SlideShare une entreprise Scribd logo
1  sur  5
Mr.S.B.Dandawate*, Mrs.S.L.Shaikh / International Journal of Engineering Research and
Applications (IJERA) ISSN: 2248-9622 www.ijera.com
Vol. 3, Issue 3, May-Jun 2013, pp.1383-1387
1383 | P a g e
Analysis of Effect on Transient Stability of Interconnected Power
System by Introduction of HVDC Link.
Mr.S.B.Dandawate*, Mrs.S.L.Shaikh**
*,**(Department of Electrical Engineering, Walchand College of Engineering, Sangli)
ABSTRACT
Modern power employs HVDC links as a
reliable and economical option for long EHVAC
transmission line. The HVDC link in the power
system behaves very differently than
conventional HVAC lines during the disturbances
in the power system. This paper analyses the
effect of HVDC system on the transient stability
of power system. Effect is studied on IEEE 24 bus
reliability test system. A self-sufficient model
developed in MATLAB Simulink has been given
with full details, which can work as a basic
structure for an advanced and detailed study.
Keywords – Transient Stability, HVDC.
I. INTRODUCTION
The improving reliability of supply is one
of the objective to interconnect the generators
located at large distances and the purpose is
achieved by running the synchronous generators in
parallel i.e. in synchronism and with adequate
capacity to meet the load demand [1]. The stability
problem is concerned with the behavior of the
synchronous machines after they have been
perturbed while operating in synchronism. If
perturbation does not involve any net change in
power, the machine should return to the original
state. If unbalance between the supply and load is
created by the change in load, in generation, or in
network conditions, a new operating state is
necessary. In any case all the interconnected
synchronous machines should remain in
synchronism if the system is to be kept stable [2].
Distinction should be made between sudden and
major disturbances, which we shall call large
impacts, and smaller and more normal random
impacts. If one of these large impacts occurs, the
study of system behavior following it is referred to
as the transient stability problem [3]. The system
response to such disturbances involves large
excursions of generator rotor angles, power flows,
bus voltages, and other system variables. The ability
of the system to survive a certain disturbance
depends on its precise operating
condition at the time of the occurrence of
disturbance. A change in the system loading,
generation schedule, network interconnections, or
type of circuit protection may give completely
different results in a stability study for the same
disturbance. Thus the transient stability study is a
very specific one, from which the engineer
concludes that under given system conditions and
for a given impact the synchronous machines will or
will not remain in synchronism [4].
The problem of interest is one where a power
system operating under a steady load condition is
perturbed, causing the readjustment of the voltage
angles of the synchronous machines. Any unbalance
between the generation and load initiates a transient
that causes the rotors of the synchronous machines
to “swing” because net accelerating (or decelerating)
torques are exerted on these rotors. If these net
torques are sufficiently large to cause some of the
rotors to swing far enough so that one or more
machines “slip a pole,” synchronism between the
machines is lost [3].
The transient stability is affected by lots of
components present in power system and its
behavior during the disturbance, like excitation
system of generators, reactive power compensating
devices, circuit breakers and steam valves of turbine.
In this paper the effect of adding the HVDC line in
the power system has been studied. The HVDC line
shows very different behavior under transients than
the HVAC lines as the power flow in DC lines is
independent upon the voltage angles at the both
ends. To study its effect on the transient stability,
24-Bus IEEE Reliability test system has been
simulated in the MATLAB- Simulink environment.
The PMU have been simulated to collect the voltage
angles at the generator terminals and the behavior of
the system is studied from these measurements.
The paper is organized as follows. Section II
details the simulated 24 bus system, Section III gives
the details of PMU and its simulation, Section IV
details HVDC system and its controls. Section V
presents the simulation results, and Section VI
concludes.
II. DESCRIPTION OF THE
BENCHMARK POWER SYSTEM
This section first introduces the models of
the different power system elements of the IEEE
24 bus system that is
Mr.S.B.Dandawate*, Mrs.S.L.Shaikh / International Journal of Engineering Research and
Applications (IJERA) ISSN: 2248-9622 www.ijera.com
Vol. 3, Issue 3, May-Jun 2013, pp.1383-1387
1384 | P a g e
used for the simulations. The fig.1 shows the layout
of it.
Fig. 1:-IEEE Reliability Test system
The system contains 10 plants, one
synchronous condensers and a reactor [5]. They are
interconnected by 230KV network and 138KV
network, both of them are interconnected through
the 5 two winding transformers as shown in fig.1.
The generators inside the plants are assumed to be
coherent generators and considered as a single unit
in the system with capacity equal to addition of
capacities of all units in the plant. The generators are
equipped with AVR’s and PSS. The plants are
considered as the hydro power plants and hence
hydraulic turbine and governor blocks in Simulink
are used to supply mechanical power to it. Fig. 2
below gives the Simulink model of the subsystem
simulated for the plants.
Fig. 2:- Synchronous machine, excitation and
governor subsystem
Following table gives the loading of each generator
–
TABLE 1: - GENERATOR OUTPUTS BEFORE
DISTURBANCE.
Generator
No.
Bus
No.
Real Power
(MW)
Reactive
Power
(MVAr)
1 1 200.02 325.26
2 2 174.98 223.17
3 3 224.96 261.01
4 13 175.22 -196.98
5 15 50.07 -45.35
6 16 50.06 -64.026
7 18 200.17 -31.11
8 21 150.13 -36.033
9 22 100.17 -22.295
10 23 327.86 -91.17
The loads are modeled as a constant impedance load
and hence the power absorbed by them is
proportional to the square of the voltage across
them. System contains a reactor of capacity 100
MVAr at bus 6 and a synchronous condenser of
capacity -200 to 50 MVAr at bus 14.
III. HVDC SYSTEM AND CONTROLLES
HVDC systems are employed in modern
power systems because of numerous economical and
technical advantages over AC transmission when
line length is more. The behavior of the HVDC line
during and after the disturbance is different than the
HVAC line as the power flow of the AC line is
dependent upon the voltage angles at both the ends
of the line while in DC line the power flow
dependent merely upon the AC voltage magnitude at
both ends and can be explained from following
circuit diagram
Fig.3:- Equivalent circuit of HVDC line
The power flow is governed by the equations
(1)
(2)
In the benchmark model one 200KV,
100MW, 100Km single pole CSC based HVDC line
has been added in 230KV network between bus 18
to bus 11. Passive harmonic filters are employed to
absorb the generated harmonics and to supply the
required reactive power for the converter operations
at the rectifier as well as inverter end. Terminal of
the line connected to the bus 18 acts as a rectifier
while connected to bus 11 acts as an inverter. Hence
Mr.S.B.Dandawate*, Mrs.S.L.Shaikh / International Journal of Engineering Research and
Applications (IJERA) ISSN: 2248-9622 www.ijera.com
Vol. 3, Issue 3, May-Jun 2013, pp.1383-1387
1385 | P a g e
the line guides power flow from 230KV network to
138KV network.
Three modes of operation are designed to control the
power injections from the end buses of each HVDC-
link to desired value [6]. Under normal conditions,
