POWER FACTOR
Basics
and
Benefits of Improvement
Power Factor Basics
• In all industrial electrical distribution systems, the major loads are resistive and inductive. Resistive loads
are incandescent lighting and resistance heating. In case of resistive loads the voltage (v) , current (I),
resistance relations are linearly related, i.e. V= I x R and Power (kW) = V x I
• Typical Inductive loads are A.C. Motors, Transformers and ballast –type lightings. Inductive loads require
two kinds of power : a) Active power (kW) to perform the work and b) Reactive power ( KVAr) to create
and maintain electro-magnetic field.
• The vector sum of the active power and reactive power make up the total (or apparent) power used
which is measured in KVA
• The ratio of KW to KVA is called the Power Factor which is always less than or equal to unity. Theoretically, if the loads have
unity power factor, maximum power can be transferred for the same distribution system capacity.
• However, as the loads are inductive in nature, with the power factor ranging from 0.2 to 0.9, the electrical distribution
network is stressed for the capacity at low power factor.
KVAR
Reactive Power
KW
Active Power
KVA
Total Power
KW, KVAr and KVA Vector Diagram
PF = KW / KVA
= Cos ф
Cos ф
• The active power (shaft power required) in KW and the reactive power required in (KVAr) are 900 apart vectorially in a pure
inductive circuit i.e. reactive power lagging active power. The vector sum of two is called the apparent power KVA.
A Starch Industry had installed a 1500 KVA transformer. The initial demand of the plant was 1160 KVA with power factor of 0.70 . The %
loading of transformer was about 78% ( 1160/1500 = 77.3 %) .
To improve the power factor and to avoid the penalty, the unit had added about 410 KVAr capacitor in motor load end. This improves
the PF to 0.89 and reduced the required KVA to 913 which is vector sum of KW and KVAr.
KVAR =828
KW=812
Cos ф =0.70
PF =812/1160
= 0.70
KVA=1160
KW=812
KVAR=
828-410=418
KVA=913
PF= 812/913
= 0.89
After improvement, the penalty will be avoided and the 1500 KVA transformer is now
loaded only to 60% capacity. The transformer can now also be loaded more in the future.
Cos ф =0.89
Example
Advantages of Power Factor Improvement
• Reactive component of the network reduced
and so also the total current in the system
from the source end.
• I2 R losses of the system are reduced because
of reduction in current.
• Voltage level at the load end is increased.
• KVA loading on the source Generators,
transformers and lines up to capacitor
reduces giving capacity relief.
• A high power factor can help in utilizing the
full capacity of the electrical system
Cost Benefits of PF improvement
• Reduction in KVA demand ( Maximum
demand) charges in utility bill.
• Distribution losses (KWH) reduced within the
plant network.
• Better voltage at motor terminals and
improved performance of motors.
• A high power factor eliminates penalty
charges imposed when operating at low
power factor.
• Reduction in investment on kVA rating of
transformers , Cables, switchgear etc as its
delivering load reduces.
KW / KVA = Cos ф1
KVAr / KVA = Sin ф1
KVAr/ KW = Sin ф1 / Cos ф1
KVAr/ KW = Tan ф1
KVAr = KW X Tan ф1
KVAr required to improve the power factor
from Cos ф1 to Cosф2 will be
KVAr = KW ( tan ф1 – tan ф2 )
Example: The utility bill shows an average power factor
of 0.72 with an average kw of 650 . How much KVAr is
required to improve the power factor to 0.95.
Cos ф1 = 0.72 , tan ф1 = 0.963
Cos ф2 = 0.95 , tan ф2 = 0.329
KVAr required = KW ( tanф1 – tanф2)
= 650 ( 0.963 -0.329 ) = 412 KVAr
• The primary purpose of capacitors is to reduce the maximum demand. Maximum benefits of capacitors is derived by
locating them as close as possible to the load.
• At this location , its KVAr are confined to the smallest possible segment, decreasing the load current .This in turn will
reduce power losses of the system substantially .
• Power losses are proportional to the square of the current . When power losses are reduced, the voltage at the motor
terminals increases ,thus motor performance also increases.
Selection and location of capacitors
Operational Performance of Capacitors
•This can be made by monitoring capacitor charging current via the rated charging current.
• The capacity of fused elements can be replenished as charging current.
•The portable analyzer can be used for measuring KVAr delivered as well to charging current.
•Capacitors consume 0.2 to 6.0 watt per KVAr, which is negligible in comparison to benefits
• Nameplates can be misleading with respect to rating . It is good to check
by charging current.
• Capacitor boxes may contain only insulated compound and insulated
terminals with no capacitor element inside.
• Capacitors for single phase motor starting and those used for lighting
circuit for voltage boost are not power factor capacitor units and these
cannot withstand power system conditions.
Some basic checks for the Capacitors :
• Induction motors are characterized by power factor less than unity i.e. lagging PF. It leads to lower overall
efficiency and higher overall operating cost.
• The capacitors are connected in parallel with motor to improve power factor.
• The impacts of PF correction include :
• reduced KVA demand (and hence reduced utility demand charges),
• reduced I2R losses in cables upstream of the capacitors (and hence reduced energy charges),
• reduced voltage drop in the cables (leading to improved voltage Regulation).
•This increases the overall efficiency of the plant.
• The size of capacitors required for a particular motor should not exceed 90% of the no load KVAr of the
motor.
Power factor correction of Motors
The capacitor rating for power connection by direct connection to induction motors
is shown below.
Motor
Rating ( HP)
Capacitors Rating ( KVAr) for Motor Speed
3000 1500 1000 750 600 500
5 2 2 2 3 3 3
7.5 2 2 3 3 4 4
10 3 3 4 5 5 6
15 3 4 5 7 7 7
20 5 6 7 8 9 10
25 6 7 8 9 9 12
30 7 8 9 10 10 15
40 9 10 12 15 16 20
50 10 12 15 18 20 22
60 12 14 15 20 22 25
75 15 16 20 22 25 30
100 20 22 25 26 32 35
125 25 26 30 32 35 40
150 30 32 35 40 45 50
200 40 45 45 50 55 60
250 45 50 50 60 65 70
Power Factor : Basics and  Benefits of Improvement

