CPD Presentation - Smoke control and environmental ventilation in residential common corridors

Colt UK
Colt UKColt UK
Smoke control and environmental ventilation
in residential common corridors
CPD Presentation - Smoke control and environmental ventilation in residential common corridors
A Brief History



Private Company founded in 1931



I J O’Hea OBE (1897 - 1984)



Current Group Turnover £128 million



Manufacturing plants in the UK,
Holland, Germany, Saudi Arabia, China and Singapore

I J O’Hea.
Colt Founder
Current UK Business markets
Business Segments


Smoke Control



Building Products – Louvres and Shading



Climate – Environmental Control and Ventilation



Service
Contents
Business Segments


Introduction



Ventilation systems, extra requirements, performance



Design details



Cooling
The quest for energy efficiency (ADL and BREAAM) has led to very good
sealing and insulation in residential buildings and an increase in district heating
schemes.
This has unintended consequences for stair lobbies, corridors and entrance
halls, which tend to overheat, resulting in unpleasant conditions for residents
and possible issues maintaining cold water supply temperatures.

Caspian Wharf, a Berkley Homes development, uses a
district heating system and therefore overheating in the
common corridors was a concern for the design team.
Q: What can you do to avoid heat building up in these common areas?
A: Use the existing smoke control system for day-to-day ventilation.

The simple solution is to use the ventilation equipment which is already
providing smoke control to these areas.

Natural or mechanical smoke ventilation systems may be adapted for day-today ventilation use.
Q: Will you require additional equipment or modifications?
A: Yes, but the amount varies

If your building has a multiple shaft smoke control system, it can readily be
configured to provide day-to-day ventilation with minimal additions.

If the building has a single shaft system, you will need inlet air. You could
provide it from the stair, using a weathered roof smoke vent. In this case, you
will need fire rated smoke dampers between the stair and the corridor.

You will need to consider fan noise, as noise levels considered acceptable for
emergency use will not be acceptable for day-to-day ventilation use.
Smoke Ventilation of Common Corridors in Residential Developments

Legislation, Standards and Guidance
•

Approved Document B to the Building Regulations (ADB)

•

BS 9991

•

BS EN 12101 / BS 8519

•

Smoke Control Association Guide
(free download from www.feta.co.uk)
Smoke Ventilation Requirements

In multi-storey residential buildings, the main escape route is always via
common corridors and/or lobbies to protected stairs.
Smoke spread to the corridor from a fire in an apartment is unavoidable as the
occupants make their escape.
The 2006 version of ADB requires staircases and common corridors / lobbies
which adjoin a staircase to be ventilated.
The ventilation system allows the smoke in the corridor to be cleared and largely
prevents smoke from entering the staircase, assisting escape for occupants of
higher storeys should the whole building need to be evacuated.
Smoke Ventilation Requirements

ADB Requires:

•

All corridors/lobbies adjoining stairs to be ventilated by either natural or
mechanical means.

•

Stairs to be ventilated by a vent with a free area of 1.0m2 from the top storey
to outside.

Activation:

•

In a single stair building, the vents should be automatic via smoke detectors
in the common access space.

•

If a multi-stair building, the lobby ventilation can be manual, BUT the vent at
the top of the stair must be interlinked to open at the same time.
Smoke Ventilation Requirements
Smoke Control Requirements

Common Corridors can be ventilated:
•

Naturally – using AOV.

•

Naturally using shafts/chimneys.

•

Mechanically, using shafts.

•

Mechanically, using pressure differentials, in accordance with BS EN 121016: 2005.

All of these can be adapted to provide some means of day-to-day
environmental control - we’ll look at each in turn
Smoke Ventilation for Apartment Buildings: AOV Systems

Lobbies / corridors should be ventilated by an
AOV with a free area of at least 1.5m2

To achieve 1.5m2, a 1.5m wide vent opening to 30° needs to be at least 2.0m high and the
stroke of the motor will need to be around 1.2m
Smoke Ventilation for Apartment Buildings: AOV Systems
Smoke Control Requirements – Natural AOV

Note that some layouts, though ADB compliant, don’t ventilate all corridor sections
Day-to-day Ventilation for Apartment Buildings: AOV Systems
Environmental Control Requirements – Natural AOV

AOV can be used for day-to-day ventilation, but:
•Ventilation is single sided, has no separate inlet, has poor temperature control
•Potential for maglocks on cross corridor doors for through flow?
•Vents must close on fire, except for the fire floor
• Consider finger trapping
• Consider fall protection – up to 1.1m from floor level
• Control requirements
• Temperature Sensors (internal and external)
• Rain Sensor
Smoke Ventilation for Apartment Buildings: Natural Shaft Systems
Smoke Control Requirements – Natural Shafts

If a shaft system is used, the following criteria should be met:
• Be closed at the base
• Have a minimum cross-sectional area of 1.5m2 with a minimum dimension of
0.85m in either direction.
• Extend at least 0.5m above the highest structure within 2m
• Extend 2.5m above the ceiling of the highest level served by the shaft.
The vent into the shaft, the vent at the top of the shaft and any safety grilles in
the shaft should all have a minimum free area of 1.0m2.
Smoke Ventilation for Apartment Buildings: Natural Shaft Systems
Smoke Control Requirements – Natural Shafts