the HVDC-links operate in constant power mode
when the rectifier operates in constant current
control and the inverter operates in constant
extinction angle control. During disturbances, when
α reaches extreme values, the mode of operation
changes. The control modes can be written as
follows.
• Mode 1: Constant power/current control at the
rectifier and constant extinction angle at the inverter.
• Mode 2: Minimum firing angle control at the
rectifier and constant power/current control at the
inverter.
• Mode 3: Minimum firing angle control at the
rectifier, and constant extinction control at the
inverter. This is the transition mode between Mode 1
and Mode 2.
HVDC link cannot be started abruptly as it may give
a shock to existing system. The link is programmed
to start and reach a steady state. Then steps are
applied on the reference current of the rectifier and
on the inverter reference voltage in order to execute
the purpose. The converters are deblocked and
started by ramping the rectifier and inverter
reference current. At t = 0.02 s, the reference current
is ramped to reach the minimum value of 0.1 pu in
0.3 s (0.033 pu/s). At the end of this first ramp (t =
0.32 s) the DC line is charged at its nominal voltage
and DC voltage reaches steady-state. At t= 0.4 s, the
reference current is ramped from 0.1 pu to 1 pu
(500A) in 0.18 s (3 pu/s). At the end of this starting
sequence (t=0.54 s) , the DC current reaches steady
state.
IV. PMU IMPLEMENTATION IN SYSTEM
A Phasor Measurement Unit (PMU) is a
device that provides synchrophasor and frequency
measurements for one or more three phase AC
voltage or current waveforms. The PMU takes
reading throughout the system where it has been
installed at the same time and hence we have the
phasors from all across the system at same instant so
it can be compared to study system behavior at that
instant. The device uses CT and PT signals as an
input and samples it N times per cycle of the 50 Hz
(in this case) and by applying DFT we get the
fundamental component of the phasor as
(4)
The conventional phasor representation of the phasor
is releted to the fundamental component as
(5)
The devices are simulated in the Simulink and the
MATLAB code has been generated to calculate the
phasors in Simulink model(Fig.5).
Fig.5:-Simulink model to simulate PMU
The devices are connected at each generator
terminal hence we have the synchronized phasors of
all generator terminals. PMU in this case gives 25
phasors per second as per reference (9). Because of
implementation of DFT technique PMU gives output
of phasor angles between -1800
to +1800
instead of
00
to 3600
(7).
V. SIMULATION AND RESULTS
The Simulink model of the IEEE 24 bus
reliability test system is given in Fig. 6. To study the
transient stability of the model, the disturbance has
been created by applying three phase to ground solid
short circuit to various locations in the power
system. The faults are cleared by opening the
respective transmission lines and the critical clearing
time of each fault for a particular operating condition
of the power system has been noted. The same
exercise is carried out for a system with and without
HVDC link. The behavior of the system is studied
by observing rotor angles of the synchronous
machines. When angles of the machine moves away
from each other by 1800
, it is considered that
stability is lost. PMUs installed at the generator
terminals gives us the voltage angles of the
respective generator terminal voltage. The
assumption have been made that the terminal voltage
angle and rotor angles are same, and hence the
PMUs gives us directly the rotor angles of the
generators. As the time frame of interest in transient
stability analysis is usually three to five seconds
after the disturbance [1], this
study is conducted to the first three seconds after the
short-circuit inception.
Mr.S.B.Dandawate*, Mrs.S.L.Shaikh / International Journal of Engineering Research and
Applications (IJERA) ISSN: 2248-9622 www.ijera.com
Vol. 3, Issue 3, May-Jun 2013, pp.1383-1387
1386 | P a g e
Fig. 6:- Simulink Model of IEEE 24 Bus Test
System.
V.1. Illustrative Example
A three phase to ground fault is applied to
bus 16 at t=1s, and the fault is cleared by tripping
lines 16-14, at t=1.5sec and t=1.7sec without HVDC
link. From the generator angles (Fig.7 and Fig.8) we
can see the system loses synchronism for FCT
0.7sec, the generators 6, 7, 8 and 9 speeds up from
rest of the system. Study is repeated after addition of
HCDC link in Model and the generator rotor angle
movement is observed for FCT 0.7sec (Fig. 9).
Results shows that after inception of HVDC link, the
system does not loses synchronism when fault
cleared at 0.7sec.
Fig.7:- Rotor angles for FCT 0.5 sec, without
HVDC.
Fig.8:- Rotor angles for FCT 0.7 sec, without
HVDC.
Fig.9:- Rotor angles for FCT 0.7 sec, with HVDC.
Same study has been conducted for faults at various
locations in the system and the critical clearing time
has been noted down in Table 2.
TABLE 2:- CRITICAL CLEARING TIME (IN
SEC.) FOR DIFFERENT CONTINGENCIES
Fault
Location
Line
Opened
Critical
FCT
Without
HVDC
(Sec.)
Critical
FCT with
HVDC
(Sec.)
Bus 16 16-17 0.7 1.4
Bus 16 16-14 0.68 1.6
Bus 16 16-17 &
16-14
0.6 2.0
Bus 14 14-11 0.932 3.0
Bus 21 15-21 0.32 0.9
VI. CONCLUSION
Transient stability of the interconnected
Mr.S.B.Dandawate*, Mrs.S.L.Shaikh / International Journal of Engineering Research and
Applications (IJERA) ISSN: 2248-9622 www.ijera.com
Vol. 3, Issue 3, May-Jun 2013, pp.1383-1387
1387 | P a g e
power system gets improved with HVDC link
introduced in it. A significant improvement in the
critical fault clearing time is observed when HVDC
link is present. The role of HVDC in transient
stability improvement depends mainly upon the
location and the power rating of HVDC transmission
line. A complete model for transient stability study
of a multi-machine power system was developed
using Simulink. Thus a Simulink model is not only
best suited for an analytical study of a typical power
system network, but it can also incorporate the state-
of-the-art tools for a detailed study and parameter
optimization. A Simulink model is very user
friendly, with tremendous interactive capacity and
unlimited hierarchical model structure.
REFERENCES
[1] W.D Stevensen,J.J.Grainger, Power System
Anlysis (Tata Mcgraw Hill Education, 2003)
[2] P. Kundur,Power System Stability and ControlI
(Tata McGraw Hill Education,2011 )
[3] E.W.Kimbark,Power System Sability Vol
I,II,III, (John Willey , 2003)
[4] P. M. Anderson and A. A. Fouad, Power
System Control and Stability (Iowa State
University Press, Ames, IA, 1977)
[5] A report prepared by the Reliability Test
System Task Force of the Application of
Probability Methods Subcommittee, IEEE
reliability test system, IEEE Transactions on
Power Apparatus and Systems, Vol. PAS-98,
No.6 Nov./Dec. 1979
[6] J. Arrillaga, High Voltage Direct Current
Transmission, (IEE Press Power Engineering
Series, 1883).
[7] A.G.Phadke, J.S. Thorp,Synchronised Phasor
Measurement and Their Applications,(Springer
2008).
[8] A.G.Phadke,J.S.Thorp,M.G.Admaik,A New
Measurement Technique for Tracking Voltage
Phasors,Local System frequency,and Rate of
Change of Frequency,Power Engineering
Review,Vol 2 Issue 5, 1983,0272-1724
[9] IEEE Standard for Synchrophasors for Power
System , IEEE Std 1344-1995(R2001).
BIOGRAPHIES
S. B. Dandawate: Has completed B.E in Electrical
Engineering from University of Pune and doing
M.Tech in Power System in Walchand College of
Engineering, Sangli. His areas of interest are Power
System Stability, Power System Operation and
Control and HVDC Transmission System.
S. L. Shaikh : She is associate Professor in the
faculty of Electrical Engineering in Walchand
College of Engineering Sangli. Her research areas
are power system stability and power quality.

