IEEE Guide for the Protection of
Communication Installations from
Lightning Effects
IEEE Power Engineering Society
Sponsored by the
Power Systems Communications Committee
IEEE
3 Park Avenue
New Yarkr NY 10016-5997
USA
15 August 2011
IEEE Std 1692"1-2011
© Alokin Industries LLC
Lincoln, Nebraska
Second Edition
April 2014
The objective of this Abstract is to clarify technical
concepts and provide informative background for
the practitioner. Whereas IEEE 1692-2011
primarily addresses theory and installation detail
for wireless sites, this Abstract extends the
application discussion to wire-line sites.
IEEE 1692-2011 was produced by the Power
Systems Communications Committee of the IEEE
Power Engineering Society and released in
August, 2011. For detail information regarding
IEEE 1692-2011 refer to http://ieeexplore.ieee.org
You are welcome to address comments or
questions to Alokin at:
info@alokin.com
1-800-501-2910
Table of Contents
IEEE 1692-2011
I Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
II Basic Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
A. Equi-potential Ground Plane
B. Grounding – Soil Resistivity
C. Surge Protection – Application Considerations
III Power Line Strikes and Flashovers . . . . . . . . . . . . . . . . . . . 4
A. Lightning – Flashover Dynamics
B. Surge Protection – Performance Limitations
C. Recommended Solution – AC Isolation
IV Lightning Ground Potential Rise (L-GPR) . . . . . . . . . . . . . . . 6
A. Lightning – Discharge Dynamics
B. Soil Resistivity – Ground Voltage
C. Grounding – Frequency Dependent
D. Fault Paths – Recommended Solutions
V Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
AC Isolation
I Technology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
A. Lightning Detector
B. Controller
C. AC Contactor
II Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
1
IEEE 1692-2011
I Introduction
Background
Every year, communications equipment in
the outside plant (OSP) suffers millions of
dollars of damage. A severe lightning storm
in rural America typically means loss of
service, truck rolls, non-warranty parts
replacement and insurance claims.
Most of the damage is unexplained or
not investigated, and yet is preventable.
IEEE 1692 is the first industry publication
that provides guidance for lightning
protection of electronic communications
equipment in the OSP environment.
Related documents, NFPA 70 (the national
electric code), NFPA 780 and NESC only
address the protection of buildings and
personnel safety.
Purpose
The purpose of this IEEE 1692 Abstract is
to:
1. familiarize the reader with the faults
that are accountable for most of the
unexplained lightning related
damage, and
2. explain the advantages of blocking
technologies to effectively isolate
and protect communications
equipment.
Action
Readers are encouraged to thoroughly
review the recommendations for application
to their networks.
2
Fig 1. Simplified Equi-potential plane design
Fig 2. Soil Resistivity Values of Common Earth Compositions
II Basic Protection
Most lightning threats to communications equipment in urban areas can be mitigated by appropriate
surge protection and grounding practices.
A. Equi-potential Ground Plane
Essential to all lightning protection strategies is
keeping all ground points close to the same
potential to minimize voltage differentials:
1. Connect all equipment grounds to a
common ground bar,
2. Connect all power and communication
structures on site to a common (single
point) ground, and
3. Locate grounding ingress/egress at ground
level to minimize the voltage differential with respect to ground.
B. Grounding – Soil Resistivity
The effectiveness of a grounding system is dependent on multiple factors such as soil resistivity,
grounding electrode contact with the earth, and arrangement of the grounding components (rods,
wires and bars).
However, achieving low ground resistance (5 Ohms or less) may not be practical or even possible in
higher soil resistivity conditions. Referring to Figure 2, sand-gravel, limestone and granite are 20 to
100 times more resistive than surface soils and clay.1
Sand-gravel and limestone encompass a
broad range of possible soil resistivity values that may significantly vary within a given area.
Dehydration during arid seasons
dramatically increases soil resistivity.2
L-GPR produced by “dry lightning“ can be
extremely damaging (refer to Pg. 7, Soil
Resistivity-Ground Voltage).
1
USDA Bulletin 1751F-670
2
Ibid
Fig 3. Surface Dehydration effect on Soil Resistivity
3
Fig 4. Mutual Inductance of Ground Rods
To achieve lower 60Hz impedance in multi-
electrode grounds it is necessary to assure the
electrodes are as far apart as they are deep to
minimize the mutual inductance between the
electrodes. Mutual inductance reduces the
grounding efficiency for all frequencies.
3
However, longer or additional ground electrodes do
not reduce the grounding impedance behavior at
the lower lightning frequencies (refer to Pg 7,
Grounding-Frequency Dependent).
Grounding is subject to degradation from corrosion and other environmental factors and requires
periodic maintenance and testing to maintain desired ground resistance.
C. Surge Protection – Application Considerations
Surge Protection Devices (SPDs) have proven to be an effective deterrent against most power and
signal line threats. Surge protection responds to elevated voltage and redirects the energy to the
return conductor or ground - the intended primary fault paths in Figure 5. SPD failure produces the
destructive secondary fault paths.
All mode protection (L-L, L-N, L-G & N-G) is necessary for primary protection of
outside plant electronic sites.
NFPA 70 (NEC) permits only one neutral-ground bond at the site, located at the
service disconnect. A second N-G bond after the service disconnect can circumvent
circuit breaker protection.
.
The neutral ground mode on a secondary SPD at the Power Distribution
Panel must be disabled, which may otherwise provide an additional fault
path for elevated voltage on the master ground bar during a GPR event
(refer to Pg. 9, Fault: Ground System Transients).
3
Megger, Getting Down to Earth, 2010, P38
Fig 5. AC and Signal line SPD Protection
Fig 6A. Primary SPD Modes
Fig 6B. Secondary SPD Modes
4
Surge protectors are reactive devices. The response of
surge protectors allows let-through voltage that may
fatigue sensitive electronic circuits over time.
Hybrid SPDs combine faster reaction and high capacity
to reduce let through voltage.
III Power Line Strikes & Flashovers
A direct strike to a power line or signal cable creates high voltage transients that can produce
destructive current on the conductors. The extreme voltage and current produced by a lightning
strike can overwhelm the best SPD.
A. Lightning – Flashover Dynamics
Lightning produces an extremely high current
pulse than can momentarily reach 200KA within
2uSec.
4
The familiar vulnerability to lightning is a transient. Despite the use of a protective ground wire,
lightning current can flashover from the ground wire to a phase or neutral line. If the protecting
ground wire exhibits a high impedance to ground, a significant voltage can develop that exceeds the
air breakdown value (~3MV/m), allowing the lightning current to arc to a phase or neutral conductor,
impressing severe current on the terminal circuits.
5
4
The Lightning Discharge, Martin A. Uman, International Geophysics Series, Vol 39, 1987, Pg 341
5
Handbook of Chemistry and Physics, Chemical Rubber Company, any recent edition
Fig 8. Simplified Lightning Discharge Profile
Fig 9, Power line Flashover
Fig 7. SPD Let-through Voltage
5
B. Surge Protection – Performance Limitations
The threshold voltage of an SPD is not an ideal
constant. The actual performance of surge protection
is subject to the applied voltage. Higher voltage
increases the current, and higher voltage across the
SPD will be let through to connected equipment.
Severe voltage produced by a direct strike or flashover
may expose the electronic circuits to very high let-
through voltage, potentially damaging equipment and
the SPD.
C. Recommended Solution – AC Isolation
AC Isolation provides protection from flashovers and other severe utility transients. Detection of
lightning before the strike preemptively opens the AC circuit, blocking transients that may otherwise
overwhelm surge protection.
During isolation from AC power, operations safely continue on resident DC power until the threat has
passed, at which time AC power is automatically re-connected.
Fig 10. SPD Performance is Current Dependent
Fig 11. AC Isolation Solution of Severe Power Line Transients
6
Fig 13. Post-Strike Ground Charge Motion
Fig 14. Ground Voltage Gradients
Fig 12. Pre-Strike Ground Charge Motion
IV Lightning Ground Potential Rise (L-GPR)
IEEE-1692 primarily focuses on the threat posed by L-GPR, undoubtedly the least understood and
consequently, least protected lightning threat. The energy from a lightning ground strike is not
immediately dissipated in local earth. The voltage of the earth rises as energy is radiated outward
creating momentary voltage gradients between ground points.
A. Lightning – Discharge Dynamics
Lightning is an electrostatic discharge – a
transfer of electrical charge between the cloud
and ground. Prior to a strike, negative charge
accumulates in the lower portion of a storm cell
causing a concentration of offsetting positive
charge in the earth. During this process the
earth’s normal electric field of 100V/m
increases to over 2,000 V/m and changes from
negative to positive polarity
6
.
Prior to discharge, the voltage differential
between the cloud base and earth dramatically
rises to between 10M and100M volts.
7
The discharge produces ground current that
radiates through the earth’s surface in all
directions. The peak current amplitude of a
lightning strike ranges from 5KA to 200KA.
There are typically 3 to 4 discharges per
lightning channel (the visible flicker is repetitive
ground strikes).
8
Consequently, successive
waves of energy are radiated from the strike
point.
The discharge creates voltage gradients
radiating from the strike point, comparable
to the waves created by a rock striking a
water surface. The 5 - 200KA lightning
current converts to ground current.
6
Lightning, Martin A. Uman, Dover Publications, ISBN 0-486-64575-4, Pg 48, 51
7
Ibid, Pg 214-215
8
Lightning, Martin A. Uman, Dover Publications, ISBN 0-486-64575-4, Pg 4
7
B. Soil Resistivity – Ground Voltage
Soil resistivity is a significant determinant of the voltage, or potential, gradient. Higher soil resistivity
