Waterside
Energy Recovery
Requirements, Design and
Application


            Mick Schwedler, PE
            manager
            Trane
            applications engineering
              © 2011 Ingersoll Rand
reasons to use
Energy Recovery
 Required by code or standard
 Availability of simultaneous heating
  and cooling loads
 Economically justified
    Reduces heating load
    Reduces ancillary power

 Environmentally responsible
    Reduces emissions
    Eligible for “green” benefits (energy, water
     usage)
ASHRAE 90.1-2010 (since 1999)
Waterside Energy Recovery
IF …   Facility operates 24 hours per day
         Heat rejection exceeds 6 million Btu/hr
          (~ 450 tons)
           Design service water heating load
            exceeds 1 million Btu/hr

THEN Required energy recovery is
     (smaller of):
       60% of design heat rejection

           Preheating water to 85°F
types of
Heat-Recovery Chillers
 Single condenser (“bundle”)

 Dual condenser
                                           heat-
                         standard
   Equally sized       condenser   =    recovery
                                        condenser
    bundles

 Auxiliary condenser
                                           heat-
   Unequally sized      standard
                        condenser   >    recovery
                                        condenser
    bundles
heat-recovery chillers
Single Condenser



helical-rotary (screw)
compressor
                                       scroll compressor




                         centrifugal compressor
heat-recovery chillers
Dual Condenser
heat-recovery         leaving      capacity         chiller
condenser             water        control?         efficiency
Full capacity         hot          yes              decreases
Partial capacity      warm         no               increases



                heat-recovery
                   condenser

                     standard
                    condenser

                      evaporator
                                        water-cooled chiller with
                                        centrifugal compressor
heat-recovery chillers
Comparison of Options
                     Chiller condenser option
Characteristic       Dual         Auxiliary     “Heat pump”
Configuration        Second,      Second,       No extra
                     full-size    smaller       condenser
                     condenser    condenser
Application          Large        Preheating    Large base-
                     heating      loads         heating loads
                     loads                      or continuous
                                                operation
Leaving water        Hot          Warm          Hot
Capacity control?    Yes          No            Yes
Chiller efficiency   Decreases    Increases     Acceptable
variable air volume
Tempering Supply Air
When required supply/primary airflow is
less than minimum setting:
     Reduce primary airflow to minimum
     Let space temperature drift downward
     Add heat to avoid overcooling
        105°F (40.6°C) water often is sufficient




  Supply air is always dehumidified
waterside heat recovery
Temperatures
Service-water      85°F to 95°F
preheating      (29.4°C to 35°C)


Space heating     105°F to 110F
                (40.6°C to 43.3C)
                 source: 2008 ASHRAE Systems
                   and Equipment Handbook
tempering VAV supply air
Heating Coil Selection
selection parameter           1-row coil     2-row coil
Entering water                113°F          105°F
Coil flow rate                4.33 gpm       1.75 gpm
Fluid delta-T                6.02°F          14.91°F
Coil fluid pressure drop      10.3 ft H2O    0.21 ft H2O
Air pressure drop:
    design cooling airflow   0.45 in. wg     0.79 in. wg
    minimum airflow (est)    0.04 in. wg     0.07 in. wg
Leaving-coil (primary) air    75°F           75°F


                                     Effectively balances
                             heat-recovery temperatures
                              and system pressure drops
waterside heat recovery
Effect on Chillers
 Compressor work is proportional
  to lift
    “Lift” is pressure difference between evaporator
     and condenser
    Warmer condenser water (for heat recovery)
     raises condenser pressure

 Changes in lift affect different compressors
  differently
    Positive displacement
    Centrifugal (full load vs. part load)
positive-displacement water chiller
Refrigeration Cycle

                                   heat recovery
                        5           condenser
                                                           2
                                 4             3
    pressure




               expansion          liquid/vapor
                                                       compressor
                  device            separator


                    7                              1
                                evaporator
                            6



                                enthalpy
positive-displacement water chiller
   Capacity
                      100                                                compressor
                                                                         type:

                       80                                                   scroll
chiller capacity, %




                                                                            screw

                       60


                       40


                       20


                        0
                            0°       10°       20°       30°       40°
                            temperature rise (leaving-condenser water)
positive-displacement water chiller
   Efficiency
                           100                                                compressor
                                                                              type:
power increase, % kW/ton




                            80                                                   scroll
                                                                                 screw (S)
                                                                                 screw (M)
                            60
                                                                                 screw (L)

                            40


                            20


                            0
                                 0°       10°       20°       30°       40°
                                 temperature rise (leaving-condenser water)
centrifugal chiller performance
   Power Increase
                                           Heat recovery
                           40             Chiller 85-105 F               32
power increase, % kW/ton




                                                                               impeller diameter, inches
                                                     compressor
                                                        change
                           30
                                                                          30
                                 power increase

                           20


                                                                          28
                           10
                                                 impeller diameter


                            0                                             26
                                85   87    89   91   93   95   97    99
                                     condenser water temperature, °F
centrifugal chiller comparison
Efficiency
                Operating mode
Chiller type    Cooling                Heat recovery

Cooling only    0.57 kW/ton            Not applicable
                (6.2 COP)

Heat recovery   0.60 kW/ton            0.69 kW/ton
                (5.9 COP)              (5.1 COP)