Contenu connexe

Tendances

Flexible Ac Transmission Systems 2Mark Materials and Question Bank
Flexible Ac Transmission Systems 2Mark Materials and Question BankFlexible Ac Transmission Systems 2Mark Materials and Question Bank
Flexible Ac Transmission Systems 2Mark Materials and Question Bank
Santhosh Kumar
 
Ee423 fault analysis_notes
Ee423  fault analysis_notesEe423  fault analysis_notes
Ee423 fault analysis_notes
Acot Benard
 

Tendances (17)

Gi3311211125
Gi3311211125Gi3311211125
Gi3311211125
 
FACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY pptFACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY ppt
 
Comparison of Multi-Machine Transient Stability Limit Using UPFC
Comparison of Multi-Machine Transient Stability Limit Using UPFCComparison of Multi-Machine Transient Stability Limit Using UPFC
Comparison of Multi-Machine Transient Stability Limit Using UPFC
 
Unit1 8
Unit1 8Unit1 8
Unit1 8
 
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMSLOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS
 
Transient stability analysis on a multi machine system in psat
Transient stability analysis on a multi machine system in psatTransient stability analysis on a multi machine system in psat
Transient stability analysis on a multi machine system in psat
 
Controllers For A VSC-HVDC Link Connected To A Weak AC System
Controllers For A VSC-HVDC Link Connected To A Weak AC SystemControllers For A VSC-HVDC Link Connected To A Weak AC System
Controllers For A VSC-HVDC Link Connected To A Weak AC System
 
Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...
Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...
Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...
 