Construction:
The shaft should be constructed from non-combustible material and the vents
should be E30S rated.
The shaft should be vertical with no more than 4m at an inclined angle (max
30°)
Operation:
On detection of smoke in the corridor, the vent on the fire floor, at the top of the
shaft and the top of the stair should all open simultaneously – vents on all other
levels should remain closed.
Smoke Ventilation for Apartment Buildings: Natural Shaft Systems
Smoke Control Requirements – Natural Shafts
Smoke Ventilation for Apartment Buildings: Natural Shaft Systems
Smoke Control Requirements – Natural Shafts

Internal Damper to shaft, concealed by decorative grille, or Fire Door:
Day-to-day Ventilation for Apartment Buildings: Natural Shaft Systems
Environmental Control Requirements – Natural Shafts

Natural shafts can be used for environmental ventilation, but:
•There is no permanent air inlet unless specially provided
•Is lobby geometry and vent location suitable?
•Ventilation rate and temperature control is variable (with time and with floor)
•Risk of cross contamination between floors
•Vents must close on fire, except for the actual fire floor
•Motorised doors have issues with finger trapping and access to the shaft
•Control requirements
• Temperature Sensor (internal and external)
• Rain Sensor
Day-to-day Ventilation for Apartment Buildings: Natural Shaft Systems

+

Standard
roof vent

+

Fire dampers between
stair & corridor

Corridor
temperature
sensor

+
Ceiling grilles?
Weathered
roof vent +
rain sensor

OR AOV?
Smoke Ventilation for Apartment Buildings: Mechanical Shaft Systems
Smoke Control Requirements – Mechanical Shafts

Approved Document B permits the use of mechanical ventilation for smoke
control of common escape routes but gives no design guidance on how to
design such a system. The Smoke Control association guide provides much
of the missing guidance.

The main objective is to keep smoke from entering the staircase, unless the
system has been designed to trade off extended travel distances.
Smoke Ventilation for Apartment Buildings: Mechanical Shaft Systems

Typically:
• 0.6m2 shaft
• 0.8m2 damper
• Run and standby fan
• 1.0m2 stair vent
• Standby Generator
• Fire rated cabling
Smoke Ventilation for Apartment Buildings: Mechanical Shaft Systems
Smoke Control Requirements – Mechanical Shafts

Internal Damper to shaft, concealed by decorative grille, or bottom hinged flap:
Day-to-day Ventilation for Apartment Buildings: Mechanical Shaft Systems
Environmental Control Requirements – Natural Shafts

Mechanical shafts can be used for environmental ventilation, but:
•There is no permanent air inlet unless specially provided
•Is lobby geometry and vent location suitable?
•Vents must close on fire, except for the actual fire floor
•Flap vents have issues with finger trapping and access to the shaft
•Fan noise becomes an important issue
•Control requirements
• Temperature Sensor (internal and external)
• Rain Sensor
Day-to-day Ventilation for Apartment Buildings: Mechanical Shaft Systems
Corridor
Temperature
Sensor

Standard
roof vent

Variable Speed
Drive for
Extract/Supply
Fans

+

+

+
Ceiling Grilles

+

Fire Damper Between
Stair & Corridor

+
Noise Attenuation for
Smoke Extract Fans

Weathered
roof vent +
rain sensor

OR add a separate, quieter fan
Smoke Ventilation for Apartment Buildings: Extended Travel Distance
It has become common practice for architects to gain design flexibility by
extending dead end travel distances beyond 7.5/15m using improved
smoke ventilation as a compensating feature

Extended corridor systems generally require dedicated inlet and exhaust

7.5m
Smoke Ventilation for Apartment Buildings: Extended Travel Distance
Inlet via Staircase

Smoke Control Requirements – Mechanical Shafts

7.5m
Push-pull, often reversible

7.5m

7.5m
Smoke Ventilation for Apartment Buildings: Extended Travel Distance
Smoke Control Requirements – Mechanical Shafts

Internal Damper to shaft, concealed by decorative grille, or bottom hinged flap:
Day-to-day Ventilation for Apartment Buildings: Extended Travel Distance
Environmental Control Requirements – Mechanical Shafts

• Dedicated inlet air provision already exists and is usually well located
• Although if via part open stair door an alternative may be needed
• Vents must close on fire, except for the actual fire floor
• Flap vents have issues with finger trapping
• Fan noise becomes an important issue
• Control requirements
Temperature Sensor (internal and external)
Rain Sensor
Day-to-day Ventilation for Apartment Buildings: Extended Travel Distance
Smoke Control Requirements – Mechanical Shafts
Supply

Supply

Extract

Extract

D-t-d damper
above ceiling?
Smoke
damper
Day-to-day Ventilation for Apartment Buildings: Extended Travel Distance
Variable Speed
Drive for
Extract/Supply
Fans

Corridor
Temperature
Sensor

+
+

Noise Attenuation for Smoke
Extract Fans

+
Details that count - Fans
Environmental Control Requirements – Mechanical Shafts

Dual purpose smoke extract fans can be used, but:
• High tip clearance means low efficiency – high energy bills
• Smoke fans are generally noisy
• Future energy use restrictions from Europe may prohibit dual purpose
fans on the basis of efficiency limits.

Consider smaller secondary fans?
Details that count - Fans

Basic Smoke Control Installation

Dual purpose systems
Details that count – Rain defence
Environmental Control Requirements – Stair/Shaft Inlet

Dual purpose systems
should consider rain entry
Details that count – Air flow
Environmental Control Requirementscan be difficult
Balancing multiple floors – Mechanical Shafts

• Don’t expect CIBSE levels of accuracy
• Limit number of floors ventilated simultaneously?
• Rotate groups of floors to be ventilated?
•Inherent balance - ground level supply, roof level extract?

Does ceiling void need to be ventilated too?