                Entering to leaving water temperatures:
Evaporator      54°F to 44°F           54°F to 44°F
                (12.2°C to 6.7°C)      (12.2°C to 6.7°C)
Condenser       85°F to 95°F           85°F to 105°F
                (29.4°C to 35.0°C)     (29.4°C to 40.6°C)
heat-recovery chiller control
Condensing Temperature
                                               unloading with constant
  % maximum pressure differential




                                        leaving hot-water temperature

                                                            C
                                                                                    A




                                                   unloading with constant
                                    B              entering hot-water temperature



                                                      % load
heat-recovery chiller control
Condensing Temperature
Compressor type         Acceptable basis of control
Positive displacement   Entering-condenser water temperature

                        Leaving-condenser water temperature
                        • Provides less capacity
                        • Uses more power

Centrifugal             Entering-condenser water temperature
                        • Reduces likelihood of surge
Energy Recovery Topics
 Airside                    Waterside
    Outdoor air               Requirements
       Types
                               Types
       Requirements
       Operation              System configurations
    Supply air tempering      Operation
       Requirements
       Operation
system configuration
Primary–Secondary

                                            Available heat
 off                                        = 150 × (52.6 – 40)
         52.6°F            40°F             = 1890 MBh

                                            Auxiliary heat required
 750 gpm
                                            = 2000 – 1890
         52.6°F            40°F             = 110 MBh

                  heat-recovery
 300 gpm          chiller                   production
52.6°F                                      (supply)

                       40°F
                                            distribution
                       225 gpm
                                            (demand)
                                     40°F
56°F                              825 gpm
system configuration
Preferential Loading

                                                           Available heat
 off                                                       = 150 × (56 – 40)
         51.2°F            40°F                            = 2400 MBh

                                                           Rejected heat
 750 gpm
                                                           = 2400 – 2000
                                            production
51.2°F                                      (supply)       = 400 MBh

                              40°F
525 gpm                                     distribution
                              225 gpm
                                            (demand)

         56.0°F            40°F

                  heat-recovery
 300 gpm          chiller
                                     40°F
56°F                              825 gpm
system configurations
Sidestream Loading

 off                                                       Available heat
                                                           = 150 × (56 – 42.7)
         50.2°F            40°F                            = 2000 MBh

 900 gpm                                    production     No rejected heat
50.2°F                                      (supply)       No auxiliary heat

51.2°F                        40°F
                                            distribution
                              75 gpm
                                            (demand)

                             42.7°F
         56°F

                  heat-recovery
 300 gpm          chiller
                                     40°F
56°F                              825 gpm
system configurations
Sidestream Loading
Control strategies:
     Satisfy heating requirements
     Maintain leaving-condenser
      water temperature
      (positive-displacement compressors)
system configuration comparison
Heat Available/Required
                       System configuration
                       Primary–
Characteristic         secondary           Preferential   Sidestream
Cooling load:
cooling-only units     393 tons            350 tons       383 tons
heat-recovery unit     157 tons            200 tons       167 tons
Heat-recovery          40°F                40°F           42.7°F
supply temperature
Available heat         1890 MBh            2400 MBh       2000 MBh
Auxiliary heat         110 MBh             –400 MBh*      0 MBh
required
*Surplus recovered heat must be rejected
system configurations
 Variable Primary Flow

                                             Piping heat-recovery chiller
                                             in sidestream position may
                                             simplify control




                           bypass line

      modulating control valve
VFD   for minimum chiller flow


                        heat-recovery
                        chiller
                                         control
                                           valve
system configurations
Distributed Sidestream
Typical application:
     Remote heating requirement
     Chilled water load
     Small chiller (or water-to-water heat pump)


                                                 heating
                                                  load
                         heat-recovery chiller



         chilled water
      supply or return
airside system options
 Load-shedding
 economizer
                                            heat-recovery chiller


                                                                    heating
                                                                     load


                        chilled water
                     supply or return




                                        Control cooling load so
                                         heat rejection equals
                                             heating load
outdoor-air                controller
temperature sensor
airside system options
Loading chiller with
exhaust airstream
                              Water from chiller

               Water to chiller
  EA                                            RA
           C
                                                             EA

                                                     space
                                                     T

       H                  T       C        H
OA                  MA                CA       SA
single condenser
Heat-Recovery Control
                                                         controller
                                                    V1

         cooling
          tower
                                                         heating
                                                                      T1
                                                          load
 V2
                   heat                condenser
              exchanger

              P                P                water-cooled
                          T2                    chiller

 controller                        P
                                       evaporator


                                                         cooling
                                                          load
Dual-Condenser Chillers

heat-recovery
condenser


standard
condenser
piped to cooling tower




                         centrifugal
                         heat-recovery chiller
dual condenser
Heat-Recovery Control
controller
             cooling                         T2
              tower
                                                  P                         heating
     V2                                                    controller        load


                                  standard
                                 condenser                                 T1
                                             heat-
                P                          recovery         P
                                          condenser
                                                                        auxiliary
                                                      water-cooled      heat
                P
                                     evaporator       chiller

                                                                Control based on
                                                                entering-condenser
                                                                water temperature
                       cooling
                        load
Analysis Tools
tool                     application
System Analyzer™         High-level scoping (< 1 hr)

TRACE™ Chiller Plant     Simplified building entries
Analyzer
                         Full analysis of chilled water
                         plant, economic rates