Contenu connexe

Tendances

Tendances (20)

Reactive power compensation
Reactive power compensationReactive power compensation
Reactive power compensation
 
Series & shunt compensation and FACTs Devices
Series & shunt compensation and FACTs DevicesSeries & shunt compensation and FACTs Devices
Series & shunt compensation and FACTs Devices
 
Unified Power Flow Controller(upfc)1
Unified Power Flow Controller(upfc)1Unified Power Flow Controller(upfc)1
Unified Power Flow Controller(upfc)1
 
Economic operation of Power systems by Unit commitment
Economic operation of Power systems by Unit commitment Economic operation of Power systems by Unit commitment
Economic operation of Power systems by Unit commitment
 
Load on power system
Load on power systemLoad on power system
Load on power system
 
Unit5ppts
Unit5pptsUnit5ppts
Unit5ppts
 
Principles of Power Systems V.K Mehta Complete Book - Chapter 2
Principles of Power Systems V.K Mehta Complete Book - Chapter 2Principles of Power Systems V.K Mehta Complete Book - Chapter 2
Principles of Power Systems V.K Mehta Complete Book - Chapter 2
 
Power factor improvement
Power factor improvement Power factor improvement
Power factor improvement
 
Power quality ppt
Power quality pptPower quality ppt
Power quality ppt
 
Introduction to Power Quality Problems
Introduction to Power Quality ProblemsIntroduction to Power Quality Problems
Introduction to Power Quality Problems
 
Restructuring of power grid
Restructuring of power gridRestructuring of power grid
Restructuring of power grid
 
Wind Power Generation Schemes
Wind Power Generation SchemesWind Power Generation Schemes
Wind Power Generation Schemes
 
demand side management
demand side managementdemand side management
demand side management
 
importance of reactive power in power system
importance of reactive power in power systemimportance of reactive power in power system
importance of reactive power in power system
 