produces higher voltage potentials for a given current.
At a half-mile distance, an average lightning strike of 25KA produces very low voltage in a soil-clay
region. However, a site with a sand-gravel composition will be exposed to potentially damaging
voltage. The diagram below displays approximate ground potentials. (Referring to the dashed line in
Figure 15, a 25KA strike in limestone measuring 2,000 Ohm-M produces a gradient potential of
30,000V over one half mile.)
Caveat: Communication sites in urban areas are relatively immune to the L-GPR threat due to the
extensive underground infrastructure that is highly conductive, substantially reducing the effective soil
resistivity. By contrast, rural areas characterized by elevated soil resistivity are highly vulnerable to
just one near-proximity ground strike.
C. Grounding – Frequency Dependent
Grounding is designed to provide a low impedance current path to earth for both safety and
equipment protection purposes. However, grounding systems behave differently at different
frequencies. Grounding is a very effective conductor at very low frequencies, as demonstrated by
grounding resistance tests typically conducted at 50 –150Hz. However, grounding is inductive at the
lower frequencies of lightning between 5KHz and 500KHz.
9
9
IEEE Transaction on Power Deliver, Vol 23, No 4, October 2006, Triggered Lightning Experiments; Brian
DeCarlo, Vladimir Rakov, et.al
Fig 15. Soil Resistivity effect on L-GPR Voltage
Fig 16. Grounding Effectiveness is Frequency Dependent
8
The resulting high impedance at these frequencies significantly affects the current path. The
referenced studies found that in higher resistivity earth over 50% of the lightning current impressed on
the grounding system was forced onto the AC phase and neutral lines.
Although longer or additional grounding electrodes reduce AC-60Hz impedance, the higher
inductance of longer ground rods may also increase the impedance for the low-range frequencies of
lightning.
D. Fault Paths – Recommended Solutions
The unexplained lightning related damage to communications equipment is typically attributable to an
L-GPR fault, inducing either a signal line transient or a ground system transient. A signal line
transient is evident if the protectors have failed. However, a ground system transient can inflict
significant equipment damage without affecting the protectors.
Fault: Signal Line Transients
The lightning discharge current on cable shields can induce
currents on adjacent conductors, producing high voltages in
cables and electrical equipment. The shield current
produces a magnetic field which couples to the signal lines
and produces a current in the opposite direction.
Note that a similar fault may be caused by 60Hz GPR in
close proximity to a power substation or generation plant.
Recommended Solution: Optical Isolation
Optical Isolation inserts a dielectric path for signal lines that may otherwise expose personnel or
equipment to voltage transients. Applications include:
1. Service centers that potentially expose operators
2. Services to high voltage facilities - substations and power generation plants
3. Class A facilities that must continuously operate in all circumstances
Fig 17. Magnetic Field Induced Current
Fig 18. Optical Isolation Solution of Signal line Transients
9
Fig 20. SPD conduction of L-GPR
Fault: Ground System Transients
Single point grounding of the communication’s site seeks to achieve an equi-potential ground plane
that assures very low voltage differentials between bonded ground circuits, and thus little threat of
fault current.
However, connection to the AC power service introduces a remote, lower potential ground reference
during an L-GPR event. The high potential difference between the communications ground and the
AC service ground makes the power phase and neutral lines a preferred discharge path between the
grounds. The safety ground is only partially effective because of the higher impedance to lightning
frequencies.
10
The grounding system near a lightning ground strike elevates in potential with respect to other
grounds. The voltage impressed on the grounding system elevates the master ground bar (MGB).
The signal line surge protectors are connected to
the MGB. SPDs are bi-directional devices (to
protect against positive and negative polarity
transients
11
) and activate if the MGB voltage
exceeds their threshold. The activated SPD
provides a conductive path for the elevated MGB
voltage to the Tip and Ring circuits. A fault path
is created to the lower potential ground
references on the signal line terminations and the
remote power ground circuit for the electronics
equipment.
Voltage on the subscriber circuit is substantially
dissipated over the intervening distance.
However, there is a significant potential
difference on the adjoining power circuit, exposing
the communications equipment.
Referring to Figure 20, if the MGB experiences a LGPR of 1,000V and the SPD has a 250V
threshold, about 750V is applied to the Tip and Ring line card circuits relative to remote ground.
10
The Self and Mutual inductance of linear conductors, Edward B. Rosa, Bulletin of the Bureau of
Standards, Vol 4, No. 2, 1908 Pg 301-344
11
IEEE Std C62.45-1992
Fig 19. Ground System Fault Path
10
Recommended Solutions
Radial Grounding (for tower sites) - recognizes the
frequency limitations of vertical grounding. Since
current from a lightning ground strike radiates near
the surface12
, radials off the vertical grounding
reduce the grounding impedance to the low-range
frequencies of lightning.
1. The combination of vertical and horizontal
electrodes provides lower impedance
grounding.
2. The radials increase the capacitive coupling
between the grounding system and the
earth.
3. However, the effectiveness of the radial
grounding diminishes in soil resistivity over
500 Ohm-M.
13
AC Isolation - detects lightning before the strike and preemptively disconnects the utility power
phase and neutral circuit. Opening the power circuit creates a single point ground condition,
effectively isolating the communications equipment and blocking the fault path. Absent a secondary
path, the lightning energy is forced to dissipate through the grounding system. Communications are
continuously maintained on battery or generator power during the isolation period. Utility power is
automatically restored after the threat has passed.
AC Isolation requirements:
1. Standby power is required to maintain operations during the isolation period.
2. The AC Isolator also includes an AC voltage monitor that responds to AC surges and sags
within 3 cycles. However, the AC Isolator must be installed on the line side of the primary
SPD to provide an initial fast response to AC transients caused by non-lightning events
(e.g. capacitor bank switching and inductive motor switching).
12
An Examination of Lightning Strike Grounding Physics: C.B. More, G.D. Aulich and William Rison; Langmuir
Laboratory for Atmospheric Research
13
IEEE 1692-2011, 8.1 Note 3
Fig 21. Radial Grounding for Towers
Fig 22. AC Isolation of Ground System Transients
11
V Summary
Lightning energy radiates outward through the atmosphere, the earth’s surface and all conductors
over a wide frequency range. Rural and remote communication’s installations are particularly
vulnerable to lightning. New protection technologies have evolved to augment traditional protection
practices and effectively mitigate the lightning threat.
Critical to a solution is correct diagnosis of the problem. Sites with good grounding and surge
protection practices are still vulnerable to severe power line faults and lightning ground potential rise
(L-GPR). In fact, both grounding and better surge protection actually facilitate the L-GPR fault path.
Effective protection against lightning damage requires a combination of technologies to address
unique circumstances. The recommended protection strategies are:
1. All exposures:
Optimize the equi-potential ground plane, within the limitations of local soil resistivity
2. AC Transients:
Primary all-mode surge protection
AC Isolation for power line strikes and flash-over exposure
3. Lightning Ground Potential Rise (L-GPR):
Optical Isolation for signal line transients
AC Isolation for grounding system transients
Radial grounding for towers with available real estate and low soil resistivity
Note: The effectiveness of the blocking technologies - Optical Isolation and AC Isolation, is not
subject to soil resistivity or the resistance of the grounding system. A high resistance ground will just
take a little longer to dissipate the blocked energy.
Augmenting traditional protection practices with the appropriate blocking technology affords
the best protection strategy to minimize lightning related damage.
12
13
AC Isolation
I Technology
If L-GPR is the least understood lightning phenomenon, then AC Isolation is the least recognized
solution. AC Isolation is:
1. A blocking technology – open circuits the potential fault path to the communications
equipment
2. Pre-emptive – disconnects the fault path before the threatening ground strike occurs
3. Intelligent – discriminates lightning ground strikes from other electric field phenomenon
The AC Isolation technology is comprised of three components: a Lightning Detector, a Contactor to
disconnect/re-connect AC power and a Controller that manages the detection and isolation functions
and provides connection to remote communications. The Contactor is an electro-mechanical device
with a response time of about 15mSec – too slow to react to a nearby lightning event. Consequently,
the AC Isolator must discriminate the potential lightning threat before the ground strike occurs to
provide sufficient time for the Contactor to isolate the communications equipment.
A. Lightning Detector
Reliable detection of lightning ground strikes requires discrimination of the electric field orientation.
Cloud to ground lightning is primarily a vertical electric field, whereas cloud to cloud lightning and
electromagnetic transmission are primarily horizontal fields.
Prior to a stroke discharge, the development of a
lightning channel rapidly changes the electric
field strength at ground level. L-GPR produced
by a remote ground strike causes a significant
ground potential increase that also produces an
electric field change.
The Lightning Detector is responsive to both
events. The electric field change is detected,
converted to voltage and compared to the
Lightning Detector threshold. If it exceeds the