Are separate day-to-day dampers a cost effective benefit?

Night cooling?
Details that count – Temperature control
Environmental Control Requirements – Mechanical Shafts

Manage expectations
• Don’t expect A/C levels of accuracy
• Systems will alleviate stuffiness and limit overheating
• Corridors are transit spaces and don’t need close control
(except in high value buildings with demanding residents)
Details that count – Temperature control
Enhance conditions with active cooling provided by the Colt Corridor
Coolstream Evaporative Cooling System
A ventilation system based
on supplying outside air
alone is able to achieve
temperatures in the corridor
typically 2-5oC above the
outside ambient.
With Coolstream we are
able to reduce supply
temperatures below outside
ambient, providing active
cooling in the corridors.
Colt Corridor Coolstream

32ºC

24ºC

Evaporative cooling and ventilation systems use the cooling power of water to
reduce the temperature, creating a more favourable environment in corridors.
Running and maintenance costs are extremely low and the warmer the outside
air, the more efficient evaporative cooling becomes.
Evaporative cooling
•Offers a reduction in energy costs of up to 90% compared to conventional air
conditioning
•Low cost of operation and maintenance
•Free from refrigerants, no F gas compliance
•Integrated water quality system, simple technology
•VDI 6022 certification for water hygiene
•Filtered air supply
•Decentralised, modular approach maximises reliability

Low Running
Costs

10 hours per day during
the summer months
= £350 per year
electricity costs for a
typical installation
Colt Corridor Coolstream
Main unit size

Size 10

Size 16

Final overall plant size dependant on project specific requirements
Design

Installation

Equipment/Controls

Commissioning

Maintenance

The End
1 sur 42

Recommandé

CPD Presentation: Smoke Ventilation using Shafts par
CPD Presentation: Smoke Ventilation using ShaftsCPD Presentation: Smoke Ventilation using Shafts
CPD Presentation: Smoke Ventilation using ShaftsColt UK
10.2K vues55 diapositives
CPD Presentation: Car Park Ventilation par
CPD Presentation: Car Park VentilationCPD Presentation: Car Park Ventilation
CPD Presentation: Car Park VentilationColt UK
6.4K vues49 diapositives
Smoke extraction in buildings par
Smoke extraction in buildingsSmoke extraction in buildings
Smoke extraction in buildingsvysakhmanohar
31.9K vues59 diapositives
CPD Presentation: General Principles of Smoke Control par
CPD Presentation: General Principles of Smoke ControlCPD Presentation: General Principles of Smoke Control
CPD Presentation: General Principles of Smoke ControlColt UK
4.3K vues62 diapositives
FIRE FIGHTING PRESENTATION par
FIRE FIGHTING PRESENTATIONFIRE FIGHTING PRESENTATION
FIRE FIGHTING PRESENTATIONASGHAR KHALIL
5K vues39 diapositives
Smoke Control in Buildings par
Smoke Control in BuildingsSmoke Control in Buildings
Smoke Control in BuildingsIllinois ASHRAE
2.2K vues16 diapositives

Contenu connexe

Tendances

Introduction To Mechanical Smoke Control CPD Presentation par
Introduction To Mechanical Smoke Control CPD PresentationIntroduction To Mechanical Smoke Control CPD Presentation
Introduction To Mechanical Smoke Control CPD PresentationAxair Fan (UK) Ltd.
1.5K vues74 diapositives
Smoke Control par
Smoke ControlSmoke Control
Smoke Controlrsmservicesinc
3.1K vues10 diapositives
FIRE DETECTION & ALARM SYSTEMS.pdf par
FIRE DETECTION & ALARM SYSTEMS.pdfFIRE DETECTION & ALARM SYSTEMS.pdf
FIRE DETECTION & ALARM SYSTEMS.pdfRiyaVerma238431
80 vues30 diapositives
Fire safety par
Fire safetyFire safety
Fire safetyPrachi Gupta
1.9K vues65 diapositives
FDA-Fire detection and alarm system par
FDA-Fire detection and alarm systemFDA-Fire detection and alarm system
FDA-Fire detection and alarm systemFathimaNasi
2.4K vues32 diapositives
Fire fighting systems par
Fire fighting systemsFire fighting systems
Fire fighting systemsMark Mikhaiel
2.9K vues50 diapositives

Tendances(20)