Microturbine ppt
Microturbine pptMicroturbine ppt
Microturbine ppt
 
Structure of power system
Structure of power systemStructure of power system
Structure of power system
 
Reactive power consumption in modern power system
Reactive power consumption in modern power systemReactive power consumption in modern power system
Reactive power consumption in modern power system
 
Tcsc ppt
Tcsc pptTcsc ppt
Tcsc ppt
 
economics of power generation
economics of power generationeconomics of power generation
economics of power generation
 
Unit-V-Power Plant Economics and Environment.pptx
Unit-V-Power Plant Economics and Environment.pptxUnit-V-Power Plant Economics and Environment.pptx
Unit-V-Power Plant Economics and Environment.pptx
 

Similaire à Power Factor : Basics and Benefits of Improvement

Power factor improvement of an induction motor
Power factor improvement of an induction motorPower factor improvement of an induction motor
Power factor improvement of an induction motor
IIT Roorkee
 
1590053 634881478003587500
1590053 6348814780035875001590053 634881478003587500
1590053 634881478003587500
Navyasri Jiguru
 
2006_18_spring_wiring_matters_power_factor_correction_pfc.pdf
2006_18_spring_wiring_matters_power_factor_correction_pfc.pdf2006_18_spring_wiring_matters_power_factor_correction_pfc.pdf
2006_18_spring_wiring_matters_power_factor_correction_pfc.pdf
asprilla mangombe
 
Energy Efficiency in Electrical Systems.pptx
Energy  Efficiency in Electrical Systems.pptxEnergy  Efficiency in Electrical Systems.pptx
Energy Efficiency in Electrical Systems.pptx
PoojaAnupGarg
 

Similaire à Power Factor : Basics and Benefits of Improvement (20)

Power Factor.ppt
Power Factor.pptPower Factor.ppt
Power Factor.ppt
 
powerfactor.pdf
powerfactor.pdfpowerfactor.pdf
powerfactor.pdf
 
Power factor improvement of an induction motor
Power factor improvement of an induction motorPower factor improvement of an induction motor
Power factor improvement of an induction motor
 
power factor correction soham+niraj
power factor correction soham+nirajpower factor correction soham+niraj
power factor correction soham+niraj
 
power factor and power factor correction schneider EMERSON EDUARDO RODRIGUES
power factor and power factor correction schneider EMERSON EDUARDO RODRIGUESpower factor and power factor correction schneider EMERSON EDUARDO RODRIGUES
power factor and power factor correction schneider EMERSON EDUARDO RODRIGUES
 
Mohsin rana
Mohsin ranaMohsin rana
Mohsin rana
 
1590053 634881478003587500
1590053 6348814780035875001590053 634881478003587500
1590053 634881478003587500
 
Day 3: Power Supply Quality in Buildings
Day 3: Power Supply Quality in Buildings Day 3: Power Supply Quality in Buildings
Day 3: Power Supply Quality in Buildings
 
PowerFactorImprovement.pptx
PowerFactorImprovement.pptxPowerFactorImprovement.pptx
PowerFactorImprovement.pptx
 
Automatic power factor correction and its advantage
Automatic power factor correction and its advantageAutomatic power factor correction and its advantage
Automatic power factor correction and its advantage
 
How Power Factor corection works.pdf
How Power Factor corection works.pdfHow Power Factor corection works.pdf
How Power Factor corection works.pdf
 
Power factor improvement
Power factor improvementPower factor improvement
Power factor improvement
 
Improvement of Load Power Factor by Using Capacitor
Improvement of Load Power Factor by Using CapacitorImprovement of Load Power Factor by Using Capacitor
Improvement of Load Power Factor by Using Capacitor
 
Application of Capacitors to Distribution System and Voltage Regulation
Application of Capacitors to Distribution System and Voltage RegulationApplication of Capacitors to Distribution System and Voltage Regulation
Application of Capacitors to Distribution System and Voltage Regulation
 