threshold, isolation is initiated.
Figure 23 depicts the increasing L-GPR
amplitude from an approaching storm. Low soil
resistivity areas (T) that readily dissipate L-GPR
energy produce a weaker electric field change,
requiring a more sensitive detection threshold.
For the same lightning strike, high resistivity soil
(S) dissipates less L-GPR energy, producing a
stronger field change. A less sensitive detection
threshold is necessary to ignore distant lightning
activity that is not threatening.
Fig 23. Detection Sensitivity
based on Soil Resistivity
14
The Lightning Detector circuitry provides:
1. Sensitivity adjustment for user specification of the detection range based on the local soil
conditions,
2. A voltage comparator to evaluate the differential voltage caused by the changing electric
fields near the earth,
3. Communication with the Controller to open/close the Contactor controlling the AC service,
and
4. User test of the detection and communication circuits
B. Controller
The Controller opens the Contactor in response to a signal from the Lightning Detector or an internal
AC voltage monitor, based on the user specified thresholds.
1. The AC detector monitors the AC power service with two voltage comparators to detect fast
transients and slower surge/sag activity.
2. Adjustable count-down timers determine the initial isolation period for L-GPR and AC power
threats. Subsequent threat detection during an isolation period restarts the respective timer.
3. AC power is re-connected after it stabilizes within the user defined thresholds. Consequently,
the communications equipment is protected from power recovery transients.
4. The Controller targets re-connection of AC power at the zero voltage cross-over to mitigate
local switching transients and minimize in-rush currents.
5. Alarm relays are provided for connection to the site alarm panel.
A Remote Controller provides several additional features:
1. Remote communications on an Ethernet or POTS connection,
2. Remote monitoring of threat activity and adjustment of protection settings (detection
thresholds and isolation timers),
3. Event logging and remote download of threat activity and the corresponding protection
response; the log may be correlated with 3
rd
party lightning data,
4. Remote monitoring of the battery plant or test of the stand-by generator, and
5. Remote test of the AC Isolator.
C. Contactor
The Contactor disconnects the phase and neutral lines; the safety ground is not disconnected.
The Contactor is sized equal to or greater than the amperage of the AC service. For example,
equipment wired off a 200A service disconnect requires a 200A contactor; equipment wired off the
load center may only require a 60A contactor, or less.
Contactors for this application are rated for several million cycles.
15
II Installation
Installation typically requires the services of a commercial electrician.
The Controller is installed:
A. off the service disconnect, on the load side of primary AC SPD, and before the transfer
switch,
B. or, off the load center and before the cabinet power distribution panel
The Controller may be mounted externally on a power pedestal, an adjoining frame, or on the interior
wall of a shelter. The Lightning Detector must be mounted externally with a 360o
view that is
unobstructed for a minimum 8 feet.
Fig 24. Typical Wireless Site (Cell Tower) Installation
Fig 25. Typical Wire-line Site (Remote Terminal) Installation
16
17
Glossary
AC Isolation. The physical disconnection of the AC utility power from electronic systems to protect
against power transients and lightning ground potential rise. Typically an automatic process based
on detection sensor(s).
All Mode (ref SPD). An AC surge protector that provides all modes of power protection, Typically
referenced to 240V split phase and 3 phase power systems. The modes are: Line-Neutral (L-N),
Line-Line (L-L), Line-Ground (L-G) and Neutral-Ground (N-G)
Capacitance. The property of parallel conductive surfaces to store energy in an electrical field between
the surfaces. The degree of capacitance varies directly with the area of the parallel plates and
inversely to the distance of separation between the plates. A property of a capacitor is to pass AC
signals and block DC signals. The AC impedance will vary inversely with frequency.
Contactor. A relay that is designed to control power in AC power systems. A contactor is frequently used
in electric motor starters and electrical power panels.
Equi-potential. Pertaining to equal electrical potential; where all points on the grounding system
(sometimes referred to as a plane) strive to be at the same potential to mitigate ground current
loops.
Flashover. A current arc from one conductor to another when struck by lightning. A typical example is a
lightning strike to the ground protection wire on an aerial power line that arcs to the phase or neutral
line below. In the first several uSec of lightning contact the immediate voltage can exceed 100KV
while the impedance to ground can be very high. The phase lines are at a moderate voltage with
respect to ground and provide another path to ground, as does the neutral line.
GPR (Ground Potential Rise). The increase of electrical potential in the earth with respect to another
location. This may result from a downed power line or a power distribution fault, referred to as 60Hz
GPR; or a lightning ground strike (L-GPR). GPR is typically a momentary condition and magnitudes
can vary between mV and KV.
Ground. A direct physical connection to the earth, or a reference point in an electrical circuit from which
other voltages are measured.
Ground Resistance. Ground resistance is the resistance of the grounding system to current flow.
However, ground impedance is a more complete characterization of grounding conductivity that
includes capacitive and inductive reactance. Grounding impedance is primarily a function of soil
resistivity, surface area contact with grounding electrodes and the physical dimensions of the
conductors.
Ground Ring. A series of buried grounding electrodes connected by a conductor such as a wire or cable,
in direct contact with the earth encircling the grounded structure.
Grounding Electrode. More commonly called a ground rod which is driven into the earth for the purpose
of providing an electrical connection to the earth.
Impedance. The total opposition to current including resistance, inductive reactance and capacitive
reactance. In DC circuits there is no reactance and the impedance is just the resistance. (Refer to
Reactance)
Inductance. The property of a conductor that provides a direct opposition to AC current from a self
induced magnetic field caused by a change in current.
L-GPR (Lightning Ground Potential Rise). Ground potential rise created by a lightning ground strike.
L-GPR radiates in all directions and is typically more severe than 60Hz GPR which returns to the
distribution source. L-GPR creates extreme potential differentials across the earth surface.
The differential voltages decrease with distance based on soil conditions.
18
MGB (Master Ground Bar). A metal bar used as a common grounding point in communication systems.
The MGB contributes to providing a single point ground.
Neutral-Ground Bond. The point where the power neutral line and ground are bonded together at the
power transformer and the power service disconnect. NEC requires an N-G bond at the service
disconnect location; no other N-G bonds are permitted after that point.
Neutral-Ground Mode (SPD). The protection mode in a surge protector that limits voltages between the
neutral and ground lines. Other modes are line to neutral and line to line. Not all surge protectors
have a N-G mode.
Optical Isolation. Use of a di-electric plastic fiber to transmit signals and concurrently isolate the
electronics on either side of the fiber from each other electrically.
Potential (Electric Potential or Voltage). A description of the difference in potential energy (per unit
charge) between points in an electric field. The concept is exemplified by the voltage between two
battery terminals. The magnitude of potential is an indicator of the ability to move charge. In Ohms
Law the voltage determines how much current will flow through a given resistor.
Reactance. The opposition to alternating current due to capacitance (capacitive reactance) or inductance
(inductive reactance). Reactance plus resistance equals impedance.
Resistance. The property of a material to oppose the flow of electrical current. Resistance is comparable
to friction in mechanical systems. In Ohms Law a given resistance will allow a specific current for a
given voltage.
Rise Time. The measure of time for an electrical signal to go from the lowest to the highest level.
Typically measured between the 10% and 90% levels.
Service Disconnect. A switch at the AC utility service entrance that allows disconnection of the service
from the load circuits. A circuit breaker is typically used as both overload protection and switch.
The circuit breaker rating defines the current limit of the service.
Single Point Ground. A grounding system design that ensures all ground conductors from the electronics
equipment are connected to a single point on the grounding electrode or ground ring. A single point
ground mitigates ground current loops and ground potential differences.
Soil Resistivity. A measure of soil’s ability to oppose conductance of electrical current. Soil resistivity is
measured in units of Ohm-meters or Ohm-centimeters. Soil resistivity values can vary significantly
from 2 to 10,000 ohm-meters. Moisture content can significantly affect soil resistivity, particularly
during prolonged seasonal changes.
SPD. A surge protection device is used to mitigate transients and surges on power and signal lines by
limiting the voltage between the SPD terminals. An SPD has a high resistance in a normal voltage
range and low resistance in higher than normal voltages. The conduction voltage level is referred to
as the threshold level. There are various technologies used in SPD’s that offer tradeoffs between
speed of operation, protection voltage threshold and energy carrying capacity.
Transient. Transient describes short term excess voltage on power or signal lines. The time duration can
vary from a few milliseconds to nanoseconds. Excess voltages can exceed several thousand volts.
The cause of a voltage transient can be lightning or power switching equipment.
Lightning Protection Considerations for Wired Systems
Lightning Protection Considerations for Wired Systems