Introduction To Mechanical Smoke Control CPD Presentation par Axair Fan (UK) Ltd.
Introduction To Mechanical Smoke Control CPD PresentationIntroduction To Mechanical Smoke Control CPD Presentation
Introduction To Mechanical Smoke Control CPD Presentation
FDA-Fire detection and alarm system par FathimaNasi
FDA-Fire detection and alarm systemFDA-Fire detection and alarm system
FDA-Fire detection and alarm system
FathimaNasi2.4K vues
Fire Protection System - Automatic Fire Detectors par SSudhaVelan
Fire Protection System - Automatic Fire DetectorsFire Protection System - Automatic Fire Detectors
Fire Protection System - Automatic Fire Detectors
SSudhaVelan534 vues
Intro to basic fire alarm technology par Arman Nasar
Intro to basic fire alarm technologyIntro to basic fire alarm technology
Intro to basic fire alarm technology
Arman Nasar18.2K vues
Fire Detection and Alarm Systems par J.T.A.JONES
Fire Detection and Alarm SystemsFire Detection and Alarm Systems
Fire Detection and Alarm Systems
J.T.A.JONES75.8K vues
Fire alarm protection & alarm detection system par Manoj Temghare
Fire alarm protection & alarm detection systemFire alarm protection & alarm detection system
Fire alarm protection & alarm detection system
Manoj Temghare1.9K vues
Fire alarm system and common types of detectors par Muhammad Farid
Fire alarm system and common types of detectorsFire alarm system and common types of detectors
Fire alarm system and common types of detectors
Muhammad Farid13.1K vues
CPD Presentation: Smoke curtains and fire curtains par Colt UK
CPD Presentation: Smoke curtains and fire curtainsCPD Presentation: Smoke curtains and fire curtains
CPD Presentation: Smoke curtains and fire curtains
Colt UK10K vues
Fire alarm , detection and suppression system par Kamran Hassan
Fire alarm , detection and suppression systemFire alarm , detection and suppression system
Fire alarm , detection and suppression system
Kamran Hassan1.9K vues
Fire Safety and Building Materials par Sorab Mishra
Fire Safety and Building MaterialsFire Safety and Building Materials
Fire Safety and Building Materials
Sorab Mishra3.7K vues
Bs mechanical ventilation and air conditioning presentation slides par Pui Chun Shian
Bs mechanical ventilation and air conditioning presentation slidesBs mechanical ventilation and air conditioning presentation slides
Bs mechanical ventilation and air conditioning presentation slides
Pui Chun Shian1.2K vues

Similaire à CPD Presentation - Smoke control and environmental ventilation in residential common corridors

Presentation emb and industrial ventilation par
Presentation emb and industrial ventilationPresentation emb and industrial ventilation
Presentation emb and industrial ventilationjkborade
669 vues48 diapositives
Presentation industrial ventilation roda par
Presentation industrial ventilation rodaPresentation industrial ventilation roda
Presentation industrial ventilation rodaEeu SC
367 vues48 diapositives
Bs ii-presentation par
Bs ii-presentationBs ii-presentation
Bs ii-presentationLee Chun Yee
366 vues75 diapositives
Bs ii presentation finale par
Bs ii presentation finaleBs ii presentation finale
Bs ii presentation finaleTee Joanne
404 vues70 diapositives
150519 AS1668 Part 1 Presentation par
150519 AS1668 Part 1 Presentation150519 AS1668 Part 1 Presentation
150519 AS1668 Part 1 PresentationCIBSE NSW
4.2K vues28 diapositives
ashraeqatar_16.04.09_s_p_introduction_to_car_park_jetfan_ventilation_1.pdf par
ashraeqatar_16.04.09_s_p_introduction_to_car_park_jetfan_ventilation_1.pdfashraeqatar_16.04.09_s_p_introduction_to_car_park_jetfan_ventilation_1.pdf
ashraeqatar_16.04.09_s_p_introduction_to_car_park_jetfan_ventilation_1.pdfMarcGajudo
7 vues87 diapositives

Similaire à CPD Presentation - Smoke control and environmental ventilation in residential common corridors(20)

Presentation emb and industrial ventilation par jkborade
Presentation emb and industrial ventilationPresentation emb and industrial ventilation
Presentation emb and industrial ventilation
jkborade669 vues
Presentation industrial ventilation roda par Eeu SC
Presentation industrial ventilation rodaPresentation industrial ventilation roda
Presentation industrial ventilation roda
Eeu SC367 vues
Bs ii presentation finale par Tee Joanne
Bs ii presentation finaleBs ii presentation finale
Bs ii presentation finale
Tee Joanne404 vues
150519 AS1668 Part 1 Presentation par CIBSE NSW
150519 AS1668 Part 1 Presentation150519 AS1668 Part 1 Presentation
150519 AS1668 Part 1 Presentation
CIBSE NSW4.2K vues
ashraeqatar_16.04.09_s_p_introduction_to_car_park_jetfan_ventilation_1.pdf par MarcGajudo
ashraeqatar_16.04.09_s_p_introduction_to_car_park_jetfan_ventilation_1.pdfashraeqatar_16.04.09_s_p_introduction_to_car_park_jetfan_ventilation_1.pdf
ashraeqatar_16.04.09_s_p_introduction_to_car_park_jetfan_ventilation_1.pdf
MarcGajudo7 vues
Mark Harber - Design solutions to mitigate apartment overheating par IES / IAQM
Mark Harber - Design solutions to mitigate apartment overheatingMark Harber - Design solutions to mitigate apartment overheating
Mark Harber - Design solutions to mitigate apartment overheating
IES / IAQM124 vues
Natural smoke and_heat_exhaust_systems par jkborade
Natural smoke and_heat_exhaust_systemsNatural smoke and_heat_exhaust_systems
Natural smoke and_heat_exhaust_systems
jkborade387 vues
Natural Smoke And Heat Exhaust Systems par Maxpromotion
Natural Smoke And Heat Exhaust SystemsNatural Smoke And Heat Exhaust Systems
Natural Smoke And Heat Exhaust Systems
Maxpromotion1.2K vues
UNIT-V FIRE SAFETY INSTALLATION par karthi keyan
UNIT-V    FIRE SAFETY INSTALLATIONUNIT-V    FIRE SAFETY INSTALLATION
UNIT-V FIRE SAFETY INSTALLATION
karthi keyan91 vues
Sertus Smoke & Access brochure par Jessica Blake
Sertus Smoke & Access brochureSertus Smoke & Access brochure
Sertus Smoke & Access brochure
Jessica Blake221 vues