EnergyPlus, HAP, TRACE   Full energy simulation
                         Hour-by-hour calculations of
                         energy consumption, power
                         demand, related costs
Waterside Energy
Recovery Steps
 Simultaneous heating     Place the chiller(s) in
  and cooling loads         the appropriate system
                            location
 Chiller HR capacity =
  Design heat recovery     Design the system with
  load                      the proper connections
                            and controls
 Select lowest
  temperature that         Train the building
  meets requirements        operators

 Select the proper        Operate the system
  chiller type              properly

 Analyze the system
waterside heat recovery
References
From Trane:
 Waterside Heat Recovery in HVAC Systems
 SYS-APM005-EN

 1991 Engineers Newsletter: “Two Good
 Old Ideas Combine to Form One New Great Idea”
 http://www.trane.com/commercial/library/EN20-1.pdf

By others:
 2008 ASHRAE Handbook: HVAC Systems and Equipment
 chapter 8

 2003 ASHRAE Journal: “Energy Efficiency for Semiconductor
 Manufacturing Facilities”
 Ralph M. Cohen, PE (August issue)
waterside heat recovery
References
2008 ASHRAE Handbook: HVAC Systems and Equipment
chapter 8

2003 ASHRAE Journal: “Energy Efficiency for Semiconductor
Manufacturing Facilities”
Ralph M. Cohen, PE (August issue)

Contenu connexe

Tendances

HOW TO CONTROL PRILLING TOWER DUST EMISSION.pdf
HOW TO CONTROL PRILLING TOWER DUST EMISSION.pdfHOW TO CONTROL PRILLING TOWER DUST EMISSION.pdf
HOW TO CONTROL PRILLING TOWER DUST EMISSION.pdf
PremBaboo4
 
Net zero energy neighbourhood.pdf
Net zero energy neighbourhood.pdfNet zero energy neighbourhood.pdf
Net zero energy neighbourhood.pdf
wafa786110
 
Types of ac and humidity control
Types of ac and humidity controlTypes of ac and humidity control
Types of ac and humidity control
Ananth Kumar M
 

Tendances (20)

Ammonia plant GSFC by Vishal Tapiawala
Ammonia plant GSFC by Vishal TapiawalaAmmonia plant GSFC by Vishal Tapiawala
Ammonia plant GSFC by Vishal Tapiawala
 
Air distribution Product
Air distribution ProductAir distribution Product
Air distribution Product
 
HOW TO CONTROL PRILLING TOWER DUST EMISSION.pdf
HOW TO CONTROL PRILLING TOWER DUST EMISSION.pdfHOW TO CONTROL PRILLING TOWER DUST EMISSION.pdf
HOW TO CONTROL PRILLING TOWER DUST EMISSION.pdf
 
Duct system
Duct systemDuct system
Duct system
 
PRESENTATION ON DUCT DESIGN
PRESENTATION ON DUCT DESIGNPRESENTATION ON DUCT DESIGN
PRESENTATION ON DUCT DESIGN
 
Gas Flare Stack Process
Gas Flare Stack ProcessGas Flare Stack Process
Gas Flare Stack Process
 
Ductwork
DuctworkDuctwork
Ductwork
 
Hydrogenation Reactor Run Away Conditions
Hydrogenation Reactor Run Away ConditionsHydrogenation Reactor Run Away Conditions
Hydrogenation Reactor Run Away Conditions
 
Net zero energy neighbourhood.pdf
Net zero energy neighbourhood.pdfNet zero energy neighbourhood.pdf
Net zero energy neighbourhood.pdf
 
Cooling tower
Cooling towerCooling tower
Cooling tower
 
Section 5 multistage separation processes
Section 5   multistage separation processesSection 5   multistage separation processes
Section 5 multistage separation processes
 
Types of ac and humidity control
Types of ac and humidity controlTypes of ac and humidity control
Types of ac and humidity control
 
Amine gas treating
Amine gas treatingAmine gas treating
Amine gas treating
 
Wood_joints.pdf
Wood_joints.pdfWood_joints.pdf
Wood_joints.pdf
 
FYDP Sem 2
FYDP Sem 2FYDP Sem 2
FYDP Sem 2
 
Duct sizing methods and filter types
Duct sizing methods and filter typesDuct sizing methods and filter types
Duct sizing methods and filter types
 
AIR HANDLING UNIT
AIR HANDLING UNITAIR HANDLING UNIT
AIR HANDLING UNIT
 
Airconditioning ppt
Airconditioning pptAirconditioning ppt
Airconditioning ppt
 
flare system design.pdf
flare system design.pdfflare system design.pdf
flare system design.pdf
 
Earth Air Tube Heat Exchanger
Earth Air Tube Heat ExchangerEarth Air Tube Heat Exchanger
Earth Air Tube Heat Exchanger
 

En vedette

Standard 90.1-2010 Update
Standard 90.1-2010 UpdateStandard 90.1-2010 Update
Standard 90.1-2010 Update
Illinois ASHRAE
 

En vedette (20)

YEA ASHRAE Kick-Off Meeting 2011
YEA ASHRAE Kick-Off Meeting 2011YEA ASHRAE Kick-Off Meeting 2011
YEA ASHRAE Kick-Off Meeting 2011
 