Contenu connexe

Tendances

Surge_Protection_Device_for_Solar_PV_Application
Surge_Protection_Device_for_Solar_PV_ApplicationSurge_Protection_Device_for_Solar_PV_Application
Surge_Protection_Device_for_Solar_PV_ApplicationAllied Power APS
 
Presentation lightning protection system by jmv lps
Presentation lightning protection system by jmv lpsPresentation lightning protection system by jmv lps
Presentation lightning protection system by jmv lpsMahesh Chandra Manav
 
An Article on Electrical Safety
An Article on Electrical SafetyAn Article on Electrical Safety
An Article on Electrical SafetyIJSRD
 
Electromagnetic earthing and coupling, Electromagnetic Shielding
Electromagnetic earthing and coupling, Electromagnetic Shielding Electromagnetic earthing and coupling, Electromagnetic Shielding
Electromagnetic earthing and coupling, Electromagnetic Shielding Suleyman Demirel University
 
Your electrical safety specilist for all equipments Powered AC and DC
Your electrical safety specilist for all equipments   Powered AC and DCYour electrical safety specilist for all equipments   Powered AC and DC
Your electrical safety specilist for all equipments Powered AC and DCMahesh Chandra Manav
 
Power surge protection devices
Power surge protection devices Power surge protection devices
Power surge protection devices Pratik Rasam
 
Linkedin Emc Safety General Info
Linkedin Emc Safety General InfoLinkedin Emc Safety General Info
Linkedin Emc Safety General InfoBharat Shah
 
EFFECT OF ELECTROMAGNETICE FIELD (EMI).
EFFECT OF ELECTROMAGNETICE FIELD (EMI).EFFECT OF ELECTROMAGNETICE FIELD (EMI).
EFFECT OF ELECTROMAGNETICE FIELD (EMI).Arshad Hussain
 
Lightning concepts iii
Lightning concepts iiiLightning concepts iii
Lightning concepts iiiILDTECH
 
Electromagnetic interference shielding in unmanned aerial vehicle against lig...
Electromagnetic interference shielding in unmanned aerial vehicle against lig...Electromagnetic interference shielding in unmanned aerial vehicle against lig...
Electromagnetic interference shielding in unmanned aerial vehicle against lig...TELKOMNIKA JOURNAL
 
Over voltage(Switch Gear and Protection)
Over voltage(Switch Gear and Protection)Over voltage(Switch Gear and Protection)
Over voltage(Switch Gear and Protection)Jaydeep Chauhan
 
Protection against over voltage
Protection against over voltageProtection against over voltage
Protection against over voltageMuhammedArifTanoli
 
Guide to Surge Protection Devices
Guide to Surge Protection DevicesGuide to Surge Protection Devices
Guide to Surge Protection DevicesJason Koffler
 
Emi emc-pdf
Emi emc-pdfEmi emc-pdf
Emi emc-pdfnagastra
 
Electromagnetic Compatibility
Electromagnetic CompatibilityElectromagnetic Compatibility
Electromagnetic CompatibilityVesa Linja-aho
 
Paper Electron Tube Afs Epri R5
Paper   Electron Tube   Afs Epri R5Paper   Electron Tube   Afs Epri R5
Paper Electron Tube Afs Epri R5John Kappenman
 
17th Edition Parts 53 To 56
17th  Edition Parts 53 To 5617th  Edition Parts 53 To 56
17th Edition Parts 53 To 56Paul Holden
 

Tendances (20)

Hv sytem overvolatge
Hv sytem overvolatge Hv sytem overvolatge
Hv sytem overvolatge
 
Surge_Protection_Device_for_Solar_PV_Application
Surge_Protection_Device_for_Solar_PV_ApplicationSurge_Protection_Device_for_Solar_PV_Application
Surge_Protection_Device_for_Solar_PV_Application
 
Presentation lightning protection system by jmv lps
Presentation lightning protection system by jmv lpsPresentation lightning protection system by jmv lps
Presentation lightning protection system by jmv lps
 
An Article on Electrical Safety
An Article on Electrical SafetyAn Article on Electrical Safety
An Article on Electrical Safety
 
Electromagnetic earthing and coupling, Electromagnetic Shielding
Electromagnetic earthing and coupling, Electromagnetic Shielding Electromagnetic earthing and coupling, Electromagnetic Shielding
Electromagnetic earthing and coupling, Electromagnetic Shielding
 
Your electrical safety specilist for all equipments Powered AC and DC
Your electrical safety specilist for all equipments   Powered AC and DCYour electrical safety specilist for all equipments   Powered AC and DC
Your electrical safety specilist for all equipments Powered AC and DC
 
Power surge protection devices
Power surge protection devices Power surge protection devices
Power surge protection devices
 
Linkedin Emc Safety General Info
Linkedin Emc Safety General InfoLinkedin Emc Safety General Info
Linkedin Emc Safety General Info
 
EFFECT OF ELECTROMAGNETICE FIELD (EMI).
EFFECT OF ELECTROMAGNETICE FIELD (EMI).EFFECT OF ELECTROMAGNETICE FIELD (EMI).
EFFECT OF ELECTROMAGNETICE FIELD (EMI).
 
Lightning concepts iii
Lightning concepts iiiLightning concepts iii
Lightning concepts iii
 
Electromagnetic interference shielding in unmanned aerial vehicle against lig...
Electromagnetic interference shielding in unmanned aerial vehicle against lig...Electromagnetic interference shielding in unmanned aerial vehicle against lig...
Electromagnetic interference shielding in unmanned aerial vehicle against lig...
 
Over voltage(Switch Gear and Protection)
Over voltage(Switch Gear and Protection)Over voltage(Switch Gear and Protection)
Over voltage(Switch Gear and Protection)
 
Protection against over voltage
Protection against over voltageProtection against over voltage
Protection against over voltage
 
Emt and emc
Emt and emcEmt and emc
Emt and emc
 
Guide to Surge Protection Devices
Guide to Surge Protection DevicesGuide to Surge Protection Devices
Guide to Surge Protection Devices
 
Emi emc-pdf
Emi emc-pdfEmi emc-pdf
Emi emc-pdf
 
Electromagnetic Compatibility
Electromagnetic CompatibilityElectromagnetic Compatibility
Electromagnetic Compatibility
 
Paper Electron Tube Afs Epri R5
Paper   Electron Tube   Afs Epri R5Paper   Electron Tube   Afs Epri R5
Paper Electron Tube Afs Epri R5
 
17th Edition Parts 53 To 56
17th  Edition Parts 53 To 5617th  Edition Parts 53 To 56
17th Edition Parts 53 To 56
 
Esd
EsdEsd
Esd
 

Similaire à Lightning Protection Considerations for Wired Systems

Presentation best practice earthing and protection
Presentation   best practice earthing and protectionPresentation   best practice earthing and protection
Presentation best practice earthing and protectionMahesh Chandra Manav
 
Tes p-122.10-r0 (1)
Tes p-122.10-r0 (1)Tes p-122.10-r0 (1)
Tes p-122.10-r0 (1)Ibrahim Ali
 
Lightning and surge transfer to systems presentation by jmv lps
Lightning and surge  transfer to systems presentation by jmv lpsLightning and surge  transfer to systems presentation by jmv lps
Lightning and surge transfer to systems presentation by jmv lpsMahesh Chandra Manav
 
Behavioral studies of surge protection components
Behavioral studies of surge protection componentsBehavioral studies of surge protection components
Behavioral studies of surge protection componentsjournalBEEI
 
Water Treatment Plant Protection
Water Treatment Plant ProtectionWater Treatment Plant Protection
Water Treatment Plant ProtectionMike Nager
 
Schneider electric : Neutral Earthing
Schneider electric : Neutral EarthingSchneider electric : Neutral Earthing
Schneider electric : Neutral EarthingEduardo Higino
 
Lightning Discharge and Fundamentals of lightning Protection
Lightning Discharge and Fundamentals of lightning ProtectionLightning Discharge and Fundamentals of lightning Protection
Lightning Discharge and Fundamentals of lightning Protectionrajani51
 
Substation Earthing Design
Substation Earthing DesignSubstation Earthing Design
Substation Earthing DesignIOSRJEEE
 
COMPENSATION OF FAULT RESISTANCE IN DISTANCE RELAY FOR LONG TRANSMISSION LINE
COMPENSATION OF FAULT RESISTANCE IN DISTANCE RELAY FOR LONG TRANSMISSION LINECOMPENSATION OF FAULT RESISTANCE IN DISTANCE RELAY FOR LONG TRANSMISSION LINE
COMPENSATION OF FAULT RESISTANCE IN DISTANCE RELAY FOR LONG TRANSMISSION LINEIRJET Journal
 
Earthing systems - Basic constructional aspects
Earthing systems - Basic constructional aspectsEarthing systems - Basic constructional aspects
Earthing systems - Basic constructional aspectsBruno De Wachter
 
Presentation department of space by jmv lps
Presentation department of space by jmv lpsPresentation department of space by jmv lps
Presentation department of space by jmv lpsMahesh Chandra Manav
 
Presentation department of space by jmv lps
Presentation department of space by jmv lpsPresentation department of space by jmv lps
Presentation department of space by jmv lpsMahesh Chandra Manav
 
Smart Grid Overvoltage Protection
Smart Grid Overvoltage ProtectionSmart Grid Overvoltage Protection
Smart Grid Overvoltage ProtectionMike Nager
 
Underground Cable Fault Detection Using Arduino
Underground Cable Fault Detection Using ArduinoUnderground Cable Fault Detection Using Arduino
Underground Cable Fault Detection Using ArduinoIRJET Journal
 

Similaire à Lightning Protection Considerations for Wired Systems (20)

Presentation jmv internal
Presentation jmv internalPresentation jmv internal
Presentation jmv internal
 
Presentation best practice earthing and protection
Presentation   best practice earthing and protectionPresentation   best practice earthing and protection
Presentation best practice earthing and protection
 