Plus de Colt UK

Smoke and environmental ventilation of multi-storey buildings using shafts we... par
Smoke and environmental ventilation of multi-storey buildings using shafts we...Smoke and environmental ventilation of multi-storey buildings using shafts we...
Smoke and environmental ventilation of multi-storey buildings using shafts we...Colt UK
390 vues4 diapositives
Seven good practices for pressurisation systems par
Seven good practices for pressurisation systemsSeven good practices for pressurisation systems
Seven good practices for pressurisation systemsColt UK
176 vues1 diapositive
Can car park ventilation schemes be more energy efficient? Yes – and they sho... par
Can car park ventilation schemes be more energy efficient? Yes – and they sho...Can car park ventilation schemes be more energy efficient? Yes – and they sho...
Can car park ventilation schemes be more energy efficient? Yes – and they sho...Colt UK
218 vues2 diapositives
Q&A from Dr John H Klotes webinar on design fires for smoke control par
Q&A from Dr John H Klotes webinar on design fires for smoke controlQ&A from Dr John H Klotes webinar on design fires for smoke control
Q&A from Dr John H Klotes webinar on design fires for smoke controlColt UK
617 vues4 diapositives
CPD Presentation Evaporative cooling in data centres par
CPD Presentation   Evaporative cooling in data centresCPD Presentation   Evaporative cooling in data centres
CPD Presentation Evaporative cooling in data centresColt UK
1.8K vues30 diapositives
The top three considerations when specifying glass louvred ventilators par
The top three considerations when specifying glass louvred ventilatorsThe top three considerations when specifying glass louvred ventilators
The top three considerations when specifying glass louvred ventilatorsColt UK
345 vues3 diapositives

Plus de Colt UK(20)

Smoke and environmental ventilation of multi-storey buildings using shafts we... par Colt UK
Smoke and environmental ventilation of multi-storey buildings using shafts we...Smoke and environmental ventilation of multi-storey buildings using shafts we...
Smoke and environmental ventilation of multi-storey buildings using shafts we...
Colt UK390 vues
Seven good practices for pressurisation systems par Colt UK
Seven good practices for pressurisation systemsSeven good practices for pressurisation systems
Seven good practices for pressurisation systems
Colt UK176 vues
Can car park ventilation schemes be more energy efficient? Yes – and they sho... par Colt UK
Can car park ventilation schemes be more energy efficient? Yes – and they sho...Can car park ventilation schemes be more energy efficient? Yes – and they sho...
Can car park ventilation schemes be more energy efficient? Yes – and they sho...
Colt UK218 vues
Q&A from Dr John H Klotes webinar on design fires for smoke control par Colt UK
Q&A from Dr John H Klotes webinar on design fires for smoke controlQ&A from Dr John H Klotes webinar on design fires for smoke control
Q&A from Dr John H Klotes webinar on design fires for smoke control
Colt UK617 vues
CPD Presentation Evaporative cooling in data centres par Colt UK
CPD Presentation   Evaporative cooling in data centresCPD Presentation   Evaporative cooling in data centres
CPD Presentation Evaporative cooling in data centres
Colt UK1.8K vues
The top three considerations when specifying glass louvred ventilators par Colt UK
The top three considerations when specifying glass louvred ventilatorsThe top three considerations when specifying glass louvred ventilators
The top three considerations when specifying glass louvred ventilators
Colt UK345 vues
CPD Presentation: Key considerations when specifying weather louvres par Colt UK
CPD Presentation: Key considerations when specifying weather louvresCPD Presentation: Key considerations when specifying weather louvres
CPD Presentation: Key considerations when specifying weather louvres
Colt UK4.9K vues
People feel better in colt conditions par Colt UK
People feel better in colt conditions People feel better in colt conditions
People feel better in colt conditions
Colt UK500 vues
You want to improve your factory’s productivity: what’s next? par Colt UK
You want to improve your factory’s productivity: what’s next?You want to improve your factory’s productivity: what’s next?
You want to improve your factory’s productivity: what’s next?
Colt UK140 vues
Can your factory be more productive? par Colt UK
Can your factory be more productive?Can your factory be more productive?
Can your factory be more productive?
Colt UK172 vues
Are you sure your natural ventilation system is really energy efficient? par Colt UK
Are you sure your natural ventilation system is really energy efficient?Are you sure your natural ventilation system is really energy efficient?
Are you sure your natural ventilation system is really energy efficient?
Colt UK141 vues
When is a U value real? par Colt UK
When is a U value real?When is a U value real?
When is a U value real?
Colt UK345 vues
Questions and answers from Paul Compton's pressurisation webinar par Colt UK
Questions and answers from Paul Compton's pressurisation webinar Questions and answers from Paul Compton's pressurisation webinar
Questions and answers from Paul Compton's pressurisation webinar
Colt UK212 vues
The Lakanal House inquest and Local Authority tower blocks par Colt UK
The Lakanal House inquest and Local Authority tower blocksThe Lakanal House inquest and Local Authority tower blocks
The Lakanal House inquest and Local Authority tower blocks
Colt UK243 vues
Not all “Class A” weather louvres are equal par Colt UK
Not all “Class A” weather louvres are equalNot all “Class A” weather louvres are equal
Not all “Class A” weather louvres are equal
Colt UK221 vues
Green micro-algae façade becomes reality in Hamburg par Colt UK
Green micro-algae façade becomes reality in HamburgGreen micro-algae façade becomes reality in Hamburg
Green micro-algae façade becomes reality in Hamburg
Colt UK567 vues
The CPR and mandatory CE marking: what is changing and what will it mean for you par Colt UK
The CPR and mandatory CE marking: what is changing and what will it mean for youThe CPR and mandatory CE marking: what is changing and what will it mean for you
The CPR and mandatory CE marking: what is changing and what will it mean for you
Colt UK172 vues
5 reasons why it’s wrong to use HVAC control systems for smoke ventilation par Colt UK
5 reasons why it’s wrong to use HVAC control systems for smoke ventilation5 reasons why it’s wrong to use HVAC control systems for smoke ventilation
5 reasons why it’s wrong to use HVAC control systems for smoke ventilation
Colt UK120 vues
How to boost your ventilation system’s cooling capacity par Colt UK
How to boost your ventilation system’s cooling capacityHow to boost your ventilation system’s cooling capacity
How to boost your ventilation system’s cooling capacity
Colt UK145 vues
Adding attenuation to a Natural Ventilation System retrospectively can be an ... par Colt UK
Adding attenuation to a Natural Ventilation System retrospectively can be an ...Adding attenuation to a Natural Ventilation System retrospectively can be an ...
Adding attenuation to a Natural Ventilation System retrospectively can be an ...
Colt UK135 vues

