Exergy Analysis of a Chilling Plant – A Review
Mr. Manish G. Vasava
, Dr. Neeraj K. Chavda**

PG Student and corresponding author, **
Associate Professor.
* **
Mechanical Engineering Department, ADIT Engineering College, Vallabh Vidhyanagar, Anand, Gujarat,
ABSTRACT
Exergy analysis is widely used in the design, simulation and performance analysis of various types of
engineering applications in comparison with energy analysis. Energy analysis presents only quantities results
while exergy analysis presents qualitative results about actual energy consumption. This paper emphasizes
review of open literature related to the application of exergy analysis in various engineering application since its
development. It has been found that application of exergy analysis in vapour compression refrigeration system
has been increased in last decade only.
Keywords – Energy, Exergy, Exergy Analysis, Vapour Compression Refrigeration System, Chilling Plant
I. INTRODUCTION
The term Exergy was published for the first
time by Rant in 1956, and refers to the Greek words
ex (external) and ergos (work). Another term
describing the same is Available Energy or simply
Availability. The term Exergy is related to Ideal
Work and Exergy Losses relate to Lost Work.
Recently, exergy analysis method has been widely
used in the design, simulation and performance
assessment of various types of systems for
identifying losses and in-efficiencies. Exergy is
defined as the maximum work that may be achieved
by bringing a system into equilibrium with its
environment. First law of thermodynamic only deals
with the quality of energy, while exergy deals with
both quality and quantity. Every system not in
equilibrium with its environment has some quantity
of exergy, while a system that is in equilibrium with
its environment has, by definition, zero exergy since
it has no ability to do work with respect to its
environment.
A chilling Plant works on VCRS that cools
Air/Water, creating a more comfortable environment.
Chillers are also used to provide process cooling to
equipment in an effort to maximize productivity.
Chillers circulate chilled water to process unit in
order to transfer heat from process to water. This
water then returns to the evaporator side of the chiller
where the heat is passed from the water to a liquid
refrigerant. The refrigerant leaves the evaporator as a
cold vapor and enters the compressor where it is
compressed into a hot vapor. Upon leaving the
compressor, the vapor enters the condenser side of
the chiller where heat is transferred from the
refrigerant to the air side of the condenser where it is
circulated to an open surrounding environment for
the final removal of heat.
II. LITERATURE REVIEW
The detailed review of literature related to
the inception, development, and various application
of exergy analysis has been carried by Enrico S. et.
al.[1].
The review is divided into following sub groups.
(1) Conceptual literature in line with Exergy.
(2) Inception of “Exergy”
(3) Development of Exergy
(4) Expertise phase of Exergy
(5) Application of exergy analysis in various fields.
Number of literatures published in the sub
group number 1 to 4 is presented in Table 1.1 while
the application of exergy analysis in various
engineering field is tabulated in Table 1.2.
Sub Group Duration of
Year
Number of
Research
Papers
Published
Conceptual
Literature in line of
Exergy
1824-1952 33
Inception of Exergy 1953 1
Development of
Exergy analysis
1954-1970 71
Expertise Phase of
Exergy
After 1970 292
Table 1.1 Development Scenario of Exergy
RESEARCH ARTICLE OPEN ACCESS
Mr. Manish G. Vasava et al Int. Journal of Engineering Research and Applications www.ijera.com
ISSN : 2248-9622, Vol. 4, Issue 5( Version 6), May 2014, pp.124-128
www.ijera.com 125 | P a g e
Type of Engineering
Applications of exergy
analysis
Number of Research
Papers Published
1931-1960
1961-1980
1981-2000
2001-2010
2011-2014
Steam Power Cycles 2 4 5 5 -
Gas Turbine Cycles - 4 6 9 -
Renewable Energy
Cycles
- - 4 1 -
Combined &
Cogeneration Cycles
- 9 20 11 -
Heat exchangers & Heat
Networking
1 5 18 8 -
Cryogenics 4 15 14 12 -
Chemical Processes 3 10 15 11 -
Distillation &
Desalination
1 6 15 8 -
Industrial &
Agricultural Systems
2 6 22 8 -
Environmental Appli. - 8 21 12 -
VCRS - - - 5 8
Table 1.2 Application of Exergy Analysis
From Table 1.1, it is found that, exergy
analysis has grown from child to adult from 1824 to
till date and scientists and researchers are enjoying
the fruitful results of expertise in the field of Exergy
analysis. From Table 1.2, it is clear that, since its
development, exergy analysis has been widely used
in most of the engineering applications. The study of
exergy analysis related to VCRS has been increased
in last decade only.
Other literatures related exergy analysis is
presented in the following section.
Amir V et al. [2] have studied on exergy
concept and it’s characteristic. Here author had
introduced the detail information about exergy and
also describe about exergy losses, entropy and energy
in thermodynamic systems. Here, author had define
dead state, surroundings, immediate surroundings,
environment and different forms of exergy. In this
paper the concept of exergy and its characteristic and
application in various fields has been discussed. And
different forms of exergy have been derived. Also a
brief comparison between energy and exergy analysis
has been done.
Yunus A et al. [3] describe that At present
day also human ,tend to judge things on the basis of
their quantity rather than quality, and perceive bigger
things as being better, stronger, and more
competitive. Assessments made on the basis of
quantity only (the first law) may be grossly
inadequate and misleading. When two companies
merge, for example, we expect the joint company to
be more productive and more dominant in a
competitive world, and when two states or countries
merge, we expect the new union to be stronger. But
experience shows that often this is not the case,
confirming the phrase “bigger is not necessarily
better”. In thermodynamics, this is analogous to a
system with a larger energy content not necessarily
having a larger exergy content or work potential. so
requirement of exergy analyses to know how
effectively useful energy converted into useful work.
Aprea C et al. [4] presented the experimental studies
of performances of a vapour compression
refrigeration plant using as working fluids R22 and
its substitute R417A (R125/R134a/R600,
46.6/50/3.4% in mass). This type of plant is applied
to a commercially available cold store, generally
adopted for preservation of foodstuff. The
experimental analysis had allowed the determination
of the best energetic performances of R22 in
comparison with those of R417A in terms of the
coefficient of performance, exergetic efficiency,
exergy destroyed in the plant components and other
variables characterizing the refrigeration plant
performance.
Guiyin F et al. [5] has investigated Exergy
analysis of a dual mode refrigeration system for ice
storage air conditioning. Here, dual mode
refrigeration system consists of conventional air
conditioning operation unit and the ice storage
operation unit. The refrigeration system studied is a
dual-mode refrigeration cycle process. This indicates
that the refrigeration system operates not only in
conventional air conditioning mode during daytime,
but also in ice storage mode during nighttime. . The
results show that the exergy efficiency of the
refrigeration system in ice storage operating mode is
17.63% lower than that of the refrigeration system in
air conditioning operating mode.
Akhilesh A et al.[6] presented a detailed
exergy analysis of an actual vapour compression
refrigeration (VCR) cycle. A computational model
has been developed for computing coefficient of
performance (COP), exergy destruction, exergetic
efficiency and efficiency defects for R502, R404A
and R507A. The present investigation has been done
for evaporator and condenser temperatures in the
range of 50 ℃to 0℃and 40 ℃ to 55℃, respectively.
The results indicate that R507A is a better substitute
to R502 than R404A.
The efficiency defect in condenser is highest, and
lowest in liquid vapour heat exchanger for the
refrigerants considered. In this communication, an
extensive energy and exergy analysis of R502,
R404A and R507A in an actual vapour compression
cycle have been presented. The conclusions of the
present analysis are summarized below.
 COP and exergetic efficiency for R507A are
better than that for R404A at condenser
Mr. Manish G. Vasava et al Int. Journal of Engineering Research and Applications www.ijera.com
ISSN : 2248-9622, Vol. 4, Issue 5( Version 6), May 2014, pp.124-128
www.ijera.com 126 | P a g e
temperatures between 40O
C and 55O
C. However,
both refrigerants show 4–17% lower value of
COP and exergetic efficiency in comparison to
R502 for the condenser temperatures between
40O
C and 55O
C.
 The worst component from the viewpoint of
irreversibility or exergy destruction is condenser
followed by compressor, throttle valve and
evaporator, respectively. The most efficient
component is liquid vapour heat exchanger. The
summation of efficiency defects for R507A is
less than R404A for condenser temperatures
between 40 ℃ and 55℃.
Rahim K.J et al. [7] had submitted Energy,
Exergy and Thermo economics Analysis of Water
Chiller Cooler for Gas Turbines Intake Air Cooling.
In the present study, the performance of a cooling
system that consists of a chilled water external loop
coupled to the GT entrance is investigated. An
objective of the present study is to assess the
importance of using a coupled thermo-economics
analysis in the selections of the cooling system and
operation parameters. In the present study, the
profitability resulting from cooling the intake air is
calculated for electricity rates between 0.07 and 0.15
$/kWh and a payback period of 3 years. Cash flow
analysis of the GT power plant in the city of Yanbu
shows a potential for increasing the output power of
the plant and increased revenues.
Bukola O.B [8] presents experimental
results of investigation of effects of sub-cooling on
the performance of four ozone-friendly alternative
refrigerants (R32, R152a, R143a, and R134a) in a
domestic refrigeration system. The study was
performed using a system designed for R12 with the
aim of finding a drop-in replacement for the
refrigerant. Average refrigeration capacities of R152a
and R134a were 2.6% higher and 3.4% lower than
that of R12, respectively, while average capacities of
R143a and R32 were 22.4% and 31.3% lower than
that of R12, respectively. Also, the results obtained