Tes p-122.10-r0 (1)
Tes p-122.10-r0 (1)Tes p-122.10-r0 (1)
Tes p-122.10-r0 (1)
 
Lightning and surge transfer to systems presentation by jmv lps
Lightning and surge  transfer to systems presentation by jmv lpsLightning and surge  transfer to systems presentation by jmv lps
Lightning and surge transfer to systems presentation by jmv lps
 
Behavioral studies of surge protection components
Behavioral studies of surge protection componentsBehavioral studies of surge protection components
Behavioral studies of surge protection components
 
Water Treatment Plant Protection
Water Treatment Plant ProtectionWater Treatment Plant Protection
Water Treatment Plant Protection
 
Schneider electric : Neutral Earthing
Schneider electric : Neutral EarthingSchneider electric : Neutral Earthing
Schneider electric : Neutral Earthing
 
Lightning Discharge and Fundamentals of lightning Protection
Lightning Discharge and Fundamentals of lightning ProtectionLightning Discharge and Fundamentals of lightning Protection
Lightning Discharge and Fundamentals of lightning Protection
 
EMC and HFPQ for industrial networks - Jos Knockaert, UGent and Peter Thomas...
EMC and HFPQ for industrial networks -  Jos Knockaert, UGent and Peter Thomas...EMC and HFPQ for industrial networks -  Jos Knockaert, UGent and Peter Thomas...
EMC and HFPQ for industrial networks - Jos Knockaert, UGent and Peter Thomas...
 
EMC for Networks - Peter Thomas, Control Specialists and Jos Knockaert, UGent
EMC for Networks - Peter Thomas, Control Specialists and Jos Knockaert, UGentEMC for Networks - Peter Thomas, Control Specialists and Jos Knockaert, UGent
EMC for Networks - Peter Thomas, Control Specialists and Jos Knockaert, UGent
 
تأريض2
تأريض2تأريض2
تأريض2
 
Substation Earthing Design
Substation Earthing DesignSubstation Earthing Design
Substation Earthing Design
 
Umtsrns 108 earthing & lightning protection
Umtsrns 108 earthing & lightning protectionUmtsrns 108 earthing & lightning protection
Umtsrns 108 earthing & lightning protection
 
Emi unit iv ppt
Emi unit iv pptEmi unit iv ppt
Emi unit iv ppt
 
COMPENSATION OF FAULT RESISTANCE IN DISTANCE RELAY FOR LONG TRANSMISSION LINE
COMPENSATION OF FAULT RESISTANCE IN DISTANCE RELAY FOR LONG TRANSMISSION LINECOMPENSATION OF FAULT RESISTANCE IN DISTANCE RELAY FOR LONG TRANSMISSION LINE
COMPENSATION OF FAULT RESISTANCE IN DISTANCE RELAY FOR LONG TRANSMISSION LINE
 
Earthing systems - Basic constructional aspects
Earthing systems - Basic constructional aspectsEarthing systems - Basic constructional aspects
Earthing systems - Basic constructional aspects
 
Presentation department of space by jmv lps
Presentation department of space by jmv lpsPresentation department of space by jmv lps
Presentation department of space by jmv lps
 
Presentation department of space by jmv lps
Presentation department of space by jmv lpsPresentation department of space by jmv lps
Presentation department of space by jmv lps
 
Smart Grid Overvoltage Protection
Smart Grid Overvoltage ProtectionSmart Grid Overvoltage Protection
Smart Grid Overvoltage Protection
 
Underground Cable Fault Detection Using Arduino
Underground Cable Fault Detection Using ArduinoUnderground Cable Fault Detection Using Arduino
Underground Cable Fault Detection Using Arduino
 

Plus de Analynk Wireless, LLC

Analynk Participation in Aruba Atmosphere 2018
Analynk Participation in Aruba Atmosphere 2018Analynk Participation in Aruba Atmosphere 2018
Analynk Participation in Aruba Atmosphere 2018Analynk Wireless, LLC
 
DIN Rail Mount Tachometer for Process Measurement and Control
DIN Rail Mount Tachometer for Process Measurement and ControlDIN Rail Mount Tachometer for Process Measurement and Control
DIN Rail Mount Tachometer for Process Measurement and ControlAnalynk Wireless, LLC
 
Analynk Wireless Enclosure Options and More
Analynk Wireless Enclosure Options and MoreAnalynk Wireless Enclosure Options and More
Analynk Wireless Enclosure Options and MoreAnalynk Wireless, LLC
 
Industrial Wireless Communications - Hazardous Area Antennas
Industrial Wireless Communications - Hazardous Area AntennasIndustrial Wireless Communications - Hazardous Area Antennas
Industrial Wireless Communications - Hazardous Area AntennasAnalynk Wireless, LLC
 
Tachometer transmitter for industrial process measurement and control
Tachometer transmitter for industrial process measurement and controlTachometer transmitter for industrial process measurement and control
Tachometer transmitter for industrial process measurement and controlAnalynk Wireless, LLC
 
Cavitation Control in Process Control Valves
Cavitation Control in Process Control ValvesCavitation Control in Process Control Valves
Cavitation Control in Process Control ValvesAnalynk Wireless, LLC
 
Defending industrial control systems from cyber attack
Defending industrial control systems from cyber attackDefending industrial control systems from cyber attack
Defending industrial control systems from cyber attackAnalynk Wireless, LLC
 
Solar power supply for industrial wireless transmitters
Solar power supply for industrial wireless transmittersSolar power supply for industrial wireless transmitters
Solar power supply for industrial wireless transmittersAnalynk Wireless, LLC
 
Signal Alarms for Process Monitoring
Signal Alarms for Process MonitoringSignal Alarms for Process Monitoring
Signal Alarms for Process MonitoringAnalynk Wireless, LLC
 
Hazardous Area Wireless Equipment Enclosures
Hazardous Area Wireless Equipment EnclosuresHazardous Area Wireless Equipment Enclosures
Hazardous Area Wireless Equipment EnclosuresAnalynk Wireless, LLC
 
Analynk Model A16000 RF Expansion Module
Analynk Model A16000 RF Expansion ModuleAnalynk Model A16000 RF Expansion Module
Analynk Model A16000 RF Expansion ModuleAnalynk Wireless, LLC
 
Alokin Lightning Shield Protects Equipment
Alokin Lightning Shield Protects EquipmentAlokin Lightning Shield Protects Equipment
Alokin Lightning Shield Protects EquipmentAnalynk Wireless, LLC
 
Hazardous Area Antenna - Iridium Satellite Communication
Hazardous Area Antenna - Iridium Satellite CommunicationHazardous Area Antenna - Iridium Satellite Communication
Hazardous Area Antenna - Iridium Satellite CommunicationAnalynk Wireless, LLC
 
Hazardous Area Explosion Proof Antenna for GLONASS, GPS, and IRIDIUM
Hazardous Area Explosion Proof Antenna for GLONASS, GPS, and IRIDIUMHazardous Area Explosion Proof Antenna for GLONASS, GPS, and IRIDIUM
Hazardous Area Explosion Proof Antenna for GLONASS, GPS, and IRIDIUMAnalynk Wireless, LLC
 

Plus de Analynk Wireless, LLC (15)

Analynk Participation in Aruba Atmosphere 2018
Analynk Participation in Aruba Atmosphere 2018Analynk Participation in Aruba Atmosphere 2018
Analynk Participation in Aruba Atmosphere 2018
 
DIN Rail Mount Tachometer for Process Measurement and Control
DIN Rail Mount Tachometer for Process Measurement and ControlDIN Rail Mount Tachometer for Process Measurement and Control
DIN Rail Mount Tachometer for Process Measurement and Control
 
Analynk Wireless Enclosure Options and More
Analynk Wireless Enclosure Options and MoreAnalynk Wireless Enclosure Options and More
Analynk Wireless Enclosure Options and More
 
Industrial Wireless Communications - Hazardous Area Antennas
Industrial Wireless Communications - Hazardous Area AntennasIndustrial Wireless Communications - Hazardous Area Antennas
Industrial Wireless Communications - Hazardous Area Antennas
 
Tachometer transmitter for industrial process measurement and control
Tachometer transmitter for industrial process measurement and controlTachometer transmitter for industrial process measurement and control
Tachometer transmitter for industrial process measurement and control
 
Cavitation Control in Process Control Valves
Cavitation Control in Process Control ValvesCavitation Control in Process Control Valves
Cavitation Control in Process Control Valves
 
Defending industrial control systems from cyber attack
Defending industrial control systems from cyber attackDefending industrial control systems from cyber attack
Defending industrial control systems from cyber attack
 
Solar power supply for industrial wireless transmitters
Solar power supply for industrial wireless transmittersSolar power supply for industrial wireless transmitters
Solar power supply for industrial wireless transmitters
 
Signal Alarms for Process Monitoring
Signal Alarms for Process MonitoringSignal Alarms for Process Monitoring
Signal Alarms for Process Monitoring
 
Hazardous Area Wireless Equipment Enclosures
Hazardous Area Wireless Equipment EnclosuresHazardous Area Wireless Equipment Enclosures
Hazardous Area Wireless Equipment Enclosures
 