Illinois ASHRAE Research Promotion
Illinois ASHRAE Research PromotionIllinois ASHRAE Research Promotion
Illinois ASHRAE Research Promotion
 
Illinois ASHRAE 2011 Technology Awards
Illinois ASHRAE 2011 Technology AwardsIllinois ASHRAE 2011 Technology Awards
Illinois ASHRAE 2011 Technology Awards
 
Chicago Energy Modeling Conference Welcome Address
Chicago Energy Modeling Conference Welcome AddressChicago Energy Modeling Conference Welcome Address
Chicago Energy Modeling Conference Welcome Address
 
Chicago Energy Modeling Conference Key Note
Chicago Energy Modeling Conference Key NoteChicago Energy Modeling Conference Key Note
Chicago Energy Modeling Conference Key Note
 
Nicor Gas Non-Residential Energy Efficiency Programs
Nicor Gas Non-Residential Energy Efficiency ProgramsNicor Gas Non-Residential Energy Efficiency Programs
Nicor Gas Non-Residential Energy Efficiency Programs
 
Building EQ
Building EQBuilding EQ
Building EQ
 
Preliminary Modeling & Life Cycle Costing: Underpinnings of Integrated Design.
Preliminary Modeling & Life Cycle Costing:  Underpinnings of Integrated Design.Preliminary Modeling & Life Cycle Costing:  Underpinnings of Integrated Design.
Preliminary Modeling & Life Cycle Costing: Underpinnings of Integrated Design.
 
Measurement & Verification
Measurement & VerificationMeasurement & Verification
Measurement & Verification
 
Modeling, It's Not Just For Calendars and Energy
Modeling, It's Not Just For Calendars and EnergyModeling, It's Not Just For Calendars and Energy
Modeling, It's Not Just For Calendars and Energy
 
Assessing Your Building Energy Costs: Benefits of Energy Modeling to Owners
Assessing Your Building Energy Costs:  Benefits of Energy Modeling to OwnersAssessing Your Building Energy Costs:  Benefits of Energy Modeling to Owners
Assessing Your Building Energy Costs: Benefits of Energy Modeling to Owners
 
Net Zero Energy Buildings
Net Zero Energy BuildingsNet Zero Energy Buildings
Net Zero Energy Buildings
 
High performance-chilled-water-systems ashrae-chicago
High performance-chilled-water-systems ashrae-chicagoHigh performance-chilled-water-systems ashrae-chicago
High performance-chilled-water-systems ashrae-chicago
 
ASHRAE Standard 100
ASHRAE Standard 100ASHRAE Standard 100
ASHRAE Standard 100
 
Smart Ideas for Your Business
Smart Ideas for Your BusinessSmart Ideas for Your Business
Smart Ideas for Your Business
 
Standard 90.1-2010 Update
Standard 90.1-2010 UpdateStandard 90.1-2010 Update
Standard 90.1-2010 Update
 
ComEd Retro-Commissioning Program
ComEd Retro-Commissioning ProgramComEd Retro-Commissioning Program
ComEd Retro-Commissioning Program
 
Illinois ASHRAE Kick-Off Meeting 2011
Illinois ASHRAE Kick-Off Meeting 2011Illinois ASHRAE Kick-Off Meeting 2011
Illinois ASHRAE Kick-Off Meeting 2011
 
Manual google sketchup and sketchup pro 7 bible
Manual   google sketchup and sketchup pro 7 bibleManual   google sketchup and sketchup pro 7 bible
Manual google sketchup and sketchup pro 7 bible
 
Home Design in SketchUp Pro
Home Design in SketchUp ProHome Design in SketchUp Pro
Home Design in SketchUp Pro
 

Similaire à Waterside energy-recovery hourlong-chicago_ashrae

Floating head pressure
Floating head pressure Floating head pressure
Floating head pressure
Brad Wilkins
 
Load Match Next Generation
Load Match Next GenerationLoad Match Next Generation
Load Match Next Generation
kiakaha
 
Feedwater heaters in thermal power plants
Feedwater heaters in thermal power plantsFeedwater heaters in thermal power plants
Feedwater heaters in thermal power plants
SHIVAJI CHOUDHURY
 
Solar Pumping Station 100 79
Solar Pumping Station 100 79Solar Pumping Station 100 79
Solar Pumping Station 100 79
kiakaha
 
Solar Pumping Station 100 79
Solar Pumping Station 100 79Solar Pumping Station 100 79
Solar Pumping Station 100 79
kiakaha
 
REGENERATIVE FEEDHEATING.pptx
REGENERATIVE FEEDHEATING.pptxREGENERATIVE FEEDHEATING.pptx
REGENERATIVE FEEDHEATING.pptx
ssuser28a1a31
 
Solar Thermal Power Plant 2nd presentaion
Solar Thermal Power Plant 2nd presentaionSolar Thermal Power Plant 2nd presentaion
Solar Thermal Power Plant 2nd presentaion
Sulaiman Dawood Barry
 

Similaire à Waterside energy-recovery hourlong-chicago_ashrae (20)

Janani Enterprises, Coimbatore, Heat Exchanger
Janani Enterprises, Coimbatore, Heat ExchangerJanani Enterprises, Coimbatore, Heat Exchanger
Janani Enterprises, Coimbatore, Heat Exchanger
 