showed that as the degree of sub-cooling increases,
the pressure ratio reduces, while both the refrigerant
mass flow rate and the coefficient of performance
(COP) increase. The COPs of R152a and R134a
obtained at various degrees of sub-cooling are close
to that of R12, while significant deviations in COPs
of R32 and R143a were obtained when compared
with that of R12. The overall assessment of the
results showed that R152a and R134a refrigerants
had the most similar performance characteristics to
R12, with R152a having a slightly better
performance, while the performances of R32 and
R143a were significantly lower than that of R12.
Ust Y et al. [9] has analyzed exegetic
performance coefficient criterion for a vapour
compression refrigeration system for different
refrigerant. This analysis has been carried out using
the refrigerants R32, R410A, R143A, R404A and
R125. The COP at maximum EPC condition for the
refrigerant R125 is bigger than the other refrigerants
studied in this paper. According to the results, the
refrigerant R32 shows the best performance in terms
of EPC among the other refrigerants (R410A,
R143A, R404A and R125).
Ahamed J.U et al. [10] worked on exergy
analysis in various usable sectors where vapour
compression refrigeration systems are used. Exergy
losses, exergy efficiency, second law efficiency and
irreversibility of the system components as well as of
the whole system are measured. In the vapour
compression system, R134a, R290 and R600a are
considered as refrigerants. Exergy parameters in the
compressor, evaporator, condenser and expansion
devices are calculated and analyzed. Exergy losses
depend on evaporator temperatures, condensing
temperature, refrigerants and ambient temperature.
Most of the exergy losses occur in the condenser.
Expansion device has the lowest losses. Exergy
parameters are compared for different operating
temperatures. It is found that hydrocarbons (R600a)
have 50% higher exergy efficiency than R134a.
Mixture of hydrocarbons also shows the best
performance based on the exergy analysis. After the
successful investigation of the HC as a refrigerant on
the basis of performance, the following conclusions
can be drawn based on the results obtained:
 Exergy loss for butane and isobutene are less
than that of the refrigerant R134a in the present
test unit. In the higher evaporating temperature
exergy loss is decreased for all refrigerants.
 Exergy efficiency is also higher for butane
compared to that of isobutene and R-134a as
refrigerants.
 Exergy loss in the compressor is higher than that
in the other parts of the system i.e. up to 69% of
the total exergy loss occurs in the compressor.
 The co-efficient of performances for butane and
isobutene are comparable with that of R134a.
 Exergy loss increases with the increase of
condenser temperature. Its higher for butane
compared that of R134a and iso butane.
Camelia S et al. [11] work on a comparative
analysis of the refrigerant effect on the operation and
performances of a one stage vapour compression
refrigeration system. the paper is to present and
propose an analysis model for comparing the
operation of a VCR System with different
refrigerants, from performances point of view and
from limitations in terms of compression ratio. This
paper presents a comparative analysis of five
refrigerants working in a one stage VCRS with sub
cooling and superheating. Based on the exergy
analysis, exergy destruction rates were estimated for
each component of the system in a comparative
Mr. Manish G. Vasava et al Int. Journal of Engineering Research and Applications www.ijera.com
ISSN : 2248-9622, Vol. 4, Issue 5( Version 6), May 2014, pp.124-128
www.ijera.com 127 | P a g e
manner for five refrigerants (R22, R134a, R717,
R507a, R404a) proving a different behavior and thus
bringing important information about system
optimization when working with a specific
refrigerant.
Vaibhav J et al. [12] investigated
thermodynamic analysis of R134a, R410a, R407c
and M20 in comparison to R22. In the present
research study a refrigerant property dependent
thermodynamic model of a simple reciprocating
system, which can simulate the performance of actual
system as closely as possible, has been used to
compare the characteristics of various refrigerants.
From the comparison of performance parameters it
can be concluded that R407C is a potential HFC
refrigerant replacement for new and existing systems
presently using R22 with minimum investment and
efforts.
Jyoti S et al. [13] Presented a theoretical
performance study of a vapour compression
refrigeration system with refrigerants R-407C and R-
410A. A computational model based on energy and
exergy analysis is presented for the investigation. The
exergetic efficiency of R-407C is 2.5-5.1% higher
than R410A for considered range of dead state
temperatures. A theoretical investigation showed that
better performances of R-407C in comparisons with
R-410A.
Ratnesh S et al.[14] investigated a domestic
refrigerator designed to work with R-134a to assess
the possibility of using a mixture of propane and
isobutene. The performance of the refrigerator using
azotropic mixture as refrigerants was investigated
and compared with the performance of refrigerator
when R-134, R12, R22, R290, R600a is used as a
refrigerant. It has been found from the calculations
that mixture of propane and isobutene (mint gas) is
producing better results than other refrigerants.
R.S.Mishra [15] presents methods for
improving first law and second law efficiency have
using new refrigerants: R134a, R290, R600a,
R1234yf, R502,R404a and R152a and R12, R502.
For exergy and energy analysis six type of vapour
compression refrigeration system have been
considered with using eco-friendly refrigerants with
multi-evaporators, multiple compressors and multiple
expansion valve with parallel and series with
intrercooling and flash chambers. Numerical
computational model have been carried out for the
system. Performance of the system using R600 and
R152a nearly matching same values under the
accuracy of 5 % can be used in the system and
difficulties detected with R600, R290 and R600a
having flammable problems therefore safety
measures are required using these refrigerants,
therefore R134a is recommended for practical and
commercial applications.
Naushad A.A et al. [16] has conducted theoretical
exergy analysis of HFO-1234yf and HFO-1234ze,
both ultra low Global Warming Potential(GWP) and
zero Ozone Depletion Potential(ODP) refrigerants in
simple vapour compression refrigeration system and
comparison of their results with HFC-134a
refrigerant as possible alternative replacements in
Automotive air-conditioning and stationary
refrigeration is presented. Results obtained indicate
that HFO-1234yf and HFO-1234ze can be good
replacement of R-134a.
III. CONCLUSION
In this paper, review of exergy analysis
method has been studied since then when the word
“exergy” was not in use. From the review it is clear
that application of exergy in various fields are on its
peak. The literature related to exergy analysis of
VCRS is available since last decade only and
particular for chilling plant is rare. Thus, it seems that
there is scope of application of exergy analysis in
chilling plant for analyzing its performance.
REFERENCES
Journal Papers
[1] Enrico S and Goran W,” A brief
Commented History of Exergy From the
Beginnings to 2004 “, Int. J. of
Thermodynamics, March 2007, Vol. 10 (No.
1), pp. 1-26.
[2] Amir V, Aminreza N, Mohammad G and
Sadegh V,” Exergy Concept and its
Characteristic”, International journal of
Multidisciplinary Sciences and Engineering
,July 2011, Vol. 2, No. 4.
[3] Yunus A, Byard W and Ibrahim D, “ Is
bigger thermodynamically better? Exergy”,
International Journal 2 , 2002, 62-68.
[4] Aprea C and Renno C, “Experimental
comparison of R22 with R417A
performance in a vapour compression
refrigeration plant subjected to a cold
store”,Energy conversion and Management
45, 2004.
[5] Guiyin F , Lin X, Fan Y and Hui L,” Exergy
Analysis of a Dual Mode Refrigeration
System for Ice Storage air conditioning”,
International Journal on Architectural
Science, 2005,Volume 6, Number 1, p.1-6.
[6] Akhilesh A and kaushik S, “ Theoretical
analysis of a vapour compression system
with R502, R404a and R507a”, International
journal of refrigeration 31 ,2008, 998-1005.
[7] Rahim K. J, Majed M. A and Galal M Z
“Energy, Exergy and Thermoeconomics
Analysis of Water Chiller Cooler for Gas
Turbines Intake Air Cooling”, Intechopen,
2009.
Mr. Manish G. Vasava et al Int. Journal of Engineering Research and Applications www.ijera.com
ISSN : 2248-9622, Vol. 4, Issue 5( Version 6), May 2014, pp.124-128
www.ijera.com 128 | P a g e
[8] Bukola O B,” Exergetic performance of a
domestic refrigerator using R12 and its
alternative refrigerants”, Journal of
Engineering Science and Technology
,2010,Vol. 5, No. 4.
[9] Ust, Y, Akkaya A V and Safa A,
“Analysis of a vapour compression
refrigeration system via exergetic
performance coefficient criterion”, Journal
of the Energy Institute, 2011.
[10] Ahamed J U, Saidur R, Masjuki H H and
Mehjabin S , “ Prospect of Hydrocarbon
uses based on exergy analysis in the vapour
compression refrigeration system”,
International Journal of Renewable Energy
Research I,2011.
[11] Camelia S, Adina G, Dorin S and
Alexandru D, “Exergy analysis and
refrigerant effect on the operation and
performance limits of a one stage vapour
compression refrigeration system”,
Termotehnica,1/2011.
[12] Vaibhav J, Kachhwaha S S and Mishra R S
, “Comparative performance study of vapour
compression refrigeration system with
R22/R134a/R410A/R407C/M20”,
International Journal of Energy and
Environment,2011, Volume 2, Issue 2.
[13] Jyoti S and R.C. Gupta , “Exergy Analysis
of Vapour Compression Refrigeration
System with Using R-407C and R-410A”,
International Journal of Engineering
Research & Technology
(IJERT),September-2012, Vol. 1.
[14] Ratnesh S and Akhilesh L , “Analysis of
Ecofriendly Refrigerant with commonly
used Refrigerant in domestic refrigerators “
,Global J. of Engg. & Appl. Sciences, 2012.
[15] R S Mishra , “Irreversibility analysis of
multi-evaporators vapour compression
refrigeration systems using new and
refrigerants:R134a, R290, R600, R600a,
R1234yf, R502, R404a and R152a and R12,
R502”,International journal of advance
research and innovation,2013, volume
2,188-200.
[16] Naushad A. A, Bipin Y, and Jitendra K,
“Theoretical Exergy Analysis of HFO-
1234yf and HFO-1234ze as an Alternative
Replacement of HFC-134a in Simple
Vapour Compression Refrigeration System”,
International Journal of Scientific &
Engineering Research,, Issue 8, August-
2013, Volume 4.