Analynk Model A16000 RF Expansion Module
Analynk Model A16000 RF Expansion ModuleAnalynk Model A16000 RF Expansion Module
Analynk Model A16000 RF Expansion Module
 
Alokin Lightning Shield Protects Equipment
Alokin Lightning Shield Protects EquipmentAlokin Lightning Shield Protects Equipment
Alokin Lightning Shield Protects Equipment
 
Hazardous Area Antenna - Iridium Satellite Communication
Hazardous Area Antenna - Iridium Satellite CommunicationHazardous Area Antenna - Iridium Satellite Communication
Hazardous Area Antenna - Iridium Satellite Communication
 
Hazardous Area Explosion Proof Antenna for GLONASS, GPS, and IRIDIUM
Hazardous Area Explosion Proof Antenna for GLONASS, GPS, and IRIDIUMHazardous Area Explosion Proof Antenna for GLONASS, GPS, and IRIDIUM
Hazardous Area Explosion Proof Antenna for GLONASS, GPS, and IRIDIUM
 
RF Wireless DIN System
RF Wireless DIN SystemRF Wireless DIN System
RF Wireless DIN System
 

Dernier

UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSISrknatarajan
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Christo Ananth
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...ranjana rawat
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxupamatechverse
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxupamatechverse
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...Call Girls in Nagpur High Profile
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...Call Girls in Nagpur High Profile
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)simmis5
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTINGMANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTINGSIVASHANKAR N
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlysanyuktamishra911
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingrknatarajan
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdfankushspencer015
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
 

Dernier (20)

UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSIS
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTINGMANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 