Energy efficiency in Refrigeration Systems
Energy efficiency in Refrigeration SystemsEnergy efficiency in Refrigeration Systems
Energy efficiency in Refrigeration Systems
 
Hvac - presentation (Air conditioning presentation)
Hvac - presentation (Air conditioning presentation) Hvac - presentation (Air conditioning presentation)
Hvac - presentation (Air conditioning presentation)
 
Feb. 2016 webinar_condensate_return_piping
Feb. 2016 webinar_condensate_return_pipingFeb. 2016 webinar_condensate_return_piping
Feb. 2016 webinar_condensate_return_piping
 
Floating head pressure
Floating head pressure Floating head pressure
Floating head pressure
 
Load Match Next Generation
Load Match Next GenerationLoad Match Next Generation
Load Match Next Generation
 
Chillers 16 jlr cn (c)
Chillers 16 jlr cn (c)Chillers 16 jlr cn (c)
Chillers 16 jlr cn (c)
 
01 regenerative feed heating
01 regenerative feed heating01 regenerative feed heating
01 regenerative feed heating
 
Feedwater heaters in thermal power plants
Feedwater heaters in thermal power plantsFeedwater heaters in thermal power plants
Feedwater heaters in thermal power plants
 
Theoretical analysis of the performance of dual pressure condenser in a therm...
Theoretical analysis of the performance of dual pressure condenser in a therm...Theoretical analysis of the performance of dual pressure condenser in a therm...
Theoretical analysis of the performance of dual pressure condenser in a therm...
 
Theoretical analysis of the performance of dual pressure condenser in a therm...
Theoretical analysis of the performance of dual pressure condenser in a therm...Theoretical analysis of the performance of dual pressure condenser in a therm...
Theoretical analysis of the performance of dual pressure condenser in a therm...
 
Solar Pumping Station 100 79
Solar Pumping Station 100 79Solar Pumping Station 100 79
Solar Pumping Station 100 79
 
Solar Pumping Station 100 79
Solar Pumping Station 100 79Solar Pumping Station 100 79
Solar Pumping Station 100 79
 
Presentation 1 Training Slides.pptx
Presentation 1 Training Slides.pptxPresentation 1 Training Slides.pptx
Presentation 1 Training Slides.pptx
 
REGENERATIVE FEEDHEATING.pptx
REGENERATIVE FEEDHEATING.pptxREGENERATIVE FEEDHEATING.pptx
REGENERATIVE FEEDHEATING.pptx
 
Hera Eenergy All Product
Hera Eenergy All ProductHera Eenergy All Product
Hera Eenergy All Product
 
Steam turbine deaerating condenser perforamace improvement
Steam turbine deaerating condenser perforamace improvementSteam turbine deaerating condenser perforamace improvement
Steam turbine deaerating condenser perforamace improvement
 
Ntpc (national thermal power corporation) sipat boiler haxxo24 i~i
Ntpc (national thermal power corporation) sipat boiler haxxo24 i~iNtpc (national thermal power corporation) sipat boiler haxxo24 i~i
Ntpc (national thermal power corporation) sipat boiler haxxo24 i~i
 
Solar Thermal Power Plant 2nd presentaion
Solar Thermal Power Plant 2nd presentaionSolar Thermal Power Plant 2nd presentaion
Solar Thermal Power Plant 2nd presentaion
 
Rac k10655 (hariom)
Rac k10655 (hariom)Rac k10655 (hariom)
Rac k10655 (hariom)
 

Plus de Illinois ASHRAE

Plus de Illinois ASHRAE (12)

ASHRAE Standard 189.1
ASHRAE Standard 189.1ASHRAE Standard 189.1
ASHRAE Standard 189.1
 
Solar Project Risk from the Developer’s Point of View
Solar Project Risk from the Developer’s Point of ViewSolar Project Risk from the Developer’s Point of View
Solar Project Risk from the Developer’s Point of View
 
Illinois Chapter of ASHRAE April 2011 Student Night
Illinois Chapter of ASHRAE April 2011 Student NightIllinois Chapter of ASHRAE April 2011 Student Night
Illinois Chapter of ASHRAE April 2011 Student Night
 
Solar Thermal Cooling
Solar Thermal CoolingSolar Thermal Cooling
Solar Thermal Cooling
 
Life Safety Products
Life Safety ProductsLife Safety Products
Life Safety Products
 
Smoke Control in Buildings
Smoke Control in BuildingsSmoke Control in Buildings
Smoke Control in Buildings
 
Control Dampers
Control DampersControl Dampers
Control Dampers
 
Rock Valley College - Chilled Beams Lesson Learned
Rock Valley College - Chilled Beams Lesson LearnedRock Valley College - Chilled Beams Lesson Learned
Rock Valley College - Chilled Beams Lesson Learned
 
Active Chilled Beam Technology
Active Chilled Beam TechnologyActive Chilled Beam Technology
Active Chilled Beam Technology
 
Enhancing the Healing Environment with Geothermal Energy - Sherman Hospital
Enhancing the Healing Environment with Geothermal Energy - Sherman HospitalEnhancing the Healing Environment with Geothermal Energy - Sherman Hospital
Enhancing the Healing Environment with Geothermal Energy - Sherman Hospital
 