An overview of FACTS devices
An overview of FACTS devicesAn overview of FACTS devices
An overview of FACTS devices
 
Power system stability and control using facts devices
Power system stability and control using facts devicesPower system stability and control using facts devices
Power system stability and control using facts devices
 
Influencing Power Flow and Transient Stability by Static Synchronous Series C...
Influencing Power Flow and Transient Stability by Static Synchronous Series C...Influencing Power Flow and Transient Stability by Static Synchronous Series C...
Influencing Power Flow and Transient Stability by Static Synchronous Series C...
 
Flexible Ac Transmission System
Flexible Ac Transmission SystemFlexible Ac Transmission System
Flexible Ac Transmission System
 
Flexible Ac Transmission Systems 2Mark Materials and Question Bank
Flexible Ac Transmission Systems 2Mark Materials and Question BankFlexible Ac Transmission Systems 2Mark Materials and Question Bank
Flexible Ac Transmission Systems 2Mark Materials and Question Bank
 
Ee423 fault analysis_notes
Ee423  fault analysis_notesEe423  fault analysis_notes
Ee423 fault analysis_notes
 
Stability Modeling Of Storage Devices In FACTS Applications
Stability Modeling Of Storage Devices In FACTS ApplicationsStability Modeling Of Storage Devices In FACTS Applications
Stability Modeling Of Storage Devices In FACTS Applications
 
Study of various FACTS devices for Steady and Dynamic state stability of Powe...
Study of various FACTS devices for Steady and Dynamic state stability of Powe...Study of various FACTS devices for Steady and Dynamic state stability of Powe...
Study of various FACTS devices for Steady and Dynamic state stability of Powe...
 
Unit I - Basic Electrical and Electronics Engineering
Unit I - Basic Electrical and Electronics EngineeringUnit I - Basic Electrical and Electronics Engineering
Unit I - Basic Electrical and Electronics Engineering
 

En vedette

Medidas de velocidad
Medidas de velocidadMedidas de velocidad
Medidas de velocidad
Jhoely Perez
 
Cliodhna Egan Certified Administrator Certificate
Cliodhna Egan Certified Administrator CertificateCliodhna Egan Certified Administrator Certificate
Cliodhna Egan Certified Administrator Certificate
Cliodhna Egan
 
Materi kuliah 10 stack
Materi kuliah 10   stackMateri kuliah 10   stack
Materi kuliah 10 stack
kua
 
3. set item bahagian b
3. set item bahagian b3. set item bahagian b
3. set item bahagian b
hisyam720
 

En vedette (20)

L33054060
L33054060L33054060
L33054060
 
P33077080
P33077080P33077080
P33077080
 
W33123127
W33123127W33123127
W33123127
 
Ic3313881393
Ic3313881393Ic3313881393
Ic3313881393
 
Ik3314371440
Ik3314371440Ik3314371440
Ik3314371440
 
Fe33940945
Fe33940945Fe33940945
Fe33940945
 
Gd3310901094
Gd3310901094Gd3310901094
Gd3310901094
 
Ez33917920
Ez33917920Ez33917920
Ez33917920
 
Cc32497503
Cc32497503Cc32497503
Cc32497503
 
Presentacion skype
Presentacion skypePresentacion skype
Presentacion skype
 
Actitud
ActitudActitud
Actitud
 
Exam.
Exam.Exam.
Exam.
 
Medidas de velocidad
Medidas de velocidadMedidas de velocidad
Medidas de velocidad
 
Os demônios da outra dimensão
Os demônios da outra dimensãoOs demônios da outra dimensão
Os demônios da outra dimensão
 
Cliodhna Egan Certified Administrator Certificate
Cliodhna Egan Certified Administrator CertificateCliodhna Egan Certified Administrator Certificate
Cliodhna Egan Certified Administrator Certificate
 
Grupo 3
Grupo 3Grupo 3
Grupo 3
 
Google docs
Google docsGoogle docs
Google docs
 
Materi kuliah 10 stack
Materi kuliah 10   stackMateri kuliah 10   stack
Materi kuliah 10 stack
 
Lap. penyumbang dana kampanye
Lap. penyumbang dana kampanyeLap. penyumbang dana kampanye
Lap. penyumbang dana kampanye
 
3. set item bahagian b
3. set item bahagian b3. set item bahagian b
3. set item bahagian b
 

Similaire à Ib3313831387

POWER QUALITY ISSUE WITH GRID CONNECTED WIND ENERGY SYSTRM
POWER QUALITY ISSUE WITH GRID CONNECTED WIND ENERGY SYSTRMPOWER QUALITY ISSUE WITH GRID CONNECTED WIND ENERGY SYSTRM
POWER QUALITY ISSUE WITH GRID CONNECTED WIND ENERGY SYSTRM
Ravijesh Kumar
 