Contenu connexe

Tendances

HEAT TRANSFER ENHANCEMENT TECHNIQE
HEAT TRANSFER ENHANCEMENT TECHNIQE HEAT TRANSFER ENHANCEMENT TECHNIQE
HEAT TRANSFER ENHANCEMENT TECHNIQE
pat2606
 
Heat Transfer Characteristics of a Plate Fin Heat Sink with Pin Fins of Vario...
Heat Transfer Characteristics of a Plate Fin Heat Sink with Pin Fins of Vario...Heat Transfer Characteristics of a Plate Fin Heat Sink with Pin Fins of Vario...
Heat Transfer Characteristics of a Plate Fin Heat Sink with Pin Fins of Vario...
ijtsrd
 
Simulation Based Interpretation and Recent Trends on Performance Analysis on ...
Simulation Based Interpretation and Recent Trends on Performance Analysis on ...Simulation Based Interpretation and Recent Trends on Performance Analysis on ...
Simulation Based Interpretation and Recent Trends on Performance Analysis on ...
ijtsrd
 
Selection of Material for Improving Heat Transfer Rate for Fins using CFD
Selection of Material for Improving Heat Transfer Rate for Fins using CFDSelection of Material for Improving Heat Transfer Rate for Fins using CFD
Selection of Material for Improving Heat Transfer Rate for Fins using CFD
ijtsrd
 
Thermodynamic simulation of year round air conditioning system for variable r...
Thermodynamic simulation of year round air conditioning system for variable r...Thermodynamic simulation of year round air conditioning system for variable r...
Thermodynamic simulation of year round air conditioning system for variable r...
eSAT Journals
 

Tendances (19)

HEAT TRANSFER ENHANCEMENT TECHNIQE
HEAT TRANSFER ENHANCEMENT TECHNIQE HEAT TRANSFER ENHANCEMENT TECHNIQE
HEAT TRANSFER ENHANCEMENT TECHNIQE
 
IRJET- Double Pipe Heat Exchanger with Spiral Flow
IRJET- Double Pipe Heat Exchanger with Spiral FlowIRJET- Double Pipe Heat Exchanger with Spiral Flow
IRJET- Double Pipe Heat Exchanger with Spiral Flow
 
Heat Transfer Characteristics of a Plate Fin Heat Sink with Pin Fins of Vario...
Heat Transfer Characteristics of a Plate Fin Heat Sink with Pin Fins of Vario...Heat Transfer Characteristics of a Plate Fin Heat Sink with Pin Fins of Vario...
Heat Transfer Characteristics of a Plate Fin Heat Sink with Pin Fins of Vario...
 
Simulation Based Interpretation and Recent Trends on Performance Analysis on ...
Simulation Based Interpretation and Recent Trends on Performance Analysis on ...Simulation Based Interpretation and Recent Trends on Performance Analysis on ...
Simulation Based Interpretation and Recent Trends on Performance Analysis on ...
 