Lightning Protection Considerations for Wired Systems

  • 1. IEEE Guide for the Protection of Communication Installations from Lightning Effects IEEE Power Engineering Society Sponsored by the Power Systems Communications Committee IEEE 3 Park Avenue New Yarkr NY 10016-5997 USA 15 August 2011 IEEE Std 1692"1-2011
  • 2. © Alokin Industries LLC Lincoln, Nebraska Second Edition April 2014 The objective of this Abstract is to clarify technical concepts and provide informative background for the practitioner. Whereas IEEE 1692-2011 primarily addresses theory and installation detail for wireless sites, this Abstract extends the application discussion to wire-line sites. IEEE 1692-2011 was produced by the Power Systems Communications Committee of the IEEE Power Engineering Society and released in August, 2011. For detail information regarding IEEE 1692-2011 refer to http://ieeexplore.ieee.org You are welcome to address comments or questions to Alokin at: info@alokin.com 1-800-501-2910
  • 3. Table of Contents IEEE 1692-2011 I Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 II Basic Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 A. Equi-potential Ground Plane B. Grounding – Soil Resistivity C. Surge Protection – Application Considerations III Power Line Strikes and Flashovers . . . . . . . . . . . . . . . . . . . 4 A. Lightning – Flashover Dynamics B. Surge Protection – Performance Limitations C. Recommended Solution – AC Isolation IV Lightning Ground Potential Rise (L-GPR) . . . . . . . . . . . . . . . 6 A. Lightning – Discharge Dynamics B. Soil Resistivity – Ground Voltage C. Grounding – Frequency Dependent D. Fault Paths – Recommended Solutions V Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 AC Isolation I Technology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 A. Lightning Detector B. Controller C. AC Contactor II Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
  • 4.
  • 5. 1 IEEE 1692-2011 I Introduction Background Every year, communications equipment in the outside plant (OSP) suffers millions of dollars of damage. A severe lightning storm in rural America typically means loss of service, truck rolls, non-warranty parts replacement and insurance claims. Most of the damage is unexplained or not investigated, and yet is preventable. IEEE 1692 is the first industry publication that provides guidance for lightning protection of electronic communications equipment in the OSP environment. Related documents, NFPA 70 (the national electric code), NFPA 780 and NESC only address the protection of buildings and personnel safety. Purpose The purpose of this IEEE 1692 Abstract is to: 1. familiarize the reader with the faults that are accountable for most of the unexplained lightning related damage, and 2. explain the advantages of blocking technologies to effectively isolate and protect communications equipment. Action Readers are encouraged to thoroughly review the recommendations for application to their networks.
  • 6. 2 Fig 1. Simplified Equi-potential plane design Fig 2. Soil Resistivity Values of Common Earth Compositions II Basic Protection Most lightning threats to communications equipment in urban areas can be mitigated by appropriate surge protection and grounding practices. A. Equi-potential Ground Plane Essential to all lightning protection strategies is keeping all ground points close to the same potential to minimize voltage differentials: 1. Connect all equipment grounds to a common ground bar, 2. Connect all power and communication structures on site to a common (single point) ground, and 3. Locate grounding ingress/egress at ground level to minimize the voltage differential with respect to ground. B. Grounding – Soil Resistivity The effectiveness of a grounding system is dependent on multiple factors such as soil resistivity, grounding electrode contact with the earth, and arrangement of the grounding components (rods, wires and bars). However, achieving low ground resistance (5 Ohms or less) may not be practical or even possible in higher soil resistivity conditions. Referring to Figure 2, sand-gravel, limestone and granite are 20 to 100 times more resistive than surface soils and clay.1 Sand-gravel and limestone encompass a broad range of possible soil resistivity values that may significantly vary within a given area. Dehydration during arid seasons dramatically increases soil resistivity.2 L-GPR produced by “dry lightning“ can be extremely damaging (refer to Pg. 7, Soil Resistivity-Ground Voltage). 1 USDA Bulletin 1751F-670 2 Ibid Fig 3. Surface Dehydration effect on Soil Resistivity
  • 7. 3 Fig 4. Mutual Inductance of Ground Rods To achieve lower 60Hz impedance in multi- electrode grounds it is necessary to assure the electrodes are as far apart as they are deep to minimize the mutual inductance between the electrodes. Mutual inductance reduces the grounding efficiency for all frequencies. 3 However, longer or additional ground electrodes do not reduce the grounding impedance behavior at the lower lightning frequencies (refer to Pg 7, Grounding-Frequency Dependent). Grounding is subject to degradation from corrosion and other environmental factors and requires periodic maintenance and testing to maintain desired ground resistance. C. Surge Protection – Application Considerations Surge Protection Devices (SPDs) have proven to be an effective deterrent against most power and signal line threats. Surge protection responds to elevated voltage and redirects the energy to the return conductor or ground - the intended primary fault paths in Figure 5. SPD failure produces the destructive secondary fault paths. All mode protection (L-L, L-N, L-G & N-G) is necessary for primary protection of outside plant electronic sites. NFPA 70 (NEC) permits only one neutral-ground bond at the site, located at the service disconnect. A second N-G bond after the service disconnect can circumvent circuit breaker protection. . The neutral ground mode on a secondary SPD at the Power Distribution Panel must be disabled, which may otherwise provide an additional fault path for elevated voltage on the master ground bar during a GPR event (refer to Pg. 9, Fault: Ground System Transients). 3 Megger, Getting Down to Earth, 2010, P38 Fig 5. AC and Signal line SPD Protection Fig 6A. Primary SPD Modes Fig 6B. Secondary SPD Modes
  • 8. 4 Surge protectors are reactive devices. The response of surge protectors allows let-through voltage that may fatigue sensitive electronic circuits over time. Hybrid SPDs combine faster reaction and high capacity to reduce let through voltage. III Power Line Strikes & Flashovers A direct strike to a power line or signal cable creates high voltage transients that can produce destructive current on the conductors. The extreme voltage and current produced by a lightning strike can overwhelm the best SPD. A. Lightning – Flashover Dynamics Lightning produces an extremely high current pulse than can momentarily reach 200KA within 2uSec. 4 The familiar vulnerability to lightning is a transient. Despite the use of a protective ground wire, lightning current can flashover from the ground wire to a phase or neutral line. If the protecting ground wire exhibits a high impedance to ground, a significant voltage can develop that exceeds the air breakdown value (~3MV/m), allowing the lightning current to arc to a phase or neutral conductor, impressing severe current on the terminal circuits. 5 4 The Lightning Discharge, Martin A. Uman, International Geophysics Series, Vol 39, 1987, Pg 341 5 Handbook of Chemistry and Physics, Chemical Rubber Company, any recent edition Fig 8. Simplified Lightning Discharge Profile Fig 9, Power line Flashover Fig 7. SPD Let-through Voltage
  • 9. 5 B. Surge Protection – Performance Limitations The threshold voltage of an SPD is not an ideal constant. The actual performance of surge protection is subject to the applied voltage. Higher voltage increases the current, and higher voltage across the SPD will be let through to connected equipment. Severe voltage produced by a direct strike or flashover may expose the electronic circuits to very high let- through voltage, potentially damaging equipment and the SPD. C. Recommended Solution – AC Isolation AC Isolation provides protection from flashovers and other severe utility transients. Detection of lightning before the strike preemptively opens the AC circuit, blocking transients that may otherwise overwhelm surge protection. During isolation from AC power, operations safely continue on resident DC power until the threat has passed, at which time AC power is automatically re-connected. Fig 10. SPD Performance is Current Dependent Fig 11. AC Isolation Solution of Severe Power Line Transients
  • 10. 6 Fig 13. Post-Strike Ground Charge Motion Fig 14. Ground Voltage Gradients Fig 12. Pre-Strike Ground Charge Motion IV Lightning Ground Potential Rise (L-GPR) IEEE-1692 primarily focuses on the threat posed by L-GPR, undoubtedly the least understood and consequently, least protected lightning threat. The energy from a lightning ground strike is not immediately dissipated in local earth. The voltage of the earth rises as energy is radiated outward creating momentary voltage gradients between ground points. A. Lightning – Discharge Dynamics Lightning is an electrostatic discharge – a transfer of electrical charge between the cloud and ground. Prior to a strike, negative charge accumulates in the lower portion of a storm cell causing a concentration of offsetting positive charge in the earth. During this process the earth’s normal electric field of 100V/m increases to over 2,000 V/m and changes from negative to positive polarity 6 . Prior to discharge, the voltage differential between the cloud base and earth dramatically rises to between 10M and100M volts. 7 The discharge produces ground current that radiates through the earth’s surface in all directions. The peak current amplitude of a lightning strike ranges from 5KA to 200KA. There are typically 3 to 4 discharges per lightning channel (the visible flicker is repetitive ground strikes). 8 Consequently, successive waves of energy are radiated from the strike point. The discharge creates voltage gradients radiating from the strike point, comparable to the waves created by a rock striking a water surface. The 5 - 200KA lightning current converts to ground current. 6 Lightning, Martin A. Uman, Dover Publications, ISBN 0-486-64575-4, Pg 48, 51 7 Ibid, Pg 214-215 8 Lightning, Martin A. Uman, Dover Publications, ISBN 0-486-64575-4, Pg 4
  • 11. 7 B. Soil Resistivity – Ground Voltage Soil resistivity is a significant determinant of the voltage, or potential, gradient. Higher soil resistivity produces higher voltage potentials for a given current. At a half-mile distance, an average lightning strike of 25KA produces very low voltage in a soil-clay region. However, a site with a sand-gravel composition will be exposed to potentially damaging voltage. The diagram below displays approximate ground potentials. (Referring to the dashed line in Figure 15, a 25KA strike in limestone measuring 2,000 Ohm-M produces a gradient potential of 30,000V over one half mile.) Caveat: Communication sites in urban areas are relatively immune to the L-GPR threat due to the extensive underground infrastructure that is highly conductive, substantially reducing the effective soil resistivity. By contrast, rural areas characterized by elevated soil resistivity are highly vulnerable to just one near-proximity ground strike. C. Grounding – Frequency Dependent Grounding is designed to provide a low impedance current path to earth for both safety and equipment protection purposes. However, grounding systems behave differently at different frequencies. Grounding is a very effective conductor at very low frequencies, as demonstrated by grounding resistance tests typically conducted at 50 –150Hz. However, grounding is inductive at the lower frequencies of lightning between 5KHz and 500KHz. 9 9 IEEE Transaction on Power Deliver, Vol 23, No 4, October 2006, Triggered Lightning Experiments; Brian DeCarlo, Vladimir Rakov, et.al Fig 15. Soil Resistivity effect on L-GPR Voltage Fig 16. Grounding Effectiveness is Frequency Dependent
  • 12. 8 The resulting high impedance at these frequencies significantly affects the current path. The referenced studies found that in higher resistivity earth over 50% of the lightning current impressed on the grounding system was forced onto the AC phase and neutral lines. Although longer or additional grounding electrodes reduce AC-60Hz impedance, the higher inductance of longer ground rods may also increase the impedance for the low-range frequencies of lightning. D. Fault Paths – Recommended Solutions The unexplained lightning related damage to communications equipment is typically attributable to an L-GPR fault, inducing either a signal line transient or a ground system transient. A signal line transient is evident if the protectors have failed. However, a ground system transient can inflict significant equipment damage without affecting the protectors. Fault: Signal Line Transients The lightning discharge current on cable shields can induce currents on adjacent conductors, producing high voltages in cables and electrical equipment. The shield current produces a magnetic field which couples to the signal lines and produces a current in the opposite direction. Note that a similar fault may be caused by 60Hz GPR in close proximity to a power substation or generation plant. Recommended Solution: Optical Isolation Optical Isolation inserts a dielectric path for signal lines that may otherwise expose personnel or equipment to voltage transients. Applications include: 1. Service centers that potentially expose operators 2. Services to high voltage facilities - substations and power generation plants 3. Class A facilities that must continuously operate in all circumstances Fig 17. Magnetic Field Induced Current Fig 18. Optical Isolation Solution of Signal line Transients
  • 13. 9 Fig 20. SPD conduction of L-GPR Fault: Ground System Transients Single point grounding of the communication’s site seeks to achieve an equi-potential ground plane that assures very low voltage differentials between bonded ground circuits, and thus little threat of fault current. However, connection to the AC power service introduces a remote, lower potential ground reference during an L-GPR event. The high potential difference between the communications ground and the AC service ground makes the power phase and neutral lines a preferred discharge path between the grounds. The safety ground is only partially effective because of the higher impedance to lightning frequencies. 10 The grounding system near a lightning ground strike elevates in potential with respect to other grounds. The voltage impressed on the grounding system elevates the master ground bar (MGB). The signal line surge protectors are connected to the MGB. SPDs are bi-directional devices (to protect against positive and negative polarity transients 11 ) and activate if the MGB voltage exceeds their threshold. The activated SPD provides a conductive path for the elevated MGB voltage to the Tip and Ring circuits. A fault path is created to the lower potential ground references on the signal line terminations and the remote power ground circuit for the electronics equipment. Voltage on the subscriber circuit is substantially dissipated over the intervening distance. However, there is a significant potential difference on the adjoining power circuit, exposing the communications equipment. Referring to Figure 20, if the MGB experiences a LGPR of 1,000V and the SPD has a 250V threshold, about 750V is applied to the Tip and Ring line card circuits relative to remote ground. 10 The Self and Mutual inductance of linear conductors, Edward B. Rosa, Bulletin of the Bureau of Standards, Vol 4, No. 2, 1908 Pg 301-344 11 IEEE Std C62.45-1992 Fig 19. Ground System Fault Path