Electrical energy issues presented by arshad khan chiniot power limited
Electrical energy issues presented by arshad khan chiniot  power limitedElectrical energy issues presented by arshad khan chiniot  power limited
Electrical energy issues presented by arshad khan chiniot power limited
 
EDS Unit 5.pptx
EDS Unit 5.pptxEDS Unit 5.pptx
EDS Unit 5.pptx
 
2006_18_spring_wiring_matters_power_factor_correction_pfc.pdf
2006_18_spring_wiring_matters_power_factor_correction_pfc.pdf2006_18_spring_wiring_matters_power_factor_correction_pfc.pdf
2006_18_spring_wiring_matters_power_factor_correction_pfc.pdf
 
Energy Efficiency in Electrical Systems.pptx
Energy  Efficiency in Electrical Systems.pptxEnergy  Efficiency in Electrical Systems.pptx
Energy Efficiency in Electrical Systems.pptx
 
Transformers.ppt
Transformers.pptTransformers.ppt
Transformers.ppt
 
Power factor
Power factorPower factor
Power factor
 

Dernier

VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
dharasingh5698
 
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
dollysharma2066
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
ssuser89054b
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
amitlee9823
 
Integrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixIntegrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - Neometrix
Neometrix_Engineering_Pvt_Ltd
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
MsecMca
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
dharasingh5698
 

Dernier (20)

VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
 
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 
Minimum and Maximum Modes of microprocessor 8086
Minimum and Maximum Modes of microprocessor 8086Minimum and Maximum Modes of microprocessor 8086
Minimum and Maximum Modes of microprocessor 8086
 
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
 
Generative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPTGenerative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPT
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
 
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
 
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced LoadsFEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torque
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
 
A Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityA Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna Municipality
 
Work-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxWork-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptx
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.ppt
 
Integrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixIntegrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - Neometrix
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.ppt
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
COST-EFFETIVE  and Energy Efficient BUILDINGS ptxCOST-EFFETIVE  and Energy Efficient BUILDINGS ptx
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
 