Paper id 27201445
Paper id 27201445Paper id 27201445
Paper id 27201445
 
HEAT TRANSFER AUGMENTATION IN STEEL QUENCHING BY SPRAY IMPINGEMENT COOLING ME...
HEAT TRANSFER AUGMENTATION IN STEEL QUENCHING BY SPRAY IMPINGEMENT COOLING ME...HEAT TRANSFER AUGMENTATION IN STEEL QUENCHING BY SPRAY IMPINGEMENT COOLING ME...
HEAT TRANSFER AUGMENTATION IN STEEL QUENCHING BY SPRAY IMPINGEMENT COOLING ME...
 
02.jnae10085
02.jnae1008502.jnae10085
02.jnae10085
 
Optimization of Process Parameters of Direct Evaporative Cooling using Khus M...
Optimization of Process Parameters of Direct Evaporative Cooling using Khus M...Optimization of Process Parameters of Direct Evaporative Cooling using Khus M...
Optimization of Process Parameters of Direct Evaporative Cooling using Khus M...
 
IRJET- Review on An Innovative Approach to Study the Thermal Performance of M...
IRJET- Review on An Innovative Approach to Study the Thermal Performance of M...IRJET- Review on An Innovative Approach to Study the Thermal Performance of M...
IRJET- Review on An Innovative Approach to Study the Thermal Performance of M...
 
Selection of Material for Improving Heat Transfer Rate for Fins using CFD
Selection of Material for Improving Heat Transfer Rate for Fins using CFDSelection of Material for Improving Heat Transfer Rate for Fins using CFD
Selection of Material for Improving Heat Transfer Rate for Fins using CFD
 
IRJET- Design and Analysis of Split Refrigeration System with Indoor & Ou...
IRJET-  	  Design and Analysis of Split Refrigeration System with Indoor & Ou...IRJET-  	  Design and Analysis of Split Refrigeration System with Indoor & Ou...
IRJET- Design and Analysis of Split Refrigeration System with Indoor & Ou...
 
Investigation of Heat Dissipation in Petrol Engine Cylinder during Explosion ...
Investigation of Heat Dissipation in Petrol Engine Cylinder during Explosion ...Investigation of Heat Dissipation in Petrol Engine Cylinder during Explosion ...
Investigation of Heat Dissipation in Petrol Engine Cylinder during Explosion ...
 
30120140503007
3012014050300730120140503007
30120140503007
 
Pf boiler combustion
Pf boiler combustionPf boiler combustion
Pf boiler combustion
 
Paper id 26201495
Paper id 26201495Paper id 26201495
Paper id 26201495
 
IRJET- Fabrication and Performance Analysis of Refrigeration Type Desert ...
IRJET-  	  Fabrication and Performance Analysis of Refrigeration Type Desert ...IRJET-  	  Fabrication and Performance Analysis of Refrigeration Type Desert ...
IRJET- Fabrication and Performance Analysis of Refrigeration Type Desert ...
 
CFD Simulation and Heat Transfer Analysis of Automobile Radiator using Helica...
CFD Simulation and Heat Transfer Analysis of Automobile Radiator using Helica...CFD Simulation and Heat Transfer Analysis of Automobile Radiator using Helica...
CFD Simulation and Heat Transfer Analysis of Automobile Radiator using Helica...
 
Review on Exergy and Energy Analysis of Solar Air Heater
Review on Exergy and Energy Analysis of Solar Air HeaterReview on Exergy and Energy Analysis of Solar Air Heater
Review on Exergy and Energy Analysis of Solar Air Heater
 
Thermodynamic simulation of year round air conditioning system for variable r...
Thermodynamic simulation of year round air conditioning system for variable r...Thermodynamic simulation of year round air conditioning system for variable r...
Thermodynamic simulation of year round air conditioning system for variable r...
 

En vedette

三個願望
三個願望三個願望
三個願望
Jaing Lai
 
Evaluación educativa
Evaluación educativaEvaluación educativa
Evaluación educativa
Edgar68
 
Los 7 cuervos
Los 7 cuervosLos 7 cuervos
Los 7 cuervos
Edu
 
熱鬧的夏日蓮園 --王英明攝
熱鬧的夏日蓮園 --王英明攝熱鬧的夏日蓮園 --王英明攝
熱鬧的夏日蓮園 --王英明攝
Jaing Lai
 
Panoramas vu
Panoramas vuPanoramas vu
Panoramas vu
Jaing Lai
 
Objetivo 1 Envio nº2
Objetivo 1 Envio nº2Objetivo 1 Envio nº2
Objetivo 1 Envio nº2
D G
 
茅草屋 走入童話般的世界
茅草屋 走入童話般的世界茅草屋 走入童話般的世界
茅草屋 走入童話般的世界
Jaing Lai
 
Guia rapida factura excel version 2011
Guia rapida factura excel version 2011Guia rapida factura excel version 2011
Guia rapida factura excel version 2011
JFKSOFT CORP.
 

En vedette (20)

三個願望
三個願望三個願望
三個願望
 
DodecaMojón
DodecaMojónDodecaMojón
DodecaMojón
 
Trolexismo
TrolexismoTrolexismo
Trolexismo
 
Constructivismo
ConstructivismoConstructivismo
Constructivismo
 
Mreey
MreeyMreey
Mreey
 
BSL
BSLBSL
BSL
 
Evaluación educativa
Evaluación educativaEvaluación educativa
Evaluación educativa
 
Los 7 cuervos
Los 7 cuervosLos 7 cuervos
Los 7 cuervos
 
熱鬧的夏日蓮園 --王英明攝
熱鬧的夏日蓮園 --王英明攝熱鬧的夏日蓮園 --王英明攝
熱鬧的夏日蓮園 --王英明攝
 
Panoramas vu
Panoramas vuPanoramas vu
Panoramas vu
 
Momentos vocacPastoral Vocacional Franciscana (HFIC): Reflexión Momentos Vo...
Momentos vocacPastoral Vocacional Franciscana (HFIC):  Reflexión  Momentos Vo...Momentos vocacPastoral Vocacional Franciscana (HFIC):  Reflexión  Momentos Vo...
Momentos vocacPastoral Vocacional Franciscana (HFIC): Reflexión Momentos Vo...
 
Objetivo 1 Envio nº2
Objetivo 1 Envio nº2Objetivo 1 Envio nº2
Objetivo 1 Envio nº2
 
O que é arte
O que é arteO que é arte
O que é arte
 
Numerodejogadoresemcamporeduzido 141107161228-conversion-gate02
Numerodejogadoresemcamporeduzido 141107161228-conversion-gate02Numerodejogadoresemcamporeduzido 141107161228-conversion-gate02
Numerodejogadoresemcamporeduzido 141107161228-conversion-gate02
 
Habitaculo 2014
Habitaculo  2014Habitaculo  2014
Habitaculo 2014
 
鎖鏈
鎖鏈鎖鏈
鎖鏈
 
NUEVA TIENDA VIRTUAL JFKSOFT PAGO SEGURO
NUEVA TIENDA VIRTUAL JFKSOFT  PAGO SEGURONUEVA TIENDA VIRTUAL JFKSOFT  PAGO SEGURO
NUEVA TIENDA VIRTUAL JFKSOFT PAGO SEGURO
 
Art auguste rodin (catherine)
Art auguste rodin  (catherine)Art auguste rodin  (catherine)
Art auguste rodin (catherine)
 
茅草屋 走入童話般的世界
茅草屋 走入童話般的世界茅草屋 走入童話般的世界
茅草屋 走入童話般的世界
 
Guia rapida factura excel version 2011
Guia rapida factura excel version 2011Guia rapida factura excel version 2011
Guia rapida factura excel version 2011
 

Similaire à W04506124128

A Review Paper on Design of Generator in Vapour Absorption Refrigeration System
A Review Paper on Design of Generator in Vapour Absorption Refrigeration SystemA Review Paper on Design of Generator in Vapour Absorption Refrigeration System
A Review Paper on Design of Generator in Vapour Absorption Refrigeration System
ijtsrd
 