IJERD(www.ijerd.com)International Journal of Engineering Research and Develop...
IJERD(www.ijerd.com)International Journal of Engineering Research and Develop...IJERD(www.ijerd.com)International Journal of Engineering Research and Develop...
IJERD(www.ijerd.com)International Journal of Engineering Research and Develop...
IJERD Editor
 

Similaire à Ib3313831387 (20)

Simulation of D-STATCOM to study Voltage Stability in Distribution system
Simulation of D-STATCOM to study Voltage Stability in Distribution systemSimulation of D-STATCOM to study Voltage Stability in Distribution system
Simulation of D-STATCOM to study Voltage Stability in Distribution system
 
Experimental dSPACE Analysis for Self-excited Induction Generator Used in Vol...
Experimental dSPACE Analysis for Self-excited Induction Generator Used in Vol...Experimental dSPACE Analysis for Self-excited Induction Generator Used in Vol...
Experimental dSPACE Analysis for Self-excited Induction Generator Used in Vol...
 
Ct4201633637
Ct4201633637Ct4201633637
Ct4201633637
 
Optimal Location of Statcom for Power Flow Control
Optimal Location of Statcom for Power Flow ControlOptimal Location of Statcom for Power Flow Control
Optimal Location of Statcom for Power Flow Control
 
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieWIRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
 
D010121832
D010121832D010121832
D010121832
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
At4101261265
At4101261265At4101261265
At4101261265
 
Mitigation of Voltage Fluctuations in Power System Using STATCOM
Mitigation of Voltage Fluctuations in Power System Using STATCOMMitigation of Voltage Fluctuations in Power System Using STATCOM
Mitigation of Voltage Fluctuations in Power System Using STATCOM
 
POWER QUALITY ISSUE WITH GRID CONNECTED WIND ENERGY SYSTRM
POWER QUALITY ISSUE WITH GRID CONNECTED WIND ENERGY SYSTRMPOWER QUALITY ISSUE WITH GRID CONNECTED WIND ENERGY SYSTRM
POWER QUALITY ISSUE WITH GRID CONNECTED WIND ENERGY SYSTRM
 
3.application of upfc in multi machine system for transient stability improve...
3.application of upfc in multi machine system for transient stability improve...3.application of upfc in multi machine system for transient stability improve...
3.application of upfc in multi machine system for transient stability improve...
 
Optimal Reactive Power Compensation in Electric Transmission Line using STATCOM
Optimal Reactive Power Compensation in Electric Transmission Line using STATCOMOptimal Reactive Power Compensation in Electric Transmission Line using STATCOM
Optimal Reactive Power Compensation in Electric Transmission Line using STATCOM
 
I41045662
I41045662I41045662
I41045662
 
Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...
Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...
Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...
 
Hybrid T-I-D and Fuzzy Logic Based SVC Controller for Transient Stability Enh...
Hybrid T-I-D and Fuzzy Logic Based SVC Controller for Transient Stability Enh...Hybrid T-I-D and Fuzzy Logic Based SVC Controller for Transient Stability Enh...
Hybrid T-I-D and Fuzzy Logic Based SVC Controller for Transient Stability Enh...
 
www.ijerd.com
www.ijerd.comwww.ijerd.com
www.ijerd.com
 
IJERD(www.ijerd.com)International Journal of Engineering Research and Develop...
IJERD(www.ijerd.com)International Journal of Engineering Research and Develop...IJERD(www.ijerd.com)International Journal of Engineering Research and Develop...
IJERD(www.ijerd.com)International Journal of Engineering Research and Develop...
 
www.ijerd.com
www.ijerd.comwww.ijerd.com
www.ijerd.com
 
Al4201250256
Al4201250256Al4201250256
Al4201250256
 
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faultsComparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
 

Dernier

+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...
+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...
+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...
?#DUbAI#??##{{(☎️+971_581248768%)**%*]'#abortion pills for sale in dubai@
 

Dernier (20)

+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...
+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...
+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...
 
Advantages of Hiring UIUX Design Service Providers for Your Business
Advantages of Hiring UIUX Design Service Providers for Your BusinessAdvantages of Hiring UIUX Design Service Providers for Your Business
Advantages of Hiring UIUX Design Service Providers for Your Business
 
Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024
 
Scaling API-first – The story of a global engineering organization
Scaling API-first – The story of a global engineering organizationScaling API-first – The story of a global engineering organization
Scaling API-first – The story of a global engineering organization
 
What Are The Drone Anti-jamming Systems Technology?
What Are The Drone Anti-jamming Systems Technology?What Are The Drone Anti-jamming Systems Technology?
What Are The Drone Anti-jamming Systems Technology?
 
Powerful Google developer tools for immediate impact! (2023-24 C)
Powerful Google developer tools for immediate impact! (2023-24 C)Powerful Google developer tools for immediate impact! (2023-24 C)
Powerful Google developer tools for immediate impact! (2023-24 C)
 
presentation ICT roal in 21st century education
presentation ICT roal in 21st century educationpresentation ICT roal in 21st century education
presentation ICT roal in 21st century education
 
Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024
Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024
Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024
 
Handwritten Text Recognition for manuscripts and early printed texts
Handwritten Text Recognition for manuscripts and early printed textsHandwritten Text Recognition for manuscripts and early printed texts
Handwritten Text Recognition for manuscripts and early printed texts
 
GenAI Risks & Security Meetup 01052024.pdf
GenAI Risks & Security Meetup 01052024.pdfGenAI Risks & Security Meetup 01052024.pdf
GenAI Risks & Security Meetup 01052024.pdf
 
🐬 The future of MySQL is Postgres 🐘
🐬  The future of MySQL is Postgres   🐘🐬  The future of MySQL is Postgres   🐘
🐬 The future of MySQL is Postgres 🐘
 
Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...
Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...
Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...
 
