1560 (hrs) x 16 (kW electricity) x 0.5246 (kgCO2/kWh elec) = 13 Tonnes of CO2 per year To put that into perspective……..
  • 54. 1 year’s CO₂ difference would fill the Olympic swimming pool at the 2012 games 12 times!
  • 55. Also take into account… No use/leakage of F-Gases A typical 37kW air to air electric heat pump contains about 14kg of R410a gas. If the leakage from the system is for example 10% of the charge per year *(estimates put the Global Annual leakage rates of refrigerants at 27.8% !!) This is equivalent to 2.5 Tonnes of CO2 per year Another 5 swimming pools worth! * Institute of refrigeration report 2008 (New high pressure Low GWP refrigerant blends)
  • 56. Annual running costs Example : GAHP-A Air Source Heat Pump (36.2kW) (Running 60 hours per week / 6 months per year) Robur Gas Heat Pump Condensing Boiler Electric Air Source (seasonal efficiency of (seasonal efficiency of Heat Pump (seasonal 140%) 90%) COP of 2.25) = [1560(hrs) x 0.75(LF) x = [1560(hrs) x 0.75(LF) x = [1560(hrs) x 0.75(LF) x 36.2(kW) x 3.1(p/kWh)] / 36.2(kW) x 3.1(p/kWh)] / 36.2(kW) x 11.46(p/kWh)] / 1.40 0.90 2.25 = £ 938 per year = £ 1,459 per year = £ 2,157 per year Saving £500 over a condensing boiler or £1200 over an Electric Heat Pump Note: gas and electricity prices from SAP 2009 http://www.bre.co.uk/filelibrary/SAP/2009/SAP-2009_9-90.pdf
  • 57. Annual running costs There are significant running cost savings to be achieved by using a Gas Absorption Heat Pump.
  • 58. GSHP GAHP Covering Base Load Covering Base Load 140 130 120 Heating Load [kW] 110 100 90 Boiler 80 70 60 50 Boiler 40 30 20 GAHP 10 0 October November December January Febtuary March April Month
  • 59. Gas Absorption Heat Pumps Absorption Technology Different types of GAHP Benefits Integration
  • 60. Integration of other heat sources

Notes de l'éditeur

  1. Good Morning/Afternoon, thankyou for inviting me here to give this CIBSE approved CPD presentation on Gas absorption Heat pumps. Before we start to enable me to generate certificates for you all please can you fill in your name and job title on this sheet which I will use to generate the certificates. Ok, As you can see my name is Mark and I work for ENER-G
  2. Navigation Bar – In Corporate Presentation Only – Links to separate solution presentations
  3. Explain COP
  4. Advertising and PR – all about brand awareness First time the business has done any advertising in industry publications PR: Riskmanager, promoting Quick guides, renewal reminder services, wider energy management offer – CMR and solutions services.
  5. GSHP & CHP Combined
  6. Advertising and PR – all about brand awareness First time the business has done any advertising in industry publications PR: Riskmanager, promoting Quick guides, renewal reminder services, wider energy management offer – CMR and solutions services.
  7. GSHP & CHP Combined
  8. Good Morning/Afternoon, thankyou for inviting me here to give this CIBSE approved CPD presentation on Gas absorption Heat pumps. Before we start to enable me to generate certificates for you all please can you fill in your name and job title on this sheet which I will use to generate the certificates. Ok, As you can see my name is Mark and I work for ENER-G
  9. This CPD presentation will take us through the history of Gas Absorption heat pumps leading to the technology behind gas absorption heat pumps and the ABSORPTION cycle to the different types and thier use. Then onto the benefits of using the technology with some comparisons with electric air source heat pumps as regards running costs and CO2 emissions and onto integration with other heat sources.
  10. Of the four technologies being promoted as holding the key to the future of environmentally sustainable buildings - Solar, Biomass, Combined Heat and Power and Heat Pumps - it is the Heat Pump that has been around the longest. Following the successful application of absorption technology to domestic refrigeration in the 1950s and 60s, when over 4 million units were sold, the first commercial gas-fired chiller was produced in the USA by the Arkansas & Louisiana Gas Company (Arkla) in 1968. Between 1968 and 1991, over 300,000 of these chillers were sold. The modern era for gas heat pumps began in earnest in 1991, when the highly respected Italian heating equipment manufacturer Robur acquired the gas chiller business of US manufacturer Electrolux. After moving production to Europe, the process of continuous product development and improvement eventually led in 2004 to the commercial launch of the first gas absorption heat pump.
  11. To explain the differences in the technology we must first look at an electric heat pump cycle. Conventional heat pump technology uses electrical power to drive a compressor powered thermodynamic cycle. The thermodynamic cycle is a closed system comprising of two heat exchangers, one outside of the building to recover heat from the outside air and a second inside the building to heat either inside air or water for circulating around the building. The two heat exchangers are piped together and heat is moved via a working fluid which is pumped (in gaseous form) between the two heat exchangers by the compressor. The working fluid flow is regulated by an expansion device. Typically, for every kW of electricity used to power the heat pump 2 to 3kW of heat are produced. This ratio is called the Coefficient of Performance (COP) and a COP of 2 to 3 is not uncommon for an electric heat pump.