Design of waste heat driven vapour adsorption cooling system for vehicle air ...
Design of waste heat driven vapour adsorption cooling system for vehicle air ...Design of waste heat driven vapour adsorption cooling system for vehicle air ...
Design of waste heat driven vapour adsorption cooling system for vehicle air ...
eSAT Journals
 
Experimental Investigations on Solid Desiccant Cooling System
Experimental Investigations on Solid Desiccant Cooling SystemExperimental Investigations on Solid Desiccant Cooling System
Experimental Investigations on Solid Desiccant Cooling System
ijtsrd
 
Ijmet 10 01_122
Ijmet 10 01_122Ijmet 10 01_122
Ijmet 10 01_122
IAEME Publication
 
Comparison of the Performances of NH3-H20 and Libr-H2O Vapour Absorption Refr...
Comparison of the Performances of NH3-H20 and Libr-H2O Vapour Absorption Refr...Comparison of the Performances of NH3-H20 and Libr-H2O Vapour Absorption Refr...
Comparison of the Performances of NH3-H20 and Libr-H2O Vapour Absorption Refr...
IJERA Editor
 
The use of Cooking Gas as Refrigerant in a Domestic Refrigerator
The use of Cooking Gas as Refrigerant in a Domestic RefrigeratorThe use of Cooking Gas as Refrigerant in a Domestic Refrigerator
The use of Cooking Gas as Refrigerant in a Domestic Refrigerator
IJERA Editor
 

Similaire à W04506124128 (20)

Numerical Investigation of Air Cooled Condensers using Different Refrigerants
Numerical Investigation of Air Cooled Condensers using Different RefrigerantsNumerical Investigation of Air Cooled Condensers using Different Refrigerants
Numerical Investigation of Air Cooled Condensers using Different Refrigerants
 
To study the behaviour of nanorefrigerant in vapour compression cycle a review
To study the behaviour of nanorefrigerant in vapour compression cycle  a reviewTo study the behaviour of nanorefrigerant in vapour compression cycle  a review
To study the behaviour of nanorefrigerant in vapour compression cycle a review
 
A Review Paper on Design of Generator in Vapour Absorption Refrigeration System
A Review Paper on Design of Generator in Vapour Absorption Refrigeration SystemA Review Paper on Design of Generator in Vapour Absorption Refrigeration System
A Review Paper on Design of Generator in Vapour Absorption Refrigeration System
 
To study the application of nanorefrigerant in refrigeration system a review
To study the application of nanorefrigerant in refrigeration system a reviewTo study the application of nanorefrigerant in refrigeration system a review
To study the application of nanorefrigerant in refrigeration system a review
 
First law thermal performance improvement of vapour compression refrigeration...
First law thermal performance improvement of vapour compression refrigeration...First law thermal performance improvement of vapour compression refrigeration...
First law thermal performance improvement of vapour compression refrigeration...
 
Performance Evaluation of Domestic Refrigerator Using Eco-Friendly Refrigeran...
Performance Evaluation of Domestic Refrigerator Using Eco-Friendly Refrigeran...Performance Evaluation of Domestic Refrigerator Using Eco-Friendly Refrigeran...
Performance Evaluation of Domestic Refrigerator Using Eco-Friendly Refrigeran...
 
Design of waste heat driven vapour adsorption cooling system for vehicle air ...
Design of waste heat driven vapour adsorption cooling system for vehicle air ...Design of waste heat driven vapour adsorption cooling system for vehicle air ...
Design of waste heat driven vapour adsorption cooling system for vehicle air ...
 
Experimental Investigations on Solid Desiccant Cooling System
Experimental Investigations on Solid Desiccant Cooling SystemExperimental Investigations on Solid Desiccant Cooling System
Experimental Investigations on Solid Desiccant Cooling System
 
W04405127131
W04405127131W04405127131
W04405127131
 
IJREI_A thermodynamic analysis of ejector type vapour refrigeration system us...
IJREI_A thermodynamic analysis of ejector type vapour refrigeration system us...IJREI_A thermodynamic analysis of ejector type vapour refrigeration system us...
IJREI_A thermodynamic analysis of ejector type vapour refrigeration system us...
 
Ijmet 10 01_122
Ijmet 10 01_122Ijmet 10 01_122
Ijmet 10 01_122
 
Modeling of variable speed compressor vapour compression refrigeration system...
Modeling of variable speed compressor vapour compression refrigeration system...Modeling of variable speed compressor vapour compression refrigeration system...
Modeling of variable speed compressor vapour compression refrigeration system...
 
IJREI_Thermodynamic study of R134a in Vapour Compression Refrigeration System...
IJREI_Thermodynamic study of R134a in Vapour Compression Refrigeration System...IJREI_Thermodynamic study of R134a in Vapour Compression Refrigeration System...
IJREI_Thermodynamic study of R134a in Vapour Compression Refrigeration System...
 
Comparison of the Performances of NH3-H20 and Libr-H2O Vapour Absorption Refr...
Comparison of the Performances of NH3-H20 and Libr-H2O Vapour Absorption Refr...Comparison of the Performances of NH3-H20 and Libr-H2O Vapour Absorption Refr...
Comparison of the Performances of NH3-H20 and Libr-H2O Vapour Absorption Refr...
 
Optimization through Mathematical Modelling of Irreversibility and Other Para...
Optimization through Mathematical Modelling of Irreversibility and Other Para...Optimization through Mathematical Modelling of Irreversibility and Other Para...
Optimization through Mathematical Modelling of Irreversibility and Other Para...
 
IRJET- R134a Refrigerant in Vapour Compression Cycle: A Review Paper
IRJET-  	  R134a Refrigerant in Vapour Compression Cycle: A Review PaperIRJET-  	  R134a Refrigerant in Vapour Compression Cycle: A Review Paper
IRJET- R134a Refrigerant in Vapour Compression Cycle: A Review Paper
 
IRJET- Controlling A Multi-Evaporator Refrigeration System that Uses Cuo/R134...
IRJET- Controlling A Multi-Evaporator Refrigeration System that Uses Cuo/R134...IRJET- Controlling A Multi-Evaporator Refrigeration System that Uses Cuo/R134...
IRJET- Controlling A Multi-Evaporator Refrigeration System that Uses Cuo/R134...
 
A REVIEW PAPER ON ANALYSIS OF AUTOMOBILE RADIATOR
A REVIEW PAPER ON ANALYSIS OF AUTOMOBILE RADIATORA REVIEW PAPER ON ANALYSIS OF AUTOMOBILE RADIATOR
A REVIEW PAPER ON ANALYSIS OF AUTOMOBILE RADIATOR
 
The use of Cooking Gas as Refrigerant in a Domestic Refrigerator
The use of Cooking Gas as Refrigerant in a Domestic RefrigeratorThe use of Cooking Gas as Refrigerant in a Domestic Refrigerator
The use of Cooking Gas as Refrigerant in a Domestic Refrigerator
 
IRJET- Comparative Analysis of the Performance of R22 with its Alternative ...
IRJET- 	 Comparative Analysis of the Performance of R22 with its Alternative ...IRJET- 	 Comparative Analysis of the Performance of R22 with its Alternative ...
IRJET- Comparative Analysis of the Performance of R22 with its Alternative ...
 

Dernier

+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...
+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...
+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...
?#DUbAI#??##{{(☎️+971_581248768%)**%*]'#abortion pills for sale in dubai@
 
Why Teams call analytics are critical to your entire business
Why Teams call analytics are critical to your entire businessWhy Teams call analytics are critical to your entire business
Why Teams call analytics are critical to your entire business
panagenda
 

Dernier (20)

+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...
+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...
+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...
 