HTML Injection Attacks: Impact and Mitigation Strategies
HTML Injection Attacks: Impact and Mitigation StrategiesHTML Injection Attacks: Impact and Mitigation Strategies
HTML Injection Attacks: Impact and Mitigation Strategies
 
Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...
Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...
Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...
 
Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024
 
ProductAnonymous-April2024-WinProductDiscovery-MelissaKlemke
ProductAnonymous-April2024-WinProductDiscovery-MelissaKlemkeProductAnonymous-April2024-WinProductDiscovery-MelissaKlemke
ProductAnonymous-April2024-WinProductDiscovery-MelissaKlemke
 
How to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected WorkerHow to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected Worker
 
A Year of the Servo Reboot: Where Are We Now?
A Year of the Servo Reboot: Where Are We Now?A Year of the Servo Reboot: Where Are We Now?
A Year of the Servo Reboot: Where Are We Now?
 
Connector Corner: Accelerate revenue generation using UiPath API-centric busi...
Connector Corner: Accelerate revenue generation using UiPath API-centric busi...Connector Corner: Accelerate revenue generation using UiPath API-centric busi...
Connector Corner: Accelerate revenue generation using UiPath API-centric busi...
 
Boost Fertility New Invention Ups Success Rates.pdf
Boost Fertility New Invention Ups Success Rates.pdfBoost Fertility New Invention Ups Success Rates.pdf
Boost Fertility New Invention Ups Success Rates.pdf
 