Dernier

Samsung Galaxy Watch 5 Presentation par
Samsung Galaxy Watch 5 PresentationSamsung Galaxy Watch 5 Presentation
Samsung Galaxy Watch 5 Presentationaryasheel1
13 vues1 diapositive
EL FODA.pdf par
EL FODA.pdfEL FODA.pdf
EL FODA.pdfestefanimilenca
23 vues1 diapositive
solutions to decrease cyberbullying.pptx par
solutions to decrease cyberbullying.pptxsolutions to decrease cyberbullying.pptx
solutions to decrease cyberbullying.pptxsalamaalmarzooqi2005
5 vues9 diapositives
Business X Design - People, Planet & Product par
Business X Design - People, Planet & ProductBusiness X Design - People, Planet & Product
Business X Design - People, Planet & ProductCyber-Duck
31 vues42 diapositives
type book PDF to PPT.pptx par
type book PDF to PPT.pptxtype book PDF to PPT.pptx
type book PDF to PPT.pptxsamboggiano
7 vues54 diapositives
DR Portfolio.pptx par
DR Portfolio.pptxDR Portfolio.pptx
DR Portfolio.pptxrobertsd2
26 vues11 diapositives

Dernier(20)

Samsung Galaxy Watch 5 Presentation par aryasheel1
Samsung Galaxy Watch 5 PresentationSamsung Galaxy Watch 5 Presentation
Samsung Galaxy Watch 5 Presentation
aryasheel113 vues
Business X Design - People, Planet & Product par Cyber-Duck
Business X Design - People, Planet & ProductBusiness X Design - People, Planet & Product
Business X Design - People, Planet & Product
Cyber-Duck31 vues
DR Portfolio.pptx par robertsd2
DR Portfolio.pptxDR Portfolio.pptx
DR Portfolio.pptx
robertsd226 vues
Using Experiential Design to Understand the Future of AI & Immersive Storytel... par Kent Bye
Using Experiential Design to Understand the Future of AI & Immersive Storytel...Using Experiential Design to Understand the Future of AI & Immersive Storytel...
Using Experiential Design to Understand the Future of AI & Immersive Storytel...
Kent Bye20 vues
ATPMOUSE_융합2조.pptx par kts120898
ATPMOUSE_융합2조.pptxATPMOUSE_융합2조.pptx
ATPMOUSE_융합2조.pptx
kts12089826 vues
tony moura bio.pdf par jenki442
tony moura bio.pdftony moura bio.pdf
tony moura bio.pdf
jenki4427 vues
Legal PPT Presentation.pptx par 125071063
Legal PPT Presentation.pptxLegal PPT Presentation.pptx
Legal PPT Presentation.pptx
1250710635 vues
Indian wedding dresses design.pdf par Aur Dikhao
Indian wedding dresses design.pdfIndian wedding dresses design.pdf
Indian wedding dresses design.pdf
Aur Dikhao5 vues

CPD Presentation - Smoke control and environmental ventilation in residential common corridors