AWS Community Day CPH - Three problems of Terraform
AWS Community Day CPH - Three problems of TerraformAWS Community Day CPH - Three problems of Terraform
AWS Community Day CPH - Three problems of Terraform
 
Why Teams call analytics are critical to your entire business
Why Teams call analytics are critical to your entire businessWhy Teams call analytics are critical to your entire business
Why Teams call analytics are critical to your entire business
 
Exploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone ProcessorsExploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone Processors
 
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
 
Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...
Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...
Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...
 
A Year of the Servo Reboot: Where Are We Now?
A Year of the Servo Reboot: Where Are We Now?A Year of the Servo Reboot: Where Are We Now?
A Year of the Servo Reboot: Where Are We Now?
 
TrustArc Webinar - Stay Ahead of US State Data Privacy Law Developments
TrustArc Webinar - Stay Ahead of US State Data Privacy Law DevelopmentsTrustArc Webinar - Stay Ahead of US State Data Privacy Law Developments
TrustArc Webinar - Stay Ahead of US State Data Privacy Law Developments
 
Apidays Singapore 2024 - Modernizing Securities Finance by Madhu Subbu
Apidays Singapore 2024 - Modernizing Securities Finance by Madhu SubbuApidays Singapore 2024 - Modernizing Securities Finance by Madhu Subbu
Apidays Singapore 2024 - Modernizing Securities Finance by Madhu Subbu
 
presentation ICT roal in 21st century education
presentation ICT roal in 21st century educationpresentation ICT roal in 21st century education
presentation ICT roal in 21st century education
 
Apidays Singapore 2024 - Scalable LLM APIs for AI and Generative AI Applicati...
Apidays Singapore 2024 - Scalable LLM APIs for AI and Generative AI Applicati...Apidays Singapore 2024 - Scalable LLM APIs for AI and Generative AI Applicati...
Apidays Singapore 2024 - Scalable LLM APIs for AI and Generative AI Applicati...
 
EMPOWERMENT TECHNOLOGY GRADE 11 QUARTER 2 REVIEWER
EMPOWERMENT TECHNOLOGY GRADE 11 QUARTER 2 REVIEWEREMPOWERMENT TECHNOLOGY GRADE 11 QUARTER 2 REVIEWER
EMPOWERMENT TECHNOLOGY GRADE 11 QUARTER 2 REVIEWER
 
Ransomware_Q4_2023. The report. [EN].pdf
Ransomware_Q4_2023. The report. [EN].pdfRansomware_Q4_2023. The report. [EN].pdf
Ransomware_Q4_2023. The report. [EN].pdf
 
AXA XL - Insurer Innovation Award Americas 2024
AXA XL - Insurer Innovation Award Americas 2024AXA XL - Insurer Innovation Award Americas 2024
AXA XL - Insurer Innovation Award Americas 2024
 
Strategies for Landing an Oracle DBA Job as a Fresher
Strategies for Landing an Oracle DBA Job as a FresherStrategies for Landing an Oracle DBA Job as a Fresher
Strategies for Landing an Oracle DBA Job as a Fresher
 
Boost Fertility New Invention Ups Success Rates.pdf
Boost Fertility New Invention Ups Success Rates.pdfBoost Fertility New Invention Ups Success Rates.pdf
Boost Fertility New Invention Ups Success Rates.pdf
 
Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024
 
ICT role in 21st century education and its challenges
ICT role in 21st century education and its challengesICT role in 21st century education and its challenges
ICT role in 21st century education and its challenges
 
ProductAnonymous-April2024-WinProductDiscovery-MelissaKlemke
ProductAnonymous-April2024-WinProductDiscovery-MelissaKlemkeProductAnonymous-April2024-WinProductDiscovery-MelissaKlemke
ProductAnonymous-April2024-WinProductDiscovery-MelissaKlemke
 
Artificial Intelligence Chap.5 : Uncertainty
Artificial Intelligence Chap.5 : UncertaintyArtificial Intelligence Chap.5 : Uncertainty
Artificial Intelligence Chap.5 : Uncertainty
 