Hydronic Basics / Primary-Secondary Pumping
Hydronic Basics / Primary-Secondary PumpingHydronic Basics / Primary-Secondary Pumping
Hydronic Basics / Primary-Secondary Pumping
 
Natural Gas Rebate Programs
Natural Gas Rebate ProgramsNatural Gas Rebate Programs
Natural Gas Rebate Programs
 

Dernier

Salient Features of India constitution especially power and functions
Salient Features of India constitution especially power and functionsSalient Features of India constitution especially power and functions
Salient Features of India constitution especially power and functions
KarakKing
 
The basics of sentences session 3pptx.pptx
The basics of sentences session 3pptx.pptxThe basics of sentences session 3pptx.pptx
The basics of sentences session 3pptx.pptx
heathfieldcps1
 
Jual Obat Aborsi Hongkong ( Asli No.1 ) 085657271886 Obat Penggugur Kandungan...
Jual Obat Aborsi Hongkong ( Asli No.1 ) 085657271886 Obat Penggugur Kandungan...Jual Obat Aborsi Hongkong ( Asli No.1 ) 085657271886 Obat Penggugur Kandungan...
Jual Obat Aborsi Hongkong ( Asli No.1 ) 085657271886 Obat Penggugur Kandungan...
ZurliaSoop
 

Dernier (20)

UGC NET Paper 1 Mathematical Reasoning & Aptitude.pdf
UGC NET Paper 1 Mathematical Reasoning & Aptitude.pdfUGC NET Paper 1 Mathematical Reasoning & Aptitude.pdf
UGC NET Paper 1 Mathematical Reasoning & Aptitude.pdf
 
ICT role in 21st century education and it's challenges.
ICT role in 21st century education and it's challenges.ICT role in 21st century education and it's challenges.
ICT role in 21st century education and it's challenges.
 
Salient Features of India constitution especially power and functions
Salient Features of India constitution especially power and functionsSalient Features of India constitution especially power and functions
Salient Features of India constitution especially power and functions
 
2024-NATIONAL-LEARNING-CAMP-AND-OTHER.pptx
2024-NATIONAL-LEARNING-CAMP-AND-OTHER.pptx2024-NATIONAL-LEARNING-CAMP-AND-OTHER.pptx
2024-NATIONAL-LEARNING-CAMP-AND-OTHER.pptx
 
Micro-Scholarship, What it is, How can it help me.pdf
Micro-Scholarship, What it is, How can it help me.pdfMicro-Scholarship, What it is, How can it help me.pdf
Micro-Scholarship, What it is, How can it help me.pdf
 
Making communications land - Are they received and understood as intended? we...
Making communications land - Are they received and understood as intended? we...Making communications land - Are they received and understood as intended? we...
Making communications land - Are they received and understood as intended? we...
 
The basics of sentences session 3pptx.pptx
The basics of sentences session 3pptx.pptxThe basics of sentences session 3pptx.pptx
The basics of sentences session 3pptx.pptx
 
How to Create and Manage Wizard in Odoo 17
How to Create and Manage Wizard in Odoo 17How to Create and Manage Wizard in Odoo 17
How to Create and Manage Wizard in Odoo 17
 
Understanding Accommodations and Modifications
Understanding  Accommodations and ModificationsUnderstanding  Accommodations and Modifications
Understanding Accommodations and Modifications
 
Graduate Outcomes Presentation Slides - English
Graduate Outcomes Presentation Slides - EnglishGraduate Outcomes Presentation Slides - English
Graduate Outcomes Presentation Slides - English
 
Sociology 101 Demonstration of Learning Exhibit
Sociology 101 Demonstration of Learning ExhibitSociology 101 Demonstration of Learning Exhibit
Sociology 101 Demonstration of Learning Exhibit
 
Python Notes for mca i year students osmania university.docx
Python Notes for mca i year students osmania university.docxPython Notes for mca i year students osmania university.docx
Python Notes for mca i year students osmania university.docx
 
Unit-V; Pricing (Pharma Marketing Management).pptx
Unit-V; Pricing (Pharma Marketing Management).pptxUnit-V; Pricing (Pharma Marketing Management).pptx
Unit-V; Pricing (Pharma Marketing Management).pptx
 
Jual Obat Aborsi Hongkong ( Asli No.1 ) 085657271886 Obat Penggugur Kandungan...
Jual Obat Aborsi Hongkong ( Asli No.1 ) 085657271886 Obat Penggugur Kandungan...Jual Obat Aborsi Hongkong ( Asli No.1 ) 085657271886 Obat Penggugur Kandungan...
Jual Obat Aborsi Hongkong ( Asli No.1 ) 085657271886 Obat Penggugur Kandungan...
 
Food safety_Challenges food safety laboratories_.pdf
Food safety_Challenges food safety laboratories_.pdfFood safety_Challenges food safety laboratories_.pdf
Food safety_Challenges food safety laboratories_.pdf
 
On National Teacher Day, meet the 2024-25 Kenan Fellows
On National Teacher Day, meet the 2024-25 Kenan FellowsOn National Teacher Day, meet the 2024-25 Kenan Fellows
On National Teacher Day, meet the 2024-25 Kenan Fellows
 
Explore beautiful and ugly buildings. Mathematics helps us create beautiful d...
Explore beautiful and ugly buildings. Mathematics helps us create beautiful d...Explore beautiful and ugly buildings. Mathematics helps us create beautiful d...
Explore beautiful and ugly buildings. Mathematics helps us create beautiful d...
 