Ib3313831387

  • 1. Mr.S.B.Dandawate*, Mrs.S.L.Shaikh / International Journal of Engineering Research and Applications (IJERA) ISSN: 2248-9622 www.ijera.com Vol. 3, Issue 3, May-Jun 2013, pp.1383-1387 1383 | P a g e Analysis of Effect on Transient Stability of Interconnected Power System by Introduction of HVDC Link. Mr.S.B.Dandawate*, Mrs.S.L.Shaikh** *,**(Department of Electrical Engineering, Walchand College of Engineering, Sangli) ABSTRACT Modern power employs HVDC links as a reliable and economical option for long EHVAC transmission line. The HVDC link in the power system behaves very differently than conventional HVAC lines during the disturbances in the power system. This paper analyses the effect of HVDC system on the transient stability of power system. Effect is studied on IEEE 24 bus reliability test system. A self-sufficient model developed in MATLAB Simulink has been given with full details, which can work as a basic structure for an advanced and detailed study. Keywords – Transient Stability, HVDC. I. INTRODUCTION The improving reliability of supply is one of the objective to interconnect the generators located at large distances and the purpose is achieved by running the synchronous generators in parallel i.e. in synchronism and with adequate capacity to meet the load demand [1]. The stability problem is concerned with the behavior of the synchronous machines after they have been perturbed while operating in synchronism. If perturbation does not involve any net change in power, the machine should return to the original state. If unbalance between the supply and load is created by the change in load, in generation, or in network conditions, a new operating state is necessary. In any case all the interconnected synchronous machines should remain in synchronism if the system is to be kept stable [2]. Distinction should be made between sudden and major disturbances, which we shall call large impacts, and smaller and more normal random impacts. If one of these large impacts occurs, the study of system behavior following it is referred to as the transient stability problem [3]. The system response to such disturbances involves large excursions of generator rotor angles, power flows, bus voltages, and other system variables. The ability of the system to survive a certain disturbance depends on its precise operating condition at the time of the occurrence of disturbance. A change in the system loading, generation schedule, network interconnections, or type of circuit protection may give completely different results in a stability study for the same disturbance. Thus the transient stability study is a very specific one, from which the engineer concludes that under given system conditions and for a given impact the synchronous machines will or will not remain in synchronism [4]. The problem of interest is one where a power system operating under a steady load condition is perturbed, causing the readjustment of the voltage angles of the synchronous machines. Any unbalance between the generation and load initiates a transient that causes the rotors of the synchronous machines to “swing” because net accelerating (or decelerating) torques are exerted on these rotors. If these net torques are sufficiently large to cause some of the rotors to swing far enough so that one or more machines “slip a pole,” synchronism between the machines is lost [3]. The transient stability is affected by lots of components present in power system and its behavior during the disturbance, like excitation system of generators, reactive power compensating devices, circuit breakers and steam valves of turbine. In this paper the effect of adding the HVDC line in the power system has been studied. The HVDC line shows very different behavior under transients than the HVAC lines as the power flow in DC lines is independent upon the voltage angles at the both ends. To study its effect on the transient stability, 24-Bus IEEE Reliability test system has been simulated in the MATLAB- Simulink environment. The PMU have been simulated to collect the voltage angles at the generator terminals and the behavior of the system is studied from these measurements. The paper is organized as follows. Section II details the simulated 24 bus system, Section III gives the details of PMU and its simulation, Section IV details HVDC system and its controls. Section V presents the simulation results, and Section VI concludes. II. DESCRIPTION OF THE BENCHMARK POWER SYSTEM This section first introduces the models of the different power system elements of the IEEE 24 bus system that is
  • 2. Mr.S.B.Dandawate*, Mrs.S.L.Shaikh / International Journal of Engineering Research and Applications (IJERA) ISSN: 2248-9622 www.ijera.com Vol. 3, Issue 3, May-Jun 2013, pp.1383-1387 1384 | P a g e used for the simulations. The fig.1 shows the layout of it. Fig. 1:-IEEE Reliability Test system The system contains 10 plants, one synchronous condensers and a reactor [5]. They are interconnected by 230KV network and 138KV network, both of them are interconnected through the 5 two winding transformers as shown in fig.1. The generators inside the plants are assumed to be coherent generators and considered as a single unit in the system with capacity equal to addition of capacities of all units in the plant. The generators are equipped with AVR’s and PSS. The plants are considered as the hydro power plants and hence hydraulic turbine and governor blocks in Simulink are used to supply mechanical power to it. Fig. 2 below gives the Simulink model of the subsystem simulated for the plants. Fig. 2:- Synchronous machine, excitation and governor subsystem Following table gives the loading of each generator – TABLE 1: - GENERATOR OUTPUTS BEFORE DISTURBANCE. Generator No. Bus No. Real Power (MW) Reactive Power (MVAr) 1 1 200.02 325.26 2 2 174.98 223.17 3 3 224.96 261.01 4 13 175.22 -196.98 5 15 50.07 -45.35 6 16 50.06 -64.026 7 18 200.17 -31.11 8 21 150.13 -36.033 9 22 100.17 -22.295 10 23 327.86 -91.17 The loads are modeled as a constant impedance load and hence the power absorbed by them is proportional to the square of the voltage across them. System contains a reactor of capacity 100 MVAr at bus 6 and a synchronous condenser of capacity -200 to 50 MVAr at bus 14. III. HVDC SYSTEM AND CONTROLLES HVDC systems are employed in modern power systems because of numerous economical and technical advantages over AC transmission when line length is more. The behavior of the HVDC line during and after the disturbance is different than the HVAC line as the power flow of the AC line is dependent upon the voltage angles at both the ends of the line while in DC line the power flow dependent merely upon the AC voltage magnitude at both ends and can be explained from following circuit diagram Fig.3:- Equivalent circuit of HVDC line The power flow is governed by the equations (1) (2) In the benchmark model one 200KV, 100MW, 100Km single pole CSC based HVDC line has been added in 230KV network between bus 18 to bus 11. Passive harmonic filters are employed to absorb the generated harmonics and to supply the required reactive power for the converter operations at the rectifier as well as inverter end. Terminal of the line connected to the bus 18 acts as a rectifier while connected to bus 11 acts as an inverter. Hence