W04506124128

  • 1. Mr. Manish G. Vasava et al Int. Journal of Engineering Research and Applications www.ijera.com ISSN : 2248-9622, Vol. 4, Issue 5( Version 6), May 2014, pp.124-128 www.ijera.com 124 | P a g e Exergy Analysis of a Chilling Plant – A Review Mr. Manish G. Vasava , Dr. Neeraj K. Chavda**  PG Student and corresponding author, ** Associate Professor. * ** Mechanical Engineering Department, ADIT Engineering College, Vallabh Vidhyanagar, Anand, Gujarat, ABSTRACT Exergy analysis is widely used in the design, simulation and performance analysis of various types of engineering applications in comparison with energy analysis. Energy analysis presents only quantities results while exergy analysis presents qualitative results about actual energy consumption. This paper emphasizes review of open literature related to the application of exergy analysis in various engineering application since its development. It has been found that application of exergy analysis in vapour compression refrigeration system has been increased in last decade only. Keywords – Energy, Exergy, Exergy Analysis, Vapour Compression Refrigeration System, Chilling Plant I. INTRODUCTION The term Exergy was published for the first time by Rant in 1956, and refers to the Greek words ex (external) and ergos (work). Another term describing the same is Available Energy or simply Availability. The term Exergy is related to Ideal Work and Exergy Losses relate to Lost Work. Recently, exergy analysis method has been widely used in the design, simulation and performance assessment of various types of systems for identifying losses and in-efficiencies. Exergy is defined as the maximum work that may be achieved by bringing a system into equilibrium with its environment. First law of thermodynamic only deals with the quality of energy, while exergy deals with both quality and quantity. Every system not in equilibrium with its environment has some quantity of exergy, while a system that is in equilibrium with its environment has, by definition, zero exergy since it has no ability to do work with respect to its environment. A chilling Plant works on VCRS that cools Air/Water, creating a more comfortable environment. Chillers are also used to provide process cooling to equipment in an effort to maximize productivity. Chillers circulate chilled water to process unit in order to transfer heat from process to water. This water then returns to the evaporator side of the chiller where the heat is passed from the water to a liquid refrigerant. The refrigerant leaves the evaporator as a cold vapor and enters the compressor where it is compressed into a hot vapor. Upon leaving the compressor, the vapor enters the condenser side of the chiller where heat is transferred from the refrigerant to the air side of the condenser where it is circulated to an open surrounding environment for the final removal of heat. II. LITERATURE REVIEW The detailed review of literature related to the inception, development, and various application of exergy analysis has been carried by Enrico S. et. al.[1]. The review is divided into following sub groups. (1) Conceptual literature in line with Exergy. (2) Inception of “Exergy” (3) Development of Exergy (4) Expertise phase of Exergy (5) Application of exergy analysis in various fields. Number of literatures published in the sub group number 1 to 4 is presented in Table 1.1 while the application of exergy analysis in various engineering field is tabulated in Table 1.2. Sub Group Duration of Year Number of Research Papers Published Conceptual Literature in line of Exergy 1824-1952 33 Inception of Exergy 1953 1 Development of Exergy analysis 1954-1970 71 Expertise Phase of Exergy After 1970 292 Table 1.1 Development Scenario of Exergy RESEARCH ARTICLE OPEN ACCESS
  • 2. Mr. Manish G. Vasava et al Int. Journal of Engineering Research and Applications www.ijera.com ISSN : 2248-9622, Vol. 4, Issue 5( Version 6), May 2014, pp.124-128 www.ijera.com 125 | P a g e Type of Engineering Applications of exergy analysis Number of Research Papers Published 1931-1960 1961-1980 1981-2000 2001-2010 2011-2014 Steam Power Cycles 2 4 5 5 - Gas Turbine Cycles - 4 6 9 - Renewable Energy Cycles - - 4 1 - Combined & Cogeneration Cycles - 9 20 11 - Heat exchangers & Heat Networking 1 5 18 8 - Cryogenics 4 15 14 12 - Chemical Processes 3 10 15 11 - Distillation & Desalination 1 6 15 8 - Industrial & Agricultural Systems 2 6 22 8 - Environmental Appli. - 8 21 12 - VCRS - - - 5 8 Table 1.2 Application of Exergy Analysis From Table 1.1, it is found that, exergy analysis has grown from child to adult from 1824 to till date and scientists and researchers are enjoying the fruitful results of expertise in the field of Exergy analysis. From Table 1.2, it is clear that, since its development, exergy analysis has been widely used in most of the engineering applications. The study of exergy analysis related to VCRS has been increased in last decade only. Other literatures related exergy analysis is presented in the following section. Amir V et al. [2] have studied on exergy concept and it’s characteristic. Here author had introduced the detail information about exergy and also describe about exergy losses, entropy and energy in thermodynamic systems. Here, author had define dead state, surroundings, immediate surroundings, environment and different forms of exergy. In this paper the concept of exergy and its characteristic and application in various fields has been discussed. And different forms of exergy have been derived. Also a brief comparison between energy and exergy analysis has been done. Yunus A et al. [3] describe that At present day also human ,tend to judge things on the basis of their quantity rather than quality, and perceive bigger things as being better, stronger, and more competitive. Assessments made on the basis of quantity only (the first law) may be grossly inadequate and misleading. When two companies merge, for example, we expect the joint company to be more productive and more dominant in a competitive world, and when two states or countries merge, we expect the new union to be stronger. But experience shows that often this is not the case, confirming the phrase “bigger is not necessarily better”. In thermodynamics, this is analogous to a system with a larger energy content not necessarily having a larger exergy content or work potential. so requirement of exergy analyses to know how effectively useful energy converted into useful work. Aprea C et al. [4] presented the experimental studies of performances of a vapour compression refrigeration plant using as working fluids R22 and its substitute R417A (R125/R134a/R600, 46.6/50/3.4% in mass). This type of plant is applied to a commercially available cold store, generally adopted for preservation of foodstuff. The experimental analysis had allowed the determination of the best energetic performances of R22 in comparison with those of R417A in terms of the coefficient of performance, exergetic efficiency, exergy destroyed in the plant components and other variables characterizing the refrigeration plant performance. Guiyin F et al. [5] has investigated Exergy analysis of a dual mode refrigeration system for ice storage air conditioning. Here, dual mode refrigeration system consists of conventional air conditioning operation unit and the ice storage operation unit. The refrigeration system studied is a dual-mode refrigeration cycle process. This indicates that the refrigeration system operates not only in conventional air conditioning mode during daytime, but also in ice storage mode during nighttime. . The results show that the exergy efficiency of the refrigeration system in ice storage operating mode is 17.63% lower than that of the refrigeration system in air conditioning operating mode. Akhilesh A et al.[6] presented a detailed exergy analysis of an actual vapour compression refrigeration (VCR) cycle. A computational model has been developed for computing coefficient of performance (COP), exergy destruction, exergetic efficiency and efficiency defects for R502, R404A and R507A. The present investigation has been done for evaporator and condenser temperatures in the range of 50 ℃to 0℃and 40 ℃ to 55℃, respectively. The results indicate that R507A is a better substitute to R502 than R404A. The efficiency defect in condenser is highest, and lowest in liquid vapour heat exchanger for the refrigerants considered. In this communication, an extensive energy and exergy analysis of R502, R404A and R507A in an actual vapour compression cycle have been presented. The conclusions of the present analysis are summarized below.  COP and exergetic efficiency for R507A are better than that for R404A at condenser
  • 3. Mr. Manish G. Vasava et al Int. Journal of Engineering Research and Applications www.ijera.com ISSN : 2248-9622, Vol. 4, Issue 5( Version 6), May 2014, pp.124-128 www.ijera.com 126 | P a g e temperatures between 40O C and 55O C. However, both refrigerants show 4–17% lower value of COP and exergetic efficiency in comparison to R502 for the condenser temperatures between 40O C and 55O C.  