Key note speaker Neum_Admir Softic_ENG.pdf
Key note speaker Neum_Admir Softic_ENG.pdfKey note speaker Neum_Admir Softic_ENG.pdf
Key note speaker Neum_Admir Softic_ENG.pdf
 
FSB Advising Checklist - Orientation 2024
FSB Advising Checklist - Orientation 2024FSB Advising Checklist - Orientation 2024
FSB Advising Checklist - Orientation 2024
 
How to Give a Domain for a Field in Odoo 17
How to Give a Domain for a Field in Odoo 17How to Give a Domain for a Field in Odoo 17
How to Give a Domain for a Field in Odoo 17
 

Waterside energy-recovery hourlong-chicago_ashrae

  • 1. Waterside Energy Recovery Requirements, Design and Application Mick Schwedler, PE manager Trane applications engineering © 2011 Ingersoll Rand
  • 2. reasons to use Energy Recovery  Required by code or standard  Availability of simultaneous heating and cooling loads  Economically justified  Reduces heating load  Reduces ancillary power  Environmentally responsible  Reduces emissions  Eligible for “green” benefits (energy, water usage)
  • 3. ASHRAE 90.1-2010 (since 1999) Waterside Energy Recovery IF … Facility operates 24 hours per day  Heat rejection exceeds 6 million Btu/hr (~ 450 tons)  Design service water heating load exceeds 1 million Btu/hr THEN Required energy recovery is (smaller of):  60% of design heat rejection  Preheating water to 85°F
  • 4. types of Heat-Recovery Chillers  Single condenser (“bundle”)  Dual condenser heat- standard  Equally sized condenser = recovery condenser bundles  Auxiliary condenser heat-  Unequally sized standard condenser > recovery condenser bundles
  • 5. heat-recovery chillers Single Condenser helical-rotary (screw) compressor scroll compressor centrifugal compressor
  • 6. heat-recovery chillers Dual Condenser heat-recovery leaving capacity chiller condenser water control? efficiency Full capacity hot yes decreases Partial capacity warm no increases heat-recovery condenser standard condenser evaporator water-cooled chiller with centrifugal compressor
  • 7. heat-recovery chillers Comparison of Options Chiller condenser option Characteristic Dual Auxiliary “Heat pump” Configuration Second, Second, No extra full-size smaller condenser condenser condenser Application Large Preheating Large base- heating loads heating loads loads or continuous operation Leaving water Hot Warm Hot Capacity control? Yes No Yes Chiller efficiency Decreases Increases Acceptable
  • 8. variable air volume Tempering Supply Air When required supply/primary airflow is less than minimum setting:  Reduce primary airflow to minimum  Let space temperature drift downward  Add heat to avoid overcooling 105°F (40.6°C) water often is sufficient Supply air is always dehumidified
  • 9. waterside heat recovery Temperatures Service-water 85°F to 95°F preheating (29.4°C to 35°C) Space heating 105°F to 110F (40.6°C to 43.3C) source: 2008 ASHRAE Systems and Equipment Handbook
  • 10. tempering VAV supply air Heating Coil Selection selection parameter 1-row coil 2-row coil Entering water 113°F 105°F Coil flow rate 4.33 gpm 1.75 gpm Fluid delta-T 6.02°F 14.91°F Coil fluid pressure drop 10.3 ft H2O 0.21 ft H2O Air pressure drop: design cooling airflow 0.45 in. wg 0.79 in. wg minimum airflow (est) 0.04 in. wg 0.07 in. wg Leaving-coil (primary) air 75°F 75°F Effectively balances heat-recovery temperatures and system pressure drops
  • 11. waterside heat recovery Effect on Chillers  Compressor work is proportional to lift  “Lift” is pressure difference between evaporator and condenser  Warmer condenser water (for heat recovery) raises condenser pressure  Changes in lift affect different compressors differently  Positive displacement  Centrifugal (full load vs. part load)
  • 12. positive-displacement water chiller Refrigeration Cycle heat recovery 5 condenser 2 4 3 pressure expansion liquid/vapor compressor device separator 7 1 evaporator 6 enthalpy
  • 13. positive-displacement water chiller Capacity 100 compressor type: 80 scroll chiller capacity, % screw 60 40 20 0 0° 10° 20° 30° 40° temperature rise (leaving-condenser water)
  • 14. positive-displacement water chiller Efficiency 100 compressor type: power increase, % kW/ton 80 scroll screw (S) screw (M) 60 screw (L) 40 20 0 0° 10° 20° 30° 40° temperature rise (leaving-condenser water)
  • 15. centrifugal chiller performance Power Increase Heat recovery 40 Chiller 85-105 F 32 power increase, % kW/ton impeller diameter, inches compressor change 30 30 power increase 20 28 10 impeller diameter 0 26 85 87 89 91 93 95 97 99 condenser water temperature, °F
  • 16. centrifugal chiller comparison Efficiency Operating mode Chiller type Cooling Heat recovery Cooling only 0.57 kW/ton Not applicable (6.2 COP) Heat recovery 0.60 kW/ton 0.69 kW/ton (5.9 COP) (5.1 COP) Entering to leaving water temperatures: Evaporator 54°F to 44°F 54°F to 44°F (12.2°C to 6.7°C) (12.2°C to 6.7°C) Condenser 85°F to 95°F 85°F to 105°F (29.4°C to 35.0°C) (29.4°C to 40.6°C)