  • 3. Mr.S.B.Dandawate*, Mrs.S.L.Shaikh / International Journal of Engineering Research and Applications (IJERA) ISSN: 2248-9622 www.ijera.com Vol. 3, Issue 3, May-Jun 2013, pp.1383-1387 1385 | P a g e the line guides power flow from 230KV network to 138KV network. Three modes of operation are designed to control the power injections from the end buses of each HVDC- link to desired value [6]. Under normal conditions, the HVDC-links operate in constant power mode when the rectifier operates in constant current control and the inverter operates in constant extinction angle control. During disturbances, when α reaches extreme values, the mode of operation changes. The control modes can be written as follows. • Mode 1: Constant power/current control at the rectifier and constant extinction angle at the inverter. • Mode 2: Minimum firing angle control at the rectifier and constant power/current control at the inverter. • Mode 3: Minimum firing angle control at the rectifier, and constant extinction control at the inverter. This is the transition mode between Mode 1 and Mode 2. HVDC link cannot be started abruptly as it may give a shock to existing system. The link is programmed to start and reach a steady state. Then steps are applied on the reference current of the rectifier and on the inverter reference voltage in order to execute the purpose. The converters are deblocked and started by ramping the rectifier and inverter reference current. At t = 0.02 s, the reference current is ramped to reach the minimum value of 0.1 pu in 0.3 s (0.033 pu/s). At the end of this first ramp (t = 0.32 s) the DC line is charged at its nominal voltage and DC voltage reaches steady-state. At t= 0.4 s, the reference current is ramped from 0.1 pu to 1 pu (500A) in 0.18 s (3 pu/s). At the end of this starting sequence (t=0.54 s) , the DC current reaches steady state. IV. PMU IMPLEMENTATION IN SYSTEM A Phasor Measurement Unit (PMU) is a device that provides synchrophasor and frequency measurements for one or more three phase AC voltage or current waveforms. The PMU takes reading throughout the system where it has been installed at the same time and hence we have the phasors from all across the system at same instant so it can be compared to study system behavior at that instant. The device uses CT and PT signals as an input and samples it N times per cycle of the 50 Hz (in this case) and by applying DFT we get the fundamental component of the phasor as (4) The conventional phasor representation of the phasor is releted to the fundamental component as (5) The devices are simulated in the Simulink and the MATLAB code has been generated to calculate the phasors in Simulink model(Fig.5). Fig.5:-Simulink model to simulate PMU The devices are connected at each generator terminal hence we have the synchronized phasors of all generator terminals. PMU in this case gives 25 phasors per second as per reference (9). Because of implementation of DFT technique PMU gives output of phasor angles between -1800 to +1800 instead of 00 to 3600 (7). V. SIMULATION AND RESULTS The Simulink model of the IEEE 24 bus reliability test system is given in Fig. 6. To study the transient stability of the model, the disturbance has been created by applying three phase to ground solid short circuit to various locations in the power system. The faults are cleared by opening the respective transmission lines and the critical clearing time of each fault for a particular operating condition of the power system has been noted. The same exercise is carried out for a system with and without HVDC link. The behavior of the system is studied by observing rotor angles of the synchronous machines. When angles of the machine moves away from each other by 1800 , it is considered that stability is lost. PMUs installed at the generator terminals gives us the voltage angles of the respective generator terminal voltage. The assumption have been made that the terminal voltage angle and rotor angles are same, and hence the PMUs gives us directly the rotor angles of the generators. As the time frame of interest in transient stability analysis is usually three to five seconds after the disturbance [1], this study is conducted to the first three seconds after the short-circuit inception.
  • 4. Mr.S.B.Dandawate*, Mrs.S.L.Shaikh / International Journal of Engineering Research and Applications (IJERA) ISSN: 2248-9622 www.ijera.com Vol. 3, Issue 3, May-Jun 2013, pp.1383-1387 1386 | P a g e Fig. 6:- Simulink Model of IEEE 24 Bus Test System. V.1. Illustrative Example A three phase to ground fault is applied to bus 16 at t=1s, and the fault is cleared by tripping lines 16-14, at t=1.5sec and t=1.7sec without HVDC link. From the generator angles (Fig.7 and Fig.8) we can see the system loses synchronism for FCT 0.7sec, the generators 6, 7, 8 and 9 speeds up from rest of the system. Study is repeated after addition of HCDC link in Model and the generator rotor angle movement is observed for FCT 0.7sec (Fig. 9). Results shows that after inception of HVDC link, the system does not loses synchronism when fault cleared at 0.7sec. Fig.7:- Rotor angles for FCT 0.5 sec, without HVDC. Fig.8:- Rotor angles for FCT 0.7 sec, without HVDC. Fig.9:- Rotor angles for FCT 0.7 sec, with HVDC. Same study has been conducted for faults at various locations in the system and the critical clearing time has been noted down in Table 2. TABLE 2:- CRITICAL CLEARING TIME (IN SEC.) FOR DIFFERENT CONTINGENCIES Fault Location Line Opened Critical FCT Without HVDC (Sec.) Critical FCT with HVDC (Sec.) Bus 16 16-17 0.7 1.4 Bus 16 16-14 0.68 1.6 Bus 16 16-17 & 16-14 0.6 2.0 Bus 14 14-11 0.932 3.0 Bus 21 15-21 0.32 0.9 VI. CONCLUSION Transient stability of the interconnected
  • 5. Mr.S.B.Dandawate*, Mrs.S.L.Shaikh / International Journal of Engineering Research and Applications (IJERA) ISSN: 2248-9622 www.ijera.com Vol. 3, Issue 3, May-Jun 2013, pp.1383-1387 1387 | P a g e power system gets improved with HVDC link introduced in it. A significant improvement in the critical fault clearing time is observed when HVDC link is present. The role of HVDC in transient stability improvement depends mainly upon the location and the power rating of HVDC transmission line. A complete model for transient stability study of a multi-machine power system was developed using Simulink. Thus a Simulink model is not only best suited for an analytical study of a typical power system network, but it can also incorporate the state- of-the-art tools for a detailed study and parameter optimization. A Simulink model is very user friendly, with tremendous interactive capacity and unlimited hierarchical model structure. REFERENCES [1] W.D Stevensen,J.J.Grainger, Power System Anlysis (Tata Mcgraw Hill Education, 2003) [2] P. Kundur,Power System Stability and ControlI (Tata McGraw Hill Education,2011 ) [3] E.W.Kimbark,Power System Sability Vol I,II,III, (John Willey , 2003) [4] P. M. Anderson and A. A. Fouad, Power System Control and Stability (Iowa State University Press, Ames, IA, 1977) [5] A report prepared by the Reliability Test System Task Force of the Application of Probability Methods Subcommittee, IEEE reliability test system, IEEE Transactions on Power Apparatus and Systems, Vol. PAS-98, No.6 Nov./Dec. 1979 [6] J. Arrillaga, High Voltage Direct Current Transmission, (IEE Press Power Engineering Series, 1883). [7] A.G.Phadke, J.S. Thorp,Synchronised Phasor Measurement and Their Applications,(Springer 2008). [8] A.G.Phadke,J.S.Thorp,M.G.Admaik,A New Measurement Technique for Tracking Voltage Phasors,Local System frequency,and Rate of Change of Frequency,Power Engineering Review,Vol 2 Issue 5, 1983,0272-1724 [9] IEEE Standard for Synchrophasors for Power System , IEEE Std 1344-1995(R2001). BIOGRAPHIES S. B. Dandawate: Has completed B.E in Electrical Engineering from University of Pune and doing M.Tech in Power System in Walchand College of Engineering, Sangli. His areas of interest are Power System Stability, Power System Operation and Control and HVDC Transmission System. S. L. Shaikh : She is associate Professor in the faculty of Electrical Engineering in Walchand College of Engineering Sangli. Her research areas are power system stability and power quality.