The worst component from the viewpoint of irreversibility or exergy destruction is condenser followed by compressor, throttle valve and evaporator, respectively. The most efficient component is liquid vapour heat exchanger. The summation of efficiency defects for R507A is less than R404A for condenser temperatures between 40 ℃ and 55℃. Rahim K.J et al. [7] had submitted Energy, Exergy and Thermo economics Analysis of Water Chiller Cooler for Gas Turbines Intake Air Cooling. In the present study, the performance of a cooling system that consists of a chilled water external loop coupled to the GT entrance is investigated. An objective of the present study is to assess the importance of using a coupled thermo-economics analysis in the selections of the cooling system and operation parameters. In the present study, the profitability resulting from cooling the intake air is calculated for electricity rates between 0.07 and 0.15 $/kWh and a payback period of 3 years. Cash flow analysis of the GT power plant in the city of Yanbu shows a potential for increasing the output power of the plant and increased revenues. Bukola O.B [8] presents experimental results of investigation of effects of sub-cooling on the performance of four ozone-friendly alternative refrigerants (R32, R152a, R143a, and R134a) in a domestic refrigeration system. The study was performed using a system designed for R12 with the aim of finding a drop-in replacement for the refrigerant. Average refrigeration capacities of R152a and R134a were 2.6% higher and 3.4% lower than that of R12, respectively, while average capacities of R143a and R32 were 22.4% and 31.3% lower than that of R12, respectively. Also, the results obtained showed that as the degree of sub-cooling increases, the pressure ratio reduces, while both the refrigerant mass flow rate and the coefficient of performance (COP) increase. The COPs of R152a and R134a obtained at various degrees of sub-cooling are close to that of R12, while significant deviations in COPs of R32 and R143a were obtained when compared with that of R12. The overall assessment of the results showed that R152a and R134a refrigerants had the most similar performance characteristics to R12, with R152a having a slightly better performance, while the performances of R32 and R143a were significantly lower than that of R12. Ust Y et al. [9] has analyzed exegetic performance coefficient criterion for a vapour compression refrigeration system for different refrigerant. This analysis has been carried out using the refrigerants R32, R410A, R143A, R404A and R125. The COP at maximum EPC condition for the refrigerant R125 is bigger than the other refrigerants studied in this paper. According to the results, the refrigerant R32 shows the best performance in terms of EPC among the other refrigerants (R410A, R143A, R404A and R125). Ahamed J.U et al. [10] worked on exergy analysis in various usable sectors where vapour compression refrigeration systems are used. Exergy losses, exergy efficiency, second law efficiency and irreversibility of the system components as well as of the whole system are measured. In the vapour compression system, R134a, R290 and R600a are considered as refrigerants. Exergy parameters in the compressor, evaporator, condenser and expansion devices are calculated and analyzed. Exergy losses depend on evaporator temperatures, condensing temperature, refrigerants and ambient temperature. Most of the exergy losses occur in the condenser. Expansion device has the lowest losses. Exergy parameters are compared for different operating temperatures. It is found that hydrocarbons (R600a) have 50% higher exergy efficiency than R134a. Mixture of hydrocarbons also shows the best performance based on the exergy analysis. After the successful investigation of the HC as a refrigerant on the basis of performance, the following conclusions can be drawn based on the results obtained:  Exergy loss for butane and isobutene are less than that of the refrigerant R134a in the present test unit. In the higher evaporating temperature exergy loss is decreased for all refrigerants.  Exergy efficiency is also higher for butane compared to that of isobutene and R-134a as refrigerants.  Exergy loss in the compressor is higher than that in the other parts of the system i.e. up to 69% of the total exergy loss occurs in the compressor.  The co-efficient of performances for butane and isobutene are comparable with that of R134a.  Exergy loss increases with the increase of condenser temperature. Its higher for butane compared that of R134a and iso butane. Camelia S et al. [11] work on a comparative analysis of the refrigerant effect on the operation and performances of a one stage vapour compression refrigeration system. the paper is to present and propose an analysis model for comparing the operation of a VCR System with different refrigerants, from performances point of view and from limitations in terms of compression ratio. This paper presents a comparative analysis of five refrigerants working in a one stage VCRS with sub cooling and superheating. Based on the exergy analysis, exergy destruction rates were estimated for each component of the system in a comparative
  • 4. Mr. Manish G. Vasava et al Int. Journal of Engineering Research and Applications www.ijera.com ISSN : 2248-9622, Vol. 4, Issue 5( Version 6), May 2014, pp.124-128 www.ijera.com 127 | P a g e manner for five refrigerants (R22, R134a, R717, R507a, R404a) proving a different behavior and thus bringing important information about system optimization when working with a specific refrigerant. Vaibhav J et al. [12] investigated thermodynamic analysis of R134a, R410a, R407c and M20 in comparison to R22. In the present research study a refrigerant property dependent thermodynamic model of a simple reciprocating system, which can simulate the performance of actual system as closely as possible, has been used to compare the characteristics of various refrigerants. From the comparison of performance parameters it can be concluded that R407C is a potential HFC refrigerant replacement for new and existing systems presently using R22 with minimum investment and efforts. Jyoti S et al. [13] Presented a theoretical performance study of a vapour compression refrigeration system with refrigerants R-407C and R- 410A. A computational model based on energy and exergy analysis is presented for the investigation. The exergetic efficiency of R-407C is 2.5-5.1% higher than R410A for considered range of dead state temperatures. A theoretical investigation showed that better performances of R-407C in comparisons with R-410A. Ratnesh S et al.[14] investigated a domestic refrigerator designed to work with R-134a to assess the possibility of using a mixture of propane and isobutene. The performance of the refrigerator using azotropic mixture as refrigerants was investigated and compared with the performance of refrigerator when R-134, R12, R22, R290, R600a is used as a refrigerant. It has been found from the calculations that mixture of propane and isobutene (mint gas) is producing better results than other refrigerants. R.S.Mishra [15] presents methods for improving first law and second law efficiency have using new refrigerants: R134a, R290, R600a, R1234yf, R502,R404a and R152a and R12, R502. For exergy and energy analysis six type of vapour compression refrigeration system have been considered with using eco-friendly refrigerants with multi-evaporators, multiple compressors and multiple expansion valve with parallel and series with intrercooling and flash chambers. Numerical computational model have been carried out for the system. Performance of the system using R600 and R152a nearly matching same values under the accuracy of 5 % can be used in the system and difficulties detected with R600, R290 and R600a having flammable problems therefore safety measures are required using these refrigerants, therefore R134a is recommended for practical and commercial applications. Naushad A.A et al. [16] has conducted theoretical exergy analysis of HFO-1234yf and HFO-1234ze, both ultra low Global Warming Potential(GWP) and zero Ozone Depletion Potential(ODP) refrigerants in simple vapour compression refrigeration system and comparison of their results with HFC-134a refrigerant as possible alternative replacements in Automotive air-conditioning and stationary refrigeration is presented. Results obtained indicate that HFO-1234yf and HFO-1234ze can be good replacement of R-134a. III. CONCLUSION In this paper, review of exergy analysis method has been studied since then when the word “exergy” was not in use. From the review it is clear that application of exergy in various fields are on its peak. The literature related to exergy analysis of VCRS is available since last decade only and particular for chilling plant is rare. Thus, it seems that there is scope of application of exergy analysis in chilling plant for analyzing its performance. REFERENCES Journal Papers [1] Enrico S and Goran W,” A brief Commented History of Exergy From the Beginnings to 2004 “, Int. J. of Thermodynamics, March 2007, Vol. 10 (No. 1), pp. 1-26. [2] Amir V, Aminreza N, Mohammad G and Sadegh V,” Exergy Concept and its Characteristic”, International journal of Multidisciplinary Sciences and Engineering ,July 2011, Vol. 2, No. 4. [3] Yunus A, Byard W and Ibrahim D, “ Is bigger thermodynamically better? Exergy”, International Journal 2 , 2002, 62-68. [4] Aprea C and Renno C, “Experimental comparison of R22 with R417A performance in a vapour compression refrigeration plant subjected to a cold store”,Energy conversion and Management 45, 2004. [5] Guiyin F , Lin X, Fan Y and Hui L,” Exergy Analysis of a Dual Mode Refrigeration System for Ice Storage air conditioning”, International Journal on Architectural Science, 2005,Volume 6, Number 1, p.1-6. [6] Akhilesh A and kaushik S, “ Theoretical analysis of a vapour compression system with R502, R404a and R507a”, International journal of refrigeration 31 ,2008, 998-1005. [7] Rahim K. J, Majed M. A and Galal M Z “Energy, Exergy and Thermoeconomics Analysis of Water Chiller Cooler for Gas Turbines Intake Air Cooling”, Intechopen, 2009.
  • 5. Mr. Manish G. Vasava et al Int. Journal of Engineering Research and Applications www.ijera.com ISSN : 2248-9622, Vol. 4, Issue 5( Version 6), May 2014, pp.124-128 www.ijera.com 128 | P a g e [8] Bukola O B,” Exergetic performance of a domestic refrigerator using R12 and its alternative refrigerants”, Journal of Engineering Science and Technology ,2010,Vol. 5, No. 4. [9] Ust, Y, Akkaya A V and Safa A, “Analysis of a vapour compression refrigeration system via exergetic performance coefficient criterion”, Journal of the Energy Institute, 2011. [10] Ahamed J U, Saidur R, Masjuki H H and Mehjabin S , “ Prospect of Hydrocarbon uses based on exergy analysis in the vapour compression refrigeration system”, International Journal of Renewable Energy Research I,2011. [11] Camelia S, Adina G, Dorin S and Alexandru D, “Exergy analysis and refrigerant effect on the operation and performance limits of a one stage vapour compression refrigeration system”, Termotehnica,1/2011. [12] Vaibhav J, Kachhwaha S S and Mishra R S , “Comparative performance study of vapour compression refrigeration system with R22/R134a/R410A/R407C/M20”, International Journal of Energy and Environment,2011, Volume 2, Issue 2. [13] Jyoti S and R.C. Gupta , “Exergy Analysis of Vapour Compression Refrigeration System with Using R-407C and R-410A”, International Journal of Engineering Research & Technology (IJERT),September-2012, Vol. 1. [14] Ratnesh S and Akhilesh L , “Analysis of Ecofriendly Refrigerant with commonly used Refrigerant in domestic refrigerators “ ,Global J. of Engg. & Appl. Sciences, 2012. [15] R S Mishra , “Irreversibility analysis of multi-evaporators vapour compression refrigeration systems using new and refrigerants:R134a, R290, R600, R600a, R1234yf, R502, R404a and R152a and R12, R502”,International journal of advance research and innovation,2013, volume 2,188-200. [16] Naushad A. A, Bipin Y, and Jitendra K, “Theoretical Exergy Analysis of HFO- 1234yf and HFO-1234ze as an Alternative Replacement of HFC-134a in Simple Vapour Compression Refrigeration System”, International Journal of Scientific & Engineering Research,, Issue 8, August- 2013, Volume 4.