Power Factor : Basics and Benefits of Improvement

  • 2. Power Factor Basics • In all industrial electrical distribution systems, the major loads are resistive and inductive. Resistive loads are incandescent lighting and resistance heating. In case of resistive loads the voltage (v) , current (I), resistance relations are linearly related, i.e. V= I x R and Power (kW) = V x I • Typical Inductive loads are A.C. Motors, Transformers and ballast –type lightings. Inductive loads require two kinds of power : a) Active power (kW) to perform the work and b) Reactive power ( KVAr) to create and maintain electro-magnetic field. • The vector sum of the active power and reactive power make up the total (or apparent) power used which is measured in KVA
  • 3. • The ratio of KW to KVA is called the Power Factor which is always less than or equal to unity. Theoretically, if the loads have unity power factor, maximum power can be transferred for the same distribution system capacity. • However, as the loads are inductive in nature, with the power factor ranging from 0.2 to 0.9, the electrical distribution network is stressed for the capacity at low power factor. KVAR Reactive Power KW Active Power KVA Total Power KW, KVAr and KVA Vector Diagram PF = KW / KVA = Cos ф Cos ф • The active power (shaft power required) in KW and the reactive power required in (KVAr) are 900 apart vectorially in a pure inductive circuit i.e. reactive power lagging active power. The vector sum of two is called the apparent power KVA.
  • 4. A Starch Industry had installed a 1500 KVA transformer. The initial demand of the plant was 1160 KVA with power factor of 0.70 . The % loading of transformer was about 78% ( 1160/1500 = 77.3 %) . To improve the power factor and to avoid the penalty, the unit had added about 410 KVAr capacitor in motor load end. This improves the PF to 0.89 and reduced the required KVA to 913 which is vector sum of KW and KVAr. KVAR =828 KW=812 Cos ф =0.70 PF =812/1160 = 0.70 KVA=1160 KW=812 KVAR= 828-410=418 KVA=913 PF= 812/913 = 0.89 After improvement, the penalty will be avoided and the 1500 KVA transformer is now loaded only to 60% capacity. The transformer can now also be loaded more in the future. Cos ф =0.89 Example
  • 5. Advantages of Power Factor Improvement • Reactive component of the network reduced and so also the total current in the system from the source end. • I2 R losses of the system are reduced because of reduction in current. • Voltage level at the load end is increased. • KVA loading on the source Generators, transformers and lines up to capacitor reduces giving capacity relief. • A high power factor can help in utilizing the full capacity of the electrical system
  • 6. Cost Benefits of PF improvement • Reduction in KVA demand ( Maximum demand) charges in utility bill. • Distribution losses (KWH) reduced within the plant network. • Better voltage at motor terminals and improved performance of motors. • A high power factor eliminates penalty charges imposed when operating at low power factor. • Reduction in investment on kVA rating of transformers , Cables, switchgear etc as its delivering load reduces.
  • 7. KW / KVA = Cos ф1 KVAr / KVA = Sin ф1 KVAr/ KW = Sin ф1 / Cos ф1 KVAr/ KW = Tan ф1 KVAr = KW X Tan ф1 KVAr required to improve the power factor from Cos ф1 to Cosф2 will be KVAr = KW ( tan ф1 – tan ф2 ) Example: The utility bill shows an average power factor of 0.72 with an average kw of 650 . How much KVAr is required to improve the power factor to 0.95. Cos ф1 = 0.72 , tan ф1 = 0.963 Cos ф2 = 0.95 , tan ф2 = 0.329 KVAr required = KW ( tanф1 – tanф2) = 650 ( 0.963 -0.329 ) = 412 KVAr • The primary purpose of capacitors is to reduce the maximum demand. Maximum benefits of capacitors is derived by locating them as close as possible to the load. • At this location , its KVAr are confined to the smallest possible segment, decreasing the load current .This in turn will reduce power losses of the system substantially . • Power losses are proportional to the square of the current . When power losses are reduced, the voltage at the motor terminals increases ,thus motor performance also increases. Selection and location of capacitors
  • 8. Operational Performance of Capacitors •This can be made by monitoring capacitor charging current via the rated charging current. • The capacity of fused elements can be replenished as charging current. •The portable analyzer can be used for measuring KVAr delivered as well to charging current. •Capacitors consume 0.2 to 6.0 watt per KVAr, which is negligible in comparison to benefits • Nameplates can be misleading with respect to rating . It is good to check by charging current. • Capacitor boxes may contain only insulated compound and insulated terminals with no capacitor element inside. • Capacitors for single phase motor starting and those used for lighting circuit for voltage boost are not power factor capacitor units and these cannot withstand power system conditions. Some basic checks for the Capacitors :
  • 9. • Induction motors are characterized by power factor less than unity i.e. lagging PF. It leads to lower overall efficiency and higher overall operating cost. • The capacitors are connected in parallel with motor to improve power factor. • The impacts of PF correction include : • reduced KVA demand (and hence reduced utility demand charges), • reduced I2R losses in cables upstream of the capacitors (and hence reduced energy charges), • reduced voltage drop in the cables (leading to improved voltage Regulation). •This increases the overall efficiency of the plant. • The size of capacitors required for a particular motor should not exceed 90% of the no load KVAr of the motor. Power factor correction of Motors
  • 10. The capacitor rating for power connection by direct connection to induction motors is shown below. Motor Rating ( HP) Capacitors Rating ( KVAr) for Motor Speed 3000 1500 1000 750 600 500 5 2 2 2 3 3 3 7.5 2 2 3 3 4 4 10 3 3 4 5 5 6 15 3 4 5 7 7 7 20 5 6 7 8 9 10 25 6 7 8 9 9 12 30 7 8 9 10 10 15 40 9 10 12 15 16 20 50 10 12 15 18 20 22 60 12 14 15 20 22 25 75 15 16 20 22 25 30 100 20 22 25 26 32 35 125 25 26 30 32 35 40 150 30 32 35 40 45 50 200 40 45 45 50 55 60 250 45 50 50 60 65 70