  • 17. heat-recovery chiller control Condensing Temperature unloading with constant % maximum pressure differential leaving hot-water temperature C A unloading with constant B entering hot-water temperature % load
  • 18. heat-recovery chiller control Condensing Temperature Compressor type Acceptable basis of control Positive displacement Entering-condenser water temperature Leaving-condenser water temperature • Provides less capacity • Uses more power Centrifugal Entering-condenser water temperature • Reduces likelihood of surge
  • 19. Energy Recovery Topics  Airside  Waterside  Outdoor air  Requirements  Types  Types  Requirements  Operation  System configurations  Supply air tempering  Operation  Requirements  Operation
  • 20. system configuration Primary–Secondary Available heat off = 150 × (52.6 – 40) 52.6°F 40°F = 1890 MBh Auxiliary heat required 750 gpm = 2000 – 1890 52.6°F 40°F = 110 MBh heat-recovery 300 gpm chiller production 52.6°F (supply) 40°F distribution 225 gpm (demand) 40°F 56°F 825 gpm
  • 21. system configuration Preferential Loading Available heat off = 150 × (56 – 40) 51.2°F 40°F = 2400 MBh Rejected heat 750 gpm = 2400 – 2000 production 51.2°F (supply) = 400 MBh 40°F 525 gpm distribution 225 gpm (demand) 56.0°F 40°F heat-recovery 300 gpm chiller 40°F 56°F 825 gpm
  • 22. system configurations Sidestream Loading off Available heat = 150 × (56 – 42.7) 50.2°F 40°F = 2000 MBh 900 gpm production No rejected heat 50.2°F (supply) No auxiliary heat 51.2°F 40°F distribution 75 gpm (demand) 42.7°F 56°F heat-recovery 300 gpm chiller 40°F 56°F 825 gpm
  • 23. system configurations Sidestream Loading Control strategies:  Satisfy heating requirements  Maintain leaving-condenser water temperature (positive-displacement compressors)
  • 24. system configuration comparison Heat Available/Required System configuration Primary– Characteristic secondary Preferential Sidestream Cooling load: cooling-only units 393 tons 350 tons 383 tons heat-recovery unit 157 tons 200 tons 167 tons Heat-recovery 40°F 40°F 42.7°F supply temperature Available heat 1890 MBh 2400 MBh 2000 MBh Auxiliary heat 110 MBh –400 MBh* 0 MBh required *Surplus recovered heat must be rejected
  • 25. system configurations Variable Primary Flow Piping heat-recovery chiller in sidestream position may simplify control bypass line modulating control valve VFD for minimum chiller flow heat-recovery chiller control valve
  • 26. system configurations Distributed Sidestream Typical application:  Remote heating requirement  Chilled water load  Small chiller (or water-to-water heat pump) heating load heat-recovery chiller chilled water supply or return
  • 27. airside system options Load-shedding economizer heat-recovery chiller heating load chilled water supply or return Control cooling load so heat rejection equals heating load outdoor-air controller temperature sensor
  • 28. airside system options Loading chiller with exhaust airstream Water from chiller Water to chiller EA RA C EA space T H T C H OA MA CA SA
  • 29. single condenser Heat-Recovery Control controller V1 cooling tower heating T1 load V2 heat condenser exchanger P P water-cooled T2 chiller controller P evaporator cooling load
  • 30. Dual-Condenser Chillers heat-recovery condenser standard condenser piped to cooling tower centrifugal heat-recovery chiller
  • 31. dual condenser Heat-Recovery Control controller cooling T2 tower P heating V2 controller load standard condenser T1 heat- P recovery P condenser auxiliary water-cooled heat P evaporator chiller Control based on entering-condenser water temperature cooling load
  • 32. Analysis Tools tool application System Analyzer™ High-level scoping (< 1 hr) TRACE™ Chiller Plant Simplified building entries Analyzer Full analysis of chilled water plant, economic rates EnergyPlus, HAP, TRACE Full energy simulation Hour-by-hour calculations of energy consumption, power demand, related costs
  • 33. Waterside Energy Recovery Steps  Simultaneous heating  Place the chiller(s) in and cooling loads the appropriate system location  Chiller HR capacity = Design heat recovery  Design the system with load the proper connections and controls  Select lowest temperature that  Train the building meets requirements operators  Select the proper  Operate the system chiller type properly  Analyze the system
  • 34. waterside heat recovery References From Trane: Waterside Heat Recovery in HVAC Systems SYS-APM005-EN 1991 Engineers Newsletter: “Two Good Old Ideas Combine to Form One New Great Idea” http://www.trane.com/commercial/library/EN20-1.pdf By others: 2008 ASHRAE Handbook: HVAC Systems and Equipment chapter 8 2003 ASHRAE Journal: “Energy Efficiency for Semiconductor Manufacturing Facilities” Ralph M. Cohen, PE (August issue)
  • 35. waterside heat recovery References 2008 ASHRAE Handbook: HVAC Systems and Equipment chapter 8 2003 ASHRAE Journal: “Energy Efficiency for Semiconductor Manufacturing Facilities” Ralph M. Cohen, PE (August issue)