  • 1. Smoke control and environmental ventilation in residential common corridors
  • 3. A Brief History  Private Company founded in 1931  I J O’Hea OBE (1897 - 1984)  Current Group Turnover £128 million  Manufacturing plants in the UK, Holland, Germany, Saudi Arabia, China and Singapore I J O’Hea. Colt Founder
  • 4. Current UK Business markets Business Segments  Smoke Control  Building Products – Louvres and Shading  Climate – Environmental Control and Ventilation  Service
  • 5. Contents Business Segments  Introduction  Ventilation systems, extra requirements, performance  Design details  Cooling
  • 6. The quest for energy efficiency (ADL and BREAAM) has led to very good sealing and insulation in residential buildings and an increase in district heating schemes. This has unintended consequences for stair lobbies, corridors and entrance halls, which tend to overheat, resulting in unpleasant conditions for residents and possible issues maintaining cold water supply temperatures. Caspian Wharf, a Berkley Homes development, uses a district heating system and therefore overheating in the common corridors was a concern for the design team.
  • 7. Q: What can you do to avoid heat building up in these common areas? A: Use the existing smoke control system for day-to-day ventilation. The simple solution is to use the ventilation equipment which is already providing smoke control to these areas. Natural or mechanical smoke ventilation systems may be adapted for day-today ventilation use.
  • 8. Q: Will you require additional equipment or modifications? A: Yes, but the amount varies If your building has a multiple shaft smoke control system, it can readily be configured to provide day-to-day ventilation with minimal additions. If the building has a single shaft system, you will need inlet air. You could provide it from the stair, using a weathered roof smoke vent. In this case, you will need fire rated smoke dampers between the stair and the corridor. You will need to consider fan noise, as noise levels considered acceptable for emergency use will not be acceptable for day-to-day ventilation use.
  • 9. Smoke Ventilation of Common Corridors in Residential Developments Legislation, Standards and Guidance • Approved Document B to the Building Regulations (ADB) • BS 9991 • BS EN 12101 / BS 8519 • Smoke Control Association Guide (free download from www.feta.co.uk)
  • 10. Smoke Ventilation Requirements In multi-storey residential buildings, the main escape route is always via common corridors and/or lobbies to protected stairs. Smoke spread to the corridor from a fire in an apartment is unavoidable as the occupants make their escape. The 2006 version of ADB requires staircases and common corridors / lobbies which adjoin a staircase to be ventilated. The ventilation system allows the smoke in the corridor to be cleared and largely prevents smoke from entering the staircase, assisting escape for occupants of higher storeys should the whole building need to be evacuated.
  • 11. Smoke Ventilation Requirements ADB Requires: • All corridors/lobbies adjoining stairs to be ventilated by either natural or mechanical means. • Stairs to be ventilated by a vent with a free area of 1.0m2 from the top storey to outside. Activation: • In a single stair building, the vents should be automatic via smoke detectors in the common access space. • If a multi-stair building, the lobby ventilation can be manual, BUT the vent at the top of the stair must be interlinked to open at the same time.
  • 12. Smoke Ventilation Requirements Smoke Control Requirements Common Corridors can be ventilated: • Naturally – using AOV. • Naturally using shafts/chimneys. • Mechanically, using shafts. • Mechanically, using pressure differentials, in accordance with BS EN 121016: 2005. All of these can be adapted to provide some means of day-to-day environmental control - we’ll look at each in turn
  • 13. Smoke Ventilation for Apartment Buildings: AOV Systems Lobbies / corridors should be ventilated by an AOV with a free area of at least 1.5m2 To achieve 1.5m2, a 1.5m wide vent opening to 30° needs to be at least 2.0m high and the stroke of the motor will need to be around 1.2m
  • 14. Smoke Ventilation for Apartment Buildings: AOV Systems Smoke Control Requirements – Natural AOV Note that some layouts, though ADB compliant, don’t ventilate all corridor sections
  • 15. Day-to-day Ventilation for Apartment Buildings: AOV Systems Environmental Control Requirements – Natural AOV AOV can be used for day-to-day ventilation, but: •Ventilation is single sided, has no separate inlet, has poor temperature control •Potential for maglocks on cross corridor doors for through flow? •Vents must close on fire, except for the fire floor • Consider finger trapping • Consider fall protection – up to 1.1m from floor level • Control requirements • Temperature Sensors (internal and external) • Rain Sensor
  • 16. Smoke Ventilation for Apartment Buildings: Natural Shaft Systems Smoke Control Requirements – Natural Shafts If a shaft system is used, the following criteria should be met: • Be closed at the base • Have a minimum cross-sectional area of 1.5m2 with a minimum dimension of 0.85m in either direction. • Extend at least 0.5m above the highest structure within 2m • Extend 2.5m above the ceiling of the highest level served by the shaft. The vent into the shaft, the vent at the top of the shaft and any safety grilles in the shaft should all have a minimum free area of 1.0m2.
  • 17. Smoke Ventilation for Apartment Buildings: Natural Shaft Systems Smoke Control Requirements – Natural Shafts Construction: The shaft should be constructed from non-combustible material and the vents should be E30S rated. The shaft should be vertical with no more than 4m at an inclined angle (max 30°) Operation: On detection of smoke in the corridor, the vent on the fire floor, at the top of the shaft and the top of the stair should all open simultaneously – vents on all other levels should remain closed.
  • 18. Smoke Ventilation for Apartment Buildings: Natural Shaft Systems Smoke Control Requirements – Natural Shafts
  • 19. Smoke Ventilation for Apartment Buildings: Natural Shaft Systems Smoke Control Requirements – Natural Shafts Internal Damper to shaft, concealed by decorative grille, or Fire Door:
  • 20. Day-to-day Ventilation for Apartment Buildings: Natural Shaft Systems Environmental Control Requirements – Natural Shafts Natural shafts can be used for environmental ventilation, but: •There is no permanent air inlet unless specially provided •Is lobby geometry and vent location suitable? •Ventilation rate and temperature control is variable (with time and with floor) •Risk of cross contamination between floors •Vents must close on fire, except for the actual fire floor •Motorised doors have issues with finger trapping and access to the shaft •Control requirements • Temperature Sensor (internal and external) • Rain Sensor