  12. The technology in a GAHP contains significant advantages over electric heat pumps. The sealed circuit should never need to be touched. The use of a natural ammonia/water mixture as the working fluid instead of the HFC refrigerant working fluids used by electric heat pumps gives the gas absorption option another plus in the battle against global warming and acts a useful counter to the Fgas Regulations (Regulation EC 842/2006). As well has having an ozone depletion potential (ODP) of zero, Ammonia has a global warming potential (GWP) of zero with an atmospheric life cycle of less than a week compared with the current generation of HFCs with GWPs of over 2,000 and atmospheric life cycles of 30 years or more. Even the smallest HFC leak from an electric heat pump can undo a large part of the environmental benefits achieved through the operating efficiencies. In contrast, the factory sealed system of the gas heat pump means that the opportunities for refrigerant leakage are much less than those of a conventional electric heat pump and, despite that, should the gas heat pump suffer a catastrophic leak, there will be no detrimental effect to the environment.
  13. This CPD presentation will take us through the history of Gas Absorption heat pumps leading to the technology behind gas absorption heat pumps and the ABSORPTION cycle to the different types and thier use. Then onto the benefits of using the technology with some comparisons with electric air source heat pumps as regards running costs and CO2 emissions and onto integration with other heat sources.
  14. The technology can be used in ground source and because of the basic COP ( which I will come onto later) they require upto 60% less bore holes which obviously greatly reduces civils costs.
  15. Advertising and PR – all about brand awareness First time the business has done any advertising in industry publications PR: Riskmanager, promoting Quick guides, renewal reminder services, wider energy management offer – CMR and solutions services.
  16. The standard air source versions are heating only. Air source versions of GAHP’s are designed outdoor instalation which reduces plantroom/ wall space required.
  17. As you can see there is minimal drop off in output and efficiency when the temperature is colder outside
  18. You can also have an alternate heating and cooling version of the gas heat pump. This isn’t quite as efficient in cooling mode as it is in heating.
  19. Where you require heating and cooling simultaneously you can get considerable added value out of a GAHP as the cooling is effectively free.
  20. This CPD presentation will take us through the history of Gas Absorption heat pumps leading to the technology behind gas absorption heat pumps and the ABSORPTION cycle to the different types and thier use. Then onto the benefits of using the technology with some comparisons with electric air source heat pumps as regards running costs and CO2 emissions and onto integration with other heat sources.
  21. So a saving over 1 year in CO2 of 6.5 tonnes
  22. The 3 comes from a the SAP 2009 report. Table 12 The 2.25 COP comes from an independent field trial report done by The Energy Saving Trust in September 2010. I have put the web address below.
  23. The 3 comes from a the SAP 2009 report. Table 12 The 2.25 COP comes from an independent field trial report done by The Energy Saving Trust in September 2010. I have put the web address below.
  24. So a saving over 1 year in CO2 of 5.7 tonnes
  25. 1 tonne of CO2 is 556.2m3 Olympic swimming pool 50m*25m*2m = 250m3 556.2 * 6.5 + 3615.30 / 250 = 14.46 Would Rebecca Adlington swim through that to get another gold medal?
  26. Estimates attribute 13% of ALL of the world’s Global Warming to refrigerants in the atmosphere. The F-Gas refrigerant used in conventional electric air conditioners and heat pumps is an extremely strong greenhouse gas. For example R410a has a Global Warming Potential (GWP) of 1725 times that of CO2. The Robur heat pump uses the environmentally benign water/ammonia mixture that has an ozone depletion potential (ODP) of zero and a global warming potential (GWP) of zero with an atmospheric life cycle of less than a week. In addition the sealed working fluid circuit means the opportunity for refrigerant leakage is much less than with a conventional heat pump system. 2.6 tonnes = 1446.12 m3 / 250 = 5.78
  27. On to costs of running against a conventional boiler or an electric heat pump. Using a Gas Absorption Heat Pump in this scenario would have saved you approximately £700 against a condensing boiler and £1200 against an electric heat pump. Who would have thought that an electric air source heat pump using utilising renewable energy would cost more to run than a gas boiler!!!
  28. As you can see running the heat pump for as much time as possible gives the best cost savings and the best CO2 savings.
  29. To maximise usage of renewable energy with a gas absorption heat pump endeavour to size so that the base load is covered by the heat pumps so you get maximum run hours out of the units and therefore maximum cost and CO2 savings. In this example the building load is 110kW @ -4 degrees so the heat pump will cover the base load from April through to October and then gas condensing boilers will take up the reminder of the load for the coldest 4 months of the year.
  30. This CPD presentation will take us through the history of Gas Absorption heat pumps leading to the technology behind gas absorption heat pumps and the ABSORPTION cycle to the different types and thier use. Then onto the benefits of using the technology with some comparisons with electric air source heat pumps as regards running costs and CO2 emissions and onto integration with other heat sources.
  31. Due to higher flow temperatures you get from a GAHP they are more versatile and can fully integrate with condensing boilers, you can even get matched boilers to sit on the same skid for outdoor installation. Also because of being able to run at these temperatures then you can use them for DHW as these temperatures will stop legionella formation. With these higher flow temps they can also be used in retrofit situations, in most cases without having to alter the pipe work or heat sources on the secondary side. To maximise renewables they are also suited to combine with solar panels to give DHW year round.