Description of inergen system
1. 11
Description for Inergen SystemDescription for Inergen System
A. Sequence of OperationA. Sequence of Operation::
11..Activation of any single detector in any detected zone shallActivation of any single detector in any detected zone shall::
1.11.1Cause a first stage alarmCause a first stage alarm..
1.21.2Energize a lamp on the activated detector, F&G control panel and graphicEnergize a lamp on the activated detector, F&G control panel and graphic
pages with repetition to MFCPpages with repetition to MFCP..
22..Activation of a detector on the second zone shallActivation of a detector on the second zone shall::
2.1Transmit an alarm signal to remote F&G control panel with repetition to MFCP2.1Transmit an alarm signal to remote F&G control panel with repetition to MFCP..
2.22.2Cause a second stage (pre-discharge) alarm to operateCause a second stage (pre-discharge) alarm to operate..
2.32.3Operate auxiliary contacts for air-conditioning shutdown and motorized dampersOperate auxiliary contacts for air-conditioning shutdown and motorized dampers..
2.42.4Initiate time delay (Inergen agent releaseInitiate time delay (Inergen agent release).).
33..Up-on completion of the time delay the Inergen system shallUp-on completion of the time delay the Inergen system shall::
3.13.1Cause a discharge alarm to be activatedCause a discharge alarm to be activated..
3.23.2Activate visual alarm at protected area entranceActivate visual alarm at protected area entrance..
3.33.3Energize control solenoid for Inergen cylinders releasing gaseous into theEnergize control solenoid for Inergen cylinders releasing gaseous into the
protected areaprotected area..
JABAL HASOUNA SYSTEM
2. 22
B. Auxiliary Components:
1.Manual release station shall be provided at out-side the main entrance and at
Inergen bottles battery and shall, when activated, immediately release the
Inergen agent and cause immediate shutdown of power circuits.
2.Abort station (inhibit) shall be provided at out-side the main entrance and shall
,when activated, interrupt the discharge of Inergen agent and power OFF
functions. Manual release station shall override any abort station.
JABAL HASOUNA SYSTEM
3. 33
C. SEQUENCE OF INERGEN DISCHARGE:
1.Automatic Mode (System will be operated by automatic detectors(:
Fire Occurrence
Activation of two detectors on both
Detection circuits (A,B circuits(
Illumination of
Inergen control panel
Activation of Alarms
And time delay
Activation of solenoid valve
On CO2 activating cylinder
Discharge of CO2
Actuating gas
Opening of
Selector valve
Release of Inergen
cylinders
Discharge of
Inergen gas
Selector Valve Discharge Nozzle
Pressure Switch Illumination of discharge
lamp
JABAL HASOUNA SYSTEM
4. 44
2.Manual Mode (System will be operated by manual release unit located out-
side the protected area(:
Electrical Manual Operation:
Fire Occurrence Activation of Manual Station Illumination of Inergen Control Panel
Activation of Alarms & Time Delay Activation of Solenoid Valve on CO2
Actuating Cylinder
Discharge of CO2
Actuating Gas
Opening of
Selector Valve
Release of Inergen
Cylinders
Discharge of
Inergen Gas
Selector Valve Discharge
Nozzle
Pressure
Switch
Illumination of
Discharge Lamp
JABAL HASOUNA SYSTEM
5. 55
Mechanical Manual OperationMechanical Manual Operation:
Fire Occurrence Manual Actuation of
CO2 Actuating Cylinders
Discharge of CO2 Gas
Opening of
Selector Valve
Release of
Inergen Cylinders
Selector Valve Discharge Nozzle
Pressure Switch Illumination Of Discharge Valve
JABAL HASOUNA SYSTEM
6. 55
Mechanical Manual OperationMechanical Manual Operation:
Fire Occurrence Manual Actuation of
CO2 Actuating Cylinders
Discharge of CO2 Gas
Opening of
Selector Valve
Release of
Inergen Cylinders
Selector Valve Discharge Nozzle
Pressure Switch Illumination Of Discharge Valve
JABAL HASOUNA SYSTEM