  • 21. Day-to-day Ventilation for Apartment Buildings: Natural Shaft Systems + Standard roof vent + Fire dampers between stair & corridor Corridor temperature sensor + Ceiling grilles? Weathered roof vent + rain sensor OR AOV?
  • 22. Smoke Ventilation for Apartment Buildings: Mechanical Shaft Systems Smoke Control Requirements – Mechanical Shafts Approved Document B permits the use of mechanical ventilation for smoke control of common escape routes but gives no design guidance on how to design such a system. The Smoke Control association guide provides much of the missing guidance. The main objective is to keep smoke from entering the staircase, unless the system has been designed to trade off extended travel distances.
  • 23. Smoke Ventilation for Apartment Buildings: Mechanical Shaft Systems Typically: • 0.6m2 shaft • 0.8m2 damper • Run and standby fan • 1.0m2 stair vent • Standby Generator • Fire rated cabling
  • 24. Smoke Ventilation for Apartment Buildings: Mechanical Shaft Systems Smoke Control Requirements – Mechanical Shafts Internal Damper to shaft, concealed by decorative grille, or bottom hinged flap:
  • 25. Day-to-day Ventilation for Apartment Buildings: Mechanical Shaft Systems Environmental Control Requirements – Natural Shafts Mechanical shafts can be used for environmental ventilation, but: •There is no permanent air inlet unless specially provided •Is lobby geometry and vent location suitable? •Vents must close on fire, except for the actual fire floor •Flap vents have issues with finger trapping and access to the shaft •Fan noise becomes an important issue •Control requirements • Temperature Sensor (internal and external) • Rain Sensor
  • 26. Day-to-day Ventilation for Apartment Buildings: Mechanical Shaft Systems Corridor Temperature Sensor Standard roof vent Variable Speed Drive for Extract/Supply Fans + + + Ceiling Grilles + Fire Damper Between Stair & Corridor + Noise Attenuation for Smoke Extract Fans Weathered roof vent + rain sensor OR add a separate, quieter fan
  • 27. Smoke Ventilation for Apartment Buildings: Extended Travel Distance It has become common practice for architects to gain design flexibility by extending dead end travel distances beyond 7.5/15m using improved smoke ventilation as a compensating feature Extended corridor systems generally require dedicated inlet and exhaust 7.5m
  • 28. Smoke Ventilation for Apartment Buildings: Extended Travel Distance Inlet via Staircase Smoke Control Requirements – Mechanical Shafts 7.5m Push-pull, often reversible 7.5m 7.5m
  • 29. Smoke Ventilation for Apartment Buildings: Extended Travel Distance Smoke Control Requirements – Mechanical Shafts Internal Damper to shaft, concealed by decorative grille, or bottom hinged flap:
  • 30. Day-to-day Ventilation for Apartment Buildings: Extended Travel Distance Environmental Control Requirements – Mechanical Shafts • Dedicated inlet air provision already exists and is usually well located • Although if via part open stair door an alternative may be needed • Vents must close on fire, except for the actual fire floor • Flap vents have issues with finger trapping • Fan noise becomes an important issue • Control requirements Temperature Sensor (internal and external) Rain Sensor
  • 31. Day-to-day Ventilation for Apartment Buildings: Extended Travel Distance Smoke Control Requirements – Mechanical Shafts Supply Supply Extract Extract D-t-d damper above ceiling? Smoke damper
  • 32. Day-to-day Ventilation for Apartment Buildings: Extended Travel Distance Variable Speed Drive for Extract/Supply Fans Corridor Temperature Sensor + + Noise Attenuation for Smoke Extract Fans +
  • 33. Details that count - Fans Environmental Control Requirements – Mechanical Shafts Dual purpose smoke extract fans can be used, but: • High tip clearance means low efficiency – high energy bills • Smoke fans are generally noisy • Future energy use restrictions from Europe may prohibit dual purpose fans on the basis of efficiency limits. Consider smaller secondary fans?
  • 34. Details that count - Fans Basic Smoke Control Installation Dual purpose systems
  • 35. Details that count – Rain defence Environmental Control Requirements – Stair/Shaft Inlet Dual purpose systems should consider rain entry
  • 36. Details that count – Air flow Environmental Control Requirementscan be difficult Balancing multiple floors – Mechanical Shafts • Don’t expect CIBSE levels of accuracy • Limit number of floors ventilated simultaneously? • Rotate groups of floors to be ventilated? •Inherent balance - ground level supply, roof level extract? Does ceiling void need to be ventilated too? Are separate day-to-day dampers a cost effective benefit? Night cooling?
  • 37. Details that count – Temperature control Environmental Control Requirements – Mechanical Shafts Manage expectations • Don’t expect A/C levels of accuracy • Systems will alleviate stuffiness and limit overheating • Corridors are transit spaces and don’t need close control (except in high value buildings with demanding residents)
  • 38. Details that count – Temperature control Enhance conditions with active cooling provided by the Colt Corridor Coolstream Evaporative Cooling System A ventilation system based on supplying outside air alone is able to achieve temperatures in the corridor typically 2-5oC above the outside ambient. With Coolstream we are able to reduce supply temperatures below outside ambient, providing active cooling in the corridors.
  • 39. Colt Corridor Coolstream 32ºC 24ºC Evaporative cooling and ventilation systems use the cooling power of water to reduce the temperature, creating a more favourable environment in corridors. Running and maintenance costs are extremely low and the warmer the outside air, the more efficient evaporative cooling becomes.
  • 40. Evaporative cooling •Offers a reduction in energy costs of up to 90% compared to conventional air conditioning •Low cost of operation and maintenance •Free from refrigerants, no F gas compliance •Integrated water quality system, simple technology •VDI 6022 certification for water hygiene •Filtered air supply •Decentralised, modular approach maximises reliability Low Running Costs 10 hours per day during the summer months = £350 per year electricity costs for a typical installation
  • 41. Colt Corridor Coolstream Main unit size Size 10 Size 16 Final overall plant size dependant on project specific requirements

Notes de l'éditeur

  1. By investing in innovation, products, services and people, Colt International has established itself as an international leader in the fields of: Smoke Control Solar Shading Natural Ventilation Louvre Environmental Climate Control (HVAC) Air Handling Systems
  2. In December 2006, the latest version of Approved Document B was issued which changes the requirements for common corridors in apartment buildings.
  3. There are a number of options for ventilating the corridors