  • 14. 10 Recommended Solutions Radial Grounding (for tower sites) - recognizes the frequency limitations of vertical grounding. Since current from a lightning ground strike radiates near the surface12 , radials off the vertical grounding reduce the grounding impedance to the low-range frequencies of lightning. 1. The combination of vertical and horizontal electrodes provides lower impedance grounding. 2. The radials increase the capacitive coupling between the grounding system and the earth. 3. However, the effectiveness of the radial grounding diminishes in soil resistivity over 500 Ohm-M. 13 AC Isolation - detects lightning before the strike and preemptively disconnects the utility power phase and neutral circuit. Opening the power circuit creates a single point ground condition, effectively isolating the communications equipment and blocking the fault path. Absent a secondary path, the lightning energy is forced to dissipate through the grounding system. Communications are continuously maintained on battery or generator power during the isolation period. Utility power is automatically restored after the threat has passed. AC Isolation requirements: 1. Standby power is required to maintain operations during the isolation period. 2. The AC Isolator also includes an AC voltage monitor that responds to AC surges and sags within 3 cycles. However, the AC Isolator must be installed on the line side of the primary SPD to provide an initial fast response to AC transients caused by non-lightning events (e.g. capacitor bank switching and inductive motor switching). 12 An Examination of Lightning Strike Grounding Physics: C.B. More, G.D. Aulich and William Rison; Langmuir Laboratory for Atmospheric Research 13 IEEE 1692-2011, 8.1 Note 3 Fig 21. Radial Grounding for Towers Fig 22. AC Isolation of Ground System Transients
  • 15. 11 V Summary Lightning energy radiates outward through the atmosphere, the earth’s surface and all conductors over a wide frequency range. Rural and remote communication’s installations are particularly vulnerable to lightning. New protection technologies have evolved to augment traditional protection practices and effectively mitigate the lightning threat. Critical to a solution is correct diagnosis of the problem. Sites with good grounding and surge protection practices are still vulnerable to severe power line faults and lightning ground potential rise (L-GPR). In fact, both grounding and better surge protection actually facilitate the L-GPR fault path. Effective protection against lightning damage requires a combination of technologies to address unique circumstances. The recommended protection strategies are: 1. All exposures: Optimize the equi-potential ground plane, within the limitations of local soil resistivity 2. AC Transients: Primary all-mode surge protection AC Isolation for power line strikes and flash-over exposure 3. Lightning Ground Potential Rise (L-GPR): Optical Isolation for signal line transients AC Isolation for grounding system transients Radial grounding for towers with available real estate and low soil resistivity Note: The effectiveness of the blocking technologies - Optical Isolation and AC Isolation, is not subject to soil resistivity or the resistance of the grounding system. A high resistance ground will just take a little longer to dissipate the blocked energy. Augmenting traditional protection practices with the appropriate blocking technology affords the best protection strategy to minimize lightning related damage.
  • 16. 12
  • 17. 13 AC Isolation I Technology If L-GPR is the least understood lightning phenomenon, then AC Isolation is the least recognized solution. AC Isolation is: 1. A blocking technology – open circuits the potential fault path to the communications equipment 2. Pre-emptive – disconnects the fault path before the threatening ground strike occurs 3. Intelligent – discriminates lightning ground strikes from other electric field phenomenon The AC Isolation technology is comprised of three components: a Lightning Detector, a Contactor to disconnect/re-connect AC power and a Controller that manages the detection and isolation functions and provides connection to remote communications. The Contactor is an electro-mechanical device with a response time of about 15mSec – too slow to react to a nearby lightning event. Consequently, the AC Isolator must discriminate the potential lightning threat before the ground strike occurs to provide sufficient time for the Contactor to isolate the communications equipment. A. Lightning Detector Reliable detection of lightning ground strikes requires discrimination of the electric field orientation. Cloud to ground lightning is primarily a vertical electric field, whereas cloud to cloud lightning and electromagnetic transmission are primarily horizontal fields. Prior to a stroke discharge, the development of a lightning channel rapidly changes the electric field strength at ground level. L-GPR produced by a remote ground strike causes a significant ground potential increase that also produces an electric field change. The Lightning Detector is responsive to both events. The electric field change is detected, converted to voltage and compared to the Lightning Detector threshold. If it exceeds the threshold, isolation is initiated. Figure 23 depicts the increasing L-GPR amplitude from an approaching storm. Low soil resistivity areas (T) that readily dissipate L-GPR energy produce a weaker electric field change, requiring a more sensitive detection threshold. For the same lightning strike, high resistivity soil (S) dissipates less L-GPR energy, producing a stronger field change. A less sensitive detection threshold is necessary to ignore distant lightning activity that is not threatening. Fig 23. Detection Sensitivity based on Soil Resistivity
  • 18. 14 The Lightning Detector circuitry provides: 1. Sensitivity adjustment for user specification of the detection range based on the local soil conditions, 2. A voltage comparator to evaluate the differential voltage caused by the changing electric fields near the earth, 3. Communication with the Controller to open/close the Contactor controlling the AC service, and 4. User test of the detection and communication circuits B. Controller The Controller opens the Contactor in response to a signal from the Lightning Detector or an internal AC voltage monitor, based on the user specified thresholds. 1. The AC detector monitors the AC power service with two voltage comparators to detect fast transients and slower surge/sag activity. 2. Adjustable count-down timers determine the initial isolation period for L-GPR and AC power threats. Subsequent threat detection during an isolation period restarts the respective timer. 3. AC power is re-connected after it stabilizes within the user defined thresholds. Consequently, the communications equipment is protected from power recovery transients. 4. The Controller targets re-connection of AC power at the zero voltage cross-over to mitigate local switching transients and minimize in-rush currents. 5. Alarm relays are provided for connection to the site alarm panel. A Remote Controller provides several additional features: 1. Remote communications on an Ethernet or POTS connection, 2. Remote monitoring of threat activity and adjustment of protection settings (detection thresholds and isolation timers), 3. Event logging and remote download of threat activity and the corresponding protection response; the log may be correlated with 3 rd party lightning data, 4. Remote monitoring of the battery plant or test of the stand-by generator, and 5. Remote test of the AC Isolator. C. Contactor The Contactor disconnects the phase and neutral lines; the safety ground is not disconnected. The Contactor is sized equal to or greater than the amperage of the AC service. For example, equipment wired off a 200A service disconnect requires a 200A contactor; equipment wired off the load center may only require a 60A contactor, or less. Contactors for this application are rated for several million cycles.
  • 19. 15 II Installation Installation typically requires the services of a commercial electrician. The Controller is installed: A. off the service disconnect, on the load side of primary AC SPD, and before the transfer switch, B. or, off the load center and before the cabinet power distribution panel The Controller may be mounted externally on a power pedestal, an adjoining frame, or on the interior wall of a shelter. The Lightning Detector must be mounted externally with a 360o view that is unobstructed for a minimum 8 feet. Fig 24. Typical Wireless Site (Cell Tower) Installation Fig 25. Typical Wire-line Site (Remote Terminal) Installation
  • 20. 16
  • 21. 17 Glossary AC Isolation. The physical disconnection of the AC utility power from electronic systems to protect against power transients and lightning ground potential rise. Typically an automatic process based on detection sensor(s). All Mode (ref SPD). An AC surge protector that provides all modes of power protection, Typically referenced to 240V split phase and 3 phase power systems. The modes are: Line-Neutral (L-N), Line-Line (L-L), Line-Ground (L-G) and Neutral-Ground (N-G) Capacitance. The property of parallel conductive surfaces to store energy in an electrical field between the surfaces. The degree of capacitance varies directly with the area of the parallel plates and inversely to the distance of separation between the plates. A property of a capacitor is to pass AC signals and block DC signals. The AC impedance will vary inversely with frequency. Contactor. A relay that is designed to control power in AC power systems. A contactor is frequently used in electric motor starters and electrical power panels. Equi-potential. Pertaining to equal electrical potential; where all points on the grounding system (sometimes referred to as a plane) strive to be at the same potential to mitigate ground current loops. Flashover. A current arc from one conductor to another when struck by lightning. A typical example is a lightning strike to the ground protection wire on an aerial power line that arcs to the phase or neutral line below. In the first several uSec of lightning contact the immediate voltage can exceed 100KV while the impedance to ground can be very high. The phase lines are at a moderate voltage with respect to ground and provide another path to ground, as does the neutral line. GPR (Ground Potential Rise). The increase of electrical potential in the earth with respect to another location. This may result from a downed power line or a power distribution fault, referred to as 60Hz GPR; or a lightning ground strike (L-GPR). GPR is typically a momentary condition and magnitudes can vary between mV and KV. Ground. A direct physical connection to the earth, or a reference point in an electrical circuit from which other voltages are measured. Ground Resistance. Ground resistance is the resistance of the grounding system to current flow. However, ground impedance is a more complete characterization of grounding conductivity that includes capacitive and inductive reactance. Grounding impedance is primarily a function of soil resistivity, surface area contact with grounding electrodes and the physical dimensions of the conductors. Ground Ring. A series of buried grounding electrodes connected by a conductor such as a wire or cable, in direct contact with the earth encircling the grounded structure. Grounding Electrode. More commonly called a ground rod which is driven into the earth for the purpose of providing an electrical connection to the earth. Impedance. The total opposition to current including resistance, inductive reactance and capacitive reactance. In DC circuits there is no reactance and the impedance is just the resistance. (Refer to Reactance) Inductance. The property of a conductor that provides a direct opposition to AC current from a self induced magnetic field caused by a change in current. L-GPR (Lightning Ground Potential Rise). Ground potential rise created by a lightning ground strike. L-GPR radiates in all directions and is typically more severe than 60Hz GPR which returns to the distribution source. L-GPR creates extreme potential differentials across the earth surface. The differential voltages decrease with distance based on soil conditions.
  • 22. 18 MGB (Master Ground Bar). A metal bar used as a common grounding point in communication systems. The MGB contributes to providing a single point ground. Neutral-Ground Bond. The point where the power neutral line and ground are bonded together at the power transformer and the power service disconnect. NEC requires an N-G bond at the service disconnect location; no other N-G bonds are permitted after that point. Neutral-Ground Mode (SPD). The protection mode in a surge protector that limits voltages between the neutral and ground lines. Other modes are line to neutral and line to line. Not all surge protectors have a N-G mode. Optical Isolation. Use of a di-electric plastic fiber to transmit signals and concurrently isolate the electronics on either side of the fiber from each other electrically. Potential (Electric Potential or Voltage). A description of the difference in potential energy (per unit charge) between points in an electric field. The concept is exemplified by the voltage between two battery terminals. The magnitude of potential is an indicator of the ability to move charge. In Ohms Law the voltage determines how much current will flow through a given resistor. Reactance. The opposition to alternating current due to capacitance (capacitive reactance) or inductance (inductive reactance). Reactance plus resistance equals impedance. Resistance. The property of a material to oppose the flow of electrical current. Resistance is comparable to friction in mechanical systems. In Ohms Law a given resistance will allow a specific current for a given voltage. Rise Time. The measure of time for an electrical signal to go from the lowest to the highest level. Typically measured between the 10% and 90% levels. Service Disconnect. A switch at the AC utility service entrance that allows disconnection of the service from the load circuits. A circuit breaker is typically used as both overload protection and switch. The circuit breaker rating defines the current limit of the service. Single Point Ground. A grounding system design that ensures all ground conductors from the electronics equipment are connected to a single point on the grounding electrode or ground ring. A single point ground mitigates ground current loops and ground potential differences. Soil Resistivity. A measure of soil’s ability to oppose conductance of electrical current. Soil resistivity is measured in units of Ohm-meters or Ohm-centimeters. Soil resistivity values can vary significantly from 2 to 10,000 ohm-meters. Moisture content can significantly affect soil resistivity, particularly during prolonged seasonal changes. SPD. A surge protection device is used to mitigate transients and surges on power and signal lines by limiting the voltage between the SPD terminals. An SPD has a high resistance in a normal voltage range and low resistance in higher than normal voltages. The conduction voltage level is referred to as the threshold level. There are various technologies used in SPD’s that offer tradeoffs between speed of operation, protection voltage threshold and energy carrying capacity. Transient. Transient describes short term excess voltage on power or signal lines. The time duration can vary from a few milliseconds to nanoseconds. Excess voltages can exceed several thousand volts. The cause of a voltage transient can be lightning or power switching equipment.